Greenheck SEH-401 Installation Manual

Sightproof Louver
Drainable Head
Application and Design
SEH-401 is a sightproof weather louver designed to protect air intake and exhaust openings in building exterior walls when visual see through prevention is needed. Design incorporates a drainable head member and horizontal Chevron style blades to provide maximum resistance to rain and weather. The SEH­401 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.
Standard Construction
Frame . . . . . . . .Heavy gauge extruded 6063-T5 aluminum,
4 in. x 0.081 in. nominal wall thickness
Blades . . . . . . . .Chevron style, heavy gauge extruded 6063-T5
aluminum, 0.081 in. nominal wall thickness, positioned on approximately 4 in. centers
Construction . . .Mechanically fastened
Birdscreen . . . . .3/4 in. x 0.051 in. fl attened expanded aluminum in
removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 12 in. W x 12 in. H
Maximum Single Section Size . . . 120 in. W or 120 in. H (limited to 70 ft. sq.)
Options (at additional cost)
• A variety of bird and insect screens
• Blank off panel
• Extended sill
• Filter rack
• Flanged frame
• Hinged frame
• Security bars
• A variety of architectural finishes including: Clear anodize Integral color anodize Baked enamel paint Kynar paint
SEH-401
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
*Width and height dimensions furnished
approximately ¼ inch under size.
Free Area Chart (Sq. ft.)
Louver Height
Inches
12 18 30 36 48 54 66 72 84 90 102 108 120
12 0.18 0.30 0.53 0.64 0.87 0.99 1.19 1.30 1.53 1.65 1.87 1.99 2.19
18 0.33 0.53 0.95 1.16 1.57 1.78 2.14 2.35 2.76 2.97 3.38 3.59 3.95
24 0.52 0.84 1.50 1.83 2.48 2.81 3.38 3.70 4.36 4.68 5.34 5.66 6.24
30 0.65 1.07 1.92 2.34 3.19 3.61 4.35 4.77 5.61 6.04 6.77 7.20 8.04
36 0.79 1.29 2.29 2.78 3.78 4.28 5.15 5.65 6.65 7.15 8.15 8.64 9.52
42 0.94 1.54 2.73 3.33 4.52 5.12 6.16 6.76 7.95 8.55 9.74 10.33 11.38
48 1.08 1.76 3.12 3.80 5.16 5.84 7.04 7.72 9.08 9.76 11.12 11.80 12.99
54 1.28 2.09 3.71 4.52 6.14 6.94 9.36 9.17 10.79 11.60 13.21 14.02 15.44
60 1.40 2.28 4.05 4.94 6.70 7.59 9.13 10.02 11.79 12.67 14.44 15.32 16.87
66 1.56 2.54 4.51 5.49 7.46 8.44 10.16 11.14 13.11 14.09 16.06 17.04 18.76
72 1.71 2.79 4.94 8.02 8.17 9.25 11.14 12.22 14.37 15.45 17.61 18.68 20.57
78 1.83 2.98 5.29 6.45 8.76 9.91 11.93 13.09 15.40 16.55 18.86 20.02 22.04
84 2.04 3.34 5.92 7.21 9.79 11.08 13.34 14.63 17.21 18.51 21.09 22.38 24.64
90 2.15 3.51 6.22 7.58 10.30 11.66 14.03 15.39 18.11 19.46 22.18 23.54 25.91
96 2.32 3.79 6.73 8.19 11.13 12.60 15.16 16.63 19.57 21.03 23.97 25.44 28.00
102 2.47 4.03 7.05 8.71 11.83 13.39 16.19 17.68 20.80 22.36 25.48 27.04 29.77
108 2.60 4.24 7.51 9.15 12.43 14.07 16.94 18.58 21.86 23.50 26.78 28.41 31.28
114 2.76 4.49 7.97 9.71 13.19 14.93 17.98 19.72 23.20 24.94 28.42 30.16 33.20
120 2.90 4.73 8.40 10.23 13.89 15.72 18.93 20.76 24.43 26.26 29.92 31.75 34.96
Louver Width in Inches
SEH-401PERFORMANCE DATA
Sightproof Louver Drainable Head
Extruded Aluminum
Greenheck Fan Corporation certifies that
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.
the SEH­401 louvers shown
®
herein are licensed to
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 800 9001000 2000 3000
3
Exhaust
Intake
2345678910
3
) Water Penetration (Standard Air - .075 lb/ft3)
Free Air Velocity
Model SEH-401 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
Test size 48 in. x 48 in. Test duration of 15 min.
ml/m2 oz/ft2
0.30
Test Size 48 in. x 48 in.
80
60
40
20
Water Penetration per Unit Free Area
0
Test Period 15 minutes
0.25
Standard Air - .075 lb/ft
0.20
0.15
0.10
0.05
0.00
700 750 800 850 900
ft/min:
3.6 3.7 3.8 3.9 4.0 4.1 4.2 4.3 4.4 4.5
m/s:
3
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area.
penetration for Model SEH-401 is 765 fpm free area velocity.
The beginning point of water
*
These perfor mance ratings do not guarantee a louver to be weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.