Greenheck Multi-blade Fire User Manual

INSTALLATION INSTRUCTION BOOKLET
1
FOR MULTI-BLADE FIRE &
COMBINATION FIRE SMOKE DAMPERS
Instructions included in this booklet:
IOM # Description Page(s)
461335 CFSD-XXX Series
461336 FSD-XXX, DFD-XXX & CFSD-XXX Series
461337 OFSD-XXX, ODFD-XXX, OFD-XXX and OSSFD-XXX Series
461868 FSDR-XXX, SEFSDR-XXX, & SSFSDR-XXX Models
472477 GFSD Models
474015 Single Side Retaining Angle
KIT # 826249 MULTI-BLADE FIRE DAMPERS DFD / FSD / CFSD / OFSD
2–6
7–15
1627
2835
36–42
43-48
49-51
Document Number 461335
2
Return to Table of Contents
®
Installation, Operation and Maintenance Instructions
Installation Supplements
Refer to the appropriate Greenheck installation supplements for special requirements:
• Concrete Floor with Steel Deck
• Drive Slip Breakaway Connection
• Quick Connect Breakaway Connection
• Single Side Retaining Angle
• Sealant Usage in Conjunction with Fire Rated Dampers
• Smoke Detector Supplement
• Resettable Link (RRL)
• Open or Close Indicator (OCI)
CFSD-XXX SERIES
Corridor Ceiling Dampers
(with factory installed actuator and sleeve)
CFSD models meet the requirements for corridor ceiling dampers, smoke dampers and combination fire/smoke dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes New York City (MEA listing #260-91-M)
California State Fire Marshal (Listing #3225-0981:106)
and (Listing #3230-0981:105)
“UL CLASSIFIED (see complete marking on product)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
UL Standard 555 & 555S (Classification #R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C).
Safety Warning
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
All wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70 latest edition, any local codes that may apply, and wiring diagrams developed in compliance with the job or project design and specifications.
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the shipment date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.
Electrical input may be needed for this equipment. This work should be performed by a qualified electrician. Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of the unit caused
by incorrect field wiring. To avoid causing death or serious bodily harm to building occupants, follow all instructions carefully. Dampers must close completely to preserve the integrity of the fire smoke separation.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.
Electrical Guidelines
Important!
2 in. x 4 in. wood or 2 x 2 1/2 in. steel studs
Retaining angle (See Section 3)
Grille (supplied by others)
1 in. x 2 1/2 in. 16 ga. angles either inside or outside of sleeve
Opening lined with UL rated 5/8 in. gypsum board (wood studs only)
d (wood studs only)
Installation - Failure to follow these instructions will void all warranties.
3
These instructions cover the installation of CFSD-XXX leakage rated combination fire/smoke dampers with factory installed actuators and sleeves in corridor ceiling applications. These instructions meet the requirements of UL555, UL555S and the Uniform Building Code.
There are three different configurations available for this application. Configurations 1 & 2 apply when the fire rated ceiling is also the finished ceiling and the damper is installed behind a grille, register or diffuser. Configuration 3 applies when the fire rated ceiling is above the finished ceiling and the grille, register or
diffuser is somewhere below the corridor damper.
1. MAXIMUM SIZES
Corridor dampers have a maximum size of 24 in. W x 24 in. H (610mm x 610mm) and a minimum size of 8 in. W x 6 in. H. (203mm x 152mm).
2. CLEARANCES REQUIRED BETWEEN CORRIDOR DAMPER SLEEVES AND CEILING OPENINGS
The interior dimension of the prepared ceiling opening should be 1/4 in. (6mm) larger than the overall size of the damper and sleeve assembly.
These are total clearances (ignoring fastener heads) and do not need to be spaced equally around the damper.
3. SECURING CORRIDOR DAMPER SLEEVES TO FIRE RATED CEILING OPENINGS
Corridor damper and sleeve assemblies must be installed in fire rated ceiling openings using retaining angles on each side of the ceiling as described below:
Installation of Configurations 1 & 2:
• Retaining angles must be a minimum of 20 ga.
(1mm)steel and have a minimum of 1½ in. x 1¼ in. (38mm x 32mm) legs on the ducted side of the installation and 1 in. x 2½ in. (25mm x 64mm) legs on the diffuser, grille or register side.
• The 1 in. x 2½ in. (25mm x 64mm) angle may be
mounted with the 2½ in. (64mm) leg inside or outside the sleeve
Installation of Configuration 3:
• Retaining angles must be a minimum of 20 ga. (1mm) steel with 1½ in. x 1¼ in. (38mm x 32mm) legs.
Retaining angles must be attached to the sleeve using:
• Tack or spot welds
• No. 10 sheet metal screws
• ¼ in. (6mm) bolts and nuts
• 3/16 in. (5mm) steel pop rivets
The angles must be attached to all 4 sides of the sleeve with butt joints at each corner. A minimum of 2 attachments are required on each side, top and bottom. The angles may (but need not) be attached to each other at the corners.
• Retaining angles must cover the clearance space between the sleeve and the ceiling opening.
Retaining angles (See Section 3)
2 in. x 4 in. wood or 2 in x 2 1/2 in. steel studs
1 in. x 2 1/2 in. 16 ga. angles either inside or outside of sleeve
(Actuator in airstream only)
Allows access to the actuator through the grille or diffuser.
Grille (supplied by others)
Configuration #1
Opening lined with UL rated 5/8 in. gypsum boar
Configuration #2
(Actuator in airstream or out of airstream)
Retaining angle
Steel studs
Steel Stud Assembly
Wood Stud Assembly
24 in. max.
24 in. o.c. max.
4
(See Section 3)
2 in. x 4 in. wood or 2 x 2 1/2 in. steel studs
Opening lined with UL rated 5/8 in. gypsum board (wood studs only)
Retaining angle (See Section 3)
Configuration #3
(Actuator in airstream or out of airstream)
Actuator can be installed either above or below ceiling
construction
6. PREPARATION OF OPENINGS IN WOOD AND METAL STUD CORRIDOR CEILINGS
• Corridor dampers are rated in ceiling
constructions with a fire resistance rating of one hour.
• Frame openings as shown below. Maximum size
of opening is 24 in. x 24 in. (610mm x 610mm). See Fig. 1 & 2.
• Corridor ceiling must be covered with a minimum
of one sheet of 5/8 in. (16mm) UL rated gypsum board on both sides.
• All construction and fasteners must meet the
requirements of the appropriate corridor ceiling design. Gypsum panels should be attached , 12 in. (305mm) O.C. maximum, to all stud and runner flanges surrounding opening with fasteners as designated by the appropriate corridor ceiling design.
24 in. o.c. max.
2 in. x 4 in. (nominal)
wood studs
4. DUCT TO SLEEVE CONNECTIONS
Dampers are supplied with sleeves and actuators from the factory and can be installed without the need for additional field installed sleeves.
Gauge of factory furnished sleeve determines the type of duct to sleeve connections required. Any duct connection other than those breakaway connections described on page three are considered rigid. Factory furnished round duct collars on type R and CR are also considered breakaway.
5. ACTUATOR CONNECTIONS
Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping diagrams developed in compliance with the job or project design and specifications.
Opening lined with UL rated 5/8 in. gypsum board
24 in. o.c. max.
24 in. max.
24 in. max.
Fig. 1
Steel studs
Steel Stud Assembly
Fig. 2
6
9
7 7
55
55
6
Std. Clip Length
C
L
Duct
60 Duct 4 Reqd.
48 Duct 3 Reqd.
36 Duct 3 Reqd.
24 Duct 2 Reqd.
18 Duct &
Smaller
1 Reqd.
Clip Spacing
6
55
55
Duct End
BREAKAWAY CONNECTIONS
Drive Slip Joint
5
Traditional Breakaway Style Transverse Joints
Transverse joints illustrated at right have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections.
• The breakaway connections shown below (Fig. 3) can be applied with maximum of (2) #10 sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket.
Plain “S” Slip Hemmed “S” Slip Double “S” Slip
Manufactured Flanged System Breakaway Connections
Flanged connection systems manufactured by Ductmate, DuroDyne, Ward, and Nexus are approved as breakaway connections when installed as illustrated.
Fire Damper Sleeve
6 in. long 1/16 in. max. thickness plastic cleats; 12 in. c-c (min. 1 per side)
Flanged system angles
(Attach per manufacturer's instructions)
3/8 in. bolts in corners are optional
Neoprene or Butyl gasket between all angles
Duct
Fig. 5
Proprietary Flange System Breakaway Connections
Inside Slip Joint Standing “S” Standing “S” (Alt.)
Standing “S” (Alt.) Standing “S” Standing “S”
(Bar Reinforced) (Angle Reinfor ced)
Fig. 3
• Transverse joints illustrated can be applied as top and bottom joints with Drive Slip - side joints in duct heights up to 20 inches (508mm). See Fig. 4.
Fig. 4
Round and Oval Duct Breakaway Connections
Round or flat oval ducts connected to Type R, CR or CO damper collars may use no. 10 sheet metal screws as follows:
• Ducts to 22 in. (559mm) wide (or dia.) and smaller may use 3 screws.
• Ducts larger than 22 in. (559mm) wide (or dia.) may use 5 screws.
NOTE: All breakaway connections described may have duct sealant applied, PA2084T Duct Sealant Adhesive manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie, Ductmate PROseal® or CL Ward S Seal in accordance with SMACNA recommendations.
(TDC by Lockformer, TDF by Engle) TDC and TDF systems (see Fig.
6) are approved as breakaway connections when installed as
Sleeve
described in the TDC or TDF addendum to the SMACNA Duct Construction Standards except
Typical TDC/TDF
joint
Fig. 6
the corners may not be bolted. Standard 6 in. (152mm) metal clip may be used with spacing as shown in diagram (see Fig. 7). 3/8 in. (9.5mm) metal bolts and nuts may be used to fasten together corner pieces together (see Fig. 8).
60 Duct 4 Reqd.
48 Duct 3 Reqd.
36 Duct 3 Reqd.
24 Duct 2 Reqd.
Clip Spacing
6
7 7
18 Duct &
Smaller
1 Reqd.
Flange
Std. Clip Length
6
Duct
9
C
L
Corner Piece
6
3/8 in. bolt (optional)
Fig. 7
Fig. 8
Duct
Damper Maintenance
6
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
• The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
• Actuator manufacturer recommendations.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom Possible Cause Corrective Action
Damper does not fully open and/or close
RRL or TOR sensor tripped
Damper does not operate
Frame is 'racked' causing blades to bind on jamb seals
Actuator linkage loose Close damper, disconnect power, adjust and
Defective motor Replace
Screws in damper linkage Damper installed too far into wall. Move out
Contaminants on damper Clean with a non-oil based solvent (see
Heat Push reset button located on backside of
No power supplied to the actuator Add power supply
Adjust frame such that it is square and plumb
tighten linkage
to line as designated on damper label
Damper Maintenance)
RRL or TOR
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
461335• CFSD Series Rev. 11, May 2014 Copyright 2014 © Greenheck Fan Corporation
Document Number 461336
7
Return to Table of Contents
®
FSD-XXX, DFD-XXX, DFDTF-XXX
CFSD-XXX, SEDFD-XXX, SEFSD-XXX,
IMO-XXX, AND SSFSD-XXX SERIES
1 1⁄2 and 3 Hour
Fire & Combination Fire Smoke Dampers
(with factory installed sleeve and actuator)
Vertical and Horizontal Mount
Installation, Operation and Maintenance Instructions
FSD-XXX, SEFSD-XXX, SSFSD-XXX, DFD-XXX, SEDFD­XXX, and CFSD-XXX Series Dampers are intended for installation in accordance with combination fire smoke damper requirements established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes New York City (MEA listing #260-91-M)
Typical Actuator
RRL Control Device Standard
California State Fire Marshal
(Listing #3225-0981:103) & (Listing #3230-0981:104) - FSD & SSFSD models; (Listing #3225-0981:103) - DFD models; (Listing #3230-0981:105) & (Listing 3225-0981:106) - CFSD models
Installation Supplements
Refer to the appropriate Greenheck installation supplements for special requirements:
• Concrete Floor with Steel Deck
• Drive Slip Breakaway Connection
• Field Installed Sleeve
• Fire Resistant Ventilated Duct Assembly
• Firestop Material
• Greenheck Test Switch
• Grille Installation
• Metal Stud in Shaftwall
• No Flow Smoke Detector
• Open or Close Indicator
• Quick Connect Breakaway Connections
• Resettable Link
• Sealant Supplement
• Single Side Retaining Angle
• Single 3-Sided Retaining Angle
• Sleeve Extension
• Smoke Detector
• Tunnel Corridor
Safety Warning:
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
“UL CLASSIFIED (see complete marking on prod­uct)” “UL CLASSIFIED to Canadian safety standards (see complete marking on product)”
UL Standard 555 & 555S (Classification #R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C).
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.
Table of Contents
8
Pre-Installation Guidelines ................................................................................................................................ 8
Electrical Guidelines .......................................................................................................................................... 8
Installation ......................................................................................................................................................9-13
Clearances Required Between Fire Damper Sleeves and Wall/Floor Openings ............................ 9
Sleeve Length and Wall Thickness .................................. .............................................................9-10
Duct to Sleeve Connections .............................................................................................................10
Securing the Damper/Sleeve Assembly to Wall and Floor Openings ........................ ...................10
Actuator Connections ..................................... .................................................................................11
Installing Multiple Damper Section Assemblies ..............................................................................11
Connection and Operation of Temperature Control Devices .........................................................12
Recommended Preparation of Openings in Wood and Metal Stud Walls ........................... .........13
Breakaway Connections ........................................ .........................................................................14
Maintenance .....................................................................................................................................................15
Troubleshooting ................................................................................................................................................15
Pre-Installation Guidelines
The basic intent of a proper installation is to secure the fire or fire smoke damper in, not to, the opening in such a manner as to prevent distortion and disruption of damper operation. This is accomplished by allowing the fire or fire smoke damper in rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging system. The following items will aid in completing the damper installation in a timely and effective manner.
1) Check the schedules for proper damper locations
within the building. Visually inspect the damper for damage and verify that the Reusable Resettable Link (RRL) is in place or has not activated. Never install a fire damper without the proper UL approved RRL in place. (RRL is standard control option. These electric links have a button for resetting.) If damper is furnished with fusible link, visually inspect the link to verify its not missing or broken. Replace link as necessary.
2) Lift or handle damper using sleeve or frame. Do not lift
damper using blades or actuators.
3) Damper has label on outside of sleeve indicating a
‘No Screw’ area. Do not install screws into this area as screws may interfere with unexposed blade linkage and prevent damper blades from opening and/or closing.
4) Damper has label indicating position of damper
and sleeve assembly in the wall. Install accordingly to comply with manufacturer’s appropriate UL Classification file number.
5) Damper must be installed into duct or opening square
and free of twist or other misalignment. Damper must not be squeezed or stretched into duct or opening. Out of square, racked, twisted or misaligned installations can cause excessive leakage and/or torque
requirements to exceed damper/actuator design.
6) Damper and actuator must be kept clean and protected from dirt, dust and other foreign materials prior to and after installation. Examples of such foreign materials include but are not limited to:
a) Mortar dust b) Drywall dust c) Firesafing materials d) Wall texture e) Paint overspray
7) Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to exceed damper/actuator design.
8) Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). However, caulking may be applied to the retaining angles.
9) ACCESS: Suitable access (such that RRL’s and actuators can be maintained, etc.) must be provided for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to install a removable section of duct. (Refer to NFPA 90A).
10) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to these instructions are necessary.
Electrical Guidelines
Electrical Guidelines
All wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70 latest edition, any local codes that may apply, and wiring diagrams developed in compliance with the job or project design and specifications.
Electrical input may be needed for this equipment. This work should be performed by a qualified electrician. Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of the unit caused by incorrect field wiring. To avoid causing death or serious bodily harm to building occupants, follow all instructions carefully. Dampers must close completely to preserve the integrity of the fire smoke separation.
Important!
Installation - Failure to follow these instructions will void all warranties.
9
1
These instructions apply to 1 masonry, block or stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory. Dampers must be installed in accordance with these instructions to meet the requirements of UL 555 and UL 555S. The installation of the damper and all duct connections to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Damper Installation Guide, and UL Classifications R13317.
Note: Combination fire smoke dampers are manufactured and labelled for either vertical or horizontal installation. The dampers must be installed in accordance with labelling.
1. CLEARANCES REQUIRED BETWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS
Fire damper and sleeve assemblies expand during periods of intense heat. Therefore, it is essential that openings in walls or floors be larger than the fire/smoke damper and sleeve assembly to allow for this expansion. Minimum clearances required between the outside of fire damper sleeve assemblies and wall/floor openings are:
• Galvanized steel fire dampers and sleeves: 1⁄8 in. per foot (3mm per .3 m) of damper width and (3mm per .3 m) height with a minimum clearance of (6mm), maximum of 1 1⁄2 in. (38mm).
Recommended clearances, for width and/or height dimensions of:
1) 48 in. (1219mm) or less:
/2 and 3 hour rated combination fire smoke dampers mounted (blades must be horizontal) in: 1)
2) More than 48 in. (1219mm) and 96 in. (2438mm) or less: 1 in. (25mm) clearance
3) More than 96 in. (2438mm): 11⁄2 in. (38mm) clearance
• Stainless steel fire/smoke dampers and stainless steel
3
or galvanized sleeves:
16 in. per foot (5mm per .3 m) of damper width and height with a minimum clearance of 1/4 in. (6mm), maximum of 2 in. (51mm).
Recommended clearances, for width and/or height
1
8 in. per foot
1
4 in.
dimensions of:
1) 48 in. (1219mm) or less: 3⁄4 in. (19mm) clearance.
These are total clearances (ignoring fastener heads) and do not need to be equally spaced around the damper. Refer to Section 4 and Figure 6 for additional installation
1
2 in. (13mm) clearance
considerations.
Fig. 1
Access door required on jackshaft side of damper. Refer to the latest edition of NFPA 90A.
Damper Sleeve
Dampers may be mounted either vertically or horizontally. Blade axis must always be horizontal.
Example:
A 12 in. x 12 in. (305mm x 305mm) will require a minimum clearance of 1/4 in. (6mm) width and 1/4 in. (6mm) on height
A 36 in. x 12 in. (914mm x 305mm) damper will required a minimum clearance of 1/2 in. (13mm) on width and 1/4 in. (13mm) on height.
Optional blade indicator and/or electric link.
Airflow
Jackshaft
Actuator
‘A’ Dim. (Distance from end of sleeve to face of damper)
16 in. max.
Sleeve Length (L)
Clearance for expansion (1/4 in. min., 1 1/2 in. max.)
Retaining Angles (see Section 4)
LIne of Wall
DO NOT INSTALL SCREWS
LINE OF WALL
DO NOT INSTALL SCREWS BETWEEN THESE LINES AROUND ENTIRE DAMPER
C
L
6 in. max.
T
w
BETWEEN THESE LINES AROUND ENTIRE DAMPER
Detail 1
458549
2. SLEEVE LENGTH AND WALL THICKNESS
Insert the sleeved damper assembly into the prepared opening, to appropriate depth (refer to label on outside of sleeve for location of damper in wall; see Dimension A and Detail 1, Fig. 1).
Recommended maximum and minimum insertion depth can be exceeded if:
1) The operation of the damper is not impeded and
2) The CL of the damper frame remains within the plane of the wall and
3) Attachments made through the retaining angle do not penetrate the ‘No Screw’ area designated on the damper sleeve.
Wall or Floor
Sleeve
Duct
Damper
Type B
Wall or Floo
r
IMPORTANT SAFETY DANGER! : To avoid causing
10
death or serious bodily harm to building occupants, do not penetrate the ‘No Screw’ area designated on the damper sleeve or the damper may not close properly.
The sleeve may extend a maximum of 16 in. (406mm) beyond the wall or floor on the actuator side of the damper and a maximum of 6 in. on the opposite side. Recommended standard sleeve lengths for various wall thicknesses are:
)
Sleeve Length
Dimension (L)
16 in.
(406mm)
21 in.
(533mm)
24 in.
(610mm)
Wall Thickness Dimension (T
4 - 6 in.
(102mm - 152mm)
7 - 10 in.
(178mm - 254mm)
11 - 13 in.
(279mm - 330mm)
W
3. DUCT TO SLEEVE CONNECTIONS
Dampers are supplied with sleeves and actuators from the factory and can be installed without the need for additional field installed sleeves.
Gauge of factory furnished sleeve determines the type of duct to sleeve connections required (see table below). Any duct connection other than the breakaway connections described on page 7 are considered rigid. Factory furnished duct collars, type R and O, are also considered breakaway (see Fig. 2).
Type of Duct
Sleeve Gauge Duct Dimension
to Sleeve
Connection
Permitted
14 ga. (0.075 in.)
- 10 ga. (0.138 in.)
[2mm - 3.5mm]
16 ga. (0.060 in.)
[1.5mm]
16 ga. (0.060 in.)
[1.5mm]
18 ga. (0.048 in.)
[1.2mm]
20 ga. (0.036 in.)
22 ga. (.030 in.)
26 ga. (0.018 in.)
See page 7 for additional information on breakaway sleeve connections. Sleeve thickness must not be less than the gauge of the connecting duct. UL Standard 555 requires all ducts to terminate at fire damper sleeves.
[0.9mm]
[0.76mm]
24 ga. (0.024)
[0.6mm]
[0.46mm]
All duct sizes
36 in. (914mm) max. width
24 in. (610mm) max.
24 in. (610mm) diameter
85 in. (2159mm) wide and
55 in. - 84 in. wide
(1397mm - 2134mm)
31 in. - 54 in. wide
(787mm - 1372mm)
13 in. - 30 in. wide (330mm - 762mm)
12 in. wide and under
height
All duct sizes
over
(305mm)
Rigid or
Breakaway
Rigid or
Breakaway
Breakaway only
Type R and O factory furnished duct collars qualify as breakaway connections.
Fig. 2
Duct
Type C, R
Sleeve
Damper
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO
WALL AND FLOOR OPENINGS (for single side retaining
angle instructions, see supplements)
Damper/sleeve assemblies must be installed in wall and floor openings using retaining angles on at least one side of the wall or floor as described below:
• Retaining angles for 1½ hour rated dampers with a width and height 48 in. (1219mm) or less must be a minimum of 20 ga. (1mm). Retaining angles for all 3 hour rated dampers and all dampers with a width or height greater than 48 in. (1219mm) must be a minimum of 16 gauge (1.5mm). The leg of the retaining angle on the damper sleeve shall be a minimum of 1¼ in. (32mm). The leg of the retaining angle on the wall/floor shall be long enough to cover the annular space and overlap the wall/floor by a minimum of 1 in. (25mm).
• Retaining angles must be attached to the damper using one or more of the following methods of attachment (refer to label on outside of sleeve for ‘No Screw’ area):
• Tack or spot welds
• #10 (3/4 in. [19mm] max.) sheet metal screws
1
/4 in. (6mm) bolts and nuts
3
/16 in. (5mm) steel pop rivets
A minimum of two connections per side, top, and bottom, 12 in. (305mm) O.C. maximum for openings of 48 in. W x 36 in. H (1219mm x 914mm) and less, and 6 in. (152mm) O.C. for openings 80 in. W x 50 in. H (2032mm x 1270mm), 50 in. W x 72 in. H (1270mm x 1829mm), and 40 in. W x 72 in. H (1016mm x 1829mm) or less. The angles must be attached to all 4 sides of the sleeve. Ensure that attachment device does not interfere with the operation of the damper and the free movement of the damper blades. The angles need not be attached to each other at the corners. Do not secure the retaining angle to the fire separation (see Fig. 3).
• Retaining angles should not be fastened to the wall/ floor material. The angles should only sandwich the wall/floor and allow for damper expansion during periods of intense heat.
Wall or
11
Floor
Min. 1 in.
Damper
Overlap*
Retaining Angle
Sleeve
Duct
Fig. 3
Retaining Angle
2 in. Max.
6 in. Max.
6 in. Max.
2 in. Max.
*only applicable for damper sizes above 36 in. x 36 in.
Both vertical and horizontal damper installations are typified by these drawings.
5. ACTUATOR CONNECTIONS
Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping diagrams developed in compliance with applicable codes, ordinances and regulations (see Electrical
Guidelines).
6. INSTALLING MULTIPLE DAMPER SECTION ASSEMBLIES
A damper assembly is not restricted to a maximum number of sections, but must not exceed the section sizes and overall sizes shown (see chart).
Two section high dampers require reinforcement using a 14 gauge (2mm), 5 in. (127mm) wide mullion as shown in Fig. 4 below, or two individually sleeved units stacked vertically, shown below in Fig. 5. When using two individually sleeved units, the sleeve acts as the mullion, therefore no mullion is required.
The damper sections must be attached together with #10 (3/4 in. max. [19mm]) sheet metal screws, 1/4 in. (6mm) diameter nuts and bolts, tack or spot welds, or 3/16 in. (48mm) diameter steel pop rivets. Attachments must be spaced a maximum of 6 in. (152mm) on centers and a maximum of 2 in. (51mm) from corners. Attachments must
be made on front face and back face (air entering and air exiting side) of damper sections.
Note: Dampers ordered for individual installation may not be installed together. The full assembly size must be specified at the time the dampers are ordered.
14 ga. 5 in. wide support mullion
Horizontal Mount
Maximum Single
Damper Model
Section Size in a Multiple Section
Assembly
CFSD-211, 212 24 x 24 NA
DFD-210 32 x 50 128 x 96
DFD-230 32 x 48 72 x 48
DFDAF-310 32 x 50 96 x 50
DFDTF-210
FSD-211, 212, 213 36 x 48 or 32 x 50 144 x 96
FSD-211M, 212M 36 x 36 144 x 72
FSD-231 36 x 36 or 32 x 48 72 x 48
FSD-311, 311M, 312, 312M
IMO-310 32 x 50 NA
IMO-311 32 x 50 NA
SEDFD-210, SEFSD-211
SSFSD-211 24 x 30 48 x 30
FSD-231M 32 x 36 72 x 48
32 x 36 96 x 72
32 x 48 64 x 48 or 32 x 96
32 x 50 96 x 50
24 x 30 48 x 30
Maximum Over-
all Size for
Multi-Section
Dampers
Vertical Mount
Maximum Single
Damper Model
Section Size in a
Multiple Section
Assembly
DFD-210 32 x 50 128 x 100
DFD-230 32 x 50 72 x 48
DFDAF-310 32 x 50 128 x 100
DFDTF-210
FSD-211, 212, 213 36 x 48 or 32 x 50 128 x 100
FSD-211M, 212M 36 x 36 128 x 72
FSD-231 36 x 36 or 32 x 48 72 x 48
FSD-311, 311M, 312, 312M
IMO-311
SEDFD-210, SSDFD-210
SEFSD-211 SSFSD-211
FSD-331; DFDAF-330 30 x 48 120 x 96
FSD-231M 32 x 36 72 x 48
32 x 36 96 x 72
32 x 50 64 x 50
32 x 50 128 x 100
32 x 50 NA
32 x 50 NA
24 x 30 or 22 x 36 48 x 30
24 x 30 or 22 x 36 88 x 72
Maximum
Overall Size for
Multi-section
Dampers
Fig. 4
Single Sleeve Around Outside with
Support Mullion
Fig. 5
Two Individually Sleeved Units
with No Mullions
NOTE: FSD model dampers fitted with a fusible link closure
device are limited to single section sizes. Dampers with a fusible link and spring assembly closure device may not be
used for multiple section applications.
7. CONNECTION AND OPERATION OF TEMPERATURE
12
RESPONSE DEVICES (RRL STANDARD, OCI OPTION, AND TOR OPTION)
RRL - Dampers will be supplied with a thermostat-type
temperature response device, as a standard. The device is a RRL (resettable link device), which only incorporates one thermostat and therefore the damper remains closed as soon as its sensor temperature is reached. The RRL does not contain blade indication switches. Refer to Fig. 6 for wiring of the RRL thermostat.
Fig. 6 RRL Wiring
OCI - The OCI (open or closed indicator) option
contains a single pole, double throw switch used to indicate the damper blade position. The switch provides a positive open or closed signal when used in conjunction with remote indicator lights. Refer to Fig. 7
& 8 for wiring of the OCI option.
TOR - The TOR (temperature override device) option
incorporates two thermostats with fixed settings (usually 165°F [74°C] and 350°F [177°C]). The primary sensor (the sensor with the lower temperature setting) can be bypassed by an external electrical signal allowing the damper to reopen until the temperature reaches the setting of the secondary sensor (the sensor with the higher temperature setting). See Fig. 8.
When the temperature of the secondary sensor is exceeded the damper closes and remains closed thereafter.
The TOR assembly also contains a single pole, double throw switch used to indicate damper blade position. The switch provides a positive open or closed signal when used in conjunction with remote indicator lights. See Fig. 8 for wiring of the TOR thermostats and indicator switches.
If either the TOR or the RRL is ordered with a pneumatic actuator, an EP switch is required with an appropriate electric power circuit to allow the electric thermostat to control the pneumatic actuator.
Fig. 7 OCI Wiring
Fig. 8 RRL/OCI Wiring
Fig. 9 TOR Wiring
PRV - The PRV (pneumatic relief valve) option is heat
responsive device used with pneumatic actuators. This can be used in place of EP switch where a RRL is used. The PRV activates when temperature in excess of the temperature of the fusible link are detected. When the fusible link melts, air from the actuator is exhausted to close the dampers. Pneumatic actuators are to be piped per local code.
RATINGS (Fig. 6, 7, 8 & 9)
Integral Switch Type: Single Pole, double throw Electrical Capacity: 10 Amps, 1/3 hp, 120 or 240 Vac
1/2 Amp, 125 Vdc; 1/4 Amp 250 Vdc 5 Amps, 120 Vac “L” ( lamp load)
1.0 Amps, 24 Vac
1.5 Amps, 24 Vdc
Temperature Limit: 165° F (standard primary sensor)
212° F (optional primary sensor) 250° F (secondary sensor )* 350º F (secondary sensor)*
* based on actuator temperature rating
Metal Stud Construction
In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard.
Gypsum Wallboar d
Stud or Runner
Retaining Angle
1 in. Min.
Damper Sleeve
8. Recommended Preparation of Openings in Wood and Metal Stud Walls
Metal Stud Construction
13
• Frame wall openings as shown below(see Fig. 12 & 12A).
• Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening (see
Fig. 12 & 12A).
• Prepare opening between studs and sleeve assembly as shown below (see Fig. 10 & 11).
• All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance
Directory) and/or local codes.
Wooden Stud Construction
Gypsum Wallboar d
Gypsum Wallboard
Retaining Angle
Damper Sleeve
Fig. 10
Stud or Runner
In metal stud construction, exposed steel surfaces need not be covered with gypsum wallboard.
Fig. 12
Second set of studs are not required on openings
36 in. x 36 in. (914mm x 914mm) or smaller.
1 in. Min.
24 in. o.c. Maximum
12 in.
Floor Runner
24 in. o.c.
Maximum
(metal studs)
16 in. o.c.
Maximum
(wood studs)
Fig. 11
24 in. o.c.
Maximum
(metal studs)
2 Panhead Screws
16 in. o.c.
Maximum
(wood studs)
Retaining Angle
Damper Sleeve
In wood stud construction, gypsum wallboard must cover all wood stud surfaces.
Ceiling Runner
2 in. (51mm)
2 in. (51mm)
Stud or Runner
1 in. Min.
Fig. 12A
6 in.
Std. Clip Length
C
L
Duct
60 in. Duct
4 Req’d.
48 in. Duct
3 Req’d.
36 in. Duct
3 Req’d.
24 in. Duct
2 Req’d.
18 in. Duct &
Smaller
1 Req’d.
Clip Spacing
6 in. 6 in.
9 in.
7 in.7 in.
5 in. 5 in.
5 in.5 in.
Duct End
9. DUCT-SLEEVE CONNECTIONS
Drive Slip Joint
6 in.
Std. Clip Length
60 in. Duct
4 Req’d.
48 in. Duct
3 Req’d.
36 in. Duct
3 Req’d.
24 in. Duct
2 Req’d.
Clip Spacing
6 in. 6 in.
9 in.
7 in.7 in.
5 in. 5 in.
5 in.5 in.
14
Traditional Breakaway Style Transverse Joints
Transverse joints illustrated at right have always been approved as breakaway connections. SMACNA testing has also approved the following variations as breakaway connections.
• The breakaway connections shown (Fig. 14) can be applied with maximum of two #10 (19mm) sheet metal screws on each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket.
• Transverse joints illustrated can be applied as top and bottom joints with Drive Slip ­side joints in duct heights up to 20 inches (508mm)
Fig. 13
See Fig. 13.
Plain “S” Slip Hemmed “S” Slip Double “S” Slip
Inside Slip Joint Standing “S” Standing “S” (Alt.)
Fire Damper Sleeve
6 in. long 1/16 in. max. thickness plastic cleats; 12 in. c-c (min. 1 per side)
Flanged system angles
(Attach per manufacturer's instructions)
3/8 in. bolts in corners are optional
Neoprene or Butyl gasket between all angles
Duct
Fig. 15
Proprietary Flange System Breakaway Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway connections when installed as described in the TDC or TDF addendum to the SMACNA Duct Construction. Standard 6 in. (152mm) metal clip may be used with spacing as shown in diagram (see Fig. 15 & 16). 3/8 in. (9.5mm) metal bolts and nuts may be used to fasten together corner pieces. (see Fig. 17)
Sleeve
Typical TDC/TDF joint
Fig. 16
Duct
Standing “S” (Alt.) Standing “S” Standing “S”
(Bar Reinforced)
(Angle Reinforced)
Fig. 14
Round and Oval Duct Breakaway Connections
Round or flat oval ducts connected to Type R or O damper collars shall be attached with #10 (19mm) sheet metal screws as follows:
• Ducts to 22 in. (558mm) wide (or dia.) and smaller shall have three screws.
• Ducts larger than 22 in. (558mm) wide (or dia.) up to and including 36 in. (914mm) wide (or dia.) shall have five screws.
NOTE: All breakaway connections described may have duct
sealant applied, PA2084T duct sealant adhesive manufactured by Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, Grey Pookie,
Ductmate PROseal
®
, or CL Ward S Seal in accordance with
SMACNA recommendations.
Manufactured Flanged System Breakaway Connections
Flanged connection systems manufactured by Ductmate, Durodyne, Ward, and Nexus are approved as breakaway connections when installed as illustrated (Fig. 15).
Fig. 17
Fig. 18
Flange
Corner Piece
3/8 in. bolt (optional)
Damper Maintenance
15
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
• The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
• Actuator manufacturer recommendations.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom Possible Cause Corrective Action
Damper does not fully open and/or close
RRL or TOR sensor tripped
Damper does not operate
Frame is 'racked' causing blades to bind on jamb seals
Actuator linkage loose Close damper, disconnect power, adjust and tighten
Defective motor Replace
Screws in damper linkage Damper installed too far into wall. Move out to line as
Contaminants on damper Clean with a non-oil based solvent (see Damper
Heat Push reset button located on backside of RRL or TOR
No power supplied to the actuator Add power supply
Adjust frame such that it is square and plumb
linkage
designated on damper label
Maintenance)
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
461336• FSD DFD CFSD Series Rev. 22, November 2014 Copyright 2014 © Greenheck Fan Corporation
Document Number 461337
16
Return to Table of Contents
®
OFSD-XXX, ODFD-XXX,
OFD-XXX, and OSSFD-XXX Series
1½ Hour Combination Fire Smoke or Curtain Fire Dampers
Out of Wall or Out of Floor
Vertical or Horizontal Mount
Installation, Operation, and Maintenance Instructions
OFSD-XXX, ODFD-XXX, OFD-XXX, and OSSFD-XXX series dampers are intended for installation in accordance with combination fire smoke dampers requirements established by: NFPA National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes New York City (MEA listing # 260-91-M) California State Fire Marshal
Listing #3225-0981:103 & 3230-0981:104
“UL Classified (see complete marking on product)” “UL Classified to Canadian safety standards (see complete marking on product)”
UL Standard 555 & 555S (Classification R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious and hidden damage. If damage is found, record all necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of the shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage and protection from dirt, dust and the weather is highly recommended. Do not store at temperatures in excess of 100°F (38°C).
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase date. Any units or parts which prove to be defective during the warranty period will be repaired or replaced at our option. Greenheck shall not be liable for damages resulting from misapplication or misuse of its products. Greenheck will not be responsible for any installation or removal costs. Greenheck will not be responsible for any service work or backcharges without prior written authorization.
Electrical Guidelines
All wiring shall be done in accordance with the National Electrical Code ANSI/NFPA-70 latest edition, any local codes that may apply, and wiring diagrams developed in compliance with the job or project design and specifications.
Safety Warning:
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
Important!
Electrical input may be needed for this equipment. This work should be performed by a qualified electrician. Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of the unit caused by incorrect field wiring. To avoid causing death or serious bodily harm to building occupants, follow all instructions carefully. Dampers must close completely to preserve the integrity of the fire smoke separation.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the job is complete.
Loading...
+ 36 hidden pages