Greenheck Network Interface Controller User Manual

Part #475262
Network Interface Controller for
®
Tempered Air Products
Reference Guide for the Network Interface Controller
Please read and save these instructions. Read carefully before attempting to operate or maintain the product described. Protect yourself and others by observing all safety practices. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
BMS v1.00 Version Date: May 24, 2011
Introduction
Program Features
The network interface controller is a device that acts as a communication link between the BMS (Building Management System) and the unit. The network interface controller will transform the communication into an action within the unit and will provide monitoring status of various functions and temperatures. The controller has the ability to communicate with a BMS through protocols such as LonWorks®, BACnet® MSTP, BACnet® IP or Modbus. See Points List at end of document for a complete list of BMS points.
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . 1
Input/Output Points . . . . . . . . . . . . . . . . . 2
Alarms . . . . . . . . . . . . . . . . . . . . . . . . 2
Remote Display Panel (Optional) . . . . . . . . . . 2
Display Use . . . . . . . . . . . . . . . . . . . . . 2
Keypad Description . . . . . . . . . . . . . . . . . 3
Example of Parameter Adjustment. . . . . . . . . 3
Example of Alarms . . . . . . . . . . . . . . . . . 3
List of Possible Alarms . . . . . . . . . . . . . . . 4
Main Menu Overview . . . . . . . . . . . . . . . . 4
Menu Overview . . . . . . . . . . . . . . . . . . . 5
Menus
A.
Setpoint . . . . . . . . . . . . . . . . . . 6
B.
Clock/Scheduler . . . . . . . . . . . . . . 6
C.
Input/Output . . . . . . . . . . . . . . . . 6
D.
Data Logger . . . . . . . . . . . . . . . . 6
E.
Board Switch . . . . . . . . . . . . . . . 7
F.
Service
a. Information . . . . . . . . . . . . . . . . 7
b. Overrides . . . . . . . . . . . . . . . . . 7
c. BMS Config . . . . . . . . . . . . . . . 8-9
d. Service Settings . . . . . . . . . . . . . 9
a. Working hour set. . . . . . . . . . . . 9
b. Probe adjustment . . . . . . . . . . . 9
c. Password/Defaults . . . . . . . . .9 -10
G.
Manufacturer
a. Configuration . . . . . . . . . . . . . . . 10
b. I/O Configuration . . . . . . . . . . . . . 11
c. Factory Settings . . . . . . . . . . . . . 11
d. Initialization . . . . . . . . . . . . . . . . 11
Points List
LonWorks® . . . . . . . . . . . . . . . . . . . . 12
ModBus/BACnet® . . . . . . . . . . . . . . . . 13
Typical Wiring Diagram . . . . . . . . . . . . . . . 14
Troubleshooting . . . . . . . . . . . . . . . . . . .15
NTC Temperature Sensor Chart . . . . . . . . . . 15
BACnet® MSTP Quick Start . . . . . . . . . . . . 16
BACnet® IP/Eth Quick Start . . . . . . . . . . . . 17
Maintenance Log . . . . . . . . . . . . . . . . 18-19
Warranty . . . . . . . . . . . . . . . . . . . . . . .20
®
Network Interface Controller for Tempered Air Products
1
Input/Output Points
Standard Input/Output points are Supply Air Temp, Outside Air Temp and Fan Proving Status. The following are optional I/O points. See Network Interface unit diagram to see job specific I/O.
Input Points (Max 6) Output Points Digital (Max 5) Output Points Analog (Max 3)
Cold Coil Temp Call for Heat Stage 1 Heat Output
Return Air Temp Call for Cool Stage 1 Cool Output
Exhaust Discharge Temp Call for Cool Stage 2 Supply VFD
Outdoor Air After Wheel Temp Occupied Unoccupied Exhaust VFD
Dirty Filter Status Remote Exhaust Fan Energy Wheel VFD
Rotation Status Call for HGRH Return Air Damper
Sensor Alarm User Defined
CO
2
Supply VFD Monitor Signal User Defined
Exhaust VFD Monitor Signal
User Defined
Alarms
The network interface controller will monitor the unit conditions for alarm conditions. Upon detecting an alarm, the controller will record the alarm description, time, date and available temperatures for user review. An optional digital output is available for remote alarm indication. Alarms are also communicated via BMS.
 •Temperature Sensor Alarm: Network interface
controller will send an alarm in the case of a failed air temperature sensor.
 •Supply Air Low Limit: If the supply air temperature
drops below the supply air low limit (35°F), the network interface controller can do one of the following based on user setup.
- Alarm Only: Sends alarm via BMS.
- Alarm and Open NO3: Sends an alarm and turns the unit run command off, even if BMS run command is active.
- Disable: Disables the supply air low limit
function.
Display Use
The network interface controller is located in the unit control panel. The face of the controller has six keys, allowing the user to view unit conditions and alter parameters. The network interface controller is pre­programmed with easy-to-use menus.
Remote Display Panel (Optional)
A display panel allows for remote monitoring and adjustment of parameters, allowing ease of control access without going outdoors.
A remote mounted display is also available, which connects via the J4 port. A six-wire patch cable is needed.
Network Interface Controller for Tempered Air Products
2
®
Prg Esc
or
Prg Esc
Prg Esc
Esc
Prg Esc
Prg Esc
Prg Esc
!
Prg Esc
!
Prg Esc
Prg Esc
Prg Esc
!
Alarm
Down Arrow
Up Arrow
Enter
Keypad Description
Button will blink red, indicating an alarm condition. Press to review current alarms. To review previous alarms, access the DATA LOGGER through the main menu.
The arrow keys allow the user to scroll through different screens and adjust parameters.
A. In screens with adjustable parameters, pressing the Enter key moves the cursor
from the upper left corner of the screen to the parameter. The arrow keys can then be used to adjust the parameter.
B. To move to the next parameter on the same screen, press the Enter button.
C. To save the change, press the Enter button until the cursor moves back to the upper
left corner of the screen.
Esc
or
Prg
or
Supply air low limit
Alarm when supply is below: 35.0º F
Alarm delay: 300s
Supply air low limit
Alarm when supply is below: 32.0º F
Alarm delay: 300s
Supply air low limit
Alarm when supply is below: 32.0º F
Alarm delay: 300s
Escape Allows the user to exit the current menu, jumping to the Main Menu.
Program
Pressing the Prg (Program) button allows the user to enter the Main Program Menu. See below for Main Program Menu description.
Example of Parameter Adjustment
The cursor always begins in the upper left corner of the display and will be
blinking. Press the
Once the cursor has reached the desired parameter, press the
key to move the cursor down for parameter adjustment.
keys to
adjust the value.
When satisfied with the adjustment, press the
key to save the parameter. When finished, make certain the cursor is in the upper left corner. If the cursor is not in the upper left corner, the changes will not be saved. The cursor must be in the upper left corner to enable screen advancement.
Examples of Alarms
If an alarm occurs, the status line will state !PRESS ALARM BUTTON! and the the controller and the remote display (if installed).
Alarms
Press DOWN to review current alarm(s).
Press ESC to exit. Press ALARM to reset.
To view alarm, press the
recent alarm. Press the
or
or !button again to reset the alarm. If the alarm
button once. This will display the most
cannot be cleared, the cause of the alarm has not been fixed. Press the buttons to view any additional occurring alarms.
This is an example of an outdoor air sensor failure.
B3-Outdoor Temp Sensor B03 Failure
Alarms
No active alarm
Press ENTER to DATA LOGGER
®
This screen appears if there are no active alarms.
To view all saved alarms, press the
button to enter the DATA LOGGER. For
more information, see the Data Logger menu.
Network Interface Controller for Tempered Air Products
or
button will glow red on
3
Temperature Sensor
Prg Esc
Prg Esc
Failure
System has exceeded the set number of run hours
List of Possible Alarms
Failure of temperature sensor. Alarm only
The unit has been operating for a period longer than the maintenance set point.
Alarm only
Supply temperature low limit alarm
pCOe Offline
pCOe - Analog input probe on channel # disconnected or broken
Indicates a supply air temperature lower than the supply low limit set point.
Indicates communication with pCOe auxiliary I/O has failed.
Indicates an analog probe failure on the pCOe. Check integrity of auxiliary I/O analog probes.
Alarm & Open NO3
or Alarm Only
Alarm only
Alarm only
Main Menu Overview
The remote interface controller will revert to a default main menu loop. This loop includes several screens to view the operating conditions of the unit. Scroll through the menu screens by using the
with a dashed line border are dependent upon an optional accessory and may not always appear.
TIME DATE UNIT##
the InItIal menu screen DIsplays the progr am versIon, unIt coDe anD status lIne . the status lIne wIll DIsplay “!manual overrIDe!” If the ov errIDe
®
v1.00 GXXXXX00XX100b STATUS LINE
TIME DATE UNIT##
B1­B2­B3-OutsideAir: 80.0ºF B4-SupplyAir: 65.0ºF B5­B6-
Inputs
screen Is actIve or “!press alarm Button!” If there Is an alarm conDItIon.
Inputs
This screen displays real-time conditions from the input sensors located in the unit.
keys. Screens
TIME DATE UNIT##
Digital Inputs ID1-Fan Proving: Open ID2-DirtyFilter: Open
TIME DATE UNIT##
Analog Ouput Y2-VFD Supply: 100% Y3­Y4-
TIME DATE UNIT##
NO1­NO2­NO3- Unit OnOff: Open NO4­NO5­NO6-
Digital Output
DIgItal Inputs
This screen displays real-time digital input open/closed status from the selected components.
analog outputs
This screen displays real-time analog output signals to the selected components.
DIgItal ouputs
This screen displays real-time digital output open/closed status.
Network Interface Controller for Tempered Air Products
4
®
Press
Esc
Prg
or
to enter menus.
Main Menu
Main Status Supply Air Low Limit Clock Analog Input
Inputs CO2 Sensor Setup Digital Input
Digital Inputs Relay Output
Analog Output Analog Output
Digital Output Status
Data Logger
Alarm Description Board Switch Information Configuration
Setpoint
Board Switch Service
Clock/Scheduler Input/Output
Manufacturer
Information Unit Code
Overrides Expansion I/O
Service Password Controller pLAN Setup
Testing Overrides I/O Configuration
BMS Config Analog Input
Service Password Digital Input
BMS Configuration Relay Output
Modbus Setup Analog Output Config
MSTP Setup Factory Setting
TCP/IP Setup Factory Setup
BACnet ReadWrite Temperature Scale
Service Setting Display Buzzer
Service Password Initialization
Working hour set Factory Settings
Maintenance Hours New Password
Probe Adjustment Initialization
Analog Inputs
Probe Adjust
Password/Defaults
User Default
User Default settings
®
Network Interface Controller for Tempered Air Products
5
Esc
Menus
Esc
The controller is equipped with several menus to help guide users with altering program parameters. The
Prg
or
following menus can be accessed by pressing the
The Setpoint menu allows the user to view and adjust temperature related
A. Setpoint
The Setpoint menu allows the user to view and adjust temperature related parameters.
parameters.
key. To enter the desired menu, press the
key.
Supply air low limit
Alarm when supply is below 35.0°F Alarm delay: 300s Alarm Function: Alarm Only
CO2 Sensor Setup
CO2 Output 2-10VDC Scaling: 2vdc 500 ppm 10vdc 1500ppm
B. Clock/Scheduler
Clock
thIs screen DIsplays the low supply aIr temperature lImIt.
If the unit supply air temperature falls below Supply Air Low Limit for a period of Alarm Delay, the unit will do one of the following based on the Alarm Function.
• Alarm Only: Sends alarm via BMS.
• Alarm and Open NO3: Sends an alarm and opens NO3 (Unit Start/Stop
command) even if the BMS start/stop command is active.
• Disable: Disables the supply air low limit function.
The purpose of the supply low limit is to protect the building and contents from cold supply air. It is NOT designed to protect the air handling unit.
If the unit does not have cold or hot water coils, it should not need additional protection from freezing. If the unit does have cold or hot water coils, field provided coil freeze protection may be necessary.
thIs screen DIsplays co2 sensor setup.
This screen only appears if the unit is equipped with a CO2 sen sor.
This screen is used to match the settings of the CO
sensor to the network
2
interface controller.
The Clock/Scheduler menu allows the user to view and alter the time and date.
The Clock menu allows the user to view and alter the time and date.
The Clock screen allows the user to adjust the time and date.
Day: Monday Date: 01/31/10 Hour: 15:30
C. Input/Output
Analog Input
B4-Supply Air Temp Input B04: 70.0°F
D. Data Logger
13:21:04 10/05/10
OA Sensor
Outside Air T: -623.3 Supply Air T: 70.0
The Input/Output menu allows the user to quickly view the status of the controller inputs and outputs.
To manually control I/O values, go to the Service menu > Overrides.
Similar screens appear for all controller inputs and outputs.
The Data Logger menu allows the user to view past alarms.
thIs screen Is an exa mple of a recorDeD al arm.
The unit conditions are displayed for past alarm events. The date, time, temperatures and unit status are recorded.
To clear recorded alarms, press
Prg
or
and
Esc
or
simultaneously.
Network Interface Controller for Tempered Air Products
6
®
Loading...
+ 14 hidden pages