Please read and save these instructions. Read carefully before attempting to operate or maintain the product
described. Protect yourself and others by observing all safety practices. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
TAP v2.10
Version Date: 4/1/14
Introduction
Program Features
The microprocessor controller offers improved control
through easy monitoring and adjustment of unit
parameters by way of a lighted graphical display and a
push-button keypad.
Pre-Programmed Operating Sequences
The controller has been pre-programmed to offer
multiple control sequences to provide tempered
air. Factory default settings allow for easy setup
and commissioning. The sequence parameters are
fully adjustable. Refer to the Sequence of Operation
beginning on page 2 for details.
BMS Communication
With the addition of an optional BMS Communication
card, the user can remotely adjust set points, view
unit status points and alarms. The microprocessor
controller is capable of communicating over several
protocols:
• BACnet® MSTP • LonWork®
• BACnet® IP/Ethernet • Modbus
See Points List on pages 36 and 37 for a complete list
of BMS points.
Internal Time Clock
The controller has an internal programmable time
clock, allowing the user to add up to seven different
occupancy schedules. The user may also add Holidays
for additional energy savings. The time clock option
also has morning warm-up capability for optional
comfort at the time of occupancy.
Alarm Management
The microprocessor controller will monitor the unit
conditions for alarm conditions. Upon detecting an
alarm, the controller will record the alarm description,
time, date, available temperatures, and unit status for
user review. A digital output is reserved for remote
alarm indication. Alarms are also communicated via
BMS (if equipped).
Occupancy Modes
The microprocessor controller offers three modes of
determining occupancy: a dry contact, the internal time
clock or the BMS. If in the Unoccupied mode the unit
will either be shut down, or will cycle on to maintain
adjustable unoccupied room temperature and humidity
set points.
Remote Display Panel (Optional)
A touchpad display panel allows for remote monitoring
and adjustment of parameters, allowing ease of control
access without going outdoors.
WARNING
Electrical shock hazard. Can cause personal injury
or equipment damage. Service must be performed
only by personnel that are knowledgeable in the
operation of the equipment being controlled.
The microprocessor controller can be configured for air
handler, energy recovery, dedicated outdoor air system
and make-up air applications. Each application utilizes
similar technologies for heating and cooling: chilled
water, hot water, indirect gas, electric heat, packaged
DX cooling, and packaged DX cooling with digital
scrolls. All set points, lockouts and delays are user
adjustable via the keypad display.
General Operation
UNIT START COMMAND: The microprocessor
controller requires a digital input to enable operation.
The unit can then be commanded on or off by this
digital input, the BMS or internal time clock.
• Initial delay
• Factory mounted and wired dampers are powered, if equipped. (Outdoor air, exhaust air, and recirculation
air dampers).
• Exhaust fan and energy recovery wheel start after a
10 second delay, if equipped.
• Supply fan starts 15 seconds after the exhaust fan.
• Tempering operation begins (see modes below).
UNIT STOP COMMAND (OR DE-ENERGIZED):
• Supply fan, exhaust fan, tempering, and wheel are
de-energized.
• Outdoor air and Exhaust air dampers are closed after
a 10 second delay. Recirculation air dampers spring
open.
OCCUPIED/UNOCCUPIED MODES: The
microprocessor controller offers three modes of
determining occupancy: a dry contact, the internal time
clock or the BMS. When in the unoccupied mode, the
unit can be configured to shut down, or cycle on to
maintain the unoccupied room set points. The unit can
be temporarily overridden to the occupied mode via a
digital input or the keypad display.
The internal time clock can be configured with morning
warm-up to bring the space to the occupied set point
prior to occupancy.
• Occupied Mode:
- Exhaust fan on, if equipped
- Supply fan on
- Heating (refer to Heating section)
- Cooling (refer to Cooling section)
- Energy Recovery Wheel control (refer to
Energy Recover Wheel section), if equipped.
- Damper control (refer to Outdoor Air and
Recirculated Air section), if equipped.
• Unoccupied Mode (Unit Off): Unit remains off when
in unoccupied mode.
• Unoccupied Mode (Cycle on Room): Optional
unoccupied mode when there is an unoccupied
recirculation damper and room temperature and/
or humidity sensor(s) connected to the controller.
The unit will cycle on to maintain unoccupied room
set points if there is a call for unoccupied heating,
cooling or dehumidification.
DDC Controller for Tempered Air Products
2
®
Sequence of Operation
- Exhaust fan off, if equipped.
- Supply fan off.
- Recirculation air damper open.
- OA damper closed.
- Tempering operations begin (see modes below)
Set Point Control (Occupied)
Supply air temperature set point can be configured
as constant, or can be reset by either outside air
temperature, or room temperature set point. If equipped
with BMS communications, the user can also directly
command the supply temperature set point, or room
temperature set point (if equipped with a room temp
sensor).
• Outdoor Air Temperature Reset Function: The
controller will default to supply temperature reset
based on outdoor air temperature. The controller will
monitor the OA temperature and reset the supply
temperature set point based upon the outdoor air
reset function.
• Room Temperature Reset (optional): With a
room temperature sensor, the controller will adjust
the supply air temperature set point between the
minimum (55°F) and maximum (90°F), to satisfy the
desired room temperature.
Set Point Control (Unoccupied)
When equipped with an unoccupied recirculation
damper and optional room temperature and/or
humidity sensors, the unit will cycle on to maintain the
unoccupied room set points.
• Unoccupied Heating: If equipped with heating,
the unit is enabled when the room temperature is
less than the unoccupied heating set point minus
differential (65°F-5°F). The supply air temperature
set point will be set to the supply maximum reset
limit (90°F). The unit cycles off when the room
temperature reaches the unoccupied heating set
point.
• Unoccupied Cooling: If equipped with cooling,
the unit is enabled when the room temperature is
greater than the unoccupied cooling set point plus
differential (80°F+5°F). The supply air temperature
set point will be set to the supply minimum reset
limit (55°F). The unit cycles off when the room
temperature reaches the unoccupied cooling set
point.
• Unoccupied Dehumidification: If equipped with
cooling, the unit is enabled when the room relative
humidity exceeds the unoccupied room relative
humidity set point plus differential (50%+5%), or
when dehumidistat contact indicates excessive
humidity. The supply air temperature set point will be
set to the equivalent occupied supply set point.
• Morning Warm-Up: The unit uses an algorithm
involving space temperature and the heating /cooling
rate of the previous day to determine the time
required to efficiently temper the space to occupied
set point prior to occupancy.
Heating
The heating is controlled to maintain the supply
temperature set point. The heating will be locked out
when the outside air temperature is above the heating
lockout (70°F).
• Indirect Gas Furnace: Microprocessor controller
will modulate the indirect gas furnace to maintain the
supply temperature set point.
• Hot Water Coil: Microprocessor controller will
modulate a hot water valve (provided by others)
to maintain the supply temperature set point. Coil
freeze protection must be provided by others in
the field!
• Electric Heater: Microprocessor controller will
modulate an electric heater to maintain the supply
temperature set point.
• Heat Pump: Microprocessor controller will stage
compressor(s) to maintain the supply air set point.
This signal will come wired to the factory provided
heat pump module. All external water valves and
valve controls are provided, wired and mounted
by others in the field, including freeze protection.
Cooling
The cooling is controlled to maintain the supply
temperature set point. The mechanical cooling will be
locked out when the outside air temperature is below
the cooling lockout (55°F).
• Chilled Water: Microprocessor controller will
modulate a chilled water valve (provided by others) to
maintain supply air set point. Coil Freeze protection
must be provided by others in the field!
• Packaged DX Cooling (Standard Scroll):
Microprocessor controller will control stages of
cooling to maintain the supply air set point.
• Packaged DX Cooling (Digital Scroll):
Microprocessor controller will modulate the digital
scroll to maintain the supply air temperature set
point.
• Heat Pump: Microprocessor controller will power
the reversing valve within the heat pump module
to direct the refrigerant flow for airside cooling.
The cooling is controlled to maintain the supply
temperature set point. All external water valves and
valve controls are provided, wired and mounted
by others in the field, including freeze protection.
®
DDC Controller for Tempered Air Products
3
Economizer
If the application requires cooling, and the outdoor
air conditions are suitable for free cooling, the
controller may enter the economizer state. If the unit is
economizing and the discharge temperature set point is
not being met, the controller may bring on mechanical
cooling. If equipped with a modulating outdoor air and
recirculated air damper, the dampers will modulate
between the minimum OA and maximum positions to
maintain the supply temperature set point. If equipped
with an energy wheel, see Energy Recovery Wheel
Sequence.
• Temperature: The economizer will be locked out
when:
- The outside air is less than the economizer low
lockout (40°F).
- The outside air is greater than the economizer
high lockout (65°F).
- The unit is operating in dehumidification mode.
- There is a call for heating.
• Temperature/Dew Point: The economizer will be
locked out when:
- The outside air is less than the economizer low
lockout (40°F dry-bulb).
- The outside air is greater than the economizer
high lockout (75°F dry-bulb).
- The outside air is greater than the economizer
high dew point lockout (55°F dew point)
- The unit is operating in dehumidification mode.
- There is a call for heating.
Dehumidification
The cooling is controlled to maintain the cold coil set
point. The dehumidification sequence will be locked out
when the OA is less than the dehumidification lockout
(10°F) above the cold coil set point. If equipped with
BMS communications, the user can also directly set the
cold coil leaving air set point.
• Optional Room Dehumidistat: The room
dehumidistat is a field mounted sensor that monitors
the relative humidity (RH) of the room. If the RH
exceeds set point, the dehumidistat will reset the
cold coil set point to the minimum (50°F). Once the
room dehumidistat is satisfied, the cold coil set point
will return to the maximum (55°F).
• Optional Room Relative Humidity Sensor: The
controller will adjust the cold coil leaving air
temperature set point between the minimum (50°F)
and maximum (55°F) set points, to satisfy the desired
room relative humidity set point.
Reheat
While the unit is in dehumidification mode, the supply
air can be reheated via Primary Heating Source, On/Off
Hot Gas Reheat or Modulating Hot Gas Reheat.
• Primary Heating Source: The main heating source
is enabled to reheat the air to meet the supply
temperature set point. (Except heat pump). The
DDC Controller for Tempered Air Products
4
primary heat source may also be configured to act as
secondary reheat.
• Modulating Hot Gas Reheat (bypass damper): The
microprocessor controller will open the On/Off hot
gas reheat valve, and modulate the Hot Gas Reheat
bypass damper to maintain the supply temperature
set point.
• Modulating Hot Gas Reheat (valve): The
microprocessor controller will modulate the hot gas
reheat valve to maintain the supply temperature set
point.
• On/Off Hot Gas Reheat: The microprocessor
controller will open the On/Off hot gas reheat valve to
maintain the supply temperature set point.
Supply Fan VFD Sequence
If the factory has installed a VFD and wired it to the
controller, it is intended to operate at a constant speed
during operation. This speed needs to be set during
test and balance of the unit. If equipped with BMS
communications, the user can also directly command
the supply fan speed.
• Optional Room CO2 Sensor: The controller will
modulate the supply fan based upon a comparison
of the CO2 set point to the actual CO2 levels
reported from the sensor. Mechanical high static
protection cutoffs must be installed by others
to protect the system and equipment from
over-pressurization.
• Optional Duct Static Pressure Sensor: The
controller will modulate the supply fan based upon a
comparison of the duct static pressure set point to
the actual duct static pressure level reported from
the sensor. Mechanical high static protection
cutoffs must be installed by others to protect
the system and equipment from overpressurization. The manufacturer does not
assume responsibility for this.
• Optional Building Static Pressure Sensor: The
controller will modulate the supply fan based upon a
comparison of the building static pressure set point
to the actual building static pressure level reported
from the sensor.
• Optional Single Zone VAV (SZ): The controller will
control the supply air temperature and supply fan
speed to maintain the room temperature set point.
This sequence requires a room temperature sensor.
Heating - When the room requires heating, the
controller will reset the supply air temperature set
point up to the maximum (90°F) while increasing the
supply fan speed up to its maximum heating speed.
Cooling - When the room requires cooling, the
controller will first reset the supply air temperature
set point down to the minimum (55°F) while the
supply fan remains at the minimum cooling speed.
After a time delay, the supply fan speed will increase
up to its maximum cooling speed to maintain the
room temperature set point.
®
Exhaust Fan VFD Sequence
If the factory has installed a VFD and wired it to the
controller, it is intended to operate at a constant speed
during operation. This speed needs to be set during
test and balance of the unit. If equipped with BMS
communications, the user can also directly command
the exhaust fan speed.
• Optional Building Static Pressure Sensor: The
controller will modulate the exhaust fan based upon
a comparison of the building static pressure set point
to the actual building static pressure level reported
from the sensor.
• Optional Supply Fan Tracking: The controller will
proportionally modulate the exhaust fan based upon
the supply fan speed.
• Optional Outdoor Air Damper Tracking: The
controller will proportionally modulate the exhaust fan
based upon the outdoor air damper position.
Outdoor Air and Recirculated (Recirc) Air
Damper Control
If equipped with a modulating outdoor air and
recirculated air damper, the recirculated air damper will
operate inverse of the outdoor air damper. The outdoor
air damper will open to a Minimum Outdoor Air Position
(Min OA) when in occupied mode. If the controller
is configured to modulate the supply fan speed, the
minimum and maximum OA positions can be reset
based on supply fan speed. If equipped with BMS
communications, the user can also directly reset the
damper position up to the maximum OA position.
• Optional Room CO2 Sensor: The controller will
proportionally modulate the OA/RA dampers based
upon a comparison of the CO2 set point to the actual
CO2 level reported from the sensor. As the CO2 level
rises, the controller will proportionally modulate the
outdoor air damper open, between the minimum and
maximum OA position.
• Optional Building Pressure: The OA/RA dampers
will modulate based upon the signal from a building
static pressure sensor. The controller will modulate
the dampers, between the minimum and maximum
OA positions, based upon a comparison of the
building static pressure set point to the actual
building static pressure level reported from the
sensor.
Energy Recovery Wheel Sequences
Economizer (optional): If the unit is equipped with an
energy recovery wheel, the economizer will modulate/
stop the energy wheel to achieve free cooling.
• Stop Wheel: When economizer mode is enabled
and there is a signal for cooling, the wheel will stop
rotating to allow free cooling.
• Modulate Wheel: When economizer mode is
enabled and there is a signal for cooling, the
®
controller modulates wheel speed to maintain the
supply temperature set point.
• Energy Wheel Bypass Dampers (optional): During
normal operation, the dampers shall remain closed
to allow full operation of the energy wheel. During
economizer sequences, the dampers will be open to
bypass the energy wheel.
Frost Control (optional): The microprocessor
controller will activate the frost control method when
the outdoor air temperature is less than the defrost set
point (5°F) and the wheel pressure switch is closed, due
to a high wheel pressure drop. Once either the pressure
drop decreases below the pressure switch point, or the
outdoor air temperature increases, the unit will resume
normal operation.
• Electric Preheater: When frosting is occurring, the
preheater is energized to defrost the wheel.
• Modulate Wheel: When frosting is occurring, the
wheel slows to allow defrosting to occur.
• Cycle Wheel: When frosting is occurring, the
energy wheel is cycled off for a defrost cycle time
(2 minutes). After the defrost cycle time, the wheel
is re-energized to continue normal operation. The
controller will not allow another defrost cycle for a
minimum normal operating cycle time (5 minutes).
• Timed Exhaust: When frosting is occurring, the
supply fan is cycled off along with the tempering for
a defrost cycle time (5 minutes). The exhaust fan
will continue to run, allowing the warm exhaust air
to defrost the wheel. After the defrost cycle time,
the supply fan and tempering are re-energized to
continue normal operation. The controller will not
allow another defrost cycle for a minimum normal
operating cycle time (30 minutes).
Alarms
The microprocessor controller includes a digital output
for remote indication of an alarm condition. Possible
alarms include:
• Dirty Filter Alarm: If the outside air or return air
filter differential pressure rises above the differential
pressure switch set point, the microprocessor
controller will activate an alarm.
• Supply and Exhaust Air Proving Alarm:
Microprocessor controller monitors proving switch on
each blower and displays an alarm in case of blower
failure.
• Sensor Alarm: Microprocessor controller will send
an alarm if a failed sensor is detected (temperature,
pressure, relative humidity).
• Supply Air Low Limit: If the supply air temperature
drops below the supply air low limit (35°F), the
microprocessor controller will de-energize the unit
and activate the alarm output after a preset time
delay (300s).
• Other Alarms: Wheel Rotation, High Wheel
Pressure, High/Low Refrigerant Pressure.
DDC Controller for Tempered Air Products
5
24 VAC to Controller
Small Controller Overview
input: 24V~/ V ; 50 to 60 Hz
max. power: 40 VA/15W
J1J1J24J24
G
G0
Room RH or Dehumidistat
Room Temperature Sensor
After Cold Coil Temperature Sensor
Sensor B1, B2, B3 Commons
Supply Discharge Temperature Sensor
Outdoor Air Temperature Sensor
24 VAC for Analog Outputs
Energy Wheel Analog Output
Heating Analog Output
Cooling Analog Output
Hot Gas Reheat Analog Output
Supply Fan Proving
Wheel Pressure
Wheel Rotation Alarm
Unit On/Off
Exhaust Fan Proving
Occupied/Unoccupied Input
Dirty Filter
Compressor Limit
+Vterm
GND
+5 VREF
B1
B2
B3
GND
+VDC
B4
BC4
B5
BC5
VG
VG0
Y1
Y2
Y3
Y4
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
J10J9
Rx-/Tx-
J11J11
Rx+/Tx+
J2J2J5J5J4J4J3J3
field cardserial card
GND
service card
J12J12J13J13
J14J14
J15J15
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
24 VAC When Unit On
Frost Control Enable
Output to Supply Fan
Output to Exhaust Fan
24 VAC from Supply Fan Proving
Heating Enable/Reversing Valve
Compressor Output 1
Compressor Output 2
24 VAC
Output to Dampers
Alarm Dry Contact
Remote Display
(six conductor RJ25 cable)
DDC Controller for Tempered Air Products
6
Optional BACnet, LonWorks and
Modbus cards are located in
Serial Card port
®
Large Controller Overview
24VAC to Controller
Room RH or Dehumidistat
CO2 Sensor
After Cold Coil Temperature Sensor
Sensor B1, B2, B3 Commons
Supply Discharge Temperature Sensor
Outdoor Air Temperature Sensor
24VAC for Analog Outputs
Outdoor Air Damper Analog Output
Heating Analog Output
Cooling Analog Output
Hot Gas Reheat Analog Output
Supply Fan Proving
Wheel Pressure Limit
Wheel Rotation Alarm
Unit On/Off Input
Exhaust Fan Proving
Occupied/Unoccupied Input
Dirty Filter Input
Compressor Limit
Outdoor Relative Humidity Sensor
Building Pressure Sensor
Duct Pressure Sensor
Supply Fan VFD Output
Exhaust Fan VFD Output
Room Temperature Sensor
G
G0
+V
GND
+5 V
B1
B2
B3
GND
+VDC
B4
BC4
B5
BC5
VG
VG0
Y1
Y2
Y3
Y4
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
B6
B7
B8
GND
ID9
ID10
ID11
ID12
IDC9
ID13H
ID13
IDC13
ID14
ID14H
J8
!
max. power: 40 VA/15W
input: 24V~/ V ; 50 to 60 Hz
J1J24J2J3
term
REF
field cardserial card
J10J9
Rx-/Tx-
J11
Rx+/Tx+
GND
Remote Display
(six conductor RJ25 cable)
service card
!
J6
J7
J4J5
ID15H
ID15
IDC15
ID16
ID16H
Y5
Y6
B9
BC9
B10
BC10
ID17
ID18
IDC17
J19
J20
J21
J22
J23
NO14
C14
NC14
NO15
C15
NC15
C16
NO16
NO17
NO18
C16
GND
C1
NO1
J12
NO2
NO3
C1
C4
NO4
J13
NO5
NO6
C4
C7
J14
NO7
C7
NO8
J15
C8
NC8
J16J17
C9
NO9
NO10
NO11
C9
NO12
C12
NC12
E-
E+
NO13
C13
J18
NC13
24 VAC When Unit On
Wheel Frost Mode
Supply Fan Enable
Exhaust Fan Enable
24 VAC from Supply Fan Proving
Heating Enable/Reversing Valve
Staged Compressor 1
Staged Compressor 2
24 VAC
Economizer Mode/Output to Dampers
Alarm Dry Contact
Optional BACnet, LonWorks and Modbus
cards are located in
Serial Card port
®
DDC Controller for Tempered Air Products
7
Display Use
The microprocessor controller is located in the unit
control panel. The face of the controller has six keys,
allowing the user to view unit conditions and alter
parameters. The microprocessor controller is preprogrammed with easy to use menus.
To change the display contrast, hold the Enter and
Escape button while pressing the up and down arrows.
A remote mounted display is also available, which
connects via the J10 port. A six wire patch cable is
needed.
Keypad Description
Alarm
Down Arrow
Up Arrow
Enter
Button will blink red, indicating an alarm condition. Press to review current alarms. To review
previous alarms, access the DATA LOGGER through the main menu.
The arrow keys allow the user to scroll through different screens and adjust parameters.
A. In screens with adjustable parameters, pressing the Enter key moves the cursor from
the upper left corner of the screen to the parameter. The arrow keys can then be used to
adjust the parameter.
B. To move to the next parameter on the same screen, press the Enter button.
C. To save the change, press the Enter button until the cursor moves back to the upper left
corner of the screen.
Esc
EscapeAllows the user to exit the current menu, jumping to the Main Menu.
Prg
Program
Supply air low limit
Alarm when supply is
below: 35.0º F
Alarm delay: 300s
Supply air low limit
Alarm when supply is
below: 32.0º F
Alarm delay: 300s
Supply air low limit
Alarm when supply is
below: 32.0º F
Alarm delay: 300s
Pressing the Prg (Program) button allows the user to enter the Main Program Menu. Refer to
pages 10 and 11 for Main Program Menu description.
Example of Parameter Adjustment
The cursor always begins in the upper left corner of the display and will be
blinking. Press the
Once the cursor has reached the desired parameter, press the
adjust the value.
When satisfied with the adjustment, press the
When finished, make certain the cursor is in the upper left corner. If the cursor is
not in the upper left corner, the changes will not be saved. The cursor must be in
the upper left corner to enable screen advancement.
key to move the cursor down for parameter adjustment.
key to save the parameter.
keys to
DDC Controller for Tempered Air Products
8
®
Examples of Alarms
If an alarm occurs, the
Alarms
Press DOWN to review
current alarm(s).
Press ESC to exit.
Press ALARM to reset.
button will glow red on the controller and the remote display (if installed).
To view alarm, press the button once. This will display the most recent alarm.
Press the
button again to reset the alarm. If the alarm cannot be cleared,
the cause of the alarm has not been fixed. Press the
additional occurring alarms.
buttons to view any
This is an example of an outdoor air sensor failure.
Outside Air Temperature
Sensor B01 Failure
Alarms
No active alarm
Press ENTER
to DATA LOGGER
This screen appears if there are no active alarms.
To view all saved alarms, press the
button to enter the DATA LOGGER. For
more information, see the Data Logger menu.
Examples of Alarms
Outdoor Air Temperature
Sensor Failure
Supply Air Temperature
Sensor Failure
Cold Coil Temperature
Sensor Failure
Room Temperature
Sensor Failure
System has exceeded the
set number of run hours
Supply airflow Indicates a loss of airflow in the supply fan.Alarm & Shutdown
Wheel Pressure
- Dirty Wheel/High CFM
Energy recovery wheel
rotation. Check wheel.
Exhaust Airflow Indicates a loss of airflow in the exhaust fan.Alarm & Shutdown
Filter AlarmIndicates a buildup of pressure across the filters.Alarm only
A compressor limit
switch has tripped
Supply temperature low
limit alarm
Cold Coil Low LimitIndicates a cold coil temperature lower than the cold coil low limit
pCOe OfflineIndicates communication with pCOe auxiliary I/O has failed.Alarm only
pCOe - Analog input
probe on channel #
disconnected or broken
Building Pressure Sensor
Failure
Duct Pressure Sensor
Failure
Room Humidity Sensor
Failure
Outdoor Air Humidity
Sensor Failure
CO2 Sensor FailureFailure of CO2 sensorAlarm & minimum fan speed
Failure of outside air temperature sensor.Alarm only
Failure of supply air temperature sensor.Alarm & Shutdown
Failure of after cooling coil air temperature sensor.Alarm only
Failure of room temperature sensor.
(If Unoccupied - Cycle On Room is enabled)
The unit has been operating for a period longer than the
maintenance set point.
Indicates a buildup of pressure across the energy wheel.Alarm only
Indicates a wheel rotation failure.Alarm only
Indicates a high or low refrigerant pressure switch has tripped.Alarm only
Indicates a supply air temperature lower than the supply low limit
set point.
Indicates an analog probe failure on the pCOe. Check integrity of
auxiliary I/O analog probes.
Failure of building pressure sensorAlarm & minimum fan speed
Failure of duct pressure sensorAlarm & minimum fan speed
Failure of room RH sensorAlarm only
Failure of outdoor air humidity sensorAlarm only
Alarm only
Alarm only
Alarm & Shutdown
Alarm & discharge air sensor
lockout
Alarm only
®
DDC Controller for Tempered Air Products
9
Press
Prg
to enter menus.
Menu Overview
Main Menu
Main StatusUnit On/OffSupply Temp Set PtClockAnalog Inputs
Occ OverrideOccupancy ControlCold Coil Set PtMorning Warm-upDigital Outputs
¬¬¬¬¬
Supply FanRoom HumiditySchedule(s)Analog Outputs
¬¬¬¬
Exhaust FanHeat LockoutHoliday(s)
¬¬¬
Energy WheelCool Lockout
¬¬
Cooling Dehumid Lockout
¬¬
Heating Econ Lockout
¬¬
OA DamperSupply Low Limit
¬¬
On/Off Menu
¬
Setpoint
Clock/SchedulerInput/Output
¬¬ ¬
Defrost
¬
Unoccupied Cycle
¬
Supply Fan VFD
¬
Duct Pressure
¬
Single Zone VAV
¬
Exhaust Fan VFD
¬
Building Pressure
¬
CO2 Set Point
¬
OA Damper Set Point
¬
DDC Controller for Tempered Air Products
10
NOTE
Your controller may not show all menus
depending on unit configuration.
®
Menu Overview
Press
Data LoggerBoard SwitchServiceManufacturer
¬¬
Prg
to enter menus.
AlarmsBoard Switch SetInformationConfiguration
InformationUnit Code
¬¬
Information2Expansion I/O
¬¬
OverridespLAN Comm
Analog InputsField Card Comm
¬¬
Analog OutputsI/O Config
¬
Digital InputsInputs/Outputs
¬¬
Digital OutputsFactory Settings
¬
ComponentsEconomizer
¬¬
BMS ConfigDefrost Cycle
ProtocolCooling Control
¬¬
ModbusComp Rotation
¬¬
BACnet MSTPDigital Scroll
¬¬
BACnet TCP/IPComp Timers
¬¬
BACnet TCP/IPComp Staging
¬¬
BACnet R/WHeat Control
¬¬
Service SettingsHeater Reheat
Working HoursHeater Reheat 2
Maintenance HoursHot Gas Control
¬¬
Probe AdjustmentHot Gas Timers
Analog InputsHot Gas Setup
¬¬
Password/DefaultSA Reset Control
Service PasswordHeat/Cool Delay
¬¬
Service RestoreDamper Delay
¬¬
Prg Menu LockUnocc Setup
¬¬
¬
¬
¬
¬
¬
¬
Damper Delay
¬
Air Proving
¬
Fan Delay
¬
Rotation Delay
¬
CO2 Control
¬
Duct Pressure
¬
Building Pressure
¬
Units / Display
¬
Initialization
Manf Restore
¬
Manf Password
¬
Factory Restore
¬
®
DDC Controller for Tempered Air Products
11
Main Menu Overview
The microprocessor controller will revert to a default main menu loop. This loop includes several screens to view the
operating conditions of the unit. Scroll through the menu screens by using the
line border are dependent upon an optional accessory and may not always appear.
keys. Screens with a dashed
TIME DATE UNIT##
®
TAP v2.10 GWY1X000XXXX
STATUS LINE
TIME DATE UNIT##
Supply Air: 000.0°F
Outside Air: 000.0°F
OA Humidity 00.0%
Cold Coil: 000.0°F
Room Temp: 000.0°F
Room Humidity: 00.0%
STATUS LINE
THE SENSOR STATUS SCREENDISPLAYSREALTIMECONDITIONSFROMTHESENSORS
LOCATEDINTHEUNITANDTHEROOM (IFINSTALLED).
OCCUPANCY OVERRIDE (IF UNOCCUPIED)
If the unit is currently unoccupied, the occupancy can be temporarily overridden
for a period of Override Time. The Override Time parameter can be set from one
to three hours.
Supply Fan Status
Supply Fan Ramp: 0%
(0%=Min Speed by VFD)
Duct Ps Control
Duct Pressure: 0.00”wc
STATUS LINE
Exhaust Fan Status
Exhaust Fan Ramp: 0%
(0%=Min Speed by VFD)
Building Ps Control
Building Ps: +.000”wc
STATUS LINE
Energy Recovery
Wheel: 100% Speed
Wheel Differential
Pressure Is: Normal
Preheater: OFF
STATUS LINE
SUPPLY FAN STATUS. (IFEQUIPPEDWITH VFD)
If equipped with a supply fan VFD, this screen will display the supply fan ramp
being sent from the controller to the VFD. The minimum and maximum speeds are
set in the VFD (See unit Installation and Operation Manual for VFD programming).
The controller can modulate the fan between the min and max speeds via an
analog output. This screen also displays the method of fan control and the
parameter it is controlling.
Possible methods include: Constant Speed, Duct Pressure Control, Building
Pressure Control, CO2 Control, and Single Zone VAV.
EXHAUST FAN STATUS. (IFEQUIPPEDWITH VFD)
If equipped with an exhaust fan VFD, this screen will display the exhaust fan ramp
being sent from the controller to the VFD. The minimum and maximum speeds are
set in the VFD (See unit Installation and Operation Manual for VFD programming).
The controller can modulate the fan between the min and max speeds via an
analog output. This screen also displays the method of fan control and the
parameter it is controlling.
Possible methods include: Constant Speed, Building Pressure Control, Outdoor
Air Damper Tracking, and Supply Fan Tracking.
ENERGY RECOVERY WHEEL STATUS. (IFEQUIPPED)
If selected with a preheater, the status will also be displayed.
DDC Controller for Tempered Air Products
12
®
Cooling Status
Cooling Control: 000%
Compressor D 1 2
STATUS LINE
This screen appears if a cooling option is provided.
Chilled Water: The Cooling Control % is directly proportional to the 0-10 VDC
output signal.
0% Cooling = 0 VDC
100% Cooling = 10 VDC
The cooling control output can be configured to DIRECT / REVERSE acting,
along with the minimum and maximum output voltages by entering the
MANUFACTURER menu.
Packaged DX Cooling: The Cooling Control displays internal cooling ramp as a
percent. Compressor operation is displayed when engaged.
• D = Digital Scroll Compressor Operation
• 1 = First Staged Compressor Operation
• 2 = Second Staged Compressor Operation
Heat Pump Cooling: The Cooling Control displays internal cooling ramp as a
percent. Compressor operation is displayed when engaged.
• 1 = First Staged Compressor Operation
• 2 = Second Staged Compressor Operation
Heating Status
Heater Control: 000%
Hot Gas Reheat: 000%
Staged reheat is: ON
Compressor: 1 2
STATUS LINE
HEATANDREHEATOPERATIONISDISPLAYED. (IFEQUIPPED)
Heater Control displays the proportional percentage of the heater analog output.
Electric Heater: The Heater Control % is proportional to the 0-10 VDC signal
being sent to the SCR controller, located in the electric heater control center.
0% Heating = 0 VDC - 0 kW output
100% Heating = 10 VDC - Max kW output
Hot Water: The Heater Control % is proportional to the 0-10 VDC signal being
sent to the heating control valve (BY OTHERS). The heating control output can be
configured to DIRECT / REVERSE acting, along with the minimum and maximum
output voltages by entering the MANUFACTURER menu.
0% Heating = 0 VDC
100% Heating = 10 VDC
Indirect Gas: The Heater Control % is proportional to the 0-10 VDC signal being
sent to the indirect gas furnace controller, located in the indirect gas control
center. The first stage is on at 1% Heater Control. The furnace will then modulate
proportionally from minimum to maximum capacity.
0% = 0 VDC – OFF
1% = 0 VDC – MINIMUM TURNDOWN ENABLED
1 - 100% = 0 - 10 VDC = FURNACE MODULATION
Heat Pump Heating: The Heater Control % displays internal heating ramp as a
percent. Compressor operation is displayed when engaged.
• 1 = First Staged Compressor Operation
• 2 = Second Staged Compressor Operation
Hot Gas Reheat:
If hot gas reheat is staged control:
“Staged reheat is: ON/OFF” will indicate operation.
If hot gas reheat is modulating bypass damper control:
0% = OFF
1% - 100% = 0 - 10 VDC = HOT GAS REHEAT VALVE MODULATION
®
DDC Controller for Tempered Air Products
13
Outdoor Damper Status
Damper Position: 50%
Active on Minimum OA%
CO2 Level: 0
STATUS LINE
PPM
OUTDOOR AIR DAMPER STATUS . (IFEQUIPPEDWITHMODULATINGOUTDOORAND
RECIRCULATEDAIRDAMPERS)
This screen will display the outdoor air damper position commanded by the
controller and which method the damper position is actively utilizing.
Possible methods include: Active on Minimum OA%, Active on Economizer, Active
on CO2 and Active on BMS.
Menus
The controller is equipped with several menus to help guide users with altering program parameters. The following
menus can be accessed by pressing the
A. On/Off Unit
Unit On/Off
The On/Off Unit menu allows the user to view the detailed On/Off status of the
controller.
The unit ships from the factory in a disabled state. To allow the unit to operate,
Prg
key. To enter the desired menu, press the key.
the controller must receive a run command from digital input ID4. Jumper unit
Actual state:
Off by DIG INPUT (ID4)
Change to: SWITCH ON
*Power ID4 to start…
terminals R - G to allow the unit to operate.
Actual State: The controller may be in following On/Off states:
a. Unit On - Unit is ON, functioning normally.
b. Off by ALARM - Unit is OFF due to an alarm. View alarms by pressing
ALARM button.
c. Off by PLAN - Unit is OFF by pLAN network.
d. Off by BMS - Unit is OFF by BMS command
e. Off by UNOCCUPIED - Unit is OFF by unoccupied command.
f. Off by DIGITAL INPUT (ID4) - Unit is OFF by digital input 4 (ID4).
g. Off by KEYPAD - Unit is commanded OFF by this screen.
Change to (Switch Off/Switch On): Enables user manually turn unit On/Off via
display. Unit terminal G must have 24 VAC power to enable the unit.
Digital Input: Default to YES. Unit terminal G must have 24 VAC power to enable
the unit.
The user can also use the BMS or internal time clock to command the unit
On/Off state. If scheduling is desired, go to the Clock/Scheduler menu to set
a schedule.
This screen allows the user to select the source of determining occupancy. The
factory default is terminal ID6 on the controller.
Input ID6: Typically used with a remote time clock, motion sensor or switch
(default).
BMS: BMS control (see Points List). BMS can be overridden with ID6.
Time Clock: Internal time clock (Scheduler). See Clock/Scheduler menu for
more information. The Scheduler can be overridden with digital
input ID6.
®
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.