Before disposing an old air conditioner
that goes out of use, please make sure it's
inoperative and safe. Unplug the air
conditioner in order to avoid the risk of
child entrapment.
It must be noticed that air conditioner
system contains refrigerants, which require
specialized waste disposal. The valuable
materials contained in a air conditioner can
be recycled. Contact your local waste
disposal center for proper disposal of an
old air conditioner and contact your local
authority or your dealer if you have any
question. Please ensure that the pipework
of your air conditioner does not get
damaged prior to being picked up by the
relevant waste disposal center, and
contribute to environmental awareness by
insisting on an appropriate, anti-pollution
method of disposal.
Disposal of the packaging of your new air
conditioner
address of the waste materials collecting
centers and waste paper disposal services
nearest to your house.
Safety Instructions and Warnings
Before starting the air conditioner, read the
information given in the User's Guide
carefully. The User's Guide contains very
important observations relating to the
assembly, operation and maintenance of the
air conditioner.
The manufacturer does not accept
responsibility for any damages that may
arise due to non-observation of the following
instruction.
Damaged air conditioners are not to be
put into operation. In case of doubt, consult
your supplier.
Use of the air conditioner is to be carried
out in strict compliance with the relative
instructions set forth in the User's Guide.
Installation shall be done by professional
people, don't install unit by yourself.
All the packaging materials employed in
the package of your new air conditioner
may be disposed without any danger to the
environment.
The cardboard box may be broken or cut
into smaller pieces and given to a waste
paper disposal service. The wrapping bag
made of polyethylene and the polyethylene
foam pads contain no fluorochloric
hydrocarbon.
All these valuable materials may be taken to a
waste collecting center and used again after
adequate recycling.
Consult your local authorities for the name and
For the purpose of safety, the air
conditioner must be properly grounded in
accordance with specifications.
Always remember to unplug the air
conditioner before opening inlet grill. Never
unplug your air conditioner by pulling on the
power cord. Always grip plug firmly and
pull straight out from the outlet.
All electrical repairs must be carried out
by qualified electricians. Inadequate repairs
may result in a major source of danger for
the user of the air conditoiner.
1
Cautions
Do not damage any parts of the air
conditioner that carry refrigerant by
piercing or perforating the air conditioner's
tubes with sharp or pointed items, crushing
or twisting any tubes, or scraping the
coatings off the surfaces. If the refrigerant
spurts out and gets into eyes, it may result
in serious eye injuries.
Do not obstruct or cover the ventilation
grille of the air conditioner. Do not put
fingers or any other things into the
inlet/outlet and swing louver.
Do not allow children to play with the air
conditioner. In no case should children be
allowed to sit on the outdoor unit.
2. If the supply cord is damaged, it must be
replaced by the manufacturer or its service
agentor a similar qualified person.
3. If the fuse on PC board is broken please
change it with the type of T 3.15A /250VAC.
4. The wiring method should be in line with
the local wiring standard.
5. The power and connecting cable are selfprovided, For series 142, 182 (*EAA), The
requirement of the power cable:
H05RN-F 3G 2.5mm
2 .
The requirement of connecting cable:
H05RN-F 3G 2.0mm2 +H05RN-F 1x0.75mm
For other series, refer to outdoor operation
manual to select teh power cable and
connecting cable.
6. The breaker of the air conditioner should be
all-pole switch; and the distance between its
two contacts should be no less 3mm. Such
means for disconnection must be incorporation
in the fixed wiring.
7. The waste battery shall be disposed properly .
8. The indoor unit installation height is at least
2.5m.
9. The air breaker and the power switch should
installed the conveniently reachable pleace for
user.
Carefully read the following information in order to operate the airconditioner correctly.
Below are listed three kinds of Safety Cautions and Suggestions.
WARNING!
CAUTION!
INSTRUCTIONS: These information can ensure the correct operation of the machine.
Be sure to conform with the following important Safety Cautions.
The Safety Cautions should be at hand so that they can be checked at any time when needed.
If the conditioner is transferred to the new user, this manual should be as well transferred to the new user.
Incorrect operations may result in severe consequences of death or serious injuries.
Incorrect operations may result in injuries or machine damages; in some cases may
cause serious consequences.
WARNING!
Don't blow the human body with the cooling
air too long, and don't let the room temperature decrease too low
either.
Otherwise the one
will feel unpleasant
or harm ones' health.
If any abnormal phenomena is found (e. g.
smell of firing), please cut off the power
supply immediately, and contact the dealer
to find out the handling method.
In such case, to continue
using the conditioner will
damage the conditioner,
and may cause electrical
shock or fire hazard.
When need maintenance and repairment,
call dealer to handle it.
Incorrect maintenance and repairment
may cause water
leak, electrical shock
and fire hazard.
switch
off
Please let the dealer be responsible for installing
the conditioner.
Incorrect installation may cause water leak, elec-
trical shock and fire hazard.
Don't put fingers or any other things into the
inlet/outlet and swing louver while the condi-
tioner is in operation.
Because the highspeed
fan is very dangerous
and may cause injuries.
Call the dealer to take measures to prevent the
refrigerant from leaking.
If conditioner is installed in a small room be sure
to take every measure in order to prevent suffoca-
tion accident even in case of refrigerant leakage.
When conditioner is deinstalled or reinstalled
dealer should be responsible for them.
Incorrect installation may cause water leaking,
electrical shock and fire hazard.
3
Cautions
CAUTIONS!
Conditioner should not be used for any other
purpose other than airconditioning.
Don't use air-conditioner for any other special
purposes, e.g. the preservation and protection
of food, animals, plants,
pecision apparatus as well
as work of art, otherwise
the qualities of these
stuffs may be damaged.
Don't dismantle the outlet of the outdoor unit.
The exposure of fan is
very dangerous which
may harm human beings.
When air-conditioner is co-used with other
heat-radiator the frequent replacement of
room atmosphere should be required.
Inefficient ventilation may cause
suffocation.
After a long time use of air-conditioner the
base should be checked for any damages.
If the damaged base is
not repaired, the unit
may fall down and
cause accidents.
No goods or nobody is permitted to placed on
or stand on outdoor unit.
The falling of goods and
people may cause accidents.
Pets and plants should not be blowed directly
in the air flow.
Otherwise will suffer
damage.
Don't operate the air-conditioner with damp hands.
Otherwise will be shocked.
Only use correctly-typed fuse.
May not use wire or any other
materials replacing fuse, otherwise may cause faults or fire
accidents.
Don't place any burning unit
in the air flow of air-conditioner,
which may cause incomplete
combustion.
No inflammable spray fluid
should be permitted to be
placed or used near to airconditioner otherwise may
cause fire accidents.
Air-conditioner should be
cleaned only after power
supply is cut off to keep
from shock or hurt.
Don't clean air-conditioner
with water.
Otherwise may cause
shock.
When use the fumigating insecticide don't
open air-conditioner.
Otherwise the poisonous chemicals may settle
in air-conditioner which harm the health of
chemical-allergic people.
4
Cautions
Installation
Please ask the dealer or specialist to install, never try by the users themselves. After the installation please
be sure of the following conditions.
WARNING !
Please call dealer to install the air-conditioner.
Incorrect installation may cause water leaking, shock and fire hazard.
CAUTION !
Air-conditioner can't be installed in the environment with inflammable gases because the
inflammable gases near to air-conditioner may
cause fire hazard.
Installed electrical-leaking circuit breaker.
It easily cause electrical shock without circuit
breaker.
[Location]
Air-conditioner should be located in well-vented
and easily-accessible place.
Air-conditioner should not be located in the
following places:
(a) Places with machine oils or other oil vapours.
(b) Seaside with high salt content in the air.
(c) Near to hot spring with high content of sulfide
gases.
(d) Area with frequent fluctuation of voltage e.g.
factory, etc.
(e) In vehicles or ships.
(f) Kitchen with heavy oil vapour or humidity.
(g) Near to the machine emitting electric-magnetic
waves.
(h) Places with acid, alkali vapuor.
TV, radio, acoustic appliances etc are at least 1 m
far away to the indoor unit, outdoor unit, power
supply wire, connecting wire, pipes, otherwise
images may be disturbed or noises be created.
Connect earthing wire.
Earthing wire should not be connected to the gas pipe, water pipe,
lightning rod or phone line, incorrect earthing may cause shock.
Use discharge pipe correctly to ensure efficient
discharge.
Incorrect pipe use may cause water leaking.
As required, take measures against heavy snow.
Earthing
[Wiring]
Air-conditioner should be equipped with special
power supply wire.
[Operating noise]
Chose the following locations:
(a) Capable of supporting air-conditioner weight,
don't increase operating noise and vibration.
(b) Hot vapour from outdoor unit outlet and ope rating noise don't disturb neighbour.
No obstacles around the outdoor unit outlet.
5
Introduction to Spare Parts
(For series 142, 182 )
Swing louver
(Air flow direction can be adjusted by using
the SWING button on the remote controller)
Operating Control Panel
Air Inlet Grille
Air Filter
(Inside of the Inlet Grille)
(For series 242, 282, 362, 422, 482, 602 )
Discharge unit (built in)
In cooling operation,
to discharge the
water from inside the
room.
Outlet
Air filter
(located in the suction grill)
Suction grill
Note : For the wired control type unit, the unit state should be checked by the the
Drain Hose
Swing fender
(located in the outlet)
Refrigerant pipe
Cable line
Earthing line
wired controller, instead of the remote receiver; and if you set the TIMER function,
the TIMER LED on the remote receiver will not be on.
6
Maintenance
Clean the unit
Turn off the power supply switch
ON
OFF
NOTE:
For detailed information consult dealer.
Do not touch with wet hand.
(For series 142, 182 )
The 4 fixed bolts must be loosed as shown in
the figure by arrow if they are bolts, the method
is that: push the blots inward till to another edge.
Generally the fixed blots are opened for inlet
grille easily up and down as well cheaning the
air filter.After open it,lower the inlet grille using
remote controller, the maximum distance is 2.24m.
Then turn the 1 rotated clamps 90 degree as
shown in the figure, hold the air filter and nearly
in the horizontal direction slightly pull it out.
Fixing nolt
Do not use hot water or volatile liquid
Fixing nolt
Rotary fixing clamp
Fixing nolt
Outward drawable filter
Clean the air filter
Clean the air filter with water or vacuum cleaner.
Use the detergent or neutral soapy water if the
air filter is too dirty. Then rinse the air filter with
water,and reinstall after drying.
Caution:
Do not clean the air filter with hot water over 40 C,
otherwise may damage the filter.
Sweep the filter carefully.
Clean indoor (outdoor )unit
Clean with hot wet cloth and neutral detergent, then wipe with
dry cloth.Do not use too hot water (over 40 C) which may result
in fading and deforming. Do not use insecticide and chemical
washing agent.
7
Maintenance
(For series 242, 282 )
[Clean air filter]
NOTE
1. Open inlet grill
Press the elliptical "PUSH" knob, the inlet
grill will automatically drop. (the inlet grill
is catched with two pothooks)
When having to clean, don't dismantle
air-filter,otherwise may cause faults.
In the environment where there is too
much dust, air filter should be cleaned
for more times.
(about half a year one time)
PUSH
Press the elliptical knob
the inlet grill will
automatically drop
(B) Wash with water.
With too much dust, use soft brush and neutral
detergent.
Swing off the water, and then place in cool place.
5. Install air filter
(1) Put filter into protruding parts at the top of
the inlet grill.
(2) Connect the two pothooks with inlet grill
See 2
Open two
pothooks
Pothook
2. Open two othooks
3. Dismantle air filter
Drag the knob of
the grill back lift
Air filter
the filter and take
down.
4. Clean
CAUTION!
(A) Remove dust with vacuum filter.
Connet the two pothooks with inlet grill
6. Close inlet grill
See 1.
7. Press the filter signal return key on the
controller.
'' ''
[Clean inlet grill]
1. Open inlet grill
Press the elliptical "PUSH" knob, the inlet
grill will automatically drop. (the inlet grill
is catched with two pothooks)
PUSH
Open two
pothooks
Press the elliptical knob
the inlet grill will
automatically drop
Pothook
8
Maintenance
2. Take off air-filter
3. Take of inlet grill
[Dismantle and install swing
plate ]
1. Fix the swing plate at the bottom.
2. Dismantle the swing plate.
4. Clean
CAUTION!
NOTE
When the filter too much dust
To spray the special detergent for vent fan or
utensils.
5. Install inlet grill
6. Install air filter
7. Close inlet grill
see 3
see "Clean air filter"
see 1
[Clean outlet and shell]
CAUTION!
Use water to clean the plate and don't heavily
scrub, otherwise the fine hair may fall off.
Unscrew the screw at both ends of the swing
plate.
[Dismantle and install swing
plate ]
3. Install swing plate
Lightly rotate swing plate to insert the ridge
at both ends of the outlet into the groove
and then screw up.
CAUTION!
Don't use gasoline, benzene, dilutant,
polishing powder, or liquid inseticide.
9
Maintenance
(For series 362, 422, 482, 602 )
Clean the air filter
Instructions :
When not for cleaning, do not dismantle the air filter, otherwise it may cause trouble.
When the air conditioner is used in a dusty environment, the air filter should be cleaned more often
(generally once every two weeks).
Open
1. Open air inlet grille
Pull the two handles at the same time, slowly draw
them out. (when closing it, the procedure is reversed.)
2.Dismantle the air filter
Pull the two side handles at the back of the air
inlet grille, lift the air filter to dismantle it.
3. Clean
Notice
Do not use the hot water over 50 C to clean to avoid
discoloration or deformation.
Do not dry the unit on fire, the filter may be burnt.
Use cleaner or water to clean to remove dust.
(A) Use cleaner to remove dust.
(B) When the dust is too much, use soft brush and neutral detergent.
(C) Throw the water off, then put it in the shadow for airing.
10
Open and remove
Maintenance
4. Install air filter
(1)Put the air filter into those extruding parts at the top of the air inlet grille.
(2)Draw the handles at the back of the air inlet grille inwards to fix the air filter.
5. Close air inlet grille
Referring to procedure 1.
Clean the air inlet grille
1. Open air inlet grille
Pull the two handles at the same time, slowly draw them
out. (when closing it, the procedure is reversed.)
2. Remove air filter
Referring to “Clean the air filter”.
3. Remove the air inlet grille
Open the air inlet grille for 45 , the lift it up.
4. Clean
Notice
Do not use the hot water over 50 C to clean
to avoid discoloration or deformation.
Use soft brush, water and neutral detergent to clean,
then throw the water off.
Instruction
[ When there is too much dust ]
Use ventilation fan or directly spray the detergent special for kitchen
ware on the air inlet grille, 10 minutes later use water to clean.
Open
5. Install air inlet grille
Referring to procedure 3.
6. Install the air filter
Referring to “Clean the air filter”
7. Close air inlet grille
Referring to procedure 1.
11
Maintenance
Seasonal Reserve
Post-season Care
Operate the unit with FAN mode on a fair day for about half
a day to dry the inside of the unit well.
Stop operation and turn off the power supply switch .Electric
power is consumed even the air conditioner is in stop.
Clean the air filter, indoor unit and outdoor unit,and cover
the unit with dustcoat.
Pre-season Care
See that there is no obstacles blocking the air
inlet and air outlet of both indoor and outdoor
unit to avoid reduce the working efficiency.
Be sure to install the air filter, ensure that the air filter is not dirty. Otherwise may result in
machine damages or cause malfunciton due th dust inside the unit
To prevent compressor when start in HEAT mode,
please cut in the power supply switch 12 hours
before starting run,furthermore, always keep the
power supply switch on during the using senson.
NOTE
The inner part of indoor unit must be cleaned. Consult dealer, because clean must be done by
1.
technician.
In cooling operation, discharging system discharge water in room.
2.
12
Trouble Shooting
The followings are not malfuncition
Water flowing sound is heard
Hua
Hua
Cracking sound is heard
It smells.
During operation, white fog comes out of
indoor unit.
When the air conditoner is started, when the
compressor starts or stops during operation
or when the air conditioner is stopped,it sometimes sounds “ Bi- Bi-” or “Godo-Godo”. It is
the flowing sound of the refrigerant , not a
malfunction.
This is caused by heat expansion or contraction of plastics
Air blown out from the indoor unit sometimes
smells. The smell results from smells of
furniture, paint , tobacco absorbed by indoor
unit.
When in COOL or DRY mode, a thin water
fog can be seen blown out of unit ,this is the
condensed fog because the suddenly cooled
indoor air is blown out.
Automatically switch into FAN mode during
cooling.
The air conditioner cannot be restarted soon
after it stops.
Air conditioner does not start?
To prevent frost from being accumulated on the
indoor unit heat exchanger, it sometimes automatically switched into the FAN mode,but it will
soon back to the cooling mode.
This is because of the self-protection function
of the system, therefore,it cannot be restarted
for about three minutes after it stops.
Please wait for three minutes
13
Trouble Shooting
Air does not blow or the fan speed cannot be
changed during drying.
Water or vapor generated from the outdoor
unit during heating.
During heating,indoor fan is still running even
unit is stopped.
In DRY mode, when room temperature
becomes 2 C higher than temperature setting,
unit rill run intermittently at LO speed regardless
of FAN setting
This happens when the frost accumulated on
the outdoor unit is removed (during defrosting
operation).
Defrosting operation
To get ride of the excess heat, indoor fan will
continue running for a while after unit automatically stops.
Please check the following things about your air conditioner before making a
service call.
Is the power supply switch on ?
**?
Power supply switch is not in
ON position.
Unit fails to start.
Is city supply power normal ?
ON
OFF
14
Is the earth leakage breaker
in action ?
Be sure to turn off the power
supply switch immediately and
contact the sales dealer.
When Trouble Happens
Insufficient cooling or heating
The operation controller
adjusted as required
Any obstacle exists at the air
inlet or outlet?
Any other heat sources in the
room?
Air filter too dirty ?
Door or window left opened ?
Insufficient cooling
Sunlight direct into the
room ?
Horizontal swing louver
upward ? (in HEAT mode)
Too crowed in the room ?
Cooled air blown out ( when heating)
When the air conditioner does not operate properly after
you have checked the above-mentioned items or when
following phenomenon is observed,stop the operation of
the air conditioner and contact your sales dealer.
1)The fuse or breaker often shuts down.
2)Water drops off during cooling or drying operation.
3)There is an irregularity in operation or abnormal sound that
is audible.
15
When Trouble Happens
Error display ( For ERA series )
Remarks
Resumable if
lower than 100
degree
Reason
Failure description
For remote
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
Indoor ambient temp. sensor failure
Indoor coil temp. sensor failure
Outdoor ambient temp. sensor failure
type, flash
times12
3
Sensor broken down or short circuit for more than 2m continuously
Outdoor coil temp. sensor failure (compressor
discharging temp. sensor)
4
Fault phase, short of phase, out of balance greatly
CT check abnormal 3 times in 30m
High pressure switch acts 3 times in 30m
Over-current protection
High pressure abnormal
5
6
Communication abnormal for more than 4m continuously
Communication abnormal for more than 4m continuously
Float switch broken down for more than 25m continuously
Outside signal broken down for more than 10s
Sensor broken down or short circuit for more than 2m continuously
Solenoid valve act incorrectly 3 times continuously
Sensor broken down or short circuit for more than 2m continuously
EEPROM data missing
Low pressure switch acts in normal running
Power supply abnormal
Communication between wired
controller and indoor abnormal
Communication between indoor and outdoor abnormal
Drainage system abnormal
Outside alarm signal input
Gas pipe temp. sensor abnormal
Temperature protection malfunction
Discharging temp. sensor abnormal
EEPROM abnormal
Pressure abnormal(low pressure)
7
8
9
10111213141516
16
Indoor operation mode is different with the running indoor unit.
The discharging temperature is higher than 120degree
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
Spdu module temperature is too high
Compressor overheat
Abnormal mode
Outdoor coil B(suction temp sensor-for MRV II)
Outdoor discharging B(oil temp sensor-for MRV II)
SPDU module temperature protection
1718192021
shows resumable fault, * shows it is not resumable fault.
When Trouble Happens
Error display ( For EAA series )
Remarks
Resumable if
lower than 100
degree
Reason
Failure description
For remote
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
Indoor ambient temp. sensor failure
Indoor coil temp. sensor failure
Outdoor ambient temp. sensor failure
type, flash
times12
3
Sensor broken down or short circuit for more than 2m continuously
Outdoor coil temp. sensor failure (compressor
discharging temp. sensor)
4
Fault phase, short of phase, out of balance greatly
CT check abnormal 3 times in 30m
High pressure switch acts 3 times in 30m
Over-current protection
High pressure abnormal
5
6
Communication abnormal for more than 4m continuously
Communication abnormal for more than 4m continuously
Float switch broken down for more than 25m continuously
Outside signal broken down for more than 10s
Sensor broken down or short circuit for more than 2m continuously
Solenoid valve act incorrectly 3 times continuously
Sensor broken down or short circuit for more than 2m continuously
EEPROM data missing
Low pressure switch acts in normal running
Power supply abnormal
Communication between wired
controller and indoor abnormal
Communication between indoor and outdoor abnormal
Drainage system abnormal
Outside alarm signal input
Gas pipe temp. sensor abnormal
Temperature protection malfunction
Discharging temp. sensor abnormal
EEPROM abnormal
Pressure abnormal(low pressure)
7
8
9
10111213141516
17
Indoor operation mode is different with the running indoor unit.
The discharging temperature is higher than 120degree
Sensor broken down or short circuit for more than 2m continuously
Sensor broken down or short circuit for more than 2m continuously
Compressor overheat
Abnormal mode
Outdoor coil B(suction temp sensor-for MRV II)
Outdoor discharging B(oil temp sensor-for MRV II)
171819
shows resumable fault, * shows it is not resumable fault.
20
Customer Need-to-know
Customer Need-to-know
Please install the air conditioner according to the requirements specified in this manual to ensure
the air conditioner work well.
Be careful not to scratch the surface of the case during moving the air conditioner.
Please keep the installation manual for future reference when maintenance and changing installation place.
After installation ,please use the air conditioner according to the specification in the operation
manual.
Using Directions
Adjust suitable airflow direction
Keep the proper indoor temperature.
Too cool or hot is not good for your health.
Furthermore,it will result in excessive
consumption of electric power.
Optimal
temperature
Avoid direct sunlight and airflow
Effectively use timer.
Using TIMER mode, you can make the room
temperature reach a suitable temperature when
you wake up or back home.
18
Installation Procedure
CAUTIONS:
To ensure proper installation, read "Cautions" carefully before working. After
installation, start the unit correctly and show customers how to operate and
maintain the unit.
Meanings of Warning and Cautions:
Warning! Serious injury or even death might happen, if it is not observed.
Caution! Injury to people of damages to machine might happen, if it is not observed.
WARNING!
Installation shall be done by professional people, don't install unit by yourself. Incorrect installation will
cause water leakage, electric shock or fire.
Install unit as per the Manual. Incorrect installation will cause water leakage, electric shock or fire
accident.
Be sure to use specified accessaries and parts. Otherwise, water leakage, electric shock, fire accident or
unit falling down may happen.
Unit should be placed on a place strong enough to hold the unit. Or, unit will fall down causing injuries.
When install the unit, take in consideration of storms, typhoom, earthquake. Incorrect installation may
cause unit to fall down.
All electric work shall be done by experienced people as per eocal code, regulations and this Manual.
Use exclusive wire for the unit. Incorrect installation or undersized electric wire may cause electric
shock or fire accident.
All the wires and circuit shall be safe. Use exclusive wire firmly fixed. Be sure that external force
will not affect terminal bolck and electric wire. Poor contact and installation may cause fire accident.
Arrange wire correctly when connectin indoor and outdoor power supply. Fix terminal cover firmly to
avoid overheat, electric shock or even fire accident.
In case retrigerant leakage occurred during unit installation, keep a good ventilation in the room.
Poisonous gas will occur when meet with fire.
Check the unit upon installation. Be sure there is no leakage. Refrigerant will induce poisonous gas
when meet heat source as heater, oven, etc.
Cut power supply before touching terminal bolck.
CAUTION!
Unit shall be grounded. But grounding shall not be connected to gas pipe
water pipe, telephone line. Poor grounding will cause electric shock.
Be sure to install a leakage breaker to avoid electric shock.
Arrange water drainage according to this Manual. Cover pipe with insulation materials in case
dew may occur. Unproper installation of water drainage will cause water leakage and wer your furniture.
To maintain good picture or reduce noise, keep at least 1 m from T.V. radio, when install indoor and ou
tdoor unit, connecting wire and power line. (If the radio wave is relatively strong, 1 m is not enough
to reduce noise).
Don't install unit in following places:
(a) Oil mist or oil gas exists, such as kitchen, or, plastic parts may got aged, or water leakage.
(b) Where there is corrosive gas. Copper tube and welded part may be damaged due to corrosion,
causing leakage.
(c) Where there is strong radiation. This will affect unit's control system, causing malfunction of the unit
(d) Where flamable gas, dirt, and volatile matter (thinner, gasoline) exist, These matter
might cause fire accident.
Refer to paper pattern when installing unit.
Cautions for the installation personnel
Don't fail to show customers how to operate unit.
19
Earthing
Installation Procedure
1
1. BEFORE INSTALLATION
Determine the way to carry unit to installation place.
Don't remove packing until unit reaches installation place.
If unpacking is unkavoidable, protect unit properly.
2
2. SELECTION OF INSTALLATION PLACE
(1) Installation place shall meet the following and agreed by customers:
Place where proper air flow can be ensured.
No block to air flow.
Water drainage is smpoth.
Place strong enough to support unit weight.
Place where inclination is not evident on ceiling.
Enough space for mainenance.
Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.)
Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radop. This is helpful
to avoid picture disturbance and noise. (Even if 1 m iskept, noise can still appear if radio wave is strong)
(2) Ceiling height
Indoor unit can be installed on ceiling of 2.5-3m in height. (Refer to Foeld setting and Installation Manual of
ornament panel.)
(3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take necessary
measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern
for place need be reinforced)
<Don't discard any accessories until comp>
Installation space
(For series 142, 182 )
Air inlet
Air outlet
1500
Air outlet
(For series 242, 282, 362, 422, 482, 602 )
2500 Over
Air inlet
Air outlet
Air outlet
1500 Over
H
1500
260
1500 Over
310
260
Air inlet
Air inlet
1500 Over
Air outlet
1500 Over
20
Installation Procedure
3
3. PREPARATION FOR THE INSTALLATION
(1) Position of ceiling opening between unit and suspending bolt.
(For series 142, 182 )
Indoor unit 570mm
Ceiling opening 650mm
Ornament panel 700mm
Distance between
suspending bolts 535mm
Indoor unit 570mm
Ceiling opening 650mm
Ornament panel 700mm
Overlap between ceiling and
ornament panel shall be 25mm
Note:
Dimension of ceiling opening marked with * can be as
large as 910mm, but the matching part of ceiling with
ornament panel shall be over 20mm.
20 Over
(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.)
Refer to paper pattern for dimension of ceiling hole.
Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation.
Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration.
Contact your real estate dealer
(3) Install a suspending bolt.
(Use a M10 bolt)
To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new
ceiling, use built-in type bolt or parts prepared in the field.
Before going on installing adjust space between ceiling.
060710**
060608**
(Distance between suspending bolts)
860(Ceiling opening)
780
<Installation example>
Roof
Anchor bolt
Long nut
50~100
Note: All the above mentioned parts shall be prepared in field.
Suspending bolt
Ceiling
21
Installation Procedure
4
4. INSTALLATION OF INDOOR UNIT
In the case of new ceiling
(1) Install unit temporally
Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.
(2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details.
Center of the hole is marked on the paper pattern.
Center of the unit is marked on the card in the unit and on the paper pattern.
Mount paper pattern onto unit using 3 screws . Fix the corner of the drain pan at piping outlet.
< After installation on the ceiling >
(3) Adjust unit to its right position. (Refer to preparation for the installation-(1))
(4) Check unit's horizontal level.
Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level
using horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage,
problem may occur on floating switch, causing water leakage.)
(5) Remove the washer mounlting , and tighten the nut above.
(6) Remove the paper pattern.
In the case of ceiling already exists
(1) Install unit temporally
Put suspending bracket on the suspending bolt.
Be sure to use nut and washer at both ends
of the bracket. Fix the bracket firmly.
(2) Adjust the height and position of the unit.
(Refer to preparation for the installation (1) ).
(3) Proceed with and of "In the case of new ceiling".
5
2
4
3
6
Nut (Prepare in feild)
Washer (Prepared in feild)
Suspending bolts
Fasten (double nuts)
Level
Polythene pipe
Center of ceiling hole Paper pattern
Screw (accessory)
[Fix the paper pattern]
22
Insert
Washer fixing pad
(prepared in feild)
[ secure the washer firmly]
Screws at the piping outlet is fixed at the
corner of drain pan.
Paper pattern
Screw (accessory)
5
Installation Procedure
5
5. REFRIGERANT PIPING
(As for outdoor piping, please refer to installation Manual of outdoor unit.)
Outdoor is precharged with refrigerant.
Be sure to see the Fig.1, when connecting and removing piping from unit.
For the size of the flare nut, please refer to Table 1.
Apply refrigerant oil at both inside and outsid of lflare nut. Tighten it band tight 3-4 turns then tighten it.
Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage).
Check piping joints for gas leakage. Insulate piping as shown in Fig. below.
Cover joint of gas piping and insulator with seal.
Apple refrigerant oil
Torque spanner
Piping joing
Flare nut
6
6. INSTALLATION OF WATER DRAINAGE PIPE
Medium size seal pad 11 (accessory)
(Cover the piping joint
with seal pad.)
Clamp 3
spanner
Gas pipe
Liquid pipe
7
Insulator (accessory)
(For liquid pipe)
Insulator (accessory)
(For gas pipe)
8
7
Table 1
Pipe
size
6.35
9.52
15.88
19.05
Tighten
torque
1420~1720N.cm
(144~176kgf.cm)
3270~3990N.cm
(333~407kgf.cm)
6180~7540N.cm
(630~770kgf.cm)
9720~11860N.cm
(990~1210kgf.cm)
A(mm)
8.3~8.7
12.0~12.4
18.6~19.0
22.9~23.3
Flare shape
45
0.5
90
(1) Install water drainage pipe
Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm)
Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.
If downward slope can't be made, take other measures to lift it up.
Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.
1-1.5m
R0.4 ~ 0.8
2
A
Slope over 1/100
Use the self-provided stiff pipe and clamp with unit. Insert water pipe into water plug until it reaches the
1
white tape. Tighten the clip until head of the screw is less than 4mm from hose.
Wind the drain hose to the clip using seal pad 9 .
Insulate drain hose in the room.
Clamp
Tape (White)
Self-provided stiff pipe
<Cautions for the drain water lifting pipe>
Clamp
(accessory)
Large size seal pad
(accessory)
4mm below
10
Installation height shall be less than 280mm.
There should be a right angle with unit, 300mm from unit.
Suspending bracket
1~1.5m
drain water lifting pipe
Clamp
(accessory)
280 below
220
500 below
Self-provided stiff pipe
(accessory)
75 below
500 below
(Note)
Drain hose
(accessory)
300mm below
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.
If several water hoses join together, do as per following proceedures.
Connect water hoses with a T joint.
Over 100
Specifieations of the water hoses shall meet the requirements for the unit running.
23
Installation Procedure
(For series 142, 182 )
Check whether indoor unit is horizontal with leveler or polythene pipe filled with water , and check
that the dimension of the ceiling opening is correct. Take off the lever gauge before install the ornament
panel.
Fasten the screws to make the height difference between the two sides of indoor unit less than 5mm.
First fix it with screws temporally.
Fasten the two temporally fixing screws
and other two, and tighten the four screws.
Connect the wires of synchro-motor.
Connect the wire of signal.
If no response of remote controller,
check whether the wiring is correct,
restart remote controller 10 seconds
after shut off power supply.
Electric control box
(For series 142, 182 )
POWER SUPPLY: 1PH,220-230V~,50Hz
INDOOR UNIT
TERMINAL BLOCK
OUTDOOR UNIT
TERMINAL BLOCK
<Limits of panel board installation>
Install the panel board in the direction shown in the figure.
The incorrect direction will result in water leakage,
meanwhile swing and signal receiving are displayed that
cannot be connected.
123LN
123
24
Installation Procedure
(2) Check if water drainage is smooth after installation.
(For series 242, 282, 362, 422, 482, 602 )
Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.
After wiring
Check water drainage in cooling operation.
When wiring is not complete
Remove cover of control box, connect 1PH power to terminal 1 and 2 on terminal block.,use remote
controller to operate the unit.
Note, in this operation, fan will be running.
Upon confirmation of a smooth water drainage, be sure to cut off power supply.
Method of water charging
Self-provided stiff pipe
Water drainage port for
maintenance
(Drain water from
this hole)
100mm
Watering can of plastic
pipe should be about
100 mm long
(For series 242, 282 )
OUTDOOR UNIT
TERMINAL BLOCK
POWER SUPPLY:
Maintenance
Inspecting hole
Charge water from
inspecting hole
Charge water from
air outlet
INDOOR UNIT
TERMINAL BLOCK
L N
1PH,220-230V~,50Hz
Connect with
outdoor unit
1 2 3
1 2 3
1 2 3 D
Y/G
Y/G
Terminal block
PCB on
indoor unit
Terminal block
Cover of controll box
(For series 362, 422, 482, 602 )
OUTDOOR UNIT
TERMINAL BLOCK
INDOOR UNIT
TERMINAL BLOCK
R S T
POWER SUPPLY:
380-400V,3N~,50Hz
25
1 2 3
N 1 2 3
Y/G
Y/G
Installation Procedure
7. WIRING
7
All supplied parts. materials and wiring operation must in appliance with
local code and regulations.
Use copper wire only.
When make wiring, please refer to wiring diagram also.
All wiring work must be done by qualified electricians.
A circuit breaker must be installed, which can cut power supply to all system.
See Installation Manual of outdoor unit for specifications of wires, circuit breaker, switches and wiring etc.
Connecting of unit
Remove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires,
tighten clamp A. Connect wires of correct pole to the terminal block inside.
Wind seal 12 around wires. (Be sure to do that, or, dew may occur).
Upon connecting, replace control box cover (1) and (2).
Terminal block
Cover of control box(2)
*
Grounding lead
Rubber tube A
Cover of control box(1)
<<WARNING>>
Obscrve the following when connecting power supply
terminal block:
Don't connect wires of different specifications to the same
terminal block.
(Loose wire may cause overheating of circuit)
Connect wires of same specifications as shown in right Fig.
Connect wires of the
same specifications
at two sides.
Don't fail to seal it, or water may come in.
Rubber tube
Attach seal pad
Note: Have it sealed, leaving no space.
Seal pad (small size )
(Wind around wire)
In
Out
Field wiring
Don't connect wires of
the same specifications
at one side.
Don't connect wires
of the different
specifications.
12
8
8. WIRING EXAMPLE
As for outdoor unit circuit, please see Installation Manual of outdoor unit.
Note: All electric wires have their own poles, poles must match that on terminal block.
9
9. INSTALLATION OF ORNAMENT PANEL
Cautions for the installation
Be sure to show customers Operation Manual and guide them how to operate unit
correctly. Before installation. read also the Installation Manual of indoor unit.
With this ornament , 2 or 3 air flow direction is not available.
Suitable height is 3 m.
Accessory
Pad
Pad
1. Prepare ornament panel Handling of ornament panel
Ornament panel shall not be placed face down or against wall, neither
on an uneven object.
Don' t bend carelessly the swing flap, or, problem may occur.
(1)
Remove air inlet grill from ornament panel *
1
Push in the bar on inlet grill and lift it up. (Refer to Fig. 1)
Lift it up for about 45 degree and remove it from ornament. Tear off adhesive
2
tape fixing air filter on the back of the air inlet grill. (Refer to Fig. 2)
(2)
Remove cover plate at corner
Tear off the adhesive tape, and slide it off. (Refer to Fig. 3)
26
Bar
Fig. 1
45
Slide
Adbesive tape
Fig. 2
Fig. 3
Installation Procedure
2. Mounting on high ceiling
(1) Ornament panel can be mounted on ceiling as high as 3 m.
(2) Please install pad as accessary.
Cut open the pad along cutting ling. Use part a only and discard part b . (Refer to Fig. 4)
1
Install part a of the pad on the place shown in Fig. 5. Refer to Fig. 6.
2
Cutting line
Place it on the frame.
Leave no space.
a
50
Fig. 4
Part a of the pad
Swing flap motor
100
b
(3)Wiring on ornament panel
Connecting of wiring of the swing
flap motor on ornament panel. (2 places)
(Refer to Fit . 10)
If connecting is not made, error code
(A7) appears on remote controller. So,
make proper connecting.
3. Install ornament panel on indoor unit.
For indoor unit installation, please
refer to Installation Manual.
(1)
As shown in Fig.7,match the position of swing
flap motor with that of the indoor unit piping hole ,
so that ormament panel can be placed on to indoor
unit.
(2)
Installation of ornament panel
1
Place the holding ring on swing flao motor side
teporarily on hooks of the indoor unit. (2 pcs)
2
Put the other two holding rings on the hooks at
side of the indoor unit. (Care should be taken not to
push wiring of swing flap motor into seals).
3
Screw in all 4 screws under holding ring for about
15mm. (Pancl will rise).
4
Adjust the ornament panel as per Fig. 7 to cover
opening on the ceiling.
5
Tighten screws to redrce the thickness of seals
between ornament and indoor unit to 5-8mm.
Caution
If screws are not tighten tight,
problems in Fig, 8 might occur.
Tighten screws properly.
If there are still space
after tightening of screws,
please readjust the height
Gas leakage.
Gas leakage
from roof.
of indoor unit.
(Refer to Fig. 9)
Fig. 5
Side of indoor unit
both
3
Part a of the pad
2
Swing flap motor
Indoor unit
Ceiling material
If indoor unit is at horizontal level and water
drainage is smooth, then, indoor unit height
can be adjusted throrgh holes at corners of
ornament panel.
Fig. 6
Holding ring
Piping hole position
4
Fig. 7
Side of ornament panel
Fig. 10
Wiring diagram
1
Seal
5 _ 8mm
Ornament panel
Hook
2
Contamination
Mist exists and drop down.
Fig. 8
Leave no space.
Fig. 9
27
Installation Procedure
4. Installation of inlet grill and cover plate
(1)
Installation of inlet grill
Install in reversed order of "Prepare ornament pandl".
Inlet grill can be adjusted into four directions by turning inlet grill. Inlet grill position can be adjusted as
per customers request.
When installing inlet grill, take care not to twist wiring of swing flap motor.
(2)
Install cover plate on the corner
1
As shown in Fig. 11 tie the
cover plate onto the bolt on
ornament plate.
2
Install cover plate onto
ornament plate.
(Refer to Fig. 12)
Fig. 11
Pay special care to the following and check after installation
Slide all five hold rings
to let them drop in holes
on ornament plate,
Fig. 12
Item to the checked
Is indoor unit firmly installed?
Is gas leakage check performed?
Is unit properly insulated?
Is water drainage smooth?
Is power voltage meet that stipulated on the nameplate?
Is wiring and piping correctly arranged?
Is unit safely grounded?
Is wire size correct?
Are there any obstacles on air inlet and outlet grill of
indoor and outdoor unit?
Is record made for piping length and refrigerant
charging amount?
Unproper installation may cause
Unit might fall down, make vibration or noise.
This may lead to gas shortage.
Dew or water drop may occur.
Dew or water drop may occur.
Problem may occur or parts got burned.
Problem may occur or parts got burned.
There might be a danger of electric shock.
Problem may occur or parts got burned.
This may cause poor cooling.
It is hard to control refrigerant charging
amount.
ATTENTION: after finishing installation,confirm no refrigerant leakage.
Check
28
HAIER GROUP
Qingdao Haier Air Conditioner Electric Co., Ltd.
Address: Haier Garden ,Qianwangang Road , Economic Development Zone,
Qingdao ,Shandong 266500, P.R.China
Web Site: http://www.haier.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.