Fabricated Steel Stationary Louver
J Blade
Application and Design
FSJ-402 is fabricated stationary louver designed to protect
air intake and exhaust openings in building exterior walls.
Design incorporates stationary J style blades. The FSJ402 is an extremely efficient louver with AMCA LICENSED
PERFORMANCE DATA enabling designers to select and apply
with confidence.
Standard Construction
Frame . . . . . . . .4 in. x 16 gauge galvanized wall thickness
Blades . . . . . . . .J Style, 20 gauge galvanized steel wall
thickness, positioned at 45º on approximately
4 in. centers
Construction . . .Mechanically fastened
Birdscreen . . . . .½ in. x ½ in. mesh 19 gauge galvanized steel in
removable frame, inside mount (rear)
Finish . . . . . . . . . Mill
Minimum Size . . 12 in. W x 12 in. H
Maximum Single
Section Size . . .60 in. W x 96 in. H
Options (at additional cost)
• A variety of bird and insect screens
• Blank off panel
• Clip angles
• Extended sill
• Filter rack
• Flanged frame
• Stainless steel frame and blade
• Heavier gauge blade construction
• Security bars
• A variety of architectural finishes including:
Baked enamel paint
Kynar paint
FSJ-402
WATER
PENETRATION
AIR
PERFORMANCE
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
®
*Width and height dimensions furnished
approximately ¼ inch under size.
Free Area Chart (Sq. ft.)
Louver
Height
Inches
8 12182430364248 54 60
10 0.07 0.11 0.19 0.26 0.34 0.41 0.49 0.56 0.64 0.71
12 0.13 0.23 0.38 0.53 0.68 0.83 0.98 1.13 1.28 1.43
18 0.23 0.41 0.67 0.93 1.20 1.46 1.73 1.99 2.25 2.52
24 0.38 0.67 1.10 1.54 1.97 2.40 2.84 3.27 3.70 4.14
30 0.48 0.84 1.39 1.94 2.49 3.04 3.58 4.13 4.68 5.23
36 0.63 1.11 1.82 2.54 3.26 3.98 4.69 5.41 6.13 6.85
42 0.73 1.28 2.11 2.95 3.78 4.61 5.44 6.27 7.11 7.94
48 0.88 1.54 2.55 3.55 4.55 5.55 6.55 7.55 8.56 9.56
54 0.98 1.72 2.84 3.95 5.07 6.18 7.30 8.42 9.53 10.62
60 1.12 1.98 3.27 4.55 5.84 7.12 8.41 9.70 10.95 12.27
66 1.22 2.16 3.56 4.96 6.36 7.76 9.16 10.56 11.96 13.36
72 1.37 2.42 3.99 5.56 7.13 8.70 10.27 11.84 13.41 14.98
78 1.47 2.60 4.28 5.96 7.65 9.33 11.02 12.70 14.38 16.07
84 1.62 2.86 4.71 6.57 8.42 10.27 12.13 13.98 15.83 17.69
90 1.72 3.03 5.00 6.97 8.94 10.91 12.87 14.84 16.81 18.78
96 1.87 3.30 5.43 7.57 9.71 11.85 13.98 16.12 18.26 20.40
Louver Width in Inches
FSJ-402PERFORMANCE DATA
Stationary Louver J Blade
Fabricated Steel
Greenheck
Fan
Corporation
certifies that
WATER
PENETRATION
AIR
PERFORMANCE
AIR
MOVEMENT
AND CONTROL
ASSOCIATION
INTERNATIONAL, INC.
licensed to bear the
AMCA Seal. The ratings
shown are based on
tests and procedures
performed in accordance
with AMCA Publication
511 and comply with
the requirements of the
AMCA Certified Ratings
Program. The AMCA
Certified Ratings Seal
applies to air performance
and water penetration
ratings.
the FSJ402 louvers
shown
®
herein are
Airflow Resistance (Standard Air - .075 lb/ft
Pa
in. wg
1
0.9
200
100
90
80
70
60
50
40
30
20
Static Pressure Drop
10
9
8
7
6
5
ft/min
m/s
Test Size 48 in. x 48 in.
0.8
Standard Air - .075 lb/ft
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
200200 300 400 500 600 700 800 9001000 2000 3000
3
Exhaust
Intake
2345678910
3
) Water Penetration (Standard Air - .075 lb/ft3)
Free Air Velocity
Model FSJ-402 resistance to airflow (pressure drop) varies
depending on louver application (air intake or air exhaust).
Free area velocities (shown) are higher than average
velocity through the overall louver size. See louver selection
information.
Test size 48 in. x 48 in. Test duration of 15 min.
ml/m2 oz/ft2
0.30
Test Size 48 in. x 48 in.
80
60
40
20
Water Penetration per Unit Free Area
0
ft/min:
m/s:
Test Period 15 minutes
0.25
Standard Air - .075 lb/ft
0.20
0.15
0.10
0.05
0.00
700 750 800 850 900 950 1000
3.6 3.7 3.8 3.9 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 5.0
3
Free Area Velocity
The AMCA Water Penetration Test provides a method for comparing various
louver models and designs as to their efficiency in resisting the penetration
of rainfall under specific laboratory test conditions. The beginning point of
water penetration is defined as that velocity where the water penetration curve
projects through .01 oz. of water (penetration) per sq. ft. of louver free area.
The beginning point of water penetration for Model FSJ-402 is
*
839 fpm free area velocity. These perfor mance ratings do not guarantee
a louver to be weather proof or stormproof and should be used in combination
with other factors including good engineering judgement in selecting louvers.