BTUs per Gauge Pressure (PSI) - Natural Gas Models (Approximate) ..................................... ... ... 24
Chapter 6 Service .............................................................................................................................................. 25
Chapter 7 Troubleshooting - Standard Heater................................................................................................ 26
Chapter 9 Parts List .......................................................................................................................................... 30
Standard Heater Control Box Parts ..................... ... ... .... ... ... ... .... ... ... ... ... .... ...................................... 30
Deluxe Heater Control Box Parts ..................................................................................................... 32
18" Gas Heater Parts .......................... ... ... ... .... ... ... .......................................................................... 33
24", 26" and 28" Gas Heater Parts ................................................................................................... 34
This manual contains information that is important for you, the owner/operator, to know and understand.
This information relates to protecting personal safety and preventing equipment problems. It is the
responsibility of the owner/operator to inform anyone operating or working in the area of this equipment
of these safety guidelines. To help you recognize this information, we use the symbols that are defined
below. Please read the manual and pay attention to these sections. Failure to read this manual and its
safety instructions is a misuse of the equipment and may lead to serious injury or death.
This is the safety alert symbol. It is used to alert you to
potential personal injury hazards. Obey all safety
messages that follow this symbol to avoid possible
injury or death.
DANGER indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a
potentially hazardous situation which, if not avoided, may
result in property damage.
NOTE indicates information about the equipment that you
should pay special attention.
4PNEG-012 Vane Axial Heater
Page 5
1. Safety
Introduction
Thank you for choosing a GSI product. It is designed to give excellent performance and service for
many years.
This manual describes the operation of the Deluxe and Standard Vane Axial Heater: VHD and VHS. It
is designed for low to medium temperature grain conditioning, and is ideal for the aeration of rice,
popcorn or other select grains. It is available in both propane vapor and natural gas models.
Our foremost concern is your safety and the safety of others associated with this equipment. We want
to keep you as a customer. This manual is to help you understand safe operating p rocedures and some
problems which may be encountered by the operator and other personnel.
As owner and/or operator, it is your responsibility to know what requirements, hazards and precautions
exist, and to inform all personnel associated with the equipment or in the area. Safety precautions may
be required from the personnel. Avoid any alterations to the equipment. Such alterations may produce
a very dangerous situation where SERIOUS INJURY or DEATH may occur.
This equipment shall be installed in accordance with the current installation codes and applicable
regulations which should be carefully followed in all cases. Authorities having jurisdiction should be
consulted before installations are made.
PNEG-012 Vane Axial Heater5
Page 6
2. Safety Decals
If a decal is damaged or missing contact:
GSI Decals
1004 E. Illinois St.
Assumption, IL. 62510
Phone: 1-217-226-4421
A free replacement will be sent to you.
Roof Damage Warning and Disclaimer
The manufacturer does not warrant any roof damage caused by excessive vacuum or internal
pressure from fans or other air moving systems. Adequate ventilation and/or “makeup air”
devices should be provided for all powered air handling systems. The manufacturer does not
recommend the use of downward flow systems (suction). Severe roof damage can result from
any blockage of air passages. Running fans during high humidity/cold weather conditions can
cause air exhaust or intake ports to freeze.
CAUTION!
Excessive vacuum (or pressure) may
damage roof. Use positive aeration
system. Make sure all roof vents are
open and unobstructed. Start roof
fans when supply fans are started.
Do not operate when conditions exist
that may cause roof vent icing.
DC-969
6PNEG-012 Vane Axial Heater
Page 7
Heater Access Door Decals
WARNING
2. Safety Decals
DC-1225
Stay clear of rotating
blade. Blade could start
automatically. Can cause
serious injury. Disconnect
power before servicing.
DC-1225
WARNING
Flame and pressure beyond
door can cause serious
injury. Do not operate with
service door removed. Keep
head and hands clear.
DC-1227
DC-113
Size: 4.75" x 1.625"
Located above access door on
heater housing.
Size: 4.875" x 2.25"
Located above access door on
heater housing.
See Note below.
DC-1227
Size: 4.875" x 2.25"
Located above access door on
heater housing.
See Note below.
NOTE: May be substituted with DC-1559 combination decals.
PNEG-012 Vane Axial Heater7
Page 8
2. Safety Decals
Control Box Decals
DC-889
Size: 2.813" x 1.375"
Located in control box on side
opposite switches.
Similar decal is incorporated into the
control panel decal.
WARMER
VAPORIZER ADJUSTMENT
VAPORIZER COIL SHOULD BE ADJUSTED
SO VAPOR PIPE TRAIN IS WARM
(100°F-125°F) TO THE TOUCH
COLDER
DC-535
8PNEG-012 Vane Axial Heater
Page 9
Heater Specifications
Fan Model18"24"26"28"
Inside Diameter (inches)18-5/16"24-1/4"26-5/16"28-1/8"
Bolt Circle Diameter (inches)19-7/16"25-3/4"27-15/16"29-5/8"
Length (inches)2222-1/2"22-1/4"25-1/4"
Weight (pounds)83129133136
Fan Model18"24"26"28"
Minimum Operating Pressure (PSI)2222
Maximum Operating Pressure (PSI)15101520
Minimum Supply Line (inches)1/2"3/4"3/4"3/4"
High Temperature Orifice (inches)11/64"7/32"7/32"7/32"
High Temperature BTU Rating at Maximum Pressure1,400,000 2,100,000 2,700,000 3,000,000
High Temperature Fuel Flow at Maximum Pressure (CFH)58587711281253
Low Temperature Orifice (inches)3/32"3/32"3/32"3/32"
Low Temperature BTU Rating at Maximum Pressure400,000350,000400,000500,000
Low Temperature Fuel Flow at Maximum Pressure (CFH)167146167208
3. Specifications
Common Measurements
Vapor Models
Liquid Models
Fan Model18"24"26"28"
Minimum Operating Pressure (PSI)N/A222
Maximum Operating Pressure (PSI)N/A101520
Minimum Supply Line (inches)N/A3/8"3/8"3/8"
High Temperature Orifice (inches)N/A7/32"7/32"7/32"
High Temperature BTU Rating at Maximum PressureN/A2,100,0002,700,0003,000,000
High Temperature Fuel Flow at Maximum Pressure (CFH)N/A233034
Low Temperature Orifice (inches)N/A3/32"3/32"3/32"
Low Temperature BTU Rating at Maximum PressureN/A350,000400,000500,000
Low Temperature Fuel Flow at Maximum Pressure (CFH)N/A44.55.5
Natural Gas
Fan Model18"24"26"28"
Minimum Operating Pressure (PSI)1111
Maximum Operating Pressure (PSI)7457
Minimum Supply Line (inches)3/4"1"1-1/4"1-1/4"
High Temperature Orifice (inches) 17/64"3/8"3/8"3/8"
High Temperature BTU Rating at Maximum Pressure1,400,000 2,100,000 2,700,000 3,000,000
High Temperature Fuel Flow at Maximum Pressure (CFH)1400210027003000
Low Temperature Orifice (inches)11/64"7/32"7/32"7/32"
Low Temperature BTU Rating at Maximum Pressure400,000350,000400,000500,000
Low Temperature Fuel Flow at Maximum Pressure (CFH)400350400500
PNEG-012 Vane Axial Heater9
Page 10
4. Installation
Fuel Connection
Do not use propane tanks which have previously been used for ammonia unless
they have been purged according to procedures of the national LP association.
Investigate to be sure that the fuel supply system complies with all local codes for
LP gas installations.
Liquid Propane Models
1. LP models are designed to run on liquid propane, with liquid draw from the propane tank. Avoid
using propane supply tanks that have been use for vapor draw for long periods of time. Wh en using
liquid draw systems any moisture that may be present in tank or lines may freeze when system is
used in cold weather. To avoid this, the usual precaution is to purge the system with methanol.
2. Run proper size line
service person inspect installation to be sure everything is installed according to local codes
and ordinances.
3. After installation is complete check all connections for leaks. Use liquid detergent or comparable
substance. Wear rubber gloves and eye protection. Avoid contact with liquid propane. DO NOT
USE FLAME FOR LEAK TESTING.
(See Specifications on Page 9)
to pipe train on heater. Have a qualified gas
Propane Vapor Models
1. Propane vapor models are designed to run directly off of supply tank or from a separate
external vaporizer.
2. Run proper size line
service person inspect installation to be sure everything is installed according to local codes
and ordinances.
3. After installation is complete check all connections for leaks.
(See Specifications on Page 9)
to pipe train on heater. Have a qualified gas
Natural Gas Models
1. Natural gas models are similar to vapor models, but have a larger orifice to accommodate lower
pressure, sometimes found with natural gas.
2. Run proper size line (See Specifications on Page 9) to pipe train on heater. Have a qualified gas
service person inspect installation to be sure everything is installed according to local codes
and ordinances.
3. After installation is complete check all connections for leaks.
Standard Heater Electrical Installation
Always disconnect and lock out power before working on or around heater.
Standard electrical safety practices and codes should be used when working with a heater. Refe r to the
National Electric Code Standard Handbook by the National Fire Protection Association. A qualified
electrician should make all wiring installations.
10PNEG-012 Vane Axial Heater
Page 11
IMPORTANT: Heater must be interlocked with fan for safe operation.
Heater Power Connection
1. Connect power cord to fan control box.
2. Make field connections in fan box as shown in Figure 4A.
3. Connect deluxe thermostat control as shown in Figure 4A.
IMPORTANT: Thermostat must be installed for safe operation.
4. Installation
Figure 4A Heater Wiring Installation on a Fan Unit
PNEG-012 Vane Axial Heater11
Page 12
4. Installation
Standard Heater - Second Heater Installation
Two (2) standard heaters may be connected to one grain drying system and wired so they cycle together.
One of the heaters should have a thermostat connected to it as per the installation instructions. That
heater will be referred to as the primary. The other heater (without the thermostat) will be referred to as
the secondary.
1. Install relay base (TD-100283) in primary heater control box.
2. Connect wire between terminal 13 on relay base to terminal 6 on terminal strip in primary heater.
3. Connect wire between terminal 14 on relay base to terminal 3 on terminal strip in primary heater.
4. Run two (2) wires (18 gauge) between primary and secondary heater.
5. Connect wires to terminals 5 and 9 (points A and B) on relay base in primary heater.
6. Connect wire from terminal 9 in primary to terminal 5 (point F) in secondary unit.
7. Connect wire from terminal 5 in primary to terminal 8 (point G) in secondary unit.
8. Install relay (TD-100282) in relay base.
Follow these additional steps for HIGH-LOW units.
1. Install relay base (TD-100283) in master heater control box.
2. Connect wire between terminal 13 (point E) on relay base to green wire from HIGH-LOW thermostat
in master unit. Do not disconnect other wires from green wire 3. Connect wire between terminal 14
on relay base to terminal 14 on other relay base in master heater.
3. Run two (2) wires (18 gauge) between master and slave heater.
4. Connect wires to terminals 5 and 9 (points C and D) on relay base in master heater.
5. Connect wire from terminal 9 in master to terminal 6 (point H) in slave unit.
6. Connect wire from terminal 5 in master to cycle solenoid and red light in slave unit. Do not connect
wire to side of cycle solenoid and light that are connected to terminal.
Figure 4B Standard Heater - Second Heater Relay Connection
12PNEG-012 Vane Axial Heater
Page 13
4. Installation
Deluxe Heater Electrical Installation
Always disconnect and lock out power before working on or around heater.
Standard electrical safety practices and codes should be used when working with a heater. Refer to the
National Electric Code Standard Handbook by the National Fire Protection Association. A qualified
electrician should make all wiring installations.
IMPORTANT: Heater must be interlocked with fan for safe operation.
Heater Power Connection
1. Connect power cord to fan control box.
2. Make field connections in fan box as shown in Figure 4C.
3. Connect deluxe thermostat control as shown in Figure 4C.
IMPORTANT: Thermostat must be installed for safe operation.
Figure 4C Illustration of deluxe Vane Axial Heater wiring installation on a fan unit.
PNEG-012 Vane Axial Heater13
Page 14
4. Installation
Deluxe Heater - Second Heater Installation
For Deluxe Units Using HF-7318 Control Board
Two (2) deluxe heaters may be connected to one grain drying system and wired so they cycle together.
One of the heaters should have a thermostat connected to it as per the installation instructions. That
heater will be referred to as the master. The other heater (without the thermostat) will be referred to as
the slave.
Installation for ON/OFF Units
1. Install relay base (TD-100283) in master heater control box.
2. Connect wire between terminal 6 on circuit board and terminal 14 on relay base in master heater.
3. Connect wire between terminal 13 on relay base and terminal 8 on circuit board in master heater.
4. Run two (2) wires (18 gauge) between master and slave heaters.
5. Connect wires to terminal 5 and 9 (points A and B) on relay base in master heater.
6. Connect wire from terminal 9 in master to terminal 14 (point F) in slave unit.
7. Connect wire from terminal 5 in master to terminal 15 (point E) in slave unit.
8. Install relay (TD-100282) in relay base.
Additional Steps for High-Low Units
1. Run two (2) wires (18 gauge) between master and slave unit.
2. Connect wires to terminals 21 and 22 (points C and D) on circuit board in main heater.
3. Connect wire from terminal 21 in master to terminal 12 (point H) in slave unit.
4. Connect wire from terminal 22 in master to terminal 13 (point G) in slave unit.
5. Install relay (TD-100282) in relay base.
Figure 4D The Control Board (HF-7318)
14PNEG-012 Vane Axial Heater
Page 15
Bin Configuration
4. Installation
Figure 4E
IMPORTANT: When mounting two (2) heate rs on a bin it is imperative that they be situated as shown in
Figure 4E. Plenum thermostat must be to the right of master heater and master heater
must be to the right of slave heater.
Transition High-Limit Installation
1. Mark location on transition one (1) foot up from the bottom (entrance collar) and centered in
the transition.
2. Drill or knock out 7/8" diameter hole on marked location.
3. Install transition high-limit using supplied self-drilling screws.
Figure 4F The transition connecting the Vane Axial Heater to the bin with the plenum sensor in place.
PNEG-012 Vane Axial Heater15
Page 16
4. Installation
Plenum Thermostat Mounting
The plenum thermostat must be ordered separately from the heater unit.
1. Follow installation instructions provided with the thermostat assembly.
2. Position the housing so that the bolt flanges are vertical, and the cord exits the housing from the
bottom. Mark position.
3. Use 6 (4.00") or 8 (2.66") self-drilling screws to mount the housing to the bin sidewall. DO NOT
TIGHTEN COMPLETELY. Insert corrugation seal into gap between housing and sidewall.
Tighten screws.
4. Caulk between the housing and the sidewall to seal.
Figure 4G Plenum thermostat mounted on bin wall.
IMPORTANT: Thermostat must be installed for safe operation.
Figure 4H Side view of thermostat showing corrugation seal.
16PNEG-012 Vane Axial Heater
Page 17
4. Installation
Heater Orifice Setup
The factory has set the orifices size for propane, high temperature and natural gas, low temperature.
1. Determine the type of gas to be used: Propane or natural gas.
2. Determine the operating temperature ranges to be used: High or low. Refer to tables on Page 23
and Page 24.
3. For natural gas high temperature applications remove reducer bushing with pressure gauge and
remove 7/32" primary orifice from system. Replace reducer bushing and check connections
for leaks. For natural gas high temperature configuration there is no primary orifice in the system.
Refer to Fuel - Temperature Table below.
4. For propane low temperature applications remove reducer bushing with pressure gauge and
replace the supplied 7/32" primary orifice with a 3/32" orifice supplied in control box. Replace
reducer bushing and check connections for leaks. Refer to Fuel - Temperature Table below.
Figure 4I
Fuel - Temperature
Fuel
Natural GasRemove primary orifice completely.
Propane
No modifications required.
Standard with 7/32" orifice.
HighLow
T emperature
No modifications required.
Standard with 7/32" orifice.
Replace primary orifice with 3/32"
orifice supplied in control box.
Make sure the configuration matches the appropriate application in the
Fuel - Temperature Table above. Propane has a higher BTU content than
natural gas. Do not remove 3/8" secondary orifice. Excessive heat rise due to
improper orifice sizing or removing the 3/8" secondary orifice will damage
grain or cause fire.
PNEG-012 Vane Axial Heater17
Page 18
5. Operation
Operating Temperature Table
IMPORTANT: The below table is not intended as a drying guide. It should be used as a reference
for setting maximum plenum temperature for safe operation.
Do not exceed plenum temperatures listed in table below.
High Temperature
Batch Dry
No Stirring
120°140°160°
100°100°Not Recommended
110°120°Not Recommended
High Temperature
with Stirring
Corn
Rice
Beans
and
Wheat
Low T e mpe r ature
Batch
5°-20° above
Ambient
Temperature
5°-10° above
Ambient
Temperature
5°-20° above
Ambient
Temperature
Cycling Heater Operation
1. Thermostat must be wired into heater control box for heater to operate.
2. Open all manual shut off valves to heater unit.
3. Start fan. This will supply power to heater.
4. Turn thermostat dial to its highest setting.
Continuous
Flow (Recirculating)
5. Turn toggle switch ON.
6. Heater should now be lit. If not check to see that all gas is ON.
7. Watch thermometer on plenum and when it reaches desired temperature turn thermostat back
slowly until heater cycles OFF.
8. Gas pressure should be adjusted so burner is ON 75% of the time.
9. Watch plenum temperature as burner goes through a few cycles, to be sure that it is
operating properly.
18PNEG-012 Vane Axial Heater
Page 19
5. Operation
Time Delay Operation - Standard Heater
HH-1089E Time Delay Reset Operation
The electronic time delay will indicate the operating condition of the heater through the LED light shown
in Figure 5A. This light should be on the exterior control panel of the heater when the unit is installed
correctly. This light is very helpful in identifying the status of the flame probe (open or closed) and will
indicate a lock out condition.
Start-up
The light should be ON when the ON/OFF switch is set to ON. This indicates that the heater h as power
and the flame probe is closed. The gas solenoid should open and ignitor should spark. The light will
remain on until the flame probe opens. The light should go OFF if flame is established within the
30 second trial for ignition.
If flame is not present or the probe does not open, then the light will blink continuously after the 30 second
time period. It will blink continuously until the heater is reset.
Turn power OFF for 10 second to reset a lock out condition. The light will stop blinking after the
10 second time period. The heater cannot be restarted if the light is blinking continuously.
Thermostat Cycle
The heater thermostat will cycle the gas solenoid OFF when temperature is reached. The flame probe
should cool to a closed condition when this occurs. The thermostat will also cool to a closed condition
with a drop in plenum temperature. The thermostat closure is a call for heat and the normal start-up for
the time delay begins again.
A condition can occur where the thermostat can call for heat before the flame probe cools to a closed
condition. The light ON the time delay will flash once at thermostat closure and remain OFF until the
flame probe closes again. The heater will not operate until this “closed” condition of both switches
is achieved.
Light StatusIndication
Light
ON
OFF
BLINKING
Flame probe is closed.
Time delay in 30 second trial for
ignition period.
Normal operation with flame present.
Flame probe open. Thermostat closed.
Normal operation with no flame present.
Flame probe open. Thermostat open.
Lock out: Flame probe closed after
30 second.
To reset: Turn power OFF. Wait
10 second. Turn power ON.
Figure 5A Flame Probe Light ON Time Delay
PNEG-012 Vane Axial Heater19
Page 20
5. Operation
High-Low Heater Operation
1. High-Limit and cycling thermostat must be wired into heater control box for heater to operate.
2. Open all manual shut off valves to heater unit.
3. Start fan. This will supply power to heater.
4. Turn thermostat dial to its highest setting.
5. Turn toggle switch ON. Both lights should illuminate indicating power to the control circuit.
6. Heater should now be lit. If not check to see that all gas is ON.
7. Open adjustment screw on solenoid valve all the way.
8. Turn thermostat dial back slowly until heater cycles to low flame.
9. Adjust screw on solenoid valve so that low flame pressure is at desired setting. (As low as possible.)
10. Turn thermostat dial to desired setting and wait for bin plenum to come up to temperature. Heat er
should cycle to low flame after a few minute.
11. If heater does not cycle to low flame increase high flame gas pressure by adjusting the regulator.
12. High flame should be adjusted so the heater cycles 75% of the time. Low flame should be adjusted
so there is enough flame for unit to keep operating.
13. Watch as burner goes through a few cycles, to be sure that it is operating properly back to
high flame.
Figure 5B
20PNEG-012 Vane Axial Heater
Page 21
5. Operation
Modulating Valve Operation
1. The modulating valve regulates gas flow through the heater based on sensing unit in the plenum,
and maintains a constant drying air temperature.
2. The sensing bulb of the modulating valve should be mounted through the bin wall with the side
reading “top” up. The bulb reacts to temperature. It changes the amount of gas (increase or
decrease), burning warmer or cooler depending on the position of the valve SET POINT. If the bulb
is cooler than it was at the SET POINT, the bulb senses the cooler temperature and opens the valve
further so more heat is applied to the drying air. If the bulb is warmer than it was at th e SET POINT,
the valve closes further and reduces the temperature until the air is at the valve SET POINT.
3. It is important that the pressure regulator be set high enough to allow the modulating valve to deliver
enough gas to maintain the plenum temperature necessary. The regulator is normally factory set
at 15 PSI (propane units). To set the regulator, run the heater and turn the modulating valve
T-handle in. This gets full line pressure to the burner. Then adjust regulator to read 15 PSI
(depending on the plenum temperature needed).
4. Turn the fan/heater ON. To set the modulating valve, turn the T-handle out (counterclockwise) until
loose and wait a few minute for the plenum temperature to equalize. When the temperature under
the bin has equalized, gradually turn T-handle in (clockwise) about 1/2 turn at a time. Wait until
temperature under bin has equalized as before. If temperature under bin is less than the desired
temperature, continue turning T-handle in, increasing gas flow and waiting for plenum temperature
to equalize until the desired temperature is the stable temperature of the plenum. If temperature
under bin is the same 10 minute after you last made any adjustments to the T-handle you can be
certain that the temperature under the bin is the SET POINT of the valve. 1 Turn of the T-handle
equals approximately 7°F of temperature.
5. The valve will now keep the plenum temperature at the set point regardless o f ambien t co nditions
as long as humidistat or thermostat do not shut down the heater. A bypass orifice is used to
maintain a small flame when outside temperature is near or above the set point of the valve. The
bypass ensures steady application of heat at minimum gas flow operation. Bypass orifice will only
operate correctly if pressure regulator is set correctly.
6. To observe how the modulating valve increases the efficiency of bin drying, check the gas pressure
of the unit in the morning and compare to the pressure read mid-afternoon. If the ambient (outside)
temperature is significantly greater later in the day (as normal), the gas pressure will be less. Since
less heat is required to maintain the same temperature in the plenum, the modulating valve will
have reduced the amount of gas used by the heater.
PNEG-012 Vane Axial Heater21
Page 22
5. Operation
Adjusting the Vaporizer
1. Vaporizer should be adjusted so the vapor pipe train runs warm to the touch (100°F-120°F).
2. Loosen 5/16" bolt on adjustment bracket.
3. Swivel vaporizer away from flame if running too hot, closer to flame if too cold.
4. Move vaporizer only 1" at a time and allow a few minute for temperature to equalize.
5. Tighten 5/16" bolt and watch heater run for several minute to verify adjustment.
Figure 5C
Adjusting the vaporizer coil on a liquid propane model. The Figure 5C shows the setting in, and
the Figure 5D shows the coil out.
Figure 5D
22PNEG-012 Vane Axial Heater
Page 23
5. Operation
BTUs per Gauge Pressure (PSI) - Propane Models (Approximate)
All heaters are constructed of durable weather-resistant materials, so a minimum amount of service
should be required. Before the unit is started for the first time each season there are a few items that
need to be checked out. All damaged parts should be repaired or replaced.
1. Disconnect and lock out power to fan/heater. Open control box lid and inspect all components for
moisture, vibration or rodent damage. Inspect and tighten all loose terminal connectio ns. Re place
any damaged wiring.
2. Remove burner orifice tube and inspect for dirt or foreign material. Clean out if necessary.
3. Inspect holes in burner ring for possible corrosion or plugging with dirt or rust. Clean if necessary.
4. Be sure primary air inlet screen is intact and clean for proper burn.
5. Check perforated ring on natural gas models to be sure it is clean and no holes are plugged.
6. Inspect flame probe and ignitor and adjust or replace if necessary.
Always disconnect and lock out power before working on or around heater.
PNEG-012 Vane Axial Heater25
Page 26
7. Troubleshooting - Standard Heater
TroubleProbable CauseCheck-out Procedure
Burner will not fire. No gas
pressure on gauge.
No ignition spark.
Burner will not fire. No gas
pressure on gauge. Constant
ignition spark.
Burner will not fire. Gas pressure
on gauge. No ignition spark.
1. Heater not wired.
2. Fan not running.2. Fan contactor must be energized for heater to run.
3. Blown fuse.3. Visually check fuse.
4. Bad ON/OFF switch.
5. Housing high-limit switch. 5. Reset switch. Check for power on terminals 1 and 8.
6. Thermostat open.
7. Flame probe open.
1. Electronic time delay.1. Time delay is in lock out or not receiving power.
2. Gas supply.
1. Loose wire.
2. Ignitor/spark plug.
3. Ignition transformer/wire.
1. Visually check fan control box to see if wires
are connected.
4. Check ON/OFF switch contact block for proper
installation and continuity. Check for power on
terminals 1 and 8.
6. Plenum temperature above set point temperature or
open circuit.
7. Remove wires from flame probe and check with ohm
meter. Probe should be closed when cold.
2. Make sure all valves are open to heater and gas tank is
not empty.
1. Check for power on terminals 4 and 7. Look for loose
wires or incorrect wiring.
2. Turn gas OFF to heater. Check gap on ignitor. Check
porcelain for any sign of cracks. Remove plug wire from
spark plug/ignitor. Carefully holding wire by insulation.
Try to get an arc between end of wire and heater
housing (or other wire using two (2) pole transformer).
3. Turn gas OFF to heater. If no spark present after
checking ignitor, remove wire from ignition transformer.
Check for spark at ignition transformer with an insulated
screwdriver. Spark should jump a minimum 1/4" gap.
Replace transformer if no spark is established, replace
the ignition wires.
1. Check for gas at burner. If no gas, remove pipe train and
check orifice and burner ring for blockage.
2. Check to be sure flame probe is in good condition and is
located in flame. Flame probe contacts should open
when probe gets hot.
4. See that flame burns continuous and is not intermittent.
On ring burners be sure flame burns completely
around ring.
5. Have tank and lines checked by a qualified gas
service man.
Burner will not fire or fires for
30 second and locks out. Gas
pressure on gauge. Spark is ON.
1. Plugged orifice.
2. Flame probe.
3. Incorrect supply voltage.3. Voltage to heater must be 110V AC.
4. Regulator set too low.
5. Moisture in fuel.
26PNEG-012 Vane Axial Heater
Page 27
Standard Heater Wiring
8. Wiring Diagrams
PNEG-012 Vane Axial Heater27
Page 28
8. Wiring Diagrams
Standard Heater Schematic
28PNEG-012 Vane Axial Heater
Page 29
Deluxe Heater
8. Wiring Diagrams
PNEG-012 Vane Axial Heater29
Page 30
9. Parts List
Standard Heater Control Box Parts
30PNEG-012 Vane Axial Heater
Page 31
9. Parts List
Standard Heater Control Box Parts List
Ref #Part #DescriptionQty
1HF-7698Backing Plate - Heater1
2HF-8111Control Box - Standard1
3069-1376-8Control Box Lid - Poly Blank1
4090-1699-9Rivet, 1/8" Diameter x 0.775" Long ARSM 0.501-0.625 Grip Range4
590-0009Lamp, 120V Amber1
6D03-0696Control Box Latch2
7DC-1878Decal, Heater Standard w/ Reset1
8E240-1107Terminal Strip 12 Position 10A 12 Gauge4
11HH-7016HH-7016HH-7016Rubber Grommet - LP Model Only
12HF-7056HF-7056HF-7056Pivot Bracket - LP Model Only
13HF-7057HF-7057HF-7057Adjustment Bracket - LP Model Only
Part #
Description
14HF-7060HF-7060HF-7060Vaporizer Support Weldment
15THF-3237THF-3237THF-3237Vaporizer Cover - Vapor/NG Only
16HH-1650HH-1650HH-1650Spark Plug
17THH-4179THH-4179THH-4179Flame Sensor (Deluxe)
17HH-1097HH-1097HH-1097Flame Probe (Standard)
18CD-0187CD-0187CD-0187Flame Sen sor Bracket (Deluxe)
18HF-4485HF-4485HF-4485Flame Probe Bracket (Standard)
19HH-7054HH-7054HH-7054Bu rner Cone
9D07-0008Plug Vinyl for 1/2" NPT1
10HF-7509Hose, 1/2" x 18" LP Gas Assembly1
11CD-019824", 26", 28" LP Vaporizer Coil1
12HH-4847Elbow, 1/2"-90° SCH 80 Black2
PNEG-012 Vane Axial Heater43
Page 44
NOTES
44 PNEG-012 Vane Axial Heater
Page 45
10. Warranty
GSI Group, LLC Limited Warranty
The GSI Group, LLC (“GSI”) warrants products which it manufactures to be free of defects in materials and workmanship
under normal usage and conditions for a period of 12 months after sale to the original end-user or if a foreign sale,
14 months from arrival at port of discharge, whichever is earlier. The end-user’s sole remedy (and GSI’s only obligation)
is to repair or replace, at GSI’s option and expense, products that in GSI’s judgment, contain a material defect in materials
or workmanship. Expenses incurred by or on behalf of the end-user without prior written authorization from the GSI
Warranty Group shall be the sole responsibility of the end-user.
Warranty Extensions:
The Limited Warranty period is extended for the following products:
ProductWarranty Period
Performer Series Direct Drive Fan Motor3 Years
AP Fans and Flooring
Cumberland
Feeding/Watering
Systems
Grain SystemsGrain Bin Structural Design5 Years
Grain Systems
Farm Fans
Zimmerman
All Fiberglass HousingsLifetime
All Fiberglass PropellersLifetime
Feeder System Pan Assemblies5 Years **
Feed Tubes (1-3/4" and 2.00")10 Years *
Centerless Augers10 Years *
Watering Nipples10 Years *
Portable and Tower Dryers2 Years
Portable and Tower Dryer Frames and
Internal Infrastructure †
5 Years
* Warranty prorated from list price:
0 to 3 years - no cost to end-user
3 to 5 years - end-user pays 25%
5 to 7 years - end-user pays 50%
7 to 10 years - end-user pays 75%
** Warranty prorated from list price:
0 to 3 years - no cost to end-user
3 to 5 years - end-user pays 50%
† Motors, burner components
and moving parts not included.
Portable dryer screens included.
Tower dryer screens not included.
GSI further warrants that the portable and tower dryer frame and basket, excluding all auger and auger drive
components, shall be free from defects in materials for a period of time beginning on the twelfth (12
the date of purchase and continuing until the sixtieth (60
th
) month from the date of purchase (extended warranty period).
th
) month from
During the extended warranty period, GSI will replace the frame or basket components that prove to be defective
under normal conditions of use without charge, excluding the labor, transportation, and/or shipping costs incurred in
the performance of this extended warranty.
Conditions and Limitations:
THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE LIMITED WARRANTY DESCRIPTION SET FORTH
ABOVE. SPECIFICALLY, GSI MAKES NO FURTHER WARRANTY OF ANY KIND, EXPRESS OR IMPLIED,
INCLUDING, WITHOUT LIMITATION, WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE OR USE IN CONNECTION WITH: (I) PRODUCT MANUFACTURED OR SOLD BY GSI OR (II) ANY
ADVICE, INSTRUCTION, RECOMMENDATION OR SUGGESTION PROVIDED BY AN AGENT, REPRESENTATIVE
OR EMPLOYEE OF GSI REGARDING OR RELATED TO THE CONFIGURATION, INSTALLATION, LAYOUT,
SUITABILITY FOR A PARTICULAR PURPOSE, OR DESIGN OF SUCH PRODUCTS.
GSI shall not be liable for any direct, indirect, incidental or consequential damages, including, without limitation, loss of
anticipated profits or benefits. The sole and exclusive remedy is set forth in the Limited Warranty, which shall not exceed
the amount paid for the product purchased. This warranty is not transferable and applies only to the original end-user.
GSI shall have no obligation or responsibility for any representations or warranties made by or on behalf of any dealer,
agent or distributor.
GSI assumes no responsibility for claims resulting from construction defects or unauthorized modifications to products
which it manufactured. Modifications to products not specifically delineated in the manual accompanying the equipment
at initial sale will void the Limited Warranty.
This Limited Warranty shall not extend to products or parts which have been damaged by negligent use, misuse,
alteration, accident or which have been improperly/inadequately maintained. This Limited Warranty extends solely to
products manufactured by GSI.
Prior to installation, the end-user has the responsibility to comply with federal, state and local codes which apply to the
location and installation of products manufactured or sold by GSI.
9101239_1_CR_rev7.DOC (revised July 2009)
PNEG-012 V ane Axial Heater 45
Page 46
This equipment shall be installed in accordance with
the current installation codes and applicable
regulations which should be carefully followed in all