Greenheck Microprocessor Controller User Manual

Document 475595
Microprocessor Controller for
®
Tempered Air Products
Reference Guide for the Microprocessor Controller
Please read and save these instructions. Read carefully before attempting to operate or maintain the product described. Protect yourself and others by observing all safety practices. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
TAP v2.10 Version Date: 4/1/14
Introduction
Program Features
The microprocessor controller offers improved control through easy monitoring and adjustment of unit parameters by way of a lighted graphical display and a push-button keypad.
Pre-Programmed Operating Sequences
The controller has been pre-programmed to offer multiple control sequences to provide tempered air. Factory default settings allow for easy setup and commissioning. The sequence parameters are fully adjustable. Refer to the Sequence of Operation beginning on page 2 for details.
BMS Communication
With the addition of an optional BMS Communication card, the user can remotely adjust set points, view unit status points and alarms. The microprocessor controller is capable of communicating over several protocols:
• BACnet® MSTP • LonWork®
• BACnet® IP/Ethernet • Modbus
See Points List on pages 36 and 37 for a complete list of BMS points.
Internal Time Clock
The controller has an internal programmable time clock, allowing the user to add up to seven different occupancy schedules. The user may also add Holidays for additional energy savings. The time clock option
also has morning warm-up capability for optional comfort at the time of occupancy.
Alarm Management
The microprocessor controller will monitor the unit conditions for alarm conditions. Upon detecting an alarm, the controller will record the alarm description, time, date, available temperatures, and unit status for user review. A digital output is reserved for remote alarm indication. Alarms are also communicated via BMS (if equipped).
Occupancy Modes
The microprocessor controller offers three modes of determining occupancy: a dry contact, the internal time clock or the BMS. If in the Unoccupied mode the unit will either be shut down, or will cycle on to maintain adjustable unoccupied room temperature and humidity set points.
Remote Display Panel (Optional)
A touchpad display panel allows for remote monitoring and adjustment of parameters, allowing ease of control access without going outdoors.
WARNING
Electrical shock hazard. Can cause personal injury or equipment damage. Service must be performed only by personnel that are knowledgeable in the operation of the equipment being controlled.
®
DDC Controller for Tempered Air Products
1
Table of Contents Sequence of Operation
Sequence of Operation . . . . . . . . . . . . . . . 2
General Operation. . . . . . . . . . . . . . . . 2-3
Set Point Control. . . . . . . . . . . . . . . . . . 3
Heating. . . . . . . . . . . . . . . . . . . . . . . 3
Cooling. . . . . . . . . . . . . . . . . . . . . . . 3
Economizer . . . . . . . . . . . . . . . . . . . . 4
Dehumidification. . . . . . . . . . . . . . . . . . 4
Reheat . . . . . . . . . . . . . . . . . . . . . . . 4
Supply Fan VFD . . . . . . . . . . . . . . . . . . 4
Exhaust Fan VFD . . . . . . . . . . . . . . . . . 5
Outdoor Air and Recirculated (Recirc) Air . . . . . 5
Energy Recovery Wheel Sequence . . . . . . . . 5
Alarms . . . . . . . . . . . . . . . . . . . . . . . 5
Controller Overview . . . . . . . . . . . . . . . . 6-7
Display Use . . . . . . . . . . . . . . . . . . . . . 8
Example of Parameter Adjustment . . . . . . . . . 8
Example of Alarms. . . . . . . . . . . . . . . . . . 9
Menu Overview . . . . . . . . . . . . . . . . . 10-11
Main Menu Overview . . . . . . . . . . . . . . 12-14
Menus
A.
On/Off Unit . . . . . . . . . . . . . . . . . 14
B.
Setpoint . . . . . . . . . . . . . . . . 15-21
C.
Clock/Scheduler . . . . . . . . . . . . . .22
D.
Input/Output . . . . . . . . . . . . . . . .22
E.
Data Logger . . . . . . . . . . . . . . . . 22
F.
Board Switch. . . . . . . . . . . . . . . .23
G.
Service
a. Information. . . . . . . . . . . . . . . . .23
b. Overrides . . . . . . . . . . . . . . . 23-25
c. BMS Config . . . . . . . . . . . . . . 26-27
d. Service Settings
a. Working hour set . . . . . . . . . . . . 27
b. Probe adjustment. . . . . . . . . . . .27
c. Password/Defaults . . . . . . . . . . . 27
H.
Manufacturer
a. Configuration . . . . . . . . . . . . . . . 28
b. I/O Configuration . . . . . . . . . . . . . 28
c. Factory Settings . . . . . . . . . . . . 29-34
d. Initialization . . . . . . . . . . . . . . . . 35
Remote Display . . . . . . . . . . . . . . . . . . . 35
Points List
LonWorks® . . . . . . . . . . . . . . . . . . . .36
ModBus/BACnet®. . . . . . . . . . . . . . . . .37
Expansion I/O (pCOe) . . . . . . . . . . . . . . . .38
Troubleshooting . . . . . . . . . . . . . . . . . . . 39
NTC Temperature Sensor Chart. . . . . . . . . . .39
BACnet® MSTP Quick Start. . . . . . . . . . . . .40
BACnet® IP/Eth Quick Start. . . . . . . . . . . . .41
Economizer Commissioning Tool . . . . . . . . . .42
Maintenance Log . . . . . . . . . . . . . . . . . . 43
Our Commitment. . . . . . . . . . . . . . Backcover
The microprocessor controller can be configured for air handler, energy recovery, dedicated outdoor air system and make-up air applications. Each application utilizes similar technologies for heating and cooling: chilled water, hot water, indirect gas, electric heat, packaged DX cooling, and packaged DX cooling with digital scrolls. All set points, lockouts and delays are user adjustable via the keypad display.
General Operation
UNIT START COMMAND: The microprocessor
controller requires a digital input to enable operation. The unit can then be commanded on or off by this digital input, the BMS or internal time clock.
• Initial delay
• Factory mounted and wired dampers are powered, if equipped. (Outdoor air, exhaust air, and recirculation air dampers).
• Exhaust fan and energy recovery wheel start after a 10 second delay, if equipped.
• Supply fan starts 15 seconds after the exhaust fan.
• Tempering operation begins (see modes below).
UNIT STOP COMMAND (OR DE-ENERGIZED):
• Supply fan, exhaust fan, tempering, and wheel are
de-energized.
• Outdoor air and Exhaust air dampers are closed after a 10 second delay. Recirculation air dampers spring open.
OCCUPIED/UNOCCUPIED MODES: The microprocessor controller offers three modes of determining occupancy: a dry contact, the internal time clock or the BMS. When in the unoccupied mode, the unit can be configured to shut down, or cycle on to maintain the unoccupied room set points. The unit can be temporarily overridden to the occupied mode via a digital input or the keypad display.
The internal time clock can be configured with morning warm-up to bring the space to the occupied set point prior to occupancy.
Occupied Mode:
- Exhaust fan on, if equipped
- Supply fan on
- Heating (refer to Heating section)
- Cooling (refer to Cooling section)
- Energy Recovery Wheel control (refer to
Energy Recover Wheel section), if equipped.
- Damper control (refer to Outdoor Air and
Recirculated Air section), if equipped.
Unoccupied Mode (Unit Off): Unit remains off when in unoccupied mode.
Unoccupied Mode (Cycle on Room): Optional unoccupied mode when there is an unoccupied recirculation damper and room temperature and/ or humidity sensor(s) connected to the controller. The unit will cycle on to maintain unoccupied room set points if there is a call for unoccupied heating, cooling or dehumidification.
DDC Controller for Tempered Air Products
2
®
Sequence of Operation
- Exhaust fan off, if equipped.
- Supply fan off.
- Recirculation air damper open.
- OA damper closed.
- Tempering operations begin (see modes below)
Set Point Control (Occupied)
Supply air temperature set point can be configured as constant, or can be reset by either outside air temperature, or room temperature set point. If equipped with BMS communications, the user can also directly command the supply temperature set point, or room temperature set point (if equipped with a room temp sensor).
Outdoor Air Temperature Reset Function: The controller will default to supply temperature reset based on outdoor air temperature. The controller will monitor the OA temperature and reset the supply temperature set point based upon the outdoor air reset function.
• Room Temperature Reset (optional): With a room temperature sensor, the controller will adjust the supply air temperature set point between the minimum (55°F) and maximum (90°F), to satisfy the desired room temperature.
Set Point Control (Unoccupied)
When equipped with an unoccupied recirculation damper and optional room temperature and/or humidity sensors, the unit will cycle on to maintain the unoccupied room set points.
Unoccupied Heating: If equipped with heating, the unit is enabled when the room temperature is less than the unoccupied heating set point minus differential (65°F-5°F). The supply air temperature set point will be set to the supply maximum reset limit (90°F). The unit cycles off when the room temperature reaches the unoccupied heating set point.
• Unoccupied Cooling: If equipped with cooling, the unit is enabled when the room temperature is greater than the unoccupied cooling set point plus differential (80°F+5°F). The supply air temperature set point will be set to the supply minimum reset limit (55°F). The unit cycles off when the room temperature reaches the unoccupied cooling set point.
• Unoccupied Dehumidification: If equipped with cooling, the unit is enabled when the room relative humidity exceeds the unoccupied room relative humidity set point plus differential (50%+5%), or when dehumidistat contact indicates excessive humidity. The supply air temperature set point will be set to the equivalent occupied supply set point.
• Morning Warm-Up: The unit uses an algorithm involving space temperature and the heating /cooling
rate of the previous day to determine the time required to efficiently temper the space to occupied set point prior to occupancy.
Heating
The heating is controlled to maintain the supply temperature set point. The heating will be locked out when the outside air temperature is above the heating lockout (70°F).
Indirect Gas Furnace: Microprocessor controller will modulate the indirect gas furnace to maintain the supply temperature set point.
Hot Water Coil: Microprocessor controller will modulate a hot water valve (provided by others) to maintain the supply temperature set point. Coil
freeze protection must be provided by others in the field!
Electric Heater: Microprocessor controller will modulate an electric heater to maintain the supply temperature set point.
Heat Pump: Microprocessor controller will stage compressor(s) to maintain the supply air set point. This signal will come wired to the factory provided heat pump module. All external water valves and
valve controls are provided, wired and mounted by others in the field, including freeze protection.
Cooling
The cooling is controlled to maintain the supply temperature set point. The mechanical cooling will be locked out when the outside air temperature is below the cooling lockout (55°F).
Chilled Water: Microprocessor controller will modulate a chilled water valve (provided by others) to maintain supply air set point. Coil Freeze protection
must be provided by others in the field!
Packaged DX Cooling (Standard Scroll): Microprocessor controller will control stages of cooling to maintain the supply air set point.
Packaged DX Cooling (Digital Scroll): Microprocessor controller will modulate the digital scroll to maintain the supply air temperature set point.
Heat Pump: Microprocessor controller will power the reversing valve within the heat pump module to direct the refrigerant flow for airside cooling. The cooling is controlled to maintain the supply temperature set point. All external water valves and
valve controls are provided, wired and mounted by others in the field, including freeze protection.
®
DDC Controller for Tempered Air Products
3
Economizer
If the application requires cooling, and the outdoor air conditions are suitable for free cooling, the controller may enter the economizer state. If the unit is economizing and the discharge temperature set point is not being met, the controller may bring on mechanical cooling. If equipped with a modulating outdoor air and recirculated air damper, the dampers will modulate between the minimum OA and maximum positions to maintain the supply temperature set point. If equipped with an energy wheel, see Energy Recovery Wheel Sequence.
Temperature: The economizer will be locked out when:
- The outside air is less than the economizer low
lockout (40°F).
- The outside air is greater than the economizer
high lockout (65°F).
- The unit is operating in dehumidification mode.
- There is a call for heating.
Temperature/Dew Point: The economizer will be locked out when:
- The outside air is less than the economizer low
lockout (40°F dry-bulb).
- The outside air is greater than the economizer
high lockout (75°F dry-bulb).
- The outside air is greater than the economizer
high dew point lockout (55°F dew point)
- The unit is operating in dehumidification mode.
- There is a call for heating.
Dehumidification
The cooling is controlled to maintain the cold coil set point. The dehumidification sequence will be locked out when the OA is less than the dehumidification lockout (10°F) above the cold coil set point. If equipped with BMS communications, the user can also directly set the cold coil leaving air set point.
• Optional Room Dehumidistat: The room dehumidistat is a field mounted sensor that monitors the relative humidity (RH) of the room. If the RH exceeds set point, the dehumidistat will reset the cold coil set point to the minimum (50°F). Once the room dehumidistat is satisfied, the cold coil set point will return to the maximum (55°F).
Optional Room Relative Humidity Sensor: The controller will adjust the cold coil leaving air temperature set point between the minimum (50°F) and maximum (55°F) set points, to satisfy the desired room relative humidity set point.
Reheat
While the unit is in dehumidification mode, the supply air can be reheated via Primary Heating Source, On/Off Hot Gas Reheat or Modulating Hot Gas Reheat.
Primary Heating Source: The main heating source is enabled to reheat the air to meet the supply temperature set point. (Except heat pump). The
DDC Controller for Tempered Air Products
4
primary heat source may also be configured to act as secondary reheat.
Modulating Hot Gas Reheat (bypass damper): The microprocessor controller will open the On/Off hot gas reheat valve, and modulate the Hot Gas Reheat bypass damper to maintain the supply temperature set point.
Modulating Hot Gas Reheat (valve): The microprocessor controller will modulate the hot gas reheat valve to maintain the supply temperature set point.
On/Off Hot Gas Reheat: The microprocessor controller will open the On/Off hot gas reheat valve to maintain the supply temperature set point.
Supply Fan VFD Sequence
If the factory has installed a VFD and wired it to the controller, it is intended to operate at a constant speed during operation. This speed needs to be set during test and balance of the unit. If equipped with BMS communications, the user can also directly command the supply fan speed.
Optional Room CO2 Sensor: The controller will modulate the supply fan based upon a comparison of the CO2 set point to the actual CO2 levels reported from the sensor. Mechanical high static
protection cutoffs must be installed by others to protect the system and equipment from over-pressurization.
Optional Duct Static Pressure Sensor: The controller will modulate the supply fan based upon a comparison of the duct static pressure set point to the actual duct static pressure level reported from the sensor. Mechanical high static protection
cutoffs must be installed by others to protect the system and equipment from over­pressurization. The manufacturer does not assume responsibility for this.
• Optional Building Static Pressure Sensor: The controller will modulate the supply fan based upon a comparison of the building static pressure set point to the actual building static pressure level reported from the sensor.
Optional Single Zone VAV (SZ): The controller will control the supply air temperature and supply fan speed to maintain the room temperature set point. This sequence requires a room temperature sensor. Heating - When the room requires heating, the controller will reset the supply air temperature set point up to the maximum (90°F) while increasing the supply fan speed up to its maximum heating speed. Cooling - When the room requires cooling, the controller will first reset the supply air temperature set point down to the minimum (55°F) while the supply fan remains at the minimum cooling speed. After a time delay, the supply fan speed will increase up to its maximum cooling speed to maintain the room temperature set point.
®
Exhaust Fan VFD Sequence
If the factory has installed a VFD and wired it to the controller, it is intended to operate at a constant speed during operation. This speed needs to be set during test and balance of the unit. If equipped with BMS communications, the user can also directly command the exhaust fan speed.
Optional Building Static Pressure Sensor: The controller will modulate the exhaust fan based upon a comparison of the building static pressure set point to the actual building static pressure level reported from the sensor.
Optional Supply Fan Tracking: The controller will proportionally modulate the exhaust fan based upon the supply fan speed.
Optional Outdoor Air Damper Tracking: The controller will proportionally modulate the exhaust fan based upon the outdoor air damper position.
Outdoor Air and Recirculated (Recirc) Air Damper Control
If equipped with a modulating outdoor air and recirculated air damper, the recirculated air damper will operate inverse of the outdoor air damper. The outdoor air damper will open to a Minimum Outdoor Air Position (Min OA) when in occupied mode. If the controller is configured to modulate the supply fan speed, the minimum and maximum OA positions can be reset based on supply fan speed. If equipped with BMS communications, the user can also directly reset the damper position up to the maximum OA position.
Optional Room CO2 Sensor: The controller will proportionally modulate the OA/RA dampers based upon a comparison of the CO2 set point to the actual CO2 level reported from the sensor. As the CO2 level rises, the controller will proportionally modulate the outdoor air damper open, between the minimum and maximum OA position.
Optional Building Pressure: The OA/RA dampers will modulate based upon the signal from a building static pressure sensor. The controller will modulate the dampers, between the minimum and maximum OA positions, based upon a comparison of the building static pressure set point to the actual building static pressure level reported from the sensor.
Energy Recovery Wheel Sequences
Economizer (optional): If the unit is equipped with an
energy recovery wheel, the economizer will modulate/ stop the energy wheel to achieve free cooling.
Stop Wheel: When economizer mode is enabled and there is a signal for cooling, the wheel will stop rotating to allow free cooling.
Modulate Wheel: When economizer mode is enabled and there is a signal for cooling, the
®
controller modulates wheel speed to maintain the supply temperature set point.
Energy Wheel Bypass Dampers (optional): During normal operation, the dampers shall remain closed to allow full operation of the energy wheel. During economizer sequences, the dampers will be open to bypass the energy wheel.
Frost Control (optional): The microprocessor controller will activate the frost control method when the outdoor air temperature is less than the defrost set point (5°F) and the wheel pressure switch is closed, due to a high wheel pressure drop. Once either the pressure drop decreases below the pressure switch point, or the outdoor air temperature increases, the unit will resume normal operation.
Electric Preheater: When frosting is occurring, the preheater is energized to defrost the wheel.
Modulate Wheel: When frosting is occurring, the wheel slows to allow defrosting to occur.
Cycle Wheel: When frosting is occurring, the energy wheel is cycled off for a defrost cycle time (2 minutes). After the defrost cycle time, the wheel is re-energized to continue normal operation. The controller will not allow another defrost cycle for a minimum normal operating cycle time (5 minutes).
Timed Exhaust: When frosting is occurring, the supply fan is cycled off along with the tempering for a defrost cycle time (5 minutes). The exhaust fan will continue to run, allowing the warm exhaust air to defrost the wheel. After the defrost cycle time, the supply fan and tempering are re-energized to continue normal operation. The controller will not allow another defrost cycle for a minimum normal operating cycle time (30 minutes).
Alarms
The microprocessor controller includes a digital output for remote indication of an alarm condition. Possible alarms include:
Dirty Filter Alarm: If the outside air or return air filter differential pressure rises above the differential pressure switch set point, the microprocessor controller will activate an alarm.
Supply and Exhaust Air Proving Alarm: Microprocessor controller monitors proving switch on each blower and displays an alarm in case of blower failure.
Sensor Alarm: Microprocessor controller will send an alarm if a failed sensor is detected (temperature, pressure, relative humidity).
Supply Air Low Limit: If the supply air temperature drops below the supply air low limit (35°F), the microprocessor controller will de-energize the unit and activate the alarm output after a preset time delay (300s).
Other Alarms: Wheel Rotation, High Wheel Pressure, High/Low Refrigerant Pressure.
DDC Controller for Tempered Air Products
5
24 VAC to Controller
Small Controller Overview
input: 24V~/ V ; 50 to 60 Hz
max. power: 40 VA/15W
J1J1 J24J24
G
G0
Room RH or Dehumidistat
Room Temperature Sensor
After Cold Coil Temperature Sensor
Sensor B1, B2, B3 Commons
Supply Discharge Temperature Sensor
Outdoor Air Temperature Sensor
24 VAC for Analog Outputs
Energy Wheel Analog Output
Heating Analog Output Cooling Analog Output
Hot Gas Reheat Analog Output
Supply Fan Proving
Wheel Pressure
Wheel Rotation Alarm
Unit On/Off
Exhaust Fan Proving
Occupied/Unoccupied Input
Dirty Filter
Compressor Limit
+Vterm
GND
+5 VREF
B1
B2
B3
GND
+VDC
B4
BC4
B5
BC5
VG
VG0
Y1
Y2
Y3
Y4
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
J10J9
Rx-/Tx-
J11J11
Rx+/Tx+
J2J2 J5J5J4J4J3J3
field card serial card
GND
service card
J12J12 J13J13
J14J14
J15J15
C1
NO1
NO2
NO3
C1
C4
NO4
NO5
NO6
C4
C7
NO7
C7
NO8
C8
NC8
24 VAC When Unit On Frost Control Enable Output to Supply Fan Output to Exhaust Fan
24 VAC from Supply Fan Proving Heating Enable/Reversing Valve Compressor Output 1 Compressor Output 2
24 VAC Output to Dampers
Alarm Dry Contact
Remote Display
(six conductor RJ25 cable)
DDC Controller for Tempered Air Products
6
Optional BACnet, LonWorks and Modbus cards are located in Serial Card port
®
Large Controller Overview
24VAC to Controller
Room RH or Dehumidistat
CO2 Sensor
After Cold Coil Temperature Sensor
Sensor B1, B2, B3 Commons
Supply Discharge Temperature Sensor
Outdoor Air Temperature Sensor
24VAC for Analog Outputs
Outdoor Air Damper Analog Output
Heating Analog Output
Cooling Analog Output
Hot Gas Reheat Analog Output
Supply Fan Proving
Wheel Pressure Limit
Wheel Rotation Alarm
Unit On/Off Input
Exhaust Fan Proving
Occupied/Unoccupied Input
Dirty Filter Input
Compressor Limit
Outdoor Relative Humidity Sensor
Building Pressure Sensor
Duct Pressure Sensor
Supply Fan VFD Output
Exhaust Fan VFD Output
Room Temperature Sensor
G
G0
+V
GND
+5 V
B1
B2
B3
GND
+VDC
B4
BC4
B5
BC5
VG
VG0
Y1
Y2
Y3
Y4
ID1
ID2
ID3
ID4
ID5
ID6
ID7
ID8
IDC1
B6
B7
B8
GND
ID9
ID10
ID11
ID12
IDC9
ID13H
ID13
IDC13
ID14
ID14H
J8
!
max. power: 40 VA/15W
input: 24V~/ V ; 50 to 60 Hz
J1 J24 J2 J3
term
REF
field card serial card
J10J9
Rx-/Tx-
J11
Rx+/Tx+
GND
Remote Display
(six conductor RJ25 cable)
service card
!
J6
J7
J4 J5
ID15H
ID15
IDC15
ID16
ID16H
Y5
Y6
B9
BC9
B10
BC10
ID17
ID18
IDC17
J19
J20
J21
J22
J23
NO14
C14
NC14
NO15
C15
NC15
C16
NO16
NO17
NO18
C16
GND
C1
NO1
J12
NO2
NO3
C1
C4
NO4
J13
NO5
NO6
C4
C7
J14
NO7
C7
NO8
J15
C8
NC8
J16 J17
C9
NO9
NO10
NO11
C9
NO12
C12
NC12
E-
E+
NO13
C13
J18
NC13
24 VAC When Unit On
Wheel Frost Mode
Supply Fan Enable
Exhaust Fan Enable
24 VAC from Supply Fan Proving
Heating Enable/Reversing Valve
Staged Compressor 1
Staged Compressor 2
24 VAC
Economizer Mode/Output to Dampers
Alarm Dry Contact
Optional BACnet, LonWorks and Modbus cards are located in Serial Card port
®
DDC Controller for Tempered Air Products
7
Display Use
The microprocessor controller is located in the unit control panel. The face of the controller has six keys, allowing the user to view unit conditions and alter parameters. The microprocessor controller is pre­programmed with easy to use menus.
To change the display contrast, hold the Enter and Escape button while pressing the up and down arrows.
A remote mounted display is also available, which connects via the J10 port. A six wire patch cable is needed.
Keypad Description
Alarm
Down Arrow
Up Arrow
Enter
Button will blink red, indicating an alarm condition. Press to review current alarms. To review previous alarms, access the DATA LOGGER through the main menu.
The arrow keys allow the user to scroll through different screens and adjust parameters.
A. In screens with adjustable parameters, pressing the Enter key moves the cursor from
the upper left corner of the screen to the parameter. The arrow keys can then be used to adjust the parameter.
B. To move to the next parameter on the same screen, press the Enter button.
C. To save the change, press the Enter button until the cursor moves back to the upper left
corner of the screen.
Esc
Escape Allows the user to exit the current menu, jumping to the Main Menu.
Prg
Program
Supply air low limit
Alarm when supply is below: 35.0º F
Alarm delay: 300s
Supply air low limit
Alarm when supply is below: 32.0º F
Alarm delay: 300s
Supply air low limit
Alarm when supply is below: 32.0º F
Alarm delay: 300s
Pressing the Prg (Program) button allows the user to enter the Main Program Menu. Refer to pages 10 and 11 for Main Program Menu description.
Example of Parameter Adjustment
The cursor always begins in the upper left corner of the display and will be
blinking. Press the
Once the cursor has reached the desired parameter, press the adjust the value.
When satisfied with the adjustment, press the When finished, make certain the cursor is in the upper left corner. If the cursor is not in the upper left corner, the changes will not be saved. The cursor must be in the upper left corner to enable screen advancement.
key to move the cursor down for parameter adjustment.
key to save the parameter.
keys to
DDC Controller for Tempered Air Products
8
®
Examples of Alarms
If an alarm occurs, the
Alarms
Press DOWN to review current alarm(s).
Press ESC to exit. Press ALARM to reset.
button will glow red on the controller and the remote display (if installed).
To view alarm, press the button once. This will display the most recent alarm. Press the
button again to reset the alarm. If the alarm cannot be cleared, the cause of the alarm has not been fixed. Press the additional occurring alarms.
buttons to view any
This is an example of an outdoor air sensor failure.
Outside Air Temperature Sensor B01 Failure
Alarms
No active alarm
Press ENTER to DATA LOGGER
This screen appears if there are no active alarms.
To view all saved alarms, press the
button to enter the DATA LOGGER. For
more information, see the Data Logger menu.
Examples of Alarms
Outdoor Air Temperature Sensor Failure
Supply Air Temperature Sensor Failure
Cold Coil Temperature Sensor Failure
Room Temperature Sensor Failure
System has exceeded the set number of run hours
Supply airflow Indicates a loss of airflow in the supply fan. Alarm & Shutdown
Wheel Pressure
- Dirty Wheel/High CFM
Energy recovery wheel rotation. Check wheel.
Exhaust Airflow Indicates a loss of airflow in the exhaust fan. Alarm & Shutdown
Filter Alarm Indicates a buildup of pressure across the filters. Alarm only
A compressor limit switch has tripped
Supply temperature low limit alarm
Cold Coil Low Limit Indicates a cold coil temperature lower than the cold coil low limit
pCOe Offline Indicates communication with pCOe auxiliary I/O has failed. Alarm only
pCOe - Analog input probe on channel # disconnected or broken
Building Pressure Sensor Failure
Duct Pressure Sensor Failure
Room Humidity Sensor Failure
Outdoor Air Humidity Sensor Failure
CO2 Sensor Failure Failure of CO2 sensor Alarm & minimum fan speed
Failure of outside air temperature sensor. Alarm only
Failure of supply air temperature sensor. Alarm & Shutdown
Failure of after cooling coil air temperature sensor. Alarm only
Failure of room temperature sensor. (If Unoccupied - Cycle On Room is enabled)
The unit has been operating for a period longer than the maintenance set point.
Indicates a buildup of pressure across the energy wheel. Alarm only
Indicates a wheel rotation failure. Alarm only
Indicates a high or low refrigerant pressure switch has tripped. Alarm only
Indicates a supply air temperature lower than the supply low limit set point.
Indicates an analog probe failure on the pCOe. Check integrity of auxiliary I/O analog probes.
Failure of building pressure sensor Alarm & minimum fan speed
Failure of duct pressure sensor Alarm & minimum fan speed
Failure of room RH sensor Alarm only
Failure of outdoor air humidity sensor Alarm only
Alarm only
Alarm only
Alarm & Shutdown
Alarm & discharge air sensor lockout
Alarm only
®
DDC Controller for Tempered Air Products
9
Press
Prg
to enter menus.
Menu Overview
Main Menu
Main Status Unit On/Off Supply Temp Set Pt Clock Analog Inputs
¬¬¬¬ ¬
Temp Status Unit On/Off Control Room Temp Scheduler Enable Digital Inputs
¬
Occ Override Occupancy Control Cold Coil Set Pt Morning Warm-up Digital Outputs
¬¬ ¬ ¬ ¬
Supply Fan Room Humidity Schedule(s) Analog Outputs
¬¬¬¬
Exhaust Fan Heat Lockout Holiday(s)
¬¬¬
Energy Wheel Cool Lockout
¬¬
Cooling Dehumid Lockout
¬¬
Heating Econ Lockout
¬¬
OA Damper Supply Low Limit
¬¬
On/Off Menu
¬
Setpoint
Clock/Scheduler Input/Output
¬¬ ¬
Defrost
¬
Unoccupied Cycle
¬
Supply Fan VFD
¬
Duct Pressure
¬
Single Zone VAV
¬
Exhaust Fan VFD
¬
Building Pressure
¬
CO2 Set Point
¬
OA Damper Set Point
¬
DDC Controller for Tempered Air Products
10
NOTE
Your controller may not show all menus depending on unit configuration.
®
Menu Overview
Press
Data Logger Board Switch Service Manufacturer
¬¬
Prg
to enter menus.
Alarms Board Switch Set Information Configuration
Information Unit Code
¬¬
Information2 Expansion I/O
¬¬
Overrides pLAN Comm
Analog Inputs Field Card Comm
¬¬
Analog Outputs I/O Config
¬
Digital Inputs Inputs/Outputs
¬¬
Digital Outputs Factory Settings
¬
Components Economizer
¬¬
BMS Config Defrost Cycle
Protocol Cooling Control
¬¬
Modbus Comp Rotation
¬¬
BACnet MSTP Digital Scroll
¬¬
BACnet TCP/IP Comp Timers
¬¬
BACnet TCP/IP Comp Staging
¬¬
BACnet R/W Heat Control
¬¬
Service Settings Heater Reheat
Working Hours Heater Reheat 2
Maintenance Hours Hot Gas Control
¬¬
Probe Adjustment Hot Gas Timers
Analog Inputs Hot Gas Setup
¬¬
Password/Default SA Reset Control
Service Password Heat/Cool Delay
¬¬
Service Restore Damper Delay
¬¬
Prg Menu Lock Unocc Setup
¬¬
¬
¬
¬ ¬
¬
¬
Damper Delay
¬
Air Proving
¬
Fan Delay
¬
Rotation Delay
¬
CO2 Control
¬
Duct Pressure
¬
Building Pressure
¬
Units / Display
¬
Initialization
Manf Restore
¬
Manf Password
¬
Factory Restore
¬
®
DDC Controller for Tempered Air Products
11
Main Menu Overview
The microprocessor controller will revert to a default main menu loop. This loop includes several screens to view the operating conditions of the unit. Scroll through the menu screens by using the
line border are dependent upon an optional accessory and may not always appear.
keys. Screens with a dashed
TIME DATE UNIT##
®
TAP v2.10 GWY1X000XXXX STATUS LINE
TIME DATE UNIT##
Supply Air: 000.0°F Outside Air: 000.0°F OA Humidity 00.0% Cold Coil: 000.0°F Room Temp: 000.0°F Room Humidity: 00.0% STATUS LINE
Occupancy Override
Clock Override: OFF Override Time: 1 hr
THE INITIAL MENU SCREEN DISPLAYS THE PROGRAM VERSION, UNIT CODE AND STATUS
LINE. THE STATUS LINE DISPLAYS WHICH MODE THE UNIT IS IN.
Possible modes include:
• Initial Delay
• Opening Dampers
• Exhaust Fan Starting
• Supply Fan Starting
• System On
• Defrost Mode Active
• Sys On - Econ+Cooling
• Sys On - Economizer
• Sys On - Heating
• Sys On - Cooling
• Sys On - Dehumidifying
• Sys On - Dehumid & Reheat
• Unoccupied - Unit On
• Unoccupied - Unit Off
• Unoccupied - Dehumid
• Unoccupied - Dehumid & Reheat
• Unoccupied - Heating
• Unoccupied - Cooling
• Manual Override
• Remote Off
• Press Alarm Button!!!
• Temp Occupied
THE SENSOR STATUS SCREEN DISPLAYS REAL TIME CONDITIONS FROM THE SENSORS
LOCATED IN THE UNIT AND THE ROOM (IF INSTALLED).
OCCUPANCY OVERRIDE (IF UNOCCUPIED)
If the unit is currently unoccupied, the occupancy can be temporarily overridden for a period of Override Time. The Override Time parameter can be set from one to three hours.
Supply Fan Status
Supply Fan Ramp: 0% (0%=Min Speed by VFD)
Duct Ps Control Duct Pressure: 0.00”wc
STATUS LINE
Exhaust Fan Status
Exhaust Fan Ramp: 0% (0%=Min Speed by VFD)
Building Ps Control Building Ps: +.000”wc
STATUS LINE
Energy Recovery
Wheel: 100% Speed Wheel Differential
Pressure Is: Normal Preheater: OFF STATUS LINE
SUPPLY FAN STATUS. (IF EQUIPPED WITH VFD)
If equipped with a supply fan VFD, this screen will display the supply fan ramp being sent from the controller to the VFD. The minimum and maximum speeds are set in the VFD (See unit Installation and Operation Manual for VFD programming). The controller can modulate the fan between the min and max speeds via an analog output. This screen also displays the method of fan control and the parameter it is controlling.
Possible methods include: Constant Speed, Duct Pressure Control, Building Pressure Control, CO2 Control, and Single Zone VAV.
EXHAUST FAN STATUS. (IF EQUIPPED WITH VFD)
If equipped with an exhaust fan VFD, this screen will display the exhaust fan ramp being sent from the controller to the VFD. The minimum and maximum speeds are set in the VFD (See unit Installation and Operation Manual for VFD programming). The controller can modulate the fan between the min and max speeds via an analog output. This screen also displays the method of fan control and the parameter it is controlling.
Possible methods include: Constant Speed, Building Pressure Control, Outdoor Air Damper Tracking, and Supply Fan Tracking.
ENERGY RECOVERY WHEEL STATUS. (IF EQUIPPED)
If selected with a preheater, the status will also be displayed.
DDC Controller for Tempered Air Products
12
®
Cooling Status
Cooling Control: 000% Compressor D 1 2 STATUS LINE
COOLING STATUS IS DISPLAYED, ALONG WITH COMPRESSOR OPERATION. (IF EQUIPPED)
This screen appears if a cooling option is provided.
Chilled Water: The Cooling Control % is directly proportional to the 0-10 VDC output signal. 0% Cooling = 0 VDC
100% Cooling = 10 VDC
The cooling control output can be configured to DIRECT / REVERSE acting, along with the minimum and maximum output voltages by entering the
MANUFACTURER menu.
Packaged DX Cooling: The Cooling Control displays internal cooling ramp as a
percent. Compressor operation is displayed when engaged.
• D = Digital Scroll Compressor Operation
• 1 = First Staged Compressor Operation
• 2 = Second Staged Compressor Operation
Heat Pump Cooling: The Cooling Control displays internal cooling ramp as a percent. Compressor operation is displayed when engaged.
• 1 = First Staged Compressor Operation
• 2 = Second Staged Compressor Operation
Heating Status
Heater Control: 000% Hot Gas Reheat: 000% Staged reheat is: ON Compressor: 1 2
STATUS LINE
HEAT AND REHEAT OPERATION IS DISPLAYED. (IF EQUIPPED)
Heater Control displays the proportional percentage of the heater analog output.
Electric Heater: The Heater Control % is proportional to the 0-10 VDC signal being sent to the SCR controller, located in the electric heater control center. 0% Heating = 0 VDC - 0 kW output
100% Heating = 10 VDC - Max kW output
Hot Water: The Heater Control % is proportional to the 0-10 VDC signal being sent to the heating control valve (BY OTHERS). The heating control output can be configured to DIRECT / REVERSE acting, along with the minimum and maximum output voltages by entering the MANUFACTURER menu. 0% Heating = 0 VDC
100% Heating = 10 VDC
Indirect Gas: The Heater Control % is proportional to the 0-10 VDC signal being sent to the indirect gas furnace controller, located in the indirect gas control center. The first stage is on at 1% Heater Control. The furnace will then modulate proportionally from minimum to maximum capacity. 0% = 0 VDC – OFF 1% = 0 VDC – MINIMUM TURNDOWN ENABLED 1 - 100% = 0 - 10 VDC = FURNACE MODULATION
Heat Pump Heating: The Heater Control % displays internal heating ramp as a percent. Compressor operation is displayed when engaged.
• 1 = First Staged Compressor Operation
• 2 = Second Staged Compressor Operation
Hot Gas Reheat:
If hot gas reheat is staged control:
“Staged reheat is: ON/OFF” will indicate operation.
If hot gas reheat is modulating bypass damper control:
0% = OFF 1% - 100% = 4 - 10 VDC = AIRFLOW DAMPER MODULATION
If hot gas reheat is modulating valve control:
0% = OFF 1% - 100% = 0 - 10 VDC = HOT GAS REHEAT VALVE MODULATION
®
DDC Controller for Tempered Air Products
13
Outdoor Damper Status
Damper Position: 50% Active on Minimum OA% CO2 Level: 0 STATUS LINE
PPM
OUTDOOR AIR DAMPER STATUS . (IF EQUIPPED WITH MODULATING OUTDOOR AND
RECIRCULATED AIR DAMPERS)
This screen will display the outdoor air damper position commanded by the controller and which method the damper position is actively utilizing.
Possible methods include: Active on Minimum OA%, Active on Economizer, Active on CO2 and Active on BMS.
Menus
The controller is equipped with several menus to help guide users with altering program parameters. The following menus can be accessed by pressing the
A. On/Off Unit
Unit On/Off
The On/Off Unit menu allows the user to view the detailed On/Off status of the controller.
The unit ships from the factory in a disabled state. To allow the unit to operate,
Prg
key. To enter the desired menu, press the key.
the controller must receive a run command from digital input ID4. Jumper unit
Actual state: Off by DIG INPUT (ID4)
Change to: SWITCH ON *Power ID4 to start…
terminals R - G to allow the unit to operate.
Actual State: The controller may be in following On/Off states: a. Unit On - Unit is ON, functioning normally. b. Off by ALARM - Unit is OFF due to an alarm. View alarms by pressing
ALARM button. c. Off by PLAN - Unit is OFF by pLAN network. d. Off by BMS - Unit is OFF by BMS command e. Off by UNOCCUPIED - Unit is OFF by unoccupied command. f. Off by DIGITAL INPUT (ID4) - Unit is OFF by digital input 4 (ID4). g. Off by KEYPAD - Unit is commanded OFF by this screen.
Change to (Switch Off/Switch On): Enables user manually turn unit On/Off via display. Unit terminal G must have 24 VAC power to enable the unit.
Unit ON/OFF Control
Enable unit OnOff By digit input: Yes
By BMS: No
Occupancy Control
Type: Unit OFF Source: Input ID6
DDC Controller for Tempered Air Products
14
THIS SCREEN ALLOWS THE USER TO ADJUST WHICH SYSTEM CONTROLS THE UNIT ON/OFF STATE.
Digital Input: Default to YES. Unit terminal G must have 24 VAC power to enable the unit.
The user can also use the BMS or internal time clock to command the unit On/Off state. If scheduling is desired, go to the Clock/Scheduler menu to set a schedule.
BMS: YES allows BMS to control unit On/Off state.
THIS SCREEN DISPLAYS WHAT THE UNIT WILL DO IN UNOCCUPIED MODE.
This screen allows the user to select the source of determining occupancy. The factory default is terminal ID6 on the controller. Input ID6: Typically used with a remote time clock, motion sensor or switch
(default). BMS: BMS control (see Points List). BMS can be overridden with ID6. Time Clock: Internal time clock (Scheduler). See Clock/Scheduler menu for
more information. The Scheduler can be overridden with digital input ID6.
®
Loading...
+ 30 hidden pages