Greenheck MP-220A Installation Manual

®
Field Installation Instructions
Motor Pack Contents
1. Actuator
2. Actuator Bracket
4. Connecting Links
5. Actuator Spring All necessary hardware included
Document Number 463544
MP-220A Motor Pack
UL Listed Electric Actuators with Spring Return
for use with WD-200 Series Dampers
1. The MP-220A motor pack is designed for installation on model WD-200 series backdraft dampers only.
2. For single panel damper, insert tab of motor bracket into the slot on the side of the frame. For dampers with center bars, the tab of the motor bracket should be inserted into the slot on the bottom of the center bearing rail. Position bracket over the two holes on the bottom of the frame and secure with the #10 hardware provided.
3. Loosely connect the actuator arm assembly to the connecting link using the provided hardware. Fasteners should be placed as far apart as possible to provide greater stability to the linkage. The connecting links may need to be modified or shortened on some dampers sizes. To make the adjustment easier, release the spring from the spring adjustment bracket.
Note: The connecting link(s) have been
installed on the damper at the factory.
4. To adjust the actuator linkage, position the actuator arm approximately 1/8” away from the rubber bumper. While holding the damper blades closed, tighten the fasteners between the connecting link and actuator arm assembly. Place the spring onto the first hook of the adjustment bracket (see Fig. 1). Operate the damper manually. Verify that the linkage and fasteners do not interfere with any components of the assembly and that the damper blades close completely when
released. To increase spring tension, move the spring to the next hook as shown in Fig 1.
Note: It is important to avoid too much
spring tension; use just enough tension to close the damper. Too much tension could impair opening of the damper or cause damage to the components as the crankarm impacts the rubber bumper.
5. Actuators are supplied with junction box and covers. When wiring, make sure the supply voltage agrees with the actuator voltage. On dual voltage motor packs, be sure to connect the proper motor leads for the correct voltage and insulate any unused wire. The voltage of each specific model is indicated on a label that is affixed to the actuator (see page 2 and 3 for typical wiring diagrams).
6. If the damper fails to open properly, check for one of the following causes:
• Check for an ‘out of square’ or racked damper
• Check for mounting screws interfering with the blade and linkage rotation
• Spring tension too great
• Excessive voltage drop
• Excessive negative pressure in the building If actuator fails to function:
• Check for correct voltage
• Check for proper wiring
Motor Pack Quantity
More than one motor pack may be required depending on damper size. On single panel dampers, the actuator is installed as shown on page 1 in the Single Panel view. On double panel dampers, the actuator is installed as shown on page 1 in the multiple panel view. On triple panel dampers, two actuators are installed as shown in the multiple panel view.
Chart 1
Motor Packs 24V (50/60 Hz)
Stall Amps .66 .15 .07 .041
Spec ID# G24 G110-240 G-110-240 G460
110 thru 120V
(50/60Hz)
Actuator Specifications
MP-220A motor pack uses a single phase shaded pole stall type impedance protected electric actuators and are supplied in various voltages (see chart). For 277, 380, 575 or 600 volt operation, a transformer and a 120V motor pack is required.
208 thru 240V
(50/60 Hz)
460V (60Hz)
Typical Wiring Diagrams
Wiring diagrams are shown for motor packs and dampers installed with power ventilator fan equipment with single speed motor. The damper will open when the fan is on and close when the fan is off. For connection to 2-speed fan motors or for other control sequences consult the factory. The wiring diagrams shown with end switches are for applications where it is desirable to have the damper fully open before fan start-up.
Single Phase
Three Phase
Loading...
+ 1 hidden pages