Greenheck SMD-301M User Manual

Model SMD-301M
H*
W*
Model SMD-301M is a leakage rated modulating smoke damper with class I leakage. The SMD-301M serves the function of both a control damper and smoke damper. High strength airfoil blades insure lowest resistance to airflow in HVAC systems with velocities to 2000 fpm (10.2m/s) and 4 in. wg (1 kPa) Model SMD-301M may be installed vertically (with blades running horizontal) or horizontally and is rated for airflow and leakage in either direction.
UL 555S Leakage Rating
Leakage Class: I Operational Rating Maximum Velocity: 2000 fpm (10.2m/s) Maximum Pressure: 4 in. wg (1 kPa) Maximum Temperature: 250ºF (121ºC)
Construction Standard Optional
Frame Material Galvanized Steel -
Frame Material Thickness
Frame Type
Blade Material Galvanized Steel -
Blade Material Thickness
Blade Type Double Skin Airfoil -
Linkage
Axle Bearings Bronze 304SS
Axle Material Plated Steel -
Blade Seals Silicone -
Jamb Seals 304SS -
16 ga. (1.5mm) -
5 in. x 1 in.
(127mm x 25mm)
hat channel
14 ga. (2mm)
Equivalent
Plated Steel Out
of Airstream,
Concealed in Jamb
-
-
-
Smoke Dampers
Steel Airfoil Blades
UL 555S Leakage Class I
Model SMD-301M meets the requirements for smoke dampers established by:
National Fire Protection Association
NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes New York City (MEA listing #260-91-M) CSFM California State Fire Marshal
Leakage (Smoke) Damper Listing (#3230-0981:104)
“UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
Standard 555S (Listing #R13317)
Greenheck Fan Corporation certifies that the model SMD-301M shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with
R
the requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to air performance ratings only.
Size Limitations
W x H
Inches 8 x 6 32 x 50 128 x 100
mm 203 x 152 813 x1270 3251 x 2540
Minimum
Size
Maximum Size
Single
Section
Multiple Section
OPTIONS:
• Factory mounted accessories
- Retaining angles
- Quick connect breakaway connections
- S & drive connections
- Access doors
• Greenheck test switches (GTS-3 & GTS-4)
• Momentary test switch
• POC retaining angles
• OCI (Open closed indication switches)
• Sealed transitions and sleeves
• Security bars
• Smoke detectors
• Transitions: R, C, O
LH
RH
*W&H dimensions furnished approximately 1/4 in. (6mm) undersize. Right hand drive is shown. Left hand drive is available upon request. Damper also may be rotated 180° in the field for opposite side drive.
(Add sleeve thickness for overall sleeved damper dimension)
Features:
• Frames are constructed with reinforced corners. Low profile head and sill are used on sizes less than 17 in. high (432mm).
• Blades are double skin airfoil shape of galvanized steel with full length structural reinforcement
• Actuators: 24V
Installation instructions available at www.greenheck.com
Pressure Drop Data SMD-301M
5D 6D
5D 6D
5D
D
4 (W) (H)
3.14
This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC system.
AMCA Test Figures
Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations
because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high entrance and exit losses due to the sudden changes of area in the system.
5D 6D
3
(1.201 kg/m
3
).
Figure 5.3
Figure 5.2
5D
D
4 (W) (H
3.14
)
Figure 5.5
12x12
48x12
24x24
36x36
12x48
AMCA 5.2 Pressure Drop SMD-301M
5D 6D
D
4 (W) (H)
3.14
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
Velocity
(fpm)
Pressure Drop
(in. wg)
500 0.03 500 0.01 500 0.01 500 0.01 500 0.02 1000 0.12 1000 0.06 1000 0.06 1000 0.05 1000 0.08 1500 0.26 1500 0.12 1500 0.12 1500 0.12 1500 0.18 2000 0.46 2000 0.22 2000 0.22 2000 0.21 2000 0.33 2500 0.72 2500 0.34 2500 0.34 2500 0.33 2500 0.51 3000 1.04 3000 0.49 3000 0.49 3000 0.48 3000 0.74 3500 1.41 3500 0.67 3500 0.67 3500 0.65 3500 1.00 4000 1.84 4000 0.87 4000 0.88 4000 0.85 4000 1.31
12in. X 48 in.
(
305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36in. x 36 in. (914mm x 914mm) 12 in. x 12 in. (305mm x 305mm)
5D
* Sizes are in inches.
R
Greenheck Fan Corporation certifies that the model SMD-301M shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Pro­grams. The AMCA Certified Ratings Seal applies to air performance ratings only.
Loading...
+ 4 hidden pages