DUCT TYPE AIR CONDITIONER
OPERATION MANUAL AND INSTALLATION MANUAL
Please read this manual carefully before installation.
Keep this operation manual for future reference.
No.0150509256 C
DUCT TYPE AIR CONDITIONER
OPERATION MANUAL AND INSTALLATION MANUAL
Contents
AD48HS1ERA
AD60HSIERA
Cautions
Safety Precautions
Parts and Functions
Operation
Installation Manual For Wire Controller
Heating Mode
Care and Maintenance
Troubleshooting
Precaution for Installation
Is The Unit Installed Correctly
Installation Procedure
13
14
15
16
19
20
21
3
4
6
9
English
Please read this manual carefully before installation.
Keep this operation manual for future reference.
Cautions
Disposal of the old air conditioner
Before disposing an old air conditioner that goes out of use, please make sure it's inoperative and safe. Unplug the air conditioner
in order to avoid the risk of child entrapment.
It must be noticed that air conditioner system contains refrigerants, which require specialized waste disposal. The valuable
materials contained in a air conditioner can be recycled. Contact your local waste disposal center for proper disposal of an old
air conditioner and contact your local authority or your dealer if you have any question. Please ensure that the pipework of your
air conditioner does not get damaged prior to being picked up by the relevant waste disposal center, and contribute to environmental
awareness by insisting on an appropriate, anti-pollution method of disposal.
Disposal of the packaging of your new air conditioner
All the packaging materials employed in the package of your new air conditioner may be disposed without any danger to the
environment.
The cardboard box may be broken or cut into smaller pieces and given to a waste paper disposal service. The wrapping bag
made of polyethylene and the polyethylene foam pads contain no fluorochloric hydrocarbon.
All these valuable materials may be taken to a waste collecting center and used again after adequate recycling.
Consult your local authorities for the name and address of the waste materials collecting centers and waste paper disposal
services nearest to your house.
Safety Instructions and Warnings
Before starting the air conditioner, read the information given in the User's Guide carefully. The User's Guide contains very
important observations relating to the assembly, operation and maintenance of the air conditioner.
The manufacturer does not accept responsibility for any damages that may arise due to non-observation of the following
instruction.
Damaged air conditioners are not to be put into operation. In case of doubt, consult your supplier.
Use of the air conditioner is to be carried out in strict compliance with the relative instructions set forth in the User's Guide.
Installation shall be done by professional people, don't install unit by yourself.
For the purpose of safety, the air conditioner must be properly grounded in accordance with specifications.
Always remember to unplug the air conditioner before opening inlet grill. Never unplug your air conditioner by pulling on
the power cord. Always grip plug firmly and pull straight out from the outlet.
All electrical repairs must be carried out by qualified electricians. Inadequate repairs may result in a major source of
danger for the user of the air conditoiner.
Do not damage any parts of the air conditioner that carry refrigerant by piercing or perforating the air conditioner's tubes
with sharp or pointed items, crushing or twisting any tubes, or scraping the coatings off the surfaces. If the refrigerant
spurts out and gets into eyes, it may result in serious eye injuries.
Do not obstruct or cover the ventilation grille of the air conditioner. Do not put fingers or any other things into the inlet/outlet
and swing louver.
Do not allow children to play with the air conditioner. In no case should children be allowed to sit on the outdoor unit.
This appliance is not intended for use by persons (including children) with reducedphysical, sensory or mental capabilities, or
lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by
a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.
3
Safety Precautions
Before starting to use the system, read carefully this "SAFETY PRECAUTIONS" to ensure a proper operation of the system.
Safety precautions described here are classified to " WARNING" and " CAUTION". Precautions which are shown
in the column of " WANING" means that an improper handing could lead to a grave result like a death, serious injury,
etc. However, even if precautions are shown in the column of " CAUTION", a very serious problem could occur depending
on situation. Make sure to observe these safety precautions faithfully because they are very important information to ensure
the safety.
Symbols which appear frequently in the text have following meanings.
Strictly prohibited.
Observe instructions faithfully.
Provide a positive grounding.
When you have read through the manual, keep it always at hand for read consultation. If the operator is replaced, make
sure to hand over this manual to the new operator.
CAUTIONS FOR INSTALLATION
WARNING
The system should be applied to places as office,
restaurant, residence and the like.
Application to inferior environment such as an
engineering shop, could cause equipment
malfunction and serious injury or death.
Do not install nearby the place where may have
leakage of flammable gas.
If the gas leakes and gathers around, it may cause
the fire.
Where strong winds may prevail, the system
should be fixed securely to prevent a collapse.
The system should be installed by your dealer or
a professional installer.
Installation by yourself is not encouraged because
it could cause such problems as water leakage,
electrical shock or fire accident by some improper
handing.
CAUTION
Depending on the place of installation, a circuit
breaker may be necessary.
ON
OFF
Unless the circuit breaker is installed, it could cause
elecrical shocks.
Install on the place where can endure the weight
of air conditioner.
When you need some optional devices such as a
humidifier, electric heater, etc., be sure to use the products
which are recommended by us. These devices should
be attached by a professional installer.
Installation by yourself is not encouraged because it could
cause such problems as water leakage, electrical shock
or fire accident by some improper handing.
Drain pipe should be arranged to provide a positive
draining.
If the pipe is arranged improperly, furniture or the
likes may be damaged by leaked water.
Make sure the system is grounded.
Bodily injury could result by a collapse.Bodily injury could result by a careless installation.Grounding cable should never be connected to
a gas pipe, city water pipe, lightning conductor
rod or grounding cable of telephone. If the
grounding cable is not set properly, it could cause
electric shocks.
CAUTIONS FOR TRANSFER OR REPAIR
WARNING
Modification of the system is strictly prohibited. When the system needs a
repair, consult your dealer.
Improper practice of repair could cause water leakage, electric shock or
fire.
When the air conditioner is relocated, contact your dealer or a professional
installer.
Improper practice of installation could cause water leakage, electric shock
or fire.
4
Safety Precautions
CAUTIONS FOR OPERATION
You should refrain from exposing your body directly
to cool wind for a long time.
It could affect your physical condition or cause
some health problems.
The system should never be used for any other
purposes than intended such as for preservation
of food, flora and fauna, precision devices or work
of art.
WARNING
Do not poke the air inlet or outlet with a bar, etc.When any abnormal condition (scorching smell or
Since the internal fan is operating with a high
speed, it could cause an injury.
CAUTION
Do not handle switches with a wet hand.Combustion apparatus should not be placed
others) is found, stop the operation immediately
and turn off the power switch. Then consult your
dealer.
If you continue the operation without removing the
cause, it could result in a trouble, electric shock
or fire.
allowing a direct exposure to wind of air conditioner.
problems.
Do not wash the air conditioner with water.
It could cause electric shocks.It will not be good for their health.Use of steel or copper wire in place of a fuse is
Neither stand on the air conditioner nor
place something on it.
object.
Do not use the power switch to turn on or off the
system.
It could cause a fire or water leakage.There is a risk of injury.If the system is operated at the vicinity of such
When operating the system simultaneously with
a combustion apparatus, indoor air must be
ventilated frequently.
ON
OFF
It could cause electric shocks.It could cause deterioration of food or other
Do not install the system where the air outlet
reaches directly the flora and fauna.
It is strictly prohibited to place a container of
combustible gas or liquid near the air conditioner
or to spray it directly with the gas or liquid.
Do not touch the air outlet section while the swing
louver is operating.
Check occasionally the support structure of the
unit for any damage after a use of long period of
time.
Incomplete combustion could occur on the
apparatus.
Make sure to use a fuse of proper electric rating.
strictly prohibited because it could result in a trouble
or fire accident.
Do not operate the system while the air outlet grill
is removed.
There is a risk of injury.It could cause a fire accident.There are risks of falling or injury by collapsed
Do not use such equipment as a water heater, etc.
around the indoor unit or the wire controller.
equipment which generates steam, condensed
water may drip during cooling operation or it could
cause a fault current or short-circuit.
When cleaning the system, stop the operation and
turn off the power switch.
Insufficient ventilation could cause an oxygen
deficiency accident.
Do not put water containers on the unit such as a flower vase, etc.
If the water enters into the unit and damages the electric insulation material, it may cause electric shock.
If the structure is not repaired immediately, the
unit could topple down to cause a personal injury.
Cleaning should never be done while the internal
fans are running with high speed.
5
Safety Precautions
The machine is adaptive in following situation
1. Applicable ambient temperature range:
Cooling
Heating
Indoor temperature
Outdoor temperature
Indoor temperature
Outdoor temperature
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
max. DB/WB
min. DB/WB
32/23 C
18/14 C
46/26 C
10/6 C
27 C
15 C
24/18 C
2. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.
3. If the fuse on PC board is broken, please change it with the type of T 3.15A /250VAC.
4. The wiring method should be in line with the local wiring standard.
5. The power cable and connecting cable are self-provided.
The connecting cable should be H05RN-F 4G 0.75mm
2
.
All the cables shall have got the European authentication certificate. During installation, when the connecting cables
break off, it must be assured that the grouding wire is the last one to be broken off.
6. The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no
less than 3mm.
7. The indoor unit installation height is at least 2.5m.
8. In order to obtain the Unit's best performances, the fan speed is recommended according to the following conditions.
outdoor ambient temp.
> 40 C
operation mode
cooling
recommended fan speed
low
< 20 C
< -5 C
> 18 C
cooling
heating
heating
Parts and Functions
Indoor Unit
Duct
Air inlet
high
low
high
Air outlet
Duct
Drain pipe
6
Parts and Functions
Buttons of the wire controller
Mode switch
Choose running mode
Health switch
Used to control oxygen
function and negative ion
MODE
AUTO
FAN ONLY
COOL
DRY
HEAT
TES
HEALTH
UNIT NO.
CEN. ADD.
SYS. ADD.
CLOCK UP DOWN
TIMER
ON
OFF
DAILY
FAN
AUTO
HIGH
MED
LOW
FIX
CHECK
DEMAND
OPERATION
ROOM TEMP.
C
SET TEMP.
F
VENTILATION
RECOVERY
CENTRAL
STANDBY
PRE-HEAT
DEFROST
FILTER
SWING
MANUAL
AUTO
NORMAL
MODEFANSWING
HEALTH
CLOCK
TIMER
CHECKFILTER
ON/OFF
TEMP
TIME
SETRECOVERY
RESET
Fan speed switch
Change wind speed
Swing switch
Open and close air flap
TEMP switch
Used for changing set
temperature
Time switch
It is used to regulate setting time.
Clock, timing and address setting
Air change switch
It is used to open and close air
change function. The mode is as
follows:
No display-air change (automatic)air change (RECOVERY)-air
change (NORMAL)
Timing switch
It is used for choosing
timing running
Self-inspection
switch
It is used for inspection
service
Filter reset
After cleaning air inlet
and filter, press
this switch. The unit
begins to run
ON/OFF switch
Do on and off function. The unit is
on when pressing it; and is off
when pressing it again (needn't to
open front cover)
Reset key
When in abnormal state, push the
reset key with a spike, which may
return the unit to normal
7
Parts and Functions
Display of the wire controller
Air volume display
Display the setting speed
Running mode display
Show the selected mode
FAN ONLY
Health function display
Unit number display
Temperature
display
Display the room
temperature, setting
temperature, and
unit number
Timing operation
display
Show timing operation
content
UNIT NO.
CEN. ADD.
SYS. ADD.
TIMER
OFF
DAILY
MODE
AUTO
COOL
DRY
HEAT
TES
HEALTH
CLOCK UP DOWN
ON
FAN
AUTO
HIGH
MED
LOW
FIX
CHECK
DEMAND
C
F
CENTRAL
OPERATION
STANDBY
PRE-HEAT
DEFROST
FILTER
SWING
MANUAL
ROOM TEMP.
SET TEMP.
VENTILATION
AUTO
RECOVERY
NORMAL
MODEFANSWING
HEALTH
CLOCK
TIMER
CHECKFILTER
ON/OFF
TEMP
TIME
SETRECOVERY
RESET
Centralized display
When controlled by
centralized controller, this
information is shown.
Running display
When the compressor
runs, it displays.
Standby display
When the unit is on
power and in
standby mode,"standby"
is shown.
When in preheating
status, "preheating" is
shown.
After heating, "defrost"
is shown when
defrosting.
Filter screen warning
sign
When the sign is
shown, please clean
the filter screen
Air change display
Inspection status display
Demand display
When forced to run,"DEMAND"
will be displayed.
Remarks
The models in the manual don't have health, filter reset and Air change function.
8
Wind swing display
Operation
ON/OFF operation
CLOCK
FAN
HIGH
OPERATION
ROOM TEMP.
C
MODE
COOL
MODEFANSWING
HEALTH
CLOCK
TIMER
CHECKFILTER
ON/OFF
TEMP
TIME
SETRECOVERY
RESET
Press ON/OFF switch on line controller directly
2
The line controller displays the running state in the latest
4
time (timing and swing state may not be displayed).
1. Press "ON/OFF" switch.
5
The air conditioner starts operating, and the light on the
wired controller is on.
3
2.Choose operation mode.
Press "mode"switch to change to
"AUTO"---"FAN ONLY"---"COOL"---"DRY"---"HEAT".
3.Press "TEMP" switch
Change set temperature:press" TEMP " or "TEMP "
every time, [SET] will display,and set temperature will
increase/reduce
1
4.Press "FAN SPEED" switch
FAN ONLY Operation:
6
Press "FAN SPEED" switch to change to
"HIGH"--"MED"--"LOW"--"HIGH"
In AUTO,COOL,DRY,HEAT Operation:
Press "FAN SPEED" switch to change to
"AUTO"--"HIGH"--"MED"--"LOW"--"AUTO"
5.Press "swing" switch on the line controller to
swing the wind screen.
6.Press "ON/OFF"switch, off.
The light on the line controller is off.
Note
Several seconds after the operation of the line controller,
the setting of the unit will change.
Remarks
Avoid pressing "ON/OFF" switch frequently.
Do not press line controller or switches by sharp objects.
The temperature is on the basis of the setting value. The wind temperature may not reach the setting value because of
the outer air conditioner and system protection.
When the wired controller is power on, the screen fully displays it for two seconds. and clock zone "8888"-"888"-"88""8" flicker for 30 seconds. All the switches are invalid at the time.
9
Operation
Present time setting
The timing is based on the real time. Thus, the real time should be regulated in advance.
The clock regulation steps are as follows:
1.Press "CLOCK" switch
"CLOCK" flickers, and the time displayed is the real time.
2.Press " " and " " to regulate the time.
MODE
FAN
HIGH
OPERATION
MODEFANSWING
HEALTH
TEMP
HEAT
TIME
SETRECOVERY
RESET
CLOCK UP
ROOM TEMP.
C
CLOCK
TIMER
CHECKFILTER
ON/OFF
123
Setting of power failure compensation function
The time increases a minute each time you press " " switch.
The time decreases a minute each time you press " " switch.
3.Press "setting" switch. The setting is achieved.
Notes
If not in timing, the screen displays the real time.
If in timing, the screen displays the timing time.
If you want to know the real time, go to the first step.
When SW1-6 on PCB of wire controller is OFF, it will be in power failure compensation. If the SW1-6 is ON, it has no
compensation function.
When the power is on after blackout, the unit will return to the former state if compensation function is set. Otherwise, it
will stop. When restarting the unit, press "ON/OFF" switch on wired controller.
10
Operation
Timing setting
OFF timing: when a set time has elapsed, the unit stops running.
ON timing: when a set time has elapsed, the unit starts.
MODEFANSWING
MODE
COOL
TIMER
ON
FAN
HIGH
ROOM TEMP.
C
OPERATION
HEALTH
CLOCK
TIMER
CHECKFILTER
ON/OFF
SETRECOVERY
123
TEMP
TIME
RESET
1.Press "TIME" switch.
The display changes with the following sequence:
2.Set up "TIMER"
When timing ON or timing OFF flickers, press " " or " " to
regulate the time
Press" "or " "set up ON/OFF time.
The setting time increases ten minutes each time you press " "
switch.
The setting time decreases ten minutes each time you press " "
switch.
When setting timing ON and timing OFF at the same time,
press "timing" switch to change the setting item.
3.Time setting is achieved. Press"setting"switch.
ON
OFF
on
OFF
Press "ON/OFF" switch firstly,
and set up operation mode.
Please regulate the clock in
advance before using the
timing function.
on
OFF
CYCLE
no display
Cancel timing
If you want to change the timing mode to normal operation,
press "timing" until there is no timing display. When the
timing is invalid, the mode is in normal operation.
parts of wired controller explanation :
1.The unit starts or stops at the setting time. Meanwhile, it displays the timing time.
2."ON Timing, OFF timing and circulation"means that the unit is on and off at the setting time everyday.
Notes
The shorter setting time will be carried out firstly.
If the ON timing and OFF timing are the same, the setting is invalid.
Even in timing condition, you may start or close the unit through pressing "ON/OFF" switch.
11
Operation
Query indoor malfunction history:
In the state of power on or power off, press [CHECK] button, enter the malfunction-querying mode of all indoor units in
the group. Then [CHECK] and [UNIT NO.] will display, and the actual indoor numbers will be displayed in some sequence
(unit number is in decimals). At the same time, in the time region, there will be the current malfunction and the latest time
malfunction, the displaying format is [XX:YY], in which XX stands for the current malfunction, if normal, it will display "--";
YY stands for the latest time malfunction. The failure code of every unit will display for 3 seconds. After the failure codes
of all indoor units in the whole group are displayed, the mode will quit automatically.
How to change the function switches?
No.TypeState of switchFunction description
SW1-1
SW1-2
SW1-3
SW1-4
SW1-5
SW1-6
Select the master or
the slave controller
Select the controller
mode
Room temperature
display option
o
26
lock
Temperature sensor
position option
Auto restart
Factory SetingONdefault settingSW1-7
ONset as the slave controller
OFFset as the master controller
ON
OFF
ON
OFF
ON
OFF
ON
OFF
standard controller
air handler controller
visible room temperature
invisible room temperature
o
lock
o
lock
Unavailable 26
available 26
Sensor of the controller
Sensor in the unit
ONunavailable
OFF
available
Factory SettingOFFdefault settingSW1-8
Notes
1. Switches or jumper wire must be adjusted when the wire controller is powered off. If the wire controller is
powered on, the above operations will be invalid.
2. Function difference between master wire controller and slave one:
Contrastive
items
Master wire
controller
FunctionAll of functions
Slave wire controller
Only with below functions: ON/OFF, MODE, FAN
SPEED, SET TEMP., SWING
12
Installation Manual For Wire Controller
1. Take down wire controller from the holder
2. Install the controller holder
According to the position of 2 screw holes on the
FAN ONLY
CEN. ADD.
SYS. ADD.
TIMER
DAILY
HEALTH
UNIT NO.
ON
OFF
MODE
AUTO
COOL
DRY
HEAT
TES
FAN
AUTO
HIGH
MED
LOW
FIX
CHECK
DEMAND
CLOCKUP DOWN
C
F
CENTRAL
OPERATION
STANDBY
PRE-HEAT
DEFROST
SWING
MANUAL
ROOM TEMP.
SET TEMP.
VENTILATION
RECOVERY
NORMAL
FILTER
AUTO
MODE FAN SWING
TEMP
HEALTH
TIME
CLOCK
SET RECOVERY
TIMER
CHECK FILTER
RESET
Wire controller
52¡ 0.2
Bracket
10.45
holder, drill 2 holes on the wall, and strike the wood
stopper to the holes respectively.
Then align the 2 screw holes of wired controller
holder to the wood stopper, fix the holder on the wall
5.3
with wood screw.
Note:Try a wall as flat as possible for installation.
ON/OFF
Screw holes
Don't use excessive force to tighten screws,
otherwise, the holder will be damaged.
3.Wiring instruction
Use shielded wire between indoor and wire controller.And be earthed on one side, or the unit will not work normally
because of interference.
Note:Confirm the terminal connection firmly, and do not get in tough with shielded wire.
4.Place wire controller on the holder, and pay attention not to pressing any wires.
There are three methods to connection wire controller and the indoor units:
A.One wired controller can control max. up to 16 sets of indoor units, and 3 pieces of polar wire must connect the wire
controller and the master unit (the indoor unit connected with wire controller directly), the others connect with the master
unit through 2 pieces of polar wire.
B. One wire controller controls one indoor unit, and the indoor unit connects with the wire controller through 3 pieces of
polar wire.
C. Two wired controllers control one indoor unit. The wire controller connected with indoor unit is called master one, the
other is called slave one. Master wire controller and indoor unit; master and slave wire controllers are all connected
through 3 pieces of polar wire.
6. Communication wiring:
The wire controller is equipped with special communication wiring in the accessories. 3-core terminal (1-white 2-yellow
3-red) is connected with the terminal A, B, C of wire controller respectively.
The communication wiring is 5 meter long; if the actual length is more than it, please distribute wiring according to below
table:
Communication wiring length(m) Dimensions of wiring
< 100 0.3mm2x3-core shielded wire
100 and <200 0.5mm2x3-core shielded wire
200 and <300 0.75mm2x3-core shielded wire
2
300 and <400 1.25mm
400 and <600 2mm
x3-core shielded wire
2
x3-core shielded wire
*One side of the shielded sheet of communication wire must be earthed.
13
Heating Mode
"HOT KEEP" function
"HOT KEEP"is operated in the following cases.
When heating is started:
In order to prevent blowing out of cool wind, the indoor unit fan stopped according to the room temperature which heating
operation is started. Wait for approx. 2 to 3 minute, and the operation will be automatically changed to the ordinary heating
mode.
Defrosting operation (in the heating mode):
When it is liable to frost, the heating operation is stopped automatically for 5 to 12 minutes once per approx. one hour,
and defrosting is operated. After defrosting is completed, operation mode is automatically changed to ordinary heating
operation.
When the room thermostat is actuated:
When room temperature increases and room temperature controller actuates, the fan speed is automatically changed to
stop under low temperature condition of indoor heat exchanger. When room temperature decreases, air conditioner
automatically changes over to ordinary heating operation.
Warming Operation
Heat pump type warming
With the heat pump type warming, the mechanism of heat pump that concentrate heat of outdoor air with the help of
refrigerant to warm the indoor space, is utilized.
Defrosting operation
When a room is warmed with a heat pump type air conditioner, frost accumulates on the heat exchanger of outdoor unit
along with the drop of indoor temperature. Since the accumulated frost reduces the effect of warming, it is necessery to
automatically switch the operation to the defrosting mode. During the defrosting operation, heating operation is interrupted.
Atmospheric temperature and warming capacity
Warming capacity of heat pump type air conditioner decreases along with the drop of outdoor temperature. When the
warming capacity is not sufficient, it is recommended to use another heating implement.
Period of warm-up
Since the heat pump type air conditioner employs a method to circulate warm winds to warm
the entire space of a room, it takes time before the room temperature rises.
It is recommendable to start the operation a little earlier in a very cold morning.
14
Care and Maintenance
Points to observe
Turn off the power supply switch.Do not touch with wet hand.Do not use hot water or volatile liquid.
Do not
use!
Benzine
Tooth powder
ON
OFF
CAUTION
Do not open the inlet grill until fan stops completely.
Fan will continue rotating for a while by the law of inertia after operation is being stopped.
Cleaning the air filter
1.Clean the air filter by lightly tapping it or with the cleaner. It is more effective to clean
the air filter with water.
If the air filter is very dirty, dissolve neutral detergent in the lukewarm water (approx. 30 C),
rinse the air filter in the water, and thoroughly wash the air filter off the detergent
in the plain water.
2.After drying the air filter, set it up on the air conditioner.
Thinner
CAUTION
Do not dry the air filter with fire.
Do not run the air conditioner without the air filter.
Care and Cleaning of the unit
Clean with soft and dry cloth.
If it is very dirty, dissolve neutral detergent in the lukewarm water and make the cloth wet with the water. After wiping,
clean off the detergent using clean water.
Post-Season Care
Operate the unit with FAN mode on a fair day for about half a day to dry the inside of the unit well.
Stop operation and turn off the power supply switch. Electric power is consumed even the air conditioner is in stop.
Clean the air filter and set it in the place.
Pre-Season Care
See that there are no obstacles blocking the air inlet and air outlet of both indoor and outdoor units.
Make sure that the air filter is not dirty.
Cut in the power supply switch 12 hours before starting run.
15
Troubleshooting
Please check the following things about your air conditioner before making a servie call.
Unit fails to start
Is the power source switch
adjust cut in?
ON
OFF
Power supply switch is not
ON.
Is city supply power in normal? Isn't the signal receiving
section exposed to the direct
sunlight or strong illumination?
Power
stoppage?
Cooling or heating is not sufficient
Isn't the earth leakage breaker
in action?
It is dangerous. Turn off the
power supply switch
immediately and contact the
sales dealer.
Is the thermostat adjust as
required?
Isn't the air filter dirty?Isn't any doors or windows
left open?
Doesn't any obstacle exist at
the air inlet or outlet?
Isn't the swing louver horizontal? (At HEATING mode)
If swing louver is horizontal, the blow wind does not reach floor.
Cooling is not sufficient
Isn't sun-shine invading direct? Isn't any unexpected heating
load generated?
Isn't the room much crowded?
The wind does not blow during
heating operation
Isn't it warming up?
When the air conditioner does not operate properly after you have checked the above mentioned items or when the following
phenomenon is observed, stop the operation of the air conditioner and contact your sales dealer.
The fuse or breaker often shuts down.
Water drops off during cooling operation.
There is a irregularity in operation or abnormal sound is audible.
When the CHECK LED1 (red) flickers, an irregularity has occurred in the air conditioner.
16
Troubleshooting
The followings are not malfunction
Water flowing sound is heard.
Shuru
Shuru
When the air conditioner is started, when the compressor starts or stops during
operation or when the air conditioner is stopped, it sometimes sounds "shuru shuru"
or "gobo gobo". It is the flowing sound of the refrigerant, and it is not a trouble.
This is caused by heat expansion or contraction of plastics.Cracking sound is heard.
It smells.Air which blows out from the indoor unit sometimes smells. The smell results from
residents of tobacco smoke or cosmetics stuck inside of unit.
During operation, white fog comes
out of indoor unit.
When the air conditioner is used at restaurant etc. where dense edible oil fume is
always exists, white fog sometimes blows out of air outlet during operation. In this
case consult sales dealer for cleaning the heat exchanger.
It is switched into the FAN mode
during cooling.
To prevent frost from being accumulated on the indoor unit heat exchanger, it is
sometimes automatically switched to the FAN mode but it will soon return to the
cooling mode.
The air conditioner can not be
restarted soon
after it stops.
Unit does
not start
Air does not blow or the fan speed
can not be changed during
Even if the operation switch is turned on, cooling, dehumidifying or heating is not
operable for three minutes after the conditioner is stopped. Because the
protecting circuit is activated (During this time air conditioner operates
in fan mode).
Wait for
three
minutes
When it is excessively cooled during dehumidifying, the blower automatically repeats
reducing and lowering the fan speed.
dehumidifyin.
During operation, operation mode
has changed over automatically.
Water or steam generates from
the outdoor unit during heating.
Isn't the AUTO mode selected?
In the case of AUTO mode, operation mode is changed automatically from cooling
to heating or vise-versa according to the room temperature.
This results when frost accumulated on the outdoor unit is removed (during defrosting
operation).
01610F3Indoor mode abnormalDifferent from outdoor unit mode
2115/Outdoor unit abnormal
2216/Outdoor unit abnormal
2418/Outdoor unit abnormal
2519/Outdoor unit abnormal
271B/Outdoor unit abnormal
281C/Outdoor unit abnormal
291D/Outdoor unit abnormal
301E/Outdoor unit abnormal
311F/Outdoor unit abnormal
3220/Outdoor unit abnormal
3321/Outdoor unit abnormal
3523/Outdoor unit abnormal
3624/Outdoor unit abnormal
3725/Outdoor unit abnormal
3826/Outdoor unit abnormal
3927/Outdoor unit abnormal
432B/Outdoor unit abnormal
442C/Outdoor unit abnormal
472F/Outdoor unit abnormal
4830/Outdoor unit abnormal
4931/Outdoor unit abnormal
583A/Outdoor unit abnormal
593B/Outdoor unit abnormal
633F/Outdoor unit abnormal
6440/Outdoor unit abnormal
1. For the indoor failure,only running LED ON remote receiver will indicate.
2. For the outdoor failure,timer LED and running LED will indicate.timer LED of remote receiver stands for ten's place,and running LED stands for one's
place.timer LED will flash firstly,2 seconds later,running LED will flash too. Afer that,4 seconds later,they will flash in turns again.Flash times equals to the
failure code of outdoor plus.
20.For example,failure code of outdoor is 2,the indoor unit should display 22.As a result,timer LED flashes twice firstly,then running LED flashes twice.
3.To get much more details of outdoor unit failure,Please refer to the the outdoor unit trouble shooting list.
Flash times of
Running LED(or
indoor PCB LED3)
controller)
CODE DISPLAY
Failure code(from
panel controller)
E8Abnormal communication
Trouble shooting
between indoor and outdoor
units
between indoor wired controller
and indoor unit PCB
Possible reasons
at wrong position,or short circuit
at wrong position,or short circuit
Wrong connection,or the wires be
disconected,or wrong address
setting of indoor unit,or faulty
power supply or faulty PCB
Abnormal communication between
indoor wired controller and indoor
unit PCB
wrong position,or the float switch
broken down,or the float switch
disconected,or at wrong position.
Refer to the outdoor unit trouble
shooting
list
18
Precaution For Installation
Please read these "Safety Precautions" first then accurately execute the installation work.
Though the precautionary points indicated herein are divided under two headings, and , those
points which are related to the strong possibility of an installation done in error resulting in death or serious injury are
listed in the section. However, there is also a possibility of serious consequences in relationship to the
points listed in the section as well. In either case, important safety related information is indicated, so by all
means, properly observe all that is mentioned.
After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please
explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's
manual. Moreover, ask the customer to keep this sheet together with the owner's manual.
This system should be applied to places as office, restaurant, residence and the like. Application to inferior environment
such as engineering shop could cause equipment malfunction.
Please entrust installation to either the company which sold you the equipment or to a professional contractor. Defects
from improper installations can be the cause of water leakage, electric shocks and fires.
Execute the installation accurately, based on following the installation manual. Again, improper installations can result
in water leakage, electric shocks and fires.
When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned countermeasure
for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration. In regards to preparing
this countermeasure, consult with the company from which you perchased the equipment, and make the installation
accordingly. In the rare event that a refrigerant leakage and exceeding of threshold concentration does occur, there is
the danger of a resultant oxygen deficiency accident.
For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient,
injury can result from a falling of the unit.
Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and
hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit.
For electrical work, please see that a licensed electrician executes the work while following the safety standards related
to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive use circuits
are used. Insufficient power source circuit capacity and defective installation execution can be the cause of electric
shocks and fires.
Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to
the terminal connection part, through properly securing it. Improper connection or securing can result in heat generation
or fire.
Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can
also result in heat generation or fire.
When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated
refrigerant (R410A) within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from
such mixing.
Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this company
can result in water leakage, electric shock, fire and refrigerant leakage.
WARNING
CAUTION
WARNING
WARNING
CAUTION
CAUTION
Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightning rod or a telephone ground
wire. Improper placement of ground wires can result in electric shock.
The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not installing
an earth leakage breaker may result in electric shock.
Do not install the unit where there is a concern about leakage of combustible gas. The rare event of leaked gas collecting
around the unit could result in an outbreak of fire.
For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to
prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.
19
Is The Unit Installed Correctly
Confirm the following items for safe and comfortable use of air conditioner.
The installation work is to be burden on the sales dealer, and do not conduct it by yourself.
Installation place
Avoid installing the air conditioner near
the place where possibility of inflammable
gas leakage exists.
Explosion (Ignition) may occur.
Select the place so as not to annoy
neighbor with the hot air or noise.
Install the unit at well ventilated place.Install the air conditioner firmly on the
foundation that can fully support the
weight of the unit.
If not, it may cause vibration or noise.If some obstacle exist, it may cause
capacity reduction or noise increase.
Snow protection work is necessary
where outdoor unit is blocked up by snow.
It is advisable not to install the air conditioner at the following special place.
It may cause malfunction, consult the
sales dealer when you have to install
the unit on such a place.
For details consult your sales dealer.
The place where corrosive gas generates
(Hot spring area etc.)
The place where salt breeze blows
(Seaside etc.)
The place where dense soot smoke exists
The place where humidity is extraordinarily high
The place where near the machine which
radiates the electromagnetic wave
The place where voltage variation is considerably large
Electric work
The electric work must be burden on the authorized engineer with qualification for electric work and grounding work, and
the work must be conducted in accordance with electric equipment technical standard.
The power source for the unit is to be of exclusive use.
An earth leakage breaker should be installed.(This is necessary to prevent electric shock.)
The unit must be grounded.
When you change your address or the installation place
Special technology is required for removal or reinstallation of air conditioner, consult the sales dealer. Besides, construction
expense is charged for removal or reinstallation.
For inspection and maintenance
The capacity of air conditioner will decrease by contamination of inside of unit when it is used for about three years although
depending upon the circumstances under which it is used, and so in addition to the usual maintenance service, special
inspection/maintenance service is necessary. It is recommended to make a maintenance contract (charged) by consulting
your sales dealer.
20
Installation Procedure
Indoor Unit
NOTE
All wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATIONS. These instructions
do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular
problems occur, the matter should be referred to your local distributor.
WARNING
BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE TO FOLLOW
THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR
PROPERTY DAMAGE.
Before installation (Before finishing installation, do not throw the attached parts installation needs)
Confirm the way to move the unit to the installation place.
Before moving the unit to the installation place, do not remove their packages. When having to remove the package, use
a soft material or protection board with rope to lift the unit assembly to avoid unit damage or bumping a scrape.
Choose installation place
The chosen installation place should meet the following requirements and get the user's consent.
Place ensures ideal airflow distribution.
The passage of airflow has no obstacles.
When importing outside air, it should be imported directly from outdoors. (If the pipe can not be extended, it also can not
be imported from top)
Place ensures enough space for maintenance.
The pipe length between indoor and outdoor unit is in the permitted limit (referring to outdoor unit installation part).
The indoor unit, outdoor unit, electric wire and connection wire is at least 1m away from television and radio. This is to
avoid the image disturbance and noise caused by the above mentioned home appliance. (Even if 1m away, if the
electromagnetic wave is too strong, it can also cause noise.)
The indoor unit can install on the ceiling, which height is no more than 3m.
Install and use the hoisting screw. Check if the installation place can bear the weight of unit assembly. If not certain,
strengthen it before install the unit.
Over 100Over 900
Air out
Air in
Checking meatus
(600x600)
Over 300
Over 200
Ceiling
Installation for indoor unit
1.The position relation among hoisting screw (unit: mm)
1270
853
794
1103
Down side
360
250
Up side
2.If necessary, cut the opening installation and checking needed on the ceiling. (If having ceiling)
Before installation, finish the preparation work of all the pipes (refrigerant, drainage) and wire (wire controller connection
wire, indoor and outdoor unit connection wire) of indoor unit, so that after installation, they can be immediately connected
with outdoor unit.
Cut the opening on the ceiling. Maybe it needs to strengthen the ceiling to keep the ceiling even and flat and prevent the
ceiling from vibration. For details, please consult to the builder.
21
Installation Procedure
Indoor Unit
3. Hanger bolts installation
Use care of the piping direction when the unit is installed.(Use
M10 screw bolt)
In order to bear the weight of the unit, for existed ceiling, using
foundation screw bolt, and for new ceiling, using burying embedded
screw bolt, burying screw bolt or spot supplied other parts.
Before going on installation, adjust the gaps with ceiling.
4. Installation of indoor unit
Fix the indoor unit to the hanger bolts.
If required, it is possible to suspend the unit to the beam, etc.
Directly by use of the bolts without using the hanger bolts.
Note
When the dimensions of main unit and ceiling holes does not
match, it can be adjusted with the slot holes of hanging bracket.
5. Adjusting to the levelness
(a) Adjust the out-of levelness using a level or by the following
method.
Make adjustment so that the relation between the lower surface
of the unit proper and water level in the hose becomes as given
below.
(b)Unless the adjustment to the levelness is made properly,
malfunctioning or failure of the float switch may occur.
Hole-in anchor
Hole-in plug
M10 nut
Main unit
Piping side
Supply water
Water level
0~5 mm
(0~0.2")
Bring the piping side slightly lower.
Insert
Concrete
Hanging bolt M10
Hanging bolt
M10 washer
M10 spring washer
PVC hose
22
Installation Procedure
(a)
Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an elevation or making traps.
Drain Piping
Good piping
Suspension
bolts
Heat
insulation
(b)
When connecting the drain pipe to unit, pay suffcient attention
1.5m ~ 2m
A downhill grade
of 1/100 or more
not to apply excess force to the piping on the unit side. Also,
fix the piping at a point as close as possible to the unit.
(c)
For drain pipe, use hard PVC general purpose pipe VP-25(I.D.1")
which can be purchased locally. When connecting, insert a
PVC pipe end securely into the drain socket before tightening
securely using the attached drain hose and clamp. Adhesive
must not be used connection of the drain socket and drain
hose (accessory).
(d)
When constructing drain piping for several units, position the
common pipe about 100 mm below the drain outlet of each
unit as shown in the sketch. Use VP-30(11/4") or thicker pipe
for this purpose.
Improper piping
Avoid riding across an elevation
Air vent
Drain socket
Drain socket
Pipe cover(large)
[for insulation]
Main unit
Pipe cover(small) [for insulation]
(accessory)
Secure the elevation as high as possible (approx. 100 mm)
(accessory)
Drain hose
(accessory)
Clamp
(accessory)
Keep free from traps
Do not pipe under water
Stage
difference
part
Adhesion
Drain hose
VP-25 joint
(field purchased)
Pipe cover [for insulation]
(field purchased)
VP-25
(field purchased)
The stiff PVC pipe put indoor side should be heat insulated.
(e)
(f)
Avoid putting the outlet of drain hose in the places with irritant gas generated. Do not insert the drain hose directly into
A downhill grade of 1/100 or more
VP-30
drainage, where the gas with sulfur may be generated.
(g)
Because the drain spout is at the position, which negative
pressure may occur. So with the rise of water level in the drain
pan, water leakage may occur. In order to prevent water leakage,
we designed a backwater bend. The structure of backwater
bend should be able to be cleaned. As the right figure shown,
use T type joint. The backwater bend is set near the air
conditioner.
H1H2
H1=100mm or the static pressure of
air sending motor
H2=1/2H1 (or between 50~100mm)
As figure shown, set a backwater bend in the middle of drain
hose.
Drainage Test
(1)
Conduct a drainage test after completion of the electrical work.
(2)
During the trial, make sure that drain flows properly through the piping and that no
water leaks from connections.
(3)
In case of a new building, conduct the test before it is furnished with the ceiling.
(4)
Be sure to conduct this test even when the unit is installed in the heating season.
Procedures
(a)
Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.
(b)
Check the drain while cooling operation.
23
Installation Procedure
Air Duct
Please consult the after-sales service personnel for the choosing and installation of suction inlet, suction duct, discharging
outlet and discharging duct. Calculating the design drawing and outer static pressure, and choose the discharging duct
with proper length and shape.
muffler cavity (air sending)
Sacking joint
Insulation
Air outlet
A
Air conditioner
main unit
Checking meatus
Air volume adjuster
Ceiling
Air suction grille with air filter
The length difference among every duct is limited below 2:1.
Reduce the length of duct as possible as can.
Reduce the amount of bend as possible as can.
Use heat insulation material to bind and seal the part connecting main
unit and the flare part of air discharging duct. Perform duct installation
work, before the fitment of ceiling.
Calculation method of the dimension of the simple quadrate air duct
Presuming the unit length friction impedance of the duct is
1Pa/m, when the dimension of one side of the air duct is
fixed as 250mm, as shown below:
AD48HS1ERA AD60HS1ERA
Air volume
2400m3/h(40m3/min)250x560(mmxmm)
A
600m3/h(10m3/min)
B
Duct
250x190(mmxmm)
Enlarging chart of profile chart A
Vibration resistance hook
B
A
Static pressure
box
A
Air conditioner
Good exampleBad exampleBad example
A
Equipped with
air filter (bought)
The calculation of duct resistance (the simple calculation is as follow table)
Straight part
Bend part
Air out part
Static pressure box
Air inlet grille (with air filter)
Calculate as per 1m length 1Pa, 1Pa/m
Each bend takes as a 3~4m long straight duct
Calculate as 25Pa
Calculate as 50Pa/each
Calculate as 40Pa/each
The chosen chart of simple duct
Note:1Pa/m=0.1mmAg/m
Shape
Item
Air volume
3
/h(m3/n)
m
100
200
300
400
500
600(10)
800
1,000
1,200(20)
1,400
1,600
Shape
Item
Square duct
Dimension
(mmxmm)
250 x 60
250 x 90
250 x 120
250 x 140
250 x 170
250 x 190
250 x 230
250 x 270
250 x 310
250 x 350
250 x 390
Air volume
3
/h(m3/n)
m
1,800(30)
2000
2400
3,000(50)
3,500
4,000
4,500
5,000
5,500
6,000(100)
Square duct
Dimension
(mmxmm)
250 x 430
250 x 470
250 x 560
250 x 650
250 x 740
250 x 830
250 x 920
250 x 1000
250 x 1090
250 x 1180
24
Installation Procedure
The attentive matters in installation of air suction and discharging duct
Recommend to use anti-frost and sound-absorbing duct. (locally bought)
The duct installation work should be finished before the fitment of ceiling.
The duct must be heat insulated.
The specific air-discharging outlet should be installed at the place where the
airflow can be reasonably distributed.
The surface should leave a checking meatus for checking and maintenance.
The examples of improper installation
Do not use air inlet duct and take the ceiling inner side as duct instead.
The result is because of the irregular outer air mass, strong wind and
sunshine, the humidity is increased.
There may be water drop on the outside of duct. For cement and other
new constructions, even if not taking ceiling inner side as duct, the
humidity will also be so high. At this time, use glass fiber to perform
heat preservation to the whole. (use iron net to bind the glass fiber)
Maybe exceeding the unit operation limit (for example: when indoor
dry bulb temperature is 35 C, wet bulb temperature 24 C), it may lead
to overload of compressor.
Affected by the capacity of air discharging fan, the strong wind in the
outer duct and wind direction, when unit air sending volume exceeds
the limit, the discharged water of heat exchanger will overflow, leading
to water leakage.
Special air discharging outlet
Use screw bolt to fix
Air
Air
Improper example
Air discharging fan
Air Duct
Duct
25
Installation Procedure
Refrigerant Pipe
The gas side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause water leakage.
The outdoor unit has been charged with refrigerant.
When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown, use spanner and
torque spanner together.
When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Use hand to twist 3-4
rings, then fasten with spanner.
Referring to Table I to confirm the fasten torque. Too tight may damage nut leading to leakage.
Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown.
Only use seal cushion to bind the joint part of air pipe and heat insulation parts.
Paste the refrigerant oil here
Torque spanner
Spanner
Pipe joint
Cone nut
Drain hose connection mouth
VP25 PVC pipe
Middle size seal cushion (accessory)
(Use seal cushion to
bind the pipe joint)
Clamp
Heat insulation (accessory)
(for liquid pipe)
Heat insulation (accessory)
(for gas pipe)
Gas pipe
Liquid pipe
80510
Liquid pipe
Air inletAir outlet
Gas pipe
530
Table I
Specification
of pipe
9.52mm
15.88mm
19.05mm
Electric box
Upper
Down side
Tighten torque
3270~3990 N.cm
(333~407 kgf.cm)
6180~7540 N.cm
(630~770 kgf.cm)
9720~11860 N.cm
(990~1210 kgf.cm)
310
30
Cone
dimension
A (mm)
12.0~12.4
18.6~19.0
22.9~23.3
Cone
45 2
A
90 0.5
R0.4~0.8
26
Installation Procedure
WARNING
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC
CONNECTIONS.
GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
Precautions for Electrical wiring
Electrical wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated
grip on the ends of the wires.
Use copper conductor only.
Selection of size of power supply and interconnecting wires
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)
Electrical Wiring
Item
Phase
Model
AD48HS1ERA
AD60HS1ERA
Wiring connection
Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by terminals.
Switch breaker
3304.0 302030
Circuit breaker
(A)
Overcurrent protector
rated capacity (A)
Power source
wire size
(minimum)
2
(mm
)
Earth leakage breaker
Switch
breaker(A)
Leak
current(mA)
27
Loading...
+ 104 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.