Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
General Safety Information
Only qualified personnel should install this unit.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. Other
considerations may be required if high winds or seismic
activity are present. If more information is needed,
contact a licensed professional engineer before moving
forward.
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC), the National Fire
Protection Agency (NFPA), where applicable. Follow
the Canadian Electric Code (CEC) in Canada.
2. The rotation of the wheel is critical. It must be free
to rotate without striking or rubbing any stationary
objects.
3. Motor must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan rpm. Adjustments to fan speed
significantly effects motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces, or chemicals.
Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open blower access doors while the fan is
running.
DANGER
Always disconnect power before working on or near a
unit. Lock and tag the disconnect switch or breaker to
prevent accidental power up.
CAUTION
When servicing the unit, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
IMPORTANT
All factory provided lifting lugs must be used when
lifting any unit. Failure to comply with this safety
precaution could result in property damage, serious
injury or death.
WARNING
Disconnect all electrical power to the fan and secure
to the “OFF” position prior to inspection or servicing.
Failure to comply with this safety precaution could
result in serious injury or death.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury
or death. Read the installation, operating and
maintenance instructions thoroughly before installing
or servicing this equipment.
®
Modular Supply Make-Up Air Unit
1
Receiving
Upon receiving the product check to make sure all items
are accounted for by referencing the bill of lading to
ensure all items were received. Inspect each crate for
shipping damage before accepting delivery. Notify the
carrier if any damage is noticed. The carrier will make
notification on the delivery receipt acknowledging any
damage to the product. All damage should be noted on
all the copies of the bill of lading which is countersigned
by the delivering carrier. A Carrier Inspection Report
should be filled out by the carrier upon arrival and
reported to the Traffic Department. If damaged upon
arrival, file claim with carrier. Any physical damage to
the unit after acceptance is not the responsibility of
manufacturer.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative to
arrange for obtaining missing parts. Sometimes it is not
possible that all items for the unit be shipped together
due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only
items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting brackets
provided or by the skid when a forklift is used. Location
of brackets varies by model and size. Handle in such
a manner as to keep from scratching or chipping the
coating. Damaged finish may reduce ability of unit to
resist corrosion.
Storage
Units are protected against damage during shipment. If
the unit cannot be installed and operated immediately,
precautions need to be taken to prevent deterioration of
the unit during storage. The user assumes responsibility
of the unit and accessories while in storage. The
manufacturer will not be responsible for damage during
storage. These suggestions are provided solely as a
convenience to the user.
INDOOR — The ideal environment for the storage of
units and accessories is indoors, above grade, in a
low humidity atmosphere which is sealed to prevent
the entry of blowing dust, rain, or snow. Temperatures
should be evenly maintained between 30°F (-1°C) and
110F (43°C) (wide temperature swings may cause
condensation and “sweating” of metal parts). All
accessories must be stored indoors in a clean, dry
atmosphere.
Remove any accumulations of dirt, water, ice, or snow
and wipe dry before moving to indoor storage. To avoid
“sweating” of metal parts allow cold parts to reach room
temperature. To dry parts and packages use a portable
electric heater to get rid of any moisture build up. Leave
coverings loose to permit air circulation and to allow for
periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the
floor on wooden blocks covered with moisture proof
paper or polyethylene sheathing. Aisles between parts
and along all walls should be provided to permit air
circulation and space for inspection.
OUTDOOR — Units designed for outdoor applications
may be stored outdoors, if absolutely necessary. Roads
or aisles for portable cranes and hauling equipment are
needed.
The fan should be placed on a level surface to prevent
water from leaking into the unit. The unit should be
elevated on an adequate number of wooden blocks so
that it is above water and snow levels and has enough
blocking to prevent it from settling into soft ground.
Locate parts far enough apart to permit air circulation,
sunlight, and space for periodic inspection. To minimize
water accumulation, place all unit parts on blocking
supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these
cause condensation of moisture from the air passing
through heating and cooling cycles.
Inspection and Maintenance during
Storage
While in storage, inspect fans once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate the fan wheel by hand ten to fifteen
revolutions to distribute lubricant on motor. Every three
months, the fan motor should be energized. If paint
deterioration begins, consideration should be given to
touch-up or repainting. Fans with special coatings may
require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust
occur. Immediately remove the original rust preventive
coating with petroleum solvent and clean with lint-free
cloths. Polish any remaining rust from surface with
crocus cloth or fine emery paper and oil. Do not destroy
the continuity of the surfaces. Wipe thoroughly clean
with Tectyl
hard to reach internal surfaces or for occasional use,
consider using Tectyl® 511M Rust Preventive or WD-40®
or the equivalent.
REMOVING FROM STORAGE — As units are removed
from storage to be installed in their final location, they
should be protected and maintained in a similar fashion,
until the equipment goes into operation.
Prior to installing the unit and system components,
inspect the unit assembly to make sure it is in working
order.
1. Check all fasteners, set screws on the fan, wheel,
bearings, drive, motor base, and accessories for
tightness.
2. Rotate the fan wheel(s) by hand and assure no parts
are rubbing.
®
506 (Ashland Inc.) or the equivalent. For
Modular Supply Make-Up Air Unit
2
®
Table of Contents
Installation
Clearance to Combustibles/Service Clearances . . 4
Indoor Unit ............................... 4
Unit Arrangement DB / HZ / UB .............. 4
Roof Mounted Unit — Arrangement DBC ......5-6
Optional Evaporative Cooling Module .......... 7
Electrical Wiring ........................... 8
Optional Electrical Heater ................... 9
Optional Evaporative Cooling Piping ........10-11
Optional Water Wizard™ ................... 12
Optional Direct Expansion (DX) Coil Piping . . . 13-14
Control Center Layout / Dirty Filter Switch ..... 37
Maintenance Log .......................38-39
Our Commitment ...................Backcover
®
Modular Supply Make-Up Air Unit
3
Installation
Service Clearances
FloorTopSidesEnds
Insulated/
Units
Non Insulated
Units
Clearance to combustibles is defined as the minimum distance required
between the heater and adjacent combustible surfaces to ensure the
adjacent surface’s temperature does not exceed 90 degrees above the
ambient temperature.
Recommended Minimum Service Clearances
Housing 32 and less
Housing 35 and higher
Clearances for component removal (such as evaporative cooler media)
may be greater than the service clearances listed.
0 inches
(0 mm)
0 inches
(0 mm)
0 inches
(0 mm)
6 inches
(152.4 mm)
on the controls side of the unit
on the controls side of the unit
Installation of Indoor Unit
1. Install Hangers. Install threaded hangers from
ceiling supports. When locating hangers, allow
enough room to open access panel(s). Two nuts
must be used on the end of each threaded hanger.
Ceiling supports are supplied by others.
2.Install Unit. Using sheet metal screws, attach the
weatherhood/thru-wall/filter section to the blower/
burner section. The flange on the weatherhood/thruwall/filter section should overlap the flange on the
blower/burner section.
Raise the assembled unit into place.
Using two nuts per hanger, fasten the unit supports
to the hangers under the unit. Appropriate unit
supports, such as the optional hanging bracket kit or
c-channel and angle iron (supplied by others) should
be used.
Using self tapping screws, attach ductwork to unit.
In order to prevent the unit from swinging and
to provide a safe environment for service and
maintenance, additional measures must be taken to
secure the unit in all directions.
Ceiling Supports
0 inches
(0 mm)
6 inches
(152.4 mm)
42 inches (1066.8 mm)
48 inches (1219.2 mm)
Ductwork
0 inches
(0 mm)
6 inches
(152.4 mm)
NOTE
Two nuts must be used on each end of each threaded
hanging rod for proper support.
NOTE
Good duct practices should be followed for all
ductwork. Ductwork should be installed in accordance
with SMACNA and AMCA guidelines, NFPA 96 and
any local codes. Reference the CAPS submittal for
duct sizes.
Sealant
3. Seal Wall Opening.
Apply sealant around
the perimeter of the
weatherhood to
prevent water
penetration and
drafts into the
building.
Seal Wall Opening
Installation of Arrangement DB / HZ / UB
1. Install Curb and/or Equipment Support(s).
Position curb/equipment support(s) on the roof
(reference the CAPS submittal for placement of curb/
equipment support(s) in relation to the unit). Verify that
unit supports are level, shim if necessary. Attach curb
to roof and flash into place. Attach the equipment
support(s) to the roof, remove metal cover, flash to
wooden nailer and reinstall cover.
Roof Curb
Metal Cover
Equipment
Support
Roof Curb and Equipment Support
2. Install Ductwork.
followed for all ductwork. All ductwork should be
installed in accordance with SMACNA and AMCA
guidelines, NFPA 96 and all local codes. Reference the
CAPS submittal for ductwork sizes.
Good duct practices should be
Hangers
Modular Supply Make-Up Air Unit
4
Indoor
Mounting
Unit Supports
NOTE
The use of a duct adapter is recommended on a
downblast (DB) arrangement to align the ductwork
with the supply unit. The duct adapter is only a guide
and is not to be used as a support for the ductwork.
3. Apply Sealant. Apply an appropriate sealant around
the perimeter of the curb and duct adapter(s) to
isolate fan vibration and prevent water penetration.
®
Supply Air Ductwork
Supply
Ductwork
by Others
Exhaust
Ductwork
by Others
(Arrangement DB only)
Sealant
Ductwork
4. Install Unit. Use a crane and a set of spreader bars
hooked to the factory lifting lugs to lift and center the
unit on the curb/equipment support(s).
Use self-tapping sheet metal screws to fasten the
unit to the curb/equip support(s).
Installation of Roof Mounted Unit
Arrangement DBC
1. Install Curb/Equipment Support(s). Position
curb/equipment support(s) on the roof (reference the
CAPS submittal for placement of curb/equipment
support(s) in relation to the unit). Verify that all unit
supports are level, shim if necessary. Attach curb
to roof and flash into place. Attach the equipment
support(s) to the roof, remove metal cover, flash to
wooden nailer and reinstall cover.
Roof Curb
Metal Cover
Equipment
Support
Roof Curb and Equipment Support
2. Install Combination Extension. Install
combination extension over curb. Lag into place
using wood screws. Locate the extension so the tall
vented side is over the exhaust opening.
Setting Unit
NOTE
The use of all lifting lugs and a set of spreader bars is
mandatory when lifting the unit.
NOTE
Some units come with the weatherhood attached and
Step 5 may not apply.
5. Assemble and Attach Weatherhood. The
weatherhood can now be assembled and attached
to the unit. Detailed assembly instructions can
be found with the weatherhood. If the optional
evaporative cooling module was selected, this
step does not apply, refer to the Installation of the
Optional Evaporative Cooling Module section.
6. Seal Weatherhood Seam. Using an appropriate
sealant, seal the seam between the weatherhood
and the unit.
Exhaust
Supply
1 inch
Inside Flange
Combination Extension
3. Install Ductwork. Good duct practices should be
followed for all ductwork. All ductwork should be
installed in accordance with SMACNA and AMCA
guidelines, NFPA 96 and any local codes. Reference
the CAPS submittal for ductwork size and location.
Ductwork
NOTE
Complete Rooftop Installation
®
The use of a duct adapter is recommended on a
downblast (DBC) arrangement to align the ductwork
with the supply unit. The duct adapter is only a guide
and is not to be used as a support for the ductwork.
Modular Supply Make-Up Air Unit
5
4. Apply Sealant. Apply an appropriate sealant
Supply Duct with
Duct Adapter Installed
Exhaust Duct
Installed
Sealant
around the perimeter of the curb and duct
adapter(s) to isolate fan vibration and prevent water
penetration.
Sealing Ductwork
5. Install Exhaust Fan. Fasten exhaust fan to curb
extension with self-tapping sheet metal screws.
Installing the exhaust fan prior to the supply unit
will allow for easier installation of options.
Model CUBE
Exhaust Fan
7. Install Supply Unit. Use a crane and a set of
spreader bars hooked to the factory lifting lugs to
lift and center the unit on the extension/equipment
support(s).
Use self-tapping sheet metal screws to fasten the
unit to the extension/equipment support(s).
Installing Supply Unit
Installing Exhaust Fan
NOTE
NFPA 96 requires the exhaust fan to be hinged.
6. Install Exhaust Options. Install optional hinge kit
with restraining cables and grease trap with drain
connection.
NOTE
The use of all lifting lugs and a set of spreader bars is
mandatory when lifting unit.
NOTE
Some units come with the weatherhood attached and
Step 8 may not apply.
8. Assemble and Attach Weatherhood. The
weatherhood can now be assembled and/or
attached to the unit. Detailed assembly instructions
can be found with the weatherhood. If the optional
evaporative cooling module was selected, this step
does not apply, refer to the next section, Installation
of the Optional Evaporative Cooling Module.
9.Seal Weatherhood Seam. Using an appropriate
sealant, seal the seam between the weatherhood
and the unit.
Modular Supply Make-Up Air Unit
6
Complete Combination Installation
®
Installation of Evaporative Cooling
Metal Cover
Equipment
Support
Module (optional)
NOTE
Small evaporative coolers ship attached to the base
unit and require no additional mounting.
1. Locate Equipment Support(s). Position equipment
support(s) on the roof (reference the CAPS submittal
for placement of equipment support(s) in relation
to the unit).
Verify that all
unit supports
are level, shim
if necessary.
Attach
equipment
support to the
roof, remove
metal cover,
flash to wooden
nailer and reinstall cover.
2. Apply Sealant. Apply an appropriate sealant around
the airstream opening to create an air tight seal.
Equipment Support
4. Secure Cooling Module to Unit. Use self-tapping
screws to fasten the cooling module to the base
unit along the top and down both sides. Fasten at
the top through the flanges. To fasten the sides,
the media must be removed. To remove the media,
first remove the access panel on the evaporative
module and disconnect the evaporative pump(s). The
media will now slide out. With the media removed,
you can access the side fastening points inside the
evaporative module. With all the screws in place,
reinstall the media, reconnect the pumps and r
einstall
the access panel.
Securing Evaporative Module
Sealant
3. Set Evaporative Cooling Module.
Use a crane
and a set of spreader bars hooked to the factory lifting
lugs to lift and center the module on the equipment
support(s). The flange on the evaporative cooler should
overlap the flange on the unit.
NOTE
When mounting the evaporative cooler, it is important
that it is level to ensure proper operation and water
drainage.
Placing Evaporative Module
NOTE
The use of all lifting lugs and a set of spreader bars is
mandatory when lifting the evaporative cooling module.
®
Modular Supply Make-Up Air Unit
7
Installation of Electrical Wiring
IMPORTANT
Before connecting power to the unit, read and
understand the following instructions and wiring
diagrams. Complete wiring diagrams are attached on
the inside of the control center door(s).
IMPORTANT
All wiring should be done in accordance with the
latest edition of the National Electric Code ANSI/
NFPA70 and any local codes that may apply. In
Canada, wiring should be done in accordance with
the Canadian Electrical Code.
IMPORTANT
The equipment must be properly grounded. Any
wiring running through the unit in the airstream must
be protected by metal conduit, metal clad cable or
raceways.
CAUTION
If replacement wire is required, it must have a
temperature rating of at least 105°C, except for an
energy cut-off or sensor lead wire which must be
rated to 150°C.
DANGER
High voltage electrical input is needed for this
equipment. This work should be performed by a
qualified electrician.
CAUTION
Any wiring deviations may result in personal injury or
property damage. Manufacturer is not responsible
for any damage to, or failure of the unit caused by
incorrect final wiring.
IMPORTANT
Manufacturer’s standard control voltage is 24VAC.
Control wire resistance should not exceed 0.75ohms
(approximately 285 feet total length for 14gauge
wire; 455 feet total length for 12gauge wire). If the
resistance exceeds 0.75 ohms, an industrial-style
plug-in relay should be wired in place of the remote
switch. The relay must be rated for at least 5 amps
and have a 24 VAC coil. Failure to comply with these
guidelines may cause motor starters to chatter or not
pull in, resulting in contactor failures and/or motor
failures.
1. Determine the Size of the Main Power Lines.
The unit’s nameplate states the voltage and the unit’s
MCA. The main power lines to the unit should be
sized accordingly. The nameplate is located on the
outside of the unit on the control panel side.
2. Provide the Opening(s) for the Electrical
Connection. Electrical openings vary by unit size
and arrangement and are field supplied.
3. Connect the Main Power. Connect the main
power lines to the disconnect switch and main
grounding lug(s). Torque field connections to
20in.-lbs.
4. Wire the Optional Convenience Outlet. The
convenience outlet requires a separate 115 volt
power supply circuit. The circuit must include short
circuit protection which may need to be supplied by
others.
5. Wire the Optional Accessories. Reference the
Ladder Diagram on the inside of the control center
door for correct wiring of the following accessories:
• Blower Switch
• Heat Switch
• Indicating Lights
• Dirty Filter Indicator
• TSCP
• KSCP
NOTE
TSCP has number-to-number wiring.
6. Wire the Optional Evaporative Cooler. Reference
the Ladder Diagram on the inside of the control
center door for correct wiring of the pump and the
optional auto-drain and flush.
NOTE
Large evaporative coolers may require a separate
power supply.
Modular Supply Make-Up Air Unit
8
®
Installation of Electric Heater
(optional)
WARNING
Electrical Shock Hazard! Disconnect all power
sources before doing any work on the unit.
The requirements and practices described below
are based on the National Electric Code (NEC) and
The Space Heating Standard of the Underwriters
Laboratories Inc. (UL). Although UL requirements
are uniform throughout the country, local electrical
codes may deviate from the National Electrical Code.
Therefore, local inspection authorities should be
consulted regarding local requirements.
Electrical Wiring Instructions
1. Use the wiring diagram supplied with the heater as
a guide in correlating field wiring with the heater
internal wiring.
2. All field wiring to the heater must meet the
requirements of the National Electric Code and any
other applicable local or state codes.
3. Wiring to the heater must be rated for 75°C (167°F)
minimum.
4. The fan is interlocked by the factory to the control
circuit so the electric heater will not operate unless
the fan is on.
5. If heater does not have a built-in disconnect switch
or main circuit breaker, install a remote disconnect
(furnished by others) in accordance with the National
Electric Code, Article 424-65.
Effect of Low Voltage on Wattage and
British Thermal Unit (BTU)
The heating elements may be used on voltages
lower than the design voltage of the heater, however,
the wattage and BTU output will be reduced to the
percentages listed in the table below.
Derated Wattage For Low Voltage
% of
Heater
Voltage
Line
Voltage
Heater
Wattage
Heater
Voltage
Line
Voltage
and BTU
4804609220820092
4408419083
2772659212011592
2548411084
24023092
22084
20875
20069
% of
Heater
Wattage
and BTU
®
Modular Supply Make-Up Air Unit
9
Installation Evaporative Cooler Piping
(optional)
Recirculating Evaporative Piping
IMPORTANT
All supply solenoids, valves and all traps must be below
the roof line or be otherwise protected from freezing.
IMPORTANT
The supply line should be of adequate size and
pressure to resupply the amount of water lost due to
bleed-off and evaporation. The drain line should be
the same size or larger than the supply line.
CAUTION
Provisions must be taken to prevent damage to the
evaporative cooling section during freezing conditions.
The sump, drain lines and supply lines must be drained
prior to freezing conditions or an alternate method must
be used to protect the lines and media.
1. Install the Water Supply Line. Supply line opening
requirements vary by unit size and arrangement and
are field supplied. Connect the water supply line to
the float valve through the supply line opening in
the evaporative cooling unit. Install a manual shutoff
valve in the supply line as shown.
2. Install the Drain Line. Connect an unobstructed
drain line to the drain and overflow connections on
the evaporative cooler. A manual shut off valve (by
others) is required for the evaporative cooler drain
line.
A trap should be used to prevent sewer gas from
being drawn into
the unit.
3. Check/Adjust
Water Level.
Check the water
level in the sump
tank. The water
level should be
Drain Trap
6 in. min.
above the pump
intake and below the overflow. Adjust the float as
needed to achieve the proper water level.
Drain Line Valve
(By Others)
Drain Line
Trap
Evaporative Cooling with Recirculating Pump
6 in. min.
Supply
Line
Supply Line
Valve
(By Others)
Overflow
Auto Drain & Fill Evaporative Piping
IMPORTANT
The supply line should be of adequate size and
pressure to resupply the amount of water lost due to
bleed-off and evaporation. The drain line should be
the same size or larger than the supply line.
CAUTION
All solenoids valves and traps must be installed below the
roof to protect the supply water line from freezing. If they
cannot be installed below the roof, an alternative method
must be used to protect the lines from freezing.
IMPORTANT
The supply solenoid (Valve A) is NOT the same as the
drain solenoids (Valve B and Valve C). Make sure to
use the proper solenoid for each location. Check your
local code requirements for proper installation of this
type of system.
Auto Drain & Flush Valves
(When provided by Manufacturer)
Assembly
Number
852178
Part numbers subject to change.
Mfg
Part
Number
461262 8210G2
461263 8262G262
461264 8210G35
1. Install the Water Supply Line. Supply line opening
requirements vary by unit size and arrangement and
are field supplied. Connect the water supply line to
the float valve through the supply line opening in the
evaporative cooling unit. Install the 1/2 in. normally
closed solenoid (Valve A) in the supply line. Install the
1/4 in. normally open solenoid (Valve B) between the
supply line and the drain line. Refer to Auto Drain &
Fill Evaporative Piping drawing on previous page.
2. Install the Drain Line. Connect an unobstructed
drain line to the sump drain overflow connection.
Install the 3/4 in. normally open solenoid (Valve C)
between the
sump drain
connection and
the drain line. A
trap should be
used to prevent
sewer gas from
being drawn into the unit.
3. Check/Adjust Water Level. Check the water level
in the sump tank. The water level should be above
the pump intake and below the overflow. Adjust the
float as needed to achieve the proper water level.
ASCO
Part
Number
Solenoid
SupplyClosed
Supply
Sump
Drain Trap
Type
Line
Drain
Drain
De-Energized
Position
Open
Open
Diameter
1/2 inch
(12.7 mm)
1/4 inch
(6.35 mm)
3/4 inch
(19.05 mm)
6 in. min.
6 in. min.
Qty.
1
1
1
Modular Supply Make-Up Air Unit
10
®
Sump Drain
VALVE C
Sump Drain Solenoid
(Normally Open)
Sump Overflow
Supply
Line
VALVE A
Supply Solenoid
(Normally Closed)
VALVE B
Supply Line Drain Solenoid
(Normally Open)
Trap
Drain Line
Evaporative Cooling with Auto Drain and Fill
®
Modular Supply Make-Up Air Unit
11
Installation of Water WizardTM (optional)
Evaporative Cooling with the Water Wizard™
NOTE
The following instructions are provided for evaporative
coolers equipped with the Water Wizard™ only.
Additional instructions are provided for evaporative
coolers equipped with the auto-drain and fill or bleed-off.
WARNING
Disconnect and lock-out all power and gas before
performing any maintenance or service to the unit.
Failure to do so could result in serious injury or death
and damage to equipment.
Roof
Line
Trap
Sump Drain
To Media
Pressure
Gauge
Manual Supply
Valve
Supply Solenoid
(Normally Closed)
Supply Line Drain Solenoid
(Normally Open)
Water Wizard™ Installation
Factory
Installed
Field
Installed
Water Wizard™ Valves
(When provided by Manufacturer)
Unit
Assembly
Model
MSX -
H12/H22
MSX - H32
(<9000 cfm)
MSX - H32
(≥9000 cfm)
MSX-H35,
H38, H42
Part numbers subject to change.
Number
852370
852371
Mfg.
ASCO
Part
Part No.
No.
461262 8210G2
383086 8210G34
383088 8210G9
383086 8210G34
Solenoid
Type
Supply Closed
Supply
Line
Drain
Supply Closed
Supply
Line
Drain
De-
Energized
Position
Open
Open
Diameter Qty.
(12.7 mm)
(12.7 mm)
(19.05 mm)
(12.7 mm)
1/2 inch
1/2 inch
3/4 inch
1/2 inch
1. Install Normally Closed Supply Line/Solenoid.
Connect the water supply line to the manual supply
valve in the unit. Install the supply solenoid in the
supply line, upstream of the manual supply valve and
below the roof line.
2. Install Normally Open Drain Line/Solenoid.
Connect the drain line to the supply line between the
manual supply valve and the supply solenoid. Install
a drain solenoid in the drain line, below the roof line.
A trap should be installed in the drain line.
3. Wire the Solenoid(s). Wire the supply line solenoid
and drain solenoid as shown on the unit’s wiring
diagram in the control center.
4. Wire the Temperature Sensor. If the evaporative
cooler shipped separate from the unit, the
temperature sensor must be wired. The sensor
1
wire is bundled inside the discharge end of the
evaporative cooler. Wire the sensor wire to terminals
as shown on the unit’s wiring diagram.
1
The Water Wizard™ start-up must be completed for
1
proper performance.
1
NOTE
NOTE
Solenoid(s) may be provided by Manufacturer (if
ordered) or by others.
CAUTION
Any wiring deviations may result in personal injury or
property damage. Manufacturer is not responsible
for any damage to, or failure of the unit caused by
incorrect final wiring.
Modular Supply Make-Up Air Unit
12
®
Installation of Direct Expansion (DX) Coil
Piping (optional)
Liquid Line
Equalizer Line
Suction Header
Distributor
Coil
IMPORTANT
Guidelines for the installation of direct expansion
cooling coils have been provided to insure proper
performance and longevity of the coils. These are
general guidelines that may have to be tailored
to meet the specific requirements of any one job.
As always, a qualified party or individual should
perform the installation and maintenance of any coil.
Protective equipment such as safety glasses, steel
toe boots and gloves are recommended during the
installation and maintenance of the coil.
IMPORTANT
All field brazing and welding should be performed
using high quality materials and an inert gas purge
(such as nitrogen) to reduce oxidation of the internal
surface of the coil.
IMPORTANT
All field piping must be self-supporting and flexible
enough to allow for the thermal expansion of the coil.
1. Locate the Distributor(s) by Removing the
Distributor Access Panel
Nozzle
Thermal
Expansion
Valve (by others)
Hot Gas Bypass
(by others)
Suction Line
Remote Sensing Bulb
Straps
Suction Connection
Installation with Hot Gas Bypass
NOTE
If a hot gas bypass kit was provided by others, refer to
the manufacturer’s instructions.
Liquid Line
Thermal
Expansion
Valve (by others)
Suction Line
Remote Sensing Bulb
Equalizer Line
Nozzle
Suction Header
Distributor
Straps
General Installation
Coil
Suction Connection
Distributor Access PanelDistributor Location
2. Verify Nozzle Placement. Inspect the refrigerant
distributor and verify
that the nozzle is in
place. The nozzle
is generally held in
place by a retaining
ring or is an integral
part of
the distributor itself.
Retainer
Ring
Nozzle Distributor
Nozzle Placement
3. Install Suction Line. Install suction line(s) from the
compressor to the suction connection(s) which are
stubbed through the side of the cabinet.
4. Install the Liquid Line and Thermal Expansion
Valve (TEV) (by others). Liquid line openings vary
by coil size and circuiting and are field supplied.
Follow the TEV recommendations for installation to
avoid damaging the valve.
5. Mount the Remote Sensing Bulb
(by others). The expansion valve’s remote sensing
bulb should be securely strapped to the horizontal
run of the suction line at the 3 or 9 o’clock position
and insulated.
6. Check Coil Piping for Leaks. Pressurize the coil to
100 psig with dry nitrogen or other suitable gas. The
coil should be left pressurized for a minimum of 10
minutes. If the coil holds the pressure, the hook-up
can be considered leak free. If the pressure drops by
5 psig or less, re-pressurize the coil and wait another
10 minutes. If the pressure drops again, there is likely
one or more small leaks which should be located and
repaired. Pressure losses greater than 5 psig indicate
a large leak that should be isolated and repaired.
7. Evacuate and Charge the Coil. Use a vacuum
pump to evacuate the coil and any interconnecting
piping that has been open to the atmosphere.
Measure the vacuum in the piping using a micron
gauge located as far from the pump as possible.
Evacuate the coil to 500 microns or less, and then
close the valve between the pump and the system.
If the vacuum holds to 500 microns or less for
one minute, the system is ready to be charged or
refrigerant in another portion of the system can be
opened to the coil. A steady rise in microns would
indicate that moisture is still present and that the coil
should be further vacuumed until the moisture has
been removed.
®
Modular Supply Make-Up Air Unit
13
8. Install the Drain Line.
Connect an unobstructed
drain line to the drain pan. A trap should be used to
prevent sewer gas from being drawn into the unit.
6 in. min.
6 in. min.
Drain Trap
IMPORTANT
All traps must be installed below the roof line or be
otherwise protected from freezing.
NOTE
Failure to obtain a high vacuum indicates a great
deal of moisture or a small leak. Break the vacuum
with a charge of dry nitrogen or other suitable gas
and recheck for leaks. If no leaks are found, continue
vacuuming the coil until the desired vacuum is
reached.
Modular Supply Make-Up Air Unit
14
®
Installation of Chilled Water Coil Piping
Hot Return
Connection
Cold Supply
Connection
Entering AirLeaving Air
(optional)
IMPORTANT
Guidelines for the installation of the cooling coil have
been provided to insure proper performance of the
coils and their longevity. These are general guidelines
that may have to be tailored to meet the specific
requirements of any one job. As always, a qualified
party or individual should perform the installation and
maintenance of the coil. Protective equipment such
as safety glasses, steel toe boots and gloves are
recommended during the installation and maintenance
of the coil.
When installing couplings, do not apply undue stress
to the connection. Use a backup pipe wrench to avoid
breaking the weld between the coil connection and
the header.
All field piping must be self-supporting. System piping
should be flexible enough to allow for the thermal
expansion and contraction of the coil.
1. Verify Coil Hand Designation. Check the coil
hand designation to ensure that it matches the
system. Coils are
generally plumbed with
the supply connection
located on the bottom
of the leaving air-side of
the coil and the return
connection at the top
of the entering air-side of the coil. This arrangement
provides a counter flow heat exchanger and positive
coil drainage.
2. Check the Coil for Leaks. Pressurize the coil to
100 psig with dry nitrogen or other suitable gas. The
coil should be left pressurized for a minimum of 10
minutes. If the coil holds the pressure, the hook-up
can be considered leak free. If the pressure drops by
5 psig or less, re-pressurize the coil and wait another
10 minutes. If the pressure drops again there is likely
one or more small leaks which should be located and
repaired. Pressure losses greater than 5 psig indicate
a large leak that should be isolated and repaired.
3. Connect the Supply and Return Lines. Connect
the supply and return lines as shown above.
4. Install the Drain Line. Connect an unobstructed
drain line to the drain
pan. A trap should be
installed to prevent
sewer gas from being
drawn into the unit.
Drain
Trap
6 in. min.
6 in. min.
Installation of Building Pressure Control
(optional)
1. Mount Pressure Tap. Using the factory provided
bracket, mount the pressure tap to the outside of the
unit. Choose a location out of the prevailing winds
and away from
supply or exhaust
fans to assure
accurate readings.
2. Run Pressure
Tap Lines. Run a
pressure tap line
from the pressure
tap on the outside of the unit to the low pressure tap
on the back of the photohelic gauge. Run a second
pressure tap line from the high pressure tap on the
back of the photohelic gauge to the space. Fifty feet
of tubing is supplied with the unit.
Factory
Wiring
Low Pressure
Tap
to Outside
Connections for Photohelic Gauge
3. Set the Building Pressure. The pressure gauge
is used to set the desired building pressure. The
pressure is set by adjusting the knobs for the upper
and lower pressure limits. Typical settings are 0.0
inch wc for the lower and 0.10 inch wc for the upper
pressure setting.
Pressure Indicating
Needle
Pressure Setting Knobs
Typical Photohelic Gauge Settings
Pressure Setting
Needles
High Pressure
Tap
to Space
All traps must be installed below the roof line or be
otherwise protected from freezing.
®
IMPORTANT
Modular Supply Make-Up Air Unit
15
Start-Up Checklist
SPECIAL TOOLS REQUIRED
• Voltage Meter (with wire probes)
• Amperage Meter
• Micro Amp Meter
• Tachometer
• Thermometer
• Incline manometer or equivalent
Start-Up Checklist
Unit Model Number _______________________________
Unit Serial Number _______________________________
Start-Up Date _______________________________
Start-Up Personnel Name __________________________
Start-Up Company _______________________________
Phone Number _______________________________
Pre Start-Up Checklist – check boxes as items
are completed.
Check tightness of all factory wiring connectionsVerify control wiring wire gaugeHand-rotate blower to verify free rotationVerify supply voltage to the main disconnectVerify remote controls wiring
Electric Heater Start-Up section for further detail.
Check line voltage L1-L2 __________
L2-L3 __________
L1-L3 __________
Set the unit’s operating temperature
________ °F
Start-Up Evaporative Cooler (optional) – refer
to Evaporative Cooler Start-Up section for further
detail.
Check media orientation
Check for proper water flow to distribution
headers
Check for distribution header orientation to
prevent water spillage
Modular Supply Make-Up Air Unit
16
®
Start-Up - Blower
Pre Start-Up Check
Rotate the fan wheel by hand and make sure no parts
are rubbing. Check the V-belt drive for proper alignment
and tension (a guide for proper belt tension and
alignment is provided in the Belt Maintenance section).
Check fasteners, set screws and locking collars on the
fan, bearings, drive, motor base, and accessories for
tightness.
WARNING
Disconnect and lock-out all power and gas before
performing any maintenance or service to the unit.
Failure to due so could result in serious injury or death
and damage to equipment.
WARNING
Check the housing, blower, and ductwork for any
foreign objects before running the blower.
1. Check the Voltage. Before starting the unit,
compare the supplied voltage, hertz, and phase with
the unit and motor’s nameplate information.
2. Check the Blower Rotation. Open the blower
access door and run the
blower momentarily to
determine the rotation.
Arrows are placed on the
blower scroll to indicate the
proper direction or reference
the example shown to the
right.
NOTE
To reverse the rotation on three phase units,
disconnect and lock-out the power, then interchange
any two power leads.
NOTE
To reverse the rotation on single phase units,
disconnect and lock-out the power, then rewire the
motor per the manufacturer’s instructions.
IMPORTANT
If the blower is rotating in the wrong direction, the unit
will move some air, but will not perform as designed.
Be sure to perform a visual inspection to guarantee
the correct blower rotation.
n
o
i
t
a
t
o
R
Blower
Housing
Blower Rotation
3. Check for Vibration. Check for unusual noise,
vibration or overheating of the bearings. Reference
the Troubleshooting section for corrective actions.
IMPORTANT
Excessive vibration may be experienced during
the initial start-up. Left unchecked, it can cause a
multitude of problems including structural and/or
component failure.
IMPORTANT
Generally, fan vibration and noise is transmitted
to other parts of the building by the ductwork. To
minimize this undesirable effect, the use of heavy
canvas duct connectors is recommended.
4. Motor Check. Measure the motor’s voltage, amps
and RPM. Compare to the specifications. Motor
amps can be reduced by lowering the motor RPM or
increasing system static pressure.
IMPORTANT
Additional starters and overloads may be provided in
the make-up air control center for optional exhaust
blowers. Any additional overloads must be checked
for proper voltage, amps and RPMs.
5. Air Volume Measurement & Check. Measure the
unit’s air volume (cfm) and compare it with it’s rated air
volume. If the measured air volume is off, adjust the
fan’s RPM by changing/adjusting the drive.
NOTE
The most accurate way to measure the air volume is
by using a pitot traverse method downstream of the
blower. Other methods can be used but should be
proven and accurate.
IMPORTANT
Changing the air volume can significantly increase
the motor’s amps. If the air volume is changed,
the motor’s amps must be checked to prevent
overloading the motor.
NOTE
To ensure accuracy, the dampers are to be open when
measuring the air volume.
6. Set-Up Optional Components. Adjust the settings
on the optional components. See the Control Center
Layout in the Reference section for location of
optional components.
• Heating Inlet Air Sensor
Typical setting: 60-70°F (15-21°C)
• Cooling Inlet Air Sensor
Typical setting: 75°F (24°C)
• Building Freeze Protection
Typical setting: 5 minutes; 45°F (7°C)
• Dirty Filter Gauge
Typical setting: Settings vary greatly for each unit.
®
Modular Supply Make-Up Air Unit
17
Start-Up - Electric Heater (optional)
Pre Start-Up Check
Check all electrical connections. Tighten any loose
connection to all components including contactors,
heating elements and main power lugs.
WARNING
Disconnect and lock-out all power before performing
any maintenance or service to the unit. Failure to due
so could result in serious injury or death and damage
to equipment.
1. Check the Voltage. Before starting the heater,
compare the supplied voltage, hertz, and phase with
the heater’s nameplate information.
2. Airflow Interlock. With the supply fan on, verify the
electric heater’s airflow interlock (DDS) is made.
3. Set the Unit’s Operating Temperature. Set the
operating temperature by adjusting the discharge
temperature selector. Typical settings are 65-70°F
(18-21°C).
NOTE
If the heater is equipped with an optional inlet air
sensor the heater will not energize unless the outdoor
air temperature is less than the inlet air sensor’s set
point.
Modular Supply Make-Up Air Unit
18
®
Optional Economizer
The following economizer sequences will function
to modulate the outdoor and return air dampers to
determine and maximize the availability of free cooling.
Although the Honeywell economizer controller contains
numerous set points, the adjustment of only a few is
necessary to ensure optimal performance.
Sequences
EC-1 Outdoor Air Temperature Reference
This mode compares the outdoor air temperature to the
dry bulb temperature set point (DRYBLB SET). Once
the outdoor air temperature is less than DRYBLB SET,
the unit will modulate the position of the dampers to
maintain a predetermined mixed air temperature (MAT
SET).
EC-2 Outdoor Air Enthalpy Reference
This mode compares the outdoor air enthalpy to a
preset enthalpy curve. When the outdoor air conditions
are within this curve, the dampers will modulate to
maintain a mixed air temperature (MAT SET).
EC-3 Differential Temperature Reference
This mode compares the outdoor air temperature and
the return air temperatures. If the outdoor air is cooler
than the return, the dampers will modulate to maintain a
preset mixed air temperature (MAT SET).
EC-4 Differential Enthalpy Reference
This mode compares the outdoor air enthalpy and the
return air enthalpy. If the outdoor air enthalpy
Relevant Set points
1.MAT SET - The mixed air temperature set point.
The control will modulate the damper to maintain
temperature as best as it can (Set point menu,
Default 53°F )
2.LOW T LOCK - The set point for the low temperature
mechanical cooling lockout. (Set point menu, Default
32°F)
3. DRYBLB SET - The outdoor air set point to call for
economizer. (Set point menu, Default 63°F)
4.MIN POS - The minimum signal voltage sent to
the dampers. This must be set to 2 VDC. (Set point
menu, Default 2.8 VDC)
5.AUX1 O – The controllers operating sequence
structure. (Set point menu, Default ‘None’)
6.ERV OAT SP - The set point for low temperature
economizer lockout. This is the low temperature set
point when AUX1 O is set to ERV. (Set point menu,
Default 32°F)
7. STG3 DLY - Time delay after second cooling stage is
enabled (Advanced setup menu, Default 2 hrs.)
Using the Keypad with Settings and
Parameters
To use the keypad when working with Set points,
System and Advanced Settings, Checkout tests, and
Alarms:
1. Navigate to the desired menu.
2. Press
currently displayed menu.
3. Use the
parameter.
4. Press (enter) to display the value of the currently
displayed item.
5. Press the
displayed parameter value.a
6. Press the
displayed parameter value.
7. Press (enter) to accept the displayed value and
store it in non-volatile RAM.
8. CHANGE STORED displays.
9. Press
parameter.
10. Press (escape) to return to the current menu
parameter.
a
When values are displayed, pressing and holding the
or button causes the display to automatically
increment.
(enter) to display the first item in the
and buttons to scroll to the desired
button to increase (change) the
button to increase (change) the
a
(enter) to return the current menu
Modulate Dampers
1. Navigate to the Checkout menu and press (Enter).
2. The cooling should turn off
3. Navigate to Damper Open and press (enter) twice to
run the test.
4. Voltage between terminals ACT 2-10 and ACT COM
should be 10 VDC. This will open the outdoor air
damper and close the return air damper
5. Press (escape), navigate to Damper Close and press
(enter) twice to run the test.
6. Voltage between terminal ACT 2-10 and ACT COM
should be 2 VDC. This will close the outdoor air
damper and open the return air damper.
®
Modular Supply Make-Up Air Unit
19
Start-Up - Evaporative Cooling
r
Recirculating (optional)
1. Check the Installation. The media may have been
removed during
installation, so
its orientation
should be
double
checked. The
Entering Air
media should
be installed with
the steeper flute
angle sloping
down towards
Media Orientation
the entering air side.
Verify that the stainless steel caps and distribution
headers are in place. The headers should be located
over the media towards the entering air side. The
caps should be placed over the headers.
2. Check the Pump Filter. Check that the pump filter
is around the pump inlet.
3. Fill the Sump and Adjust the Float. Turn on the
water supply and allow the sump tank to fill. Adjust
the float valve to shut-off the water supply when the
sump is filled to within 1 inch of the bottom of the
overflow.
4. Break-In the Media. Open the bleed-off valve
completely and saturate the media with the blower(s)
off for no less than 20minutes.
45º
Leaving Ai
15º
air sensor should be installed in an area that is
shaded from direct sunlight so the outside air sensor
probe will detect an accurate air temperature.
Set the Timer Scale and
Settings dials:
• T1 timer setting set to 10
and timer scale set to 1d
for 1 day of operation
• T2 timer setting set to 10
and the timer scale set
to 10m for 10 minutes of
drain time
Timer
Scale
Timer
Settings
Timer
Scale
8. Put the Unit into Service.
Remove the jumper, and
energize the blower(s). Verify
proper operation.
IMPORTANT
Check the media for minerals after two weeks of
service and adjust the bleed-off rate accordingly.
Bleed-Off
Valve
Overflow
Pump
Filter
Supply
Connection
Float
Valve
Threaded Float
Adjustment
T1
T2
NOTE
A jumper will need to be installed in the control center
to power the evaporative pumps with the blower(s)
off. Reference the unit’s ladder diagram to determine
proper terminals.
5. Check the Flow Rate. The pumps should provide
enough water to saturate the media in 45 to 60
seconds. Consult the factory, if adequate flow is not
achieved.
6. Adjust the Water Bleed-Off Rate. The water
bleed-off rate is dependent on the water’s mineral
content. The bleed-off should be adjusted based
on the media’s mineral deposits after two weeks of
service.
7. Set the Optional Auto Drain and Fill. This system
will automatically drain the sump tank and fill it
with fresh water at the field-adjustable intervals,
typically once every 24 hours. This flushes mineral
build-up and debris from the tank to promote low
maintenance and increase media pad life.
In addition, the system will protect the evaporative
cooler from freezing by draining the sump tank and
supply line when the outside temperatures fall below
the set point of the outside air sensor. Typically, this
is set at 45º to 50º F. The auto drain and fill outdoor
Evaporative Cooler Set-Up
Modular Supply Make-Up Air Unit
20
®
Start-Up - Water Wizard™ (optional)
L1L2L3
Function Key
Enter Key
Water Wizard™ User Interface
Key Function Description
1. Open the Solenoid. Confirm that the manual
water supply valve is closed. Press and hold the
Function Button for one second. L3 will begin
blinking (short on, long off), indicating that Flow
Test Mode is active and the supply solenoid is
open.
2. Set the Water Pressure. With the solenoid open,
set the supply water pressure to the correct setting
(see table below). Use the manual supply valve to
adjust the supply pressure. A pressure gauge is
provided between the manual supply valve and the
media.
Up Key
Down Key
5. Check Media. Start the cooling cycle and check
the media after one hour of operation. If the media
is continuously dry or if too much water is draining
from the sump tank, refer to Troubleshooting, Water
Wizard™.
NOTE
Steps 6 through 8 are provided to adjust the minimum
cooling temperature. The minimum cooling is preset
to the factory recommended 75°F (24°C). Only adjust
if needed.
NOTE
The inlet air sensor function overrides and shuts down
the evaporative cooler if the outside temperature falls
below the minimum cooling temperature.
6. Enter Program Mode. Press and hold the Enter
Key
for three seconds. The display will read
“Pro” when Program Mode is active.
WARNING
Opening the manual supply valve will allow water to
pass to the media. Be sure the sump is safely draining
before opening the manual supply valve.
NOTE
The manual supply valve ships closed and must be
adjusted for proper performance.
Recommended Water Pressure Chart
Housing
Size
Media Width
(inches)
Water Pressure
(in. wc)
MSX-H123020
3
43
MSX-H22
MSX-H32
⁄436
6061
6672
96*42
MSX-H35120*61
MSX-H38180*37
MSX-H42216*51
*Multiple media sections. Values represent total media width.
NOTE
The recommended water pressure is based on media
width. Refer to the table provided for proper water
pressure settings.
Program Display
7. Adjust the Minimum Cooling Temperature.
While in the Program Menu, use the Up and Down
Keys to navigate the Menu Options until “toF” is
displayed. Press the Enter Key
to access the
selected Menu Option setting.
Minimum Cooling
Temperature Display
Use the Up and Down Keys to adjust the Minimum
Cooling Temperature as needed. Press the Enter
Key
to save the Minimum Cooling Temperature
setting and return to the Program Menu.
NOTE
The enter key
must be pressed to save the new
minimum cooling temperature.
3. Break-in Media. Leave the supply solenoid open
to saturate and break-in media for 20 minutes with
the blower off.
4. Close Solenoid. With the pressure set, press the
Function Key
for one second to deactivate
Flow Test Mode and allow the supply solenoid to
close.
®
Modular Supply Make-Up Air Unit
21
8. Exit Program Mode. After 15 seconds of idle time
the controller will exit Program Mode.
NOTE
The freeze temperature is preset to the factory
recommended 45°F. Steps 9-11 should only be
completed if the freeze temperature needs adjustment.
NOTE
The freeze temperature is the temperature at which the
supply solenoid closes and the drain solenoid opens to
drain the supply line, preventing possible freeze damage.
A drain solenoid is required for this option.
9. Enter Program Mode. Press and hold the Enter
Key
for three seconds. The display will read
“Pro” when Program Mode is active.
Program Display
10. Adjust the Freeze Temperature. While in
Program Mode, use the Up and Down Keys to
navigate through the Menu Options until “Frt” is
displayed. Press the Enter Key
to access the
selected Menu Option setting.
Freeze Temperature Display
Use the Up and Down Keys to adjust the Freeze
Temperature setting as needed. Press the Enter
Key
to set the Freeze Temperature and return
to the Program Menu.
NOTE
The enter key
must be pressed to save the new
freeze temperature.
11. Exit Program Mode. After 15 seconds of idle time
the controller will exit Program Mode.
Modular Supply Make-Up Air Unit
22
®
Check Operation - VAV Units
(optional)
NOTE
Blower Start-Up, Steps 1-5 should be performed
before the blower is run.
NOTE
For maintenance issues associated with variable
frequency drives, consult the drive’s manual supplied
with the unit. The drives are programmed at the
factory and should not need any adjustment during
installation and start-up. For kitchen applications, the
drive may be located in the kitchen or in the unit.
Variable Volume Operation
The variable volume option is recommended when
a building’s exhaust volume may vary. This option
enables the make-up air volume to track with the
exhaust volume, providing only the amount of makeup air required. Control strategies include 2-speed and
modulating blowers. Before the unit is left in service, the
variable volume control system should be tested.
2-Speed
A variable frequency drive (VFD) is used to control
air volumes. The VFD can be switched to low or high
speed from a remote control panel. Turn the fan speed
switch on the remote control panel to each position and
confirm that the fan speed adjusts accordingly.
Modulating
Potentiometer Control — a variable frequency drive
is controlled by input from a remote
speed selector (potentiometer). This
unit allows easy manual adjustment
of make-up air volumes. To test
potentiometer operation, turn the
potentiometer to the two extremes.
With variable volume, make sure the
fan goes to maximum and minimum
speed.
When the potentiometer is at 0, the
fan speed will be at its minimum.
When the potentiometer is at 100, the
fan will be at its maximum speed.
Potentiometer
EXHAUST
(OPTIONAL)
SUPPLY
HEAT
70
75
65
80
60
85
55
90
Control
BLOWER
MAIN VALVES
DIRTY FILTERS
(OPTIONAL)
GREENHECK
®
Building Pressure Control —
a variable frequency drive is
controlled according to input from
EXHAUST
SUPPLY
HEAT
(OPTIONAL)
BLOWER
MAIN VALVES
a pressure sensing device.
Turn both knobs to the upper
most pressure setting. You may
DIRTY FILTERS
70
75
65
80
(OPTIONAL)
60
85
55
90
have to remove the outdoor
pressure tap tubing. VAV systems
PHOTOHELIC
should go to maximum speed. Set
both knobs at the lowest setting
and the VAV systems should go to
minimum speed.
Pressure Control
Building
GREENHECK
®
Reset the correct pressure limits
before starting the unit.
This picture depicts a typical
Pressure Indicating
Needle
Pressure Setting
Needles
photohelic setting. Typical
settings are 0.0 inch wc for
the lower pressure setting
and 0.10 inch wc for the
upper pressure setting. The
needle indicates a negative
building pressure. During
correct operation, the
indicating needle will remain
between or near the setting
needles.
Pressure Setting Knobs
Photohelic Gauge
External Signal — a variable frequency drive is
controlled according to input from an external 2-10 VDC
or 4-20 mA signal (by others).
A 2 VDC or 4 mA signal will send the blower to low
speed. The blower will go to maximum speed with a
10VDC or 20 mA signal.
Variable Kitchen Control — a variable frequency
drive is controlled by input from a remote speed control.
This unit allows automatic adjustment of make-up air
volumes based on varying cooking loads.
®
Modular Supply Make-Up Air Unit
23
Check Operation - Recirculating
Units (optional)
NOTE
Blower Start-Up, steps 1-5 should be performed
before the blower is run.
Recirculation Operation
The recirculation operation option is recommended
when the ventilation equipment provides the primary
source of heating for the space. Recirculation can
vary from 100% return air to 100% outside air. Control
strategies include 2-position and modulating dampers.
Before the unit is left in service, the recirculation control
system should be tested.
2-Position Damper
A 2-position spring return actuator
is used to control the return air
amounts. The damper moves from
open to closed. If power is cut to
the unit, the outdoor air damper will
fail to close.
Turn the recirculating switch on
the remote control panel to each
position and confirm that the return
air damper adjusts accordingly. The damper actuator
may take a few minutes to open or close.
Modulating
Potentiometer Control — a
modulating spring return actuator
is used to control the return air
amounts. The return air damper
modulates from fully open to fully
closed based on a signal from a
remote potentiometer.
To test potentiometer operation,
turn the potentiometer to the two
extremes. Confirm that the return
air damper fully opens and fully
closes. When the potentiometer is
at 0, the return air damper will open.
When the potentiometer is at 100, the return air damper
will close. The damper actuator may take a few minutes
to open or close.
EXHAUST
SUPPL Y
HEA T
RECIRCULA TION
75
80
85
90
(OPTIONAL)
70
65
55
BLOWER
MAIN V AL VES
DIRTY FIL TERS
(OPTIONAL)
60
GREENHECK
®
2-Position
Damper Control
BLOWER
EXHAUST
(OPTIONAL)
SUPPLY
MAIN VALVES
HEAT
DIRTY FILTERS
70
75
65
80
(OPTIONAL)
60
85
55
90
GREENHECK
®
Potentiometer
Control
Building Pressure Control — a modulating spring
return actuator is used to control the return air amounts.
The return air damper modulates from fully open to fully
closed based on a signal from a
remote pressure sensing device.
Turn both knobs to the upper most
EXHAUST
SUPPLY
BLOWER
(OPTIONAL)
MAIN VALVES
HEAT
pressure setting. You may have
to remove the outdoor pressure
tap tubing. The return air damper
DIRTY FILTERS
70
75
65
80
(OPTIONAL)
60
85
55
90
should close.
Set both knobs at the lowest
PHOTOHELIC
setting and the damper should
GREENHECK
open. It may take one to two
minutes for the damper to reach
the desired position.
Pressure Control
®
Building
Reset the correct pressure limits before starting the unit.
This picture shows a typical
Pressure Indicating
Needle
Pressure Setting
Needles
photohelic setting. Typical
settings are 0.0 inch wc
for the lower and 0.10 inch
wc for the upper pressure
setting. The needle in this
photo indicates a negative
building pressure. During
correct operation, the
indicating needle will remain
between or near the setting
needles.
Pressure Setting Knobs
Photohelic Gauge
External Signal — a modulating spring return actuator
is used to control the return air amounts. Return air
damper modulates from fully open to fully closed based
on an external 2-10 VDC or 4-20 mA signal (by others).
The return air damper will close with a 10 VDC or 20mA
signal. The return air damper should open with a 2VDC
or 4mA signal. The damper actuator may take a few
minutes to open or close.
Modular Supply Make-Up Air Unit
24
®
Operation - Electrical
Electrical Sequence
1. Exhaust Fan Contact (S1) Closed (optional)
• Power passes through N.C. contact on exhaust
fan overload (ST2 OL), which is closed if exhaust
fan (M2) has not overloaded
• Power passes to exhaust fan starter (ST2)
• N.O. contact on exhaust fan starter (ST2) is
energized and closed
• Power passes to exhaust fan
• Exhaust fan (M2) starts
2. Supply Fan Contact (S2) Closed
• Power passes through N.C. field supplied fire
contact (FSC)
• Power passes through optional N.O. contact on
exhaust fan starter (ST2), which is closed when
the optional exhaust starter (ST2) is activated
• Power passes through N.C. contact on supply
starter overload (ST1 OL), which is closed if the
supply fan has not overloaded
• Power passes through N.C. contact on optional
freeze protection timer (RT4) which remains
closed if the temperature has remained above the
set point
• Power passes to and energizes optional inlet
damper (D1), which opens
• Power passes through optional N.O. damper limit
switch (DL1), which is energized and closed when
the optional inlet damper is open. It may take
several minutes for the damper to fully open and
for the damper limit switch to close
• Power passes to and energizes fan relay (RF)
• Power passes through N.O. contact on fan relay
(RF), which closes when the fan relay (RF) is
energized
• Power passes to and energizes supply fan starter
(ST1)
• N.O. contact on supply fan starter (ST1) is
energized and closed
• Supply fan (M1) starts
3. Electric Heat Contact (S4) Closed (optional)
• Power passes through N.O. contact on fan relay
(RF), which is energized and closed
• Power passes through N.C. contact on optional
inlet air sensor (TS4), which is closed if the inlet
air temperature is below the set point
• Power passes to and energizes heat relay (RH)
• Power passes through N.O. contact on heat relay
(RH), which closes when the heat relay (RH) is
energized
• Power passes through N.O. contact on pressure
differential switch (PDS), which closes when
proper airflow is achieved
• Power passes through N.C. automatic and
manual reset temperature cutouts (A and M),
which remain closed if the maximum temperature
has not been reached
• Power passes to and energizes operating
contactor relay (C1)
• Power passes through N.O. contacts on
operating contactor (C1), which is closed
• Electric heater modulates/stages to maintain
temperature set point
• N.O. contact on fan relay (RF) is energized and
closed
• Power passes through N.O. contact on optional
inlet air sensor (TS4), which is energized and
closed if the inlet air temperature is above the set
point
• Power passes to and energizes cool relay (RC)
• N.O. contact on cool relay (RC) is energized and
closed
• Power passes to optional evaporative cooling
pump (P1)
*If DX or chilled water coils are used rather than an evaporative cooler,
the cooling sequence of operation will depend on the coil controls.
Cooling coil controls are supplied by others.
®
Modular Supply Make-Up Air Unit
25
Operation - Water Wizard™ (optional)
L1L2L3
Function Key
Enter Key
Up Key
Down Key
Dry Bulb Temperature
The dry bulb temperature is visible on the home screen.
If a number is not visible, wait 15 seconds and use the
Up and Down Keys until a number is displayed.
Wet Bulb Temperature
To view the Wet Bulb Temperature, simultaneously press
and hold the Up and Down Keys.
Water Wizard™ User Interface
Key Function Description
Drain Mode
Drain Mode locks open the drain solenoid and drains
the supply line between the supply solenoid and
the media. To activate Drain Mode simultaneously,
press the Function and Enter Keys (L2 will light). To
deactivate Drain Mode and unlock the drain solenoid,
simultaneously press the Function and Enter Keys
again.
Flow Test Mode
Activating Flow Test Mode opens the supply solenoid
and allows water to pass to the manual supply valve. To
activate Flow Test Mode, press and hold the Function
Key for one second (L3 will flash). To deactivate Flow
Test Mode and allow the supply solenoid to close, press
and hold the Function Key again for one second.
CAUTION
The sump drain line must be clear and draining to a
safe location before using Flow Test Mode.
CAUTION
Be aware of the water level in the sump tank at all
times when using the Flow Test Mode.
Indicating Lights
Three indicating lights are located across the top of the
display to indicate the status of the Water Wizard™.
Light Status
Indicating
Light
L1
L2
L3
OnOff
Call for
cooling
Drain
solenoid
open
CoolingonCooling
No call
for
cooling
Drain
solenoid
closed
off
Blinking
(Long on,
Short Off)
Call for
cooling.
Outdoor
temperature
lockout.
N/A
Supply
solenoid
locked closed
Blinking
(Short on,
Long Off)
N/A
Supply
solenoid
open.
(Drain
solenoid
closed).
Flow test
mode active
Program Mode
Program Mode allows the user to view the Program
Menu and edit the factory default settings. To access
Program Mode and view the Program Menu press and
hold the Enter key for three seconds. While viewing the
Program Menu press the Up and Down keys to scroll
through the Menu Options. To view the setting of the
selected Menu Option, press the Enter key. To edit the
setting, press the Up or Down key while viewing the
setting. To save the setting and return to the Program
Menu, press the Enter key. To return to the Program
Menu without saving the change, wait 10 seconds. To
exit Program Mode from the Program Menu, wait 10
seconds.
WARNING
Changing the default settings will significantly affect
performance. Only change a setting after reading and
understanding this entire manual.
WARNING
The Enter key must be pressed to save any changes
made to a setting.
Modular Supply Make-Up Air Unit
26
®
Troubleshooting
Blower Does Not Operate
Proper supply power at
main disconnect
Yes
24 VAC between
terminals R and X?
Yes
24 VAC between
terminals G and X?
Yes
24 VAC across
terminals 3 and X?
Yes
24 VAC across
terminals 4 and X?
No
No
No
No
No
Check main voltage
(See Blower Start-Up Step #1)
Main Disconnect (DS1) Off
(Turn Main Disconnect DS1 On)
Primary fuses blown
(Replace fuses)
Main Transformer (TR1) Defective
(Replace transformer)
Supply Switch (S2) Off
(Turn Supply Switch (S2) On)
Fire System Contact (FSC) tripped/not installed
(Correct/Replace)
Supply Fan Overload (ST1 OL) tripped
(Reset and check motor amps. Reference Blower Start-Up #4)
Optional Exhaust Fan Interlocks (ST2-ST5) open
(Correct/Replace)
Yes
24 VAC across A2 and A1 on
supply contactor (ST1)
Yes
(Optional) Freeze Protection (RT4) Tripped
(Reset)
No
(Optional) Damper Limit Switch (DL1) holding
(Wait for actuator to open fully or adjust limit switch)
(Optional) Damper Limit Switch jumper missing
(Install jumper. Reference the unit’s ladder diagram for terminals)
Fan Relay (RF) is not energized
(Check for loose connection) (Repair or replace relay)
Broken fan belt
(Replace. Reference Maintenance section)
Defective motor or capacitor
(Repair/Replace)
Blown motor fuse
(Replace)
One or more legs of 3 phase is out
(Restore missing legs)
At this time the supply contactor (ST1) should pull in,
passing power to the supply motor
and the blower should start.
®
Modular Supply Make-Up Air Unit
27
Troubleshooting
Motor Overamps
Air volume too high?
No
Actual static pressure
lower than design?
No
Blower rotation correct?
Yes
Motor voltage correct?
Yes
Motor horsepower too low?
No
Yes
Adjust drives or increase external
static pressure as needed.
(Reference Blower Start-Up Step #5)
Yes
Adjust drives to reduce blower RPM.
(Reference Blower Start-Up Step #5)
No
Reverse blower rotation.
(Reference Blower Start-Up Step #2)
No
Provide proper power supply.
(Reference Blower Start-Up Step #1)
Yes
Resize motor.
Shorted windings in motor?
Yes
Everything is working
properly, consult factory.
Yes
Replace motor.
Modular Supply Make-Up Air Unit
28
®
Troubleshooting
Insufficient Airflow
Damper(s) not fully opened?
No
System static losses too high?
No
Blower speed too low?
No
Filters dirty or clogged
No
Leaks in ductwork
No
Yes
Adjust damper linkage(s), or replace faulty actuator(s).
(Damper actuators may take a few minutes to open)
Yes
Reduce losses by improving ductwork.
Yes
Adjust drives as needed.
(Reference Blower Start-Up Step #5)
Yes
Clean or replace filters.
(Reference Filter Maintenance in the Maintenance section).
Yes
Repair leaks.
Belt slipping
Yes
Everything is working properly,
consult factory.
Too Much Airflow
Blower speed too high?
No
Filters not in place?
No
Insufficient external static
pressure?
No
Yes
Replace or tighten belt.
(Reference V-Belt Maintenance in the Maintenance section)
Yes
Adjust drives as needed.
(Reference Blower Start-Up Step #5)
Yes
Install filters.
Yes
Everything is working properly,
consult factory.
®
Increase external static pressure.
Modular Supply Make-Up Air Unit
29
Troubleshooting
Excessive Noise or Vibration
Belts worn or loose?
No
Sheaves aligned?
Yes
Wheel unbalanced?
No
Bearings worn or need
lubrication?
No
Wheel rubbing on inlet?
Yes
Replace worn belts or tighten loose belts.
(Reference V-Belt Drive Maintenance in the Maintenance section)
No
Align sheaves.
(Reference V-Belt Drive Maintenance in the Maintenance section)
Yes
Clean and/or balance wheel(s).
Yes
Replace worn bearings or lubricate bearings as needed.
(Reference Bearing Maintenance in the Maintenance section)
At this time the evaporative cooler pumps should be on
No
Replace headers and/or move the headers.
(Reference Evaporative Cooler Start-Up Step #1)
Yes
Use the main supply valve to reduce the supply of water.
Yes
Reduce the air velocity through the media.
(Reference Blower Start-Up Step #5)
Modular Supply Make-Up Air Unit
32
At this time the evaporative cooler should be
operating without water blowing through.
®
Troubleshooting
Water Wizard™ — Improper Water Supply
NOTE
If the water supply is too low, the media will
continuously appear dry.
NOTE
If the water supply is too high, the media will be
saturated and excessive water will be draining from
the sump tank.
NOTE
Some water drainage is desired to keep the media
flushed, but it should be minimized to utilize the Water
Wizard™.
1. Adjust the Manual Supply Valve. Adjust the
manual supply valve (refer to Start-Up, Water
Wizard™). If the recommended water pressure does
not provide enough water, increase the pressure
until the desired water supply is achieved. If the
recommended water pressure provides too much
water, decrease the water pressure until the desired
water supply is achieved.
4. Exit Program Mode. After 15 seconds of idle time
the controller will automatically exit Program Mode.
NOTE
Changing the On Time Factor by (1) will change the
water supply by approximately 3%.
IMPORTANT
The enter key must be pressed to save the new On
Time Factor.
CAUTION
Only proceed to Steps 2 and 3 if Step 1 does not
correct the problem.
2. Enter Program
Mode. Press and
hold the Enter key
for three seconds to
enter Program Mode.
The display will read
“Pro” when Program
Mode is active.
Program Display
3. Adjust the On Time Factor. While in the Program
Menu, use the Up and Down keys to navigate
through the menu options until “ont” is displayed.
With “ont” displayed,
press the Enter key to
access the setting.
With the setting
displayed, use the
Up and Down keys to
adjust the setting as
On Time Factor Display
needed.
Increase the factor to increase the water supply or
decrease the factor to decrease the water supply.
Press the Enter key to save the new On Time Factor
and return to the Program Menu.
®
Modular Supply Make-Up Air Unit
33
Maintenance - Routine
CAUTION
Lock-out the gas and the electrical power to the
unit before performing any maintenance or service
operations to this unit.
V-Belt Drives
V-belt drives must be checked on a regular basis for
wear, tension, alignment, and dirt accumulation.
Check the tension by measuring the deflection in the
belt as shown below.
Check the alignment by using a straight edge across
both sheaves as shown below.
IMPORTANT
Premature or frequent belt failures can be caused
by improper belt tension, or misaligned sheaves.
Abnormally high belt tension or drive misalignment
will cause excessive bearing loads and may result in
failure of the fan and/or motor bearings. Abnormally
low belt tension will cause squealing on start-up,
excessive belt flutter, slippage, and overheated
sheaves.
IMPORTANT
Do not pry belts on or off the sheave. Loosen belt
tension until belts can be removed by simply lifting the
belts off the sheaves.
IMPORTANT
Snow Accumulation
Clear snow away from roof mounted units. Keep the
snow clear of the intake and access doors.
Motors
Motor maintenance is generally limited to cleaning and
lubrication (where applicable).
Cleaning should be limited to exterior surfaces only.
Removing dust and grease build-up on the motor
assures proper motor cooling.
Motors supplied with grease fittings should be greased in
accordance with the manufacturer’s recommendations.
IMPORTANT
Do not allow water or solvents to enter the motor
or bearings. Motors and bearings should never be
sprayed with steam, water or solvents.
IMPORTANT
Greasing motors is only intended when fittings are
provided. Many motors are permanently lubricated,
requiring no additional lubrication.
Wheels
Wheels require little attention when moving clean air.
Occasionally oil and dust may accumulate on the wheel
causing imbalance. When this occurs the wheel and
housing should be cleaned to assure proper operation.
When replacing V-belts on multiple groove drives,
all belts should be changed to provide uniform drive
loading.
IMPORTANT
Do not install new belts on worn sheaves. If the
sheaves have grooves worn in them, they must be
replaced before new belts are installed.
Deflection =
Belt Span
Belt Tension
Belt Span
64
Drive Alignment
Modular Supply Make-Up Air Unit
34
®
Bearings
The bearings for manufacturer fans are carefully
selected to match the maximum load and operating
conditions of the specific class, arrangement and fan
size. The instructions provided in this manual and those
provided by the bearing manufacturer will minimize any
bearing problems.
IMPORTANT
Lubricate bearings prior to periods of extended
shutdowns or storage and rotate shaft monthly to aid
in corrosion prevention. If the fan is stored more than
three months, purge the bearings with new grease
prior to start-up.
Recommended Bearing Lubrication Schedule (in Months*)
Fan
RPM
25066666
50066654
75065433
100053211
125053211
150052110.5
20005110.50.25
*Suggested initial greasing interval is based on 12 hour
per day operation and 150°F (66°C) maximum housing
temperature. For continuous (24 hour) operation, decrease
greasing interval by 50%
• If extended grease lines are present, relubricate while in
operation, only without endangering personnel.
• For ball bearings (operating) relubricate until clean grease is
seen purging at the seals. Be sure not to unseat the seal by
over lubricating.
• For ball bearings (idle) add 1-2 shots of grease up to 2 inch
bore size, and 4-5 shots above 2 inch bore sizes with a
hand grease gun.
• For roller bearings add 4 shots of grease up to 2 inch bore
size, and 8 shots for 2-5 inch bore size with a hand grease
gun.
• Adjust relubrication frequency based on condition of purged
grease.
• A high quality lithium based grease conforming to NLGI
Grade 2 consistency, such as those listed here:
Filter maintenance is generally limited to cleaning and
replacement.
If aluminum mesh filters are installed, they can be
washed in warm soapy water.
An adhesive spray can be added to aluminum mesh
filters to increase their efficiency.
If disposable filters are installed, they can be checked
by holding up to a light source. If light cannot pass
through the filter, it should be replaced.
IMPORTANT
When reinstalling filters, be sure to install them with
the airflow in the correct direction. An airflow direction
arrow is located on the side of the filters.
IMPORTANT
Replacement filters should be from the same
manufacturer and the same size as the original filters
provided with the unit.
Evaporative Coolers
The media should be periodically brushed lightly with
a soft bristle brush in an up and down motion while
flushing with water. This aids in reducing the amount of
mineral build-up.
For large amounts of mineral build-up, clean or replace
the media and increase the water bleed-off or flush rate.
The cooling media has a useful life of 3 to 5 years
depending on the water quality and the bleed-off or
flush rate.
IMPORTANT
When reinstalling the evaporative media, make sure
that it is installed correctly. Reference the drawing
shown below.
IMPORTANT
Replacement media should be from the same
manufacturer and be the same size as the original
media provided with the unit.
45º
Entering Air
Media Orientation
®
Modular Supply Make-Up Air Unit
Leaving Air
15º
35
Cooling Coils
Maintenance - Fall
WARNING
Repair and replacement of the coil and the connecting
piping, valves, etc., should be performed by a
qualified individual.
Inspect the coil for signs of corrosion and/or leaks.
Repair any leaks as required.
Inspect the coil’s surface for foreign material. If the coil
surface needs cleaning, clean the coil from the leaving
air-side so that foreign material will be washed out of
the coil rather than pushed farther in.
Inspect and clean the drain pan to prevent the growth of
algae and other organisms.
Chilled Water Coils
IMPORTANT
Be sure to read and follow the manufacturer’s
recommendations before using any cleaning fluid.
CAUTION
Caution should be used to avoid injury when venting
the coil. High pressure and/or high temperature fluids
can cause serious injuries.
Test the circulating fluid for sediment, corrosive
products and biological contaminants. Make the
necessary corrective measures.
Maintain adequate fluid velocities and proper filtering of
the fluid.
If automatic air vents are not utilized, periodic venting of
the coil is recommended to remove accumulated air.
Evaporative Coolers
The water should be shut off and all the lines drained
when the outside temperature drops below 45°F.
Remove drain plugs for the winter.
Clean all interior parts of any mineral deposits or foreign
materials that may have built-up during the cooling season.
Replace any worn or non-functioning parts.
Winterizing Chilled Water Coils
During the winter, chilled water coils need to be
protected against freezing. Manufacturer recommends
protecting the coils by either blowing-out the coils or by
flushing the coils.
Blowing-Out Coils
1. Close valves on the supply and return lines.
2. Open drain valves and/or drain plug. Remove vent
plug to allow coil to drain faster.
3. After coil is fully drained, connect a blower to the
caps. Do not connect the blower to the air vent or
drain plug.
4. Close the vent plug on the header that the blower
is connected to. Open the drain valve or cap on the
other header.
5. Turn on blower for 30 minutes. Place mirror at
discharge. If the mirror fogs up, repeat procedure
until no fog appears on the mirror.
6. After drying the coil, wait a few minutes then repeat
Step #5.
7. Leave drains open and do not install plugs until
beginning of cooling season.
Flushing Coils
Manufacturer recommends the use of inhibited glycol
(such as propylene or ethylene) to flush water coils
to protect against freezing. Additionally, the use of
inhibited glycol provides corrosion protection.
The table below indicate the percentage of glycol
required to prevent freezing in a coil at a given outdoor
air freeze point. Completely fill coil with solution. Drain
coil. Residual glycol fluid per these concentrations can
be left in the coil without concern of freezing. Recovered
fluid can be used to flush other coils.
Modular Supply Make-Up Air Unit
36
Percent of
Ethylene
Glycol
by Volume
03200320
1025-41026-3
2016-92019-7
303-16308-13
40-13-2540-7-22
50-34-3750-28-33
60-55-4860-60-51
Freeze Point
°FºC°FºC
Percent of
Propylene
Glycol
by Volume
Freeze Point
®
Reference
Typical Control Center Layout
10
7
11
9
3
1517
8
12
13
1. Primary Fuses — provides proper fusing to low
voltage transformer.
2. Low Voltage Transformer — provides low
voltage to controls and optional evaporative cooling
controls.
3. Low Voltage Fuse — provides proper fusing to
controls and optional evaporative cooling controls.
4. Control Terminal Block — provides wiring
access to controls.
5. Building Freeze Protection Timer (optional)—
prevents the discharge of cold air into the building.
6. Fan Relay — allows power to pass to energize
motor starter.
7. Supply Motor Starter — 24 volt magnetic
contacts for starting supply motor.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be obtained
from AMCA International, Inc. at www.amca.org.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.