Greenheck FSJ-602 Installation Manual

®
Fabricated Steel Stationary Louver
J Blade
Application and Design
FSJ-602 is fabricated stationary louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates stationary J style blades. The FSJ­602 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.
Standard Construction
thickness
Blades . . . . . . . .J Style, 20 gauge galvanized steel wall
thickness, positioned at 45º on approximately
5.5 in. centers
Construction . . .Mechanically fastened
Birdscreen . . . . .½ in. x ½ in. mesh 19 gauge galvanized steel in
removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 12 in. W x 16 in. H
Maximum Single Section Size . . . 60 in. W x 96 in. H
Options (at additional cost)
• A variety of bird and insect screens
• Blank off panel
• Clip angles
• Extended sill
• Filter rack
• Flanged frame
• Stainless steel frame and blade
• Heavier gauge blade construction
• Security bars
• A variety of architectural finishes including: Baked enamel paint Kynar paint
FSJ-602
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
®
*Width and height dimensions furnished
approximately ¼ inch under size.
Free Area Chart (Sq. ft.)
Louver Height Inches
8 12182430364248 54 60
12 0.10 0.18 0.30 0.41 0.53 0.65 0.77 0.88 1.00 1.12
18 0.22 0.39 0.65 0.90 1.16 1.41 1.67 1.92 2.18 2.43
24 0.34 0.61 1.00 1.39 1.79 2.18 2.57 2.97 3.36 3.75
30 0.46 0.82 1.35 1.88 2.41 2.94 3.49 4.01 4.54 5.07
36 0.59 1.03 1.70 2.37 3.04 3.71 4.38 5.05 5.72 6.39
42 0.74 1.30 2.15 2.99 3.83 4.68 5.52 6.37 7.21 8.06
48 0.88 1.55 2.55 3.55 4.56 5.56 6.56 7.57 8.57 9.57
54 1.02 1.79 2.95 4.12 5.28 6.44 7.60 8.77 9.93 11.09
60 1.16 2.04 3.36 4.68 6.00 7.32 8.64 9.96 11.29 12.61
66 1.30 2.28 3.76 5.24 6.72 8.20 9.68 11.16 12.64 14.12
72 1.43 2.52 4.165.8 7.43 9.07 10.70 12.34 13.98 15.61 16.93
78 1.55 2.74 4.51 6.28 8.06 9.83 11.61 13.38 15.16 16.93
84 1.67 2.95 4.86 6.77 8.69 10.60 12.51 14.42 16.34 18.25
90 1.79 3.16 5.21 7.26 9.31 11.36 16.42 15.47 17.52 19.57
96 1.92 3.37 5.56 7.75 9.94 12.13 14.32 16.51 18.70 20.89
Louver Width in Inches
FSJ-602PERFORMANCE DATA
Stationary Louver J Blade
Fabricated Steel
Greenheck Fan Corporation certifies that
WATER
PENETRATION
AIR
PERFORMANCE
AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC.
licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and water penetration ratings.
the FSJ­602 louvers shown
®
herein are
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 800 9001000 2000 3000
3
Exhaust
Intake
2345678910
3
) Water Penetration (Standard Air - .075 lb/ft3)
Free Air Velocity
Model FSJ-602 resistance to airflow (pressure drop) varies depending on louver application (air intake or air exhaust). Free area velocities (shown) are higher than average velocity through the overall louver size. See louver selection information.
Test size 48 in. x 48 in. Test duration of 15 min.
ml/m2 oz/ft2
0.30
Test Size 48 in. x 48 in.
80
60
40
20
Water Penetration per Unit Free Area
0
ft/min:
m/s:
Test Period 15 minutes
0.25
Standard Air - .075 lb/ft
0.20
0.15
0.10
0.05
0.00
800 850 900 950 1000 1050 1100
4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 5.0 5.1 5.2 5.3 5.4 5.5
3
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing various louver models and designs as to their efficiency in resisting the penetration of rainfall under specific laboratory test conditions. The beginning point of water penetration is defined as that velocity where the water penetration curve projects through .01 oz. of water (penetration) per sq. ft. of louver free area.
The beginning point of water penetration for Model FSJ-602 is
* 896 fpm free area velocity. These perfor mance ratings do not guarantee
a louver to be weather proof or stormproof and should be used in combination with other factors including good engineering judgement in selecting louvers.
Loading...
+ 3 hidden pages