Greenheck SMD-M201 User Manual

SMOKE DAMPERS
R
Application
Model SMD-M201 is a leakage rated smoke damper with 3V style blades. The SMD-M201 has been qualified to 10.2 m/s and 1 kPa for operational closure in emergency smoke control situations. Model SMD-M201 may be installed vertically (with blades running horizontally) or horizontally and is rated for airflow and leakage in either direction.
Ratings
UL 555S Leakage Rating
Leakage Class: I Operational Rating: Limits are actuator dependant Maximum Velocity: 10.2 m/s Maximum Pressure: 1 kPa Maximum Temperature: 177°C—Depending on actuator
Construction Standard Optional
Frame Material Galvanized steel -
Frame Material Thickness
Frame Type 127mm x 25mm
Blade Material Galvanized steel -
Blade Material Thickness
Blade Type 3V -
Linkage Plated steel out of
Axle Bearings Bronze -
Axle Material Plated steel -
Blade Seals Silicone -
Jamb Seals 304SS -
1.5mm
(16 ga.)
(5 in. x 1in.) hat channel
1.5mm
(16 ga.)
airstream, concealed
in jamb
-
Double Flange
-
-
Model SMD-M201
Steel 3V Blades
UL 555S Leakage Class I
Model SMD-M201 meets the requirements for smoke dampers established by:
National Fire Protection Association
NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes
“UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standard 555S (Listing #R13447)
Greenheck Kunshan Co. Ltd. and Greenheck Fan Corporation certifies that the model SMD-M201 shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to air performance ratings only.
W
Size Limitations
W x H Minimum Size
mm 203 x 152 813 x 1270 or
Inches 8 x 6 32 x 50 or
Single Section Multi- Section
Options:
• OCI(OpenClosedIndicationswitches)
• Galvanizedsteelsleeved
• Actuators(24V,230V)
• Flanges
• Momentarytestswitch
• POCretainingangles
• 69°C fusible link (BS476)
• Transitions(R,C)
•Sleevewithintegralflangeonboth sides
available
Maximum Size
914 x 1219
36 x 48
H
3658 x 2540 or
7315 x 1270
144 x 100 or
288 x 50
LH
* W&H dimensions furnished approximately 6mm undersize.
(Add sleeve thickness for overall sleeved damper dimension) Right hand drive is shown. Left hand drive is available upon request.
Features:
 •Framesareconstructedwithreinforcedcorners.
Low profile head and sill are used on sizes less than 432mm (17 in.) high.
 •Bladesarereinforcedwith3longitudinalstructurally
designed vee's.
 •Actuators:24Vor230V
Installation instructions available at www.greenheck.com
RH
Pressure Drop Data SMD-M201
5D 6D
5D
D
4 (W) (H
)
3.14
This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of 1.201 kg/m
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC system.
AMCA Test Figures
Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations
because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high entrance and exit losses due to the sudden changes of area in the system.