EVITA® OXY sensors are used for measuring
the concentration of dissolved oxygen in water
– especially in controlling and monitoring aeration
processes in wastewater treatment plants, but also
in applications such as fi sh frarms.
®
EVITA
OXY 4100 transmitter and a USC Universal Signal
Converter.
There are two versions of the transmitter – a ball
fl oat version, OXY 4100, and a probe version, OXY
4150/3150. The operating principle is identical for
both versions.
There are three versions of the USC - a USC 5000
basic version, and a USC 6000 with added features,
both point to point. A USC 7000 with HART
multidrop functionality enabling up to 15 transmitters
on only two wires.
The EVITA
the oxygen meter. The transmitter converts the
measurements by the sensor into a current signal
and at the same time also performs the necessary
calculations/corrections. The signal converter is the
display and programming unit and offers additional
outputs.
OXY consists of an OXY 1100 sensor, an
®
®
OXY 1100 sensor is the heart of
2
USC 5000 IP 67 (NEMA 4X)
USC 6000/7000 IP 67 (NEMA 4X)
OXY 4150/3150 transmitter
Documentation needs to be consulted.
The user shall be made aware of that, if the
equipment is used in a manner not specifi ed
by the manufacturer, the protection provided
by the equipment may be impaired.
USC 6000/7000 19”
The EVITA® OXY system offers several advantages:
2-wire transmitter
– simple and fast installation
Easy maintenance
– simple automatic calibration in atmospheric
air initiated by using the TILTCAL® or the USC
5000/6000/7000
– self-cleaning ball fl oat
– simple sensor replacement after 2-3 years
High reliability
– self-diagnosing
– membrane leakage detection
– fault indication on transmitter current output
Flexible communication
– HART
®
communication as standard gives added
features
setting of measuring range and units from a
distance
display of dissolved oxygen and temperature,
remaining OXY 1100 sensor life and specifi c
event codes
– Option module can be fi tted in the USC
6000/7000 without the need for tools
3
Mechanical installation
Transmitter
Mounting on a handrail
The mounting bracket for OXY 4100 and 4150 can
be mounted directly on a handrail using the supplied
hose clips. Retighten the hose clips after a few
days use to ensure a tight mounting of the mounting
bracket.
In case of strong sideways forces, the PVC pipe
should be mounted with supporting wires. This takes
up some of the sideways mechanical forces on the
pipe and avoids cracking of the mounting bracket.
4
Fig. 1
v
= 0.05 m/s (2”/sec).
min.
(max. 14’)
Fig. 2
Mounting on a concrete wall
The mounting bracket for OXY 4100 and 4150 can
be mounted directly on to a concrete wall using 2
screws AISI 316 (diameter max. 10 mm or 3/8 UN).
or 3/8 UN
Pipe mounting
The OXY 4150 transmitter can be mounted in a PVC
pipe as shown in fi g. 4.
Mounting of OXY 4150 transmitter
using cable bracket
The strength of the transmitter cable is such that the
transmitter can be allowed to hang from it.
Bracket (A) is available as accessory supplied by
HACH LANGE. However, (B) is not.
B
A
Fig. 3
Fig. 4
Fig. 5
5
Assembly
6
Ball fl oat assembly
Mount the single parts as shown in fi g. 6.
Q
E
Fig. 6
D
Q
C
Q
B
A
A: OXY 4100; 1 1/4” pipe thread
B: is supplied with transmitter
C: 45° PVC or ABS elbow; inside diameter: 50 mm
D: PVC or ABS tube; 50 mm or 1
E: 90° PVC or ABS elbow; inside diameter: 50 mm
Q: PVC or ABS adhesive; supplied by customer
1
or 1
/2”; supplied by customer
customer
1
or 1
/2”; supplied by customer
1
/2”; supplied by
Q
Q
Probe assembly
Mount the single parts as shown in fi g. 6a.
F
E
Fig. 6a
Q
D
C
B
A
A: OXY 4150/3150; diameter 50 mm
B: adaptor with 1
union with diameter 50 mm (081B0028); is
supplied with system packages 1A and 2A
C: adaptor with 1½” and 50 mm outside diameter
(081B0027); is supplied with system packages
1A and 2A
D: PVC or ABS socket; inside diameter: 50 mm or
1½”; supplied by customer
E: PVC or ABS tube; 50 mm or 1½”; supplied by
customer
F: 90° PVC or ABS elbow; inside diameter: 50 mm
or 1½”; supplied by customer
Q: PVC or ABS adhesive; supplied by customer
1
/4” pipe thread (085G3325) or
7
OXY 4100
8
Mounting and replacement of OXY
1100 sensor
Mount the sensor on the ball fl oat as shown in fi g. 7.
At mark 5: Turn until a “click” is heard.
Fig. 7
OXY 4150/3150
Mounting and replacement of OXY
1100 sensor
Mount the sensor on the probe as shown in fi g. 8.
At mark 5: Turn until a “click” is heard.
Fig. 8
9
USC 5000/6000/7000
10
Mounting on a handrail
Mount the bracket on a vertical or horizontal pipe
using the two stainless steel hose clips.
Mounting on a concrete wall
Mount the bracket on to a wall using four screws
(diameter max. 8 mm or 5/16 UN).
Fig. 10
Fig. 9
Fig. 11Fig. 12
USC 6000/7000 19” version
Mounting in panel
First mount the terminal board in the front panel IP
65 (NEMA 4X) enclosure, fi gs. 13 and 14, or the
back of the panel bracket, fi g. 15. Plug in the 19”
USC 6000/7000 signal converter in the enclosure or
bracket using the four small screws to tigthen it.
Fig. 13Fig. 14Fig. 15
11
Optional add-on module USC 6000/7000
12
Unpack the add-on module and locate it in the bottom of the signal converter as shown in fi g. 16.
Press the add-on module forward as far as possible.
See fi g. 17. Avoid touching the pc board and the
sockets.
The add-on module has now been installed and
the signal converter is ready to be installed on the
terminal box. The menus related to the optional
add-on module will automatically become visible
and electrical inputs and outputs are automatically
established by power on.
Fig. 16
Fig. 17
Fig. 18
Optional add-on module USC 6000/7000 19” version
Unpack the add-on module and locate it in the
bottom of the signal converter as shown in fi g. 19.
Press the add-on module forward as far as possible.
See fi g. 20. Avoid touching the pc board and the
sockets.
The add-on module has now been installed and
the signal converter is ready to be installed on the
terminal box. The menus related to the optional
add-on module will automatically become visible
and electrical inputs and outputs are automatically
established by power on.
Fig. 19
Fig. 20
Fig. 21
13
Electrical installation
OXY 4100/4150/3150 stand alone transmitter
14
The transmitter is connected using the two-wire,
shielded cable. The two leads carry supply voltage,
a 4-20 mA current signal, and HART® communication.
+–
EVITA® OXY connected to loop-powered display.
Fig. 22
If the cable is extended, the total length of the cable
must not exceed 1000 m (3000’). Always use twowire, shielded cable for the extension (min. 2 x 0.2
mm2 (24 AWG)).
Red
Shield
Black
Examples of coupling to loop-powered display and
PLC/SCADA system are shown in fi g. 22, fi g. 23 and
fi g. 24, respectively.
A suitable power supply shall be considered
in the end-use application. The power supply
must be a Class 2 power source (limited
circuit) according to the National Electrical
Code (NEC) and provided double/reinforced
insulation between mains and the 12-30 V
d.c. supply for the oxygen transmitter.
Note:Components like motors, pumps and
computers may cause high voltage potential
differences between the protective earth/
ground wire and the water in the tank, that
results in unstable readings. If this problem
occurs, mount an earthing electrode in the
tank to equalise the electrical potential of the
water to PE.
If the fl ow velocity in the tank is high, it may
cause a static potential locally. Is this the
case, mount the earthing electrode close to
the transmitter.
Red
Fig. 23
BlackShield
EVITA® OXY supplied from PLC/SCADA
system.
Fig. 24
Black
Red
EVITA® OXY connected to a PLC/SCADA
system with external power supply.
Shield
15
USC 5000/6000 and OXY 4100/4150 point to point
16
The transmitter is connected using the two-wire,
shielded cable. The two leads carry supply voltage,
a 4-20 mA current signal and HART
®
communication.
If the cable is extended, the total length of the cable
must not exceed 1000 m (3000’). Always use twowire, shielded cable for the extension (min. 2 x 0.2
2
(24 AWG)).
mm
Depending on the USC version the power supply
should be connected to terminals L, N and PE when
using 100-240 V a.c., or to terminals 1 and 2 when
using 24 V a.c./d.c., see fi g. 25 and fi g. 26.
USC 5000/6000 - IP 67 versionUSC 6000 - 19” version
Shield
Black
Red
I out 1
Shield
Black
Red
Relay 3*
Relay 2*
Relay 1*
I out 1
I out 2
Relay 3
Relay 2
Relay 1
On the USC signal converter it is possible to
disable the function of the digital input (used for
calibration control on the EVITA INSITU 4100
transmitter).
Note: The digital input is available on both USC
5000, USC 6000 and USC 7000.
Fig. 26
USC
Input
USC
Digital input
081R9433.02.01
DIG IN
Function
On
On
Off
Fig. 25
I out 2*
Digital input
*Only USC 6000
Digital input
Fig. 25a
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.