GW Instek PEL-2000A Series, PEL-2004A, PEL-2002A User Manual

Programmable DC Electronic Load
PEL-2000A Series
USER MANUAL
GW INSTEK PART NO. 82EL-2004AEA1
ISO-9001 CERTIFIED MANUFACTURER
Visit us at www.TestEquipmentDepot.com
January 2016
This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual may be photocopied, reproduced or translated to another language without prior written consent of the Good Will company.
The information in this manual was correct at the time of printing. However, Good Will continues to improve products and reserves the right to change specification, equipment, and maintenance procedures at any time without notice.
Table of Contents
Table of Contents
SAFETY INSTRUCTIONS ................................................... 5
GETTING STARTED ......................................................... 10
Main Features ...................................... 12
Series Overview ................................... 13
Package Contents and Accessories....... 15
Measurement Overview ....................... 16
Front Panel Overview ........................... 17
Display Overview – Mainframe ............ 23
Rear Panel Overview ............................ 27
Front Panel Overview – Load Module ... 30 LED Display Overview – Load Module .. 34
Installation .......................................... 37
Load Connections ................................ 45
Frame Link Connection ........................ 57
Channel Control Connection ................ 59
Go/NoGo Connection .......................... 62
OPERATING DESCRIPTION ............................................. 63
Operating Mode Description ............... 64
Parallel Unit Mode ............................... 75
Run Program ........................................ 77
Sequence ............................................. 80
OCP Test Automation .......................... 85
Parallel Dynamic Loading .................... 86
Configurations Description .................. 87
Interface and File System ..................... 97
TUTORIALS .................................................................... 104
Local loads ........................................ 105
Single Channel Load .......................... 107
3
PEL-2000A Series User Manual
Parallel Load Modules ........................ 109
Programming ..................................... 111
Sequences .......................................... 113
Frame Link ......................................... 114
Channel Control ................................. 116
General Configuration Options .......... 118
OPERATION ................................................................... 119
Local Mode Operation ....................... 123
Mainframe Basic Operation ............... 130
Creating a Program Sequence ............ 156
Edit Sequence .................................... 169
OCP Test Automation ......................... 179
Channel Configuration ....................... 186
Mainframe Configuration ................... 215
Interface Configuration (settings) ...... 230
Save / Recall ...................................... 236
INTERFACE .................................................................... 267
Interface Configuration ...................... 268
FAQ ............................................................................... 276
APPENDIX ..................................................................... 277
Fuse Replacement .............................. 277
Firmware Update ............................... 278
Calibration ......................................... 279
Range Chart ....................................... 280
Default Settings ................................. 285
Specifications .................................... 287
Dimensions ....................................... 298
EC Declaration of Conformity ............. 300
INDEX ............................................................................ 301
4
SAFETY INSTRUCTIONS
WARNING
Warning: Identifies conditions or practices that could result in injury or loss of life.
CAUTION
Caution: Identifies conditions or practices that could result in damage to THE PEL-2002A/2004A or to other properties.
DANGER High Voltage
Attention Refer to the Manual
Protective Conductor Terminal
Earth (ground) Terminal
SAFETY INSTRUCTIONS
This chapter contains important safety instructions that you must follow when operating the PEL-2002A/PEL-2004A, and when keeping it in storage. Read the following before operating the PEL-2002A/2004A to ensure your safety and to keep the PEL-2000A series in the best possible condition.
Safety Symbols
These safety symbols may appear in this manual or on the PEL­2002A/2004A.
5
Do not dispose electronic equipment as unsorted municipal waste. Please use a separate collection facility or contact the supplier from which this instrument was purchased.
Safety Guidelines
General Guideline
CAUTION
Do not place any heavy object on the PEL-
2002A/2004A.
Avoid severe impact or rough handling that
leads to damaging the PEL-2002A/2004A.
Do not discharge static electricity to the PEL-
2002A/2004A.
Do not block or obstruct the cooling fan vent
openings.
Do not perform measurement at circuits directly
connected to Mains (Note below).
Do not disassemble the PEL-2002A/2004A
unless you are qualified as service personnel.
The equipment is not for measurements
performed for CAT II, III and IV.
(Measurement categories) EN 61010-1:2010 specifies the measurement categories and their requirements as follows. The PEL-2002A/2004A falls under category I.
Measurement category IV is for measurement performed at the
source of low-voltage installation.
Measurement category III is for measurement performed in the
building installation.
Measurement category II is for measurement performed on the
circuits directly connected to the low voltage installation.
Measurement category I is for measurements performed on
circuits not directly connected to Mains.
PEL-2000A Series User Manual
6
SAFETY INSTRUCTIONS
Power Supply
WARNING
AC Input voltage: 115V/230V switchable,
50/60Hz
The power supply voltage should not fluctuate
more than 15%.
Connect the protective grounding conductor of
the AC power cord to an earth ground, to avoid electrical shock.
Fuse
WARNING
Fuse type: T3.15A/250V
Make sure the correct type of fuse is installed
before power up.
To avoid fire, only replace the fuse with the
specified type and rating.
Disconnect the power cord before fuse
replacement.
Make sure the cause of a fuse blowout is fixed
before replacing the fuse.
Cleaning the PEL-2000A
Disconnect the power cord before cleaning.
Use a soft cloth dampened in a solution of mild
detergent and water. Do not spray any liquid.
Do not use chemicals or cleaners containing
harsh material such as benzene, toluene, xylene, and acetone.
Operation Environment
Location: Indoor, no direct sunlight, dust free,
almost non-conductive pollution (Note below)
Temperature: 0°C to 40°C
Altitude: Up to 2000m
Transient Overvoltage on the main supply is
2500V.
7
PEL-2000A Series User Manual
(Pollution Degree) EN 61010-1:2010 specifies the pollution degrees and their requirements as follows. THE PEL-2002A/2004A falls under degree 2.
Pollution refers to “addition of foreign matter, solid, liquid, or
gaseous (ionized gases), that may produce a reduction of dielectric strength or surface resistivity”.
Pollution degree 1: No pollution or only dry, non-conductive
pollution occurs. The pollution has no influence.
Pollution degree 2: Normally only non-conductive pollution
occurs. Occasionally, however, a temporary conductivity caused by condensation must be expected.
Pollution degree 3: Conductive pollution occurs, or dry, non-
conductive pollution occurs which becomes conductive due to condensation which is expected. In such conditions, equipment is normally protected against exposure to direct sunlight, precipitation, and full wind pressure, but neither temperature nor humidity is controlled.
Storage environment
Location: Indoor
Relative Humidity: < 80%
Temperature: −10°C to 70°C
Disposal
Do not dispose this instrument as unsorted municipal waste. Please use a separate collection facility or contact the supplier from which this instrument was purchased. Please make sure discarded electrical waste is properly recycled to reduce environmental impact.
8
SAFETY INSTRUCTIONS
Green/ Yellow:
Earth
Blue:
Neutral
Brown:
Live (Phase)
Power cord for the United Kingdom
When using the PEL-2002A/2004A in the United Kingdom, make sure the power cord meets the following safety instructions.
NOTE: This lead/appliance must only be wired by competent persons
WARNING: THIS APPLIANCE MUST BE EARTHED
IMPORTANT: The wires in this lead are coloured in accordance with the following code:
As the colours of the wires in main leads may not correspond with the coloured marking identified in your plug/appliance, proceed as follows:
The wire which is coloured Green & Yellow must be connected to the Earth terminal marked with either the letter E, the earth symbol or coloured
Green/Green & Yellow.
The wire which is coloured Blue must be connected to the terminal which is marked with the letter N or coloured Blue or Black.
The wire which is coloured Brown must be connected to the terminal marked with the letter L or P or coloured Brown or Red.
If in doubt, consult the instructions provided with the equipment or contact the supplier.
This cable/appliance should be protected by a suitably rated and approved HBC mains fuse: refer to the rating information on the equipment and/or user instructions for details. As a guide, a cable of 0.75mm2 should be protected by a 3A or 5A fuse. Larger conductors would normally require 13A types, depending on the connection method used.
Any exposed wiring from a cable, plug or connection that is engaged in a live socket is extremely hazardous. If a cable or plug is deemed hazardous, turn off the mains power and remove the cable, any fuses and fuse assemblies. All hazardous wiring must be immediately destroyed and replaced in accordance to the above standard.
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
TestEquipmentDepot.com
9
PEL-2000A Series User Manual
Main Features ................................................................. 12
Series Overview ............................................................... 13
Package Contents and Accessories .................................. 15
Measurement Overview ................................................... 16
Front Panel Overview ...................................................... 17
Display Overview – Mainframe ........................................ 23
Rear Panel Overview ........................................................ 27
GETTING STARTED
This chapter describes the features and functions of the PEL-2002A/2004A, including the front and rear panel appearance, panel installation and connection types. Use the Tutorial section for quick access to step by step instructions on the main functions.
10
GETTING STARTED
Front Panel Overview – Load Module ............................... 30
LED Display Overview – Load Module ............................. 34
Installation ..................................................................... 37
Load Module Installation ..................... 37
GPIB Installation ................................. 40
Rack Mount Installation ....................... 41
Channel Number .................................. 42
Power Up & Self Test ........................... 43
Load Connections ........................................................... 45
Precautions and Procedures ................ 45
Remote (Sense) Connection ................. 50
Single Load Connections ...................... 52
Parallel Load Connections.................... 54
Frame Link Connection .................................................... 57
Channel Control Connection ............................................ 59
Go/NoGo Connection ..................................................... 62
11
Main Features
Description
The PEL-2002A and 2004A are multichannel programmable DC electronic load mainframes. The PEL-2002A mainframe is able to hold 2 load modules, whilst the PEL-2004A is able to hold 4. The flexible module configuration allows the mainframes to either sink multiple loads independently or large loads when used in parallel.
The PEL-2000A series support four operation modes: constant current (CC), constant voltage (CV and CV+CC), constant resistance (CR) and constant power (CP). Constant current and constant resistance mode can operate in either static or dynamic mode.
Feature Overview
Flexible operation with removable load modules
Multiple independent isolated channels
High performance, up to 5 digit resolution
High slew rate enabling a high response speed
High capacity when frame linked
Different load module types can be used in the
same mainframe
Dedicated parallel mode.
Supports rack mount installation (PEL-2004A)
Supports frame link connections, with up to 4
slave units
Color LCD display
120 different sets of programmable sequences
Accurate load simulation using Sequences
4 panel setups
USB flash drive support
PEL-2000A Series User Manual
12
GETTING STARTED
Interface
USB
RS-232C
GPIB (optional)
PEL-2020A PEL-2030A
PEL-2004A Mainframe
LOCAL UTILITY
CAL.
F5F4F3F2
ON / OFF
SHIFTPRESET
ENTER
F1
FILEFUNC
LOAD
9
CHAN
87
3
CLEAR
21
0
4 5 6
HELP
P0 LOCK
P3P1 P2
P6P4 P5
P9P7 P8
A / B
DYNA.
STATIC/
SHORTDISPLAY
LOAD
V sense
500V DC
MAX
MAX
500V DC80V DC
MAX
MAX 80V DC
V sense
LOAD
DISPLAY SHORT
STATIC/ DYNA.
A / B
R
80V DC
MAX MAX
80V DC
L
MAX 80V DC
MAX 80V DC
R
V senseV sense
L
LOAD
DISPLAY SHORT
STATIC/ DYNA.
R / L
R / L
DYNA.
STATIC/
SHORTDISPLAY
LOAD
L
V sense V sense
R
80V DC
MAX
80V DC
MAX
L
80V DC
MAX MAX
80V DC
R
R
L 20A / 80V , 100W
DC Electronic Load
20A / 80V , 100W
PEL-2020A
R
L 5A / 80V , 30W
DC Electronic Load
40A / 80V , 250W
PEL-2030A PEL-2040A
DC Electronic Load
70A / 80V , 350W
PEL-2041A
DC Electronic Load
10A / 500V , 350W
DC Electronic Load
PEL-2004A
PEL-2020A PEL-2030A
PEL-2020A PEL-2040A
PEL-2002A Mainframe
P8P7 P9
P5P4 P6
P2P1 P3
LOCKP0
HELP
654
0
1 2
CLEAR
3
7 8
CHAN
9
LOAD
FUNC FILE
F1
ENTER
PRESET SHIFT
OFF
ON /
F2 F3 F4 F5
CAL.
UTILITYLOCAL
80V DC
MAX
MAX 80V DC
V sense
LOAD
DISPLAY SHORT
STATIC/
DYNA.
A / B
R / L
DYNA.
STATIC/
SHORTDISPLAY
LOAD
L
V sense V sense
R
80V DC
MAX
80V DC
MAX
L
80V DC
MAX MAX
80V DC
R
PEL-2040A
DC Electronic Load
70A / 80V , 350W
DC Electronic Load
PEL-2002A
R
L20A / 80V , 100W
DC Electronic Load
20A / 80V , 100W
PEL-2020A
Series Overview
The PEL-2000A series comprises of two different Mainframes: the PEL-2002A and the PEL-2004A. The Mainframes differ by the number of load modules that can be accommodated. The PEL­2002A has two load module slots whilst the PEL-2004A has 4. There are 4 different load module models, the PEL-2020A, PEL-2030A, PEL-2040A and PEL-2041A.
13
PEL-2000A Series User Manual
Load Module
Channels
Power (W)
CH L/R
(low/high
range)
Current (A)
Range
Low/High
Voltage (V)
PEL-2020A
(100Wx2)
2
100/100
2/20
1-80
PEL-2030A
(30/(25/250W))
2
30/(25/250)
5/4/40
1-80
PEL-2040A
1
(35/350)
7/70
1-80
PEL-2041A
1
(35/350)
1/10
2.5-500
The 4 different load module models each differ in the amount of current, voltage and power and the number of channels that the load module can accommodate. The procedures in this manual will be load module model independent unless specifically stated. Below is a table showing the basic differences between each load module model. For detailed specifications, please see page 287.
14
GETTING STARTED
Standard Accessories
Description Power Cable
Mains power cable (region dependent)
CD ROM
Contains PEL-2000A Series Electronic DC Load User Manual, Programming Manual and USB Driver
GTL-120
Load cables 2X red, 2X black (per load module)
GTL-121
Remote sense cables , 1X red, 1X black (per load module)
Options
Description
PEL-2020A
PEL-2030A
PEL-2040A
PEL-2041A
Load Module
PEL-001
GPIB interface (Factory installed)
Optional Accessories
Description PEL-002
PEL-2000A Rack Mount kit (handle only)
GTL-232
RS-232C
GTL-246
USB
GTL-248
GPIB cable
GTL-249
Frame link
Package Contents and Accessories
The PEL-2000A electronic load generator has a number of standard and optional accessories that can be ordered.
15
PEL-2000A Series User Manual
Function
Description
Constant Current Mode (CC)
In constant current mode, the PEL-2002A/2004A will sink a constant amount of current, regardless of the voltage.
Constant Voltage Mode (CV)
Under constant voltage mode, the voltage remains unchanged, regardless of the current.
Constant Resistance Mode (CR)
In constant resistance mode, the resistance load will remain unchanged as the voltage and current remain proportional.
Constant Power Mode (CP)
In constant power mode, the PEL-2000A will ensure the power consumed is constant.
Programmable Sequences (Prog.)
The PEL-2000A series supports programming sequences. With up to 120 different memory settings in 12 programs with 10 sequences.
Sequences (Seq.)
Used to create load profiles to accurately simulate a load. Sequences can be created for each channel.
Parallel Unit Mode
Parallel Unit Mode enables the PEL-2000A mainframes to easily use load modules (of the same type/rating) in parallel. Parallel mode is used in conjunction with CC or CR modes. CP and CV mode cannot be used with this mode.
Measurement Overview
The PEL-2000A series has a number of different operating modes that are completely configurable. All the modes have customizable Go/NoGo limits, range limits, timers, slew rates, alarms and protection limits. For parallel loads, there is a dedicated Parallel configuration mode. To make tests, Programs and Sequences can be created.
16
Front Panel Overview
DC Electronic Load
PEL-2002A
LOCAL
CAL.
F5F4F3F2
ON / OFF
SHIFTPRESET
ENTER
F1
FILEFUNC
LOAD
9
CHAN
87
3
CLEAR
21
0
4 5 6
P0 LOCK
P3P1 P2
P6P4 P5
P9P7 P8
UTILITY
HELP
LCD display
Function keys
System Keys
Number Pad
Operation
keys
PowerUSB input
Selector
Knob
LCD display
320 by 240, TFT LCD display.
Function keys
F1 F5
~
Assigned to the menu functions on the bottom of the display.
GETTING STARTED
17
PEL-2000A Series User Manual
System Keys
LOCAL
CHAN
CHAN/LOCAL is used to select the load channel. Combined with the shift key, Local is used to activate/deactivate local control (during remote control via the interface or frame link connections).
LOCAL
CHAN
Brings up the Channel Menu.
LOCAL
CHAN
SHIFT
Used to activate local control mode during remote control via the interface
FUNC
Used to access the Program, Sequence or Parallel menu.
FILE
Used to access the File menu.
UTILITY
HELP
Brings up the Help menu and utility menu.
UTILITY
HELP
Provides help for the last function /key pressed.
UTILITY
HELP
SHIFT
Activates the Utility Menu.
18
GETTING STARTED
Number pad
CAL.
987
3
CLEAR
21
0
4 5 6
P0 LOCK
P3P1 P2
P6P4 P5
P9P7 P8
Enter numerical values, or to save/recall presets (P0-P9).
0
P0
Number values.
PRESET
0
P0
+
Preset numbers P0­P9.
CAL.
Decimal point and Calibration key
CAL.
Decimal point.
+
CAL.
SHIFT
Activate calibration mode.
Note
Please note, calibration mode is not supported. Please see your distributor for calibration needs.
CLEAR
LOCK
Clears current values. Alternative function locks the keys and the Selector knob.
CLEAR
LOCK
Clears the current value.
+
CLEAR
LOCK
SHIFT
Locks all the keys and Selector knob.
USB Input
USB flash memory slot.
19
Selector Knob
Used to select operations and to increase/decrease values.
When turned left or right moves the cursor in menus or changes the selected item or value.
When pushed down, acts as the Enter key.
Operation Keys
PRESET
Saves and recalls preset settings and values.
When pressed in combination with the number pad, Presets P0-P9 can be recalled or saved.
PRESET
Inactive
PRESET
Active. Used in combination with the number pad and/or shift key.
PRESET
0
P0
+
Press to recall a channel preset
Hold to save a channel preset
PRESET
SHIFT
Press to recall all channel presets.
Hold to save all channel presets.
PEL-2000A Series User Manual
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
20
TestEquipmentDepot.com
GETTING STARTED
SHIFT
The shift key is used to access alternate functions assigned to select keys. The shift key is also used to toggle between coarse and fine control mode when used in conjunction with the selector knob to adjust parameters.
SHIFT
Inactive mode.
SHIFT
Active. When active the shift key can be used to access the Local and Utility menus.
SHIFT
+
Coarse control mode.
SHIFT
+
Fine control mode
ENTER
Confirms selections.
ON / OFF
LOAD
Turns the current load/channel on or off
ON / OFF
LOAD
Load is currently off. (unlit)
ON / OFF
LOAD
Load is currently on. (orange light)
21
PEL-2000A Series User Manual
Power
Turns the unit on or into standby mode.
Standby mode.
On.
22
Display Overview – Mainframe
CV
ConfigureConfigure
Mode
CV
Curr Limit
A Value 80.00 V
40.00 A
SPEC
Slow
Response
Slow
Main
Screen
Menu
Icons
F2
F3
F4 F5
Current
Operation
Channel
Status
Panel
F1
Mainframe
Status
Panel
USB
SEQ
EXT
FRM
Alarm
*CH1
main
80V
B Value 80.00 V
Mainframe Status Panel
The Mainframe Status Panel displays the status of the Mainframe interface, programs and alarm status.
USB
SEQ
FRM
Alarm
Framelink
status
Load
type
Alarm
Interface
status
Frame Link Status
FRS
FRM
Indicates Frame Link is turned on and that the mainframe is set as either a master (FRM) or slave (FRS) unit.
GETTING STARTED
23
PEL-2000A Series User Manual
Load Type
SEQ
PROG
LOAD LOAD
PROG
SEQ
The Load Type Icon indicates if a Sequence (SEQ) or Program (PROG) is turned on. If not then LOAD is displayed as default. When any Load type is running, their icon will turn orange.
Interface Status
USB
GPIB
RS232
The interface status icon displays which interface type is set.
Current Operation Channel Status Panel
The Current Operation Channel Status panel generally displays the status of the current channel.
CV
*CH1
SPEC
Slow
EXT
Channel
Go/NoGo
Channel Control
Mode
main
Voltage Range
Response Speed
80V
Menu
Channel
CH1~ CH8
*CHx CHxS CHxP
Displays the current channel.
* = independent mode S = Parallel Sync mode P = Parallel mode
24
GETTING STARTED
Mode
Displays the current mode.
CCL CCH CCDL CCDH CRL CRH CRDL CRDH CV CPL CPH
CC Static Low Range CC Static High Range CC Dynamic Low Range CC Dynamic High Range CR Static Low Range CR Static High Range CR Dynamic Low Range CR Dynamic High Range CV Mode CP Low Range CP High Range
Go/NoGo
SPEC
If Go/NoGo is turned on, SPEC will be displayed.
Response Speed
Slow Fast
In CV mode the response speed will be shown, Slow or Fast.
Channel Control
EXT
When Channel Control is set to External, EXT will be displayed.
Voltage Range
Displays the voltage range of the current setting.
Menu
Shows the current menu.
main conf s_edit file s_loop
= Chan menu = ChanConfigure menu = ChanSeq.Edit menu = File menu = ChanSeq.EditLoop menu
Main Screen
Main display screen.
25
PEL-2000A Series User Manual
Menu Icons
F1~F5
Each Menu Icon is controlled by the F1~F5 function keys directly below.
26
Rear Panel Overview
AWG 24
STRIP GAUGE
10.0 mm
1
CH CONT 11CH CONT 21CH CONT 31CH CONT 4
1
CH CONT 51CH CONT 61CH CONT 71CH CONT 8
SER. NO. LB
2
1
FRAME CONT
GO / NG OUTPUT
GPIB
RS232C
DISCONNECT POWER CORD
BEFORE REPLACING FUSE
50/60 Hz
180 VA MAX
AC
250V
T 3.15A
REPLACE FUSE
115V
230V
FUSE RATING
AS SPECIFIED
WARNING
TO AVOID ELECTRIC SHOCK THE POWER CORD PROTECTIVE
DO NOT REMOVE COVERS. REFER SERVICING TO QUALIFIED PERSONNEL.
250V FUSE OF THE SPECIFIED TYPE AND RATING.
FOR CONTINUED FIRE PROTECTION. REPLACE FUSE ONLY WITH
NO OPERATOR SERVICEABLE COMPONENTS INSIDE.
GROUNDING CONDUCTOR MUST BE CONNECTED TO GROUND.
Go/NoGo
Output
GPIB
RS232C
USB-B
terminal
USB-A
terminal
Frame Control 1,2
Power switch, Power Socket, Fuse
Channel Control, 1~8
GROUNDING CONDUCTOR MUST BE CONNECTED TO GROUND.
NO OPERATOR SERVICEABLE COMPONENTS INSIDE.
FOR CONTINUED FIRE PROTECTION. REPLACE FUSE ONLY WITH
250V FUSE OF THE SPECIFIED TYPE AND RATING.
DO NOT REMOVE COVERS. REFER SERVICING TO QUALIFIED PERSONNEL.
TO AVOID ELECTRIC SHOCK THE POWER CORD PROTECTIVE
WARNING
AS SPECIFIED
FUSE RATING
230V
115V
REPLACE FUSE
T 3.15A
250V
AC
120 VA MAX
50/60 Hz
BEFORE REPLACING FUSE
DISCONNECT POWER CORD
RS232C
GPIB
GO / NG OUTPUT
FRAME CONT
1
2
SER. NO. LB
CH CONT 41CH CONT 31CH CONT 21CH CONT 1
1
10.0 mm
STRIP GAUGE
AWG 24
Power switch, Power Socket, Fuse
Channel Control, 1~4
Go/NoGo
Output
GPIB
RS232C
USB-B
terminal
USB-A
terminal
Frame Control 1,2
Go/NoGo Output
GO / NG OUTPUT
The Go/NoGo Output terminal outputs a pass (high)/fail (low) voltage for each channel.
See page 274, 62 for details.
PEL-2004A
PEL-2002A
GETTING STARTED
27
PEL-2000A Series User Manual
RS232 port/ GPIB port
RS232C
The RS232 and GPIB port is used for remote control connections.
RS-232C: DB-9 pin male
GPIB: 24-pin female
See pages 268, 269 for remote control details.
USB-A(host)/ USB-B (device) port
The USB-B (device) port, like the RS232/GPIB port is used for remote control. Like the front panel, the USB-A port is used for data storage.
See page 97 for interface details.
Frame Control Port
2
1
FRAME CONT
The Frame Control port is used for Frame Link connections. Mainframes are daisy-chained together. There are two Frame control ports.
1: Slave 2: Master
Connection type: MIL 20-pin connector.
For details about frame link connections see page 57, 271.
Power Switch
External Power Switch
28
GETTING STARTED
Power Socket/ Fuse
The power supply socket accepts the AC mains Voltage. The fuse holder is located below the power socket.
Power: 50/60 Hz (180 VA)
Fuse: T3.15A/250V
For fuse replacement details see page 277.
Channel Control port (1~8)
1
CH CONT 1
Each channel has a dedicated Channel control port to enable external monitoring and control. The channel control port has 6 wire sockets that are screw-less and self clamping.
Required wire gauge: 24 AWG
For connection or specification details see pages 59 & 270.
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
TestEquipmentDepot.com
29
PEL-2000A Series User Manual
R / L
DYNA.
STATIC/
SHORTDISPLAY
LOAD
L
V sense V sense
R
80V DC
MAX
80V DC
MAX
L
80V DC
MAX MAX
80V DC
R
R
L 20A / 80V , 100W
DC Electronic Load
20A / 80V , 100W
PEL-2020A
LED display
R/L A/B Key
Display Key
Load Key
Slave Knob
Static/ Dynamic Key
Short Key
V Sense L
V Sense R
Terminals
(Left)
Terminals (Right)
LED display
2x5 digit custom LED display.
Right/Left Key
or
A/B Key
R / L
A/B
The L/R key is used to switch between the right and left load channel on a dual channel load module. The A/B key is used to switch between A&B Values for single channel load modules.
Display Key
DISPLAY
Used to alternate the display output on the load module.
Front Panel Overview – Load Module
30
GETTING STARTED
Current
Voltage
Power
s
Load time
Load Key
LOAD
Activates the load for the active channel. (Right or Left)(A or B)
Left Voltage Sense
L
V sense
80V DC
MAX
The voltage sense terminals are used when precise measurement is needed. V Sense terminals are used to compensate for voltage drops across the main terminals caused by the resistance of the load wires.
It is automatically activated when connected to a DUT.
Right Voltage Sense
V sense
R
80V DC
MAX
Positive and Negative Terminals Left
L
80V DC
MAX
The terminals for both the left and right side of a load can draw differing amounts depending on the load module specifications.
31
PEL-2000A Series User Manual
Positive and Negative Terminals Right
MAX
80V DC
R
For 2 channel load modules, the left terminals are used for the 1st channel and the right terminals are used for the 2nd channel.
On single channel load modules, the left terminals are the lower (-) potential terminals, whilst the right terminals are the positive (+) potential terminals.
Static/Dynamic Selector Key
STATIC/
DYNA.
The STATIC/DYNA. Key manually switches the load from Static (manual) to Dynamic loads.
Dynamic loads are only supported in CC and CR mode. For more information see page 64 &
67.
Slave Knob (Load)
The Slave Knob is used to edit and vary parameters for the active channel on the local load. Depending on the Mainframe setup, the Slave Knob will either only update the load (locally) or will update both the local module and the mainframe*. The Slave Knob can also be configured to display measured or set values on the local load module**.
* For more information on “Knob Type”, see page 223.
** For more information on “Slave Knob”, see page 227.
32
GETTING STARTED
Short Key
SHORT
The SHORT key is used to manually short circuit the active channel on the local active load. When a load is off, the SHORT key will toggle the Short key type.
Hold: Hold the SHORT key to short the channel load.
Toggle: Press the SHORT key to toggle shorting the load on or off.
Load on: Pressing or holding the SHORT key will short the load, depending on the short type selected.
33
PEL-2000A Series User Manual
1
2
3
5
6
7
4
1
&
2
Channel Display
or
Left and right channel indicator.
5 digit display.
3
&
7
Channel Number Indicator
Indicates the channel number (1-8).
Indicates if the load is active on the load module. (Dual channel load modules)
Indicates if the load is on for single channel load modules.
LED Display Overview – Load Module
34
4
Mode Indicator
The Mode Indicator LEDs will indicate what the current mode or settings are on the active channel(s).
or
Value A or B for a single channel load module. Applies to CR, CV, CP and CC static mode only.
Constant Current Mode (CC) mode activated.
Constant Voltage Mode (CV) mode activated.
Constant Resistance Mode (CR).
Constant Power Mode (CP).
Display is shown on dual channel load modules when both left (L) and right (R) channel information is displayed.
Press the Display button repeatedly to show information for both channels.
Lights up when Go/NoGo is activated and the load passes (GO) the Go/NoGo limits.
or
L or R will light up when the left or right channel is selected.
Lights up when in Static mode.
GETTING STARTED
35
PEL-2000A Series User Manual
Lights up when in Dynamic mode.
Lights up when a load is shorted.
Lights up when Go/NoGo is activated and the load fails (NG) the Go/NoGo limits.
5
&
6
Channel Unit Indicators
The Unit Indicators display the current unit.
Voltage
Resistance
Current
Power
36
GETTING STARTED
WARNING
To avoid static electricity, please use appropriate anti­static work practices.
Module installation
The PEL-2004A and 2002A can accommodate 4 and 2 load modules, respectively. Module loads can have 1 or 2 channels. Installation of load modules is the same for both models.
Steps
1. Ensure the PEL mainframe is turned off from the rear panel. Disconnect the power cord.
2. Slide the module onto the rails of an empty load slot.
Installation
The installation chapter describes how to load the different load modules, install the optional GPIB card, the rack mount kit and how to determine each channel number.
Load Module Installation
37
PEL-2000A Series User Manual
3. Use the supplied screw to fix the module to the load slot, located under the load terminals.
4. Install any additional modules as described above.
5. If there are any slots empty, install the supplied panel cover (GW Instek part number: 63FP-AG106501). The panel cover will improve safety and increase air flow.
38
GETTING STARTED
6. Use the supplied screws to fix the panel cover(s) over the load slot.
39
GPIB Installation
WARNING
To avoid static electricity, please use appropriate anti­static work practices.
GPIB Card installation
The PEL-2004A and 2002A has GPIB as an option (GW Instek part no. PEL-001).
Steps
1. Ensure the mainframe is disconnected from mains power.
2. Remove the screws from the GPIB cover plate and remove the cover plate from the rear panel.
3. Slide the GPIB card into the slot and push gently until the back plate is flush with the rear panel.
1
2
4. Use the screws that were removed from step 1 to secure the GPIB card.
PEL-2000A Series User Manual
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
40
TestEquipmentDepot.com
Rack Mount Installation
Background
The PEL-2004A can be used in a standard 19” rack mount enclosure with the optional rack mount kit (GW Instek part no. 11EL-20040201). Each unit requires a rack height of 4U with a 1U space for ventilation top and bottom. The rear of the rack mount enclosure must be free of obstruction to allow heat to dissipate from the mainframe(s).
Steps
1. Screw the rack mount brackets as shown below using the supplied bolts.
PEL-2004A
2. Insert into a standard 19” rack enclosure with at least 1U of space top and bottom for ventilation.
1U
1U
GETTING STARTED
41
PEL-2000A Series User Manual
Description
The channel number for a module load is determined by which slot it occupies on the mainframe chassis. There can be 1 or 2 channels per slot, depending on the load module type.
The PEL-2002A has two slots; The PEL-2004A has 4 slots. Channel 1 is the farthest away from the main display panel and channel 8 (PEL2004A) or channel 4 (PEL-2002A) is the closest to the main display panel.
Below the PEL-2004A has all 4 slots occupied with the PEL-2020A, 2030A, 2040A & 2041A series load modules (LM), respectively. The PEL-2020A & 2030A have 2 channels per load module, the PEL­2040A & 2041A have only 1. So the channel determination is:
LM1: CH1, CH2; LM2: CH3, CH4; LM3: CH5; LM4: CH6.
CH1
LOCAL UTILITY
CAL.
F5F4F3F2
ON / OFF
SHIFTPRESET
ENTER
F1
FILEFUNC
LOAD
9
CHAN
87
3
CLEAR
21
0
4 5 6
HELP
P0 LOCK
P3P1 P2
P6P4 P5
P9P7 P8
A / B
DYNA.
STATIC/
SHORTDISPLAY
LOAD
V sense
500V DC
MAX
MAX
500V DC80V DC
MAX
MAX
80V DC
V sense
LOAD
DISPLAY SHORT
STATIC/ DYNA.
A / B
R
80V DC
MAX MAX
80V DC
L
MAX
80V DC
MAX
80V DC
R
V senseV sense
L
LOAD
DISPLAY SHORT
STATIC/ DYNA.
R / L
R / L
DYNA.
STATIC/
SHORTDISPLAY
LOAD
L
V sense V sense
R
80V DC
MAX
80V DC
MAX
L
80V DC
MAX MAX
80V DC
R
R
L 20A / 80V , 100W
DC Electronic Load
20A / 80V , 100W
PEL-2020A
R
L 5A / 80V , 30W
DC Electronic Load
40A / 80V , 250W
PEL-2030A PEL-2040A
DC Electronic Load
70A / 80V , 350W
PEL-2041A
DC Electronic Load
10A / 500V , 350W
DC Electronic Load
PEL-2004A
CH2
CH3
CH4
CH5 CH6
Main Display Panel
Channel Number
42
Power Up & Self Test
Panel operation
1. Connect the power cord
to the power socket.
2. Turn the external power
switch on.
3. Hold the power button
on the front panel to turn on the power.
The power button turns green from red (standby).
WARNING
Ensure that the power outlet has a ground socket. The power outlet will have a ground connection if it is a 3 socket type.
Upon turning on, the Mainframe will perform a self-test. The self-test checks the System, followed by any attached channels.
GETTING STARTED
43
PEL-2000A Series User Manual
Initial
CH1 CH2 CH3 CH4 CH5
System
Success Success Success Success Success
Success
When the system check happens, the load modules will display each channel as it is checked, then display the current mode.
4. If any of the System checks fail, please power down the load generator and reinstall the appropriate load module(s).
5. To turn off the load
generator, hold the power button for a few seconds.
The PEL mainframe will return to standby mode.
44
Load Connections
Introduction
The PEL-2000A load generator supports a number of different load configurations for flexible operation.
Single DUT, single load Single DUT, parallel load Multiple DUTs, multiple loads Multiple DUTs, multiple mainframe loads Single DUT, parallel mainframes DC loads Low voltage connections
The PEL-2000A also supports a number of different control methods and interfaces. The connections used are described here:
Frame link Channel control Go/NoGo
Wire Gauge considerations
Before connecting the PEL-2000A, wire gauge must be taken into account. Load wires must be large enough to resist overheating when a short­circuit condition occurs as well as maintain a good regulation. The size, polarity and length of a wire are all factors in determining if a wire will withstand short circuiting.
Precautions and Procedures
GETTING STARTED
45
PEL-2000A Series User Manual
Wire Selection
Wires that are selected must be large enough to withstand a short circuit and limit voltage drops to no more than 2V per wire. Use the table below to help make a suitable selection.
AWG
Max Current A(Amp)
24
7.64
22
10.0
20
13.1
18
17.2
16
22.6
14
30.4
12
40.6
10
55.3
Load Line Inductance Considerations
When using the PEL-2000A load generator, voltage drop and voltage generated due to load line inductance and current change must be taken into account. Extreme changes in voltage may exceed the minimum or maximum voltage limits. Exceeding the maximum voltage limit may damage the PEL-2000A.
To determine the voltage generated, the following equation can be used.
E = L x ( I / T)
E= voltage generated L=load line inductance
I= change of current (A) T= time (us)
Load line inductance (L) can be approximated as 1uH per 1 meter of wire. (∆ I / ∆ T) is the slew rate in A/us.
46
GETTING STARTED
Current
Voltage
time
time
∆I
∆T
E
Min. V
The diagram above shows how changes in current can affect voltage.
Limiting Load line inductance
Load line inductance can be reduced by ensuring load wires are as short as possible and by twisting positive and negative load wires together. Current change can be limited by limiting the slew rate when switching.
“Twisted pair” will be shown on any connection
diagram where the load wires should be twisted together.
DUT
-
+
Programable
Electronic
Load
-
+
Twisted
Pair
DUT
-
+
Programable
Electronic
Load
-
+
DUT
-
+
Programable
Electronic
Load
-
+
47
PEL-2000A Series User Manual
Load module considerations
The PEL-2000A supports single and dual channel load modules.
Single channel load modules have one bank of negative terminals and one bank of positive terminals. Each terminal pair has a 40A capacity. For higher loads, each terminal can be wired in parallel to increase capacity.
Dual channel load modules have one bank of positive and negative terminals for each channel.
Single Channel Load Module
Dual Channel Load Module
Single channel
MAX
80V DC
L
80V DC
MAX MAX
80V DC
R
Left channel
Right channel
Connection
Follow the procedure below for all load connections.
CAUTION
Ensure that power is off from the load generator and the DUT before making any connections.
Steps
1. Carefully lift the terminal covers.
2. Connect the positive (+) terminal on the load module to the high potential output of the DUT.
3. Connect the negative (-) load terminal to the low potential output of the DUT.
48
GETTING STARTED
L
80V DC
MAX MAX
80V DC
R
DUT
4. Close the terminal cover securely. Ensure the wires are secured properly and that the wires are not exposed when the cover is in place.
WARNING
Ensure that the wires are tied or twisted together to prevent noise and inductance.
CAUTION
Ensure the polarity is correct before proceeding with any connections. Using the wrong polarity could result in reverse voltage damage.
L
80V DC
MAX MAX
80V DC
R
DUT
Ensure the input voltage doesn’t exceed specifications.
Exceeding the voltage specifications could result in damage to the instrument.
49
Remote (Sense) Connection
Background
The electronic load modules have two voltage sense contacts: Vsense L(black), Vsense R(red). Voltage sense can be used to help compensate for long cable length. The longer the cable, the higher the potential resistance and inductance, therefore a short cable is best. Twisting the cable can help reduce induced inductance and using the Vsense terminals compensates the voltage drop seen across the load leads, especially leads with higher resistance. This is useful when used in CV, CR or CP mode.
WARNING
VsenseR (red) must have a higher (+) potential than VsenseL (black).
Connection
The diagram below shows how a DUT can be connected using voltage sense. Note that the sense wires are also twisted pairs.
Single Channel
Load Module
-
-
+ +
Twisted
Pair
Twisted
Pair
+ +
-
-
DUT
-
+
Note
The wire gauge for the sense wires should be no smaller than 16 gauge.
Input
The voltage sense terminals must use a wire gauge of 16 to 14.
PEL-2000A Series User Manual
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
50
TestEquipmentDepot.com
GETTING STARTED
Remote Sense Terminal connection
The voltage sense terminals use a screw-less clamp connector. The clamp must be opened prior to inserting a wire. Use a small screwdriver to push the clamp release mechanism. Insert both wires then release the clamp mechanism.
V sense
80V DC
MAX
1
2
51
PEL-2000A Series User Manual
Dual Channel Load Module Connection
A dual channel load module can be used to sink two loads concurrently.
Twisted
Pair
DUT
-
+
Twisted
Pair
DUT
Dual channel Load Module
-
+
-
+
-
+
L
R
Single Channel Load Module Connection
On a single channel load module, the left terminals are both negative (-), whilst the right terminals are both positive (+). Note this also applies to the voltage sense terminals.
Single Channel
Load Module
-
-
+ +
Twisted
Pair
DUT
-
+
CAUTION
For loads exceeding 40A, both positive and both negative terminals must be used in parallel.
Single Channel
Load Module
-
-
+ +
Twisted
Pair
DUT
-
+
Single Load Connections
52
GETTING STARTED
DC Connection
For purely DC operation, a resistor and capacitor can be connected in parallel to the electronic load to reduce oscillation. The capacitor and resistor values are dependent on the load settings. Ensure the capacitor ripple current is within allowable limits.
Twisted
Pair
DUT
Dual channel Load Module
-
+
-
+
-
+
L
R
Low Voltage Connection
Using the load generator with low voltage loads is generally limited to over 1 volt (load module dependent). In order to support low voltage loads, an auxiliary power supply is needed to boost the voltage to a range suitable for the load generator.
Precautions: Take into account the combined power of the
load and auxiliary power supply.
Make sure the auxiliary power supply is able
to provide enough current.
Take into account any noise or irregularities
from the auxiliary supply.
The diagram below shows a typical connection.
DUT
-
+
Load Module
-
+
Auxiliary
+-
WARNING
Using an auxiliary power supply may induce reverse current. The PEL-2000A series has reverse voltage protection. For details see the protection section on page 87.
53
PEL-2000A Series User Manual
Parallel load modules
When the power output of a DUT exceeds the power rating of a channel or load module, the channel terminals, load modules or mainframes can be used in parallel to dissipate more power when used in CC or CR mode. Each channel will sink the amount of current specified. The total power sunk is the sum of all channels/modules. The amount of power can vary from each channel. For example if CH1 is 25A and CH2 is 20A, then the total current sunk is 45A. Parallel loads are supported for both static and dynamic loads (see page 85 for a description on parallel dynamic loading). Note that the same modules must be used when operating the parallel.
The PEL-2000A also features a dedicated parallel configuration setting known as Parallel Unit. When Parallel Unit is turned on, load modules of the same type and rating to be used in parallel for CC and CR mode. See page 75 and 211 for more information.
Parallel Load Connections
54
GETTING STARTED
Parallel load
DUT
-
+
Single Channel
Load Module
-
+
Single Channel
Load Module
-
+
Single Channel
Load Module
-
+
Single Channel
Load Module
-
+
Note
Please note that the same load modules must be used in parallel.
Parallel loads using frame link connections
The PEL-2000A mainframes can also be connected in parallel. Please note, when using a frame link connection there is a delay between the master and the slave. Please see page 57 for details.
DUT
DUT
Slave
Slave
DUT
DUT
DUT
Master
Slave
Slave
Max 7kW
55
PEL-2000A Series User Manual
Multi-output power supply load
The PEL-2000A is also able to sink a number of loads concurrently from multiple DUTs or sink a number of loads from the same DUT (i.e. multiple output power supply).
Twisted
Pair
Multiple-output DUT
Twisted
Pair
Twisted
Pair
Dual channel Load Module
-
+
-
+
L
R
Twisted
Pair
Dual channel Load Module
-
+
-
+
L
R
-
+
-
+
-
+
-
+
56
Frame Link Connection
Background
Frame link control involves connecting multiple mainframes using the frame link connections. Up to 4 slave mainframes can be connected to the master mainframe. The first mainframe (master) can be used to control the other slave frames. There is a delay time of 2ms between the master and first slave mainframe, and 4ms, 6ms, and 8ms to the second, third, and fourth slave mainframes, respectively. The connectors used are standard MIL 20-pin connectors. For pin arrangement, see page 271. The frame link cable (part no. GTL-249) is an optional accessory, see page 15 for details.
Frame Link Connection
RS232C
GPIB
GO / NG OUTPUT
SER. NO. LB
FRAME CONT
1
2
1
CH CONTCH CONT 21CH CONT 31CH CONT 4
1
STRIP GAUGE
10.0 mm
AWG 24
1
CH CONT 51CH CONT 6CH CONT 71CH CONT 8
1
AC
180 VA MAX 50/60 Hz
DISCONNECT POWER CORD BEFORE REPLACING FUSE
REPLACE FUSE AS SPECIFIED
FUSE RATING
115V
230V
T 3.15A
250V
WARNING
TO AVOID ELECTRIC SHOCK THE POWER CORD PROTECTIVE GROUNDING CONDUCTOR MUST BE CONNECTED TO GROUND FOR CONTINUED FIRE PROTECTION. REPLACE FUSE ONLY WITH 250V FUSE OF THE SPECIFIED TYPE AND RATING. NO OPERATOR SERVICEABLE COMPONENTS INSIDE. DO NOT REMOVE COVERS. REFER SERVICING TO QUALIFIED PERSONNEL.
RS232C
GPIB
GO / NG OUTPUT
SER. NO. LB
FRAME CONT
1
2
1
CH CONTCH CONT 21CH CONT 31CH CONT 4
1
STRIP GAUGE
10.0 mm
AWG 24
1
CH CONT 51CH CONT 6CH CONT 71CH CONT 8
1
AC
180 VA MAX 50/60 Hz
DISCONNECT POWER CORD BEFORE REPLACING FUSE
REPLACE FUSE AS SPECIFIED
FUSE RATING
115V
230V
T 3.15A
250V
WARNING
TO AVOID ELECTRIC SHOCK THE POWER CORD PROTECTIVE GROUNDING CONDUCTOR MUST BE CONNECTED TO GROUND FOR CONTINUED FIRE PROTECTION. REPLACE FUSE ONLY WITH 250V FUSE OF THE SPECIFIED TYPE AND RATING. NO OPERATOR SERVICEABLE COMPONENTS INSIDE. DO NOT REMOVE COVERS. REFER SERVICING TO QUALIFIED PERSONNEL.
RS232C
GPIB
GO / NG OUTPUT
SER. NO. LB
FRAME CONT
1
2
1
CH CONTCH CONT 21CH CONT 31CH CONT 4
1
STRIP GAUGE
10.0 mm
AWG 24
1
CH CONT 51CH CONT 6CH CONT 71CH CONT 8
1
AC
180 VA MAX 50/60 Hz
DISCONNECT POWER CORD BEFORE REPLACING FUSE
REPLACE FUSE AS SPECIFIED
FUSE RATING
115V
230V
T 3.15A
250V
WARNING
TO AVOID ELECTRIC SHOCK THE POWER CORD PROTECTIVE GROUNDING CONDUCTOR MUST BE CONNECTED TO GROUND FOR CONTINUED FIRE PROTECTION. REPLACE FUSE ONLY WITH 250V FUSE OF THE SPECIFIED TYPE AND RATING. NO OPERATOR SERVICEABLE COMPONENTS INSIDE. DO NOT REMOVE COVERS. REFER SERVICING TO QUALIFIED PERSONNEL.
2
1
FRAME CONT
2
2
1
FRAME CONT
2
1
2
1
FRAME CONT
1
Output
Master
(FRM)
Output
Input
Input
Slave
(FRS)
Slave
(FRS)
GETTING STARTED
57
PEL-2000A Series User Manual
The first mainframe that is connected is the master frame; any additional frames are slave units. The ribbon cable connects to the master from connector 2, and the slave from connector 1. Each successive slave unit is connected in a cascading manner the same way.
Ensure the Mainframes are turned off before connecting the ribbon cables. Push the cable into the frame link connector. Ensure the arrows line up. The latches will close when the connection is complete. To remove, pull the latches out and connector will come out.
Insertion
Removal
WARNING
Ensure all the mainframes are off and disconnected from mains power before connecting.
58
Channel Control Connection
Background
The Channel Control connecters are located on the rear panel of each mainframe. There are two channel control connectors for each load slot, one for each channel, if applicable. The channel control connector is used to externally:
Turn on/off loads.
Supply a reference voltage.
Monitor the load input.
For further details on channel control and the interface see pages 93, 270.
RS232C
GPIB
GO / NG OUTPUT
SER. NO. LB
FRAME CONT
1
2
1
CH CONTCH CONT 21CH CONT 31CH CONT 4
1
STRIP GAUGE
10.0 mm
AWG 24
1
CH CONT 5
1
CH CONT 6CH CONT 71CH CONT 8
1
AC
180 VA MAX 50/60 Hz
DISCONNECT POWER CORD BEFORE REPLACING FUSE
REPLACE FUSE
AS SPECIFIED
FUSE RATING
115V
230V
T 3.15A 250V
WARNING
TO AVOID ELECTRIC SHOCK THE POWER CORD PROTECTIVE GROUNDING CONDUCTOR MUST BE CONNECTED TO GROUND FOR CONTINUED FIRE PROTECTION. REPLACE FUSE ONLY WITH 250V FUSE OF THE SPECIFIED TYPE AND RATING. NO OPERATOR SERVICEABLE COMPONENTS INSIDE. DO NOT REMOVE COVERS. REFER SERVICING TO QUALIFIED PERSONNEL.
The Channel Control input/output pin layout is shown below.
GND
I MON
V MON
EXT VREF
Load On
+15V
Output
Input
Output
1
2
3
4
5
6
GETTING STARTED
59
PEL-2000A Series User Manual
External Voltage Connection
The external voltage reference input must be between 0~10V.
GND
EXT VREF
External
Voltage
Twisted
Pair
1
2
3
4
5
6
WARNING
Ensure the external voltage reference is stable and has low noise. The External Voltage should be no more than 10V.
No more than 12 volts may be used as an external voltage. More than 12 volts may damage the load generator.
Load on connection
To turn a load on, an active low voltage (0-1V) must be applied across Load On (pin 5) and GND (pin 1), similarly an active high voltage (4-5V) must be applied to turn a load off. The Load On input must be TTL.
TTL input
voltage
GND
Load On
1
2
3
4
5
6
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
60
TestEquipmentDepot.com
GETTING STARTED
Voltage and Current Monitor Output
The Voltage Monitor Output (VMON) and Current Monitor Output (IMON) output the load input voltage and load input current as a percentage of rating current/voltage. Where 0 volts = 0% rating and 10 volts = 100% load input rating voltage or current.
The voltage monitor output is across pins 1 & 3, and the current monitor output is across pins 1 &
2. Pin 6 outputs a +15V reference voltage.
Below shows the pin configuration of the voltage and current monitor outputs.
I MON
V MON
GND
Current Monitor
Voltage Monitor
1
2
3
4
5
6
+15V
Reference voltage
Connector Connection
The channel control connector is a screw less clamp connector. The internal clamp mechanism must be opened before a wire can be inserted. To open the internal clamp, push the button above the wire socket, to close, release the button. Ensure at least 10mm is striped from the wire. The diagram below shows the wire insertion procedure.
1
2
WARNING
All connections to the channel control connector must use a 24 AWG wire gauge.
61
PEL-2000A Series User Manual
Background
The Go/NoGo port is a 15 socket port. Each channel has a dedicated line for a Go/NoGo output. The ports are open-collector with active low (1.1V) indicating a pass and active high (30V) as fail (an alarm). The Go/NoGo terminal is a DB­15 female.
For more details on the Go/NoGo interface see page 274.
GND
CH5 Go/NoGo
CH2 Go/NoGo
CH3 Go/NoGo
CH4 Go/NoGo
Go/NoGo Enable
CH6 Go/NoGo
CH7 Go/NoGo
CH8 Go/NoGo
CH1 Go/NoGo
GND
Go/NoGo Connection
62
GETTING STARTED
Operating Mode Description ........................................... 64
Constant Current Mode ....................... 64
Constant Resistance Mode ................... 67
Constant Voltage Mode ........................ 70
Constant Power Mode .......................... 73
Parallel Unit Mode .......................................................... 75
Run Program ................................................................... 77
Sequence ........................................................................ 80
OCP Test Automation ...................................................... 85
Parallel Dynamic Loading ................................................ 86
Configurations Description ............................................. 87
Protection Modes ................................ 87
Operating Configurations .................... 89
Channel Control ................................... 93
Interface and File System ................................................ 97
Interface .............................................. 97
File System .......................................... 97
File Format ........................................ 102
OPERATING
DESCRIPTION
63
PEL-2000A Series User Manual
Background
In Constant Current Mode the load units will sink the amount of current programmed. Regardless of the voltage, the current will stay the same. There are two ranges in CC mode: High and Low. There are two main modes in CC mode: Static and Dynamic. Static mode can be used for stability tests and dynamic mode can be used to test transient load conditions.
Go/NoGo is supported for both High and Low range as well as Static and Dynamic mode.
CC Mode
Load Current
Load Input Voltage
Operating Mode Description
There are four basic operating modes: constant current (CC), Constant Resistance (CR), Constant Voltage (CV/CV+CC) and Constant Power (CP). All channels operate using any of the modes. Each mode has a number of configurable options including slew rate, levels, protection modes, Go/NoGo and extensive save options.
Constant Current Mode
64
GETTING STARTED
Range
There are two selectable ranges for constant current mode: high and low range.
Low range has a higher resolution, but a lower range. If the current exceeds the Low Range, High range must be used.
Static Functions
Static mode tests the stability of the voltage output from a power source. Single channel load modules can have two 2 current levels A (A Value) & B (B Value). A & B have the same range. Pressing the A/B key on the module load will cycle through the A and B states. Alternatively, the mainframe can select A or B Value.
Dual channel load modules only have one current level (A Value) per channel in static mode.
Static Mode: Single Channel Load module.
Current
A Value
B Value
Slew Rate (rise) Slew Rate (fall)
Time 1 Time 2
CC Mode: Static
Dynamic Functions
Dynamic load functions allow you to set load levels (Level1, Level2), load time (Timer1, Timer2), and the slew rate (rising, falling). Depending on the settings, the load will switch automatically between levels 1 and 2.
Dynamic loading can be used for charge discharge cycle testing etc.
65
PEL-2000A Series User Manual
Current
Time
Level 1
Level 2
Timer 1 Timer 2
CC Mode: Dynamic
Timer 1
Slew rate
The slew rate is the rate at which the current will increase to a set level. There are two slew rates: rising slew rate & falling slew rate. In CC mode the slew rate is defined as A/uS.
Current
Time
Level 1
Level 2
Slew Rate (rise)
A/uS
Slew Rate (fall)
A/uS
Time 1 Time 2
Slew Rate
As can be seen above, the rising and falling slew rate need not be the same.
Go/NoGo
Using Go/NoGo, the Center, High and Low voltage limits can be set for both Static and Dynamic modes. A delay time of up to 1 second can also be set.
66
GETTING STARTED
Load
Current
Voltage
High
Go
Low
CC Mode: Static:Go/NoGo
Current
NoGoNoGo
Current
Voltage
Level 1
Level 2
CC Mode: Dynamic:Go/NoGo
High
Low
Go NoGo
GO is specified as between the Low and High Go/NoGo limits. NoGo is specified as outside the Go/NoGo limits.
Background
In Constant Resistance Mode the load units will linearly sink current and voltage to match a set resistance. CR mode has two different values (single load modules), two different ranges and rising and falling slew rates. Like CC mode, Constant resistance mode supports both dynamic and static loads. As with the other modes, Go/NoGo is supported.
Constant Resistance Mode
67
PEL-2000A Series User Manual
CR Mode
Load Input
Voltage
Load Current
Resistance
Resistance Range
There are two ranges: High and Low. The Low range is used for low voltage ranges, whilst the High range uses high voltage ranges. The current range always remains in High range, regardless of the selected voltage range.
Static Functions A/B range
For static mode, single channel load modules have two resistance levels, A & B Value. The A/B key can be used to switch between these resistance levels. Dual channel load modules only have one resistance level, A Value.
Single Load Module
CR Mode
Load Input
Voltage
Load Current
A Value
B Value
Dynamic Functions
CR mode supports Dynamic loading. Dynamic load has two resistance levels (Level 1&2), and two timers (Timer 1&2) to switch between the resistance levels. Rising and falling slew rates can be set to determine the speed at which the load generator switches between load levels.
68
GETTING STARTED
Dynamic CR Mode
Load Input
Voltage
Load
Current
Level1
Level2
Timer 1 Timer 2 Timer 1
Slew Rate
The rising and falling slew rate (A/uS) determines the speed at which the load levels change from A to B Value (Static mode) or from Level1 to 2 (Dynamic mode) and vice versa.
Go/NoGo
Go/NoGo is also supported. Center, High and Low limits can be set as either percentages or voltage values. A delay time of up to 1 second can also be set.
High
Low
Go
NoGo
NoGo
CR Mode: GO/NOGO
Load Input
Voltage
Load Current
Resistance
69
Constant Voltage Mode
Background
In Constant Voltage Mode the load units will sink current whilst keeping the voltage constant.
Single channel load modules support 2 values (A Value, B Value) and have an adjustable cut-off current limit. Dual channel load modules only have A value.
Response speed can also be set to fast (Fast) or slow (Slow). The response speed relates to the slew rate of the current response.
Constant voltage mode only operates in high range.
Go/NoGo functionality is also supported either as a percentage or as a current value.
CV Mode
Load Input
Voltage
Load
Current
Voltage levels
Two voltage levels can be set: A & B (single channel load module).
PEL-2000A Series User Manual
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
70
TestEquipmentDepot.com
GETTING STARTED
CV Mode
Voltage
Time
A value
B value
CV + CC
When using CV mode, a current limit can be set for CV + CC mode.
When the voltage input is greater than A Value (load voltage) then the channel will operate in CV mode if the input current is less than the current limit. When the input current exceeds the current limit, the channel will operate in CC mode.
When the voltage input is less than A Value (load voltage) current stops flowing.
CV + CC Mode
Load Input
Voltage
Input Current
Current Limit
71
PEL-2000A Series User Manual
Response Speed
Response speed can be set to fast or slow. Fast response and slow response is determined by the load module specifications. Slow response speeds are suitable for large loads as quick current changes will induce induction which can cause large voltage drops. The PEL series will try to rectify any voltage drops. However if voltage drops are too large, they may cause the load generator to go into oscillation. Large voltage drops caused by line voltage induction may damage the machine.
Range
Fast
Slow
1kHz
100Hz
Go/NoGo
Go/NoGo testing can be with either current (Ampere) values (High, Low) or percentage values (Center, High %, Low %). A delay time of up to 1 second can also be set.
CV Mode: GO/NOGO
Voltage
Load
Current
High
Low
Load
Voltage
Go
NoGo
NoGo
72
Constant Power Mode
Background
In Constant Power Mode the load units will ensure a constant power load for the power supply.
Single channel load modules support 2 values (A Value, B Value) and have an adjustable cut-off current limit. Dual channel load modules only have A value.
Constant power mode can operate in high or low range.
Go/NoGo functionality is also supported either as a percentage or as a current value.
CP Mode
Load Input
Voltage
Load Current
Va
Vb
Ia Ib
Power levels
Two power levels can be set: A & B (single channel load module).
GETTING STARTED
73
PEL-2000A Series User Manual
CP Mode
Load Current
A Value
B Value
High/Low Range
There are two ranges: High and Low. The Low range is used for low power ranges, whilst the High range uses high power ranges.
CP Mode
High range
Low range
Go/NoGo
Go/NoGo testing can set High and Low Current limits as a Value (in Amperes) or as a percentage. A delay time of up to 1 second can also be set.
CP Mode
Load Input
Voltage
Load Current
NoGoGo
No Go
74
GETTING STARTED
Background
The Parallel configuration menu allows load modules of the same type and rating to be configured as a single unit when used in parallel. This saves the hassle of configuring each channel individually.
Parallel Configuration is only supported under CC and CR mode.
Parallel Configuration has three configuration settings: Parallel Unit, Parallel Mode and Display Mode.
Parallel Unit
This configuration setting sets the number units that are to be used in parallel and enables or disables the Parallel Unit mode.
Parallel Mode
The Parallel Mode setting determines how the Current Levels/Resistance Values are set when used in parallel. There are two settings: Para and Sync.
The Para setting allows the all the parallelized load modules to be operated as a single large load module.
Sync mode allows the settings of a single unit to be synchronized across all the other parallelized load modules.
Parallel Unit Mode
75
PEL-2000A Series User Manual
CC Example
Consider 3 load modules set to CC mode in Parallel.
In CC mode the total current for all units is the sum of each unit.
nIIII 21 Total
For example, to set a total load current of 90A, the Current Level setting in Para mode would be 90A, whilst it would be 30A in Sync mode.
Para mode
Sync Mode
CCDH
ConfigureConfigure
Mode
CC
Dynamic
Range
High
Level2 SlewRate SlewRate Timer1 Timer2
Level1 90
10
0.80
0.80
0.025
0.025
A A A/uS A/uS mS mS
main
80V
CH1P
LOAD
USB
CCDH
ConfigureConfigure
Mode
CC
Dynamic
Range
High
Level2 SlewRate SlewRate Timer1 Timer2
Level1 30
10
0.80
0.80
0.025
0.025
A A A/uS A/uS mS mS
main
80V
CH1S
LOAD
USB
CR Example
When used in CR mode, the equation for equivalent resistance for all the parallel loads is:
RnRRq
111
R
1
21e
For example, if 2 load modules have a set resistance
of 100Ω each, the equivalent resistance of the load modules would be 50Ω. The Level setting in Para mode would be 50Ω and 100Ω in Sync mode.
Para mode
Sync Mode
CRDL
ConfigureConfigure
Mode
CR
Dynamic
CH1P
Range
High
Level2 SlewRate SlewRate Timer1 Timer2
Level1 50.0000
100.000
0.40
0.40
0.025
0.025
Ω Ω
A/uS A/uS mS mS
main
80V
LOAD
USB
CRDL
ConfigureConfigure
Mode
CR
Dynamic
CH1S
Range
High
Level2 SlewRate SlewRate Timer1 Timer2
Level1 100.000
100.000
0.40
0.40
0.025
0.025
Ω Ω
A/uS A/uS mS mS
main
80V
LOAD
USB
76
GETTING STARTED
Display Mode
Display mode determines what units are displayed on the local load modules: V/I, V/W, I/W, S. The displayed units can only be controlled through this menu.
Background
The Program function on the PEL-2000A series supports a total of 12 different programs at any one time with 10 sequences to each program. Up to 12 programs can be chained together. The Program function is able to create a number of Go/NoGo tests.
Run Program is not supported in Parallel Mode (page 75).
Program Sequence
A program sequence is simply a single load test. A program is a battery of each of these tests run in succession. Each sequence loads the settings for each channel from Memory Data (Memory MXXX). The Memory Data stores settings such as the operating mode and range for each channel. Each sequence loads all channels at the same time, unless programmed otherwise. Sequences for each channel run synchronously.
Time
CH1
Sequence
001
Sequence
002
Sequence
003
CH2
CH3
CH4
CH5 CH5 Active = Off
Run Program
77
PEL-2000A Series User Manual
Each Sequence has a number of configuration options that apply to all the channels equally.
Sequence Item
Description
Memory
Loads the channel settings for each load module Range: M001~M120
Run
Sets the running configuration for the current sequence. The sequence can be skipped, run or run manually only.
Range: Auto | Skip | Manual
On-Time
Sets the Sequence Run On-Time Range: 0.1 ~ 60.0s
Off-Time
Sets the Sequence Off-Time Range: Off | 0.1 ~ 60.0s
Short-time
Sets whether the Short-Time for the sequence.
Range: Off | 0.1s ~ On-time
P/F-Time
Sets the Pass/Fail time for the sequence
Range: Off | 0.1 ~ (On-Time+Off­Time)-0.1s
Short Channel
Selects which channel will be shorted during the sequence
Range: CH1 ~ CH8
Program
Sequences are run sequentially to create a Program. There are 10 Sequences in each Program.
1 2 3 4 5Sequence
Program 1
(P01)
6 7 8 9 10
78
GETTING STARTED
If less than 10 Sequences are desired for a Program, any additional Sequences can be skipped (not run).
1 2 3 4 5Sequence
Program 1
(P01)
6 7 8 9 10
Sequence 2 & 3 are skipped.
Program Chain
Any of the 12 programs can be chained together to create a Program Chain. Unlike Program Sequences, Program Chains need not be run sequentially in numerical order. Any program can be chained to any program. It is possible to chain programs into an infinite loop to continue a program indefinitely.
12 2 3 4 11Program
Program
Chain
1 5 6 7 8 9 10
Above, a program chain running sequences out-of­order.
Go/NoGo Results
If Go/NoGo limits have been configured, the Pass/Fail results for each channel will be displayed for all the sequences and programs.
Start
Exit
PROG
P
1 1 1 1
S
1 2 3 4
1 G G G G
2
N N N
G
Channel
Program no.
Sequence no.
Channel
Go/NoGo
79
Sequence
Background
The Sequence function is used to create high resolution load simulations. Each Sequence can be configured to create a unique load profile to accurately simulate loads in real time. Sequences are only applicable for CC (Static) and CR (Static) modes.
Note: Sequences are not to be confused with the sequences used to create a program. They are not the same and cannot be used interchangeably. Sequences (SEQ memory) cannot be used in Programs and Programs cannot load Sequences.
Load Profiling
The Sequence function is able to simulate a load to a high resolution. Each channel is able to change its load sink within 100us per point independently. When used in parallel, multiple loads can be sunk concurrently to simulate the loads placed on multiple output power sources.
The diagram below shows the load profile of a DUT at start-up.
PEL-2000A Series User Manual
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
80
TestEquipmentDepot.com
GETTING STARTED
Points
Up to 120 points can be used with each Sequence. Each point can have a different duration, slew rate and value.
A new point can be inserted or deleted at any stage of a Sequence. Any new points that are inserted will have a value averaged from its neighbors as default.
Time
Point1
Point2
Point4
Point5
Point6
Point7
Point3
Value
Sequence – Points
A new point is inserted after Point 3.
Loop
Sequences can be programmed to loop a number of times starting from any point in the sequence.
Sequence - Loop
Time
Point1
Point2
Point4
Point3
Value
x2
From Point3 the sequence is looped two times.
81
PEL-2000A Series User Manual
On End Of Seq. function
If more than one Sequence is programmed on the mainframe, the On End Of Seq. function will hold the load current (of the selected sequence) to a designated value until all the other sequences have finished running.
End Of Seq. Example
Time
End Of Seq. = 1 Amps
End of
Sequences
End Of Seq. = OFF
In the example above, Seq. 1 will hold the load current at 1A at the end of its sequence until the last sequence has finished. Seq. 2 is the longest sequence, and as such the End Of Seq. setting is not applicable. Seq. 3 is turned off after its sequence has finished (0 amps).
Trig Out
The Trigger Out function allows a trigger sequence signal to be output from a channel via PIN 4 on Frame Link connector 1 when using Sequences. The Trig Out function is used from the Channel Duration menu.
82
GETTING STARTED
Time
Trig
Out
Time
Value
Point1
Point2
Point3
Point4
Point5
Point6
CH1
Trigger Sequence
As can be seen above, a trigger sequence signal is output for every rising edge point.
Trig In
The Trigger In setting allows a sequence to start after a trigger (Trig Out) has been received via the frame link connector. The Trig In setting is used for frame linked mainframes.
Channel Duration Time Setting
The Channel Duration Time Setting feature allows the point time duration of one Sequence to be imported by another Sequence. If the receiving
sequence doesn’t have enough points, more will be
created (without values).
For example, the sequences for CH1 and CH2 are shown below. CH1 has a total of 6 points with long durations, whilst CH2 has only 2 points, looped 5 times. The points from CH2 are also significantly shorter in duration.
83
PEL-2000A Series User Manual
Time
Value
Time
Value
Point1
Point2
Point3
Point4
Point5
Point6
Point1
Point2
CH1
CH2
Below shows the resulting sequence when CH1 imports CH2. CH1 imports the duration time settings and number of points from CH2, but not the value data.
Time
Value
Point1
Point2
Point1
Point2
Point1
Point2
Point1
Point2
CH1 import CH2
84
GETTING STARTED
Background
The OCP test function creates an automatic test to test the over current protection of power supply products. See page 179 for operation details.
This test will test to see when the over current protection of a power supply is tripped and return the measurements for the voltage and current when the over current protection was tripped. The PEL-2000A also has a user-defined OCP setting in the event that the power supply OCP fails.
The diagram below shows an example of the OCP Test Automation function.
OCP Test Automation
85
Parallel Dynamic Loading
Background
The PEL-2000A series of DC electronic loads support parallel dynamic loading. This simply means that when the load modules of a mainframe are connected in parallel and set to dynamic mode, they can perform dynamic tests synchronously following the same clock. Under dynamic mode, load current or resistance is pulsed between two preset levels. When used in parallel, higher powered outputs can be tested. This ability gives the PEL-2000A series the flexibility to perform dynamic tests over a wide range of power outputs.
For connection details see the Parallel Load Connections section on page 54.
The diagram below shows how two load modules are able to sink a higher load when used in parallel under dynamic mode.
Total load
Load 2
Load 1
Note
Note: The same type of load modules must be used operated in parallel.
PEL-2000A Series User Manual
86
Background
The PEL-2000A series include a number of protection modes: Over Current Protection, Over Voltage Protection, Over Power Protection, Under voltage protection and Constant Power Protection.
The protection modes are useful to protect both the load modules and the DUT(s). A buzzer can be set to notify when a protection setting has been tripped. When a protection feature is activated and has been tripped then the load unit will display an alarm. The Mainframe will also display an alarm. When an alarm has been tripped the load will stop sinking current/voltage. There are three Over load protection settings: ON, OFF and Clear.
CCDH
Configure
Previous
Menu
Protection
Go-NoGo
CH1
Other
OCP Setting OVP Level OVP Setting OPP Level OPP Setting
OCP Level A
V
W
5.075 OFF
81.6
ON
29.75 OFF
Alarm
Conf
80V
GETTING STARTED
Configurations Description
There are a number of different configurations for the PEL series including protection modes, operating configurations, and file system configurations. The Configuration Description section describes what the different configurations are used for and how they can be relevant to different operations.
Protection Modes
87
PEL-2000A Series User Manual
Over Current Protection
When a load unit is operating in CR, CV or CP mode, the unit may need over current protection to prevent excessive current being sunk. Over current protection stops the load from sinking more current than its recommended limit which can cause damage to the unit.
CV Mode: OCP
V
I
OCP level
CR Mode: OCP
V
Resistance
OCP level
CP Mode: OCP
V
I
OCP level
Power
I
Over Voltage Protection
Over voltage protection is used to limit the amount of voltage sunk. If the OVP trips, the PEL series load will stop sinking voltage.
CC Mode: OVP
CP Mode: OVP
V
I
OVP level
Power
V
I
OVP level
88
GETTING STARTED
Over Power Protection
Over power protection is used when the power range exceeds the specifications of the load. When OPP is tripped power will cease to be sunk.
Reverse voltage Protection
Reverse voltage protection prevents reverse voltage damage to the PEL-2000A series up to the specified rating. When Reverse voltage protection has been tripped an alarm tone will sound until the reverse voltage is removed.
For more details please see the specifications.
Under voltage Protection
Under voltage protection will turn off the load when the voltage drops below a set limit.
Constant Power Protection
Constant power protection will prevent excessive power draw.
Background
There are number of operating configuration settings. Configuration settings are for the following:
CC Vrange, Von Voltage, Von Latch, Short Key, CH Cont, Independent load sync, D-time, Step resolution settings and Response settings.
CC Vrange
CC Vrange (page 192) is used to set the voltage range as High or Low for CC mode. CC voltage range is dependent on the load module specifications.
Operating Configurations
89
PEL-2000A Series User Manual
Von Voltage
Von Voltage is the voltage limit at which the load will start to sink current. There are two operation modes for Von Voltage: Von latched: ON and Von latched: OFF.
Latched: ON will sink current when Von has been tripped, and will continue to sink current even if the voltage drops below the Von Voltage.
Von Latched: OFF will sink current when Von has been tripped, but will stop sinking current when the voltage drops below the Von Voltage setting.
Von Latch: ON
time
time
load
Output
PEL Load
V
I
Von Latch: OFF
time
time
load
Output
PEL Load
V
I
Von
Von
As can be seen in the diagram below, when Von-Latch is set to off, the load module will start to sink current when the Von-voltage limit has been tripped. It will stop sinking current when the output drops below the Von voltage limit.
Von Latch: OFF - Start
time
Von Latch: OFF - Stop
Output
time
time
PEL Load
time
V
I
load
load
Von
Output
PEL Load
V
I
Von
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
90
TestEquipmentDepot.com
GETTING STARTED
Short
When short mode is on, the load unit can simulate a short circuit.
Shorting can be individually set for each channel when programming sequences.
To initiate a short circuit manually, the short key is used. It can be used at any time during an operation. It will not affect the settings. After a short circuit has finished, the load unit will resume the previous operation.
The short key can be set to toggle or hold. When pressed in toggle mode, shorts are toggled on and off. When pressed in hold mode, the key needs to be held to short the load.
Note
A short circuit may trip a protection mode if too much current is sunk.
CH CONT
Channel Control. When Channel control is activated (External) it can be used to monitor the voltage and current output of the load as well as turn loads on or off remotely from the Channel Control (CH CONT) connectors located on the rear panel.
For more information about channel control, see external voltage control on page 93.
Independent
The Independent setting will allow the load modules to be controlled independently from the mainframe.
91
PEL-2000A Series User Manual
Load D-Time
Load Delay time is used to delay activating a load (up to 10 seconds) after the load key has been pressed. However the Load D-Time setting will only work for loads that are initiated manually or when the PEL series mainframe is configured to Auto load (page 217) at run time.
Step Resolution
Each channel voltage, current and resistance setting can have the step resolution configured. The step resolution refers to the step resolution of the coarse adjustment of these settings. The fine adjustment cannot be configured, see page 202 for details.
For example if the step resolution for CCH (CC high range) is .5 A, then the resolution can be incremented in .5A steps;
8.08.59.09.5
The step resolution parameters apply to the following:
CCH Step – CC high range CCL Step – CC low range CRH Step – CR high range CRL Step – CR low range CV Step – CV high range
Step Resolution Range
The step resolution range is dependent on the load module and the range:
Max resolution: Module dependant, see page 202
Min resolution: Channel range/2
Response
The Response setting sets the bandwidth of the load generator to 100kHz(normal) or 1MHz(fast). The Response setting is particularly important for limiting startup current.
92
GETTING STARTED
Background
External channel control is used with the Channel Control connectors. Each channel control connector can activate each load, monitor voltage and current and has an external voltage reference input. The voltage and current monitors output 0~100% of the rated current/voltage as a voltage of 0~10V.
RS232C
GPIB
GO / NG OUTPUT
SER. NO. LB
FRAME CONT
1
2
1
CH CONTCH CONT 21CH CONT 31CH CONT 4
1
STRIP GAUGE
10.0 mm
AWG 24
1
CH CONT 51CH CONT 6CH CONT 71CH CONT 8
1
AC
180 VA MAX 50/60 Hz
DISCONNECT POWER CORD BEFORE REPLACING FUSE
REPLACE FUSE
AS SPECIFIED
FUSE RATING
115V
230V
T 3.15A 250V
WARNING
TO AVOID ELECTRIC SHOCK THE POWER CORD PROTECTIVE GROUNDING CONDUCTOR MUST BE CONNECTED TO GROUND FOR CONTINUED FIRE PROTECTION. REPLACE FUSE ONLY WITH 250V FUSE OF THE SPECIFIED TYPE AND RATING. NO OPERATOR SERVICEABLE COMPONENTS INSIDE. DO NOT REMOVE COVERS. REFER SERVICING TO QUALIFIED PERSONNEL.
External Voltage Reference
A voltage reference of 0-10V is used to represent 0­100% of the rating voltage/current of a load module. As seen below the external voltage reference and the rating voltage/current have a linear relationship. By varying the reference voltage between 0~10V the voltage/current setting will be changed accordingly.
External Voltage Control
Voltage/
Current Setting
(Percent
Rating)
External Voltage
100%
0%
10V
0V
Channel Control
93
PEL-2000A Series User Manual
To determine the Percent Rating (voltage or current load input), use the following formula;
VorARating
V
VoltageExternal
InputLoad
10
Where Rating V or A is the rating voltage/current of the load module.
Current Monitor
The load current input can be externally monitored using the IMON pin of a channel control connector. The IMON pin outputs a voltage of 0~10V to represent the input current as a percentage (0~100%) of rating current.
Current Monitor
Current Monitor
Output
Load Input Current
10V
0V
Rating current
0A
To determine the Current Monitor Output (IMON) , use the following formula;
V
ARating
currentinputLoad
IMON 10
Where “Rating A” is the rating current of the load module.
94
GETTING STARTED
Voltage Monitor
The input voltage, like the load input current can be externally monitored with the channel control connectors. The VMON pin of the channel control connector outputs a voltage of 0~10V to represent the load input voltage as a percentage (0~100%) of the rating voltage.
Voltage Monitor
Voltage Monitor
Output
Load Input
Voltage
10V
0V
Rating voltage
0V
To determine the Voltage Monitor Output (VMON) , use the following formula;
V
VRating
voltageinputLoad
VMON 10
Where “Rating V” is the rating voltage of the load module.
95
PEL-2000A Series User Manual
Turning on the Load
A load is turned on when Load On input is set to On (active low). A load is turned off when the Load On input is set to Off (active high).
When a load is turned on from the channel control interface, the load can be turned off from the mainframe, local module and via remote control. However the opposite is not true; when a load is turned off using the channel control interface, the load cannot be turned on via the mainframe, local module or via remote control.
For connections and configurations, see pages 59 and 270 respectively.
96
Interface and File System
Background
RS-232 configuration.
Page 231
RS-232 pin connection.
Page 268
GPIB configuration.
Page 233
GPIB pin configuration.
Page 269
USB configuration.
Page 234
Background
The PEL series is able to save and recall a number of different data types for each channel:
Presets Memory Setup SEQ (Sequence)
All data types can be saved and recalled to internal memory or saved to a USB flash drive. Each channel has its own dedicated memory for each
Interface
The PEL-2000A series support RS232, GPIB and USB remote frame control. Only one type of connection is supported at any one time.
For connection options and configurations see the options below.
GETTING STARTED
File System
97
PEL-2000A Series User Manual
data type. Thus files are saved/recalled for each channel and each data type.
Preset Data
Preset data can be saved into 10 memory slots for each channel. Preset data contains the mode, range, CV response speed and Go/NoGo settings.
Internal Format
External Format
P0~P9
20X0X_XX.P
Preset Contents
Preset data contains the following data;
CHAN
Mode
Range
Static/Dynamic
CV response
speed
Go/NoGo
SPEC Test
High
Center
Entry Mode
Low
Memory Data
Each channel can save up to 120 different Memory data types (M001~M120) into internal memory. Memory data contains general channel settings and is used when programming sequences. Memory data can be stored both internally and
externally to USB. Preset data and Memory data store the same contents.
Internal Format
External Format
M001~M120
20X0X_XX.M
Memory Contents
Memory data contains the following data;
CHAN
Mode
Range
Static/Dynamic
CV response
speed
Go/NoGo
SPEC Test
High
Center
Entry Mode
Low
98
GETTING STARTED
SEQ Data
SEQ data contains Sequence data. SEQ data can only be saved to and from USB. SEQ refers to Sequence data, not Program sequences.
Internal Format
External Format
N/A (Internal buffer)
20X0X_XX.A
SEQ Contents
SEQ data contains the following data;
Seq.Edit
No. (Points)
Slew rate
Duration time
Value
Slew rate
Loop
Repeat
On End Load
Start of Loop
CC Vrange
Setup Data
Setup data can be saved to 4 internal memory slots. Setup data contains Memory data, Program Sequence, Chain data, configuration settings and operation settings for every channel. Setup data can be saved to Internal memory or to USB.
Internal Format
External Format
Setup Memory 1~4
200X0_XX.S
Setup Contents
Setup data contains the following data;
Program
PROG
Memory
On-Time
P/F-Time
Short Channel
SEQ (program
sequence no.)
Run
Off-Time
Short-Time
Chain
Start
Program
Sequence (P01~P12)
99
PEL-2000A Series User Manual
Run
Active Channel
(CH01~08)
CHAN
Mode
Range
Static/Dynamic
CV response
speed
Go/NoGo
SPEC Test
High
Center
Entry Mode
Low
Save: Internal memory
When saving data to internal memory, either the current channel or all the channel data can be saved. Not all data types can save the current channel or all the channel data.
Data Type
Current Ch
All Ch
Preset
Memory
SEQ
(single save)
Setup
Save: External memory
Only SEQ, Memory and Preset data can be saved for a single channel to USB. All four data types (SEQ, Memory, Setup, Preset) can save all channels to USB.
Data Type
Current Ch
All Ch
Preset
Memory
SEQ
Setup
Test Equipment Depot - 800.517.8431 - 99 Washington Street Melrose, MA 02176
100
TestEquipmentDepot.com
Loading...