Installation, Operation and Maintenance Instructions
Installation Supplements
Refer to the appropriate Greenheck installation
supplements for special requirements:
• Concrete Floor with Steel Deck
• Drive Slip Breakaway Connection
• Quick Connect Breakaway Connection
• Single Side Retaining Angle
• Sealant Usage in Conjunction with Fire Rated
Dampers
• Smoke Detector Supplement
• Resettable Link (RRL)
• Open or Close Indicator (OCI)
CFSD-XXX SERIES
Corridor Ceiling Dampers
(with factory installed actuator and sleeve)
CFSD models meet the requirements for corridor ceiling
dampers, smoke dampers and combination fire/smoke
dampers established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
California State Fire Marshal (Listing #3225-0981:106)
and (Listing #3230-0981:105)
“UL CLASSIFIED (see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards (see
complete marking on product)”
UL Standard 555 & 555S (Classification #R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100°F (38°C).
Safety Warning
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specifications.
Warranty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the shipment date. Any units or parts which
prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not
be responsible for any service work or backcharges
without prior written authorization.
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit caused
by incorrect field wiring.To avoid causing death or serious
bodily harm to building occupants, follow all instructions
carefully. Dampers must close completely to preserve the
integrity of the fire smoke separation.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the
job is complete.
Electrical Guidelines
Important!
2 in. x 4 in. wood
or 2 x 2 1/2 in.
steel studs
Retaining angle
(See Section 3)
Grille (supplied by others)
1 in. x 2 1/2 in. 16 ga.
angles either inside
or outside of sleeve
Opening lined with UL
rated 5/8 in. gypsum
board (wood studs only)
d (wood studs only)
Installation - Failure to follow these instructions will void all warranties.
3
These instructions cover the installation of CFSD-XXX
leakage rated combination fire/smoke dampers with
factory installed actuators and sleeves in corridor
ceiling applications. These instructions meet the
requirements of UL555, UL555S and the Uniform
Building Code.
There are three different configurations available for
this application. Configurations 1 & 2 apply when the
fire rated ceiling is also the finished ceiling and the
damper is installed behind a grille, register or diffuser.
Configuration 3 applies when the fire rated ceiling is
above the finished ceiling and the grille, register or
diffuser is somewhere below the corridor damper.
1. MAXIMUM SIZES
Corridor dampers have a maximum size of
24 in. W x 24 in. H (610mm x 610mm) and a
minimum size of 8 in. W x 6 in. H. (203mm x
152mm).
2. CLEARANCES REQUIRED BETWEEN CORRIDOR
DAMPER SLEEVES AND CEILING OPENINGS
The interior dimension of the prepared ceiling
opening
should be 1/4 in. (6mm) larger than the overall size
of the damper and sleeve assembly.
These are total clearances (ignoring fastener
heads) and do not need to be spaced equally
around the damper.
3. SECURING CORRIDOR DAMPER SLEEVES TO FIRE
RATED CEILING OPENINGS
Corridor damper and sleeve assemblies must
be installed in fire rated ceiling openings using
retaining angles on each side of the ceiling as
described below:
Installation of Configurations 1 & 2:
• Retaining angles must be a minimum of 20 ga.
(1mm)steel and have a minimum of 1½ in. x 1¼
in. (38mm x 32mm) legs on the ducted side of the
installation and 1 in. x 2½ in. (25mm x 64mm) legs
on the diffuser, grille or register side.
• The 1 in. x 2½ in. (25mm x 64mm) angle may be
mounted with the 2½ in. (64mm) leg inside or
outside the sleeve
Installation of Configuration 3:
• Retaining angles must be a minimum of 20 ga.
(1mm) steel with 1½ in. x 1¼ in. (38mm x 32mm)
legs.
Retaining angles must be attached to the sleeve
using:
• Tack or spot welds
• No. 10 sheet metal screws
• ¼ in. (6mm) bolts and nuts
• 3/16 in. (5mm) steel pop rivets
The angles must be attached to all 4 sides of the
sleeve with butt joints at each corner. A minimum of
2 attachments are required on each side, top and
bottom. The angles may (but need not) be attached
to each other at the corners.
• Retaining angles must cover the clearance space
between the sleeve and the ceiling opening.
Retaining angles
(See Section 3)
2 in. x 4 in. wood
or 2 in x 2 1/2 in.
steel studs
1 in. x 2 1/2 in. 16 ga.
angles either inside or
outside of sleeve
(Actuator in airstream only)
Allows access to the actuator through the grille or diffuser.
Grille (supplied by others)
Configuration #1
Opening lined with UL
rated 5/8 in. gypsum
boar
Configuration #2
(Actuator in airstream or out of airstream)
Retaining angle
Steelstuds
Steel Stud Assembly
Wood Stud Assembly
24 in. max.
24 in. o.c. max.
4
(See Section 3)
2 in. x 4 in. wood
or 2 x 2 1/2 in.
steel studs
Opening lined with UL
rated 5/8 in. gypsum
board (wood studs only)
Retaining angle
(See Section 3)
Configuration #3
(Actuator in airstream or out of airstream)
Actuator can be installed either above or below ceiling
construction
6. PREPARATION OF OPENINGS IN WOOD AND
METAL STUD CORRIDOR CEILINGS
• Corridor dampers are rated in ceiling
constructions with a fire resistance rating of one
hour.
• Frame openings as shown below. Maximum size
of opening is 24 in. x 24 in. (610mm x 610mm).
See Fig. 1 & 2.
• Corridor ceiling must be covered with a minimum
of one sheet of 5/8 in. (16mm) UL rated gypsum
board on both sides.
• All construction and fasteners must meet the
requirements of the appropriate corridor ceiling
design. Gypsum panels should be attached , 12
in. (305mm) O.C. maximum, to all stud and runner
flanges surrounding opening with fasteners as
designated by the appropriate corridor ceiling
design.
24 in. o.c. max.
2 in. x 4 in.
(nominal)
wood studs
4. DUCT TO SLEEVE CONNECTIONS
Dampers are supplied with sleeves and actuators
from the factory and can be installed without the
need for additional field installed sleeves.
Gauge of factory furnished sleeve determines
the type of duct to sleeve connections required.
Any duct connection other than those breakaway
connections described on page three are
considered rigid. Factory furnished round duct
collars on type R and CR are also considered
breakaway.
5. ACTUATOR CONNECTIONS
Electrical and/or pneumatic connections to
damper actuators should be made in accordance
with wiring and piping diagrams developed in
compliance with the job or project design and
specifications.
Opening lined
with UL rated
5/8 in. gypsum
board
24 in. o.c. max.
24 in.
max.
24 in.
max.
Fig. 1
Steel
studs
Steel Stud Assembly
Fig. 2
6
9
77
55
55
6
Std. ClipLength
C
L
Duct
60 Duct4 Reqd.
48 Duct3 Reqd.
36 Duct3 Reqd.
24 Duct2 Reqd.
18 Duct &
Smaller
1 Reqd.
Clip Spacing
6
55
55
Duct End
BREAKAWAY CONNECTIONS
Drive Slip Joint
5
Traditional Breakaway Style Transverse
Joints
Transverse joints illustrated at right have always
been approved as breakaway connections. SMACNA
testing has also approved the following variations as
breakaway connections.
• The breakaway connections shown below (Fig. 3)
can be applied with maximum of (2) #10 sheet metal
screws on each side and on the bottom located in
the center of the slip pocket and penetrating both
sides of the slip pocket.
Plain “S” Slip Hemmed “S” SlipDouble “S” Slip
Manufactured Flanged System Breakaway
Connections
Flanged connection systems manufactured by
Ductmate, DuroDyne, Ward, and Nexus are approved
as breakaway connections when installed as illustrated.
Fire Damper Sleeve
6 in. long 1/16 in. max.
thickness plastic cleats;
12 in. c-c (min. 1 per side)
Flanged system angles
(Attach per
manufacturer's
instructions)
3/8 in. bolts in
corners are optional
Neoprene or Butyl gasket
between all angles
Duct
Fig. 5
Proprietary Flange System Breakaway
Connections
Inside Slip JointStanding “S”Standing “S” (Alt.)
Standing “S” (Alt.)Standing “S”Standing “S”
(Bar Reinforced)(Angle Reinfor ced)
Fig. 3
• Transverse joints illustrated can be applied as top
and bottom joints with Drive Slip - side joints in
duct heights up to 20 inches (508mm). See Fig. 4.
Fig. 4
Round and Oval Duct Breakaway
Connections
Round or flat oval ducts connected to Type R, CR or
CO damper collars may use no. 10 sheet metal screws
as follows:
• Ducts to 22 in. (559mm) wide (or dia.) and smaller
may use 3 screws.
• Ducts larger than 22 in. (559mm) wide (or dia.) may
use 5 screws.
NOTE: All breakaway connections described may have
duct sealant applied, PA2084T Duct Sealant Adhesive
manufactured by Precision, DP1010 water base duct
sealant manufactured by Design Polymetrics, Grey
Pookie, Ductmate PROseal® or CL Ward S Seal in
accordance with SMACNA recommendations.
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems (see Fig.
6) are approved as breakaway
connections when installed as
Sleeve
described in the TDC or TDF
addendum to the SMACNA Duct
Construction Standards except
Typical TDC/TDF
joint
Fig. 6
the corners may not be bolted.
Standard 6 in. (152mm) metal clip
may be used with spacing as shown in diagram (see
Fig. 7). 3/8 in. (9.5mm) metal bolts and nuts may be
used to fasten together corner pieces together (see
Fig. 8).
60 Duct
4 Reqd.
48 Duct
3 Reqd.
36 Duct
3 Reqd.
24 Duct
2 Reqd.
Clip Spacing
6
77
18 Duct &
Smaller
1 Reqd.
Flange
Std. Clip
Length
6
Duct
9
C
L
Corner Piece
6
3/8 in. bolt
(optional)
Fig. 7
Fig. 8
Duct
Damper Maintenance
6
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary,
use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft
bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such
as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
• The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
• Actuator manufacturer recommendations.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
SymptomPossible CauseCorrective Action
Damper does not
fully open and/or
close
RRL or TOR sensor
tripped
Damper does not
operate
Frame is 'racked' causing blades
to bind on jamb seals
Actuator linkage looseClose damper, disconnect power, adjust and
Defective motorReplace
Screws in damper linkageDamper installed too far into wall. Move out
Contaminants on damperClean with a non-oil based solvent (see
HeatPush reset button located on backside of
No power supplied to the actuatorAdd power supply
Adjust frame such that it is square and plumb
tighten linkage
to line as designated on damper label
Damper Maintenance)
RRL or TOR
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without
notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library
under Warranties.
Installation, Operation and Maintenance Instructions
FSD-XXX, SEFSD-XXX, SSFSD-XXX, DFD-XXX, SEDFDXXX, and CFSD-XXX Series Dampers are intended for
installation in accordance with combination fire smoke
damper requirements established by:
National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
Refer to the appropriate Greenheck installation supplements
for special requirements:
• Concrete Floor with Steel Deck
• Drive Slip Breakaway Connection
• Field Installed Sleeve
• Fire Resistant Ventilated Duct Assembly
• Firestop Material
• Greenheck Test Switch
• Grille Installation
• Metal Stud in Shaftwall
• No Flow Smoke Detector
• Open or Close Indicator
• Quick Connect Breakaway Connections
• Resettable Link
• Sealant Supplement
• Single Side Retaining Angle
• Single 3-Sided Retaining Angle
• Sleeve Extension
• Smoke Detector
• Tunnel Corridor
Safety Warning:
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
“UL CLASSIFIED (see complete marking on product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
UL Standard 555 & 555S (Classification #R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess of
100°F (38°C).
Warranty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which
prove to be defective during the warranty period will be
repaired or replaced at our option. Greenheck shall not
be liable for damages resulting from misapplication or
misuse of its products. Greenheck will not be responsible
for any installation or removal costs. Greenheck will not
be responsible for any service work or backcharges
without prior written authorization.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when the
job is complete.
The basic intent of a proper installation is to secure the
fire or fire smoke damper in, not to, the opening in such a
manner as to prevent distortion and disruption of damper
operation. This is accomplished by allowing the fire or fire
smoke damper in rated separation openings to expand
and for the connecting duct to separate in the event of the
collapse of the hanging system. The following items will
aid in completing the damper installation in a timely and
effective manner.
1) Check the schedules for proper damper locations
within the building. Visually inspect the damper for
damage and verify that the Reusable Resettable Link
(RRL) is in place or has not activated. Never install a
fire damper without the proper UL approved RRL in
place. (RRL is standard control option. These electric
links have a button for resetting.) If damper is furnished
with fusible link, visually inspect the link to verify its not
missing or broken. Replace link as necessary.
2) Lift or handle damper using sleeve or frame. Do not lift
damper using blades or actuators.
3) Damper has label on outside of sleeve indicating a
‘No Screw’ area. Do not install screws into this area as
screws may interfere with unexposed blade linkage and
prevent damper blades from opening and/or closing.
4) Damper has label indicating position of damper
and sleeve assembly in the wall. Install accordingly
to comply with manufacturer’s appropriate UL
Classification file number.
5) Damper must be installed into duct or opening square
and free of twist or other misalignment. Damper must
not be squeezed or stretched into duct or opening. Out
of square, racked, twisted or misaligned installations
can cause excessive leakage and/or torque
requirements to exceed damper/actuator design.
6) Damper and actuator must be kept clean and
protected from dirt, dust and other foreign materials
prior to and after installation. Examples of such foreign
materials include but are not limited to:
a) Mortar dust
b) Drywall dust
c) Firesafing materials
d) Wall texture
e) Paint overspray
7) Damper should be sufficiently covered as to prevent
overspray if wall texturing or spray painting will be
performed within 5 feet of the damper. Excessive dirt
or foreign material deposits on damper can cause
excessive leakage and/or torque requirements to
exceed damper/actuator design.
8) Caulking is not necessary, nor is it allowed, between
the damper sleeve and the wall or floor opening
(annular space). However, caulking may be applied to
the retaining angles.
9) ACCESS: Suitable access (such that RRL’s and
actuators can be maintained, etc.) must be provided
for damper inspection and servicing. Where it is not
possible to achieve sufficient size access, it will be
necessary to install a removable section of duct. (Refer
to NFPA 90A).
10) The Code Authority Having Jurisdiction (AHJ) must
evaluate and provide approval of final installation
where variations to these instructions are necessary.
Electrical Guidelines
Electrical Guidelines
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specifications.
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit
caused by incorrect field wiring. To avoid causing death
or serious bodily harm to building occupants, follow all
instructions carefully. Dampers must close completely to
preserve the integrity of the fire smoke separation.
Important!
Installation - Failure to follow these instructions will void all warranties.
9
1
These instructions apply to 1
masonry, block or stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory. Dampers
must be installed in accordance with these instructions to meet the requirements of UL 555 and UL 555S. The installation of the
damper and all duct connections to the damper sleeve shall conform to the latest editions of NFPA 90A, Standard for the
Installation of Air Conditioning and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation Damper Installation
Guide, and UL Classifications R13317.
Note: Combination fire smoke dampers are manufactured and labelled for either vertical or horizontal installation. The
dampers must be installed in accordance with labelling.
1. CLEARANCES REQUIRED BETWEEN FIRE DAMPER
SLEEVES AND WALL/FLOOR OPENINGS
Fire damper and sleeve assemblies expand during periods
of intense heat. Therefore, it is essential that openings in
walls or floors be larger than the fire/smoke damper and
sleeve assembly to allow for this expansion. Minimum
clearances required between the outside of fire damper
sleeve assemblies and wall/floor openings are:
• Galvanized steel fire dampers and sleeves: 1⁄8 in. per
foot (3mm per .3 m) of damper width and
(3mm per .3 m) height with a minimum clearance of
(6mm), maximum of 1 1⁄2 in. (38mm).
Recommended clearances, for width and/or height
dimensions of:
1) 48 in. (1219mm) or less:
/2 and 3 hour rated combination fire smoke dampers mounted (blades must be horizontal) in: 1)
2) More than 48 in. (1219mm) and 96 in. (2438mm) or
less: 1 in. (25mm) clearance
3) More than 96 in. (2438mm): 11⁄2 in. (38mm) clearance
• Stainless steel fire/smoke dampers and stainless steel
3
or galvanized sleeves:
⁄16 in. per foot (5mm per .3 m) of
damper width and height with a minimum clearance of
1/4 in. (6mm), maximum of 2 in. (51mm).
Recommended clearances, for width and/or height
1
⁄8 in. per foot
1
⁄4 in.
dimensions of:
1) 48 in. (1219mm) or less: 3⁄4 in. (19mm) clearance.
These are total clearances (ignoring fastener heads) and
do not need to be equally spaced around the damper.
Refer to Section 4 and Figure 6 for additional installation
1
⁄2 in. (13mm) clearance
considerations.
Fig. 1
Access door required on
jackshaft side of damper.
Refer to the latest edition
of NFPA 90A.
Damper
Sleeve
Dampers may be mounted either vertically or horizontally. Blade axis must always be horizontal.
Example:
A 12 in. x 12 in. (305mm x 305mm) will
require a minimum clearance of 1/4
in. (6mm) width and 1/4 in. (6mm) on
height
A 36 in. x 12 in. (914mm x 305mm)
damper will required a minimum
clearance of 1/2 in. (13mm) on width
and 1/4 in. (13mm) on height.
Optional blade indicator
and/or electric link.
Airflow
Jackshaft
Actuator
‘A’ Dim.
(Distance from
end of sleeve to
face of damper)
16 in. max.
Sleeve Length (L)
Clearance for expansion
(1/4 in. min., 1 1/2 in. max.)
Retaining Angles
(see Section 4)
LIne of Wall
DO NOT INSTALL SCREWS
LINE OF WALL
DO NOT INSTALL SCREWS
BETWEEN THESE LINES
AROUND ENTIRE DAMPER
C
L
6 in. max.
T
w
BETWEEN THESE LINES
AROUND ENTIRE DAMPER
Detail 1
458549
2. SLEEVE LENGTH AND WALL THICKNESS
Insert the sleeved damper assembly into the prepared
opening, to appropriate depth (refer to label on
outside of sleeve for location of damper in wall; see
Dimension A and Detail 1, Fig. 1).
Recommended maximum and minimum insertion depth
can be exceeded if:
1) The operation of the damper is not impeded and
2) The CL of the damper frame remains within the plane
of the wall and
3) Attachments made through the retaining angle do not
penetrate the ‘No Screw’ area designated on the
damper sleeve.
Wall or Floor
Sleeve
Duct
Damper
Type B
Wall or Floo
r
IMPORTANT SAFETY DANGER! : To avoid causing
10
death or serious bodily harm to building occupants, do
not penetrate the ‘No Screw’ area designated on the
damper sleeve or the damper may not close properly.
The sleeve may extend a maximum of 16 in. (406mm)
beyond the wall or floor on the actuator side of the
damper and a maximum of 6 in. on the opposite side.
Recommended standard sleeve lengths for various wall
thicknesses are:
)
Sleeve Length
Dimension (L)
16 in.
(406mm)
21 in.
(533mm)
24 in.
(610mm)
Wall Thickness
Dimension (T
4 - 6 in.
(102mm - 152mm)
7 - 10 in.
(178mm - 254mm)
11 - 13 in.
(279mm - 330mm)
W
3. DUCT TO SLEEVE CONNECTIONS
Dampers are supplied with sleeves and actuators from
the factory and can be installed without the need for
additional field installed sleeves.
Gauge of factory furnished sleeve determines the
type of duct to sleeve connections required (see table
below). Any duct connection other than the breakaway
connections described on page 7 are considered rigid.
Factory furnished duct collars, type R and O, are also
considered breakaway (see Fig. 2).
Type of Duct
Sleeve GaugeDuct Dimension
to Sleeve
Connection
Permitted
14 ga. (0.075 in.)
- 10 ga. (0.138
in.)
[2mm - 3.5mm]
16 ga. (0.060 in.)
[1.5mm]
16 ga. (0.060 in.)
[1.5mm]
18 ga. (0.048 in.)
[1.2mm]
20 ga. (0.036 in.)
22 ga. (.030 in.)
26 ga. (0.018 in.)
See page 7 for additional information on breakaway sleeve connections.
Sleeve thickness must not be less than the gauge of the connecting duct.
UL Standard 555 requires all ducts to terminate at fire damper sleeves.
[0.9mm]
[0.76mm]
24 ga. (0.024)
[0.6mm]
[0.46mm]
All duct sizes
36 in. (914mm) max. width
24 in. (610mm) max.
24 in. (610mm) diameter
85 in. (2159mm) wide and
55 in. - 84 in. wide
(1397mm - 2134mm)
31 in. - 54 in. wide
(787mm - 1372mm)
13 in. - 30 in. wide
(330mm - 762mm)
12 in. wide and under
height
All duct sizes
over
(305mm)
Rigid or
Breakaway
Rigid or
Breakaway
Breakaway only
Type R and O
factory furnished
duct collars qualify
as breakaway
connections.
Fig. 2
Duct
Type C, R
Sleeve
Damper
4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO
WALL AND FLOOR OPENINGS (for single side retaining
angle instructions, see supplements)
Damper/sleeve assemblies must be installed in wall and
floor openings using retaining angles on at least one side
of the wall or floor as described below:
• Retaining angles for 1½ hour rated dampers with a
width and height 48 in. (1219mm) or less must be a
minimum of 20 ga. (1mm). Retaining angles for all 3 hour
rated dampers and all dampers with a width or height
greater than 48 in. (1219mm) must be a minimum of 16
gauge (1.5mm). The leg of the retaining angle on the
damper sleeve shall be a minimum of 1¼ in. (32mm).
The leg of the retaining angle on the wall/floor shall be
long enough to cover the annular space and overlap the
wall/floor by a minimum of 1 in. (25mm).
• Retaining angles must be attached to the damper using
one or more of the following methods of attachment
(refer to label on outside of sleeve for ‘No Screw’ area):
• Tack or spot welds
• #10 (3/4 in. [19mm] max.) sheet metal screws
1
•
/4 in. (6mm) bolts and nuts
3
•
/16 in. (5mm) steel pop rivets
A minimum of two connections per side, top, and bottom,
12 in. (305mm) O.C. maximum for openings of
48 in. W x 36 in. H (1219mm x 914mm) and less, and 6 in.
(152mm) O.C. for openings 80 in. W x 50 in. H
(2032mm x 1270mm), 50 in. W x 72 in. H (1270mm x
1829mm), and 40 in. W x 72 in. H (1016mm x 1829mm)
or less. The angles must be attached to all 4 sides of the
sleeve. Ensure that attachment device does not interfere
with the operation of the damper and the free movement
of the damper blades. The angles need not be attached
to each other at the corners. Do not secure the retaining
angle to the fire separation (see Fig. 3).
• Retaining angles should not be fastened to the wall/
floor material. The angles should only sandwich the
wall/floor and allow for damper expansion during
periods of intense heat.
Wall or
11
Floor
Min. 1 in.
Damper
Overlap*
Retaining
Angle
Sleeve
Duct
Fig. 3
Retaining
Angle
2 in. Max.
6 in. Max.
6 in. Max.
2 in. Max.
*only applicable for damper sizes above 36 in. x 36 in.
Both vertical and horizontal damper installations are typified by these
drawings.
5. ACTUATOR CONNECTIONS
Electrical and/or pneumatic connections to damper
actuators should be made in accordance with wiring and
piping diagrams developed in compliance with applicable
codes, ordinances and regulations (see Electrical
Guidelines).
6. INSTALLING MULTIPLE DAMPER SECTION
ASSEMBLIES
A damper assembly is not restricted to a maximum
number of sections, but must not exceed the section
sizes and overall sizes shown (see chart).
Two section high dampers require reinforcement using a
14 gauge (2mm), 5 in. (127mm) wide mullion as shown in
Fig. 4 below, or two individually sleeved units stacked
vertically, shown below in Fig. 5. When using two
individually sleeved units, the sleeve acts as the mullion,
therefore no mullion is required.
The damper sections must be attached together with
#10 (3/4 in. max. [19mm]) sheet metal screws, 1/4 in. (6mm)
diameter nuts and bolts, tack or spot welds, or 3/16 in.
(48mm) diameter steel pop rivets. Attachments must be
spaced a maximum of 6 in. (152mm) on centers and a
maximum of 2 in. (51mm) from corners. Attachments must
be made on front face and back face (air entering and air
exiting side) of damper sections.
Note: Dampers ordered for individual installation may
not be installed together. The full assembly size must be
specified at the time the dampers are ordered.
14 ga.
5 in. wide
support
mullion
Horizontal Mount
Maximum Single
Damper Model
Section Size in a
Multiple Section
Assembly
CFSD-211, 21224 x 24NA
DFD-21032 x 50128 x 96
DFD-23032 x 4872 x 48
DFDAF-31032 x 5096 x 50
DFDTF-210
FSD-211, 212, 21336 x 48 or 32 x 50144 x 96
FSD-211M, 212M36 x 36144 x 72
FSD-23136 x 36 or 32 x 4872 x 48
FSD-311, 311M, 312,
312M
IMO-31032 x 50NA
IMO-31132 x 50NA
SEDFD-210,
SEFSD-211
SSFSD-21124 x 3048 x 30
FSD-231M32 x 3672 x 48
32 x 3696 x 72
32 x 4864 x 48 or 32 x 96
32 x 5096 x 50
24 x 3048 x 30
Maximum Over-
all Size for
Multi-Section
Dampers
Vertical Mount
Maximum Single
Damper Model
Section Size in a
Multiple Section
Assembly
DFD-21032 x 50128 x 100
DFD-23032 x 5072 x 48
DFDAF-31032 x 50128 x 100
DFDTF-210
FSD-211, 212, 21336 x 48 or 32 x 50128 x 100
FSD-211M, 212M36 x 36128 x 72
FSD-23136 x 36 or 32 x 4872 x 48
FSD-311, 311M,
312, 312M
IMO-311
SEDFD-210,
SSDFD-210
SEFSD-211
SSFSD-211
FSD-331; DFDAF-33030 x 48120 x 96
FSD-231M32 x 3672 x 48
32 x 3696 x 72
32 x 5064 x 50
32 x 50128 x 100
32 x 50NA
32 x 50NA
24 x 30 or 22 x 3648 x 30
24 x 30 or 22 x 3688 x 72
Maximum
Overall Size for
Multi-section
Dampers
Fig. 4
Single Sleeve Around Outside with
Support Mullion
Fig. 5
Two Individually Sleeved Units
with No Mullions
NOTE:FSD model dampers fitted with a fusible link closure
device are limited to single section sizes. Dampers with a
fusible link and spring assembly closure device may not be
used for multiple section applications.
7. CONNECTION AND OPERATION OF TEMPERATURE
12
RESPONSE DEVICES (RRL STANDARD, OCI OPTION,
AND TOR OPTION)
RRL - Dampers will be supplied with a thermostat-type
temperature response device, as a standard. The device
is a RRL (resettable link device), which only incorporates
one thermostat and therefore the damper remains
closed as soon as its sensor temperature is reached.
The RRL does not contain blade indication switches.
Refer to Fig. 6 for wiring of the RRL thermostat.
Fig. 6 RRL Wiring
OCI - The OCI (open or closed indicator) option
contains a single pole, double throw switch used
to indicate the damper blade position. The switch
provides a positive open or closed signal when used in
conjunction with remote indicator lights. Refer to Fig. 7
& 8 for wiring of the OCI option.
TOR - The TOR (temperature override device) option
incorporates two thermostats with fixed settings (usually
165°F [74°C] and 350°F [177°C]). The primary sensor
(the sensor with the lower temperature setting) can be
bypassed by an external electrical signal allowing the
damper to reopen until the temperature reaches the
setting of the secondary sensor (the sensor with the
higher temperature setting).
See Fig. 8.
When the temperature of the secondary sensor is
exceeded the damper closes and remains closed
thereafter.
The TOR assembly also contains a single pole, double
throw switch used to indicate damper blade position. The
switch provides a positive open or closed signal when
used in conjunction with remote indicator lights. See
Fig. 8 for wiring of the TOR thermostats and indicator
switches.
If either the TOR or the RRL is ordered with a pneumatic
actuator, an EP switch is required with an appropriate
electric power circuit to allow the electric thermostat to
control the pneumatic actuator.
Fig. 7 OCI Wiring
Fig. 8 RRL/OCI Wiring
Fig. 9 TOR Wiring
PRV - The PRV (pneumatic relief valve) option is heat
responsive device used with pneumatic actuators. This
can be used in place of EP switch where a RRL is used.
The PRV activates when temperature in excess of the
temperature of the fusible link are detected. When the
fusible link melts, air from the actuator is exhausted to
close the dampers. Pneumatic actuators are to be piped
per local code.
RATINGS (Fig. 6, 7, 8 & 9)
Integral Switch Type: Single Pole, double throw
Electrical Capacity: 10 Amps, 1/3 hp, 120 or 240 Vac
• Gypsum wall board must be fastened 12 in. (305mm) on center to all stud and runner flanges surrounding opening (see
Fig. 12 & 12A).
• Prepare opening between studs and sleeve assembly as shown below (see Fig. 10 & 11).
• All construction and fasteners must meet the requirements of the appropriate wall design (See UL Fire Resistance
Directory) and/or local codes.
Wooden Stud Construction
Gypsum Wallboar d
Gypsum Wallboard
Retaining
Angle
Damper
Sleeve
Fig. 10
Stud or Runner
In metal stud construction,
exposed steel surfaces need
not be covered with gypsum
wallboard.
Fig. 12
Second set of studs are not required on openings
36 in. x 36 in. (914mm x 914mm) or smaller.
1 in. Min.
24 in. o.c.
Maximum
12 in.
Floor Runner
24 in. o.c.
Maximum
(metal studs)
16 in. o.c.
Maximum
(wood studs)
Fig. 11
24 in. o.c.
Maximum
(metal studs)
2 Panhead
Screws
16 in. o.c.
Maximum
(wood studs)
Retaining
Angle
Damper
Sleeve
In wood stud construction,
gypsum wallboard must cover
all wood stud surfaces.
Ceiling Runner
2 in. (51mm)
2 in. (51mm)
Stud or Runner
1 in. Min.
Fig. 12A
6 in.
Std. Clip
Length
C
L
Duct
60 in. Duct
4 Req’d.
48 in. Duct
3 Req’d.
36 in. Duct
3 Req’d.
24 in. Duct
2 Req’d.
18 in. Duct &
Smaller
1 Req’d.
Clip Spacing
6 in.6 in.
9 in.
7 in.7 in.
5 in.5 in.
5 in.5 in.
Duct End
9. DUCT-SLEEVE CONNECTIONS
Drive Slip Joint
6 in.
Std. ClipLength
60 in. Duct
4 Req’d.
48 in. Duct
3 Req’d.
36 in. Duct
3 Req’d.
24 in. Duct
2 Req’d.
Clip Spacing
6 in.6 in.
9 in.
7 in.7 in.
5 in.5 in.
5 in.5 in.
14
Traditional Breakaway Style Transverse Joints
Transverse joints illustrated at right have always been
approved as breakaway connections. SMACNA testing
has also approved the following variations as breakaway
connections.
• The breakaway connections shown (Fig. 14) can be
applied with maximum of two #10 (19mm) sheet metal
screws on each side and on the bottom located in the
center of the slip pocket and penetrating both sides of
the slip pocket.
• Transverse joints illustrated
can be applied as top and
bottom joints with Drive Slip side joints in duct heights up
to 20 inches (508mm)
Fig. 13
See Fig. 13.
Plain “S” Slip Hemmed “S” SlipDouble “S” Slip
Inside Slip JointStanding “S”Standing “S” (Alt.)
Fire Damper Sleeve
6 in. long 1/16 in. max.
thickness plastic cleats;
12 in. c-c (min. 1 per side)
Flanged system angles
(Attach per
manufacturer's
instructions)
3/8 in. bolts in
corners are optional
Neoprene or Butyl gasket
between all angles
Duct
Fig. 15
Proprietary Flange System Breakaway Connections
(TDC by Lockformer, TDF by Engle)
TDC and TDF systems are approved as breakaway
connections when installed as described in the TDC or
TDF addendum to the SMACNA
Duct Construction. Standard 6 in.
(152mm) metal clip may be used
with spacing as shown in diagram
(see Fig. 15 & 16). 3/8 in. (9.5mm)
metal bolts and nuts may be used
to fasten together corner pieces.
(see Fig. 17)
Sleeve
Typical TDC/TDF joint
Fig. 16
Duct
Standing “S” (Alt.)Standing “S”Standing “S”
(Bar Reinforced)
(Angle Reinforced)
Fig. 14
Round and Oval Duct Breakaway Connections
Round or flat oval ducts connected to Type R or O damper
collars shall be attached with #10 (19mm) sheet metal
screws as follows:
• Ducts to 22 in. (558mm) wide (or dia.) and smaller
shall have three screws.
• Ducts larger than 22 in. (558mm) wide (or dia.) up to
and including 36 in. (914mm) wide (or dia.) shall have
five screws.
NOTE: All breakaway connections described may have duct
sealant applied, PA2084T duct sealant adhesive
manufactured by Precision, DP1010 water base duct
sealant manufactured by Design Polymetrics, Grey Pookie,
Ductmate PROseal
®
, or CL Ward S Seal in accordance with
SMACNA recommendations.
Manufactured Flanged System Breakaway
Connections
Flanged connection systems manufactured by Ductmate,
Durodyne, Ward, and Nexus are approved as breakaway
connections when installed as illustrated (Fig. 15).
Fig. 17
Fig. 18
Flange
Corner Piece
3/8 in. bolt
(optional)
Damper Maintenance
15
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild
detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do
not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
• The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
• Actuator manufacturer recommendations.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
SymptomPossible CauseCorrective Action
Damper does not fully
open and/or close
RRL or TOR sensor
tripped
Damper does not
operate
Frame is 'racked' causing blades to bind
on jamb seals
Actuator linkage looseClose damper, disconnect power, adjust and tighten
Defective motorReplace
Screws in damper linkageDamper installed too far into wall. Move out to line as
Contaminants on damperClean with a non-oil based solvent (see Damper
HeatPush reset button located on backside of RRL or TOR
No power supplied to the actuatorAdd power supply
Adjust frame such that it is square and plumb
linkage
designated on damper label
Maintenance)
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to
change specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product
area tabs and in the Library under Warranties.
1½ Hour Combination Fire Smoke or Curtain Fire Dampers
Out of Wall or Out of Floor
Vertical or Horizontal Mount
Installation, Operation, and Maintenance Instructions
OFSD-XXX, ODFD-XXX, OFD-XXX, and OSSFD-XXX
series dampers are intended for installation in accordance
with combination fire smoke dampers requirements
established by:
NFPA National Fire Protection Association
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
IBC International Building Codes
New York City (MEA listing # 260-91-M)
California State Fire Marshal
Listing #3225-0981:103 & 3230-0981:104
“UL Classified (see complete marking on product)”
“UL Classified to Canadian safety standards (see
complete marking on product)”
UL Standard 555 & 555S (Classification R13317)
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess
of 100°F (38°C).
Warranty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which
prove to be defective during the warranty period will
be repaired or replaced at our option. Greenheck shall
not be liable for damages resulting from misapplication
or misuse of its products. Greenheck will not be
responsible for any installation or removal costs.
Greenheck will not be responsible for any service work
or backcharges without prior written authorization.
Electrical Guidelines
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specifications.
Safety Warning:
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
Important!
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit
caused by incorrect field wiring. To avoid causing death
or serious bodily harm to building occupants, follow all
instructions carefully. Dampers must close completely to
preserve the integrity of the fire smoke separation.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when
the job is complete.
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.