Greenheck SES-401 Installation Manual

Sightproof Louver
Application and Design
SES-401 is a sightproof louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates Chevron style blades to prevent maximum resistance to visual see through. The SES-401 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.
Standard Construction
4 in. x 0.081 in. nominal wall thickness
Blades . . . . . . . .Chevron style, heavy gauge extruded
6063-T5 aluminum, 0.081 in. nominal wall thickness, positioned on approximately 4 in. centers
Construction . . .Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 in. fl attened expanded
aluminum in removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 12 in. W x 12 in. H
Maximum Single Section Size . . . 120 in. W or 120 in. H (limited to 70 ft. sq.)
SES-401
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
Options (at additional cost)
• A variety of bird and insect screens
• Blank off panel
• Extended sill
• Filter rack
• Flanged frame
• Hinged frame
• Security bars
• A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel paint Kynar paint
*Width and height dimensions furnished
approximately ¼ inch under size.
Free Area Chart (Sq. ft.)
Louver Height Inches
12 18 30 36 48 54 66 72 84 90 102 108 120
12 0.19 0.30 0.54 0.65 0.89 1.00 1.21 1.33 1.56 1.68 1.91 2.03 2.23
18 0.34 0.55 0.98 1.19 1.62 1.83 2.21 2.42 2.85 3.06 3.49 3.70 4.08
24 0.53 0.87 1.54 1.88 2.55 2.88 3.47 3.81 4.48 4.81 5.49 5.82 6.41
30 0.65 1.07 1.92 2.34 3.19 3.61 4.35 4.77 5.62 6.00 6.78 7.20 8.05
36 0.81 1.33 2.36 2.87 3.90 4.42 5.32 5.83 6.86 6.04 8.40 8.92 9.82
42 0.97 1.59 2.82 3.43 4.66 5.27 6.35 6.96 8.19 8.80 10.03 10.65 11.72
48 1.11 1.82 3.22 3.93 5.33 6.04 7.27 7.97 9.38 10.08 11.49 12.19 13.42
54 1.32 2.15 3.82 4.66 6.32 7.16 8.62 9.45 11.12 11.95 13.62 14.45 15.91
60 1.45 2.36 4.19 5.10 6.93 7.84 9.44 10.35 12.18 13.09 14.92 15.83 17.43
66 1.61 2.62 4.65 5.67 7.69 8.71 10.48 11.50 13.53 14.54 16.57 17.59 19.36
72 1.76 2.87 5.10 6.21 8.43 9.54 11.49 12.60 14.82 15.93 18.16 19.27 21.21
78 1.89 3.08 5.47 6.66 9.05 10.24 12.33 13.52 15.91 17.10 19.49 20.68 22.77
84 2.11 3.44 6.10 7.44 10.10 11.43 13.76 15.09 17.75 19.09 21.75 23.08 25.41
90 2.22 3.62 6.43 7.83 10.64 12.04 14.50 15.90 18.71 20.11 22.91 24.32 26.77
96 2.40 3.91 6.94 8.46 11.49 13.00 15.65 17.17 20.20 21.71 24.74 26.25 28.91
102 2.55 4.16 7.38 8.99 12.20 13.89 16.63 18.24 21.46 23.07 26.29 27.90 30.71
108 2.68 4.37 7.76 9.45 12.84 14.53 17.50 19.19 22.58 24.27 27.66 29.35 32.31
114 2.84 4.64 8.23 10.03 13.62 15.42 18.56 20.36 23.95 25.74 29.34 31.13 34.27
120 3.00 4.89 8.68 10.57 14.35 16.25 19.56 21.45 25.24 27.13 30.91 32.81 36.12
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Model SES-401 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 800 900 1000 2000 3000
3
Exhaust
Intake
2345678910
Free Air Velocity
Louver Width in Inches
3
) Water Penetration (Standard Air - .075 lb/ft3)
Test size 48 in. x 48 in. Test duration of 15 min.
ml/m2 oz/ft2
0.30
80
0.25
0.20
60
0.15
40
0.10
20
Water Penetration per Unit Free Area
0.05
0.00
0
ft/min:
m/s:
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area.
penetration for Model SES-401 is 718 fpm free area velocity.
These perfor mance ratings do not guarantee a louver to be weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.
Extruded Aluminum
WATER
PENETRATION
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.
Test Size 48 in. x 48 in.
Test Period 15 minutes
Standard Air - .075 lb/ft
600 650 700 750 800
3.1 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.9 4.0
3
Free Area Velocity
The beginning point of water
*
SES-401PERFORMANCE DATA
Sightproof Louver
Greenheck Fan Corporation certifies that
AIR
the SES­401 louvers shown
®
herein are licensed to
Loading...