Please read and save these instructions for future reference. Read carefully before attempting to assemble, install,
operate or maintain the product described. Protect yourself and others by observing all safety information. Failure
to comply with instructions could result in personal injury and/or property damage!
Energy recovery wheels are certified by the AHRI Air-to-Air Energy Recovery Ventilation Equipment Certification
Program in accordance with AHRI Standard 1060. Actual performance in packaged equipment may vary.
Certified Ratings are available in the Certified Product Directory at www.ahridirectory.org
General Safety Information
Only qualified personnel should install this system.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards. Other
considerations may be required if high winds or seismic
activity are present. If more information is needed,
contact a licensed professional engineer before moving
forward.
DANGER
Always disconnect power before working on or near
this equipment. Lock and tag the disconnect switch or
breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components may
be hot enough to cause pain or injury. Allow time for
cooling before servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
1. Follow all local electrical and safety codes, as well as
the National Electrical Code (NEC), the National Fire
Protection Agency (NFPA), where applicable. Follow
the Canadian Electrical Code (CEC) in Canada.
2. All moving parts must be free to rotate without
striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum
cataloged fan RPM. Adjustments to fan speed
significantly affects motor load. If the fan RPM is
changed, the motor current should be checked to
make sure it is not exceeding the motor nameplate
amps.
5. Do not allow the power cable to kink or come in
contact with oil, grease, hot surfaces or chemicals.
Replace cord immediately if damaged.
6. Verify that the power source is compatible with the
equipment.
7. Never open access doors to the unit while it is
running.
®
Energy Recovery Ventilator1
Page 2
Receiving
Upon receiving the product check to ensure all items
are accounted for by referencing the delivery receipt or
packing list. Inspect each crate or carton for shipping
damage before accepting delivery. Alert the carrier
of any damage detected. The customer will make
a notation of damage (or shortage of items) on the
delivery receipt and all copies of the bill of lading which
is countersigned by the delivering carrier. If damaged,
immediately contact your Greenheck Representative.
Any physical damage to the unit after acceptance is not
the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity
of each item have been received. If any items are
missing, report shortages to your local representative to
arrange for obtaining missing parts. Sometimes it is not
possible that all items for the unit be shipped together
due to availability of transportation and truck space.
Confirmation of shipment(s) must be limited to only
items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting brackets
provided or by the skid when a forklift is used. Location
of brackets varies by model and size. Handle in such
a manner as to keep from scratching or chipping the
coating. Damaged finish may reduce ability of unit to
resist corrosion.
Storage
Units are protected against damage during shipment. If
the unit cannot be installed and operated immediately,
precautions need to be taken to prevent deterioration of
the unit during storage. The user assumes responsibility
of the unit and accessories while in storage. The
manufacturer will not be responsible for damage during
storage. These suggestions are provided solely as a
convenience to the user.
INDOOR — The ideal environment for the storage of
units and accessories is indoors, above grade, in a
low humidity atmosphere which is sealed to prevent
the entry of blowing dust, rain, or snow. Temperatures
should be evenly maintained between 30°F (-1°C)
and 110°F (43°C) (wide temperature swings may
cause condensation and “sweating” of metal parts).
All accessories must be stored indoors in a clean, dry
atmosphere.
Remove any accumulations of dirt, water, ice, or snow
and wipe dry before moving to indoor storage. To avoid
“sweating” of metal parts allow cold parts to reach room
temperature. To dry parts and packages use a portable
electric heater to get rid of any moisture build up. Leave
coverings loose to permit air circulation and to allow for
periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the
floor on wooden blocks covered with moisture proof
paper or polyethylene sheathing. Aisles between parts
and along all walls should be provided to permit air
circulation and space for inspection.
OUTDOOR — Units designed for outdoor applications
may be stored outdoors, if absolutely necessary. Roads
or aisles for portable cranes and hauling equipment are
needed.
The fan should be placed on a level surface to prevent
water from leaking into the unit. The unit should be
elevated on an adequate number of wooden blocks so
that it is above water and snow levels and has enough
blocking to prevent it from settling into soft ground.
Locate parts far enough apart to permit air circulation,
sunlight, and space for periodic inspection. To minimize
water accumulation, place all unit parts on blocking
supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these
cause condensation of moisture from the air passing
through heating and cooling cycles.
Inspection and Maintenance during
Storage
While in storage, inspect fans once per month. Keep a
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts,
the source should be located and eliminated. At each
inspection, rotate the fan wheel by hand ten to fifteen
revolutions to distribute lubricant on motor. Every three
months, the fan motor should be energized. If paint
deterioration begins, consideration should be given to
touch-up or repainting. Fans with special coatings may
require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be
restored to good condition promptly if signs of rust
occur. Immediately remove the original rust preventive
coating with petroleum solvent and clean with lint-free
cloths. Polish any remaining rust from surface with
crocus cloth or fine emery paper and oil. Do not destroy
the continuity of the surfaces. Wipe thoroughly clean
with Tectyl
hard to reach internal surfaces or for occasional use,
consider using Tectyl® 511M Rust Preventive or WD-40®
or the equivalent.
REMOVING FROM STORAGE — As units are removed
from storage to be installed in their final location, they
should be protected and maintained in a similar fashion,
until the equipment goes into operation.
Prior to installing the unit and system components,
inspect the unit assembly to make sure it is in working
order.
1. Check all fasteners, set screws on the fan, wheel,
bearings, drive, motor base, and accessories for
tightness.
2. Rotate the fan wheel(s) by hand and assure no parts
are rubbing.
®
506 (Ashland Inc.) or the equivalent. For
Energy Recovery Ventilator2
®
Page 3
Table of Contents
Dimensional Data and Weights
Dimensional Data and Weights ...................3
Service Clearances and Access Panel Locations .....4
Intake and Discharge Locations ..................4
Installation
Hang Mounting with Hanging Vibration Isolators ...5
Base Mounting with Base Vibration Isolators ......6
Duct Connections ...........................6
Electrical Connections .........................7
Frost Control ...............................7
Wiring Schematics .......................... 8-9
System Start-Up
Pre-Start-Up Checklist ......................10
Unit Documentation Record ..................10
Unit Start-Up Checklist ......................11
General ..................................12
Energy Wheel .............................12
Blower Wheel Rotation ......................12
Fan RPM .................................12
Motor ....................................12
Routine Maintenance
General ..................................12
Fasteners and Set Screws ...................12
Removal of Dust and Dirt ....................12
Internal Filters .............................12
Energy Wheel Maintenance ................ 12-13
Troubleshooting ..............................14
Optional Vari-Green
®
EC Motors ................15
Maintenance Log ...................... Backcover
Our Commitment ...................... Backcover
Discharge
Intake
Side "A"
Discharge
Side "A"
Front View
A
Side "B"
Back View
MiniVentABC
450
750
All dimensions are in inches.
DISCHARGE
SIDE "A"
40.228.619.9160
45.835.323.8240
D
G
E
INTAKE
SIDE "A"
F
Intake
Side "B"
Energy Wheel
C
B
Weight
(lbs.)
K
L
J
H
INTAKE
SIDE "B"
N
M
FRONT VIEW
P
E
F
D
G
BACK VIEW
Q
DISCHARGE
SIDE "B"
MiniVent DEFGHJKLMNPQ
450
750
All dimensions are in inches.
Intake and Discharge positions are not labeled because
they are configurable by rotation of the unit about the
vertical axis. The supply and exhaust can be on either
side, but the intake/discharge relationship must be
maintained. For example, Outdoor Air Intake = Intake
Side “B”/Outdoor Air Discharge = Discharge Side “B”.
The preferred configuration is to have the energy wheel
motor in the exhaust airstream.
10 812 6 4.3 1.4 6 1.5 61 4.8 3.4
10 10 18 74 2.2 5.1 1.5 5.1 1.1 4 1.5
®
Energy Recovery Ventilator3
Page 4
Service Clearances and Access
Panel Locations
Recommended Service Clearances
The MiniVent requires minimum clearances to perform
routine maintenance, such as filter replacement, energy
wheel cassette and fan inspection. Fan and motor
assemblies, energy recovery
wheel cassette and filter
sections are provided with
a service door or panel for
proper component access.
MiniVentAB
450
750
All dimensions are in inches.
2515
3121
Intake and Discharge Locations
Intake and discharge locations are shown. Both intake
locations are capable of being field relocated to suit
installation needs (see optional locations).
Intake Side “A” (optional)
Access Panel Locations
1. • Outdoor and exhaust fans and motor
• Electrical connection
2. • Energy wheel cassette
• Internal filters
1
B
A
Discharge
Side “B”
1
Discharge
Side “A”
Intake
Side “A”
2
2
Cassette
Slides Out
Intake
Side “B”
Discharge
Side “A”
Intake
Side “A”
Discharge
Side “B”
Intake
Side “B”
Intake Side “B” (optional)
Changing the discharge location
Step 1 - Remove the
metal cover for optional
intake by unfastening the
four sheet metal screws
holding it in place.
Step 2 - Hand bend
flanges out to form a
duct collar in the newly
uncovered intake opening.
Step 3 - Hand bend
flanges in on original intake
and replace metal cover
removed in Step 1.
Intake
Cover
Intake Duct
Collar
Energy Recovery Ventilator4
®
Page 5
Installation
The system design and installation should follow
accepted industry practice, such as described in the
ASHRAE Handbook and SMACNA.
Minimum service clearance should be provided on
the side of the unit for routine service and component
removal should it become necessary.
Before beginning installation see page 3 for detail on
appropriate service clearances.
Hang Mounting with Hanging Vibration
Isolators
• The hanging isolator kit includes four (4) isolators
and required hardware.
• Locate the support rods as shown in the drawing.
• Assemble each isolator as shown.
B
A
C
3/8-inch threaded rod,
provided by others
Nut
Hanger bracket,
factory-mounted
Small flat washer
Big flat washer
Isolator
Big flat washer
Small flat washer
Lock washer
Nut
Hanging Vibration Isolator Assembly
MiniVent-450
Nut
Hanger bracket,
factory-mounted
1/2-inch threaded rod,
provided by others
Lock Washer
Flat Washer
Isolator
Flat Washer
Lock Washer
Nut
MiniVentABC
450
750
All dimensions are in inches.
37.626.419.9
43.23323.8
Electrical and Fan Access Panel
(underside)
Hanging Vibration Isolator Assembly
MiniVent-750
®
Energy Recovery Ventilator5
Page 6
Base Mounting with Base Vibration
Isolation
• The base isolators kit includes four (4) isolators,
four (4) brackets and required hardware.
• Rotate the MiniVent 180 degrees, so the electrical
and fan component panel is accessible from the top.
The corners, where the brackets are fastened, are
now closest to the mounting surface.
• Assemble and mount the isolators as shown in the
figures below.
Note: The hanging and base mounting brackets are
fastened to the same unit corners.
Electrical
and
Fan Access Panel
Duct Connections
Examples of good and poor fan-to-duct connections are
shown below. Airflow out of the fan should be directed
straight or curve the same direction as the fan wheel
rotates. Poor duct installation will result in low airflow,
loud noise and excessive vibrations.
4x Wheel Diameter
MiniVent
POOR
Less
than 4x Wheel Diameter
Recommended Discharge Duct Size and Length
MiniVent
450
750
All dimensions are in inches.
ERV
Blower Size
810 x 832
1010 x 1040
Duct
Size
GOOD
GOOD
Straight Duct
Length
Factory-mounted
bracket
3/8-inch bolt
Flat washer
Base Vibration Isolator Assembly
Lock washer
Isolator
Assembled and Mounted Isolator Detail
Energy Recovery Ventilator6
®
Page 7
Electrical Connections
Before connecting power to the unit, read and
understand the following instructions and wiring
diagrams. Complete wiring diagrams are attached inside
the blower door of the unit.
All wiring should be done in accordance with the
National Electrical Code ANSI/NFPA 70 latest edition
and any local codes that may apply. In Canada, wiring
should be done in accordance with the Canadian
Electrical Code. The equipment must be properly
grounded.
Caution
If any of the original wire must be replaced, the
replacement wire must have a temperature rating of at
least 105ºC.
DANGER
High voltage electrical input is required for this
equipment. This work should be performed by a
qualified electrician.
Electrical Connection Location
MiniVentAB
450
750
All dimensions are in inches.
Electrical
Connection
21.87512.5
28.37515.5
B
Frost Control
Extremely cold outdoor air temperatures can cause
moisture condensation and frosting on the energy
recovery wheel. Frost control is an optional feature that
will prevent/control wheel frosting.
1. Timed Exhaust frost control
This option is provided with a thermodisc mounted in
the outdoor air intake compartment.
Timed exhaust frost control includes a timer in
addition to the thermodisc. When timed exhaust frost
control is initiated, the timer will turn the supply blower
off. Time exhaust using default timer setting will shut
down the supply fan for 5 minutes every 30 minutes
to allow exhaust to defrost energy wheel. Use the test
procedure for troubleshooting.
Frost Control Test Procedure
1. Remove power from unit.
2. Jumper the temperature indicating thermodisc in
the unit control center. Thermodisc has a pre-set
temperature of 5ºF.
3. Set the frost control timer scale for T1 and T2 to 1m.
Set the timer settings for T1 and T2 to 10.
4. Add power to the unit. Blower should cycle on for
one minute, then turn off for one minute.
5. Remove power from unit and remove jumpers that
were placed. Re-set timer settings.
• T1 timer setting set to 5 and timer scale set to
10m for 5 minutes of wheel off time.
• T2 timer setting set to 5 and timer scale set to
1h for 30 minutes of wheel on time
A
Wheel and Filter Access
Sequence for wiring MiniVent unit:
1. The unit’s nameplate contains the voltage and total
amperage required. The wire supplying power to
the unit should be sized accordingly.
2. The main power line should be connected to the
appropriate terminal blocks.
Power may be routed to the MiniVent through the
opening on the underside of the unit. The locations
for the opening are provided in the figure to the
right.
3. Refer to the wiring diagrams in this manual or in the
unit for controlling the MiniVent.
Timer
Scale
Timer
Settings
Timer
Scale
T1
T2
®
Energy Recovery Ventilator7
Page 8
Wiring Schematics
Timed Exhaust Frost Control
TR
115/208/230V PRIMARY
24V SECONDARY
R
VIOLET
RED
ORANGE
BLACK
GROUND
115
208
230
L2
FIELD TO CONNECT
TO TERMINAL DESIGNATED
WITH UNIT LINE VOLTAGE
CONNECT TERMINAL 15
FROM COMPONENT "T1"
WITH LINE VOLTAGE
PURPLE
L1
L2
FIELD MOUNT
IN OUTDOOR
AIR DUCT
COM
NO
A1
TH
B1
T1
A2
Potentiometer Control
(VERIFY MAIN UNIT POWER ON UNIT NAMEPLATE)
MAIN UNIT POWER -115/208/230/60/1
L1
L2
L2L1
GROUND
YELLOW
REMOTE PANEL
BLACK
BLACK
T1
16
15
ENERGY WHEEL MOTOR
M1
TA OR B
SEE NOTE #3
L1
MAIN UNIT INTERNAL JUNCTION BOX
SEE NOTE#2
SEE NOTE#2
BLACK
A
WHITE
BLACK
B
WHITE
BLOWER MOTOR A
MA
BLOWER MOTOR B
MB
Legend
MA Blower Motor A
MB Blower Motor B
M1 Energy Wheel Motor
M2 Exhaust Blower Motor
M3 Supply Blower Motor
T1 Frost Control Timer
Typical Settings: t1 (OFF) = 5 min.
t2 (ON) = 30 min.
TH Thermostat; non-adjustable 5° setting.
Required to be mounted in outdoor air duct.
TR Transformer
Energy Recovery Ventilator8
®
Page 9
Wiring Schematics
0-10 VDC Fan Motor Control
(VERIFY MAIN UNIT POWER ON UNIT NAMEPLATE)
MAIN UNIT POWER -110/50/1-115/60/1
L2 (NEUTRAL)
L1
GROUND
L2
L1
24 VAC
0-10VDC
SEE NOTE#1
SEE NOTE#2
24 VAC
0-10VDC
SEE NOTE#1
SEE NOTE#2
24v
A-
A+
A
24v
B-
B+
B
BLACK
BLACK
BLACK
WHITE
RED
BLACK
WHITE
BLACK
WHITE
RED
BLACK
WHITE
Solid State Speed Motor Control
(VERIFY MAIN UNIT POWER ON UNIT NAMEPLATE)
MAIN UNIT POWER -115/208/230/60/1
L2
L1
GROUND
ENERGY WHEEL MOTOR
M1
BLOWER MOTOR A
MA
BLOWER MOTOR B
MB
L2
L1
SEE NOTE#2
SPEED CONTROLLER
A
SPEED CONTROLLER
SEE NOTE#2
B
BLOWER A
ON OFF
BLOWER B
ON OFF
A2
B2
BLACK
BLACK
BLACK
BLACK
ENERGY WHEEL MOTOR
M1
BLOWER MOTOR A
MA
BLOWER MOTOR B
MB
Legend
MA Blower Motor A
MB Blower Motor B
M1 Energy Wheel Motor
M2 Exhaust Blower Motor
M3 Supply Blower Motor
T1 Frost Control Timer
Typical Settings: t1 (OFF) = 5 min.
t2 (ON) = 30 min.
TH Thermostat; non-adjustable 5° setting.
Required to be mounted in outdoor air duct.
TR Transformer
®
Energy Recovery Ventilator9
Page 10
System Start-Up
DANGER
Electric shock hazard. Can cause injury or death.
Before attempting to perform any service or
maintenance, turn the electrical power to unit to OFF
at disconnect switch(es). Unit may have multiple
power supplies.
CAUTION
Use caution when removing access panels or other
unit components, especially while standing on a
ladder or other potentially unsteady base. Access
panels and unit components can be heavy and
serious injury may occur.
CAUTION
Do not operate without the filters and birdscreens
installed. They prevent the entry of foreign objects
such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to
internal components may result and void warranty.
WARNING
• Unit was factory tested. All blowers, fans,
and compressors are set-up to run correctly
when supplied power. If any one fan is running
backwards or the compressor is making loud
noises, immediately turn off the power. Switch two
leads on the incoming power to the disconnect.
This will ensure proper operation of the unit. Failure
to comply may damage the compressors and void
the warranty.
• Do not jumper any safety devices when operating
the unit. This may damage components within or
cause serious injury or death.
Every installation requires a comprehensive start-up
to ensure proper operation of the unit. As part of that
process, the following checklist must be completed and
information recorded. Starting up the unit in accordance
with this checklist will not only ensure proper operation,
but will also provide valuable information to personnel
performing future maintenance. Should an issue arise
which requires factory assistance, this completed
document will allow unit experts to provide quicker
resolve. Qualified personnel should perform start-up to
ensure safe and proper practices are followed.
Unit Documentation Record
Unit Model No. ___________________________________
Unit Serial No. _____________________________________
Energy Wheel Date Code ___________________________
Start-Up Date _____________________________________
Start-Up Personnel Name __________________________
Start-Up Company _________________________________
Phone Number ____________________________________
Pre-Start-Up Checklist
Disconnect and lock-out all power switches.
Remove any foreign objects that are located in the
energy recovery unit.
Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and
accessories for tightness.
Rotate the fan wheels and energy recovery wheels
by hand and ensure no parts are rubbing.
Check the fan belt drives for proper alignment and
tension.
Filters can load up with dirt during building
construction. Replace any dirty pleated filters and
clean the aluminum mesh filters in the intake hood.
Verify that non-motorized dampers open and close
properly.
Check the tightness of all factory wiring
connections.
Verify control wire gauge.
Verify diameter seal settings on the energy recovery
wheel.
SPECIAL TOOLS
• Volt meter
• Incline manometer or equivalent
• Tachometer
• Amperage meter
Energy Recovery Ventilator10
®
Page 11
Start-Up Checklist
Line Voltage. Check at unit disconnect.
L1-L2Volts
Motor Amp Draw
Supply Motor AmpsL1AmpsL2Amps
Exhaust Motor AmpsL1AmpsL2Amps
Fan RPM
Supply Fan RPM
Exhaust Fan RPM
Correct fan rotation direction?
Supply FanYes / No
Exhaust FanYes / No
Energy Wheel Motor
L1AmpsL2Amps
Outdoor Air TemperatureDeg F
Return Air TemperatureDeg F
Outdoor Air Relative Humidity% RH
Return Air Relative Humidity% RH
®
Energy Recovery Ventilator11
Page 12
System Start-Up - continued
Airflow
General
Check all fasteners and set screws for tightness. This is
especially important for bearings and fan wheels Also,
if dampers are not motorized, check that they open and
close without binding.
Check Voltage
Before starting the unit compare the supplied voltage
with the unit’s nameplate voltage and the motor voltage.
Energy Recovery Wheel
First, follow the instructions for pulling the energy
recovery cassette halfway out of the unit.
Air Seals — turn the energy recovery wheel by hand to
verify free operation. Check that the air seals, located
around the outside of the wheel and across the center
(both sides of wheel), are secure and in good condition.
Air seals which are too tight will prevent proper rotation
of the energy recovery wheel. Recheck the air seals
for tightness. Air seal clearance may be checked by
placing a sheet of paper, like a feeler gauge, against
the wheel face. To adjust the air seals, loosen all eight
seal retaining screws. These screws are located on the
bearing support that spans the length of the cassette
through the wheel center. Tighten the screws so the air
seals tug slightly on the sheet of paper as the wheel is
turned.
Replace cassette into unit, plug in wheel drive, replace
access door and apply power. Observe that the wheel
rotates freely. If wheel does not rotate or is binding,
remove the cassette; instructions provided on page13.
Check Blower Wheel Rotation
First, hand rotate the blower to ensure that the wheel is
not rubbing against the scroll. If the blower is rotating in
the wrong direction, the unit will move some air but not
perform properly.
To check the rotation,
open the blower
access panel, which is
labeled either supply
or exhaust, and run the
blower momentarily to
determine the rotation.
Air Volume Check and Measurement
Along with the building balance, the unit’s airflow (cfm)
should be measured and compared with its rated air
volume. The MiniVent is direct drive, therefore balancing
dampers or speed controls are required for airflow
balancing. Air volume measurement must be conducted
with access doors on the unit.
The most accurate way to measure the air volume is by
using the pitot traverse method in the ductwork away
from the blower. Other methods can be used but should
be proven and accurate.
n
o
i
t
a
t
o
R
Forward Curved
To adjust the air volume, change the fan rpm or the
system static pressure. See Troubleshooting section in
this guide.
With all access panels on the unit, compare measured
amps to the motor nameplate full load amps and correct
if overamping.
Measure Motor Voltage, Amperage and Fan
RPM
All access doors must be installed, run the
measurement leads through the provided electrical
access hole in the bottom access panel of the MiniVent.
Measure and record the input voltage and motor
amperage(s).
To measure the fan rpm, the blower door will need to
be removed. Minimize measurement time because the
motor may overamp with the door removed. Do not
operate units with access doors/panels open as the
motors will overload.
With all access panels on the unit, compare measured
amps to the motor nameplate full load amps and correct
if overamping.
Routine Maintenance
WARNING
Disconnect all electrical power to the MiniVent prior
to inspection or servicing. Failure to comply with this
safety precaution could result in serious injury or
death.
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury
or death. Read the installation, operating, and
maintenance instructions thoroughly before installing
or servicing this equipment.
After the MiniVent has been put into operation, an
annual inspection and maintenance program should be
set-up to preserve reliability and performance.
The MiniVent energy recovery ventilator requires
very little maintenance. However, small problems
left unchecked, over time, could lead to loss of
performance or early motor failure. We recommend that
the unit be inspected once or twice a year.
The motor should be checked for lubrication at this
time. Lubricate only those motors which have an oil hole
provided. A few drops of all-purpose oil (SAE 20) will be
sufficient.
Fasteners and Set Screws
Any fan vibration has a tendency to loosen mechanical
fasteners. A periodic inspection should include
checking all fasteners and set screws for tightness.
Particular attention should be paid to set screws
attaching the fan wheel to the shaft and the shaft to
the bearings. Loose bearing set screws will lead to
premature failure of the fan shaft.
Energy Recovery Ventilator12
®
Page 13
Removal of Dust and Dirt
The fan motor and wheel(s) should be checked for
dust and dirt accumulation. Dirt buildup clogs cooling
openings on the motor housing and causes motor
overheating. Dirt buildup can contaminate bearing
lubricant and collect on fan wheel blades causing loss
of performance or premature failure. Cleaning can be
accomplished by brushing off any dust that may have
accumulated. Under no circumstances should motors or
bearings be sprayed with steam or water. Even filtered
units can accumulate build up and should be checked
when cleaning filters.
Maintenance to these components is achieved through
the provided access panels.
Internal Filter Maintenance
Opening the access
panels labeled “Filter
Access” provides
access to the oneinch
deep, pleated 30%
MiniVent
450
750
efficient filters. These filters should be checked regularly
and cleaned or replaced as needed.
Internal
Filter Size
14 x 202
16 x 202
Quantity
Energy Wheel
Annual inspection of the energy recovery wheel is
recommended. MiniVent units ventilating smoking
lounges and other non-clean air spaces should have
energy recovery wheel inspections more often based
upon need.
Accessing the Energy Recovery Wheel
Disconnect power to the MiniVent. Remove access
panel labeled “Energy Wheel Cassette Access”. Unplug
the wheel drive motor. Pull the cassette halfway out.
Removing the Energy Recovery Wheel
First, remove the drive belt and the collars on both
bearings. On the pulley side of the cassette remove the
four (4) fasteners that hold the bearing support channel
in place. Once the bearing support is removed the
wheel can be pulled from the cassette. To replace the
wheel reverse this procedure.
Recommended Cleaning Procedure
First, remove the energy recovery wheel by following the
instructions on this page.
Wash the segments or small wheels with a non-acid
based (evaporator) coil cleaner or alkaline detergent
solution, such as 409™ or Fantastik™. Non-acid based
coil cleaner such as KMP Acti-Clean AK-1 concentrate
in a 5% solution has been demonstrated to provide
excellent results. Do not use acid based cleaners,
aromatic solvents, temperatures in excess of 140ºF or
steam; damage to the wheel may result. Soak in the
cleaning solution until dirt, grease, and/or tar deposits
are loosened. Internal heat exchange surfaces may be
examined by separating the polymer strips by hand.
Note: Some staining of the desiccant may remain and is
not harmful to performance.
After soaking, rinse the dirty solution from the wheel
until the water runs clear. Allow excess water to drain
from the media prior to reinstalling the wheel in the
cassette. A small amount of water remaining in the
wheel will be dried out by the airflow.
Frequency of Cleaning
A regular cleaning cycle must be established for the
energy recovery wheel in order to maintain optimum
sensible and latent energy transfer. In reasonably clean
environments such as schools, offices or retail stores,
the energy recovery wheel should be inspected annually
and cleaned as needed.
For applications experiencing unusually high levels
of tobacco smoke, such as lounges, nightclubs, bars
and restaurants, washing of the energy recovery wheel
every three months may be necessary to maintain latent
energy (water vapor) transfer efficiency.
Failure to follow a regular cleaning cycle for the energy
recovery wheel can result in significant energy transfer
performance losses.
Energy Recovery Wheel Belt Drive
Drive belt(s) should be inspected annually. Normal
operation eventually causes stretching or wear on the
belt(s). Once this occurs the belt(s) should be replaced.
Replacement or spare energy wheel drive belt kits are
available and ship with their own instructions. The serial
number and date code of the energy wheel cassette are
required to obtain the proper replacement belt kit from
the factory. The energy wheel serial number and date
code are located on a label above the drive pulley on
the energy wheel cassette.
®
Energy Recovery Ventilator13
Page 14
Troubleshooting
SymptomPossible CauseCorrective Action
Unit is NOT
operating
Excessive noise
Low airflow (cfm)
Electrical
Motor
Fan wheel rubbing on inlet
Bearings
Check fuses/circuit breakers, replace if needed. Check
for On/Off switches. Check for correct supply voltage.
Check motor horsepower is correct and not tripping
overloads.
Adjust wheel and/or inlet cone. Tighten wheel hub or
bearing collars on shaft.
Replace defective bearing(s). Lubricate bearings.
Tighten collars and fasteners.
Wheel out of balanceClean, replace or rebalance.
Fan speed too lowCheck for correct rpms with catalog data.
Fan wheels are operating
backwards
Refer to Blower Wheel Rotation information on page 12.
Dirty filters or energy wheelReplace filters and/or follow the cleaning procedures.
High static pressure
Incorrect fan-to-duct connections. Make sure dampers
open appropriately. Increase fan speed
Fan speed too highCheck for correct fan rpm.
High airflow (cfm)
Low static pressure
Make sure grilles, filters and access doors are installed.
Decrease fan speed.
Air seals too tightRefer to Energy Recovery Wheel, Air Seals on page 12.
Energy wheel does
NOT turn
Energy wheel runs
intermittently
No power to wheel motor
Wheel drive belt
Wheel motor overloads are
tripping due to rubbing between
wheel and air seals.
Make sure wheel drive is plugged in/connected. Verify
power is available.
Check for loose or broken belts. Replace belts; consult
factory.
Recheck air seals, make sure they are not too tight. See
Energy Recovery Wheel, Air Seals on page 12.
Always provide the unit model and serial number when requesting parts or service information. Always check
motor amps and compare to nameplate rating.
Energy Recovery Ventilator14
®
Page 15
Optional Vari-Green® Electronically
Commutated (EC) Motor
Features
Speed control These motors can be
controlled by either the
dial on the motor or
a 0-10 VDC signal for
remote control.
Soft start – All motors feature soft-start technology
which eliminates inrush current at start-up. The motors
will reliably start at any speed setting. There will be a
four second delay between the application of power and
the motor starting.
Overload protection – If the motor becomes
overloaded, it will automatically reduce its speed until it
is no longer overloaded. This prevents the motor from
operating in the "service factor" should the motor be
misapplied.
Locked rotor protection – If the motor ever encounters
a locked-rotor scenario, the motor will automatically
shut itself down. It will try to restart up to 3 times, and if
after the 3rd time the motor will still not rotate, the motor
will not attempt to start again until power is cycled.
Thermal protection – The motors have electronic
thermal protection. If the motor temperature exceeds its
limits, it will slow itself down until the temperatures have
dropped.
Operation and Wiring
These motors can be controlled by either the dial on
the motor or a 0-10 VDC signal for remote control. The
motor will be supplied from the factory with the correct
accessory depending on what control option was
ordered.
Dial on Motor - Turn the dial with your fingers to adjust.
To increase the speed, rotate the dial clockwise. To
decrease the speed, rotate the dial counter-clockwise.
Turning the dial full CCW will turn the motor off. A 16-pin
connector with two jumper wires must be installed for
the dial to function.
0-10 VDC Signal - From 0-1.9V, the motor will be off,
and will operate within the 2-10V range. This motor
does not require 24V power for operation. For 0-10V
operation, a 16-pin connector with two wires connected
to pins 8 and 16 is required.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs.
Greenheck’s Energy Recovery Ventilators catalog, Models
ERM, MiniVent, ERV and ERVe provides additional information
describing the equipment, fan performance, available
accessories, and specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be obtained
from AMCA International, Inc. at www.amca.org.