Sightproof Louver
Drainable Head
Application and Design
SEH-401 is a sightproof weather louver designed to protect
air intake and exhaust openings in building exterior walls when
visual see through prevention is needed. Design incorporates
a drainable head member and horizontal Chevron style blades
to provide maximum resistance to rain and weather. The SEH401 is an extremely efficient louver with AMCA LICENSED
PERFORMANCE DATA enabling designers to select and apply
with confidence.
Standard Construction
Frame . . . . . . . .Heavy gauge extruded 6063-T5 aluminum,
4 in. x 0.081 in. nominal wall thickness
Blades . . . . . . . .Chevron style, heavy gauge extruded 6063-T5
aluminum, 0.081 in. nominal wall thickness,
positioned on approximately 4 in. centers
Construction . . .Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 in. fl attened expanded aluminum in
removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 12 in. W x 12 in. H
Maximum Single
Section Size . . . 120 in. W or 120 in. H (limited to 70 ft. sq.)
Options (at additional cost)
• A variety of bird and insect screens
• Blank off panel
• Extended sill
• Filter rack
• Flanged frame
• Hinged frame
• Security bars
• A variety of architectural finishes including:
Clear anodize
Integral color anodize
Baked enamel paint
Kynar paint
SEH-401
WATER
PENETRATION
AIR
PERFORMANCE
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
®
*Width and height dimensions furnished
approximately ¼ inch under size.
Free Area Chart (Sq. ft.)
Louver Height
Inches
12 18 30 36 48 54 66 72 84 90 102 108 120
12 0.18 0.30 0.53 0.64 0.87 0.99 1.19 1.30 1.53 1.65 1.87 1.99 2.19
18 0.33 0.53 0.95 1.16 1.57 1.78 2.14 2.35 2.76 2.97 3.38 3.59 3.95
24 0.52 0.84 1.50 1.83 2.48 2.81 3.38 3.70 4.36 4.68 5.34 5.66 6.24
30 0.65 1.07 1.92 2.34 3.19 3.61 4.35 4.77 5.61 6.04 6.77 7.20 8.04
36 0.79 1.29 2.29 2.78 3.78 4.28 5.15 5.65 6.65 7.15 8.15 8.64 9.52
42 0.94 1.54 2.73 3.33 4.52 5.12 6.16 6.76 7.95 8.55 9.74 10.33 11.38
48 1.08 1.76 3.12 3.80 5.16 5.84 7.04 7.72 9.08 9.76 11.12 11.80 12.99
54 1.28 2.09 3.71 4.52 6.14 6.94 9.36 9.17 10.79 11.60 13.21 14.02 15.44
60 1.40 2.28 4.05 4.94 6.70 7.59 9.13 10.02 11.79 12.67 14.44 15.32 16.87
66 1.56 2.54 4.51 5.49 7.46 8.44 10.16 11.14 13.11 14.09 16.06 17.04 18.76
72 1.71 2.79 4.94 8.02 8.17 9.25 11.14 12.22 14.37 15.45 17.61 18.68 20.57
78 1.83 2.98 5.29 6.45 8.76 9.91 11.93 13.09 15.40 16.55 18.86 20.02 22.04
84 2.04 3.34 5.92 7.21 9.79 11.08 13.34 14.63 17.21 18.51 21.09 22.38 24.64
90 2.15 3.51 6.22 7.58 10.30 11.66 14.03 15.39 18.11 19.46 22.18 23.54 25.91
96 2.32 3.79 6.73 8.19 11.13 12.60 15.16 16.63 19.57 21.03 23.97 25.44 28.00
102 2.47 4.03 7.05 8.71 11.83 13.39 16.19 17.68 20.80 22.36 25.48 27.04 29.77
108 2.60 4.24 7.51 9.15 12.43 14.07 16.94 18.58 21.86 23.50 26.78 28.41 31.28
114 2.76 4.49 7.97 9.71 13.19 14.93 17.98 19.72 23.20 24.94 28.42 30.16 33.20
120 2.90 4.73 8.40 10.23 13.89 15.72 18.93 20.76 24.43 26.26 29.92 31.75 34.96
Louver Width in Inches
SEH-401PERFORMANCE DATA
Sightproof Louver Drainable Head
Extruded Aluminum
Greenheck
Fan
Corporation
certifies that
WATER
PENETRATION
AIR
PERFORMANCE
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
bear the AMCA Seal. The
ratings shown are based
on tests and procedures
performed in accordance
with AMCA Publication
511 and comply with
the requirements of the
AMCA Certified Ratings
Program. The AMCA
Certified Ratings Seal
applies to air performance
and water penetration
ratings.
the SEH401 louvers
shown
®
herein are
licensed to
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 800 9001000 2000 3000
3
Exhaust
Intake
2345678910
3
) Water Penetration (Standard Air - .075 lb/ft3)
Free Air Velocity
Model SEH-401 resistance to airflow (pressure drop) varies
depending on louver application (air intake or air exhaust).
Free area velocities (shown) are higher than average
velocity through the overall louver size. See louver selection
information.
Test size 48 in. x 48 in. Test duration of 15 min.
ml/m2 oz/ft2
0.30
Test Size 48 in. x 48 in.
80
60
40
20
Water Penetration per Unit Free Area
0
Test Period 15 minutes
0.25
Standard Air - .075 lb/ft
0.20
0.15
0.10
0.05
0.00
700 750 800 850 900
ft/min:
3.6 3.7 3.8 3.9 4.0 4.1 4.2 4.3 4.4 4.5
m/s:
3
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing
various louver models and designs as to their efficiency in resisting
the penetration of rainfall under specific laboratory test conditions. The
beginning point of water penetration is defined as that velocity where the
water penetration curve projects through .01 oz. of water (penetration)
per sq. ft. of louver free area.
penetration for Model SEH-401 is 765 fpm free area velocity.
The beginning point of water
*
These perfor mance ratings do not guarantee a louver to be weather proof
or stormproof and should be used in combination with other factors