Greenheck MSX User Manual

Document 470658
®
®
Make-Up Air Unit
Installation, Operation and Maintenance Manual
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
General Safety Information
Only qualified personnel should install this unit. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electric Code (CEC) in Canada.
2. The rotation of the wheel is critical. It must be free to rotate without striking or rubbing any stationary objects.
3. Motor must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum cataloged fan rpm. Adjustments to fan speed significantly effects motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
5. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces, or chemicals. Replace cord immediately if damaged.
6. Verify that the power source is compatible with the equipment.
7. Never open blower access doors while the fan is running.
DANGER
Always disconnect power before working on or near a unit. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
When servicing the unit, motor may be hot enough to cause pain or injury. Allow motor to cool before servicing.
IMPORTANT
All factory provided lifting lugs must be used when lifting any unit. Failure to comply with this safety precaution could result in property damage, serious injury or death.
WARNING
Disconnect all electrical power to the fan and secure to the “OFF” position prior to inspection or servicing. Failure to comply with this safety precaution could result in serious injury or death.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
®
Modular Supply Make-Up Air Unit
1
Receiving
Upon receiving the product check to make sure all items are accounted for by referencing the bill of lading to ensure all items were received. Inspect each crate for shipping damage before accepting delivery. Notify the carrier if any damage is noticed. The carrier will make notification on the delivery receipt acknowledging any damage to the product. All damage should be noted on all the copies of the bill of lading which is countersigned by the delivering carrier. A Carrier Inspection Report should be filled out by the carrier upon arrival and reported to the Traffic Department. If damaged upon arrival, file claim with carrier. Any physical damage to the unit after acceptance is not the responsibility of manufacturer.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of unit to resist corrosion.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
INDOOR — The ideal environment for the storage of units and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Temperatures should be evenly maintained between 30°F (-1°C) and 110F (43°C) (wide temperature swings may cause condensation and “sweating” of metal parts). All accessories must be stored indoors in a clean, dry atmosphere.
Remove any accumulations of dirt, water, ice, or snow and wipe dry before moving to indoor storage. To avoid “sweating” of metal parts allow cold parts to reach room temperature. To dry parts and packages use a portable electric heater to get rid of any moisture build up. Leave coverings loose to permit air circulation and to allow for periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing. Aisles between parts and along all walls should be provided to permit air circulation and space for inspection.
OUTDOOR — Units designed for outdoor applications may be stored outdoors, if absolutely necessary. Roads or aisles for portable cranes and hauling equipment are needed.
The fan should be placed on a level surface to prevent water from leaking into the unit. The unit should be elevated on an adequate number of wooden blocks so that it is above water and snow levels and has enough blocking to prevent it from settling into soft ground. Locate parts far enough apart to permit air circulation, sunlight, and space for periodic inspection. To minimize water accumulation, place all unit parts on blocking supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these cause condensation of moisture from the air passing through heating and cooling cycles.
Inspection and Maintenance during Storage
While in storage, inspect fans once per month. Keep a record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate the fan wheel by hand ten to fifteen revolutions to distribute lubricant on motor. Every three months, the fan motor should be energized. If paint deterioration begins, consideration should be given to touch-up or repainting. Fans with special coatings may require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe thoroughly clean with Tectyl hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive or WD-40® or the equivalent.
REMOVING FROM STORAGE — As units are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the equipment goes into operation.
Prior to installing the unit and system components, inspect the unit assembly to make sure it is in working order.
1. Check all fasteners, set screws on the fan, wheel, bearings, drive, motor base, and accessories for tightness.
2. Rotate the fan wheel(s) by hand and assure no parts are rubbing.
®
506 (Ashland Inc.) or the equivalent. For
Modular Supply Make-Up Air Unit
2
®
Table of Contents
Installation
Clearance to Combustibles/Service Clearances . . 4
Indoor Unit ............................... 4
Unit Arrangement DB / HZ / UB .............. 4
Roof Mounted Unit — Arrangement DBC ......5-6
Optional Evaporative Cooling Module .......... 7
Electrical Wiring ........................... 8
Optional Electrical Heater ................... 9
Optional Evaporative Cooling Piping ........10-11
Optional Water Wizard™ ................... 12
Optional Direct Expansion (DX) Coil Piping . . . 13-14
Optional Chilled Water Coil Piping ........... 15
Optional Building Pressure Control ........... 15
Start-Up
Start-Up Check List ....................... 16
Blower ................................. 17
Optional Electric Heater .................... 18
Optional Economizer ...................... 19
Optional Evaporative Cooling Recirculating .... 20
Optional Water Wizard™ .................21-22
Operation
Optional VAV Units ........................ 23
Optional Recirculating Units ................ 24
Electrical ................................ 25
Optional Water Wizard™ ................... 26
Troubleshooting
Blower ................................. 27
Motor Overamps ......................... 28
Insufficient / Too Much Airflow .............. 29
Excessive Noise or Vibration ................ 30
Optional Electric Heater .................... 31
Optional Evaporative Cooling ............... 32
Optional Water Wizard™ ................... 33
Maintenance
Routine ...............................34-36
Fall .................................... 36
Reference
Control Center Layout / Dirty Filter Switch ..... 37
Maintenance Log .......................38-39
Our Commitment ...................Backcover
®
Modular Supply Make-Up Air Unit
3
Installation
Service Clearances
Floor Top Sides Ends
Insulated/
Units
Non Insulated
Units
Clearance to combustibles is defined as the minimum distance required between the heater and adjacent combustible surfaces to ensure the adjacent surface’s temperature does not exceed 90 degrees above the ambient temperature.
Recommended Minimum Service Clearances
Housing 32 and less
Housing 35 and higher
Clearances for component removal (such as evaporative cooler media) may be greater than the service clearances listed.
0 inches
(0 mm)
0 inches
(0 mm)
0 inches
(0 mm)
6 inches
(152.4 mm)
on the controls side of the unit
on the controls side of the unit
Installation of Indoor Unit
1. Install Hangers. Install threaded hangers from
ceiling supports. When locating hangers, allow enough room to open access panel(s). Two nuts must be used on the end of each threaded hanger. Ceiling supports are supplied by others.
2. Install Unit. Using sheet metal screws, attach the weatherhood/thru-wall/filter section to the blower/ burner section. The flange on the weatherhood/thru­wall/filter section should overlap the flange on the blower/burner section.
Raise the assembled unit into place. Using two nuts per hanger, fasten the unit supports
to the hangers under the unit. Appropriate unit supports, such as the optional hanging bracket kit or c-channel and angle iron (supplied by others) should be used.
Using self tapping screws, attach ductwork to unit. In order to prevent the unit from swinging and
to provide a safe environment for service and maintenance, additional measures must be taken to secure the unit in all directions.
Ceiling Supports
0 inches
(0 mm)
6 inches
(152.4 mm)
42 inches (1066.8 mm)
48 inches (1219.2 mm)
Ductwork
0 inches
(0 mm)
6 inches
(152.4 mm)
NOTE
Two nuts must be used on each end of each threaded hanging rod for proper support.
NOTE
Good duct practices should be followed for all ductwork. Ductwork should be installed in accordance with SMACNA and AMCA guidelines, NFPA 96 and any local codes. Reference the CAPS submittal for duct sizes.
Sealant
3. Seal Wall Opening. Apply sealant around the perimeter of the weatherhood to prevent water penetration and drafts into the building.
Seal Wall Opening
Installation of Arrangement DB / HZ / UB
1. Install Curb and/or Equipment Support(s).
Position curb/equipment support(s) on the roof (reference the CAPS submittal for placement of curb/ equipment support(s) in relation to the unit). Verify that unit supports are level, shim if necessary. Attach curb to roof and flash into place. Attach the equipment support(s) to the roof, remove metal cover, flash to wooden nailer and reinstall cover.
Roof Curb
Metal Cover
Equipment Support
Roof Curb and Equipment Support
2. Install Ductwork. followed for all ductwork. All ductwork should be installed in accordance with SMACNA and AMCA guidelines, NFPA 96 and all local codes. Reference the CAPS submittal for ductwork sizes.
Good duct practices should be
Hangers
Modular Supply Make-Up Air Unit
4
Indoor
Mounting
Unit Supports
NOTE
The use of a duct adapter is recommended on a downblast (DB) arrangement to align the ductwork with the supply unit. The duct adapter is only a guide and is not to be used as a support for the ductwork.
3. Apply Sealant. Apply an appropriate sealant around the perimeter of the curb and duct adapter(s) to isolate fan vibration and prevent water penetration.
®
Supply Air Ductwork
Supply Ductwork by Others
Exhaust Ductwork by Others
(Arrangement DB only)
Sealant
Ductwork
4. Install Unit. Use a crane and a set of spreader bars hooked to the factory lifting lugs to lift and center the unit on the curb/equipment support(s).
Use self-tapping sheet metal screws to fasten the
unit to the curb/equip support(s).
Installation of Roof Mounted Unit Arrangement DBC
1. Install Curb/Equipment Support(s). Position
curb/equipment support(s) on the roof (reference the CAPS submittal for placement of curb/equipment support(s) in relation to the unit). Verify that all unit supports are level, shim if necessary. Attach curb to roof and flash into place. Attach the equipment support(s) to the roof, remove metal cover, flash to wooden nailer and reinstall cover.
Roof Curb
Metal Cover
Equipment Support
Roof Curb and Equipment Support
2. Install Combination Extension. Install combination extension over curb. Lag into place using wood screws. Locate the extension so the tall vented side is over the exhaust opening.
Setting Unit
NOTE
The use of all lifting lugs and a set of spreader bars is mandatory when lifting the unit.
NOTE
Some units come with the weatherhood attached and Step 5 may not apply.
5. Assemble and Attach Weatherhood. The weatherhood can now be assembled and attached to the unit. Detailed assembly instructions can be found with the weatherhood. If the optional evaporative cooling module was selected, this step does not apply, refer to the Installation of the Optional Evaporative Cooling Module section.
6. Seal Weatherhood Seam. Using an appropriate sealant, seal the seam between the weatherhood and the unit.
Exhaust
Supply
1 inch Inside Flange
Combination Extension
3. Install Ductwork. Good duct practices should be followed for all ductwork. All ductwork should be installed in accordance with SMACNA and AMCA guidelines, NFPA 96 and any local codes. Reference the CAPS submittal for ductwork size and location.
Ductwork
NOTE
Complete Rooftop Installation
®
The use of a duct adapter is recommended on a downblast (DBC) arrangement to align the ductwork with the supply unit. The duct adapter is only a guide and is not to be used as a support for the ductwork.
Modular Supply Make-Up Air Unit
5
4. Apply Sealant. Apply an appropriate sealant
Supply Duct with Duct Adapter Installed
Exhaust Duct Installed
Sealant
around the perimeter of the curb and duct adapter(s) to isolate fan vibration and prevent water penetration.
Sealing Ductwork
5. Install Exhaust Fan. Fasten exhaust fan to curb extension with self-tapping sheet metal screws.
Installing the exhaust fan prior to the supply unit will allow for easier installation of options.
Model CUBE Exhaust Fan
7. Install Supply Unit. Use a crane and a set of spreader bars hooked to the factory lifting lugs to lift and center the unit on the extension/equipment support(s).
Use self-tapping sheet metal screws to fasten the
unit to the extension/equipment support(s).
Installing Supply Unit
Installing Exhaust Fan
NOTE
NFPA 96 requires the exhaust fan to be hinged.
6. Install Exhaust Options. Install optional hinge kit with restraining cables and grease trap with drain connection.
NOTE
The use of all lifting lugs and a set of spreader bars is mandatory when lifting unit.
NOTE
Some units come with the weatherhood attached and Step 8 may not apply.
8. Assemble and Attach Weatherhood. The weatherhood can now be assembled and/or attached to the unit. Detailed assembly instructions can be found with the weatherhood. If the optional evaporative cooling module was selected, this step does not apply, refer to the next section, Installation of the Optional Evaporative Cooling Module.
9. Seal Weatherhood Seam. Using an appropriate sealant, seal the seam between the weatherhood and the unit.
Modular Supply Make-Up Air Unit
6
Complete Combination Installation
®
Installation of Evaporative Cooling
Metal Cover
Equipment Support
Module (optional)
NOTE
Small evaporative coolers ship attached to the base unit and require no additional mounting.
1. Locate Equipment Support(s). Position equipment support(s) on the roof (reference the CAPS submittal for placement of equipment support(s) in relation to the unit). Verify that all unit supports are level, shim if necessary. Attach equipment support to the roof, remove metal cover, flash to wooden nailer and reinstall cover.
2. Apply Sealant. Apply an appropriate sealant around the airstream opening to create an air tight seal.
Equipment Support
4. Secure Cooling Module to Unit. Use self-tapping screws to fasten the cooling module to the base unit along the top and down both sides. Fasten at the top through the flanges. To fasten the sides, the media must be removed. To remove the media, first remove the access panel on the evaporative module and disconnect the evaporative pump(s). The media will now slide out. With the media removed, you can access the side fastening points inside the evaporative module. With all the screws in place, reinstall the media, reconnect the pumps and r
einstall
the access panel.
Securing Evaporative Module
Sealant
3. Set Evaporative Cooling Module.
Use a crane and a set of spreader bars hooked to the factory lifting lugs to lift and center the module on the equipment support(s). The flange on the evaporative cooler should overlap the flange on the unit.
NOTE
When mounting the evaporative cooler, it is important that it is level to ensure proper operation and water drainage.
Placing Evaporative Module
NOTE
The use of all lifting lugs and a set of spreader bars is mandatory when lifting the evaporative cooling module.
®
Modular Supply Make-Up Air Unit
7
Installation of Electrical Wiring
IMPORTANT
Before connecting power to the unit, read and understand the following instructions and wiring diagrams. Complete wiring diagrams are attached on the inside of the control center door(s).
IMPORTANT
All wiring should be done in accordance with the latest edition of the National Electric Code ANSI/ NFPA70 and any local codes that may apply. In Canada, wiring should be done in accordance with the Canadian Electrical Code.
IMPORTANT
The equipment must be properly grounded. Any wiring running through the unit in the airstream must be protected by metal conduit, metal clad cable or raceways.
CAUTION
If replacement wire is required, it must have a temperature rating of at least 105°C, except for an energy cut-off or sensor lead wire which must be rated to 150°C.
DANGER
High voltage electrical input is needed for this equipment. This work should be performed by a qualified electrician.
CAUTION
Any wiring deviations may result in personal injury or property damage. Manufacturer is not responsible for any damage to, or failure of the unit caused by incorrect final wiring.
IMPORTANT
Manufacturer’s standard control voltage is 24VAC. Control wire resistance should not exceed 0.75ohms (approximately 285 feet total length for 14gauge wire; 455 feet total length for 12gauge wire). If the resistance exceeds 0.75 ohms, an industrial-style plug-in relay should be wired in place of the remote switch. The relay must be rated for at least 5 amps and have a 24 VAC coil. Failure to comply with these guidelines may cause motor starters to chatter or not pull in, resulting in contactor failures and/or motor failures.
1. Determine the Size of the Main Power Lines. The unit’s nameplate states the voltage and the unit’s MCA. The main power lines to the unit should be sized accordingly. The nameplate is located on the outside of the unit on the control panel side.
2. Provide the Opening(s) for the Electrical Connection. Electrical openings vary by unit size
and arrangement and are field supplied.
3. Connect the Main Power. Connect the main power lines to the disconnect switch and main grounding lug(s). Torque field connections to 20in.-lbs.
4. Wire the Optional Convenience Outlet. The convenience outlet requires a separate 115 volt power supply circuit. The circuit must include short circuit protection which may need to be supplied by others.
5. Wire the Optional Accessories. Reference the Ladder Diagram on the inside of the control center door for correct wiring of the following accessories:
• Blower Switch
• Heat Switch
• Indicating Lights
• Dirty Filter Indicator
• TSCP
• KSCP
NOTE
TSCP has number-to-number wiring.
6. Wire the Optional Evaporative Cooler. Reference the Ladder Diagram on the inside of the control center door for correct wiring of the pump and the optional auto-drain and flush.
NOTE
Large evaporative coolers may require a separate power supply.
Modular Supply Make-Up Air Unit
8
®
Installation of Electric Heater
(optional)
WARNING
Electrical Shock Hazard! Disconnect all power sources before doing any work on the unit.
The requirements and practices described below are based on the National Electric Code (NEC) and The Space Heating Standard of the Underwriters Laboratories Inc. (UL). Although UL requirements are uniform throughout the country, local electrical codes may deviate from the National Electrical Code. Therefore, local inspection authorities should be consulted regarding local requirements.
Electrical Wiring Instructions
1. Use the wiring diagram supplied with the heater as a guide in correlating field wiring with the heater internal wiring.
2. All field wiring to the heater must meet the requirements of the National Electric Code and any other applicable local or state codes.
3. Wiring to the heater must be rated for 75°C (167°F) minimum.
4. The fan is interlocked by the factory to the control circuit so the electric heater will not operate unless the fan is on.
5. If heater does not have a built-in disconnect switch or main circuit breaker, install a remote disconnect (furnished by others) in accordance with the National Electric Code, Article 424-65.
Effect of Low Voltage on Wattage and British Thermal Unit (BTU)
The heating elements may be used on voltages lower than the design voltage of the heater, however, the wattage and BTU output will be reduced to the percentages listed in the table below.
Derated Wattage For Low Voltage
% of
Heater
Voltage
Line
Voltage
Heater
Wattage
Heater
Voltage
Line
Voltage
and BTU
480 460 92 208 200 92
440 84 190 83
277 265 92 120 115 92
254 84 110 84
240 230 92
220 84
208 75
200 69
% of
Heater
Wattage
and BTU
®
Modular Supply Make-Up Air Unit
9
Installation Evaporative Cooler Piping (optional)
Recirculating Evaporative Piping
IMPORTANT
All supply solenoids, valves and all traps must be below the roof line or be otherwise protected from freezing.
IMPORTANT
The supply line should be of adequate size and pressure to resupply the amount of water lost due to bleed-off and evaporation. The drain line should be the same size or larger than the supply line.
CAUTION
Provisions must be taken to prevent damage to the evaporative cooling section during freezing conditions. The sump, drain lines and supply lines must be drained prior to freezing conditions or an alternate method must be used to protect the lines and media.
1. Install the Water Supply Line. Supply line opening requirements vary by unit size and arrangement and are field supplied. Connect the water supply line to the float valve through the supply line opening in the evaporative cooling unit. Install a manual shutoff valve in the supply line as shown.
2. Install the Drain Line. Connect an unobstructed drain line to the drain and overflow connections on the evaporative cooler. A manual shut off valve (by others) is required for the evaporative cooler drain line.
A trap should be used to prevent sewer gas from
being drawn into the unit.
3. Check/Adjust Water Level.
Check the water level in the sump tank. The water level should be
Drain Trap
6 in. min.
above the pump intake and below the overflow. Adjust the float as needed to achieve the proper water level.
Drain Line Valve
(By Others)
Drain Line
Trap
Evaporative Cooling with Recirculating Pump
6 in. min.
Supply
Line
Supply Line
Valve
(By Others)
Overflow
Auto Drain & Fill Evaporative Piping
IMPORTANT
The supply line should be of adequate size and pressure to resupply the amount of water lost due to bleed-off and evaporation. The drain line should be the same size or larger than the supply line.
CAUTION
All solenoids valves and traps must be installed below the roof to protect the supply water line from freezing. If they cannot be installed below the roof, an alternative method must be used to protect the lines from freezing.
IMPORTANT
The supply solenoid (Valve A) is NOT the same as the drain solenoids (Valve B and Valve C). Make sure to use the proper solenoid for each location. Check your local code requirements for proper installation of this type of system.
Auto Drain & Flush Valves
(When provided by Manufacturer)
Assembly
Number
852178
Part numbers subject to change.
Mfg Part
Number
461262 8210G2
461263 8262G262
461264 8210G35
1. Install the Water Supply Line. Supply line opening requirements vary by unit size and arrangement and are field supplied. Connect the water supply line to the float valve through the supply line opening in the evaporative cooling unit. Install the 1/2 in. normally closed solenoid (Valve A) in the supply line. Install the 1/4 in. normally open solenoid (Valve B) between the supply line and the drain line. Refer to Auto Drain & Fill Evaporative Piping drawing on previous page.
2. Install the Drain Line. Connect an unobstructed drain line to the sump drain overflow connection. Install the 3/4 in. normally open solenoid (Valve C) between the sump drain connection and the drain line. A trap should be used to prevent sewer gas from being drawn into the unit.
3. Check/Adjust Water Level. Check the water level in the sump tank. The water level should be above the pump intake and below the overflow. Adjust the float as needed to achieve the proper water level.
ASCO
Part
Number
Solenoid
Supply Closed
Supply
Sump
Drain Trap
Type
Line
Drain
Drain
De-Energized
Position
Open
Open
Diameter
1/2 inch
(12.7 mm)
1/4 inch
(6.35 mm)
3/4 inch
(19.05 mm)
6 in. min.
6 in. min.
Qty.
1
1
1
Modular Supply Make-Up Air Unit
10
®
Sump Drain
VALVE C
Sump Drain Solenoid
(Normally Open)
Sump Overflow
Supply
Line
VALVE A
Supply Solenoid
(Normally Closed)
VALVE B
Supply Line Drain Solenoid
(Normally Open)
Trap
Drain Line
Evaporative Cooling with Auto Drain and Fill
®
Modular Supply Make-Up Air Unit
11
Installation of Water WizardTM (optional)
Evaporative Cooling with the Water Wizard™
NOTE
The following instructions are provided for evaporative coolers equipped with the Water Wizard™ only. Additional instructions are provided for evaporative coolers equipped with the auto-drain and fill or bleed-off.
WARNING
Disconnect and lock-out all power and gas before performing any maintenance or service to the unit. Failure to do so could result in serious injury or death and damage to equipment.
Roof
Line
Trap
Sump Drain
To Media
Pressure
Gauge
Manual Supply
Valve
Supply Solenoid
(Normally Closed)
Supply Line Drain Solenoid
(Normally Open)
Water Wizard™ Installation
Factory
Installed
Field
Installed
Water Wizard™ Valves
(When provided by Manufacturer)
Unit
Assembly
Model
MSX -
H12/H22
MSX - H32
(<9000 cfm)
MSX - H32
(≥9000 cfm)
MSX-H35,
H38, H42
Part numbers subject to change.
Number
852370
852371
Mfg.
ASCO
Part
Part No.
No.
461262 8210G2
383086 8210G34
383088 8210G9
383086 8210G34
Solenoid
Type
Supply Closed
Supply
Line
Drain
Supply Closed
Supply
Line
Drain
De-
Energized
Position
Open
Open
Diameter Qty.
(12.7 mm)
(12.7 mm)
(19.05 mm)
(12.7 mm)
1/2 inch
1/2 inch
3/4 inch
1/2 inch
1. Install Normally Closed Supply Line/Solenoid. Connect the water supply line to the manual supply valve in the unit. Install the supply solenoid in the supply line, upstream of the manual supply valve and below the roof line.
2. Install Normally Open Drain Line/Solenoid. Connect the drain line to the supply line between the manual supply valve and the supply solenoid. Install a drain solenoid in the drain line, below the roof line. A trap should be installed in the drain line.
3. Wire the Solenoid(s). Wire the supply line solenoid and drain solenoid as shown on the unit’s wiring diagram in the control center.
4. Wire the Temperature Sensor. If the evaporative cooler shipped separate from the unit, the temperature sensor must be wired. The sensor
1
wire is bundled inside the discharge end of the evaporative cooler. Wire the sensor wire to terminals as shown on the unit’s wiring diagram.
1
The Water Wizard™ start-up must be completed for
1
proper performance.
1
NOTE
NOTE
Solenoid(s) may be provided by Manufacturer (if ordered) or by others.
CAUTION
Any wiring deviations may result in personal injury or property damage. Manufacturer is not responsible for any damage to, or failure of the unit caused by incorrect final wiring.
Modular Supply Make-Up Air Unit
12
®
Loading...
+ 28 hidden pages