Document Number 461868
FSDR-XXX, SEFSDR-XXX,
®
AND SSFSDR-XXX MODELS
1 1⁄2 Hour Fire & Combination Fire
Smoke Dampers
Vertical and Horizontal Mount
Installation, Operation and Maintenance Instructions
FSDR-XXX, SEFSDR-XXX, and SSFSDR-XXX Model
Dampers are intended for installation in accordance
with combination fire smoke damper requirements
established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshal (CSFM)
Fire Listing (3225-0981:0112)
Leakage Listing (3230-0981:0113)
INSTALLATION SUPPLEMENTS
Refer to the appropriate Greenheck installation
supplements for special requirements:
• Steel Deck Supplement
RECEIVING AND HANDLING
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100°F (38°C).
WARRANTY
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the shipment date. Any units or parts which
prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not
be responsible for any service work or backcharges
without prior written authorization.
“UL CLASSIFIED (see complete marking on
product)”
“UL CLASSIFIED to Canadian safety standards (see
complete marking on product)”
UL Standard 555 & 555S (Classification #R13317)
ELECTRICAL GUIDELINES
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specifications.
SAFETY WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment. To avoid causing death or serious bodily harm
to building occupants, follow all instructions carefully.
Dampers must close completely to preserve the integrity
of the fire smoke separation.
SAFETY CAUTION!
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit
caused by incorrect field wiring.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the
job is complete.
Table of Contents
Pre-Installation Guideline ..............................................................................................................................................2
Installation ................................................................................................................................................................. 3-6
• Clearances Required Between Fire Damper Sleeves and Wall/Floor Openings ....................................................3
• Sleeve Length and Wall Thickness ............................................................................................................................3
• Round Duct Connections ...........................................................................................................................................3
• Securing the Damper Assembly to Wall and Floor Openings ............................................................................. 3-4
• Actuator Connections ................................................................................................................................................4
• Connection and Operation of Temperature Control Devices ............................................................................... 4-5
• FSDR-XXX and DFDR-XXX Blade Orientation ..........................................................................................................5
• Recommended Preparation of Openings in Wood and Metal Stud ........................................................................6
Maintenance ..................................................................................................................................................................7
Troubleshooting .............................................................................................................................................................7
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the fire smoke or fire damper in the opening in such a manner
as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire or fire smoke
damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse
of the hanging system. The following items will aid in completing the damper installation in a timely and effective
manner.
1) Check the schedules for proper damper locations
within the building. Visually inspect the damper for
damage and verify that the fusible link is in place or
has not separated. If fusible link is not present or has
separated, replace link. Never install a fire damper
without the proper UL approved fusible link in place.
(Fusible link is standard control option. An electric
link may have been provided. Electric links have a
button for resetting.)
2) Lift or handle damper using the frame. Do not lift
damper using blades or actuators.
3) Do not install screws into the main body area of
the damper frame as screws may interfere with and
prevent damper blade from opening and/or closing.
4) Damper has label indicating position of damper
assembly in the wall. Install accordingly to comply
with manufacturer’s appropriate UL Classification file
number.
5) Damper must be installed into duct or opening free of
distortion or other misalignment. Damper must not be
squeezed or stretched into duct or opening. Out of
round, racked, twisted or misaligned installations can
cause excessive leakage and/or torque requirements
to exceed damper/actuator design.
6) Damper and actuator must be kept clean and
protected from dirt, dust and other foreign materials
prior to and after installation. Examples of such
foreign materials include but are not limited to:
a) Mortar dust
b) Drywall dust
c) Firesafing materials
d) Wall texture
e) Paint overspray
7) Damper should be sufficiently covered as to prevent
overspray if wall texturing or spray painting will be
performed within 5 feet of the damper. Excessive dirt
or foreign material deposits on damper can cause
excessive leakage and/or torque requirements to
exceed damper/actuator design.
8) Caulking is not necessary, nor is it allowed, between
the damper sleeve and the wall or floor opening
(annular space). However, caulking may be applied to
the retaining plates.
9) ACCESS: Suitable access (such that fusible links,
RRL’s, actuators, and linkages can be maintained)
must be provided for damper inspection and
servicing. Where it is not possible to achieve
sufficient size access, it will be necessary to install a
removable section of duct. (Refer to NFPA 90A).
10) The Code Authority Having Jurisdiction (AHJ) must
evaluate and provide approval of final installation
where variations to these instructions are necessary.
Installation - Failure to follow these instructions will void all warranties.
These instructions apply to 1½ hour rated combination fire smoke and fire dampers mounted in: 1) masonry, block or
stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory. Dampers must be
installed in accordance with these instructions to meet the requirements of UL 555 and UL 555S. The installation of the
damper and all duct connections to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard
for the Installation of Air Conditioning and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Damper
Installation Guide, and UL Classifications R13317.
2
3.375 IN.
FUSIBLE
LINK
LOCATION
CLEARANCE FOR
EXPANSION
6 IN. MAX
SLEEVE LENGTH
TW
DUCT
CONNECTION
AREA
AIRFLOW
1.50 IN.
ACTUATOR
16.00 IN MAX
OPTIONAL BLADE POSITION
INDICATOR AND/OR ELECTRIC
LINK.
DUCT
CONNECTION
AREA
2.00 IN.
1.50 IN.
Optional
Second
Retaining
Plate
Do not place retainer
plate in this groove
1. CLEARANCES REQUIRED BETWEEN FIRE
DAMPER SLEEVES AND WALL/FLOOR
OPENINGS
Fire damper assemblies expand during periods of
intense heat. Therefore, it is essential that openings in
walls or floors be larger than the fire damper assembly
to allow for this expansion. The wall/floor opening
must be a minimum of 7/8 in. (22mm) larger than the
outside diameter of the damper. Refer to Section 4 for
additional installation considerations.
2. SLEEVE LENGTH AND WALL/FLOOR
THICKNESS
Insert the damper assembly into the prepared opening,
to appropriate depth (see Fig. 1).
Recommended maximum and minimum insertion depth
can be exceeded if:
1) the operation of the damper actuator is not
impeded and
2) the CL of the damper blade remains within
the plane of the wall/floor
IMPORTANT SAFETY DANGER! : To avoid
causing death or serious bodily harm to
building occupants, do not insert screws
into the damper frame unless used for duct
connection within 2 in. (51mm) of the frame
end.
The sleeve may extend a maximum of 16 in. (406mm)
beyond the wall or floor on the actuator side of the
damper and a maximum of 6 in. (152mm) on the
opposite side.
Fig. 1
3. ROUND DUCT CONNECTIONS
Round duct connections to shall be attached with #8 or
#10 sheet metal screws as follows:
• Ducts 22 in. (558mm) dia. and smaller shall have
three screws.
• Ducts larger than 22 in. (558mm) dia. up to and
including 24 in. (610mm) dia. shall have five screws.
NOTE: All connections described may have duct
sealant, PA2084T duct sealant adhesive manufactured
by Precision, DP1010 water base duct sealant
manufactured by Design Polymetrics, Grey Pookie,
Ductmate PROseal®, or CL Ward S Seal applied in
accordance with SMACNA recommendations.
4. SECURING THE DAMPER/SLEEVE ASSEMBLY
TO WALL AND FLOOR OPENINGS
Damper assemblies must be installed in wall/floor
openings using a single retaining plate on either side of
the wall/floor or by using a retaining plate on both sides
of the wall/floor. The use of a second retaining plate is
allowed, but is not necessary. A single retaining plate
is provided with the dampers. A second retaining plate
can be ordered as an option. The outside dimension of
the supplied retainer plate is nominal dia. + 4½ inches
(114mm).
3