Greenheck MiniVent User Manual

Page 1
Document 459023
Model MiniVent
®
Energy Recovery Ventilator
Installation, Operation and Maintenance Manual
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with instructions could result in personal injury and/or property damage!
Energy recovery wheels are certified by the AHRI Air-to-Air Energy Recovery Ventilation Equipment Certification Program in accordance with AHRI Standard 1060. Actual performance in packaged equipment may vary.
Certified Ratings are available in the Certified Product Directory at www.ahridirectory.org
General Safety Information
Only qualified personnel should install this system. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
DANGER
Always disconnect power before working on or near this equipment. Lock and tag the disconnect switch or breaker to prevent accidental power up.
CAUTION
When servicing the unit, the internal components may be hot enough to cause pain or injury. Allow time for cooling before servicing.
CAUTION
Precaution should be taken in explosive atmospheres.
1. Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) in Canada.
2. All moving parts must be free to rotate without striking or rubbing any stationary objects.
3. Unit must be securely and adequately grounded.
4. Do not spin fan wheel faster than maximum cataloged fan RPM. Adjustments to fan speed significantly affects motor load. If the fan RPM is changed, the motor current should be checked to make sure it is not exceeding the motor nameplate amps.
5. Do not allow the power cable to kink or come in contact with oil, grease, hot surfaces or chemicals. Replace cord immediately if damaged.
6. Verify that the power source is compatible with the equipment.
7. Never open access doors to the unit while it is running.
®
Page 2
Receiving
Upon receiving the product check to ensure all items are accounted for by referencing the delivery receipt or packing list. Inspect each crate or carton for shipping damage before accepting delivery. Alert the carrier of any damage detected. The customer will make a notation of damage (or shortage of items) on the delivery receipt and all copies of the bill of lading which is countersigned by the delivering carrier. If damaged, immediately contact your Greenheck Representative. Any physical damage to the unit after acceptance is not the responsibility of Greenheck Fan Corporation.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.
Handling
Units are to be rigged and moved by the lifting brackets provided or by the skid when a forklift is used. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of unit to resist corrosion.
Storage
Units are protected against damage during shipment. If the unit cannot be installed and operated immediately, precautions need to be taken to prevent deterioration of the unit during storage. The user assumes responsibility of the unit and accessories while in storage. The manufacturer will not be responsible for damage during storage. These suggestions are provided solely as a convenience to the user.
INDOOR — The ideal environment for the storage of
units and accessories is indoors, above grade, in a low humidity atmosphere which is sealed to prevent the entry of blowing dust, rain, or snow. Temperatures should be evenly maintained between 30°F (-1°C) and 110°F (43°C) (wide temperature swings may cause condensation and “sweating” of metal parts). All accessories must be stored indoors in a clean, dry atmosphere.
Remove any accumulations of dirt, water, ice, or snow and wipe dry before moving to indoor storage. To avoid “sweating” of metal parts allow cold parts to reach room temperature. To dry parts and packages use a portable electric heater to get rid of any moisture build up. Leave coverings loose to permit air circulation and to allow for periodic inspection.
The unit should be stored at least 3½ in. (89 mm) off the floor on wooden blocks covered with moisture proof paper or polyethylene sheathing. Aisles between parts and along all walls should be provided to permit air circulation and space for inspection.
OUTDOOR — Units designed for outdoor applications
may be stored outdoors, if absolutely necessary. Roads or aisles for portable cranes and hauling equipment are needed.
The fan should be placed on a level surface to prevent water from leaking into the unit. The unit should be elevated on an adequate number of wooden blocks so that it is above water and snow levels and has enough blocking to prevent it from settling into soft ground. Locate parts far enough apart to permit air circulation, sunlight, and space for periodic inspection. To minimize water accumulation, place all unit parts on blocking supports so that rain water will run off.
Do not cover parts with plastic film or tarps as these cause condensation of moisture from the air passing through heating and cooling cycles.
Inspection and Maintenance during Storage
While in storage, inspect fans once per month. Keep a record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate the fan wheel by hand ten to fifteen revolutions to distribute lubricant on motor. Every three months, the fan motor should be energized. If paint deterioration begins, consideration should be given to touch-up or repainting. Fans with special coatings may require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe thoroughly clean with Tectyl hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive or WD-40® or the equivalent.
REMOVING FROM STORAGE — As units are removed
from storage to be installed in their final location, they should be protected and maintained in a similar fashion, until the equipment goes into operation.
Prior to installing the unit and system components, inspect the unit assembly to make sure it is in working order.
1. Check all fasteners, set screws on the fan, wheel, bearings, drive, motor base, and accessories for tightness.
2. Rotate the fan wheel(s) by hand and assure no parts are rubbing.
®
506 (Ashland Inc.) or the equivalent. For
Energy Recovery Ventilator2
®
Page 3
Table of Contents
Dimensional Data and Weights
Dimensional Data and Weights ...................3
Service Clearances and Access Panel Locations .....4
Intake and Discharge Locations ..................4
Installation Hang Mounting with Hanging Vibration Isolators ...5
Base Mounting with Base Vibration Isolators ......6
Duct Connections ...........................6
Electrical Connections .........................7
Frost Control ...............................7
Wiring Schematics .......................... 8-9
System Start-Up
Pre-Start-Up Checklist ......................10
Unit Documentation Record ..................10
Unit Start-Up Checklist ......................11
General ..................................12
Energy Wheel .............................12
Blower Wheel Rotation ......................12
Fan RPM .................................12
Motor ....................................12
Routine Maintenance
General ..................................12
Fasteners and Set Screws ...................12
Removal of Dust and Dirt ....................12
Internal Filters .............................12
Energy Wheel Maintenance ................ 12-13
Troubleshooting ..............................14
Optional Vari-Green
®
EC Motors ................15
Maintenance Log ...................... Backcover
Our Commitment ...................... Backcover
Discharge
Intake
Side "A"
Discharge Side "A"
Front View
A
Side "B"
Back View
MiniVent A B C
450
750
All dimensions are in inches.
DISCHARGE SIDE "A"
40.2 28.6 19.9 160
45.8 35.3 23.8 240
D
G
E
INTAKE SIDE "A"
F
Intake Side "B"
Energy Wheel
C
B
Weight
(lbs.)
K
L
J
H
INTAKE SIDE "B"
N
M
FRONT VIEW
P
E
F
D
G
BACK VIEW
Q
DISCHARGE SIDE "B"
MiniVent D E F G H J K L M N P Q
450
750
All dimensions are in inches.
Intake and Discharge positions are not labeled because they are configurable by rotation of the unit about the vertical axis. The supply and exhaust can be on either side, but the intake/discharge relationship must be maintained. For example, Outdoor Air Intake = Intake Side “B”/Outdoor Air Discharge = Discharge Side “B”. The preferred configuration is to have the energy wheel motor in the exhaust airstream.
10 8 12 6 4.3 1.4 6 1.5 6 1 4.8 3.4
10 10 18 7 4 2.2 5.1 1.5 5.1 1.1 4 1.5
®
Page 4
Service Clearances and Access Panel Locations
Recommended Service Clearances
The MiniVent requires minimum clearances to perform routine maintenance, such as filter replacement, energy wheel cassette and fan inspection. Fan and motor assemblies, energy recovery wheel cassette and filter sections are provided with a service door or panel for proper component access.
MiniVent A B
450 750
All dimensions are in inches.
25 15
31 21
Intake and Discharge Locations
Intake and discharge locations are shown. Both intake locations are capable of being field relocated to suit installation needs (see optional locations).
Intake Side “A” (optional)
Access Panel Locations
1. • Outdoor and exhaust fans and motor
• Electrical connection
2. • Energy wheel cassette
• Internal filters
1
B
A
Discharge
Side “B”
1
Discharge
Side “A”
Intake
Side “A”
2
2
Cassette
Slides Out
Intake
Side “B”
Discharge Side “A”
Intake Side “A”
Discharge Side “B”
Intake Side “B”
Intake Side “B” (optional)
Changing the discharge location
Step 1 - Remove the
metal cover for optional intake by unfastening the four sheet metal screws holding it in place.
Step 2 - Hand bend flanges out to form a duct collar in the newly uncovered intake opening.
Step 3 - Hand bend flanges in on original intake and replace metal cover removed in Step 1.
Intake Cover
Intake Duct
Collar
Energy Recovery Ventilator4
®
Page 5
Installation
The system design and installation should follow accepted industry practice, such as described in the ASHRAE Handbook and SMACNA.
Minimum service clearance should be provided on the side of the unit for routine service and component removal should it become necessary.
Before beginning installation see page 3 for detail on appropriate service clearances.
Hang Mounting with Hanging Vibration Isolators
• The hanging isolator kit includes four (4) isolators
and required hardware.
• Locate the support rods as shown in the drawing.
• Assemble each isolator as shown.
B
A
C
3/8-inch threaded rod, provided by others
Nut
Hanger bracket, factory-mounted
Small flat washer
Big flat washer
Isolator
Big flat washer Small flat washer Lock washer Nut
Hanging Vibration Isolator Assembly
MiniVent-450
Nut
Hanger bracket, factory-mounted
1/2-inch threaded rod, provided by others
Lock Washer
Flat Washer
Isolator
Flat Washer
Lock Washer
Nut
MiniVent A B C
450 750
All dimensions are in inches.
37.6 26.4 19.9
43.2 33 23.8
Electrical and Fan Access Panel (underside)
Hanging Vibration Isolator Assembly
MiniVent-750
®
Page 6
Base Mounting with Base Vibration Isolation
• The base isolators kit includes four (4) isolators, four (4) brackets and required hardware.
• Rotate the MiniVent 180 degrees, so the electrical and fan component panel is accessible from the top. The corners, where the brackets are fastened, are now closest to the mounting surface.
• Assemble and mount the isolators as shown in the figures below.
Note: The hanging and base mounting brackets are fastened to the same unit corners.
Electrical
and
Fan Access Panel
Duct Connections
Examples of good and poor fan-to-duct connections are shown below. Airflow out of the fan should be directed straight or curve the same direction as the fan wheel rotates. Poor duct installation will result in low airflow, loud noise and excessive vibrations.
4x Wheel Diameter
MiniVent
POOR
Less
than 4x Wheel Diameter
Recommended Discharge Duct Size and Length
MiniVent
450
750
All dimensions are in inches.
ERV
Blower Size
8 10 x 8 32
10 10 x 10 40
Duct
Size
GOOD
GOOD
Straight Duct
Length
Factory-mounted bracket
3/8-inch bolt
Flat washer
Base Vibration Isolator Assembly
Lock washer
Isolator
Assembled and Mounted Isolator Detail
Energy Recovery Ventilator6
®
Page 7
Electrical Connections
Before connecting power to the unit, read and understand the following instructions and wiring diagrams. Complete wiring diagrams are attached inside the blower door of the unit.
All wiring should be done in accordance with the National Electrical Code ANSI/NFPA 70 latest edition and any local codes that may apply. In Canada, wiring should be done in accordance with the Canadian Electrical Code. The equipment must be properly grounded.
Caution
If any of the original wire must be replaced, the replacement wire must have a temperature rating of at least 105ºC.
DANGER
High voltage electrical input is required for this equipment. This work should be performed by a qualified electrician.
Electrical Connection Location
MiniVent A B
450
750
All dimensions are in inches.
Electrical Connection
21.875 12.5
28.375 15.5
B
Frost Control
Extremely cold outdoor air temperatures can cause moisture condensation and frosting on the energy recovery wheel. Frost control is an optional feature that will prevent/control wheel frosting.
1. Timed Exhaust frost control
This option is provided with a thermodisc mounted in the outdoor air intake compartment.
Timed exhaust frost control includes a timer in addition to the thermodisc. When timed exhaust frost control is initiated, the timer will turn the supply blower off. Time exhaust using default timer setting will shut down the supply fan for 5 minutes every 30 minutes to allow exhaust to defrost energy wheel. Use the test procedure for troubleshooting.
Frost Control Test Procedure
1. Remove power from unit.
2. Jumper the temperature indicating thermodisc in the unit control center. Thermodisc has a pre-set temperature of 5ºF.
3. Set the frost control timer scale for T1 and T2 to 1m. Set the timer settings for T1 and T2 to 10.
4. Add power to the unit. Blower should cycle on for one minute, then turn off for one minute.
5. Remove power from unit and remove jumpers that were placed. Re-set timer settings.
• T1 timer setting set to 5 and timer scale set to
10m for 5 minutes of wheel off time.
• T2 timer setting set to 5 and timer scale set to
1h for 30 minutes of wheel on time
A
Wheel and Filter Access
Sequence for wiring MiniVent unit:
1. The unit’s nameplate contains the voltage and total amperage required. The wire supplying power to the unit should be sized accordingly.
2. The main power line should be connected to the appropriate terminal blocks.
Power may be routed to the MiniVent through the
opening on the underside of the unit. The locations for the opening are provided in the figure to the right.
3. Refer to the wiring diagrams in this manual or in the unit for controlling the MiniVent.
Timer Scale
Timer
Settings
Timer Scale
T1
T2
®
Page 8
Wiring Schematics
Timed Exhaust Frost Control
TR
115/208/230V PRIMARY
24V SECONDARY
R
VIOLET
RED
ORANGE
BLACK
GROUND
115
208
230
L2
FIELD TO CONNECT
TO TERMINAL DESIGNATED
WITH UNIT LINE VOLTAGE
CONNECT TERMINAL 15 FROM COMPONENT "T1"
WITH LINE VOLTAGE
PURPLE
L1
L2
FIELD MOUNT
IN OUTDOOR
AIR DUCT
COM
NO
A1
TH
B1
T1
A2
Potentiometer Control
(VERIFY MAIN UNIT POWER ON UNIT NAMEPLATE)
MAIN UNIT POWER -115/208/230/60/1
L1
L2
L2 L1
GROUND
YELLOW
REMOTE PANEL
BLACK
BLACK
T1
16
15
ENERGY WHEEL MOTOR
M1
T A OR B
SEE NOTE #3
L1
MAIN UNIT INTERNAL JUNCTION BOX
SEE NOTE#2
SEE NOTE#2
BLACK
A
WHITE
BLACK
B
WHITE
BLOWER MOTOR A
MA
BLOWER MOTOR B
MB
Legend MA Blower Motor A MB Blower Motor B M1 Energy Wheel Motor M2 Exhaust Blower Motor M3 Supply Blower Motor T1 Frost Control Timer
Typical Settings: t1 (OFF) = 5 min.
t2 (ON) = 30 min.
TH Thermostat; non-adjustable 5° setting.
Required to be mounted in outdoor air duct.
TR Transformer
Energy Recovery Ventilator8
®
Page 9
Wiring Schematics
0-10 VDC Fan Motor Control
(VERIFY MAIN UNIT POWER ON UNIT NAMEPLATE)
MAIN UNIT POWER -110/50/1-115/60/1
L2 (NEUTRAL)
L1
GROUND
L2
L1
24 VAC
0-10VDC
SEE NOTE#1
SEE NOTE#2
24 VAC
0-10VDC
SEE NOTE#1
SEE NOTE#2
24v
A-
A+
A
24v
B-
B+
B
BLACK
BLACK
BLACK
WHITE
RED
BLACK
WHITE
BLACK
WHITE
RED
BLACK
WHITE
Solid State Speed Motor Control
(VERIFY MAIN UNIT POWER ON UNIT NAMEPLATE)
MAIN UNIT POWER -115/208/230/60/1
L2
L1
GROUND
ENERGY WHEEL MOTOR
M1
BLOWER MOTOR A
MA
BLOWER MOTOR B
MB
L2
L1
SEE NOTE#2
SPEED CONTROLLER
A
SPEED CONTROLLER
SEE NOTE#2
B
BLOWER A
ON OFF
BLOWER B
ON OFF
A2
B2
BLACK
BLACK
BLACK
BLACK
ENERGY WHEEL MOTOR
M1
BLOWER MOTOR A
MA
BLOWER MOTOR B
MB
Legend MA Blower Motor A MB Blower Motor B M1 Energy Wheel Motor M2 Exhaust Blower Motor M3 Supply Blower Motor T1 Frost Control Timer
Typical Settings: t1 (OFF) = 5 min.
t2 (ON) = 30 min.
TH Thermostat; non-adjustable 5° setting.
Required to be mounted in outdoor air duct.
TR Transformer
®
Page 10
System Start-Up
DANGER
Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit to OFF at disconnect switch(es). Unit may have multiple power supplies.
CAUTION
Use caution when removing access panels or other unit components, especially while standing on a ladder or other potentially unsteady base. Access panels and unit components can be heavy and serious injury may occur.
CAUTION
Do not operate without the filters and birdscreens installed. They prevent the entry of foreign objects such as leaves, birds, etc.
CAUTION
Do not run unit during construction phase. Damage to internal components may result and void warranty.
WARNING
• Unit was factory tested. All blowers, fans, and compressors are set-up to run correctly when supplied power. If any one fan is running backwards or the compressor is making loud noises, immediately turn off the power. Switch two leads on the incoming power to the disconnect. This will ensure proper operation of the unit. Failure to comply may damage the compressors and void the warranty.
• Do not jumper any safety devices when operating the unit. This may damage components within or cause serious injury or death.
Every installation requires a comprehensive start-up to ensure proper operation of the unit. As part of that process, the following checklist must be completed and information recorded. Starting up the unit in accordance with this checklist will not only ensure proper operation, but will also provide valuable information to personnel performing future maintenance. Should an issue arise which requires factory assistance, this completed document will allow unit experts to provide quicker resolve. Qualified personnel should perform start-up to ensure safe and proper practices are followed.
Unit Documentation Record
Unit Model No. ___________________________________
Unit Serial No. _____________________________________
Energy Wheel Date Code ___________________________
Start-Up Date _____________________________________
Start-Up Personnel Name __________________________
Start-Up Company _________________________________
Phone Number ____________________________________
Pre-Start-Up Checklist
Disconnect and lock-out all power switches. Remove any foreign objects that are located in the
energy recovery unit.
Check all fasteners, set-screws, and locking collars
on the fans, bearings, drives, motor bases and accessories for tightness.
Rotate the fan wheels and energy recovery wheels
by hand and ensure no parts are rubbing.
Check the fan belt drives for proper alignment and
tension.
Filters can load up with dirt during building
construction. Replace any dirty pleated filters and clean the aluminum mesh filters in the intake hood.
Verify that non-motorized dampers open and close
properly.
Check the tightness of all factory wiring
connections.
Verify control wire gauge. Verify diameter seal settings on the energy recovery
wheel.
SPECIAL TOOLS
• Volt meter
• Incline manometer or equivalent
• Tachometer
• Amperage meter
Energy Recovery Ventilator10
®
Page 11
Start-Up Checklist
Line Voltage. Check at unit disconnect.
L1-L2 Volts
Motor Amp Draw
Supply Motor Amps L1 Amps L2 Amps
Exhaust Motor Amps L1 Amps L2 Amps
Fan RPM
Supply Fan RPM
Exhaust Fan RPM
Correct fan rotation direction?
Supply Fan Yes / No
Exhaust Fan Yes / No
Energy Wheel Motor
L1 Amps L2 Amps
Outdoor Air Temperature Deg F
Return Air Temperature Deg F
Outdoor Air Relative Humidity % RH
Return Air Relative Humidity % RH
®
Energy Recovery Ventilator 11
Page 12
System Start-Up - continued
Airflow
General
Check all fasteners and set screws for tightness. This is especially important for bearings and fan wheels Also, if dampers are not motorized, check that they open and close without binding.
Check Voltage
Before starting the unit compare the supplied voltage with the unit’s nameplate voltage and the motor voltage.
Energy Recovery Wheel
First, follow the instructions for pulling the energy recovery cassette halfway out of the unit.
Air Seals — turn the energy recovery wheel by hand to verify free operation. Check that the air seals, located around the outside of the wheel and across the center (both sides of wheel), are secure and in good condition.
Air seals which are too tight will prevent proper rotation of the energy recovery wheel. Recheck the air seals for tightness. Air seal clearance may be checked by placing a sheet of paper, like a feeler gauge, against the wheel face. To adjust the air seals, loosen all eight seal retaining screws. These screws are located on the bearing support that spans the length of the cassette through the wheel center. Tighten the screws so the air seals tug slightly on the sheet of paper as the wheel is turned.
Replace cassette into unit, plug in wheel drive, replace access door and apply power. Observe that the wheel rotates freely. If wheel does not rotate or is binding, remove the cassette; instructions provided on page13.
Check Blower Wheel Rotation
First, hand rotate the blower to ensure that the wheel is not rubbing against the scroll. If the blower is rotating in the wrong direction, the unit will move some air but not perform properly.
To check the rotation, open the blower access panel, which is labeled either supply or exhaust, and run the blower momentarily to determine the rotation.
Air Volume Check and Measurement
Along with the building balance, the unit’s airflow (cfm) should be measured and compared with its rated air volume. The MiniVent is direct drive, therefore balancing dampers or speed controls are required for airflow balancing. Air volume measurement must be conducted with access doors on the unit.
The most accurate way to measure the air volume is by using the pitot traverse method in the ductwork away from the blower. Other methods can be used but should be proven and accurate.
n
o
i
t
a
t
o
R
Forward Curved
To adjust the air volume, change the fan rpm or the system static pressure. See Troubleshooting section in this guide.
With all access panels on the unit, compare measured amps to the motor nameplate full load amps and correct if overamping.
Measure Motor Voltage, Amperage and Fan RPM
All access doors must be installed, run the measurement leads through the provided electrical access hole in the bottom access panel of the MiniVent. Measure and record the input voltage and motor amperage(s).
To measure the fan rpm, the blower door will need to be removed. Minimize measurement time because the motor may overamp with the door removed. Do not
operate units with access doors/panels open as the motors will overload.
With all access panels on the unit, compare measured amps to the motor nameplate full load amps and correct if overamping.
Routine Maintenance
WARNING
Disconnect all electrical power to the MiniVent prior to inspection or servicing. Failure to comply with this safety precaution could result in serious injury or death. Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating, and maintenance instructions thoroughly before installing or servicing this equipment.
After the MiniVent has been put into operation, an annual inspection and maintenance program should be set-up to preserve reliability and performance.
The MiniVent energy recovery ventilator requires very little maintenance. However, small problems left unchecked, over time, could lead to loss of performance or early motor failure. We recommend that the unit be inspected once or twice a year.
The motor should be checked for lubrication at this time. Lubricate only those motors which have an oil hole provided. A few drops of all-purpose oil (SAE 20) will be sufficient.
Fasteners and Set Screws
Any fan vibration has a tendency to loosen mechanical fasteners. A periodic inspection should include checking all fasteners and set screws for tightness. Particular attention should be paid to set screws attaching the fan wheel to the shaft and the shaft to the bearings. Loose bearing set screws will lead to premature failure of the fan shaft.
Energy Recovery Ventilator12
®
Page 13
Removal of Dust and Dirt
The fan motor and wheel(s) should be checked for dust and dirt accumulation. Dirt buildup clogs cooling openings on the motor housing and causes motor overheating. Dirt buildup can contaminate bearing lubricant and collect on fan wheel blades causing loss of performance or premature failure. Cleaning can be accomplished by brushing off any dust that may have accumulated. Under no circumstances should motors or bearings be sprayed with steam or water. Even filtered units can accumulate build up and should be checked when cleaning filters.
Maintenance to these components is achieved through the provided access panels.
Internal Filter Maintenance
Opening the access panels labeled “Filter Access” provides access to the oneinch deep, pleated 30%
MiniVent
450 750
efficient filters. These filters should be checked regularly and cleaned or replaced as needed.
Internal
Filter Size
14 x 20 2
16 x 20 2
Quantity
Energy Wheel
Annual inspection of the energy recovery wheel is recommended. MiniVent units ventilating smoking lounges and other non-clean air spaces should have energy recovery wheel inspections more often based upon need.
Accessing the Energy Recovery Wheel
Disconnect power to the MiniVent. Remove access panel labeled “Energy Wheel Cassette Access”. Unplug the wheel drive motor. Pull the cassette halfway out.
Removing the Energy Recovery Wheel
First, remove the drive belt and the collars on both bearings. On the pulley side of the cassette remove the four (4) fasteners that hold the bearing support channel in place. Once the bearing support is removed the wheel can be pulled from the cassette. To replace the wheel reverse this procedure.
Recommended Cleaning Procedure
First, remove the energy recovery wheel by following the instructions on this page.
Wash the segments or small wheels with a non-acid based (evaporator) coil cleaner or alkaline detergent solution, such as 409™ or Fantastik™. Non-acid based coil cleaner such as KMP Acti-Clean AK-1 concentrate in a 5% solution has been demonstrated to provide excellent results. Do not use acid based cleaners, aromatic solvents, temperatures in excess of 140ºF or steam; damage to the wheel may result. Soak in the cleaning solution until dirt, grease, and/or tar deposits are loosened. Internal heat exchange surfaces may be examined by separating the polymer strips by hand.
Note: Some staining of the desiccant may remain and is not harmful to performance.
After soaking, rinse the dirty solution from the wheel until the water runs clear. Allow excess water to drain from the media prior to reinstalling the wheel in the cassette. A small amount of water remaining in the wheel will be dried out by the airflow.
Frequency of Cleaning
A regular cleaning cycle must be established for the energy recovery wheel in order to maintain optimum sensible and latent energy transfer. In reasonably clean environments such as schools, offices or retail stores, the energy recovery wheel should be inspected annually and cleaned as needed.
For applications experiencing unusually high levels of tobacco smoke, such as lounges, nightclubs, bars and restaurants, washing of the energy recovery wheel every three months may be necessary to maintain latent energy (water vapor) transfer efficiency.
Failure to follow a regular cleaning cycle for the energy recovery wheel can result in significant energy transfer performance losses.
Energy Recovery Wheel Belt Drive
Drive belt(s) should be inspected annually. Normal operation eventually causes stretching or wear on the belt(s). Once this occurs the belt(s) should be replaced.
Replacement or spare energy wheel drive belt kits are available and ship with their own instructions. The serial number and date code of the energy wheel cassette are required to obtain the proper replacement belt kit from the factory. The energy wheel serial number and date code are located on a label above the drive pulley on the energy wheel cassette.
®
Energy Recovery Ventilator 13
Page 14
Troubleshooting
Symptom Possible Cause Corrective Action
Unit is NOT operating
Excessive noise
Low airflow (cfm)
Electrical
Motor
Fan wheel rubbing on inlet
Bearings
Check fuses/circuit breakers, replace if needed. Check for On/Off switches. Check for correct supply voltage.
Check motor horsepower is correct and not tripping overloads.
Adjust wheel and/or inlet cone. Tighten wheel hub or bearing collars on shaft.
Replace defective bearing(s). Lubricate bearings. Tighten collars and fasteners.
Wheel out of balance Clean, replace or rebalance.
Fan speed too low Check for correct rpms with catalog data.
Fan wheels are operating backwards
Refer to Blower Wheel Rotation information on page 12.
Dirty filters or energy wheel Replace filters and/or follow the cleaning procedures.
High static pressure
Incorrect fan-to-duct connections. Make sure dampers open appropriately. Increase fan speed
Fan speed too high Check for correct fan rpm.
High airflow (cfm)
Low static pressure
Make sure grilles, filters and access doors are installed. Decrease fan speed.
Air seals too tight Refer to Energy Recovery Wheel, Air Seals on page 12.
Energy wheel does NOT turn
Energy wheel runs intermittently
No power to wheel motor
Wheel drive belt
Wheel motor overloads are tripping due to rubbing between wheel and air seals.
Make sure wheel drive is plugged in/connected. Verify power is available.
Check for loose or broken belts. Replace belts; consult factory.
Recheck air seals, make sure they are not too tight. See Energy Recovery Wheel, Air Seals on page 12.
Always provide the unit model and serial number when requesting parts or service information. Always check motor amps and compare to nameplate rating.
Energy Recovery Ventilator14
®
Page 15
Optional Vari-Green® Electronically Commutated (EC) Motor
Features
Speed control ­These motors can be controlled by either the dial on the motor or a 0-10 VDC signal for remote control.
Soft start – All motors feature soft-start technology which eliminates inrush current at start-up. The motors will reliably start at any speed setting. There will be a four second delay between the application of power and the motor starting.
Overload protection – If the motor becomes overloaded, it will automatically reduce its speed until it is no longer overloaded. This prevents the motor from operating in the "service factor" should the motor be misapplied.
Locked rotor protection – If the motor ever encounters a locked-rotor scenario, the motor will automatically shut itself down. It will try to restart up to 3 times, and if after the 3rd time the motor will still not rotate, the motor will not attempt to start again until power is cycled.
Thermal protection – The motors have electronic thermal protection. If the motor temperature exceeds its limits, it will slow itself down until the temperatures have dropped.
Operation and Wiring
These motors can be controlled by either the dial on the motor or a 0-10 VDC signal for remote control. The motor will be supplied from the factory with the correct accessory depending on what control option was ordered.
Dial on Motor - Turn the dial with your fingers to adjust. To increase the speed, rotate the dial clockwise. To decrease the speed, rotate the dial counter-clockwise. Turning the dial full CCW will turn the motor off. A 16-pin connector with two jumper wires must be installed for the dial to function.
0-10 VDC Signal - From 0-1.9V, the motor will be off, and will operate within the 2-10V range. This motor does not require 24V power for operation. For 0-10V operation, a 16-pin connector with two wires connected to pins 8 and 16 is required.
®
Energy Recovery Ventilator 15
Page 16
Maintenance Log
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date ___________________Time _____________ AM/PM
Notes: ___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs.
Greenheck’s Energy Recovery Ventilators catalog, Models ERM, MiniVent, ERV and ERVe provides additional information describing the equipment, fan performance, available accessories, and specification data.
AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety information. This publication can be obtained from AMCA International, Inc. at www.amca.org.
®
Phone: 715.359.6171 • Fax: 715.355.2399 • Parts: 800.355.5354 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
459023 • MiniVent, Rev. 12, April 2015 Copyright 2015 © Greenheck Fan Corporation16
Loading...