Rated Maximum Minimum
DB C
WB C
DB C
WB C
DB C
WB C
DB C
WB C
27 32 18
19 23 14
35 43 10
24 26 6
20 27 15
14.5 -- --
7 24 -7
6 18 --
AF072XCEAA
AF092XCEAA
AF122XCEAA
AF142XCEAA
AS072XCEAA
AS092XCEAA
AS122XCEAA
AS142XCEAA
z 1 z
Chff^j\bZe Abj Chg]blbhg^j
2.DESCRIPTION OF PRODUCTS & FEATURES
2.1. Products code explanation
A D 14 2 X L E A A
Climate type: T1 standard test condition
Design number (A stands for design sequence, Fixed
frequency type)
Product type: A stands for heat pump type, refrigerant is R22
B stands for heat pump type, refrigerant is R407C
E stands for heat pump type, refrigerant is R410
Q stands for cool only type, refrigerant is R410A
Design number,L means low pressure type
Product series: X stands for multi split units
Applicable voltage: 2 stands for 220~230V/50Hz,
4 stands for 220V/60Hz,N stand for 380~400VAC/50Hz
Cooling / Heating capacity,14=14000BTU/h
Product type : “B” stands for cassette type, “C” stands for
convertible type, ”D” stands for duct, “S” stands for wall
mounted type, ”Q” stands for chiller system, "E" stands for
ceiling concealed type, “U” stands for outdoor unit
Air Conditioner
A
2.2 Product character
2.2.1 Phylogeny
E-Multi(R410A) series is multi split ON/OFF type series, developed based on Free Multi (R407C).
2.2.2 Operating individually and operating simultaneously
The unit can realize individual operation which can control one unit running, stop, and adjusting running mode.
Also the unit can operate simultaneously which control multi indoor units at same time.
2.2.3 Variable quantity of indoor unit
If you want to add or reduce the quantity of indoor units (of course the match must correspond with the design),
it can meet your need at any time. More convenient, more random.
2.2.4 Universal outdoor unit, multiform indoor unit
We realize universal outdoor unit, and 6 kinds of indoor unit, choose freely according to customer
indoor decoration, more stylish and more beautiful
2.2.5 The total capacity of indoor unit can be more than that of outdoor unit.
When all the indoor units are running at the same time, the actual capacity of every indoor unit is proportional
according to outdoor capacity.
2.2.6 Long distribution pipe and high drop
The distance of outdoor and indoor can be max. 15m, and the drop between indoor and outdoor can be max.
up to 5m, consequently, the installation can be more free, and can meet various need of the customer.
2.2.7 Duct type unit be equipped with high efficiency filter, and its high static pressure can be up to
30Pa, running more silent, making room air more comfortable and more clean.
2.2.8 Auto-check function
The unit can display the malfunction codes on the control board by using advanced auto-check technology
,convenient for user find and dwell with the abnormal running.
2.2.9 Auto
restart function (optional )
All indoor units have auto-restart function. When the power supply cut off suddenly, the unit will automatically
recover the previous running mode once the power supply is on
2.2.11 universal PCB
Except AB072-142XCEAA types, the other units' PCBs are completely same with Free Multi
R407C types, so it's easy to get spare parts ,install Multi R410a and solve problems.
E-
3. Speci
fication
3.1.Outdoor Units
Model
Capacity
Cooling
Heating
Electrical parameters
Power supply
Power input
EER/COP
Performance
Air flow
Noise Level
Installation
External
dimensions(WxHxD)
Shipping
dimensions(WxHxD)
Cooling
Heating
H
H/M/L
Btu/h
kw
Btu/h
kw
Ph/V/Hz
kw
kw
m3/h
dB(A)
mm
mm
AU282XHEAA
2800042000
8.2
3100045000
9.0
230VAC
1PH
2720
2630
3.01/3.423.01/3.42
38006000
5660
1068x340x840
1100x410x9901095x410x1400
AU422XIEAA
12.3
13.0
50Hz
4.08
3.8
948x340x1250
Net weight/Shipping
weight
Compressor
type
Refrigerant type
Refrigerant liquid pipe
Refrigerant gas pipe
Max pipe length
Max drop between
Console type units can be controlled by remote controller(YR-H71), centrol controller YCZA001 and weekly timer YCS-A001, but in central controller installation, it need detector YCJA001, console type c
ouldn't be connected with controller YR-E12
z 6 z
3.5. Wall mounted type
Capacity
Cooling
Heating
Electrical parameters
Power supply
Performance
Air flow
Noise Level
l
Installation
External
dimensions(WxHxD)
Shipping
dimensions(WxHxD)
Net weight/Shipping
weight
Refrigerant liquid pipe
Refrigerant gas pipe
Control
Static pressure
- Multi R410a wall mounted indoor units use same PCB with R407C, they only can be controlled
E
by remote controller, in central control or weekly timer installation, it need detector to set address.
Model
Ph/V/Hz
H/M/L
H/M/L
Wired /Infrared
Btu/h
kw
Btu/h
kw
m3/h
dB(A)
mm
mm
kg
mm
mm
Pa
AS072XCEAAAS092XCEAAAS122XCEAAAS142XCEAA
700090001200013000
2.05
735095001300014500
2.15
350/300/240
40/35/31
795x197x265
Chff^j\bZe Abj Chg]blbhg^j
2.63.53.8
2.83.8
1PH
230VAC
880 315 3
// 30
7.6/10.6
6.35
9.52
Infrared(YR-H71)
0
50Hz
500/400/350
44/40/35
795x197x265
4.25
4. Net dimensions of indoor and outdoor
4.1.AU282XHEAA
340
380
416
185
830
580
950
1068
z 7 z
4.2. Outdoor unit: AU422XIEAA
screw hole (M10)
Chff^j\bZe Abj Chg]blbhg^j
Terminal block
z 8 z
4.3. Cassette Type AB07-142XCEAA
Distance between
suspending bolts 535mm
Chff^j\bZe Abj Chg]blbhg^j
Indoor unit 570mm
Ceiling opening 650mm
Ornament panel 700mm
4.4. Wall Mounted Type AS07-142XCEAA
c
model
A S 0 7 2 X C E A A A S 0 9 2 X C EA
A
S 1 2 2 X CEEEEA
A A S 1 4 2 X C E A A
E
A
z 9 z
a
7
9 5
bc
2 6 5
1 8 2
4.5. Model: AB212XCEAA
Chff^j\bZe Abj Chg]blbhg^j
z 10 z
4.6. Duct Type AD***XLEAA
Figure showing installation dimensions: (unit:mm)
Chff^j\bZe Abj Chg]blbhg^j
Model
Series 07-09
Series 12-14
Series 18-21
a
bc
615
648125
770
804125
1060
1120125
450
450
450
d
220
220
220
e
80
80
80
g
225
225
225
i
100
100
100
f
i
4.7. Console Type AF***XCEAA
720
630
205
z 11 z
5.Part Name
5.1 Cassette Type AB07-142XCEAA
Swing louver
(Air flow direction can be adjusted by using
the SWING button on the remote controller)
Operating Control Panel
Air Inlet Grille
Air Filter
(Inside of the Inlet Grille)
Chff^j\bZe Abj Chg]blbhg^j
Operating Control Panel
2
1
COMP TIMER OPER POWER
3
4
6
5
5.2. Cassette Type AB212XCEAA
Discharge unit (built in)
In cooling operation,
to discharge the
water from inside the
room.
Outlet
Air filter
(located in the suction grill)
1
Remote receiver
2
Compressor Lamp
3
TIMER Lamp
4
OPERATION Lamp
Power Lamp
5
6
Emergency switch
Drain Hose
Swing fender
(located in the outlet)
Refrigerant pipe
Cable line
Earthing line
Suction grill
z 12 z
Chff^j\bZe Abj Chg]blbhg^j
5.3 Duct type AD***XLEAA
NOTE
When the unit have the Return air box (see the following picture)
when shipping from the factory and they are of back-side return air
type. During the installation, the unit also can be changed to a Downside Return air according to the user's need.
Note: For wall mounted unit, please refer to the data on its nameplate.
Chff^j\bZeAbjChg]blbhg^j
1 TO 2(except for 21000BTU/h units)
Outdoor unit
Indoor units
A2B2
A1
A2
B1
B2
Communication Wire connection:
1. The indoor unit whose liquid pipe is connected to A1 in A system is called unit A1, its communication
wire of A1(3)、 A1(4) should be connected to A1(P)、A1(Q) respectively.
2. The indoor unit whose liquid pipe is connected to A2 in A system is called unit A2, its communication
wire of A2(3) 、A2(4) should be connected to A2(P)、A2(Q) respectively.
3. The indoor unit whose liquid pipe is connected to B1 in B system is called unit B1, its communication
wire of B1(3) 、B1(4) should be connected to B1(P)、B1(Q) respectively.
4. The indoor unit whose liquid pipe is connected to B2 in B system is called unit B2, its communication
wire of B2(3) 、B2(4) should be connected to B2(P)、B2(Q) respectively.
Note: Because the customers themselves matcTh the communication wire, and the P and Q
are nonpolar, the customers must use shielded communication wires.
Special Installation Guide to 21000BTU indoor units on Free Multi system
Only for outdoor unit AU422XIEAA working with 21000BTU indoor units
1. Special accessory pipes for 21000BTU indoor units:
A B
Changing pipe (3/8-1/2) Collecting pipe (1/4-3/8)
φ9.52 φ12.7
z 21 z
φ6.35
φ6.35
φ9.52
2. Pipe installations:
Chff^j\bZe Abj Chg]blbhg^j
21000BTU indoor unit
A1
A2
B1
B2
Gas pipe φ12.7
Liquid pipe
Gas pipe
Liquid pipe
φ9.52
φ12.7
φ9.52
21000BTU indoor unit
Note: Though AU422XIEAA can match with the R407C free multi indoor unit, we do not
recommend so. Because that will not only lower the capacity,also the changing pipe
0010759292 will be required for all R407C free multi indoor unit when installation.
3. Outdoor wiring diagram should be changed as the following:
Coil of solenoid vavle A2
should be changed to
connected with CN29.
Coil of solenoid vavle B2
should be changed to
connected with CN23.
By-pass vavle on both
system A and system B
should be pulled out and
not connected.
z 22 z
Chff^j\bZe Abj Chg]blbhg^j
8. Installation Procedure
8.1.1. Selection of Installation Place (For AB072-142XCEAA)
(1) Place above the ceiling where it is enough space to arrange the unit.
(2) Place where the drainage pipe can be arranged well.
(3) Place where inlet and outlet air of indoor and outdoor unit will not be blocked.
(4) Do not expose the unit to the place with heavy oil or moisture (e.g.kitchen and workshop).
(5) Do not set the unit in the place where destructive gas (such as sulfuric acid gas) or pungent
gas (thinner and gasoline) concentrates and retains.
(6) Place strong enough to support the unit .
(7) No expensive articles such as television and piano below indoor unit.
(8) Enough space for maintenance.
(9) Place more than 1m away from television and radio to avoid disturbing television and radio.
(10) Easy for maintenance.
1.5m
Air outlet
2.5m Over
Air inlet
Air outlet
1.5m
( 1) Position of ceiling openin g between unit and suspending bolt (front view of unit).
Power supply wire parameters: H05RN-f 3G(0.75~1.5)mm
Signal wire parameters: H05RN-F 2x0.75mm
The signal wire must be shielded wire.
2
3
2
Wiring methods:
1.Wiring method of ring terminal
For connecting line which end is a ring,its wiring method
as shown in the right figure: remove wiring screw and pass
it through the end ring of connecting line,then connect it to
the terminal block and tighten screw.
2. Wiring method of straight terminal
For connecting line which end is not a ring, its wiring method
as follows: loosen wiring screw ans insert the end of connecting
line totally into the terminal block,then tighten the screw and pull
the connecting line slightly to confirm that it is clamped firmly.
Wiring method of ring terminal
Correct crimp
connection of wire
Terminal block
Crimp connection
clamp
Incorrect crimp
connection of wire
z 23 z
(3) Install a suspending bolt
To support the unit weight ,anchor bolt should be used in the case of
the existing ceiling. For new ceiling, use flush-in type bolt, built-in
type bolt or parts pretared in the field.
Before going on installing, adjust the distance to ceiling.
Ceiling
Note: All the above mentioned parts shall be prepared in feild,
the diameter of suspending bolt is M10
Chff^j\bZe Abj Chg]blbhg^j
Roof
Anchor bolt
Long nut or thread
Suspending bilt M10
8.1.3 . Installation of indoor unit
<Installation Example>
In case of no ceiling
Install unit temporarily
Put suspending bracket on the suspending bolt to hang the unit up. Be sure to use nut and
washer at both end of the breaket to secure firmly.
After installation on the ceiling
(1) Adjust unit to its right position (Refer to preparation for installation-(1))
(2)Check that unit is horizontal.
Water pump and floating switch is installed inside indoor unit,check four corners of the unit for
its lever using horizontal comparator or PVC tube with water.(If unit is tilting against the direction
of water drainage,problem may occur on floating water leakage.)
Nut (Prepare in feild)
Washer (Prepared in feild)
In the case of existing ceiling
(1)Install unit temporarily
Put suspending bracket on the suspending bolt to hang the
unit up.Be sure to use nut and washer at both end of the
bracket to secure it firmly.
(2)Adjust the height and position of the unit.
(3)Proceed with procedure (4) of " In the case of no ceiling "
Fasten (double nuts)
Suspending bolts
leveler
Polythene pipe
Insert
Washer fixing pad
(prepared in feild)
[ secure the washer firmly]
z 24 z
Chff^j\bZe Abj Chg]blbhg^j
8.1.4. In s t al la t io n o f w at e r d ra i na ge pi p e
(1) Install water drainage pipe
Pipe diameter shall be equal or larger than that of connecting pipe (Pipe of polythene; size:
25mm; O.D.: 32mm )
Drainpipe should be short, with a downward slope at least 1/100 to prevent air bag from forming.
If downward slope of drainpipe cannot be made,lifting pipe shall be installed.
Keep a distance of 1-1.5m between suspending bolts, to make water hose straight.
1-1.5m
slope over 1/100
Use the drainage hose and clip provided with unit.
Insert water pipe into water plug until it reaches the white tape.
Tighten the clip until head of the screw is less than 4mm from hose.
Wind the drainage hose to the clip using seal pad for heat insulation.
Insulate drainage hose in the room.
Large size seal pad
Clip
Clip
(accessory)
Tape(white)
Draingage hose
4mm below
8.1.6. C au t io n s f o r t he w a te r d r ai n ag e li f t in g p ip e
Installation height of water drainage lifting pipe shall be less than 280mm
There should be a right angle with unit ,300mm from unit.
300mm below
Drainage hose
Clip
Water drainage
lifting pipe
< Note >
The slope of water drainage hose shall be within 75mm , make the drainage plug not to bear
excessive force.
If several water hoses join together, of as per following procedures.
Suspending bracket
1-1.5m
220mm
280mm unter
Slope below 1/100
Drainage hose
Connection drainage hose with a T-joint
Specifications of the selected drainage hoses shall meet the requirements for the unit running
z 25z
Chff^j\bZe Abj Chg]blbhg^j
8.1.6. In s t al la t io n o f O r na m e nt Pa n el
Install ornament panel on indoor unit
(1) Check whether indoor unit is horizontal with leveler or polythene pipe filled with water , and
check that the dimension of the ceiling opening is correct. Take off the lever gauge before
installing the ornament panel.
(2) Fasten the screws to make the height difference between the two sides of indoor unit less than
5mm.
(3) Firstly fix it with screws temporarily.
(4) Fasten the two temporarily fixing screws and other two, and tighten the four screws.
(5) Connect the wires of synchro-motor.
(6) Connect the wire of signal.
(7) If no response of remote controller,check whether the wiring is correct,restart remote controller
10 seconds after shut off power supply.
Electric control box
Panel limitation board installation
(1)Install the panel board in the direction shown in
the figure.
(2)The incorrect direction will result in water leakage,
meanwhile swing and signal receiving are displayed
that cannot be connected.
Piping Connection
Flare connection
Indoor
Unit
Gas pipe
Liquid
pipe
Flare connection
3-way valve
Outdoor
unit
2-way valve
z 26z
Chff^j\bZe Abj Chg]blbhg^j
8.2.1. Installation procedure (For AB212XCEAA)
(1) Installation place shall meet the following and agreed by customers:
Place where proper air flow can be ensured.
No block to air flow.
Water drainage is smpoth.
Place strong enough to support unit weight.
Place where inclination is not evident on ceiling.
Enough space for mainenance.
Indoor and outdoor unit piping length is within limit. (Refer to Installation Manual for outdoor unit.)
Indoor and outdoor unit, power cable, inter unit cable are at least 1 m away fromT.V. radop. This is helpful
to avoid picture disturbance and noise. (Even if 1 m iskept, noise can still appear if radio wave is strong)
(2) Ceiling height
Indoor unit can be installed on ceiling of 2.5-3m in height. (Refer to Foeld setting and Installation Manual of
ornament panel.)
(3) Install suspending bolt. Check if the installation place is strong enough to hold weight. Take necessary
measures in case it is not safe. (Distance between holes are marked on paper pattern. Refer to paper pattern
for place need be reinforced)
Air outlet
1500mm Over
Air inlet
Air outlet
1500mm Over
(2) Cut an opening in ceiling for installation if necessary. (when ceiling already exists.)
Refer to paper pattern for dimension of ceiling hole.
Connect all pipings (refrigerant, water drainage), wirings (inter unit cable) to indoor unit, before installation.
Cut a hole in ceiling, may be a frame should be used to ensure a smooth surface and to prevent vibration.
Contact your real estate dealer
(3) Install a suspending bolt.
(Use a M10 bolt)
To support the unit weight, anchor bolt shall be used in the case of already exists ceiling. For new
ceiling, use built-in type bolt or parts prepared in the field.
Before going on installing adjust space between ceiling.
<Installation example>
Roof
Anchor bolt
Long nut
Suspending bolt
Ceiling
Note: All the above mentioned parts shall be prepared in field.
z 27 z
Chff^j\bZe Abj Chg]blbhg^j
4
4. INSTALLATION OF INDOOR UNIT
In the case of new ceiling
(1) Install unit temporally
Put suspending bracket on the suspending bolt. Be sure to use nut and washer at both ends of the bracket.
(2) As for the dimensions of ceiling hole, see paper pattern. Ask your real estate dealer for details.
Center of the hole is marked on the paper pattern.
Center of the unit is marked on the card in the unit and on the paper pattern.
Mount paper pattern onto unit using 3 screws . Fix the corner of the drain pan at piping outlet.
< After installation on the ceiling >
(3) Adjust unit to its right position. (Refer to preparation for the installation-(1))
(4) Check unit's horizontal level.
Watert pump and flating switch is installed inside indoor unit, check four corners of the unit for its level
using horizontal compartor or PVC tube with water. (If unit is tilting against the direction of water drainage,
problem may occur on floating switch, causing water leakage.)
(5) Remove the washer mounlting , and tighten the nut above.
(6) Remove the paper pattern.
In the case of ceiling already exists
(1) Install unit temporally
Put suspending bracket on the suspending bolt.
Be sure to use nut and washer at both ends
of the bracket. Fix the bracket firmly.
(2) Adjust the height and position of the unit.
(Refer to preparation for the installation (1) ).
(3) Proceed with and of "In the case of new ceiling".
5
2
4
3
6
Nut (Prepare in feild)
Washer (Prepared in feild)
Suspending bolts
Fasten (double nuts)
Level
Center of ceiling hole Paper pattern
Screw (accessory)
[Fix the paper pattern]
Insert
Washer fixing pad
(prepared in feild)
[ secure the washer firmly]
Polythene pipe
Screws at the piping outlet is fixed at the corner
of drain pan.
Paper pattern
5
Screw (accessory)
z 28z
Chff^j\bZe Abj Chg]blbhg^j
5
5. REFRIGERANT PIPING
(As for outdoor piping, please refer to installation Manual of outdoor unit.)
Outdoor is precharged with refrigerant.
Be sure to see the Fig.1, when connecting and removing piping from unit.
For the size of the flare nut, please refer to Table 1.
Apply refrigerant oil at both inside and outsid of lflare nut. Tighten it band tight 3-4 turns then tighten it.
Use torque specified in Table 1. (Too much force may damage flare nut, causing gas leakage).
Check piping joints for gas leakage. Insulate piping as shown in Fig. below.
Cover joint of gas piping and insulator with seal.
Apple refrigerant oil
Torque spanner
Piping joing
Flare nut
6
6. INSTALLATION OF WATER DRAINAGE PIPE
Medium size seal pad 11 (accessory)
(Cover the piping joint
with seal pad.)
Clamp 3
spanner
Gas pipe
Liquid pipe
7
Insulator (accessory)
(For liquid pipe)
Insulator (accessory)
(For gas pipe)
Table 1
8
7
Pipe
size
1420~1720N.cm
6.35
(144~176kgf.cm)
3270~3990N.cm
9.52
(333~407kgf.cm)
12.7
(504~616kgf.cm)
15.88
(630~770kgf.cm)
19.05
Tighten
torque
4950~6030N.cm
6180~7540N.cm
9720~11860N.cm
(990~1210kgf.cm)
A(mm)
8.3~8.7
12.0~12.4
15.4~15.8
18.6~19.0
22.9~23.3
Flare shape
(1) Install water drainage pipe
Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm)
Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.
If downward slope can't be made, take other measures to lift it up.
Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.
1-1.5m
R0.4 ~ 0.8
Slope over 1/100
Use the self-provided stiff pipe and clamp with unit. Insert water pipe into water plug until it reaches the
1
white tape. Tighten the clip until head of the screw is less than 4mm from hose.
Wind the drain hose to the clip using seal pad 9 .
Insulate drain hose in the room.
Tape (White)
Clamp
Self-provided stiff pipe
<Cautions for the drain water lifting pipe
Clamp
(accessory)
Large size seal pad
(accessory)
4mm below
10
Installation height shall be less than 280mm.
There should be a right angle with unit, 300mm from unit.
Suspending bracket
1~1.5m
drain water lifting pipe
Clamp
(accessory)
Self-provided stiff pipe
(accessory)
(Note)
Drain hose
(accessory)
300mm below
The slope of water drain hose (1) shall be within 75mm, don't apply too much force on it.
If several water hoses join together, do as per following proceedures.
Connect water hoses with a T joint.
Specifieations of the water hoses shall meet the requirements for the unit running.
z 29 z
(2) Check if water drainage is smooth after installation.
Charge, through air outlet or inspecting hole, 1200ccd water to see water drainage.
After wiring
Check water drainage in cooling operation.
When wiring is not complete
Remove cover of control box, short connect "CHECK" terminal of the indoor unit, which is on the uper
part of indoor unit PCB. Connect 1PH power to terminal 1 and 2 on terminal block.
Note, in this operation, fan will be running.
Upon confirmation of a smooth water drainage, be sure to cut off power supply
and remove short connection of "CHECK" terminal.
Chff^j\bZe Abj Chg]blbhg^j
Maintenance
Inspecting hole
Method of water charging
Self-provided stiff pipe
Water drainage port for
maintenance
(Drain water from
this hole)
100mm
Watering can of plastic
pipe should be about
100 mm long
PCB on
indoor unit
Terminal block
Charge water from
inspecting hole
Charge water from
air outlet
z 30z
Cover of controll box
Chff^j\bZe Abj Chg]blbhg^j
7
7. WIRING
All supplied parts. materials and wiring operation must in appliance with
local code and regulations.
Use copper wire only.
When make wiring, please refer to wiring diagram also.
All wiring work must be done by qualified electricians.
A circuit breaker must be installed, which can cut power supply to all system.
See Installation Manual of outdoor unit for specifications of wires, circuit breaker, switches and wiring etc.
Connecting of unit
Remove cover of switch box (1) , drag wires into rubber tube A, then, after proper wiring with other wires,
tighten clamp A. Connect wires of correct pole to the terminal block inside.
12
Wind seal
Upon connecting, replace control box cover (1) and (2).
Obscrve the following when connecting power supply
terminal block:
Don't connect wires of different specifications to the same
terminal block.
(Loose wire may cause overheating of circuit)
Connect wires of same specifications as shown in right Fig.
around wires. (Be sure to do that, or, dew may occur).
Terminal block
Grounding lead
Cover of control box(1)
<<WARNING>>
Rubber tube A
Connect wires of the
same specifications
at two sides.
*
Rubber tube
Attach seal pad
Cover of control box(2)
Don't fail to seal it, or water may come in.
Note: Have it sealed, leaving no space.
Seal pad (small size )
Out
Field wiring
(Wind around wire)
Don't connect wires
of the different
specifications.
In
Don't connect wires of
the same specifications
at one side.
12
8
8. WIRING EXAMPLE
As for outdoor unit circuit, please see Installation Manual of outdoor unit.
Note: All electric wires have their own poles, poles must match that on terminal block.
9
9. INSTALLATION OF ORNAMENT PANEL
Cautions for the installation
Be sure to show customers Operation Manual and guide them how to operate unit
correctly. Before installation. read also the Installation Manual of indoor unit.
With this ornament , 2 or 3 air flow direction is not available.
Suitable height is 3 m.
1. Prepare ornament panel Handling of ornament panel
Ornament panel shall not be placed face down or against wall, neither
on an uneven object.
Don' t bend carelessly the swing flap, or, problem may occur.
Remove air inlet grill from ornament panel *
(1)
1
Push in the bar on inlet grill and lift it up. (Refer to Fig. 1)
Lift it up for about 45 degree and remove it from ornament. Tear off adhesive
2
tape fixing air filter on the back of the air inlet grill. (Refer to Fig. 2)
(2)
Remove cover plate at corner
Tear off the adhesive tape, and slide it off. (Refer to Fig. 3)
Bar
Fig. 1
h
45
Slide
Ad esive tape
Fig. 2
Fig. 3
z 31z
Chff^j\bZe Abj Chg]blbhg^j
2. Mounting on high ceiling
(1) Ornament panel can be mounted on ceiling as high as 3 m.
(2) Please install pad as accessary.
Cut open the pad along cutting ling. Use part a only and discard part b . (Refer to Fig. 4)
1
Install part a of the pad on the place shown in Fig. 5. Refer to Fig. 6.
2
Cutting line
Place it on the frame.
Leave no space.
a
50
Fig. 4
Part a of the pad
Swing flap motor
100
b
(3)Wiring on ornament panel
Connecting of wiring of the swing
flap motor on ornament panel. (2 places)
(Refer to Fit . 10)
If connecting is not made, error code
(A7) appears on remote controller. So,
make proper connecting.
3. Install ornament panel on indoor unit.
For indoor unit installation, please
refer to Installation Manual.
(1)
As shown in Fig . 7, match the position of swing
flap motor with that of the indoor unit piping hole ,
so that ormament panel can be placed on to indoor
unit.
(2)
Installation of ornament panel
1
Place the holding ring on swing flao motor side
teporarily on hooks of the indoor unit. (2 pcs)
2
Put the other two holding rings on the hooks at
side of the indoor unit. (Care should be taken not to
push wiring of swing flap motor into seals).
3
Screw in all 4 screws under holding ring for about
15mm. (Pancl will rise).
4
Adjust the ornament panel as per Fig. 7 to cover
opening on the ceiling.
5
Tighten screws to redrce the thickness of seals
between ornament and indoor unit to 5-8mm.
Caution
If screws are not tighten tight,
problems in Fig, 8 might occur.
Tighten screws properly.
If there are still space
after tightening of screws,
please readjust the height
Gas leakage.
Gas leakage
from roof.
of indoor unit.
(Refer to Fig. 9)
Fig. 5
Side of indoor unit
both
Part a of the pad
2
Swing flap motor
3
Indoor unit
Ceiling material
Fig. 6
Side of ornament panel
Fig. 10
Wiring diagram
Holding ring
Piping hole position
4
Fig. 7
If indoor unit is at horizontal level and water
drainage is smooth, then, indoor unit height
can be adjusted throrgh holes at corners of
ornament panel.
1
Seal
5 _ 8mm
Ornament panel
Hook
2
Contamination
Mist exists and drop down.
Fig. 8
Leave no space.
Fig. 9
z 32 z
Chff^j\bZe Abj Chg]blbhg^j
4. Installation of inlet grill and cover plate
(1)
Installation of inlet grill
Install in reversed order of "Prepare ornament pandl".
Inlet grill can be adjusted into four directions by turning inlet grill. Inlet grill position can be adjusted as
per customers request.
When installing inlet grill, take care not to twist wiring of swing flap motor.
(2)
Install cover plate on the corner
1
As shown in Fig. 11 tie the
cover plate onto the bolt on
ornament plate.
2
Install cover plate onto
ornament plate.
(Refer to Fig. 12)
Fig. 11
Pay special care to the following and check after installation
Slide all five hold rings
to let them drop in holes
on ornament plate,
Fig. 12
Item to the checked
Is indoor unit firmly installed?
Is gas leakage check performed?
Is unit properly insulated?
Is water drainage smooth?
Is power voltage meet that stipulated on the nameplate?
Is wiring and piping correctly arranged?
Is unit safely grounded?
Is wire size correct?
Are there any obstacles on air inlet and outlet grill of
indoor and outdoor unit?
Is record made for piping length and refrigerant
charging amount?
Unproper installation may cause
Unit might fall down, make vibration or noise.
This may lead to gas shortage.
Dew or water drop may occur.
Dew or water drop may occur.
Problem may occur or parts got burned.
Problem may occur or parts got burned.
There might be a danger of electric shock.
Problem may occur or parts got burned.
This may cause poor cooling.
It is hard to control refrigerant charging
amount.
Check
- 33 z
Chff^j\bZe Abj Chg]blbhg^j
! Warning
The electric wiring work shall be conducted by qualified electricians according to the installation
instructions. A separate power circuit shall be used. Insufficient power cord amperage or improper
wiring will cause danger of electric shock or fire.
During wiring connection, the power cord shall be of the specified cable and reliably fastened so
that external forces applied to the cable wouldnt transfer to the terminals. Improper connection or
fastening will cause danger of heating, fire etc.The power cord must be fitted with a grounding wire.
Grounding shall be made as specified. Unreliable grounding will cause electric shock. The grounding
wire shall not be connected to the gas pipeline, water pipeline, thunder arrestor and telephone wire
! Caution
A current leakage breaker shall be installed, otherwise it electric shock would happen easily.
The connection method of power cord is "Y" type.
If the power cord is damaged, it must be replaced by the manufacturer or its service center or
similar personnel to avoid risks. The power supply to the indoor unit shall be laid in complying
with the operational instruction manual.
The electric wiring shall avoid contacting with the high temperature part of the piping so as to
prevent the cable insulation melts and cause dangers.
After connected on the terminal block, the wires shall be bent to U form and then fastened with
wire clip.
The control wiring and refrigerant piping may be laid and fastened together.
Before completion of vacuum pumping of the refrigerant pipe system, do not electrify the indoor
unit.
The power cord of the indoor unit and connection wiring between indoor and outdoor units
shall be laid out according to the operational instruction manual of the indoor unit.
The connection of the power cord shall comply with the local regulations.
The power supply wiring connection should meet the local regulation.
After electric installation,power on them to do electric leakage test.
!
!
Wiring connection method : (the wiring diagram is attached inside the machine)
1) Ring terminal connection method
If there is a ring at the end of the connection wire,
the wire connection method is as shown in the right
figure. Remove the terminal screw and insert it
through the ring at the connection wire end, then
connect to the terminal board and fasten the screw.
2) Straight terminal connection method
If there isnt a ring at the end of the connection wire,
the connection method shall be: loosen the terminal
screw, insert the connection wire end completely into the terminal board and fasten the screw.
Pull the connection wire outwards slightly to confirm it is clamped tightly.
3) Clamping method of the connection wire
After wire connection is finished, the connection wire must be pressed tightly with wire clips,
which shall apply to the outer sheath of the connection wire.
Connection method
for ring terminal
z 34z
Chff^j\bZe Abj Chg]blbhg^j
Wire connection for built-in indoor unit
Insert from outside the connection wire and signal transmission wire through the wall hole
with pipeline already arranged.
Pull out the front ends of connection wire and signal wire and make a circle on the signal wire.
Connect the connection wire according to the connection method and indoor and outdoor wiring
diagram.
Pull the connecting conductor outwards slightly to confirm it is clamped tightly.
Connect the plug for connecting the signal wire with the plug of the signal wire connected
from the indoor unit.
After wire connection is finished, install wire clips using the same method for connection wire
clamping.
Note: When connecting the indoor unit and the outdoor unit, please do connect the wires
with the same color terminals.
Notes:
Before connecting the conductors between indoor unit and outdoor unit, check for the
number on the indoor and outdoor units connecting terminals. Connect the terminals with
the same color and number with a wire.
Wrong connection would damage the controller of the air conditioner or the machine
couldnt operate.
Do not connect the connection wire and signal wire with the same cable. They shall be
connected respectively to ensure system normal operation.
For some models, connection wire shall be provided by the user.
If the fuse on PC board is broken please change it with the type of T 3.15A /250VAC.
The power cable and connecting cable are self-provided.
power cable
H05RN-F 3G (1.0~1.5)mm
Signal cable
2
H05RN-F 2 (0.75~1.5)mm
X
2
All the cables shall have got the European authentication certificate.
The breaker of the air conditioner should be all-pole switch; and the distance between
its two contacts should be no less 3mm. Such means for disconnection must be
incorporation in the fixed wiring.
The signal wire must be shielded wire.
Note: The terminal block will be the below two types due to different models.
When wiring, please select the proper wiring type due to the actual terminal block.
INDOOR UNIT
TERMINAL BLOCK
OUTDOOR UNIT
TERMINAL BLOCK
P Q
L N
POWER SUPPLY:
1PH,220-230V~,50Hz
A 1 A 2 B 1 B2
P Q P Q P Q P Q
Y/G
P Q L N
POWER SUPPLY:
1PH,220-230V~,50Hz
Y/G
P Q
POWER
1PH,220-230V~,50Hz
P Q
L N
POWER
1PH,220-230V~,50Hz
L N
SUPPLY:
SUPPLY:
Y/G
INDOOR UNIT
TERMINAL BLOCK
Y/G
OUTDOOR UNIT
TERMINAL BLOCK
P Q L N
POWER SUPPLY:
1PH,220-230V~,50Hz
A1 A2 B 1 B2
P Q P Q P Q P Q
POWER SUPPLY:
1PH,220-230V~,50Hz
Y/G
Y/G
P Q L N
P Q L N
P Q L N
POWER SUPPLY:
1PH,220-230V~,50Hz
POWER SUPPLY:
1PH,220-230V~,50Hz
Y/G
Y/G
z 35z
Chff^j\bZe Abj Chg]blbhg^j
8.3. Duct Type (For AE***XLEAA)
8.3.1. Installation Procedure
Indoor unit
1. Select suitable places the outlet air can be sent to the
entire room, and convenient to lay out the connection
pipe, connection wire and the drainage pipe to outdoor.
2. The ceiling structure must be strong enough to support
the unit weight.
3. The connecting pipe, drain pipe and connection wire
shall be able to go though the building wall to connect
between the indoor and outdoor units.
4. The connecting pipe between the indoor and outdoor
units as well as the drain pipe shall be as short as possible. (See Figure 1)
5. If its necessary to adjust the filling amount of the refrigerant, please refer to the installation
manual attached with the outdoor unit.
6. The connecting flange should be provided by the user himself.
7. The indoor unit have 2 drainage outlet, one outlet be jamedwith rubber cap, during installation
only use another outlet (In/Out liquid pipe side). When necessary, use the two together.
8. Do not place the TV, equipment, facility, piano etc, expensive goods below the AC. This is to
prevent the water dropping down from the AC and lead to damage to the goods.
Fig 1
After selecting the unit installation location, proceed the following steps:
1. Drill a hole in the wall and insert the connecting pipe and wire through a PVC wall-through tube
purchased locally. The wall hole shall be with a outward down slope of at least 1/100. (See
Figure 2)
2. Before drilling check that there is no pipe or reinforcing bar just behind the drilling position.
Drilling shall avoid at positions with electric wire or pipe.
3. Mount the unit on a strong and horizontal building roof. If the base is not firm, it will cause
noise, vibration or pipe broken and refrigerant leakage (see Figure 6).
4. Support the unit firmly.
5. Change the form of the connection pipe, connection wire and drain pipe so that they can go
through the wall hole easily.
Fig 2
z 36z
Chff^j\bZe Abj Chg]blbhg^j
When installing the ceiling concealed type indoor unit, a specially designed return air
bellows shall be installed, as shown in Figure 3, Figure 4.
Figure 3
Figure 4
Ceiling
Air outlet grille
Installing building roof
5m( 50Pa)
0.5m(0Pa)or
Air supply
Air outlet duct
Unit
A
Return air bellows
Return air
Return air bellows
Air supply
No obstacles
within 1 m(0Pa)
Unit
Return air
Each air return and supply duct should fix to the floor precast slab by using an iron stand. Use glue to
seal the interface closely. Recommend the distance between the air return duct and the wall is more than
150mm.
The distance between air duct outlet and air conditioner outlet is according to the length of actually installed
air duct and in service behavior of the static pressure terminal: Installation sketch map for long and short
air duct is showed below, when connect to short air duct, using low static terminal (terminal color is white),
the distance between air duct outlet and air conditioner outlet is no more than 0.5m; when connect to long
air duct, using middle static terminal (terminal color is red), the distance between air duct outlet and air
conditioner outlet could be within 5m at this point.
Figure 5
sling dog
drain piping
air return duct
air return shutter
transition
air duct
air outlet
duct
air diffuser
joint of air diffuser
Drain piping of condensed water should keep a downhill grade of 1% or more. Use insulating pipe to cover
the drain piping of condensed water to keep warmth.
As figure shown, suspend and install the unit.
Figure 6
M8 broad foundation bolt
M8 suspension screw
Unit
M8 broad lock ring
M8 nut
Figure 6
z 37z
Chff^j\bZe Abj Chg]blbhg^j
Installation for air duct of indoor unit
1. Installation of air discharge duct
This type of unit uses circular air duct with its caliber of 180mm.
An additional transitive air duct is necessary for the circular air duct to connect to the air
supply inlet. It should be also connected to its respective air diffuser separately. See
Fig.1. Adjust the wind speed of each air diffuser outlet to keep in line on the whole, so
as to meet a demand of the air conditioner in the room.
Indoor unit
flexible joint
or static pressure box
Fig1: Duct connected
transitive air duct
circular air duct
joint of air diffuser
air diffuser
2. Installation of air return duct
Use rivets to connect the air return duct to the air return inlet of the indoor unit. The
other end connects to the air return shutter. as shown in Fig.2.
air return
shutter
air return
duct
Fig2: Duct return connected
indoor unit
rivet
3. Air duct insulation
Insulation layer is needed for air supply and return duct. First, paste a glue nail to the
air duct, and then attach the insulation cotton that has a tinfoil layer and use the glue
nail cover to fix. Finally, seal the air duct interface with tinfoil adhesive tape closely.
as shown in Fig3.
galvanized
board
glue nail
insulating
fabric
tinfoil
glue nail cover
adhesive tape
z 38z
Chff^j\bZe Abj Chg]blbhg^j
Installing the suspension screw:
Use M8 or M10 suspension screws (4, prepared in the field) (when the suspension screw
height exceeds 0.9 m, M10 size is the only choice). These screws shall be installed as
follows with space adapting to air conditioner overall dimensions according to the original
building structures.
Wooden structure
A square wood shall be supported by the beams and then set the suspension screws.
Square wood
Suspension
screw
New concrete slab
To set with embedded parts, foundation bolts etc.
Knife embedded part
Guide plate embedded partPipe suspension foundation bolt
Original concrete slab
Use hole hinge, hole plunger or hole bolt.
Steel reinforcement structure
Use steel angle or new support steel angle directly.
Beam
Iron reinforcement
Foundation bolt
Hanging bolt
Suspension screw
Support steel angle
Hanging of the indoor unit
Fasten the nut on the suspension screw and then hang the suspension screw in the T
slot of the suspension part of the unit.
Aided with a level meter, adjust level of the unit within 5 mm.
z 39 z
Chff^j\bZe Abj Chg]blbhg^j
! Caution
In order to drain water normally, the drain pipe shall be processed as specified in
the installation manual and shall be thermal insulated to avoid dew generation.
Improper hose connection may cause indoor water leakage.
Requirements
The indoor drain pipe shall be thermal insulated.
The connection part between the drain pipe and the indoor unit shall be insulated so as to
prevent dew generation.
The drain pipe shall be slant downwards (greater than 1/100). The middle part shall not be
of S type elbow, otherwise abnormal sound will be produced.
The horizontal length of the drain pipe shall be less than 20 m. In case of long pipe, supports shall be provided every 1.5
Central piping shall be laid out according to the following figure.
Take care not to apply external force onto the drain pipe connection part.
2m to prevent wavy form.
1.5m~2m
Insulation
(supplied by the user)
To the largest (app. 10cm)
Down slope above 1/100
Support
Down slope
above 1/100
VP30
S type elbow
Pipe and insulation material
Pipe
Insulation
Rigid PVC pipe VP31.5mm (internal diameter)
Foamed PE with thickness above 7mm
Hose
2
Drain pipe size: ? 19.05mm
(3/4") PVC pipe
The hose is used for adjusting the off-center and angle of the rigid PVC pipe.
Directly stretch the hose to install without making any deformation.
The soft end of the hose must be fastened with a hose clamp.
Please apply the hose on horizontal part
HoseHose clamp
Insulation treatment:
Wrap the hose and its clamp until to the
indoor unit without any clearance with
insulating material, as shown in the figure.
Wall
Outside
Slant
Drain pipe (supplied
by the user)
Drain confirmation
Subsidiary insulation
Insulation
Rigid PVC pipe
During trial run, check that there is no leakage at the pipe connection part during water
draining even in winter.
z 40z
Chff^j\bZe Abj Chg]blbhg^j
Allowable pipe length and drop
These parameters differ according to the outdoor unit. See the instruction manual attached
with the outdoor unit for details.
Supplementary refrigerant
The refrigerant supplementation shall be as specified in the installation instructions
attached with the outdoor unit. The added refrigerant shall be R22.
The adding procedure shall be aided with a measuring meter
for a specified amount of supplemented refrigerant
Requirement
Overfilling or underfilling of refrigerant will cause compressor
fault. The amount of the added refrigerant shall be as specified
in the instructions.
Connection of refrigerant pipe
Conduct flared connection work to connect all refrigerant pipes.
A
Pipe expander
Pipe cutting and expanding
If the pipe is too long or the flare is damaged, it needs to be cut or expanded.
The connection of indoor unit pipes must use double spanners.
The installing torque shall be as given in the following table.
Connecting pipe
O.D.(mm)
? 6.35
? 9.52
? 12.70
? 15.88
*
Size A (mm)
"
) 1.0 ~ 1.8
"
) 1.2 ~ 2.0
"
) 1.4 ~ 2.2
Installing torque
(N-m)
11.8 (1.2kgf-m)
24.5 (2.5kgf-m)
49.0 (5.0 kgf-m)
78.4 (8.0 kgf-m)
Correct
Slope Damage Bur Partial Overlong
Increased installing
torque (N-m)
13.7 (1.4 kgf-m)
29.4 (3.0 kgf-m)
53.9 (5.5 kgf-m)
98.0 (10.0 kgf-m)
Incorrect
Double-spanner
operation
z 41z
Chff^j\bZe Abj Chg]blbhg^j
Vacuum pumping
With a vacuum pump, create vacuum from the stop valve of the outdoor unit.
Emptying with refrigerant sealed in the outdoor unit is absolutely forbidden.
Open all valves
Open all the valves on the outdoor unit.
Gas leakage detection
Check with a leakage detector or soap water that if there is gas leakage at the pipe
connections and bonnets.
Insulation treatment
Conduct insulation treatment on both the gas side and liquid side of pipes respectively.
During cooling operation, both the liquid and gas sides are cold and thus shall be insulated
so as to avoid dew generation.
The insulating material at gas side shall be resistant to a temperature above 120
The indoor unit pipe connection part shall be insulated.
The notch upward (Attached detail view)
Field piping side
Indoor unit
Subsidiary insulation tube
.
z 42z
8.4. Installation Precedure(For AF***XCEAA)
Selection of installation place
Place where it is easy to route drainage pipe
more than
more than
more than
more than
Fig1
330
617
Fig2
Fig3
Tool necessary
1. Screw driver
2. Hacksaw
3. 70mm dia.hole core drill
4. Spanner(dia. 17,27mm)
5. Spanner(14,17,27mm)
6. Pipe cutter
7. Flaring tool
8. Knife
9. Nipper
10. Gas leakage detector or soap water
11. Measuring tape
12. Reamer
13. Refrigerant oil
Standard accessories
Following parts shall be field supplied
Mark
A
B
C
D
E
F
Part name
Adhensive tape
Pipe clip
Connecting hose
Insulation material
Putty
Drain hose
and outdoor piping.
Place ,away from heat source and with less
direct sunlight.
Place where cool and warm air could be
delivered evently to every corner of the room.
Place near power supply socket.Leave enough
space around the unit.
Place ,robust not causing vibration,where the
body can be supported sufficiently.
To prevent interference, place it at least 1m
away from other electric machines, such as
TV set, radio.
Installing
According to the dimension of the figure 2 shown,
nail two cement steel nails on the wall,Keep 2~3
mm out.then hang the back of the unit on them.
There must be no gap between the indoor unit
and wall.
Remove the front panel,then use two expansible
screws to fix the unit on the floor.As figure 3
shown.
Once refrigerant piping and drain piping connections
are complete,fill the gap of the throght hole with putty.
Attach the front panel and front grille in their orginal
positions once all connections are complete.
Shape and description
No.
Note: There isn't connecting wire with this unit.
Chff^j\bZe Abj Chg]blbhg^j
QTY
Remote controller
Expansion
Self-tapping screw
Wall hole cover
Dry battery #7
Cement steel nail
bushing
6
Fixing the unit
1. Position of the wall hole
Wall hole should be decided according to installation place and piping direction.(refer to installation drawings).
2. Making a wall hole
z 43z
Drill a hole of 120x70 mm dia. with a little slope towards outside
3. Piping connection
Chff^j\bZe Abj Chg]blbhg^j
Indoor side
Wall hole
70mm
(Cross section of wall hole)
(1)
Schematic diagram for unit connection
Flared pipe connection
Indoor unit
Indoor unit
(2)
Connection pipe dimensions:
Outdoor side
Thickness
of wall
3-way Valve
Outdoor uint
2-way Valve
Pipe Value
Liquid
Gas
6.35mm
12.7mm
Torque
18 N.m
50 N.m
Gas 9.52mm 40 N.m
Apply and tighten the nut.
(3)Cautions for pipe connection
Pipes free from twists, deformation, water, dust.
Dedicated tools for each R407C and R22
should be used and stored separately.
Spanner
Spanner
Joint
Nut
Optimized radii of bends
Insulation to be applied on all gaseous pipes
Flared section free from cracks
(4)
Pipe connection process
Threads on the pipes may be damaged
when tightening if the pipes are not
well aligned.
Apply refrigeration oil on the end of the pipe to be connected and on the flared section.
Align the pipes to be connected and tighten the nut. (See the figure)
Ensure that no foreign articles enter into the pipes.
Piping connection of the indoor unit
1. Arrangement of piping and drainage pipe
After opening inlet grill,you will see a control box.
Remove the cover before working.
Insulation material
Copper tube
Drain hose
Connecting electric cable
for indoor and outdoor unit
Cut away, with a hammer or a saw, the lid for piping according to piping direction.
z 44z
Chff^j\bZe Abj Chg]blbhg^j
According to the piping method, connect the piping on indoor unit with union of connection pipe.
Arrange the piping as per the wall hole and bind drain hose connecting electric cable and piping
together with polyethylene tape.
Insert the bound piping connecting electric cable and drain hoes through wall hole to connect
with outdoor unit.
2. Arrangement drain hose
Drain hose shall be placed in under place.
There should be a slope when arrange drain hose. Avoid up and down waves in drain hose.
If humidity is high, drain pipe(especially in room and indoor unit) must be covered with
installation material.
Electric wiring :
Process of wire connections
1. Loop terminal
After removing the screw, fix the wire ring on the screw, reinsert the screw into the
block terminal and then tighten the screw.
2. Straight terminal
After loosening the screw, inset the wire end into the block terminal and then tighten
the screw. Slightly pull the wire to see if it is tightly fixed.
3. Wire capping
After completion of connection, capping clips must be
applied on the external sleeve of the wires.
Wiring of indoor unit
Remove air intake screen and take out the front wires.
Connect the wires as specified in the above
methods and diagrams for indoor unit and wire con nections.
Properly apply capping clips on the wires.
Replace the air intake screen.
Do not link the connecting and signal wire with the
same cable, a snug space must be maintained
between connecting and signal wires.
Shield of the signal wire should be spot grounded.
Wiring diagram:
W
L
B
Y/G
N
R
R
P
Q
1(L)
Wiring diagram of loop terminals
Block terminal
Capping clip
TO POWER SUPPLY
(1PH,220-230,50Hz)
Note:
CONNECT TO
OUTDOOR UNIT
When connecting indoor and outdoor wire, check the number on indoor and outdoor terminal
blocks. Terminals of same number and same color shall be connected by the same wire.
Incorrect wiring may damage air conditioner's control or cause operation failure.
z 45z
Chff^j\bZe Abj Chg]blbhg^j
Others
1.Power supply requirements:
Voltage: single-phase1PH,220-230V~,50Hz
Dedicated electrical cable should be installed by a qualified technician in accordance with the state
regulation for electrical engineering.
The power source must be grounded.
A circuit breaker must be installed
Electrical cables should be connected by Y method. Damaged or wornelectrical cable must be
replaced by authorized after sales agents.
The power plug should be connected as follows: L for live line, N for neutral line and forgrounding.
Connection parameters: H05RN-F 3G(
Signal parameters:
H05RN-F2X(0.75
Cables for power supply, connection and signals are prepared by the owner.
2.Piping cutting and flaring
Be sure to carry out deburring after cutting with a pipe cutter.
Insert flaring tool to make a flare.
1.0~1.5)mm
~1.5)mm
(Shieded wire)
A
CorrectIncorrect
Flare tooling die
Lean
Damage of flare CrackPartialToo outside
Liquid pipe
Gas pipe
Pipe diameter
6.35mm(1/4")
12.7mm(1/2")
Size A (mm)
0.8 ~1.5
1.2 ~2.0
Installation inspection and test run:
Please operate unit according to this Manual.
Items to be checked during test run. Please made a '' '' in '' ''
Are there any gas leakage?
How is insulation at piping connection carried out?
Are electric wires of indoor and outdoor unit firmly inserted into terminal block?
Is electric wiring of indoor and outdoor securely fixed?
Is drainage securely carried out?
Is earth line(grounding) securely connected?
Is power supply voltage abided by the code?
Is there any noise?
Is control display normal?
Is cooling operation normal?
Is room temp. regulator normal?
z 46z
Chff^j\bZe Abj Chg]blbhg^j
Allowable pipe length and drop
These parameters differ according to the outdoor unit. See the instruction manual attached
with the outdoor unit for details.
Supplementary refrigerant
The refrigerant supplementation shall be as specified in the installation instructions
attached with the outdoor unit. The added refrigerant shall be R22.
The adding procedure shall be aided with a measuring meter
for a specified amount of supplemented refrigerant
Requirement
Overfilling or underfilling of refrigerant will cause compressor
fault. The amount of the added refrigerant shall be as specified
in the instructions.
Connection of refrigerant pipe
Conduct flared connection work to connect all refrigerant pipes.
Pipe cutting and expanding
A
Pipe expander
If the pipe is too long or the flare is damaged, it needs to be cut or expanded.
The connection of indoor unit pipes must use double spanners.
The installing torque shall be as given in the following table.
Connecting pipe
O.D.(mm)
6
. 3
5
9
. 5
2
1
2 . 7
0
5 . 8
8
1
Size A (mm)
"
) 1.0 ~ 1.8
"
) 1.2 ~ 2.0
"
) 1.4 ~ 2.2
Installing torque
(N-m)
11.8 (1.2kgf-m)
24.5 (2.5kgf-m)
49.0 (5.0 kgf-m)
78.4 (8.0 kgf-m)
Correct
Slope Damage Bur Partial Overlong
Increased installing
torque (N-m)
13.7 (1.4 kgf-m)
29.4 (3.0 kgf-m)
53.9 (5.5 kgf-m)
98.0 (10.0 kgf-m)
Incorrect
Double-spanner
operation
z 47z
Chff^j\bZe Abj Chg]blbhg^j
Vacuum pumping
With a vacuum pump, create vacuum from the stop valve of the outdoor unit.
Emptying with refrigerant sealed in the outdoor unit is absolutely forbidden.
Open all valves
Open all the valves on the outdoor unit.
Gas leakage detection
Check with a leakage detector or soap water that if there is gas leakage at the pipe
connections and bonnets.
Insulation treatment
Conduct insulation treatment on both the gas side and liquid side of pipes respectively.
During cooling operation, both the liquid and gas sides are cold and thus shall be insulated
so as to avoid dew generation.
The insulating material at gas side shall be resistant to a temperature above 120
The indoor unit pipe connection part shall be insulated.
The notch upward (Attached detail view)
Field piping side
Indoor unit
Subsidiary insulation tube
.
z 48z
Chff^j\bZe Abj Chg]blbhg^j
8.5. Wall Mounted Type (For AS***XCEAA)
Instructions to installation
PRECAUTION
Execute proper grounding. Do not connect the earth wire to a gas pipe, water pipe, lightening rod,
or a telephone ground wire. Improper placement of earth wires can result in electric shock.
An electric leakage breaker must be installed, otherwise electric shock or other accidents would occur.
After completion of the installation, the air conditioner shall be electrified to check for electric leakage.
5.5.1
. P rep a r a t i o n f o r i n st a l l a t i o n
Note: Connect ports 3 and 4 of Indoor terminal board with ports P and Q of outdoor terminal board.
Electrical Requirements
Connect To Outdoor Unit
A specialized power supply wire, which shall be installed by a competent person as per the rules of
the national standard.
Power supply must be grounded effectively.
An electric leakage breaker shall be installed.
Layout of power supply wiring shall be Y connection. If the power supply wire is damaged, it must be
replaced by the manufacturer or its service center or professional person (the power supply wire shall
be self-contained).
For connection of the power supply plug, L shall be connected with the live wire, N shall beconnected
with netural line, shall be connected with earth wire.
Power supply wire parameters:H05RN-F 3G(1.0-1.5)mm
Signal wire parameters:H05RN-F 2x(0.75-1.5)mm
Note:The singnal wire and connection wire should be provided for oneself.
The singnal wire must be shielded wire
2
;
2
(User shall self-provide signal wire ).
z 49 z
Chff^j\bZe Abj Chg]blbhg^j
8.5 .3. C h o o se t h e i n st a l la t i o n p l a ce
Install the indoor unit where the weight of the unit can be supported.
Install the indoor unit where the heat source and steam source are not close and the unit inlet and outlet
are not blocked.
Install the indoor unit where the drainage is easy and the outdoor unit can be easily connected.
Install the indoor unit where its cold air and hot air can be easily sent to all the comers of the room.
Install the indoor unit where the power socket is near and there is sufficient space around the indoor unit.
Install the indoor unit where there is no T.V set, radio set, and wireless applian ce underneath, and the
sunlight lamp is over one meter away.
If the remote controller is installed on the wall, the indoor unit shall be ensured to receive the signal
while the sunlight lamp is on.
8.5.4. Method for Cutting and Expanding Pipes.
When the pipe is too long or the mouth is damaged, the pipe needs to cut or expanded.
1.cutting hose2.Removing burr3.Put on nut4.Expand Hose
A
Hose Expander
CorrectNot Correct
cracks on expanded mouthburrincompletetoo longTilting
Expansion Size
Hose dia.
6.35 mm(1/4)
9.52 mm(3/8)
Size (mm)A
0.8-1.5
1.0-1.5
8.5.5. W h en t h e m o u n t i n g p l a t e i s f i rs t f i x e d
1. Carr y ou t, b as ed on t he neigh bor in g pill ar s or lintel s, a pr op er leveli ng f or t he plate to be fix ed agains t
the wall, then temporarily fasten the plate with one steel nail.
2. Make s
3
. Mak ing a H ole on the wal l and F itti ng th e p ipin g Ho le cover.
Make a hole of 60mm in diameter, slightly descending to outside the wall.
I
4
. D raw ing o f pi pe Rear pi pin g
Draw pipes and the drain hose, then fasten them with the adhesive tape. Left Left-rear, piping.
In case of left side piping, cut away, with a nipper, the lid for left piping.
In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for
left-rear piping which is marked on heat insulation materials.
ur
e once mo re th e p ro per l evel of the plate, by hang ing a thr ead w ith a wei ght f rom the centr al
top of the plate, then fasten securely the plate with the attachment steel nail.
2~5mm
60mm
ns
tall p ipin g ho le co ver an d s eal it off with putt y after ins tal lation .
z 50z
Chff^j\bZe Abj Chg]blbhg^j
(1) Insert the drain hose into the dent of heat insulation materials of indoor unit.
(2) Insert the indoor/outdoor electric cord from backside of indoorunit, and pull it out on the front side,
then connect them.
(3) Coat the flaring seal face with refrigerant oil and connect pipes.
Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape.
Heat insulation
Indoor side
Wall hole
70mm
(Section of wall hole) Piping hole pipe
Outdoor side
Thickness
of wall
Lid for right piping
Lid for under piping
Lid for left piping
Fix with adhesive tape
5.5.6. Other direction piping
Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe according
to the position of wall hole. When bending, be careful not to crash pipes.
Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation
of connecting part specially.
Hang surely the unit body onto the upper notches of the mounting plate. Move the body from side to verify
its secure fixing.
In order to fix the body onto the mounting plate, hold up the body aslant from the underside and then put
it down perpendicularly.
material
signal wire
Drain hose
Indoor/outdoor
electric cable
Indoor/outdoor electric cord and drain hose must
be bound with refrigerant piping by protecting tape
Piping
Change-for-fresh-air tube
8.5.7. When connecting the cord before installing the indoor unit
Insert the cord from the back side of the unit, then pull it out on the front side.
Loosen the screws and insert the cord ends fully into terminal block, then tighten the screws.
Pull the cord slightly to make sure the cords have been properly inserted and tightened.
After the cord connection, never fail to fasten the connected cord with the wiring cover.
Note: when connecting the cord, confirm the terminal number of indoor and outdoor units carefully. If
wiring is not correct, proper operation can not be carried out and will cause defect.
8.5.8 . H o w t o c o n n e ct w i ri n g t o t h e t er m i n a ls
1 . F or s olid core w iri ng ( or F - cable )( F ig. 1)
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 25mm of the exposed
solid wire.
(2) Using a screwdriver, remove the terminal screw (s) on the terminal board.
(3) Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw
using a screw driver.
2
. F or s tran d wir ing (F ig. 2 )
(1) Cut the wire with a wire cutter or wire-cutting pliers, then strip the insulation to about 10mm of the exposed
strand wiring.
(2) Using a screwdriver, remove the terminal screw (s) on the terminal board.
z 51z
Chff^j\bZe Abj Chg]blbhg^j
(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten the terminal screw using a screw driver.
Fig.1
After passing the connection cord and power cable through
the insulation tube, fasten it with the cord clamp, as shown
in Fig.18
A. Solid
Loop
Insulation
Fig.2
Insulation tube
Use VW-1,0.5 to 1.0mm thick, PVC tube as the insulation
tube.
B. Strand wire
Cord clamp
Round terminal
Wire
Screw with special
washer
Round terminal
Terminal board
Wire
Screw with
special
washer
Round
terminal
3. Ho w to ch eck the add res s es ?
When finish all the above works, please power off and power on again to the whole system but set all
the indoor units in STANDBY. Then continously press the emergency switch until you hear the buzzer
sound 5 times(Pi Pi Pi Pi Pi), and then the LCD display board will show the address of this indoor unit.
Press any key on the remote controller, it will exit the address checking precedure.
8.5.9. I n st a l la t i o n c h eck a n d t ri a l o p era t i o n
Check the Layout of the Drain Pipe and Connection Wires, and also the piping and address setting.
The drain pipe should be placed underneath, and the connection wires should be placed upside;
and the drain pipe especially the section inside the machine and indoors must be wound up with
insulating material to preserve heat. The drain pipe shall be sloped and no concave and convex
shall occur along the whole pipe. And the cases as the right figure indicates shall not occur.
8.5.10. I n st a l la t i o n c h eck
Is power supply voltage required?
Is water completely drained to outdoors?
Are power wire and connection wires between indoor and outdoor units correctly connected?
Is any gas leaked from the pipe connectors?
Are series numbers of the terminals on the indoor and outdoor units corresponding to each other?
Is the connection section of the auxiliary pipe insulated? Is the indoor unit fixed firmly?
Is noise big?
8.5.11.Tri
The person who has completed this installation shall be requested to conduct a test operation for check:
Is the temperature adjuster working normally?
Does the location for installation conform to requirements?
Winding up with Protective Plastic Tape.The connection pipes,drain pipe, and the connection wires shall
be wound up with PVC tape.
Notes: The connection pipes shall also be wound up with insulating material to preserve the temperature.
The airing direction shall be from bottom to top.
al o p era t i on
z 52z
Chff^j\bZe Abj Chg]blbhg^j
9. Wiring Diagram,PCB photo and function information
2 02 02 Indoor coil temp. sensor failuresensor broken down or short circuit for
3 4A 11 Outdoor ambient temp. sensor
4 49 12 Outdoor coil temp. sensor or
5 48 10 Over-current protection CT check abnormal 3 times in 30m
6 53 14 High pressure abnormal High pressure switch acts 3 times in 30m
7 47 22 Power supply abnormal Fault phase, out of balance greatly
8 07 06 Communication between wired
9 06 05 Communication between
10 08 21 Drainage system failure Float switch broken down for more than
15 05 17 EEPROM abnormal EEPROM data missing
16 54 26D Low pressure switch abnormal Low pressure switch acts in normal
17 50 15 Compressor overheat
18 12 23 Abnormal mode Indoor operation mode is different with the
21 32 07
22 54 08
Mark:
Display 1: For remote type, flash times;
Display 2: Diagnostic code on YR-E12;
Display 3: For central controller YCZ-A001
Diagnostic description
failure
failure
compressor discharging temp.
sensor failure
controller and indoor abnormal
indoor and outdoor abnormal
alarm signal input) abnormal
abnormal
abnormal
Outdoor power model
abnormal
The current is overlow No signal comes from current testor or
Possible reason
sensor broken down or short circuit for
more than 2m continuously
more than 2m continuously
sensor broken down or short circuit for
more than 2m continuously
Sensor broken down or short circuit for
more than 2m continuously
Communication abnormal for more than
4m continuously
Communication abnormal for more than
4m continuously
25m continuously
Outside signal broken down for more than
10s
Sensor broken down or short circuit for
more than 2m continuously
continuously
sensor broken down or short circuit for
more than 2m continuously
running(Open : Alarm, Close : Normal)
The discharging temp, is higher than 120℃
running indoor unit. (for example: one in
cooling, one in heating)
Check outdoor power model wires
connection or change the model
compressor doesn’t work
z 60z
9.3.1. Wiring Diagram For AF07-142XCEAA
Chff^j\bZe Abj Chg]blbhg^j
z 61z
9.3.2. PCB Photo
Run
Time
Power
Chff^j\bZe Abj Chg]blbhg^j
PCB 0010451212-Part 1
PCB 0010451212-Part 2:
:
CN1
SW1
CN101
LED1
CN103
z 62z
9.3.3. PCB 0010451212-Part 3:
Led4
CN28
CN22
CN5
CN6
CN
8
Chff^j\bZe Abj Chg]blbhg^j
CN27
CN10
CN13
C
N7
CN1
CN4
CN2
CN3
CN26
CN21
CN20
CN15
3
z 63z
Chff^j\bZe Abj Chg]blbhg^j
9.3.4. Diagnostic Code
Resumable failures are marked with " ", the others are not resumable failures.
Resumable failure will disappear when the failure is eliminated and its failure code
will disappear automatically within 30 seconds. But the other failure code will
disappear only after the unit starts up once again.
When failure occurs, the unit only can receive "OFF" signal from the controller.
And when the unit is shut off, the failure code will disappear.
Failure description
Room temp. sensor abnormal
Indoor coil temp. sensor abnormal (liquid pipe)
Refrigerant system abnormal
High pressure abnormal (outdoor)
Drainage abnormal
Communication between indoor and wired controller
Indoor fan motor abnormalup
Indoor fan motor abnormaldown
3 phase abnormal
Low pressure abnormal (outdoor)
Communication between indoor and outdoor abnormal
Compressor overheat
CT current abnormal
Outdoor ambient temp. sensor abnormal
Outdoor coil pipe temp. Sensor A abnormal
Outdoor discharging temp. sensor B abnormal
Flash times of indoor
receiver board
Power LED flashes 1 time
Power LED flashes 2 times
Power LED flashes 3 times
Power LED flashes 5 times
Power LED flashes 6 times
Power LED flashes 7 times
Power LED flashes 8 times
Power LED flashes 9 times
Running LED flashes once
Running LED flashes twice
Running LED flashes 3 times
Running LED flashes 4 times
Running LED flashes 5 times
Running LED flashes 6 times
Running LED flashes 7 times
Running LED flashes 8 times
Outdoor coil pipe temp. sensor B abnormal
Abnormal modes running
Outdoor discharging temp. sensor A abnormal
Indoor EEPROM abnormal
N
otice
: Wall mounted
AS
type diagnostic code is same with console type AF
Running LED flashes 10 times
Running LED flashes 11 times
Running LED flashes 12 times
Running LE
D flashes 14 times
z 64z
.
9.4.1. Wiring Diagram for AS***XCEAA
WIRING DIAGRAM INDOOR
Chff^j\bZe Abj Chg]blbhg^j
0010573506
NEGATIVE ION CONTACT
R
R
BL
BL
TRANSFORMER
SW3
CN11
CN10
CN18
B
CN2
CN15
B
1(N)
B
CN13
W
2(L)
W
CN14
W
Y/G
CN12
CN16
CN20
R
3
R
CN17
CN1
CN19
Open Close
BR
4
TERMINAL BLOCK
BR
SW1
GND
Y/G
EARTH TERMINAL
CN4
SW2
CN3
CN6
CN5
EMERGENCY SWITCH
M
RECEIVER DISPLAY
M
Detector
ROOM TEMP.
SENSOR
PIPING TEMP.
SENSOR
M
Fresh Air Motor
NEGATIVE ION
GENERATER
FAN MOTOR
UP SWING MOTOR
DOWN
M
SWING
MOTOR
Power Supply
SW1 and SW3 are used to choose the working
controller. The detailed information see the following:
SW1SW3
11
100
0
0
Working state of the wire controller
if the controller power on, the indoor unit run according to the state on the controller;
if the controller power off, the indoor unit run in the auto mode
Ignore the state on the controller and power off
Ignore the state on the controller and power off
The controller is able to be controlled
1
1-CLOSE 0-OPEN
Connect To
Outdoor Unit
state of the
wire
NOTE
OPTIONAL.
W : WHITE
B : BLACK
R : RED
BR : BROWN
Y/G: YELLOW/GREEN
PARTS IN DASHED FRAMES ARE
z 65z
9.4.2. 0010451213 PCB Photo
CN1
CN4
CN9
SW2
CN3
CN6
CN5
CN20
Chff^j\bZe Abj Chg]blbhg^j
CN10
CN11
CN18
CN13
LED1
CN15(N)
CN16(L)
SW1
CN11
N
otice
: Wall mounted
AS
type diagnostic code is same with console type AF
z 66z
.
9.5.1. Wiring Diagram
Outdoor unit: AU282XHEAA, AU422XIEAA
Chff^j\bZe Abj Chg]blbhg^j
Capacitor
Capacitor
Outdoor wiring diagram
CN2
3p
BR
Temp. Sensor
LED6
CTA
CTB
CN6
CN1
CN8
132
A1
A2
B1
B2
1
2
3
4
1
2
3
4
W
HeaterA
CompressorA
Sensor A
Gas Piping
H
CN9
M
L
Fan Motor
COM
CN25
Valve A1
CN26
Valve A2
CN27
Valve B1
CN28
Valve B2
CN29
Unloading Valve A
CN11
4-Way Valve A
CN23
Unloading Valve B
CN12
4-Way Valve B
CP1
Gas Piping
CN5
T3.15A/250VAC
B
RL7
N
CN24
Sensor B
Piping Sensor A
CN4CN3
LED3
ERR
FUSE
W
W
COM
RL8
NO
CN31
2
1
1
Piping Sensor B
5p
CN19
BR
COM
NO
3
2
0010573511
P
Q
P
Q
P
Q
P
BR
B
B
C
To Indoor Unit
Y/G
B
W
B
W
W
R
S
Heater B
R
M
CompressorB
Q
To Power Supply
B
BR
BR
R
S
C
M
R
Transformer
Note:
1.The communication terminal block to indoor cannot be connected to high
2.Heater is optional according to different outdoor unit.
3.LED3 flashing shows that failure occurs.
4.CN19 is used to select outdooor capacity:on 5P side,LED6 will be off,
and the cooling capacity is 42000BTU/h; on 3P side,LED6 will be on,the
cooling capacity is 24000-30000BTU/h.
z 67z
Chff^j\bZe Abj Chg]blbhg^j
9.5.2. AU282XHEAA and AU422XIEAA PCB Photo 0010451214
LED3 CN CN
CN9
CN25
CN26
CN27
CN28
CN29
CN11
CN23
CNCN
E
CN19
CN1
CN6
LED6
CN12
CN24
CN31heater Aheater B
CN8
z 68 z
Chff^j\bZe Abj Chg]blbhg^j
9.5.3. Electric control function (For outdoor unit)
A. Indoor unit
A.1 Cooling operation
A.1.1 Anti-freezed function of evaporator
a. Be valid in cooling or defrost mode; be invalid in trial or heating mode.
b. If the evaporator temperature is below -1℃ for 5 minutes, ourdoor fan and
compressor will stop; if the evaporator temperature goes up to over 7℃ and the
compressor has stopped for over 3 minutes, the unit will resume.
c. When the evaporator anti-freezed function works, the indoor motor and the thermostor
will work together.
d. Compressor control
Being powered on for the first time is without the 3-minutes protection. If the compressor
stops, it can start up 3 minutes later.
e. Remote controller control
The adjustment of set temperature and the remote controller shutoff will not be limited by
6-minute control, you can shut off the unit right now.
A.1.2 Dehumidification operation
*temperature range:16~30℃
*temperature control precision:±1℃
*Control characteristic:Tr=room temperature; Ts=set temperature
Tr>Ts+2℃,the compressor and the outdoor motor will go on running, the indoor
motor will run at the set speed.
T<Tr<Ts+2℃,the compressor and the outdoor motor will run for 10 minutes and then
stop for 6 minutes; the indoor motor will stop within 3 minutes after compressor stops, in
the other time, it is at low speed.
In the cross section, there is tolerance of ±1℃. *Against the current impulse: outdoor motor will run 2 seconds later after compressor
starts up.
*Flap position control:
Set the swing flap position due to the actual requirement, press “SWING” to stop swing;
press again, flap can swing freely. Powered on for the first time, the flap will not swing.
*Ice-proof protection(invalid for trial and heating mode):
Avoid the evaporator being iced in cooling or dehumification mode. When compressor
runs for over 5 minutes and indoor coil temperature is not more than -1℃, the compressor
will stop. When indoor coil temperature goes up to over 10℃, and the compressor has
stopped for over
*TIMER ON/OFF function
*SLEEP function
A.1.3 Heating operation
The compensation temperature:4.67
Control tolerance: ±1℃
*Temperature control range:16~30℃
*Temperature control precision:±1℃
*Control characteristic:
When Tr≤Ts for the first time, the compressor, 4-way valve and outdoor motor will run;
indoor motor will run at anti-cold air mode, after the compressor starts up, the
9 minutes,the compressor will re-start up.
℃
z 69 z
Chff^j\bZe Abj Chg]blbhg^j
Compensation of 5 degree will be valid
When Tr>Ts+4℃,the compressor and outdoor motor will be OFF ,
anti-cold air mode.
When Tr<Ts+4℃,the compressor, 4-way valve and outdoor motor will run; indoor motor
will run at anti-cold air mode.
*Control of indoor motor:
Manual control:set High/Med/Low/Auto speed due to the actual request.
*Flap position control:
Set the swing flap position due to the actual requirement, press “SWING” to stop swing;
press again, flap can swing freely. Powered on for the first time, the flap will not
swing,instead, flap will reset. If the reset distance is more than the max. swing distance,
the air sending will stop,but the flap swing will not stop.
* Compressor control
Being powered on for the first time is without the 3-minutes protection. If the compressor
stops, it can start up 3 minutes later.
* Remote controller control
The adjustment of set temperature and the remote controller shutoff will not be limited by
8-minute control, you can shut off the unit right now.
*TIMER ON/OFF function
*SLEEP function
*Anti-cold air operaion:
a.On compressor running or compressor running after defrosting, if the indoor evaporator
temperature is below 32℃, the indoor motor will stop; if indoor evaporator temperature is
over 32℃, indoor motor runs at low speed.
b.If indoor coil temperature can not be over 38℃ within 4 minutes, the fan motor will run
at set speed.
c.If indoor coil temperature is over 38℃ within 4 minutes, the fan motor will run at set
speed (for cassette unit, ceiling concealed unit,and AS**XAEAA).
d.If the unit stops when it arrives the set temperature, indoor motor will blow air for 50
seconds and then stop.
e.After indoor motor starts up, it will not stop because the coil temperature decreases.
f.Sensor OFF
When the compressor changes from running to stop, fan motor will stop.
g.Remote controller shuts off the unit, and indoor fan motor will stop.
*High temperature protection and high temperature cutoff protection:
a.High temperature protection: When indoor coil temperature is over 60℃,outdoormotor
stops; when indoor coil temperature reduces to 54℃, outdoor motor will re-start up, fan
speed changing frequency is over 45 seconds.
b.High temperature cutoff protection: When indoor coil temperature is over 68℃,10
seconds later, outdoor motor will stop, and indoor motor will run as the sensor is off. After
the compressor is standby for 3 minutes and when the coil temperature is below 60℃, the
unit will start up.
z 70z
indoor motor will run at
Chff^j\bZe Abj Chg]blbhg^j
9.5.4. Electric funtions of outdoor
A.1 Control of the compressor, outdoor motor and 4-way valve
A.1.1 Outdoor fan motor control
A. When system do not have overheating or over current protection, outdoor fan speed
will vary with outdoor ambient temperature, as follows:
a. in cooling mode
26℃
22℃
temperature reduce
13℃
super low speed
b. in heating mode (heat pump unit)
16℃
temperature reduce
B.When fan speed changes, if it is from Low speed to High speed, there is no time delay;
if it is from High speed to Low speed, there is 45-second delay.
C.In cooling mode, in one minute before the compressor begins to run,the outdoor motor
will be switched on to run.
D.Super low speed control:outdoor motor will be off for 1 minute at the interval of 45
seconds.
A.1.2 Compressor control
After receiving the “compressor ON” signal sent from indoor unit, the compressor will run.
Its running-stop interval is 3 minutes. Being powered on firstly is without 3-minute delay.
If the two systems receive the “compressor ON” signal simultaneously,they will start up in
turn, and the interval is 20 seconds.
A.1.3 4-way valve control
A. In cooling or dehumidification mode, 4-way valve is not electrified.
B. When receiving the “heating” and “compressor ON” signal from indoor unit, 4-way
valve and compressor will start up simultaneously.
C. In 3 minutes after heating is over, it will be shut off 2 minutes and 50 seconds later. In
3-minute standby period, at 2-minute and 50-second clock, it is electrified.
D. Changing from cooling mode to heating mode, 3 minutes later, it is eletrified.
outdoor fan motor
high speed
med speed
low speed
super low speed
22℃
low speed
med speed
9℃
high speed
high speed
med speed
low speed
28℃
24℃
15℃
super low speed
outdoor fan motor
super low speed
low speed
med speed
high speed
temperature arise
23℃
19℃
11℃
temperature arise
z 71z
Chff^j\bZe Abj Chg]blbhg^j
Changing from heating mode to cooling mode , 3 minutes later, it is shut off.
E. In heating mode, when indoor temperature has arrived the set one (sensor is OFF),
4-way valve will be shut off 3 minutes later.
A.1.4 Solenoid valve control
Cooling mode: After the outdoor unit receives the Startup signal from indoor unit, the
corresponding solenoid valve will open 10 seconds earlier than compressor startup.
Heating mode: After the outdoor unit receives the Startup signal from indoor unit, all the
solenoid valve of the corresponding system will open 10 seconds earlier than compressor
startup.
After the compressor shuts off, the solenoid valvs will close 3 minutes later.
A.1.5 Unloading valve control
When only one indoor unit of one system starts up, the solenoid valve will open.
When receiving the overheating signal from indoor unit, solenoid valve will open.
If one system only connects one indoor unit (single type), solenoid valve will open.
If two indoor units of one system are running, and ourdoor ambient temperature is no
more than –2 degree, the solenoid valve will open.
Priority of operation modes:
All indoor units are running in the same mode:
1) Operate as “prior to the earlier entering”, the outdoor will adjust if there is
non-matching type and inform of indoor units which is entering later.
2) When there i s non-matching, the indoor unit entering later will act: the indoor buzzer
sounds two times, and then the indoor unit is in standby state.
3) Method to eliminate the non-matching type
a) The operation mode of indoor unit entering later changes to the same mode of
A.2 Protection functions
Protection functions of the system can be controlled individually.
A.2.1 Overheating protection
If the units of the two systems are all operating, when the four indoor units all reach the
stop-motor point of the overheating protection, outdoor motor can stop. Outdoor motor has
not the control point of High/Med/Low speed. If one indoor unit reaches the
stop-compressor point of overheating protection, the corresponding compressor will stop,
but the outdoor motor and the other system will work normally. If the two systems all
arrives at the stop-compressor point of overheating protection, the outdoor unit stops; at
this time, if one system resumes, the outdoor motor and the system will work normally, the
compressor not resuming will stop.
A.2 3-minute protection when compressor starts up
If the compressor stops running, it must 3 minutes later that it can re-start up; if the unit is
powered off during operation within 3 minutes, after being powered on, 3 minutes later, the
compressor can start up again.
A.2.3 Communication abnormal between indoor and outdoor
Within 4 minutes after outdoor unit is powered on, it cannnot communicate with indoor unit,
or in the couse of communication, it cannot communicate with indoor unit for 4 minutes
the one earlier.
b) The operation mode of indoor unit entering later changes to FAN mode.
c) The operation mode of indoor unit entering earlier stops or changes the mode.
d) The operation mode of indoor unit entering later stops.
z 72 z
Chff^j\bZe Abj Chg]blbhg^j
contineously, then the outdoor stops running, and shows failure code. After the communication
resumes normal operation and cancel the failure
When all indoor units can not communicate normally, it shows communciation
malfunction.
A.2.4 Solenoid valve control with single unit in cooling mode
If indoor unit sends the “start-compressor” signal, the corresponding solenoid valve will
open; when shutting off the compressor, the corresponding solenoid valve will close. If the
indoor units in one system all send the “stop-compressor” signal, the solenoid valve last
receiving signal will close 3 minutes later.
A.2.5 Solenoid valve control with single unit in heating mode
If indoor unit sends the “start-compressor” signal, the corresponding two solenoid valves
will open; if there is only one indoor unit, the two valves will open too.
A.2.6 When double units of one system are in cooling mode, if the two indoor units send
the “start-compressor” signal, the two solenoid valves will open; if one indoor sends
“start-compressor” signal, while the other sends “stop-compressor”, then the solenoid
valve will open or close respectively. If the two units all send “stop-compressor” signal, the
solenoid valve will open for 3 minutes after compressor stops.
A.2.7 When double units of different system are in cooling mode, if the indoor unit sends
the “start-compressor” signal, the corresponding solenoid valves will open; If the unit
sends “stop-compressor” signal, the corresponding solenoid valve will open for 3 minutes
after compressor stops.
A.2.8 When double units of one system are in heating mode, if any of the two indoor units
sends the “start-compressor” signal, the two solenoid valves will open. After compressor
stops, the solenoid valve will close 3 minutes later.
A.2.9 When double units of different system are in heating mode, if one indoor unit of one
system sends the “start-compressor” signal, the two solenoid valves of this system will
open. After compressor stops, the solenoid valve will close 3 minutes later.
A.2.10 The treatment for 1 to 3 or 1 to 4 refers to the different combination of the above
1-7 items.
A.2.11 Treatment for anti-freezed function
When the two systems are in operation, if one system enters anti-freezed function, the
compressor of this system will stop, while the outdoor motor and the other system will
work normally. If the two systems all enter anti-freezed function, outdoor unit will stop
operation, at this moment if one system resumes, outdoor motor and the corresponding
system will work normally. The compressor of the system which does not resumes will
stop.
A.2.12 Treatment for overheating function
The treatment of stop-compressor status is identical to that of anti-freezed status. If one
system enters overheating 3, this system will stop, while the outdoor motor and the other
system will work normally. If the two systems enter overheating 3, the outdoor will stop; at
this moment if one system resumes, outdoor motor and the corresponding system will
work normally. If the indoor units of the two systems all enter the overheating 2, outdoor
motor will stop. The outdoor will not deal with the status of overheating 1.
Note: The overheating point is decided by the indoor unit.
z 73z
Chff^j\bZe Abj Chg]blbhg^j
Diagnostic code for outdoor unit
(1) The PCB 0010451214 and 0010451848 for FREE-MULTI outdoor unit run the same
procedure.
Outdoor lamp flash times Failure description
1 Discharge pipe A overheat
2 Outdoor coil temp. sensor A failure
3 Outdoor ambient temp. sensor failure
4 Discharge sensor A failure
5 Outdoor coil (suction) temp. sensor B failure
6 Discharge sensor B failure
7 Discharge pipe B overheat
9 Low pressure abnormal
10 Communication error between indoor and outdoor units
11 Over-current protection
13 High pressure abnormal
15 EEPROM failure
z 74 z
Chff^j\bZe Abj Chg]blbhg^j
10.Trouble shooting:
1 communication error
Check the outdoor communication
lamps are flashing or not
No
Check the turn of communication
wires is right or not. A to A, B to B
The lamps still
don
t flash
Check the communication wires is
good o
r not
2 sensor error
S
ensor error
Change indoor PCB
Yes
Wires are good
C
C
hange sensor
hange outdoor PCB
Use multi-meter test the
OK
Check the plug
connection is good or not
OK
Change indoor PCB
sensor the sensor
resistance is 0 ohm or
broken
z 75z
Chff^j\bZe Abj Chg]blbhg^j
3 Pressure protection
P
ressure switch alarm
Use multi-meter to test
the pressure swit
S
hort-connected: OK
Open: alarm state
Run the system, check the
true pressure is good
Check the valve state, pipes
are deformed , leaking or not,
refrigeration cha
ch.
OK
P
ressure is abnormal
rging
A
bnormal
C
heck the wires connection
OK
C
hange outdoor PCB
4 discharge temperature is over-high
Discharge temp. is
over high
Check the refrigeration charging,
pipe system is deformed, leaking or
blocked or not
5 compressor doesn
D
check the system can work for
short time or not
T
est the true temp. . if
the temp. is really
very high
C
ompressor doesn
isconn
ect compressor to
t run
if the temp. is not
very high
t run
Check the indoor controller
setting is right or not
Check the
is good or not
C
hange sensor
magnetic
contactor
z 76z
11. Outdoor performance curves
AU282XHEAA:
11000
10000
9000
8000
7000
cooling capacity (W)
6000
5000
4000
cooling capacity-temperature curves
18/12℃
heating capacity and indoor/outdoor temp. curves
18/14℃
20/15℃
indoor temp.(DB/WB)
22/16℃
25/18℃
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
18℃
20℃
25℃
32℃
35℃
40℃
43℃
46℃
27/19℃
30/22℃
32/23℃
32/24℃
13000
12000
11000
10000
9000
20/15℃
20/12℃
20/14.5℃
8000
heating capacity (W)
7000
6000
℃
—5
℃
0
℃
5
℃
/6
℃
7
outdoor temp.
℃
10
℃
15
℃
24
27/18℃
-
77-
AU422XIEAA:
16.0
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
cooling capacity (KW) changing with indoor/outdoor
temperature
18℃
14.0
12.0
cooling capacity
10.0
8.0
18/14℃ 20/15℃ 22/16℃ 25/18℃ 27/19℃ 30/22℃ 32/23℃
indoor D.B./W.B.
20℃
25℃
32℃
35℃/24℃
40℃
43℃
46℃
heating capacity and indoor/outdoor temp. curves-AU42
19000
17000
15000
20/15℃
20/12℃
13000
20/14.5℃
11000
heating capacity ( W)
9000
℃
—5
℃
0
℃
5
outdoor temp.
℃
/6
℃
7
℃
10
℃
15
℃
24
27/18℃
-
78-
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
12. Indoor air velocity and temperature distribution curves
.1 AB0 2-1 2XCEAA:
1274
a. Cooling / Air Velocity Distribution
Cooling
Blowy angle:40
Air Velocity Distribution
1.5m/s
1.5m/s
2.7m
2m
1.0m/s
0.5m/s
4m
3m
1m
b. Cooling / Temperature Distribution
Cooling
Blowy angle:40
Temperature Distribution
0m
1m
1.0m/s
2m2m
0.5m/s
3m
1m
0m
4m
2.7m
2m
4m
3m
22
25
72
1m
0m
-
79-
1m
22
52
72
2m2m
3m
1m
0m
4m
c. Heating / Air Velocity Distribution
Heating
Blowy angle:70
Air velocity Distribution
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
2.7m
2m
1.5m/s
1.0m/s
0.5m/s
4m
3m
d. Heating / Temperature Distribution
Heating
Blowy angle:70
Temperature Distribution
1.5m/s
1.0m/s
1m
0.5m/s
1m
27
0m
1m
27
2m2m
3m
4m
0m
2.7m
2m
4m
3m
1m
25
1m
22
2m2m
3m
4m
0m
25
22
1m
0m
-
80-
12.2 AB212XCEAA
a. Cooling / Air Velocity Distribution
Cooling
Blowy angle:40
Air Velocity Distribution
1.5m/s
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
2.7m
2m
1.5m/s
1.0m/s
0.5m/s
4m
3m
b. Cooling / Temperature Distribution
Cooling
Blowy angle:40
Temperature Distribution
22
52
72
1m
0m
1m
1.0m/s
0.5m/s
2m2m
22
52
3m
72
1m
0m
4m
2.7m
2m
1m
4m
3m
1m
0m
-
81-
1m
2m2m
3m
0m
4m
c. Heating / Air Velocity Distribution
Heating
Blowy angle:70
Air velocity Distribution
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
2.7m
2m
1.5m/s
1.0m/s
0.5m/s
3m
1m3m
d. Heating / Temperature Distribution
Heating
Blowy angle:70
Temper
ature Distribution
27
0m
1.5m/s
1m
27
1.0m/s
0.5m/s
1m
0m
2m2m
4m4m
2.7m
2m
3m
25
22
1m3m
0m
--
82
1m
25
22
2m2m
1m
0m
4m4m
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
12.3 AF09/122XCEAA:
a. Cooling / Air Velocity Distribution
Cooling
Blowy angle:25
Air Velocity Distribution
2.4m
1.2m/s
0m
0.4m/s
0.8m/s
5.5m
b. Cooling / Temperature Distribution
Cooling
Blowy angle:25
Temperature Distribution
2.4m
21
0m
26
24
5.5m
-
83-
c. Heating / Air Velocity Distribution
Heating
Blowy angle:5
Air velocity Distribution
2.4
1.2m/s
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
0.4m/s
0.8m/s
0
d. Heating / Temperature Distribution
Heating
Blowy angle:5
Temperature Distribution
2.4
26
0
5.5
21
24
5.5
-
84-
12.4 Wall mounted type:
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
m
Fig 1
top view
flow control panel horizal
lourer:center
m
Fig 2
top view
flow control panel horizontal
lourer:right and left
m
2
1
1.0
1.0
1.0
0.5
0.25
2
43
65
87
9
10
m
unit m/s
0.25
0.5
0.5
0.25
m
10987654321
2.0
0
1
2
1
3
2
1
2.0
0
1
2
3
0
unit m/s
unit m/s
Fig 3
top view
flow control panel horizontal
lourer:center
Fig 4
top view
flow control panel vertical
lourer:center
m
3
1.8
1
3.0
1.8
2.0
0
0.5
1.0
0.25
m
un i t
65
m /s
1
2
43
87
10
9
Condition
2.0
Fan speed:high
Operation mode:fan
1.0
0.5
1
0
2
3
0.25
56
4
m
Voltage:230V,50Hz
-
85-
1 . Air flow and static pressure chart3
AD072,092XLEAA:
750
700
650
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
AIRFLOW AND STATIC PRESSURE CHART
600
550
500
450
air flow m3/h
400
350
300
30Pa25Pa20Pa15Pa10Pa5Pa0Pa
AD122,142XLEAA:
1000
900
super high
high
med
low
static pressure (Pa)
AIRFLOW AND STATIC PRESSURE CHART
air flow m3/h
800
700
600
500
400
30Pa25Pa20Pa15Pa10Pa5Pa0Pa
static pressure (Pa)
-
86-
super high
high
med
low
AD212XLEAA
1200
1000
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
AIRFLOW AND STATIC PRESSURE CHART
air flow m3/h
800
600
400
200
super high
high
med
low
0
30Pa25Pa20Pa15Pa10Pa5Pa0Pa
static pressure (Pa)
-
87-
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.