Reference Guide for the Network Interface Controller
Please read and save these instructions. Read carefully before attempting to operate or maintain the product
described. Protect yourself and others by observing all safety practices. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
BMS v1.00
Version Date: May 24, 2011
Introduction
Program Features
The network interface controller is a device that
acts as a communication link between the BMS
(Building Management System) and the unit. The
network interface controller will transform the
communication into an action within the unit and
will provide monitoring status of various functions
and temperatures. The controller has the ability to
communicate with a BMS through protocols such
as LonWorks®, BACnet® MSTP, BACnet® IP or
Modbus. See Points List at end of document for a
complete list of BMS points.
Network Interface Controller for Tempered Air Products
1
Input/Output Points
Standard Input/Output points are Supply Air Temp, Outside Air Temp and Fan Proving Status. The following are
optional I/O points. See Network Interface unit diagram to see job specific I/O.
Input Points (Max 6)Output Points Digital (Max 5)Output Points Analog (Max 3)
Cold Coil TempCall for Heat Stage 1Heat Output
Return Air TempCall for Cool Stage 1Cool Output
Exhaust Discharge TempCall for Cool Stage 2Supply VFD
Outdoor Air After Wheel TempOccupied UnoccupiedExhaust VFD
The network interface controller will monitor the unit
conditions for alarm conditions. Upon detecting an
alarm, the controller will record the alarm description,
time, date and available temperatures for user review.
An optional digital output is available for remote
alarm indication. Alarms are also communicated via
BMS.
•Temperature Sensor Alarm: Network interface
controller will send an alarm in the case of a failed
air temperature sensor.
•Supply Air Low Limit: If the supply air temperature
drops below the supply air low limit (35°F), the
network interface controller can do one of the
following based on user setup.
- Alarm Only: Sends alarm via BMS.
- Alarm and Open NO3: Sends an alarm and turns
the unit run command off, even if BMS run
command is active.
- Disable: Disables the supply air low limit
function.
Display Use
The network interface controller is located in the unit
control panel. The face of the controller has six keys,
allowing the user to view unit conditions and alter
parameters. The network interface controller is preprogrammed with easy-to-use menus.
Remote Display Panel (Optional)
A display panel allows for remote monitoring and
adjustment of parameters, allowing ease of control
access without going outdoors.
A remote mounted display is also available, which
connects via the J4 port. A six-wire patch cable is
needed.
Network Interface Controller for Tempered Air Products
2
®
PrgEsc
or
PrgEsc
PrgEsc
Esc
PrgEsc
PrgEsc
PrgEsc
!
PrgEsc
!
PrgEsc
PrgEsc
PrgEsc
!
Alarm
Down
Arrow
Up
Arrow
Enter
Keypad Description
Button will blink red, indicating an alarm condition. Press to review current alarms. To
review previous alarms, access the DATA LOGGER through the main menu.
The arrow keys allow the user to scroll through different screens and adjust
parameters.
A. In screens with adjustable parameters, pressing the Enter key moves the cursor
from the upper left corner of the screen to the parameter. The arrow keys can then
be used to adjust the parameter.
B. To move to the next parameter on the same screen, press the Enter button.
C. To save the change, press the Enter button until the cursor moves back to the upper
left corner of the screen.
Esc
or
Prg
or
Supply air low limit
Alarm when supply is
below: 35.0º F
Alarm delay: 300s
Supply air low limit
Alarm when supply is
below: 32.0º F
Alarm delay: 300s
Supply air low limit
Alarm when supply is
below: 32.0º F
Alarm delay: 300s
EscapeAllows the user to exit the current menu, jumping to the Main Menu.
Program
Pressing the Prg (Program) button allows the user to enter the Main Program Menu.
See below for Main Program Menu description.
Example of Parameter Adjustment
The cursor always begins in the upper left corner of the display and will be
blinking. Press the
Once the cursor has reached the desired parameter, press the
key to move the cursor down for parameter adjustment.
keys to
adjust the value.
When satisfied with the adjustment, press the
key to save the parameter.
When finished, make certain the cursor is in the upper left corner. If the cursor
is not in the upper left corner, the changes will not be saved. The cursor must
be in the upper left corner to enable screen advancement.
Examples of Alarms
If an alarm occurs, the status line will state !PRESS ALARM BUTTON! and the
the controller and the remote display (if installed).
Alarms
Press DOWN to review
current alarm(s).
Press ESC to exit.
Press ALARM to reset.
To view alarm, press the
recent alarm. Press the
or
or !button again to reset the alarm. If the alarm
button once. This will display the most
cannot be cleared, the cause of the alarm has not been fixed. Press the
buttons to view any additional occurring alarms.
This is an example of an outdoor air sensor failure.
B3-Outdoor Temp
Sensor B03 Failure
Alarms
No active alarm
Press ENTER
to DATA LOGGER
®
This screen appears if there are no active alarms.
To view all saved alarms, press the
button to enter the DATA LOGGER. For
more information, see the Data Logger menu.
Network Interface Controller for Tempered Air Products
or
button will glow red on
3
Temperature Sensor
PrgEsc
PrgEsc
Failure
System has exceeded the
set number of run hours
List of Possible Alarms
Failure of temperature sensor.Alarm only
The unit has been operating for a period longer than
the maintenance set point.
Alarm only
Supply temperature low
limit alarm
pCOe Offline
pCOe - Analog input
probe on channel #
disconnected or broken
Indicates a supply air temperature lower than the
supply low limit set point.
Indicates communication with pCOe auxiliary I/O has
failed.
Indicates an analog probe failure on the pCOe.
Check integrity of auxiliary I/O analog probes.
Alarm & Open NO3
or Alarm Only
Alarm only
Alarm only
Main Menu Overview
The remote interface controller will revert to a default main menu loop. This loop includes several screens to
view the operating conditions of the unit. Scroll through the menu screens by using the
with a dashed line border are dependent upon an optional accessory and may not always appear.
TIME DATE UNIT##
theInItIalmenuscreenDIsplaystheprogr amversIon, unItcoDeanD status
lIne . the status lInewIllDIsplay “!manual overrIDe!” Iftheov errIDe
If the unit supply air temperature falls below Supply Air Low Limit for a period of
Alarm Delay, the unit will do one of the following based on the Alarm Function.
• Alarm Only: Sends alarm via BMS.
• Alarm and Open NO3: Sends an alarm and opens NO3 (Unit Start/Stop
command) even if the BMS start/stop command is active.
• Disable: Disables the supply air low limit function.
The purpose of the supply low limit is to protect the building and contents from
cold supply air. It is NOT designed to protect the air handling unit.
If the unit does not have cold or hot water coils, it should not need additional
protection from freezing. If the unit does have cold or hot water coils, field
provided coil freeze protection may be necessary.
thIsscreenDIsplays co2 sensorsetup.
This screen only appears if the unit is equipped with a CO2 sen sor.
This screen is used to match the settings of the CO
sensor to the network
2
interface controller.
The Clock/Scheduler menu allows the user to view and alter the time and date.
The Clock menu allows the user to view and alter the time and date.
The Clock screen allows the user to adjust the time and date.
Day: Monday
Date: 01/31/10
Hour: 15:30
C. Input/Output
Analog Input
B4-Supply Air Temp
Input B04: 70.0°F
D. Data Logger
13:21:04 10/05/10
OA Sensor
Outside Air T: -623.3
Supply Air T: 70.0
The Input/Output menu allows the user to quickly view the status of the controller
inputs and outputs.
To manually control I/O values, go to the Service menu > Overrides.
Similar screens appear for all controller inputs and outputs.
The Data Logger menu allows the user to view past alarms.
thIsscreenIsanexa mpleofarecorDeDal arm.
The unit conditions are displayed for past alarm events. The date, time,
temperatures and unit status are recorded.
To clear recorded alarms, press
Prg
or
and
Esc
or
simultaneously.
Network Interface Controller for Tempered Air Products
6
®
E. Board Switch
The Board Switch menu allows the user to jump between different controllers
with a remote display. This requires a remote display, along with additional
controllers, set-up in a pLAN network. A pLAN can consist of up to 32 devices, in
different combinations, but a maximum of 31 controllers.
Unit Address: The pLAN address of the controller the display is currently
accessing.
Switch to unit: The pLAN address of the controller the display would like to
access.
The Service menu allows the user to access several sub-menus regarding
controller information, controller overrides, operating hours, BMS configuration,
I/O manual management and Probe Adjustment. The user can also change the
default Service Password (Default=1000) by accessing the Service Settings
sub-menu. By accessing the BMS Config sub-menu, the user can adjust BMS
protocol settings (BACnet, LonWorks, Modbus).
enter Ingthe InformatIonsuB-menuwIllDIspl ayInformatIonaBoutthe
controlleranDtheprogr amloaDe Donthecontroller.
Code: Controller setup code determines functionality of program. When
contacting the factory, please reference this code.
Manual: Reference this Installation and Operation Manual, available at
www.greenheck.com
F. Service
b. Overrides
Testing Overrides
To resume normal operation,
cycle unit power.
Testing Overrides
Override: No Position
NO1NO2NO3- Unit On/Off: Open
NO4NO5NO6-
The Overrides menu is for start-up, commissioning and troubleshooting.
This menu allows the user to override the control loops. If further control is
required, the user can also manually control the controller inputs and outputs.
To access the Overrides sub-menu, enter the service password (Default=1000).
To manually override an output, in each respective screen, change the override
from No to Yes, then change the Position to open or closed or adjust the vdc
output setting.
To resume normal operation after overriding the controller, simply cycle power
to the unit.
This menu allows the user to manually control the outputs of the controller. The
user can manually control the analog outputs and digital outputs. EXTREME
CAUTION should be used when manually controlling the outputs and should
only be used as a troubleshooting feature. If the controller is powered down,
overrides are reset to off. Therefore, if using this troubleshooting feature, the
best way to clear manually input values is to power down the controller.
This screen only appears if the unit is equipped with an analog output option.
Network Interface Controller for Tempered Air Products
7
F. Service
PrgEsc
PrgEsc
PrgEsc
PrgEsc
c. BMS Config
The BMS Config menu allows the user to view and alter BMS protocol
settings. If the BMS protocol is BACnet or Modbus, additional screens allow
further configuration. See below for details. To access the BMS Config
sub-menu, enter the service password (Default=1000).
BMS Configuration
Protocol: BACnet MSTP
BACnet Plugin? YES
MODBUS SETUP
Address: 1
Baudrate 9600
MSTP SETUP
Instance: 77000
Baudrate 38400
MAC Addr: 0
MaxMasters: 127
MaxInfoFrames: 20
BACnet Read/Write
Function: Read
Update? Yes
*Cycle unit power to confirm
write command.
thIsscreenallowstheusertoselectthe Bms protocol. all Bms
protocolsrequIreacommunIcatIonscarDI nstalleDInthe serIal carD
port, locateDonthefaceofthecontroller .
If the protocol is BACnet MSTP or BACnet IP/Eth, the user can change
common BACnet parameters via the controller. The BACnet Plugin must be set
to YES.
thIsscreenallowstheusertoaDjust moDBusparameters.
This screen only appears if the selected BMS protocol is set to Modbus.
The address is the Modbus address of the card installed in the SERIAL CARD
port located on the face of the controller. (Factory Default Address = 1). The
Baud Rate should be set to the BMS baud rate. (Factory Default Baud Rate is
This screen only appears if the selected BMS protocol is set to BACnet MSTP and
BACnet Plugin = YES.
If a BACnet MSTP card has been installed, the default parameters can be
changed via the controller display. Factory settings are shown in the screen to
the left.
To view current parameters:
1. Power on controller and allow several minutes to initialize.
2. Go to BMS Config menu and view BACnet Read/Write screen.
3. Change Function to Read and Update? to YES.
Current BACnet MSTP parameters should now be displayed in the BACnet
MSTP SETUP screen. If all values appear to be zeros, consult the factory.
(Make sure you have allowed several minutes for the controller to initialize).
*Values may appear to be zero prior to setting the Function to READ.
To change BACnet MSTP parameters:
1. Power on controller and allow several minutes to initialize.
2. Go to BMS Config menu and view MSTP SETUP screen.
3. Move cursor to desired parameter by pressing the
to select the parameter to change. Press the
the parameter. Press
to save adjusted value.
buttons. Press
buttons to adjust
4. Once desired parameters have been entered, go to BACnet Read/Write
screen. Change Function to Write and Update? to YES.
5. Reboot the controller by cycling power to the unit. Allow several minutes
for the controller to initialize.
6. View MSTP parameters. If changed values did not save, contact the
factory.
Network Interface Controller for Tempered Air Products
DNS 1: 193.168.001.001
DNS 2: 193.168.001.001
Type: IP
BACnet Read/Write
Function: Read
Update? Yes
*Cycle unit power to confirm
write command.
thIsscreenallowstheusertoaDjust Bacnet Ip parameters .
This screen only appears if the selected BMS protocol is set to BACnet IP/Eth and
BACnet Plugin = YES.
If a BACnet IP card has been installed, the default parameters can be changed
via the controller display. The card is in DHCP mode from the factory. Once
communication is established, the user can enter static IP parameters.
To view current parameters:
1. Power on controller and allow several minutes to initialize.
2. Go to BMS Config menu and view BACnet Read/Write screen.
3. Change Function to Read and Update? to YES.
Current BACnet IP parameters should now be displayed in the BACnet TCP/IP
SETUP screen. If all values appear to be zeros, consult the factory. (Make sure
you have allowed several minutes for the controller to initialize).
*Values may appear to be zero prior to setting the Function to READ.
To change BACnet TCP/IP parameters:
1. Power on the controller and allow several minutes to initialize.
2. Go to BMS Config menu and view TCP/IP SETUP screen.
3. Move cursor to desired parameter by pressing the
to select the parameter to change. Press the
the parameter. Press
to save adjusted value.
buttons. Press
buttons to adjust
4. Once desired parameters have been entered, go to BACnet Read/Write
screen. Change Function to Write and Update? to YES.
5. Reboot the controller by cycling power to the unit. Allow several minutes
for the controller to initialize.
6. View TCP/IP parameters. If changed values did not save, contact the
factory.
F. Service
d. Service Settings
a. Working hour set
b. Probe adjustment
c. Password/Defaults
MAINTENANCE HOURS
SYSTEM
Run hours: 0000h
Set Point: 0000h
Reset to Zero? No
Analog Input
Outside Temperature
Input B3
Offset: 0.0°F
Value: 70.5°F
User Default
The Service Settings menu allows the user to change the default Service
Password (1000), save and restore default parameters, and adjust probe
values.
Run hours: The amount of time in hours that the unit has been powered.
Set Point: The amount of running time in hours before a maintenance alarm
should occur.
Reset to Zero: Reset the measured amount of run time.
the proBe aDjustmentmenuallowstheusertocalIBr atesensorproBes
wItha noffsetvalue.
Similar screens are available for remaining sensor probes.
thIsscreenallowstheusertochangethe servIce le velpassworD (pw1)
Insert new service password
(PW1): 1000
®
Network Interface Controller for Tempered Air Products
9
User Default Settings
Save? No
Restore? No
G. Manufacturer
a. Configuration
thIsscreenallowstheuserto save anD restore theDefault
parametersstoreDInmemory.
If the user would like to save their settings, move the cursor to the SAVE
position and change to YES. This will save all of the current parameters into
memory as Service Settings. If the user would like to restore to these values
at some point in the future, moving the cursor to the RESTORE position, and
selecting YES will restore the controller to the user saved defaults.
Configuration menu allows the user to change the setup code for the unit, enable
Scheduling, Holidays, expansion I/O and change Field Card settings. Users are
welcomed to enable Scheduling and Holidays. However, code changes and
expansion I/O enabling are to be done under factory advice only!
Unit Code
Select DDC configuration
code here.
Code: GXXXXX00XX100b
Configuration
Modbus settings
Baudrate: 19200
Stop bit: 2
Parity mode: None
Timeout: 300ms
Unit Expansion I/O
Enable Expansion: No
thIsscreenDIsplaysanDallowsaDjustmentofthe un It coDe .
This code is set from the factory to operate the components selected with
the unit. When troubleshooting, refer to the wiring diagram sent with the unit
(located on the control center door) to verify the Unit Code is correct. The code
will be listed on the wiring diagram.
thIsscreenallowstheusertoalterthe fIelD carD moDBussettIngs.
The FIELD CARD is used for peripheral device control (pCOe Expansion
Module).
The Modbus settings should only be changed with factory guidance.
The additional I/O points available on the pCOe expansion module allow the
user to monitor and control the additional points over the BMS and user display.
A pLAN (pCO Local Area Network) is a Carel proprietary local area network,
allowing the user to connect multiple controllers to one remote display panel.
Each controller on a pLAN must have a unique address.
This address is only applicable for units connected on a pLAN. For BACnet,
LonWorks or Modbus parameters, go to Service > BMS Config.
Network Interface Controller for Tempered Air Products
10
®
G. Manufacturer
b. I/O Configuration
The I/O Configuration menu allows adjustment of all controller inputs and
outputs. This menu is similar to the Probe Adjustment menu, except that
it additionally allows adjustment of the factory default ‘normal’ states of
the digital inputs and the direction of the analog outputs. Additionally, it
allows adjustment of the physical location of each I/O. ADJUSTMENT OF I/O
PHYSICAL LOCATION MUST ONLY BE DONE UNDER FACTORY GUIDANCE!
IMPROPER ADJUSTMENT MAY RESULT IN SYSTEM DAMAGE!
Analog Input
Outside Temperature
Channel:B3 Normal
Type: NTC
Offset: 0.0°F
Value: 70.5°F
Alarm Time Delay
Outside Temperature
Input B03: 72.0°F
Out of Range Alarm
Power Delay: 30s
Run Delay: 30s
G. Manufacturer
c. Factory Settings
Temperature Scale
Select: Fahrenheit
Display Buzzer
Select: Disable
G. Manufacturer
d. Initialization
This is an example of an analog input configuration screen.
In the I/O configuration screens, the user can alter the physical location and
type of each point.
Similar configuration screens appear for the remaining I/O.
Digital Input
ID1- Fan Proving
Channel: ID1
Action: CLOSED
Delay 0s
CLOSED
Relay Output
NO3- Unit ON
Channel: 3
Status: OFF
Analog Output Config
Y2-Heat Output
Channel: Y2
Action: DIRECT
Minimum: 0.0vdc
Maximum: 10.0vdc
The Factory Settings menu allows adjustment of parameters that are
critical for proper unit operation. Adjustment of these parameters is only
recommended with factory guidance. To access the Factory Settings menu,
enter the manufacturer password (Default=1000).
The temperature unit of measurement can either be Fahrenheit or Celsius.
If using Celsius, the user will need to manually convert the factory default
parameters in the Factory Settings menu.
The display buzzer is only applicable when a remote interface panel is
attached to the controller. If an alarm were to occur, the remote display panel
would begin buzzing loudly (if the buzzer was enabled) and would show the
alarm status.
The Initialization Menu allows the user to save and restore the controllers
default parameters. The controller can be restored with either the
Manufacturer’s default parameters from shipment, or an unconfigured factory
default.
Factory Settings
Save? No
Restore? No
New Password
Insert new manufacturer
password (PW2): 0000
Initialization
DEFAULT INSTALLATION
Erase user settings and install
global default values: No
®
thIsscreenallowstheuserto save anD restore thefactoryDefault
parametersstoreDInmemory.
The Factory Settings include the Factory default parameters and the unit setup
code. If the user would like to restore to these parameters, move the cursor to
the Restore position and change to YES.
thIsscreenallowstheusertochangethe manufacture r passworD (pw2)
Restoring to the original default parameters will result in a non-customized
controller. The user should not restore to these settings unless instructed by
the factory.
Network Interface Controller for Tempered Air Products
11
Points List • LonWorks®
Typ eNV_In dexName NVType NV
Analog20nvoOutsideTemp10 5ReadOutdoor Air Temp (###.#°F)
Analog21nvoSupplyAirTemp105ReadSupply Air Temp (###.#°F)
Network Interface Controller for Tempered Air Products
13
Typical Wiring Diagram
NETWORK INTERFACE CONTROLLER TO UNIT CONNECTION WIRING DIAGRAM
UNIT ELECTRICAL BOARD TERMINALS/COMPONENTS
R
24 VAC
C
pCO5 INTERFACE
CONTROLLER
NETWORK INTERFACE CONTROLLER/COMPONENTS
BLUE
G
J1
J3
NO1
WHITE
GO
C1
TO TERMINAL "R"
TO TERMINAL "C"
®
Wiring Diagram Code:
GEXXXXD000XX101BL00
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
USE COPPER CONDUTORS ONLY
60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
75° C FOR TERMINALS RATED 100 AMPS OR MORE.
FIELD CONTROL WIRING RESISTANCE SHOULD
NOT EXCEED 0.75 OHM.
FIELD WIRED
FACTORY SUPPLIED AND WIRED
CAUTION
NOTES
NC1
NO2
J10
C2
PINK
NO3
C3
J11
NO4
NO5
J12
C5
NO6
B1
B2
B3
B4
J2
GND
TO TERMINAL "G"
TO TERMINAL "W1"
G
W1
OAI
OAD
UNIT START/STOP
REPLACES S1 FAN SWITCH
FACTORY WIRED
HEATING STAGE 1
REPLACES S4 CALL FOR HEAT SWITCH
FACTORY WIRED
BK BLACKBL BLUEBR BROWN
GY GRAYLT BL LIGHT BLUEO ORANGE
PK PINKPR PURPLER RED
W WHITEYYELLOW
ACC AFTER COOLING COIL TEMPERATURE
EAW EXHAUST AIR AFTER WHEEL TEMPERATURE
OAAW OUTDOOR AIR AFTER WHEEL TEMPERATURE
OAD OUTDOOR AIR DISCHARGE TEMPERATURE
OAIOUTDOOR AIR INLET TEMPERATURE
RAIRETURN AIR INTLET TEMPERATURE
R20ROTATION INTERFACE RELAY
WIRE COLOR CODE
LEGEND
B5
B6
ID1
GND
ID2
GND
J13
Y3
(0/10V)
Y4
(0/10V)
Y1
(PWM)
J9
Y2
(0/10V)
GND
Network Interface Controller for Tempered Air Products
14
TO "13" ON ST1
TO "14" ON ST1
TO "NO" ON PS2
TO "C" ON PS2
13
14
NO
C
FAN PROVING STATUS
ST1
DIRTY FILTER STATUS
REPLACES FIELD INTERFACE
PS2
CONNECTION TO PS2
FACTORY WIRED
DDC Code: Verison - BMS 1.00
XXXX
G
Wiring Template: L00
D
000
X X
b
1
1
0
®
PrgEsc
PrgEsc
PrgEsc
!
Esc
PrgEsc
PrgEsc
PrgEsc
PrgEsc
PrgEsc
!
Troubleshooting
Display is hard to read.
Remote display panel
displays “NO LINK” or
is blank.
Red alarm button is
flashing.
Controller resets itself
or is not on.
Menus are locked with
a password.
Temperature sensor
failure.
Unit Controller Display: Hold
while pressing
DOWN or
Remote Display: Hold
same time, while pressing
Hold
DOWN,
UP and ENTER for 4 seconds. Set the display address
Esc
or ESC and ENTER at the same time,
UP to adjust display contrast.
or
ALARM,
DOWN or
Prg
or
UP to adjust display contrast.
PRG, and
Esc
or
ESC at the
to 32. The display requires a standard 24 AWG six conductor phone cable
connected to the unit controller.
Press the
or
ALARM button to review and clear unit alarms. Enter the
DATA LOGGER menu to view previous alarms.
Check the supply voltage to the controller at terminals G-G0. The board requires
24VAC. Check the 24VAC transformer in the unit control center.
The factory default Manufacturer Password = 1000.
The factory default Service Password = 1000.
Check the analog input terminal block (labeled terminals B1, B2, B3, etc) for loose
wires. Disconnect temperature sensors to check sensor resistance.
NTC Temperature Sensor Chart
120
110
100
90
80
70
60
50
Temperature (ºF)
40
30
20
10
0
4 6 8 10 12 14 16 18 20 22 24 26 28
Resistance (kΩ)
®
Network Interface Controller for Tempered Air Products
15
Esc
PrgEsc
PrgEsc
PrgEsc
PrgEsc
PrgEsc
BACnet® MSTP Quick Start
The card is loaded with the following default BACnet
MSTP parameters.
ParameterFactoryMinimumMaximum
Device Instance770000419 43 03
Station Address0012 7
Max Master1270127
Max Info Frames200255
Baudrate384009600-19200-38400-76800
G. Service
c. BMS Config
To view the current
parameters, go the BMS Config menu within the
controller by pressing
BMS Configuration
the
or
key.
Prg
To access the BMS
Config sub-menu, enter
Protocol: BACnet MSTP
BACnet Plugin? YES
the service-password
(Default=1000).
Protocol must be
BACnet MSTP and
MSTP SETUP
Instance: 77000
Baudrate 38400
MAC Addr: 0
MaxMasters: 127
MaxInfoFrames: 20
BACnet Plugin must be
YES.
Press the
button
arrow to view next
screen.
Current BACnet MSTP
parameters should be
BACnet Read/Write
displayed. If values
appear to be zero, follow
Function: Read
Update? Yes
*Cycle unit power to confirm
write command.
the procedure below.
To read current settings:
1. Power on controller
and allow several
minutes to initialize.
2. Go to BMS Config menu and view BACnet Read/
Write screen.
3. Change Function to Read and Update? to YES.
Current BACnet MSTP parameters should now be
displayed in the BACnet MSTP SETUP screen. If
all values appear to be zeros, consult the factory.
(Make sure you have allowed several minutes for the
controller to initialize). *Values may appear to be zero
prior to setting the Function to READ.
To change BACnet MSTP parameters:
1. Power on the controller and allow several minutes
to initialize.
2. Go to BMS Config menu and view MSTP SETUP
screen.
3. Move cursor to desired parameter by pressing the
buttons. Press
to change. Press the
parameter. Press
to select the parameter
buttons to adjust the
to save adjusted value.
4. Once desired parameters have been entered, go
to BACnet Read/Write screen. Change Function to
Write and Update? to YES.
5. Reboot the controller by cycling power to the unit.
Allow several minutes for the controller to initialize.
6. View MSTP parameters. If changed values did not
save, contact the factory.
The communication card
Status LEDRS485 LED
is located in the Serial Card port on the face of
the controller. The card
includes two sets of LED
lights for communication
troubleshooting.
Push Button
Status LED: Indicates the status of communication
between the card and controller.
•Quickgreen-off-greenifcommunicationwith
controller is ok.
•Slowred-off-redifcommunicationisnot
established.
RS485 LED: Indicates the status of communication
with the BACnet MSTP network. Wait for 40 seconds
to determine status of communication.
Current BACnet IP
parameters should be
displayed. If values
appear to be zero, follow
the procedure below.
To read current
arrow button
parameters:
DNS 1: 193.168.001.001
DNS 2: 193.168.001.001
Type: IP
1. Power on controller
and allow several
minutes to initialize.
2. Go to BMS Config
menu and view
BACnet Read/Write
Function: Read
Update? Yes
*Cycle unit power to confirm
write command.
BACnet Read/Write
screen.
3. Change Function to
Read and Update? to
YES.
Current BACnet IP
parameters should now be displayed in the BACnet
TCP/IP SETUP screen. If all values appear to be
zeros, consult the factory. (Make sure you have
allowed several minutes for the controller to initialize).
*Values may appear to be zero prior to setting the
Function to READ.
To change BACnet TCP/IP parameters:
1. Power on the controller and allow several
minutes to initialize.
2. Go to BMS Config menu and view TCP/IP
SETUP screen.
3. Move cursor to desired parameter by pressing
the
parameter to change. Press the
to adjust the parameter. Press
buttons. Press
to select the
buttons
to save
adjusted value.
4. Once desired parameters have been entered, go
to BACnet Read/Write screen. Change Function
to Write and Update? to YES.
5. Reboot the controller by cycling power to the
unit. Allow several minutes for the controller to
initialize.
®
6. View TCP/IP parameters. If changed values did
not save, contact the factory.
The communication card
is located in the Serial Card port on the face of
the controller. The card
MAC address
Status
LED
Ethernet
LED
includes two sets of LED
lights for communication
troubleshooting.
Push Button
Status LED: Indicates the status of communication
between the card and controller.
•Quickgreen-off-greenifcommunicationwith
controller is ok.
•Slowred-off-redifcommunicationisnot
established.
Ethernet LED: Indicates the status of communication
with the network. Wait for 40 seconds to determine
status of communication.
Follow this procedure to revert to factory parameters
for one power cycle. When restarted, the card will
resume using the previous user parameters.
Factory Default IP address: 172.016.000.001
1. With controller off, hold the push button located
on the BACnet IP/Eth card, while powering the
controller back on.
2. Continue to hold the button, while watching the
Status LED. Wait for the Status LED to blink red
slowly, and release before the third slow flash.
3. Wait for about one minute for the factory
parameters to be loaded.
4. Follow the procedure to read the current
parameters to confirm factory defaults have been
loaded.
Network Interface Controller for Tempered Air Products
17
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Network Interface Controller for Tempered Air Products
18
®
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
®
Network Interface Controller for Tempered Air Products
19
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the
shipment date. Any units or parts which prove to be defective during the warranty period will be replaced at our option
when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of one
year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the nearest
authorized motor service station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional
safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org.