Please read and save these instructions for future reference. Read carefully before attempting to assemble,
install, operate or maintain the product described. Protect yourself and others by observing all safety
information. Failure to comply with instructions could result in personal injury and/or property damage!
To prevent injury and property damage, follow these
instructions. Failure to adhere to installation/operation
procedures and all applicable codes may result in
hazards as indicated by warning codes outlined below:
DANGER
Indicates an imminently hazardous situation which,
if not avoided, will result in death or serious injury.
This signal word is to limited to the most extreme
situations.
WARNING
Indicates a potentially hazardous situation which, if
not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if
not avoided, may result in minor or moderate injury. It
may also be used to alert against unsafe practices.
This is the safety alert symbol. Read and
!
follow instructions carefully to avoid a
!
dangerous situation.
This symbol alerts the user to the presence
of “dangerous voltage” inside the product
that might cause harm or electrical shock.
DANGER
Equipment can start automatically. Lockout/tagout
before servicing.
CAUTION
As with all electrical products, read manual
thoroughly. Only qualified, expert personnel should
perform maintenance and installation. Contact the
nearest authorized service facility for examination,
repair, or adjustment. Do not disassemble or repair
unit unless described in this manual; death or
injury to electrical shock or fire hazard may result.
Specifications and manual data subject to change.
Consult factory for additional information.
DANGER
HAZARDOUS VOLTAGE
!
• Disconnect and lock out all power before installing
or servicing equipment.
• This equipment may require locking out multiple
power sources prior to service.
• Install and wire in accordance with all applicable
local and national electrical and construction codes.
WARNING
FAILURE TO FOLLOW THESE INSTRUCTIONS
MAY RESULT IN DEATH OR SERIOUS INJURY.
®
Motor Starter Advanced Control
1
Page 2
Installation
Wiring Schematics
Mounting
Mount the starter on a vertical surface, with the line
terminals facing up. Install using 1/4-inch diameter
hardware suitable for the mounting surface.
WARNING
• To maintain overcurrent and short circuit protection,
the manufacturer’s instructions for selecting current
elements and setting the instantaneous-trip circuit
breaker must be followed.
• Tripping of the instantaneous-trip circuit breaker
is an indication that a fault current has been
interrupted. Current-carrying components of the
magnetic motor controller should be examined and
replaced if damaged to reduce the risk of fire or
electric shock.
• Do not locate starter in an environment subject to
flammable gases, dusts or materials. Contact arcing
can induce explosion or fire.
• Locate starter in a location appropriate to enclosure
ratings and operational ratings. (e.g. NEMA-1 should
only be located in a dry, protected environment).
• Do not allow any metal shavings or debris from
installation to enter enclosure.
Wiring
Wire main power input and motor leads to the
appropriate terminals tightened to specified torques
indicated in the torque table. Use only copper
conductors rated at least 60°C for applications less
than 100A and at least 75°C ≥ 100A. Maintain proper
clearances and verify that no possibility of an electrical
short exists between the power conductors or
enclosure. Ensure that wires are not under stress and
all insulation is intact. Verify voltage input matches label
and the control power is tapped per schematic.
Low Voltage Wiring
Automation system control wiring should be run in
a separate conduit. The control terminals accept
26~14AWG wire torqued to 3.5 in-lb.
Torque Table
NEMA
Size
0015.61820
015.61820
115.61820
Input (lb-in)Output (lb-in)
StandardCombination Motor Leads
Standard product wiring diagram shown. As-built
product wiring may vary. Product wiring diagram located
on starter enclosure.
5
1
FLA (A)
Overload Setting
PCB Power
H1 H4
MCP
(Optional)
208-600VAC
Input
10
Keypad
15
OL
H1
20
25
30
35
40
208-600VAC
60VA Max.
H4
Voltage
Inputs
Relay
Outputs
Dry
Inputs
Actuator
Control
Contactor
Coil
L3L1 L2
Fireman’s
Limit Switch
M
Auto Run
Override
Shut Down
Permissive
Auto Run
Control
T1T3
T2
MTR
3PH
12-250VAC/DC Input
12-250VAC/DC Input
Status
Common
Fault
Normally
Closed Input
Normally
Open Input
Normally
Open Input
24VDC,
1A Output
Normally
Open Input
24VDC output
24V
A1
to 24VAC
Output to
M
contactor coil
A2
contactor coil
434431
32
AUX
CONT
Program Switches
Smartstart Bypass: Bypasses the Smartstart features
when on. Smartstart protects the motor by detecting
SWITCH
1
SWITCH
2
SWITCH
3
SWITCH
45
ONON
OFF OFF
ON OFF
OFF ON
several common potentially damaging fault conditions.
When Smartstart is active, the starter will shut off
under the following conditions: if locked rotor condition
is present for 0.5 seconds, if the motor takes more
than 10 seconds to start, or if the FLA setting is
determined to be incorrect.
Selects overload trip Class 10 when on and overload
trip Class 20 when off. If trip Class 20 is selected
Smartstart is bypassed. Default: ON
(ON) - Fault reset: Depress the “OFF” button for 5
seconds to reset a fault trip. Starter will return to “OFF”
mode.
(OFF) - Automatic Fault Reset: The starter will make 3
attempts at an auto fault reset separated by 5 minutes
intervals. Also allows manual reset as above.
Power Fail Modes
Default Mode - Always return to last mode with no
delay in the event of a power failure.
Default Mode - Always return to last mode with no
delay in the event of a power failure.
Always return to last mode with a 10 second delay in
the event of a power failure.
Upon a power failure, return to off mode.
Motor Starter Advanced Control
2
®
Page 3
Protective Features
Operation
Cycle
Fault
Short 24V
Locked
Rotor
Max Start
Time
Out of
Calibration
Stall
Overload
Phase
Unbalance
Trips when the starter is activated at a rate
exceeding 20 starts per minute.
Trips if the starter’s combined current drawn
from the 24VDC damper actuator terminals
and contactor terminals exceeds 1 amp.
Trips when a locked rotor condition is
detected for 0.5 seconds (Smartstart mode
only).
Trips if the motor takes more than 10 seconds
to start (Smartstart mode only).
Trips if the FLA setting is determined to be
incorrect based on the motor inrush current
(safety start mode only).
Trips if a STALL condition is detected. (0.5
seconds at 300% FLA and current slope not
decreasing). Disabled during startup.
Overload trip Class 10 or 20. Trip current =
115% of FLA. Trips when the load is greater
than the Full Load Ampere setting labeled
FLA- (1-40A). The trip time will be determined
by the Class 10/20 DIP switch.
Trips in the event of a phase failure or phase
unbalance greater than 70% (Smartstart
mode only)
• Intended for use with 3-Phase, 50/60Hz
• Accepts 208-600VAC, ±10%
• Short Circuit (RMS, Symmetrical)
Stand-Alone Overload Unit - 200 KAIC, 600V Max.
Standard Starter - 5 KAIC, 600V Max
Combination Starter - 100 KAIC, 240V Max.
30 KAIC, 480V Max.
10 KAIC, 600V Max.
• Ambient Operating Temperature = -20°C to 60°C
• Ambient Storage Temperature = -40°C to 85°C
Keypad Interface
NOTE
On NEMA-4X
Enclosures, the
interface is inside
the enclosure.
Do not attempt
to remove the
keypad on exterior
of enclosure.
5
1
FLA (A)
15
10
20
OFF ON
25
30
35
40
AUTO
12-250V
1
2
3
12-250V
4
FIREMAN’S
5
RELAYS
O1 O O2
FAULT STATUS
DRY
SHUTDOWN
DRY
PERMISS
Electronic Overload Operation
When an alarm occurs, the type of alarm will be
indicated by flashing a combination of the hand/off/auto
LED’s as indicated in the table.
FaultHandOffAuto
Cycle Fault Alarm–––
Short 24V Alarm––0
Locked Rotor Alarm–0–
Max Start Time Alarm–00
Out of Calibration Alarm0––
Stall Alarm0–0
Overload Alarm00–
Phase Unbalance Alarm000
– = off 0 = on
* Run and Fault LED’s will blink together in the event of a
hardware fault.
DANGER
• Ensure that all connections are properly
!
torqued and enclosure is closed prior to
applying power to the device.
• Ensure all mechanical equipment operated by the
starter is clear for safe operation in case of starter
activation.
• When in AUTO mode, starter may be activated
remotely by the control system.
DRY
AUTO
D1 D2
DAMPER/
ACTUATOR
LIMIT
SWITCH
L- L+ A- A+
COIL
C- C+V3 V4V1 V2D5 D6D3 D4
CONTACTOR
Operation Modes
ON (HAND): Press the ON mode button to manually
engage motor.
OFF (RESET): Pressing the OFF mode button
manually disengages the motor. Additionally, the OFF
button serves as a manual Reset. Press and hold
OFF for 5 seconds to Reset the starter after a fault
trip.
AUTO: When utilizing AUTO mode, the starter is
controlled by a remote Start/Stop command.
LED Status Indicators
MODE LEDs: Illuminates with corresponding mode
selection (HAND/OFF/AUTO). Flashing mode LED
signals a fault trip during the last operating mode.
All three mode LEDs will flash simultaneously during
Shutdown or Fireman’s Override operation.
RUN LED: Illuminates when starter is given a Run
signal and proof of flow is detected. LED will flash
when Run signal is present without proof of flow to
motor.
FAULT LED: Illuminates upon a fault condition or
overload trip. Starter must be returned to the OFF
mode in order to Reset.
®
Motor Starter Advanced Control
3
Page 4
I/O Descriptions
• Use 14-26AWG wire for I/O terminals
• Torque to 3.5 lb-in
Terminal Description
V3 / V4Wet Auto Input: Accepts wetted customer input.
Input voltage must be within 12 - 250 VAC/VDC
(4.2mA maximum). Sending voltage to the contact
will operate the starter when in Auto Mode.
V1 / V2Fireman’s Override Input: Accepts wetted
customer input. Input voltage must be within
12 -250 VAC/VDC (4.2mA maximum). Sending
voltage to the contact will operate the Motor
Starter in all modes including OFF and Shutdown
Input. When active, all mode LED’s flash.
O1 / O / O2Status and Fault Relay Output
- O1 - Fault Terminal: Con nects to a relay contact
that closes in a fault condition.
O - Common: Common connection for the fault
and status relays.
O2 - Run Status: Connects to a relay contact
that closes when the motor draws 60% of the
FLA setting. See below for Relay Output current
ratings
110VDC, 0.3A Resistive
125VDC, 0.5A GP
30VDC, 2.0A Resistive
120VAC 50/60Hz, 0.5A Resistive
125VAC 50/60Hz, 1.0A GP
240VAC 50/60Hz, 0.25A Resistive
D5 / D6 Dry Shutdown Input: When the input is open
the Motor Starter will open in all modes (except
Fireman’s Override), HAND/OFF/AUTO LED’s will
flash indicating a shutdown. (N.C. dry contact or
transistorized input)
Terminal Description
D3 / D4 Dry Permissive Auto Input: N.O. dry contact
input. When the input is open, the Auto input is
disabled. 24VDC, 2.4mA maximum
D1 / D2 Dry Auto Input: N.O. dry contact or transistorized
input. When closed, the starter will operate when
automatic mode is selected. 24VDC, 2.4mA
maximum
A- / A+Damper Control Output: 24VDC 1A maximum.
Provides a 24VDC damper control output when
the motor starter is commanded in either auto or
hand mode. The damper control output must be
wired with a damper end switch input as noted
below to prevent overloading of control circuit.
L- / L+Damper Switch Input: N.O. open dry contact.
Switch input dry contacts must be rated for at
least 24VDC, (2.4mA maximum). When used with
the damper motor output, the contactor coil is in
series with customer provided damper contacts
which disable the motor starter until the damper is
in position.
C- / C+ Contactor Output: Provides a 24V output to the
contactor when the motor starter is commanded
in either Hand or Auto mode and the damper
switch input is closed. (Wired from manufacturer).
24V, 0.42A Max. for a Franklin Control Systems
contactor with 24VAC coil.
File E242640
To conform to the EMC directive, a ferrite core is required on the input of the
starter module. Consult the factory for the recommended part number.
For a CE compliant installation, all electrical connections must be made by
a qualified electrician.
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Greenheck Motor Starters catalogs provides additional
information describing the equipment and specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be obtained
from AMCA International, Inc. at www.amca.org.