Grasslin GM40AVE Series Installation & Operating Manual

To avoid re, shock, or death, turn off power at circuit breaker and test that power is off • before wiring. Read instructions completely before installation and retain for future reference.• Observe all national and local electrical and safety codes.• Disconnect power when servicing or changing loads.• Alterations or modications to the device will void the warranty.• For outdoor locations, rain-tight or wet location conduit hubs that comply with the re-• quirements of UL 514B Conduit, Tubing, and Cable Fittings, must be used.
GM40AVE Series General Purpose Electronic Commercial Time Switches
To avoid re, shock, or death, turn off power at the circuit breaker and test that 1. power is off before wiring. Open door and remove the interior protective cover by releasing the spring 2. latch (see gure 1 below). Remove the printed circuit board by releasing the spring latch holding the bot-3. tom of the board (see gure 2 below). Select knockouts to be used. Remove the inner 1/2” knockout by inserting a 4. athead screwdriver in the slot and carefully punch the knockout loose. Re­move slug. If 3/4” knockout is required, remove the outer ring with pliers after removing the 1/2” knockout. Smooth edge with knife, if necessary. Place the enclosure in the desired mounting location, and mark the three 5. mounting holes (refer to Figure 3 below for dimensions). Install the top screw rst with one of the supplied spacers, and then hang the enclosure by the key­hole. Drive the remaining two screws at the bottom of the enclosure through the mounting holes while passing each screw through one of the supplied spacers and in to the wall. Connect conduit hubs to conduit before connecting the hubs to the enclosure. 6. After inserting hubs into enclosure, carefully tighten hub lock nut. Do not over­torque. Replace printed circuit board making sure to engage spring latch at the bot-7. tom of PCB. Wire in accordance with national and local electrical and safety codes (see 8. wiring diagrams on page 3). Grounding: Terminate all ground wires to the ground lug inside the case at the 9. bottom of the enclosure. Replace interior protective cover. 10.
INSTALLATION INSTRUCTIONS
ELECTRICAL RATINGS
N.O. Contacts:
40A Resistive @ 120~277VAC
1HP, 16FLA, 90LRA @ 120VAC 2HP, 12FLA, 52LRA @ 208~277VAC 30A Ballast @ 120VAC 20A Ballast @ 277VAC 15A Tungsten @ 120VAC 300VA Pilot Duty 120~240VAC
N.C. Contacts:
30A Resistive @ 120~277VAC
1HP, 12FLA, 30LRA @ 120VAC 2HP, 10FLA, 30LRA @ 240VAC 2A Tungsten @ 120VAC 10A Ballast @ 277VAC
WIRING CONNECTIONS:
Screw box lug terminals
ENVIRONMENTAL RATINGS:
Operating Temperature Range:
–40°F to 131°F (–40°C to 55°C) Operating Humidity: 10 - 95% RH, non-condensing
ENCLOSURE DIMENSIONS:
8.795” x 6.631” x 2.935”
(H x W x D)
SHIPPING WEIGHT:
2 lbs.
AGENCY APPROVALS:
UL Listed
PROGRAMMING INSTRUCTIONS
WARNING
Interior Protective Cover Removed
Timer Mechanism
Figure 2 - PCB Latch
Interior Protective Cover
Figure 1 - Spring Latch
Figure 3 - Rear View of Enclosure
with mounting hole dimensions
6-1/8”
2-1/2”
The installer should refer to the supplemental instruction manual included with this unit for information regarding setting the time, symbols, keys and program­ming.
AC voltage must be present at terminals L1 and L2/N for the relays to operate and the status indicator to change from 1 to 1 .
2
SPECIFIERS GUIDE
APPLICATION
The GM40AVE Series Time Controls are universal, electronic time switches designed for general purpose commercial appli­cations. The control operates on any AC voltage from 120VAC to 277VAC. The mechanism is mounted in an indoor/outdoor enclosure and has been designed for the control of lighting, heating, air conditioning, pumps, motors, or general electrical circuits in residential, commercial, industrial and agricultural facilities.
Furnish and install an Intermatic GM40AVE Auto-Volt Series with digital programmable timer with bat­tery backup. The Auto-Volt input voltage range shall be 120VAC to 277VAC, 50 / 60 Hz. All units shall incorporate two isolated sets of SPDT contacts that are each rated at 40A, 2 HP @ 277V. LED indica­tors shall provide Power and Status feedback. Enclosure shall be UL Type 3R, suitable for indoor or outdoor installation. Timers with battery backup will automatically keep time and do not require reset­ting after a power outage.
GM40AVE Digital timer controls
Moisture Resistant
Conformal Coated
Board
Automatic Voltage Selection From 120 VAC to 277 VAC
40 Amp
Rated Contacts
One Minute Intervals
Large Screw Terminals
for Easy Wiring
up to #8 AWG
Large Ground Lug
Termination
New UL Type 3R
Enclosure for
Indoor or Outdoor
Installation
Yellow and Green
LED Lights Indicate
Power and Status
Interior protective cover and door not shown
Built-in Battery
Backup
Easy to Read LCD
Screen
Easy and Simple to
Program Timer with
Large Buttons
BASIC OPERATION
Wiring and load control can be veried by manually turning the unit ON and OFF using the override (OVR) + key.