Groen DH-CE Mark, DHT-CE Mark Operation Manual

OPERATOR MANUAL & SERVICE MANUAL
IMPORTANT INFORMATION, KEEP FOR OPERATOR
This manual provides information for:
MODELS DH-CE Mark & DHT-CE Mark International
STEAM JACKETED KETTLES
· Self-Contained
· Stainless Steel
· Gas Heated
· Tilting
DH
THIS MANUAL MUST BE RETAINED FOR FUTURE REFERENCE. READ, UNDERSTAND AND FOLLOW THE INSTRUCTIONS AND WARNINGS CONTAINED IN THIS MANUAL (THE SERVICE MANUAL AND OPERATOR MANUAL SECTIONS).
NOTIFY CARRIER OF DAMAGE AT ONCE
It is the responsibility of the consignee to inspect the container upon receipt of same and to determine the possibility of any damage, including concealed damage. Unified Brands suggests that if you are suspicious of damage to make a notation on the delivery receipt. It will be the responsibility of the consignee to file a claim with the carrier. We recommend that you do so at once.
Manufacture Service/Questions 888-994-7636.
Information contained in this document is known to be current and accurate at the time of printing/creation. Unified Brands recommends referencing our product line websites, unifiedbrands.net, for the most updated product information and specifications.
PART NUMBER 128417, REV. D (6/06)
DHT
1055 Mendell Davis Drive
Jackson, MS 39272
888-994-7636, fax 888-864-7636
groen.com
OM/SM-DH-CE
IMPORTANT — READ FIRST — IMPORTANT
IT IS MOST IMPORTANT THAT THESE INSTRUCTIONS AND THE OPERATOR AND SERVICE MANUALS BE CONSULTED BEFORE INSTALLING AND COMMISSIONING THE APPLIANCE. FAILURE TO COMPLY WITH SPECIFIED PROCEDURES MAY RESULT IN DAMAGE OR THE NEED FOR A SERVICE CALL.
THESE APPLIANCES HAVE BEEN CE MARKED ON THE BASIS OF COMPLIANCE WITH THE GAS APPLIANCE DIRECTIVE, EMC AND LOW VOLTAGE DIRECTIVE FOR THE COUNTRIES, GAS TYPES AND PRESSURES AS STATED ON THE DATA PLATE.
THESE APPLIANCES MUST BE INSTALLED BY A COMPETENT PERSON IN CONFORMITY WITH INSTALLATION AND SERVICING INSTRUCTIONS AND NATIONAL REGULATIONS IN FORCE AT THE TIME. PARTICULAR ATTENTION MUST BE PAID TO THE FOLLOWING:
I. E. E. REGULATIONS FOR ELECTRICAL INSTALLATIONS ELECTRICITY AT WORK REGULATIONS GAS SAFETY (INSTALLATION AND USE) REGULATIONS HEALTH AND SAFETY AT WORK ACT LOCAL AND NATIONAL BUILDING REGULATIONS FIRE PRECAUTIONS ACT
DETAILED RECOMMENDATIONS ARE CONTAINED IN INSTITUTE OF GAS ENGINEERS PUBLISHED DOCUMENTS: IGE/UP/1, IGE/UP/2, BS6173 AND BE5440. FURTHERMORE, IF A NEED ARISES TO CONVERT THE APPLIANCE FOR USE WITH ANOTHER GAS, A COMPETENT PERSON MUST BE CONSULTED. THOSE PARTS WHICH HAVE BEEN PROTECTED BY THE MANUFACTURER MUST NOT BE ADJUSTED BY THE USER.
USERS SHOULD BE CONVERSANT WITH THE APPROPRIATE PROVISIONS OF THE FIRE PRECAUTIONS ACT AND THE REQUIREMENTS OF THE GAS SAFETY REGULATIONS. IN PARTICULAR THEY SHOULD BE AWARE OF THE NEED FOR REGULAR SERVICING BY A COMPETENT PERSON TO ENSURE THE CONTINUED SAFE AND EFFICIENT PERFORMANCE OF THE APPLIANCE.
WARNING: TO PREVENT SHOCKS, ALL APPLIANCES GAS OR ELECTRIC, MUST BE
EARTHED.
UPON COMPLETION OF THE INSTALLATION, THE OWNERS MANUAL SHOULD BE HANDED TO THE USERS AND THE INSTALLER SHOULD INSTRUCT THE RESPONSIBLE PERSON(S) IN THE CORRECT OPERATION AND MAINTENANCE OF THE APPLIANCE. THIS EQUIPMENT IS ONLY FOR PROFESSIONAL USE, AND SHALL BE OPERATED BY QUALIFIED PERSONS. IT IS THE RESPONSIBILITY OF THE SUPERVISOR OR EQUIVALENT TO ENSURE THAT USERS WEAR SUITABLE PROTECTIVE CLOTHING AND TO DRAW ATTENTION TO THE FACT THAT SOME PARTS BY NECESSITY WILL BECOME VERY HOT, AND WILL CAUSE BURNS IF TOUCHED ACCIDENTALLY.
WARNING: BEFORE REMOVING ANY PARTITION OR PANEL, ALWAYS TURN OFF THE
ELECTRIC POWER AND ALLOW THE FAN TO STOP ROTATING. BEFORE WORKING ON ANY ELECTRICAL COMPONENT, DISCONNECT THE POWER SOURCE FROM THE UNIT.
NOTE: IT IS IMPORTANT THAT THE END-USER ROUTINELY EXAMINE THE FLUE OUTLET
ON A REGULAR BASIS. DEBRIS COVERING THE FLUE OUTLET CAN CAUSE A POTENTIALLY HAZARDOUS CONDITION. REMOVE ANY FOREIGN MATERIAL BEFORE USING THIS PIECE OF EQUIPMENT.
WARNINGS AND CAUTIONS PROVIDED IN THIS OPERATOR AND SERVICE MANUAL MUST BE COMPLIED WITH.
2 OM/SM-DH CE
Contents
Regulations and Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 Model Numbers, Net Weights & Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Siting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.5 Electrical Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.6 Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.7 Total Gas Rate - Natural and Propane Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.8 Injector Diameters-Natural and Propane Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.9 Gas Pressure Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.10 Burner Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Assembly and Conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.1 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.2 Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.3 Electrical Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.4 Jacket Water Level/Jacket Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.5 Pre-Commissioning Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.6 Instruction to User . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Servicing and Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1 Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2 Jacket Vacuum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.3 Jacket Filling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.4 Water Treatment Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.5 Removal of Control Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.6 Removal of Spark Ignition Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.7 Removal of Low Water Level Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.8 Removal of Tilt Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.9 Removal of Gas Control Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.10 ON/OFF Switch and Reset Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.11 Removal of Neons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.12 Removal of Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.13 Removal of Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.14 Low Water Level Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.15 Removal of the Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.16 Spark Electrode/Flame Sensing Bracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.17 Removal of Pressure Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.18 Removal of Sight Glass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.19 Safety Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.20 Filling Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.21 Fuse Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5 User Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
5.1 Equipment Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.2 Lighting and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
5.3 Cleaning and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Service Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
OM/SM-DH CE 3
Regulations and Safety Precautions
These Appliances have been CE marked on the basis of compliance with the Gas Appliance Directive, EMC and Low Voltage Directive for the Countries, Gas Types and Pressures as stated on the Data Plate.
These appliances MUST BE installed by a competent person in conformity with the INSTALLATION AND SERVICING INSTRUCTIONS and National Regulations in force at the time.
Particular attention MUST be paid to the following:
I.E.E. Regulations for Electrical Installations Electricity at Work Regulations Gas Safety (Installation & Use) Regulations Health and Safety at Work Act Fire Precautions Act Local and National Building Regulations
Furthermore, if a need arises to convert the Appliance for use with another gas, a competent person must be consulted. Those parts which have been protected by the manufacturer MUST NOT be adjusted by the User.
Users should be conversant with the appropriate provisions of the Fire Precautions Act and the requirements of the Gas Safety Regulations. In particular the need for regular servicing by a competent person to ensure the continued safe and efficient performance of the Appliance.
WARNING
TO PREVENT SHOCKS, ALL APPLIANCES WHETHER GAS OR ELECTRIC, MUST BE EARTHED.
Upon completion of the installation, the Owners Manual should be handed to the users and the installer should instruct the responsible person(s) on the correct operation and maintenance of the Appliance. This equipment is ONLY FOR PROFESSIONAL USE, and shall be operated by QUALIFIED persons. It is the responsibility of the Supervisor or equivalent to ensure that users wear SUITABLE PROTECTIVE CLOTHING and to draw attention to the fact that, some parts will, by necessity, become VERY HOT and will cause burns if touched accidentally.
IMPORTANT - READ FIRST - IMPORTANT The Groen Steam Jacketed Kettle you have just purchased has been handcrafted from the finest materials, meticulously inspected, and carefully tested to ensure that you receive the best possible product. With reasonable care and periodic maintenance, it will provide years of faithful service. It is recommended that you establish a timetable for periodic maintenance as outlined in this manual. Space is provided in the Service Log at the back of this manual.
4 OM/SM-DH CE
Section 1
Installation
UNLESS OTHERWISE STATED, PARTS WHICH HAVE BEEN PROTECTED BY THE MANUFACTURER ARE NOT TO BE ADJUSTED BY THE INSTALLER.
1.1 Model Numbers, Net Weights and Dimensions
MODEL
DH-20 DH-40 DH-60
WIDTH
mm (inch)
890 (34.9) 1190 (46.8) 1190 (46.8)
DEPTH
mm (inch)
790 (31.0) 930 (36.5) 990 (38.9)
HEIGHT
mm (inch)
1040 (40.9) 1150 (45.2) 1240 (48.7)
WEIGHT
Kg
245 295 400
WEIGHT
lbs
535 645 880
1.2 Siting
The appliance should be installed on a level floor in a well lit and draught free position. The installation of the appliance must be executed in accordance with local and/or national regulations as listed in this manual.
1.3 Clearances
Minimum clearances of 150 mm (5.9 in) from the sides of the appliance and 250 mm (9.8 in) from the rear of the appliance are required if the appliance is installed next to combustible surfaces. A vertical clearance of 750 mm (29.6 in) minimum should be allowed between the top rim of kettle and any overlying surface.
1.4 Ventilation
The unit must be installed in an adequately ventilated room with a provision for adequate air supply to the unit. The area directly around the appliance must be cleared of all combustible material. For multiple installations, the requirements for individual appliances should be added together. Installation should be made in accordance with local and / or national regulations applying at the time. A competent installer must be employed.
WARNING THE UNIT MUST BE INSTALLED BY PERSONNEL QUALIFIED TO WORK WITH ELECTRICITY AND GAS. IMPROPER INSTALLATION CAN CAUSE INJURY TO PERSONNEL AND/OR DAMAGE TO EQUIPMENT. THE UNIT MUST BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE CODES.
CAUTION THE APPLIANCE FLUE DISCHARGES VERTICALLY FROM THE TOP OF THE UNIT AT THE REAR. IT MUST NOT BE DIRECTLY CONNECTED TO ANY FLUE, MECHANICAL EXTRACTION SYSTEM, OR DUCTING LEADING OUTSIDE THE BUILDING. THE APPLIANCE IS BEST DISCHARGED UNDER AN OPEN CANOPY WHICH CONNECTS WITH A VENTILATING SYSTEM.
Recommendations for ventilation for catering appliances are given in BS 5440:2 and are shown in the table below.
Equipment
(Unit Type)
Ventilation Rate Required
m³ /min ft³ /min
Range 17 600
Pastry Oven 17 600
Fryer
26 900
Grill 17 600
Steak Grill
26 900
Boiling Pan 17 600
Steamer 17 600
Sterilizing Sink 14 500
Bains Marie 11 400
Tea/Coffee Machine
8.5-14 300-500
1.5 Electrical Supply
This unit is designed for connection to fixed wiring. A suitably rated isolating switch with contact separation of at least 3 mm (0.12 in) on
OM/SM-DH CE 5
Gas and Electrical Connections are made at the rear of the unit.
both poles must be fitted to the installation and the wiring executed in accordance with the regulations listed in this manual.
Cable entry is at the lower rear on the right side of the appliance. Access is gained by removing relevant panels as described in Paragraphs
3.5.1 and 3.5.2.
Provide 230 VAC, 50 Hz, 1 Phase, 1 AMP or 40 Watts service. The electrical schematic is in the service compartment and this manual.
WARNING
THIS APPLIANCE MUST BE EARTHED.
1.6 Gas Supply
Incoming service must be of sufficient size to supply full rate without excessive pressure drop. A gas meter is connected to the service pipe by the Gas Supplier. Any existing meter should be checked by the Gas Supplier to ensure that it has capacity to pass the required rate of gas for the kettle in addition to other installed gas equipment.
The appliance governor is incorporated in the gas control valve which is in the control cabinet. The control valve governor is suitable for both natural and propane gases without conversion.
Installation pipe work should be fitted in accordance with IEGE/UP/2. The pipe work should not be smaller than the gas inlet connection on the kettle, i.e. Rp ½ (½'' B.S.P.)
An isolating cock must be located near the appliance to allow shut down during emergency or servicing. Test for gas soundness and purged as specified in IGE/UP/1.
Water Supply-Not applicable.
1.7 Total Gas Rate - Natural (G20 and G25) and Propane (G31) Gas
Model Kw BTU/hr
DH-20
18.6 63,500
DH-40
24.5 83,600
DH-60
39.6 135,200
6 OM/SM-DH CE
1.8 Injector Diameters-Natural and Propane Gas (See Note, Paragraph 1.10 at right)
Model DH-20 DH/1-40 DH-60
Number of Injectors
15 20 25
Natural Gas G20
1.10 mm 1.25 mm 1.30 mm
Natural Gas G25
1.20 mm 1.25 mm 1.40 mm
Propane Gas G31
0.65 mm 0.75 mm 0.75 mm
1.9 Gas Pressure Adjustment
A pressure test point is fitted on the burner manifold and on the gas control valve.
DH-20 DH/1-40 DH-60
Natural Gas-G20
mBar
8.75 5.8 8.25
WCI* 3.5 2.3 3.3
Natural Gas-G25
mBar 8.0 7.0 8.25
WCI* 3.2 2.8 3.3
Propane Gas-G31
mBar 29 21 25
WCI* 11.6 8.4 10.0
*WCI = Water Column Inches
NOTE: With reference to gas rate, pressure adjustments and conversions, this appliance is CE-approved for use with the following gases:
a) G20 natural gas may be supplied to the
appliance in Austria, Belgium, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Norway, Portugal, Spain, Sweden, Switzerland and the United Kingdom.
b) G25 natural gas may be supplied to the
appliance in Belgium, France and the Netherlands.
c) G31 propane gas may be supplied to the
appliance in France, Germany, Ireland, the Netherlands, Portugal, Spain, Switzerland, and the United Kingdom.
Use of the appliance with non-approved gases in a listed country, or use in other countries, will void CE certification.
1.10 Burner Adjustment
The burners are fixed aeration type and have no provision for adjustment of air inlet.
OM/SM-DH CE 7
Before operation, check the water level and jacket pressure.
Section 2
Assembly and Commissioning
2.1 Assembly
d) Unpack the appliance
b) Place on a firm, level floor. Adjust and fix the
feet.
CAUTION SHIPPING STRAPS ARE UNDER TENSION AND CAN SNAP BACK WHEN CUT. TAKE CARE TO AVOID PERSONAL INJURY OR DAMAGE FROM STAPLES LEFT IN THE WALLS OF THE CARTON.
2.2 Gas Supply
Connect the unit to the gas supply and test for gas soundness. For gas supply down stream of the gas valve, leak detection spray or soap solution may be used with the burners lit.
CAUTION
ENSURE THAT THE KETTLE CONTAINS LIQUID WHEN THE BURNERS ARE ALIGHT.
2.3 Electrical Supply
Before commissioning the appliance, ensure that the electrical installation has been carried out to the relevant regulations (Paragraph 1.5).
WARNING
THIS APPLIANCE MUST BE EARTHED.
2.4 Jacket Water Level/Jacket Pressure
a) Ensure the water level in the jacket is
correct, by confirming that it is between the sight glass marks. If it is low, follow instructions in Paragraph 3.3.
b) Check the pressure gauge. If it does not
show 20 or more inches of vacuum (that is, a reading of 20 to 30 below zero) see "Jacket Vacuum" (Paragraph 3.2).
2.5 Pre-Commissioning Check
a) Prior to operation, clean out kettle pan
thoroughly using hot water and detergent. Rinse pan thoroughly.
b) Remove all literature and packing materials
from the interior and exterior of the unit.
c) Ensure the open end or the elbow at the
outlet of the safety valve is directed down. If not, turn the elbow to the correct position. See detailed Instructions on Page 11 for Safety Valve installation and operation.
2.5.1 Lighting Sequence
From Initial Start Up:
a) Put a small amount of water in kettle pan.
b) Ensure gas and electricity mains are “on.”
c) Switch the toggle switch to the "on" position.
d) Turn thermostat dial to desired setting.
e) Verify that spark igniter lights the burners.
8 OM/SM-DH CE
f) If the unit does not light, it will lock-out. Turn
it off and wait one or two minutes before attempting to switch the unit on again.
g) Press reset lock-out switch and repeat steps
(b) to (e).
h) To switch unit off, switch toggle (On/Off)
switch to the "Off" position.
i) Turn gas and electricity mains off.
2.5.2 Setting The Gas Pressure
a) It is necessary to check the gas pressure
during commissioning. A pressure gauge must be connected to the pressure test point on the gas control valve or the gas manifold. See figure above for test points.
b) When checking pressure at test points on
the gas valve, undo the screw a half turn and slip tube over nipple.
c) Turn the main gas and electricity supply on.
d) Light the burners (Paragraph 2.5.1).
e) Remove control cabinet side panel screws.
f) Remove governor cap screw from control
valve. See figure for position on valve.
g) Governor is suitable for both natural and
propane gas.
h) To increase pressure turn the screw inside
the governor turret clockwise; anti-clockwise to reduce pressure. Check the burner pressure again after 15 minutes operation and adjust if necessary.
i) Disconnect the pressure gauge from the test
point. Re-seal the pressure test point and test for gas soundness.
j) Replace governor cap screw and replace lid
and panels.
2.5.3 Checking Performance of Controls
a) Light the unit. Check that controls quickly
and smoothly produce a healthy spark from the electrode to the earthing post.
b) Turn thermostat off and then on. Check that
burners go out and reignite smoothly and quickly when switched back on. Repeat several times.
c) If the unit fails to respond as described, it
should be serviced by an authorized Groen service agent.
2.6 Instruction to Installer
Important: After installing and commissioning the appliance, the user's instructions should be handed to the user or purchaser. Ensure that the instructions for lighting, turning off, correct use and cleaning are properly understood. The location of the main gas isolating valve should be emphasized and the emergency shut down procedure should be demonstrated.
OM/SM-DH CE 9
Section 3
Servicing and Conversion
IMPORTANT
BEFORE ATTEMPTING ANY SERVICING, ENSURE THAT THE ISOLATING COCK IS TURNED OFF AND CANNOT BE INADVERTENTLY TURNED ON AND THAT THE ELECTRICITY SUPPLY IS DISCONNECTED.
AFTER ANY MAINTENANCE TASK, CHECK THE APPLIANCE TO ENSURE THAT IT PERFORMS CORRECTLY AND CARRY OUT ANY NECESSARY ADJUSTMENTS AS DETAILED IN SECTION 1.
ALWAYS CHECK FOR GAS SOUNDNESS AFTER CARRYING OUT ANY SERVICING OR EXCHANGE OF GAS CARRYING COMPONENTS.
NOTE: When replacing wiring connections refer to the wiring diagram contained on the unit and within
this manual.
After Servicing
a) Test for gas soundness as specified in
IGE/UP1 as appropriate after any gas connection has been disturbed.
b) Check for correct operation, as appropriate
(see commissioning of appliance).
Regular Servicing Procedures
The following must be serviced at regular intervals.
Burners
The burner should be cleaned periodically to maintain maximum performance. Burners are best cleaned with a wire brush and any blocked parts are best cleaned with a metal broach, taking care not to damage the burner head.
The injector orifice should be cleaned with a wooden splinter. Metal reamers may distort or increase the orifice size and should be avoided.
Gears
The gear housing has fitting for proper lubrication of moving parts. The gears do not run in oil, periodic lubrication with grease is necessary. Frequency of lubrication will depend on operating conditions, but it should be performed at least once every 6 months. It is recommended that a #2 grade LGI lithium grease be used. Add grease through the Zerk fittings on the gear housing until grease flows out of bearings around the trunnion shaft. Place a
liberal amount of grease on the gear to cover the arc that is in contact with the worm gear.
Safety Valve
At least twice a month the safety valve requires checking to make sure it works correctly. When the gauge pressure is about five PSI, lift the valve lever enough to vent steam, then quickly let it snap back into place.
WARNING AVOID ANY EXPOSURE TO THE STEAM BLOWING OUT OF THE SAFETY VALVE.
This procedure should be explained to the user, since it is to be carried out at least twice a month. Safety procedures and requirements should also be explained to the user when carrying out the procedure.
Safety Valve Operating Instructions
If adding water to a boiler, DO NOT ALLOW water to flow through safety valve as sediment or debris may be deposited on seating surface.
To achieve topmost performance and maximum service life, it is necessary to maintain a proper pressure margin between set pressure of the safety valve and equipment operating pressure.
10 OM/SM-DH CE
Test the operation of the safety valve on a regular basis.
The minimum required pressure margin for this type of valve is 10% of the safety relief valve set pressure, but not less than five PSI. UNDER NO
CIRCUMSTANCES SHOULD THIS MARGIN BE LESS THAN 5 PSI. Failure to maintain this
operating margin may result in water leakage past the seat and accumulation of deposits on the seating surface. Excessive deposits may prevent the valve from operating properly, and a dangerous pressure build-up and equipment rupture may result.
Maintenance and Testing
CAUTION BEFORE TESTING, MAKE CERTAIN DIS C H ARGE P I PE IS PR O P ERLY CONNECTED TO VALVE OUTLET AND ARRANGED TO CONTAIN AND SAFELY DISPOSE OF BOILER DISCHARGE (SEE “INSTALLATION INSTRUCTIONS”).
Under normal operating conditions a “try lever test” must be performed every two months. Under severe service conditions, or if corrosion and/or deposits are noticed within the valve body, testing must be performed more often. A “try lever test” must also be performed at the end of any non-service period.
Test at or near maximum operating pressure by holding the test lever fully open for at least 5 seconds to flush the valve seat free of sediment and debris. Then release lever and permit the valve to snap shut.
If lift lever does not activate, or there is no evidence of discharge, discontinue use of equipment immediately and contact a licensed contractor or qualified service personnel.
Neither Conbraco Industries, Inc. nor its agents assume any liability for valves improperly installed or maintained.
This quality Conbraco safety relief valve, along with proper installation, use, and maintenance, will provide many years of reliable service and protection against excessive pressure build-up of water/steam. Use of this valve for any other purpose or media places all responsibility upon the user. Before installing valve or operating equipment to which it is installed, read instructions carefully. Always wear proper safety equipment.
INSTALLATION OF SAFETY VALVE
a) Installation must be performed by qualified
service personnel only.
b) The BTU/hr or lb/hr rating of this valve must
equal or exceed that of the equipment to which it is attached.
c) DO NOT use this valve on a coal or wood
boiler having an uncontrolled heat input.
d) Ensure that all connections, including the
valve inlet, are clean and free from any foreign material.
e) Use pipe compound sparingly, or tape, on
external threads only.
f) DO NOT USE A PIPE WRENCH! Use
proper type and size wrench on wrench pads only.
g) This valve must be mounted in a vertical,
upright position directly to a clean, tapped opening in the top of the boiler or equipment. Under no circumstances should there be a flow restriction or valve of any type between the safety relief valve and the pressure vessel
h) WARNING!
During operation, this valve may discharge large amounts of steam and/or hot water. To reduce the potential for bodily injury and property damage, a discharge line MUST
be installed that:
OM/SM-DH CE 11
1. is connected from the valve outlet with no intervening valve and directed downward to a safe point of discharge.
2. allows complete drainage of both the valve and the discharge line
3. is independently supported and securely anchored so as to avoid applied stress on the valve.
4. is as short and straight as possible.
5. terminates freely to atmosphere where any discharge will be clearly visible and is at no risk of freezing.
6. terminates with a plain end that is not threaded.
7. is constructed of a material suitable for exposure to temperatures of 375º F or greater.
8. is, over its entire length, of a size equal to or greater than the valve outlet.
Use only schedule 40 pipe for discharge. (Do not use schedule 80, extra strong pipe or connections). DO NOT CAP, PLUG, OR
OTHERWISE OBSTRUCT DISCHARGE PIPE OUTLET!
9) See appropriate ASME Boiler and Pressure Vessel Code for additional installation instructions.
3.1 Conversion
See Paragraphs 1.8 and 1.9 for important information for gas conversion. Verify the type of gas to be used.
To change the type of gas used (e.g. G20 to G25 or G31) change the following:
Burner injector Pressure setting Data plate
The governor spring does not need to be changed; only the pressure setting.
AL L CONVERSIONS MUS T BE FOR APPROVED GAS IN THE COUNTRIES LISTED IN PARAGRAPH 1.9.
IMPORTANT THIS APPLIANCE WAS FITTED AT THE FACTORY WITH GAS INJECTORS FOR TYPE G20 NATURAL GAS. INJECTORS FOR TYPE G25 NATURAL GAS ARE SHIPPED AS AN ACCESSORY. PRIOR TO INSTALLING EQUIPMENT, OR WHEN CONVERTING TO ANOTHER GAS, VERIFY THAT THE INJECTOR SIZE MARKING ON THE GAS INJECTOR MATCHES THE INFORMATION ON THE DATA PLATE FOR THE TYPE OF GAS BEING USED.
3.2 Jacket Vacuum
When the kettle is cold, a positive reading or a reading around zero on the pressure vacuum gauge indicates an excess of air in the jacket. Air in the jacket slows down kettle heating.
To remove air:
a) Light the unit. (Paragraph 2.5.1 )
b) When the pressure/vacuum gauge reaches
a positive pressure reading of 5 PSI, release air and steam by lifting the lever on the safety valve for about one second. Repeat this a few times. Then let the lever snap back to the closed position.
See detailed Instructions on Page 11 pertaining to Safety Valve installation and operation.
WARNING A V O I D EXPOSURE TO STEAM BLO W ING O U T O F T H E S A F E T Y VALVE.
3.3 Jacket Filling (TURN OFF GAS AND ELECTRICITY MAINS)
The jacket has been charged at the factory with the proper amount of treated, distilled water. You may need to restore jacket water to its proper level, either because it was lost as steam during venting or by draining.
12 OM/SM-DH CE
The procedure for adding water follows:
a) If you are replacing water lost as steam, use
distilled water. If you are replacing treated water that ran out of the jacket, prepare more treated water as directed below.
b) Allow the kettle to cool completely. Using the
proper size spanner, remove the pipe plug from above the globe valve.
c) Open the globe valve and pour distilled or
treated water into the pipe plug orifice. Hold the safety valve open while you pour to let air escape from the jacket.
d) Air introduced to the jacket during the filling
operation must be removed to obtain efficient heating. See Paragraph 3.2.
See detailed Instructions on Page 11 pertaining to Safety Valve installation and operation.
3.4 Water Treatment Procedure
WARNING READ AND FOLLOW WATER TREATMENT COMPOUND LABEL PRECAUTIONS TO AVOID INJURY.
a) Fill the mixing container with the measured
amount of water required. (See Table). Use
distilled water only.
Model Kettle Capacity Jacket Capacity
DH-20
75.7 Litres 6.6 Litres
DH-40
151.4 Litres 7.1 Litres
DH-60
227.1 Litres 11.3 Litres
b) Hang a strip of pH test paper on the rim of
the container, with about 1" of the strip below the surface of the water.
c) Measure the water treatment compound you
will be using. (One way to do this is to add the compound to the water from a small measuring cup).
d) Stir the water continuously, while you slowly
add water treatment compound, until the water reaches a pH between 10.5 and 11.5. Judge the pH by frequently comparing the color of the test strip with the color chart provided in the pH test kit.
e) Record the exact amounts of water and
treatment compound used. These amounts may be used again, if the same sources of water and compound are employed. However, it is advisable to check the pH every time water is prepared. For optimum performance, use correctly treated, distilled water.
3.5 Control Panels
3.5.1 Control Cabinet Lid
a) Remove the four screws around the edge of
the lid securing it to the control cabinet.
b) Remove the lid.
c) Replace in reverse order.
3.5.2 Control Cabinet Side Panel
a) Remove lid (Para 3.5.1).
b) Remove the four screws securing the side
panel to the control cabinet.
c) Remove panel.
d) Replace in reverse order.
3.5.3 Supporting Column Access Panels
a) Remove the four screws securing the two
panels to the supporting column.
b) Remove both panels.
c) Replace in reverse order.
OM/SM-DH CE 13
OM-SM-DH-CE
OM/SM-DH-CE
3.6 Removal of Spark Ignition Module (Turn the gas and electricity mains off)
a) Remove supporting column (trunnion arm)
access panels (Paragraph 3.5.3).
b) Disconnect electrical leads from spark
ignition module.
c) Remove retaining screws securing module.
d) Withdraw spark ignition module from control
cabinet.
e) Replace in reverse order.
3.7 Removal of Low Water Level Control Relay (Turn the gas and electricity mains off)
a) Remove control cabinet lid (Para 3.5.1).
b) Remove control cabinet side panel as in
Para 3.5.2.
c) Remove low water level control from its base
by undoing the two retaining clips.
d) Replace in reverse order.
Ensure the low water level control relay is correctly oriented when re-positioned.
3.8 Removal of Tilt Switch (Turn the gas and electricity mains off)
a) Remove control cabinet lid (Para 3.5.1).
b) Remove control cabinet side panel (Para
3.5.2).
c) Disconnect electrical leads from tilt switch.
d) Remove screws securing the tilt switch.
e)
Withdraw tilt switch from control cabinet.
f) Replace in reverse order.
g) Verify that the tilt switch shuts off the burner
gas supply when the kettle is tilted. Adjustment range is 5º to 10º.
3.9 Removal of Gas Control Valve (Turn the gas and electricity mains off)
a) Remove control cabinet lid (Para 3.5.1).
b) Remove control cabinet side panel (Para
3.5.2).
c) Disconnect electrical leads from control
valve.
14 OM/SM-DH CE
d) Undo union fittings on outlet side of the
control valve.
e) Remove control valve from control cabinet.
f) Replace in reverse order.
3.10 Removal of ON/OFF Switch and Reset Button (Turn the gas and electricity mains off)
a) Remove control cabinet lid. (Para 3.5.1).
b) Remove control cabinet side panel (Para
3.5.2).
c) Disconnect electrical leads from the On/Off
switch or reset button.
d) Undo and remove retaining collar which
secures the On/Off switch to the outer surface, and the reset button to the inner surface of the control cabinet.
e) Withdraw the On/Off switch or the reset
button as required.
f) Replace in reverse order.
3.11 Removal of Neons (Turn the gas and electricity mains off)
a) Remove control cabinet lid (Para 3.5.1)
b) Remove control cabinet side panel (Para
3.5.2)
c) Disconnect the electrical leads to the neon.
d) Undo and remove the retaining collar which
secures the neon to the control cabinet.
e)
Withdraw the neon from the control cabinet.
f) Replace in reverse order.
3.12 Removal of Thermostat (Turn the gas and electricity mains off)
a) Remove supporting column access panels
(Para 3.5.3).
b) Remove panel from kettle base by undoing
the retaining screws.
c) Drain kettle by tilting kettle slightly and
undoing phial boss connection. Allow kettle to drain into a suitably sized container.
WARNING
ENSURE THAT THE
OTHER ELECTRICAL LEADS AND CONNECTIONS SITUATED IN THE KETTLE BASE DO NOT GET WET. REMOVE THEM IF NECESSARY.
Important: Drained water from kettle jacket should be retained. Jacket was charged at the factory with the correct amount of treated water. This water should be used to refill the kettle. However, if water is lost during drainage see Paragraph 3.3, Jacket Filling.
d) Remove thermostat control knob and
disconnect electrical leads.
e) Undo and remove thermostat retaining
screws securing the thermostat to the supporting column.
f) Feed thermostat phial through supporting
column and withdraw the thermostat.
g) Replace in reverse order.
h) Ensure an adequate sealant is used to seal
the replacement thermostat phial boss.
i) Once the thermostat is in place, the jacket
should be refilled. (Para 3.3)
Always refer to wiring diagram when re­connecting leads. (See Page 30)
OM/SM-DH CE 15
3.13 Removal of Pressure Switch (Turn the gas and electricity mains off)
a) Remove panel from base of kettle by
undoing the retaining screws.
b) Disconnect the electrical leads from the
pressure switch.
c) Drain kettle by tilting kettle slightly and
undoing the compression fitting at the pressure switch. Allow kettle to drain into a suitably sized container.
d) Remove and withdraw the pressure switch
from the kettle base by undoing the compression fitting.
e) Replace in reverse order.
f) Once the pressure switch is in place, the
kettle jacket should be refilled. (Para 3.3)
Always refer to wiring diagram when reconnecting electrical leads. (See Page 30)
3.14 Removal of Low Water Level Sensor (Turn gas and electricity mains off)
a) Remove panel from base of kettle by
undoing the retaining screws.
b) Disconnect the electrical leads from the
water sensor.
c) Drain the kettle by tilting it slightly and
undoing the low water level sensor. Allow the kettle to drain into a suitably sized container.
d) Remove the low water sensor from the kettle
base.
e) Replace in reverse order.
f) Ensure a suitable sealant is used to seal the
low water level sensor Boss.
g) When the low water level sensor is in place,
the jacket should be filled. (Para 3.3)
3.15 Removal of Burners (Turn the gas and electricity mains off)
a) Undo compression fitting at gas pipe to
burner manifold.
b) Disconnect electrical leads to the igniter and
flame sensor.
c) Remove the four retaining nuts securing the
burner and igniter assembly to the combustion chamber. Carefully support the weight of the burner manifold and lower the assembly to a safe position.
d) The burners are now accessible and can be
removed as required. Ensure adequate sealant is used to seal the burners.
e) Replace in reverse order.
Always check for gas soundness when any part of the gas circuit has been disturbed.
3.16 Removal Of Spark Electrode/Flame Sensing Bracket (Turn the gas and electricity mains off)
a) Perform the procedure in Para 3.5.3a.
b) Perform the procedure in Para 3.5.3b.
c) Disconnect the HT spark connection from
igniter.
16 OM/SM-DH CE
Recommended spacings are shown in this drawing.
DH-20 shown
d) Perform the procedure in Paragraph 3.13(a).
e) Remove the spark electrode or flame
sensing electrode by unscrewing it.
f) Replace in reverse order.
g) Ensure that there is an adequate spark at
the sparking electrode and that the burners light smoothly and without delay.
h) As the burners ignite, ensure that the
sparking sequence stops and that the burners remain lit.
i) If the burners do not light, or ignite but do not
remain lit, further adjustment to the sparking or sensing electrode is required.
3.17 Removal of Pressure Gauge (Turn the gas and electricity mains off)
a) Using the correctly sized spanner remove
the pressure gauge from top of the sight glass.
b) Replace with new pressure gauge ensuring
that an adequate sealing compound is used.
c) Once the pressure gauge has been
replaced, the kettle jacket will require
venting. (Para 3.2)
3.18 Removal of Sight Glass (Turn the gas and electricity mains off)
a) Remove sight glass protection bars.
b) Undo top and bottom compression fittings.
c) Allow the water in the sight glass to drain.
d) Remove the sight glass.
e) Replace in reverse order.
OM/SM-DH CE 17
f) Once the sight glass has been replaced, the
lost jacket water requires replacement. (Para
3.3)
3.19 Removal of Safety Valve (Turn the gas and electricity mains off)
a) Remove the elbow from the safety valve.
b) Remove the safety valve from kettle jacket
pipework.
c) Replace in reverse order.
d) Ensure an adequate sealing compound is
used to seal the safety valve.
e) Once the safety valve has been replaced the
jacket will need to be vented. (Para 3.2)
See detailed Instructions on Page 11 pertaining to Safety Valve installation and operation.
3.20 Removal of Filling Valve (Turn the gas and electricity mains off)
a) Remove filling valve from kettle jacket pipe-
work.
b) Replace in reverse order.
c) Ensure adequate sealing compound is used
to seal the valve.
d) Once the fill valve has been replaced the
jacket will need to be vented. (Para 3.2)
3.21 Fuse Replacement (Turn the gas and electricity mains off)
a) Remove control cabinet lid (Para 3.5.1 )
b) Remove control cabinet side panel (Para
3.5.2)
c) Remove fuse from vertical fuse holder.
d) Replace fuse (identical to fuse removed)
e) Replace in reverse order.
18 OM/SM-DH CE
4. Troubleshooting
Your Groen kettle is designed to operate smoothly and efficiently if properly maintained. However, the following are checks to make in the event of a problem. Wiring diagrams are inside the service panel.
USE OF ANY REPLACEMENT PARTS OTHER THAN THOSE SUPPLIED BY GROEN OR THEIR AUTHORIZED DISTRIBUTORS CAN CAUSE INJURY TO THE OPERATOR AND DAMAGE TO THE EQUIPMENT AND WILL VOID ALL WARRANTIES.
SYMPTOM WHO WHAT TO CHECK
Kettle is hard to tilt. User a. Gears for foreign materials, lubrication and alignment.
Burners will not light. User a. Is main gas valve open (handle in line with gas pipe)?
b. Gas supply to your building. c. That kettle body is not tilted. d. Is electric power turned on at the circuit breaker or
fuse box, and is power being supplied to the appliance
e. Thermostat operation.
Kettle continues heating after it reaches the desired temperature.
User a. Thermostat dial setting.
Auth Service Rep Only
b. Thermostat calibration. c. Thermostat operation. Thermostat should click when
the dial is rotated above and below a setting.
Kettle stops heating before it reaches the desired temperature.
User a. Thermostat dial setting.
Auth Service Rep Only
b. Thermostat calibration. c. Thermostat. Thermostat should click when the dial is
rotated above and below a setting.
Kettle heats slowly User a. Air in jacket - pressure/vacuum gauge (20 to 30
below zero when the kettle is cold?)
Safety valve pops. User a. Air in jacket - pressure/vacuum gauge (20 to 30
below zero when the kettle is cold?)
b. Whether kettle was being heated while empty.
Auth Service Rep Only
c. If high pressure limit switch is set too high. d. Thermostat. Thermostat should click when the dial is
rotated above and below a setting.
e. Safety valve. If valve pops below 300 PSI, replace.
System does not produce a spark Auth
Service Rep Only
a. Thermostat. Close the contacts if they are open b. AC voltage between terminals “1" and “GR.” If it is
not 230 Volt, check the high limit switch, which should be closed.
c. That the high tension cable is firmly attached and in
good condition. If cracked or brittle, replace the pilot. e. Electrode ceramic for crack or break. f. Electronic spark ignition module. Replace if needed.
Spark is present but the pilot will not light.
Auth Service Rep Only
a. That the gas valve is opening. b. That pressure meets the control manufacturer’s
specifications. c. For gas at the pilot. If it is not flowing:
(1) Check pilot gas line for kinks or obstructions.
(2) Clean orifice, if necessary.
(3) Replace the pilot valve.
Pilot lights, but main burner will not come on and spark does not stay on.
Auth Service Rep Only
a. That the gas pressure meets the control
manufacturer’s specifications. b. Replace electric module.
OM/SM-DH CE 19
OM/SM-DH-CE
SYMPTOM WHO WHAT TO CHECK
Pilot lights, but main burner will not come on, the spark stays on.
Auth Service Rep Only
a. Sensor cable, to make certain that there are secure
attachments to terminal “13" and the sensor. b. Sensor ceramic for cracks. c. That cable is not grounded out. If it is, correct the
ground. d. Sensor cable for continuity and condition of
insulation. e. (1) Check the gas pressure.
(2) Clean the pilot Assembly.
(3) Tighten mechanical and electrical connections.
Pilot lights, but main burner will not come on, and spark does not stay on.
Auth Service Rep Only
a. Than gas pressure complies with nameplate ratings. b. Electronic spark ignition module. Replace if
necessary. c. That both gas solenoids are staying open.
Main burner comes on but will not stay lit.
Auth Service Rep Only
a. Check burner ground for bad wire or connection.
Replace with high temperature wire if necessary. b. Check for low gas supply pressure. If necessary,
replace ignition control module. c. Ceramic insulator or pilot flame sensor cracked.
Replace flame sensor.
20 OM/SM-DH CE
OM-SM-DH-CE
OM/SM-DH-CE
5. User Instructions
Regulations and Safety Precautions
These Appliances have been CE marked on the basis of compliance with the Gas Appliance Directive, EMC and Low Voltage Directive for the Countries, Gas Types and Pressures as stated on the Data Plate.
These appliances MUST BE installed by a competent person in conformity with the INSTALLATION AND SERVICING INSTRUCTIONS and National Regulations in force at the time.
Particular attention MUST be paid to the following:
I.E.E. Regulations for Electrical Installations Electricity at Work Regulations Gas Safety (Installation & Use) Regulations Health and Safety at Work Act Fire Precautions Act Local and National Building Regulations
Furthermore, if a need arises to convert the Appliance for use with another gas, a competent person must be consulted. Those parts which have been protected by the manufacturer MUST NOT be adjusted by the User.
Users should be conversant with the appropriate provisions of the Fire Precautions Act and the requirements of the Gas Safety Regulations. In particular the need for regular servicing by a competent person to ensure the continued safe and efficient performance of the Appliance.
WARNING
TO PREVENT SHOCKS, ALL APPLIANCES WHETHER GAS OR ELECTRIC, MUST BE EARTHED.
Upon completion of the installation, the Owners Manual should be handed to the users and the installer should instruct the responsible person(s) on the correct operation and maintenance of the Appliance. This equipment is ONLY FOR PROFESSIONAL USE, and shall be operated by QUALIFIED persons. It is the responsibility of the Supervisor or equivalent to ensure that users wear SUITABLE PROTECTIVE CLOTHING and to draw attention to the fact that, some parts will, by necessity, become VERY HOT and will cause burns if touched accidentally.
IMPORTANT - READ FIRST - IMPORTANT The Groen Steam Jacketed Kettle you have just purchased has been handcrafted from the finest materials, meticulously inspected, and carefully tested to ensure that you receive the best possible product. With reasonable care and periodic maintenance, it will provide years of faithful service. It is recommended that you establish a timetable for periodic maintenance as outlined in this manual. Space is provided in the Service Log at the back of this manual.
5.1 Equipment Description
5.1.1 General
Groen models DH are stainless steel, steam jacketed, floor mounted, tilting kettles with a self-contained, gas-heated steam source. The kettle body is welded into one piece and furnished with a reinforced bar rim and welded "butterfly" pouring lip. The interior of the kettle is polished to a 180 emery grit finish, and the
exterior is given a bright semi-deluxe finish. The unit is ASME shop inspected and registered with the National Board for working pressures up to 50 PSI. Kettle support, tilting mechanism, and controls are contained in an enclosed base resting on tubular legs with adjustable ball feet. Tilting is provided by a self­locking, worm-and-gear device.
OM/SM-DH CE 21
OM/SM-DH-CE
The self-contained steam source is heated by propane or natural gas and ignition is by electronic spark.
Charged at the factory with treated, distilled water, the steam source provides kettle temperature of 65 C to 150 C. Controls for the unit include a thermostat, pressure gauge, gauge glass, safety valve, pressure limit control, low water cut-off, on/off switch, and a multi-functional gas control valve.
The gas supply shuts off automatically when the kettle is tilted.
Service connections are required for gas and 230-V, single phase, 50-Hz electricity.
IMPORTANT
Prior to operation, clean out the kettle pan thoroughly using hot water and detergent. Rinse out and dry thoroughly.
The gas burners are protected by an electronic flame failure device which incorporates automatic ignition of the burners and instant shut-off of the gas supply to the burners should a gas supply interruption occur.
5.1.2 Available Options
Options available with listed models are :
a. No. 31 lift-off cover. b. No. 51 one piece, counterbalanced cover
with actuator. (Factory installed option). c. Basket insert. d. Water filler with swing spout and bracket e. Kettle brush kit.
5.1.3 Operational and Maintenance Safety
WARNING INSTALLATION OF THE UNIT MUST BE DONE BY PERSONNEL QUALIFIED TO WORK WI T H ELEC T R ICITY A ND PLUMBING IN ACCORDANCE WITH ALL APPLICABLE CODES.
BEFORE REPLACING ANY PARTS, DISCONNECT THE UNIT FROM THE ELECTRIC POWER SUP
PLY AND CLOSE THE MAIN GAS COCK. ALLOW FIVE MINUTES FOR UNBURNED GAS TO VENT.
TO PREVENT SHOCKS, ALL APPLIANCES WHETHER GAS OR ELECTRIC, MUST BE EARTHED.
CAUTION BE SURE ALL OPERATORS READ, UNDERSTAND, AND FOLLOW THE OPERATING INSTRUCTIONS, CAUTIONS AND SAFETY INSTRUCTIONS CONTAINED IN THIS MANUAL.
22 OM/SM-DH CE
OM/SM-DH-CE
5.2 Lighting and Operation
5.2.1 Initial Kettle Lighting and Operational Readiness Check
After the DH Kettle has been installed according to service and installation instructions, perform initial start-up as a test, to ensure that the unit is operating correctly. Refer to the pictures on this page for identification of DH kettle controls and indicators.
a) Remove all literature and packing material
from the interior and exterior of the unit.
b) Make sure gas and electricity supplies are
switched on.
c) Ensure that the kettle is filled with water
before lighting.
d) Check the water level in the jacket. The
level should be between the lines on the gauge glass. If the level is low the jacket water level will be required to be topped up. (This will require a service call).
e) Check the pressure gauge. If the gauge
does not show sufficient vacuum (20 to 30 below zero) then the jacket will require venting. (This will require a service call).
f) Switch the On/Off switch to the "On"
position. The "power on" neon will illuminate.
g) Turn the thermostat dial to the required
setting.
h) After 10-15 seconds the burners should
light. The "heat" neon will illuminate.
i) In the event the burners do not light, or go
out as indicated by the illumination of the lockout indicating neon, turn the unit off. Wait approximately one minute. Press the lockout reset and repeat steps (d) to (h).
WARNING AVOID CONTACT WITH THE FLUE. SURFACES ARE VERY HOT AND WILL CAUSE BURNS.
DO NOT OBSTRUCT FLUE OPENING.
5.2.2 To Shut Down Kettle
a. Turn the thermostat dial to the "Off''
position.
b. Switch the On/Off switch to the "Off"
position.
c. For a prolonged shut down, turn the gas
and electricity mains off.
Follow steps a and b.
OM/SM-DH CE 23
OM/SM-DH-CE
5.2.3 Filling the Kettle
Prior to operation, thoroughly clean the kettle using hot water and detergent.
Kettle capacities:
Model Maximum Capacity DH-20 75 Litres DH-40 150 Litres DH-60 225 Litres
To prevent surge boiling, no more than 80% of the maximum capacity should be used.
5.2.4 Users Thermostat
Provides automatic control of the Kettle Jacket temperature at settings up to 147 C maximum.
5.2.5 Sequence of Operation
The following "sequence of operation" outline is provided to help the user understand how the unit functions.
When the operator sets a temperature on the thermostat dial, the thermostat switch closes and sends a signal which (1) starts the spark and (2) opens the automatic valve for the burners.
The spark ignites the burner on low flow. The flame completes a circuit at the sensing probe and sends a signal that causes the spark to shut off and the automatic valve to open to full flow once a flame has been detected. If a flame is not detected within 15 seconds the gas is automatically cut-off and the appliance is locked-out. The unit can only be re-lit once the reset button has been pressed.
In addition to the lockout timer, safety features include:
a. Low-water cut-off relay that will shut off the
gas supply to all burners until the water level is corrected.
b. High pressure switch, set to open at about
46 PSI and shut down the burners until jacket pressure is decreased.
c. Pop safety valve, which will release steam
if the jacket pressure exceeds 50 PSI.
See detailed Instructions on Page 11 pertaining to Safety Valve installation and operation.
d. Tilt cut-off switch that shuts off all burners
when the kettle is tilted.
When the kettle reaches the set temperature, the thermostat switch opens, stopping the signal to the gas control valve and causing the valve to shut off all gas flow. When the kettle cools below the set temperature, the thermostat switch closes and starts another heating cycle. On-off cycling continues and maintains the kettle at the desired temperature.
5.2.6 To Empty Kettle
5.2.6.1 DH and DHT Kettles
To tilt the body of the kettle forward, turn the hand crank on the front of the cabinet anti­clockwise. The body will stay in the position it holds when you stop turning the handle. To return the body to the upright position, turn the crank clockwise.
5.2.6.2 DHT Kettle Only
Turn the handle on the tangent draw-off valve anti-clockwise. After approximately 3-1/2 turns the valve handle can be pulled forward so that full flow is achieved. To close the tangent draw-off valve, push the handle inward until the threads on the valve stem engage. Turn the handle clockwise until the valve is closed. Do not over-tighten since over-tightening may damage the valve seat.
WARNING DO NOT STAND IN FRONT OF THE KETTLE BODY WHEN TILTING IT. BE CAREFUL TO KEEP HOT CONTENTS FROM SPILLING. ENSURE PEOPLE ARE KEPT AWAY FROM THE KETTLE WHEN EMPTYING THE KETTLE.
5.2.7 Power Failure
If the power to the unit fails do not attempt to operate the appliance until the electricity supply is re-established.
When the power comes back on follow the steps in Paragraph 5.2.1 Initial Kettle Lighting and Operational Readiness Check.
24 OM/SM-DH CE
OM/SM-DH-CE
5.3 Cleaning and Maintenance
CAUTION DISCONNECT THE ELECTRICITY SUPPLY BEFORE ANY CLEANING IS UNDERTAKEN. THE APPLIANCE MUST NOT BE CLEANED WITH A JET OF WATER OR STEAM CLEANED.
5.3.1 Suggested Tools
a) Detergent and sanitizing agent, or a
combination cleaning - sanitizing agent.
b) Long handled and short handled kettle
brushes.
5.3.2 Precautions
Before cleaning, shut off the burner by turning the thermostat dial to "OFF". If water or cleaning/sanitizing solution will be sprayed, shut off all electric power to the unit at a remote switch such as the circuit breaker.
WARNING KEEP WATER AND SOLUTIONS OUT OF CONTROLS, GEARS AND BURNERS. NEVER SPRAY OR HOSE THE CONTROL CONSOLE, ELECTRICAL CONNECTIONS, TILTING MECHANISM OR CABINET.
5.3.3 Procedure
a) Clean all food contact surfaces as soon as
possible after use, preferably while the kettle is still hot. If the unit is in continuous use, thoroughly clean and sanitise both interior and exterior at least once every 12 hours
b) Scrape and flush out large amounts of food
residues. Be careful not to scratch the kettle with metal implements.
c) Prepare a hot solution of the detergent or
cleaning compound as instructed by the supplier. Clean the unit thoroughly. A cloth moistened with cleaning solution can be used to clean controls, control housings electrical conduit, etc.
d) Rinse kettle and draw-off parts thoroughly
with hot water, then drain completely. Keep draw-off parts together. They are not interchangeable.
e) When you reassemble the draw-off valve
hand tighten only.
f) As part of the daily cleaning program, clean
all external and internal surfaces that may have been soiled. Remember to check such parts as the underside of the kettle and the control housing.
g) To remove materials stuck to the
equipment, use a brush, sponge, cloth, plastic or rubber scraper, or plastic wool along with the detergent solution. To minimize the effort required in washing, let the detergent solution sit in the kettle and soak into the residue, or heat the detergent solution briefly. Do not use any abrasive materials or metal implement that might scratch the surface. Scratches make the surface hard to clean and provide places for bacteria to grow. DO NOT use steel wool, which may leave particles imbedded in the surface and cause eventual corrosion and pitting
h) The exterior of the unit may be polished
with a recognized stainless steel cleaner or with hot water and detergent.
i) When the equipment needs to be sanitized,
use a sanitizing solution equivalent to one that supplies 200 parts per million available chlorine. Obtain advice on the best sanitizing agent from your supplier of sanitizing products. Following the suppliers instructions, apply the sanitizing agent after the unit has been cleaned and drained. Rinse off the sanitizing agent thoroughly.
CAUTION LEAVING A CHLORINE SANITIZING AGENT IN CONTACTWITH STAINLESS STEEL FOR MORE THAN
30 MINUTES CAN CAUSE
CORROSION.
j) It is recommended that the unit be sanitized
before use.
k) If there is difficulty removing mineral
deposits or a film left by hard water or food residues, clean the kettle thoroughly and then use a deliming agent, such as GroenDelimer Descaler (P/N 114800) or LimeAway from Eco Lab Inc., in accordance with the manufacturer's
OM/SM-DH CE 25
OM/SM-DH-CE
directions. Rinse and drain the unit before further use.
l) If especially difficult cleaning problems
persist, contact your cleaning product supplier for assistance.
5.3.4 Safety Precautions
A stopcock will be fitted in the gas pipe supplying the appliance. The user must be familiar with its location and operation to turn it off in an emergency. If there is a smell of gas, turn off the gas, ventilate the area and call the gas supplier. Do not search for gas leaks with naked flames.
5.3.5 Service-Periodic Maintenance
A Maintenance and Service Log is attached. Each time maintenance is performed on your Groen equipment, enter the date on which the work was done, what was done and who did it. File the log with the warranty. Periodic inspection can minimize equipment down time and increase the efficiency of operation. The following points should be checked regularly:
a. The pressure/vacuum gauge should show a
vacuum of 20 to 30 inches when the kettle is cold. If it does not, the unit requires servicing.
b. The jacket water level should be between
the gauge glass marks. If it is not, the unit requires servicing.
c. Keep electrical wiring in good condition.
26 OM/SM-DH CE
OM/SM-DH-CE
Parts List
OM/SM-DH CE 27
OM/SM-DH-CE
Parts List
Key Description Part No. Key Description Part No.
1 Foot, Adjustable Bullet 013275 22 Label, Wiring Diagram 113077 2 Light, Indicator, Amber 220 VAC 116382 23* Burner & Flame Sensor Assembly 3 Switch, Toggle DPST 122004 23a* Burner & Flame Sensor Assy DH-20 117016 4 Label, Indicator Lights 113076 23a1* Burner Assy w/Manifold (DH-20 G20) 160362 5 Label, Operating Instructions 113075 23a2* Burner Injector (DH-20 Nat Gas G-20) 107122 6 Light, Indicator, Red 220 VAC 116381 23a3* Burner Injector (DH-20 Nat Gas G-25) 127557 7 Switch, Push Button (Momentary) 122003 23a4* Burner Injector (DH-20 PropGas G-31) 127564 8 Knob, Thermostat 122000 23b* Burner & Flame Sensor Assy DH-40 117015
9 Thermostat 009730 23b1* Burner Assy w/Manifold DH-40 G20 160364 10 Screw, Rnd Hd Mach #6-32 x 3/8” 009697 23b2* Burner Injector (DH-40 Nat Gas G-20) 102943 11 Thermostat Adapter 107172 23b3* Burner Injector (DH-40 Nat Gas G-25) 102943 12 Water Fill and Safety Valve Assly 097008 23b4* Burner Injector (DH-40 PropGas G-31) 127555
12a Valve, Safety 097005 23c* Burner & Flame Sensor DH-60 117014 12b Valve, Check 004187 23c1* Burner Assy w/Manifold DH-60 G20 160366 12c Valve, Gate 004180 23c2* Burner Injector (DH-60 Nat Gas G-20) 068964
13 Flue Stack Assembly DH-20 117039 23c3* Burner Injector (DH-60 Nat Gas G-25) 102945 13 Flue Stack Assembly DH-40 117034 23c4* Burner Injector (DH-60 PropGas G-31) 127555 13 Flue Stack Assembly DH-60 117030 23d* Igniter/Sensor Bracket Assembly 117003 14 Tilt Gear Mechanism Assembly 045752 23e* Spark/Sensing Probe 003328
14a Key, 3/8" Sq x 1-3/8" lg 001474 24 Wire Harness 14b Screw, hex hd ½ 13 x 1-1/2 008679 24a Wire Harness, Main 122045 14c Nut, hex 1/2"-13 005705 24b Wire Harness, Igniter & Sensor 122044 14d Washer, lock, 1/2" 005735 25 Gas Inlet Adapter ½ BSPT x ½ NPT 116392 14e Housing, Bearing Assy 009762 26 Water Level Probe 015589
14f Bearing Ball 009765 31 Pilot Ignition Control 113060 14g Gear, Worm 012026 32 Bracket, Gas Supply Piping 117025 14h Pin, Roll, 1/4" dia x 1" Lg 012614 40 Gasket, “U” Groove 007937
14i Ring, Retaining, Internal 1 - 3/4" 013483 41 Bottom Cover (DH-20) 049799
14j Gear, 92 T, 3" Bore 013609 41 Bottom Cover (DH-40, 60) 090630 14k Handle, Crank ¾ “ Bore 013617 43 Screw, truss head #10-32 x 1/2" lg 072189
14l Shaft, Handle, 3/4" x 13-1/2" 013624 45 Gas Test Nipple 117051
14m Spacer, 3" 013625 46 Nut Hex #8-32 002632
15 Faucet Bracket 009054 47 Water Level Switch Assy 097075 17 Equipotential Assembly 122021 48 Water Level Electrode 074665
18 Electrical Panel Assembly 122024 49 Boot Electrode 010390 18a Relay, Water Level Sensor 117737 50 Pressure Switch 108559 18b Base, Water Level Sensor Relay 117738 - Water Treatment Kit 110324 18c Terminal Block 003888 - TDO Replacement Parts 18d Panel, Electrical 122037 - Valve Stem 009048 18e Holder, Fuse 3 AG 077854 - Bonnet 009047
18f Fuse, 3 AMP, Fast Blow 079965 - O-Ring 009034
19 Hex Keps Nut ¼-20 012940 - Hex Nut 009354
21 Gas Piping Assy DH-20 (See Pg 30) 122048 - Handle 009029
21 Gas Piping Assy DH-40 (See Pg 30) 122025 - Wing Nut 009028
21 Gas Piping Assy DH-60 (See Pg 30) 122074
*NOTE: See Paragraph 1.10 (Page 7) for permissible conversions.
28 OM/SM-DH CE
OM/SM-DH-CE
Parts List, Continued
Gas Valve and Piping Assembly
Key Description Part No. Key Description Part No.
21 Gas Piping Assy i Nipple, 1/2" NPT x 8-1/2 BI 003943
a Elbow, 90 deg. 1/2" NPT BI 008747 j Screw, M5x10mm Lg, Phillips Pan hd 116388 b Nipple, Close, 1/2" NPT x 1/2" BSPT 116394 k1 Nipple, 1/2" NPT x 11" BI 005673 c Bracket, Mounting, Gas Valve 122014 k2 Nipple, 1/2" NPT x 13" BI 005674 d Valve, Gas (G20/G25 Gas) 114505 l1 Nipple, 1/2" NPT x 5-1/2" BI 010234 e Elbow 90 Deg Union, 1/2" NPT BI 005495 l2 Nipple, 1/2" NPT x 7" BI 005556
f Nipple 1/2" NPT x 4-1/2 BI 008569 l3 Nipple, 1/2" NPT x 9" BI 027224 g Swivel Joint 001155 m Nipple, 1/2" NPT x 2-1/2" BI 005552 h Coupling, Full 1/2" NPT BI 005722 n Fitting, 1/2" NPT x 5/8" tube 049093
OM/SM-DH CE 29
30 OM/SM-DH CE
OM/SM-DH-CE
Service Log
Model m _______________________________ Purchased From _________________________
Serial m _______________________________ Location ________________________________
Date Purchased __________________________ Date Installed ___________________________
Purchase Order m ______________________ For Service Call __________________________
Date Service Performed Performed By
OM/SM-DH CE 31
OM/SM-DH-CE
Service Log
Model m _______________________________ Purchased From _________________________
Serial m _______________________________ Location ________________________________
Date Purchased __________________________ Date Installed ___________________________
Purchase Order m ______________________ For Service Call __________________________
Date Service Performed Performed By
32 OM/SM-DH CE
OM/SM-DH-CE
Service Log
Model m _______________________________ Purchased From _________________________
Serial m _______________________________ Location ________________________________
Date Purchased __________________________ Date Installed ___________________________
Purchase Order m ______________________ For Service Call __________________________
Date Service Performed Performed By
OM/SM-DH CE 33
OM/SM-DH-CE
Service Log
Model m _______________________________ Purchased From _________________________
Serial m _______________________________ Location ________________________________
Date Purchased __________________________ Date Installed ___________________________
Purchase Order m ______________________ For Service Call __________________________
Date Service Performed Performed By
34 OM/SM-DH CE
Limited Warranty To Commercial Purchasers*
(for Areas Outside of the U.S. and Canada)
Groen Foodservice Equipment ("Groen Equipment") has been skillfully manufactured, carefully inspected and packaged to meet rigid standards of excellence. Groen warrants its Equipment to be free from defects in material and workmanship for (12) twelve months from date of installation or (18) eighteen months from date of shipment with the following conditions and subject to the following limitations.
I. This parts warranty is limited to Groen Equipment sold to the original commercial purchaser/users
(but not original equipment manufacturers), at its original place of installation, in areas outside the U.S. and Canada.
II. Damage during shipment is to be reported to the carrier, is not covered under this warranty, and is
the sole responsibility of the purchaser/user.
III. Groen, or an authorized service representative, will repair or replace parts, at Groen's sole election,
for any Groen Equipment, including but not limited to, drawoff valves, safety valves, gas and electric components, found to be defective during the warranty period.
IV. This warranty does not cover boiler maintenance, calibration, or periodic adjustments as specified in
operating instructions or manuals, and consumable parts such as scraper blades, gaskets, packing, etc., or labor costs incurred for removal of adjacent equipment or objects to gain access to Groen Equipment. This warranty does not cover defects caused by improper installation, abuse, careless operation, or improper maintenance of equipment. This warranty does not cover damage caused by poor water quality or improper boiler maintenance.
V. THIS WARRANTY IS EXCLUSIVE AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED
OR IMPLIED, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, EACH OF WHICH IS HEREBY EXPRESSLY DISCLAIMED. THE REMEDIES DESCRIBED ABOVE ARE EXCLUSIVE AND IN NO EVENT SHALL GROEN BE LIABLE FOR SPECIAL, CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR THE BREACH OR DELAY IN PERFORMANCE OF THIS WARRANTY.
VI. Groen Equipment is for commercial use only. If sold as a component of another (O.E.M.)
manufacturer's equipment or if used as a consumer product, such Equipment is sold AS IS and without any warranty.
* (Covers All Food Service Equipment Ordered After October 1,1995)
OM/SM-DH CE 35
1055 Mendell Davis Drive • Jackson MS 39272
888-994-7636 • 601-372-3903 • Fax 888-864-7636
groen.com
PART NUMBER 128417, REV. D (6/06)
Loading...