Greenheck SEFSDR-XXX Installation Manual

Document Number 461868
FSDR-XXX, SEFSDR-XXX,
®
AND SSFSDR-XXX MODELS
1 1⁄2 Hour Fire & Combination Fire
Smoke Dampers
Vertical and Horizontal Mount
Installation, Operation and Maintenance Instructions
FSDR-XXX, SEFSDR-XXX, and SSFSDR-XXX Model Dampers are intended for installation in accordance with combination fire smoke damper requirements established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes New York City (MEA listing #260-91-M) California State Fire Marshal (CSFM)
Fire Listing (3225-0981:0112) Leakage Listing (3230-0981:0113)
INSTALLATION SUPPLEMENTS
Refer to the appropriate Greenheck installation supplements for special requirements:
• Steel Deck Supplement
RECEIVING AND HANDLING
Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C).
WARRANTY
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.
“UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
UL Standard 555 & 555S (Classification #R13317)
ELECTRICAL GUIDELINES
All wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70 latest edition, any local codes that may apply, and wiring diagrams developed in compliance with the job or project design and specifications.
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment. To avoid causing death or serious bodily harm to building occupants, follow all instructions carefully. Dampers must close completely to preserve the integrity of the fire smoke separation.
SAFETY CAUTION!
Electrical input may be needed for this equipment. This work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of the unit caused by incorrect field wiring.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.
Table of Contents
Pre-Installation Guideline ..............................................................................................................................................2
Installation ................................................................................................................................................................. 3-6
• Clearances Required Between Fire Damper Sleeves and Wall/Floor Openings ....................................................3
• Sleeve Length and Wall Thickness ............................................................................................................................3
• Round Duct Connections ...........................................................................................................................................3
• Securing the Damper Assembly to Wall and Floor Openings ............................................................................. 3-4
• Actuator Connections ................................................................................................................................................4
• Connection and Operation of Temperature Control Devices ............................................................................... 4-5
• FSDR-XXX and DFDR-XXX Blade Orientation ..........................................................................................................5
• Recommended Preparation of Openings in Wood and Metal Stud ........................................................................6
Maintenance ..................................................................................................................................................................7
Troubleshooting .............................................................................................................................................................7
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the fire smoke or fire damper in the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire or fire smoke damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner.
1) Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify that the fusible link is in place or has not separated. If fusible link is not present or has separated, replace link. Never install a fire damper without the proper UL approved fusible link in place. (Fusible link is standard control option. An electric link may have been provided. Electric links have a button for resetting.)
2) Lift or handle damper using the frame. Do not lift damper using blades or actuators.
3) Do not install screws into the main body area of the damper frame as screws may interfere with and prevent damper blade from opening and/or closing.
4) Damper has label indicating position of damper assembly in the wall. Install accordingly to comply with manufacturer’s appropriate UL Classification file number.
5) Damper must be installed into duct or opening free of distortion or other misalignment. Damper must not be squeezed or stretched into duct or opening. Out of round, racked, twisted or misaligned installations can cause excessive leakage and/or torque requirements to exceed damper/actuator design.
6) Damper and actuator must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such
foreign materials include but are not limited to:
a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray
7) Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design.
8) Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining plates.
9) ACCESS: Suitable access (such that fusible links, RRL’s, actuators, and linkages can be maintained) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).
10) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.
Installation - Failure to follow these instructions will void all warranties.
These instructions apply to 1½ hour rated combination fire smoke and fire dampers mounted in: 1) masonry, block or stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory. Dampers must be installed in accordance with these instructions to meet the requirements of UL 555 and UL 555S. The installation of the damper and all duct connections to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Damper Installation Guide, and UL Classifications R13317.
2
3.375 IN.
FUSIBLE LINK LOCATION
CLEARANCE FOR EXPANSION
6 IN. MAX
SLEEVE LENGTH
TW
DUCT CONNECTION AREA
AIRFLOW
1.50 IN.
ACTUATOR
16.00 IN MAX
OPTIONAL BLADE POSITION INDICATOR AND/OR ELECTRIC LINK.
DUCT CONNECTION AREA
2.00 IN.
1.50 IN.
Optional Second Retaining Plate
Do not place retainer plate in this groove
1. CLEARANCES REQUIRED BETWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS
Fire damper assemblies expand during periods of
intense heat. Therefore, it is essential that openings in walls or floors be larger than the fire damper assembly to allow for this expansion. The wall/floor opening must be a minimum of 7/8 in. (22mm) larger than the outside diameter of the damper. Refer to Section 4 for additional installation considerations.
2. SLEEVE LENGTH AND WALL/FLOOR THICKNESS
Insert the damper assembly into the prepared opening, to appropriate depth (see Fig. 1).
Recommended maximum and minimum insertion depth can be exceeded if:
1) the operation of the damper actuator is not impeded and
2) the CL of the damper blade remains within the plane of the wall/floor
IMPORTANT SAFETY DANGER! : To avoid
causing death or serious bodily harm to building occupants, do not insert screws into the damper frame unless used for duct connection within 2 in. (51mm) of the frame end.
The sleeve may extend a maximum of 16 in. (406mm) beyond the wall or floor on the actuator side of the damper and a maximum of 6 in. (152mm) on the opposite side.
Fig. 1
3. ROUND DUCT CONNECTIONS
Round duct connections to shall be attached with #8 or #10 sheet metal screws as follows:
• Ducts 22 in. (558mm) dia. and smaller shall have three screws.
• Ducts larger than 22 in. (558mm) dia. up to and including 24 in. (610mm) dia. shall have five screws.
NOTE: All connections described may have duct sealant, PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie, Ductmate PROseal®, or CL Ward S Seal applied in accordance with SMACNA recommendations.
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL AND FLOOR OPENINGS
Damper assemblies must be installed in wall/floor openings using a single retaining plate on either side of the wall/floor or by using a retaining plate on both sides of the wall/floor. The use of a second retaining plate is allowed, but is not necessary. A single retaining plate is provided with the dampers. A second retaining plate can be ordered as an option. The outside dimension of the supplied retainer plate is nominal dia. + 4½ inches (114mm).
3
Loading...
+ 4 hidden pages