INSTALLATION INSTRUCTIONS
for OCI (Open/Close Indicator) on
SMD, FSD, SSSMD, SSFSD Series
Steps to install an OCI in a Smoke or Fire Smoke
Damper:
1. Drill/Saw a 3 5/8 in. (92mm) diameter hole in sleeve (Detail 2).
2. Attach indicator bracket to blade. For an Airfoil blade damper, use
existing holes in blade (Detail A). For a 3-V blade damper, drill two
0.166 in. (4mm) diameter holes
(Detail B). Fasten bracket to blade with #10 x 1/2 in. (13mm) TEK
screws (or equivalent).
3. Fit indicator link into blade bracket (Detail C).
4. Insert OCI unit through hole in sleeve (round end inside).
5. Place 4 x 4 in. J-Box over the flange of the OCI unit and align holes.
6. Mount control box to sleeve/sideplate with #10-16 x 3/4 in. (19mm)
TEK screw (or equivalent) (Detail D).
7. Place one pushnut on the switch wire. Place indicator link on switch
wire and secure with a second pushnut (Detail D).
8. Complete wiring and install J-Box cover.
Document number 459656
Smoke & Combination Fire Smoke Dampers
OCI KIT Part Number 851848
Detail 1
Upturned Leg Faces
Away From Blade End
ek Screw
or Equivelant
Part No. 415555
2 Req’d
A
Airfoil Blade
Indicator
Link
C
Note: Indicator Link Part Nos.
For Standard Sleeve (short): 457808
For Extended Sleeve (long): 457801
Indicator Bracket
Part No. 658594
1 Req’d
Indicator
Bracket
Upturned Leg
Faces Away From
Blade End
#10 x 1/2 in. Tek
Part No. 415555
Screw
or Equivelant
2 Req’d
B
0.166 in. dia.
2 Places
3-V Blade
OCI - Exploded View
Indicator Bracket
Part No. 658594
1 Req’d
1.625
1.750
All dimensions shown in inches.
D
Gasket
1 Req’d
Push Nuts
2 Req’d
Indicator Link
(short or long; see C)
1 Req’d
#10-16 x 3/4 in.
SIHWH Screw
2 Req’d
OCI
1 Req’d
J-Box
1 Req’d
1 Req’d
Nominal
Section
Height
6-7 2.625 2.625
8 3.125 3.125
9 3.625 3.625
10-11* 2.625 3.625
12-13* 2.625 4.125
14-15* 3.125 4.625
16* 3.625 5.125
17* 4.125 5.625
18 13.125 13.125
19 14.125 14.125
20 14.625 14.625
21 15.625 15.625
22 16.625 16.625
23 17.125 17.125
24 18.125 18.125
25 19.625 19.625
26 20.625 20.625
27, 39,
40, 41
28, 42 22.125 22.125
29, 43, 57 23.125 23.125
30, 44, 58 24.125 24.125
31, 45,
55, 56, 59
32 26.625 26.625
33, 47 27.625 27.625
34, 46 28.625 28.625
35, 49 29.125 29.125
36, 48 30.625 30.625
37, 51 31.125 31.125
38, 50, 52 32.125 32.125
53 23.625 23.625
54 24.625 24.625
60 4.125 4.125
3V
Style
(D)
21.625 21.625
25.125 25.125
Steel
Airfoil
Style (D)
Detail 2
INSIDE
D
SURF ACE
All dimensions shown in inches.
Wiring Diagram
8.375
3.563
Ø3.625
< 11" NOM HEIGHT
>11" NOM HEIGHT
* Note: Operator mounted
upside down on steel airfoil
units from 10 in. to 17 in.
(254mm to 432mm)
Copyright ©2015 Greenheck Fan Corporation
459656 OCI IOM Rev 10 March 2015