Greenheck MSXX04 Series, MSXX09 Series, MS4104, MS4109, MS4604 Installation Instructions Manual

...
Page 1
Document Number 477252
!
®
MSXX04 & MSXX09 Series Actuators
INSTALLATION INSTRUCTIONS
These instructions apply to the external field installation of the Honeywell actuators on Greenheck models VCD Control Dampers when they are duct mounted or sleeved.
These models are direct drive actuators that rotate to their energized position when power is applied, and spring return to their fail position when power is disconnected.
Tools Required:
Wrenches: (1) 7⁄16 in., (1) 3⁄8 in.
(1) Ratchet with 3⁄8 in. deepwell socket
(1) 1⁄8 in. Allen wrench
Part No. Quantitiy Description
1 1 External Mounting Bracket
2 1 #10-24 x .375 Shoulder Bolt
3 1 #10-24 Nut
4 8 1/4 - 20 x 1/2 Spinlock Bolt
5 8 1/4-20 Spinlock Nut
6 1 Actuator
7 1 Standoff Bracket
8 1 Extension Pin - 5 3/4 in. long
9 1 Retaining Clip - 1/2 in. dia.
Figure 1: Honeywell MSXX04 & MSXX09 Series external mount (exploded view).
5
7
1
3
2
4
6
4
8
5
9
Note: Actuator shaft collar accepts 1/2 in. (13mm) diameter shaft.
WARNING
!
Equipment Damage or Electrical Power Hazard. Line voltage can cause death or serious injury and short equipment circuitry. Disconnect power supply before installation.
CAUTION
!
Device Malfunction Hazard. Improper set screw tightening causes device malfunction. Tighten set screws with proper torque to prevent damper shaft slippage.
Without JackshaftWith Jackshaft
Page 2
FATPA DIRECT DRIVE SERIESINSTRUCTIONS
These installation instructions assume the damper is already mounted in a duct or sleeve with the damper shaft extending beyond the duct or sleeve 6 inches (152mm).
1. Install the stand-off bracket
Dampers with a jackshaft
1a. Remove the 1/2 in. (13mm) ball bearing from the
standoff bracket. Mount the stand-off bracket (item #7) with [4] ¼-20 x ½ in. (M6 x 12mm) spinlock bolts and nuts (item #4 and 5). Orient the stand-off bracket (item #7) so the hole is centered on the jackshaft (see Figure 1, With Jackshaft).
Dampers without a jackshaft (Shaft Extension) 1b. Mount the stand-off bracket (item #7) spanning
across the damper frame flanges. Fasten to the damper frame with [4] ¼-20 x ½ in. (M6 x 12mm) spinlock bolts and nuts (item #4 and 5). Be sure not to run the screws into the damper linkage, which is between the flanges.
2. Mount actuator bracket Fasten the actuator bracket (item #1) (See Figure
1) to the standoff bracket (item #7) using [4] ¼-20 x
½ in. (M6 X 20mm) spinlock bolts and nuts (item #4 and 5). Use outer four holes of the actuator bracket (item #2).
3. Fail Position If fail position is closed, make sure damper
blades are fully close and ensure blade seals are compressed prior to tightening the actuator clamp to the damper extension pin or jackshaft.
4. Install the actuator
Install the actuator (item #6) over the damper drive
shaft and tight against the actuator bracket (item #1). Install [1] #10-24 x .375 shoulder bolts (item #2) through lugs on actuator and through the holes in back of the actuator bracket (item #1). Secure with [2] #10-24 nuts (Item #5) (See Figure 1).
5. Secure actuator (Item #6) to drive shaft by tightening the set screws on actuator collar.
6. The wiring illustration identifies actuator electrical requirements and connections (See Figure 2). Wiring must comply with all applicable electrical codes.
7. Apply power to the actuator. The damper blades should fully open or close and return to the fail position when power is disconnected.
( )
L2
( )
L1
( )
L2
120 VAC
( )
L1
7° AUXILIARY
85° AUXILIARY
( )
L2
230 VAC
( )
L1
7° AUXILIARY
85° AUXILIARY
24 VAC
7° AUXILIARY
SWITCH
85° AUXILIARY
SWITCH
24 VAC wiring diagram
SWITCH
SWITCH
120 VAC wiring diagram
SWITCH
SWITCH
BLACK
RED
GREEN
BLUE
BLUE
YELLOW
YELLOW
M34624
WHITE
BLACK
GREEN
BLUE
BLUE
YELLOW
YELLOW
M34625
BLUE
BROWN
GREEN
BLUE
BLUE
YELLOW
YELLOW
2
230 VAC wiring diagram
M34626
Figure 2: MS Series wiring illustration.
Page 3
FATPA DIRECT DRIVE SERIESINSTRUCTIONS
Power Consumption
Model Volts Running Holding
MS4104 120 18W 9W
MS4109 120 23W 7W
MS4604 230 18W 11W
MS4609 230 23W 7W
MS8104 24 16VA 8VA
MS8109 24 23VA 7VA
Actuator Weight
5 lb (2.3 kg).
Noise Rating
Driving Open: Maximum 80 dBA at 1m. Holding: Maximum 20 dBA at 1m (no audible noise).
Temperature Ratings
Ambient: 0°F to 130°F (-18°C to 55°C) Shipping and Storage: -40°F to 140°F (-40°C to 60°C)
Humidity Ratings
5% to 95% RH non-condensing.
Environmental Protection Ratings
NEMA 1 IP40
Approvals
Underwriters Laboratories Inc. UL 873 plenum rating, and UL/cUL.
Actuator Timing (Under Load)
Drive Open: 15 seconds. Spring Close: 15 seconds.
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
477252• MS Series Rev. 1, October 2013 Copyright 2013 © Greenheck Fan Corporation