Electric Heated Hose Power Supply Kit
Instructions-Parts
Hopper or Hose Heat Circulation Kit
Instructions-Parts
Lower Strainer and Valve Kit
Instructions-Parts
XM Mix Manifold Kit
Instructions-Parts
Alternator Conversion Kits
Instructions-Parts
Dosing Valve Repair Kit
Instructions-Parts
High Flow Severe Duty Shutoff Check
Valve Repair Kit Instructions-Parts
312359J3
Page 4
Warnings
Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclamation point symbol alerts you to a general warning and the hazard symbol refers to procedure-specific risk. Refer back
to these warnings. Additional, product-specific warnings may be found throughout the body of this manual where
applicable.
WARNING
WARNINGWARNINGWARNING
FIRE AND EXPLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. To help prevent
fire and explosion:
•Use equipment only in well ventilated area.
•Eliminate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and plastic drop
cloths (potential static arc).
•Keep work area free of debris, including solvent, rags and gasoline.
•Do not plug or unplug power cords, or turn power or light switches on or off when flammable fumes
are present.
•Ground all equipment in the work area. See Grounding instructions.
•Use only grounded hoses.
•Hold gun firmly to side of grounded pail when triggering into pail.
•If there is static sparking or you feel a shock, stop operation immediately. Do not use equipment
until you identify and correct the problem.
•Keep a working fire extinguisher in the work area.
•Do not connect USB device in explosive atmospheres.
SPECIAL CONDITIONS FOR SAFE USE
•To prevent the risk of electrostatic sparking, the equipment’s non-metallic parts must be cleaned with
only a damp cloth.
•Refer to the Viscon HP Heater manual for special conditions for safe use.
ELECTRIC SHOCK HAZARD
Improper grounding, setup, or usage of the system can cause electric shock.
•Turn off and disconnect power at main switch before disconnecting any cables and before servicing
equipment.
•Connect only to grounded power source.
•All electrical wiring must be done by a qualified electrician and comply with all local codes and
regulations.
4312359J
Page 5
Warnings
WARNING
INTRINSIC SAFETY
Intrinsically safe equipment that is installed improperly or connected to non-intrinsically safe equipment
will create a hazardous condition and can cause fire, explosion, or electric shock. Follow local regulations and the following safety requirements.
•Only models with model number XM_D_ _ or XM_E_ _, and packaged models with part numbers
ending in 00-13, 17-23, 27-29, 31, utilizing the air-driven alternator are approved for installation in a
Hazardous (explosive atmosphere) Location - see Approvals:, page 8. Only the models stated
above meet all local safety fire codes including NFPA 33, NEC 500 and 516, and OSHA 1910.107.
To help prevent fire and explosion:
•Do not install equipment approved only for a non-hazardous location in a hazardous location.
See model ID label for intrinsic safety rating of your model.
•Do not substitute system components as this may impair intrinsic safety.
•Equipment that comes in contact with the intrinsically safe terminals must be rated for Intrinsic
Safety. This includes DC voltage meters, ohmmeters, cables, and connections. Remove the unit
from the hazardous area when troubleshooting.
•Do not connect, download, or remove USB device unless unit is removed from the hazardous (explosive atmosphere) location.
•If explosion-proof heaters are used, ensure wiring, wiring connections, switches, and electrical distribution panel all meet flame-proof (explosion-proof) requirements.
SKIN INJECTION HAZARD
High-pressure fluid from gun, hose leaks, or ruptured components will pierce skin. This may look like just
a cut, but it is a serious injury that can result in amputation. Get immediate surgical treatment.
•Do not point gun at anyone or at any part of the body.
•Do not put your hand over the spray tip.
•Do not stop or deflect leaks with your hand, body, glove, or rag.
•Do not spray without tip guard and trigger guard installed.
•Engage trigger lock when not spraying.
•Follow Pressure Relief Procedure in this manual, when you stop spraying and before cleaning,
checking, or servicing equipment.
PRESSURIZED EQUIPMENT HAZARD
Fluid from the gun/dispense valve, leaks, or ruptured components can splash in the eyes or on skin and
cause serious injury.
•Follow Pressure Relief Procedure in this manual, when you stop spraying and before cleaning,
checking, or servicing equipment.
•Tighten all fluid connections before operating the equipment.
•Check hoses, tubes, and couplings daily. Replace worn or damaged parts immediately.
MOVING PARTS HAZARD
Moving parts can pinch or amputate fingers and other body parts.
•Keep clear of moving parts.
•Do not operate equipment with protective guards or covers removed.
•Pressurized equipment can start without warning. Before checking, moving, or servicing equipment,
follow the Pressure Relief Procedure in this manual. Disconnect power or air supply.
312359J5
Page 6
Warnings
WARNING
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
•Do not operate the unit when fatigued or under the influence of drugs or alcohol.
•Do not exceed the maximum working pressure or temperature rating of the lowest rated system
component. See Technical Data in all equipment manuals.
•Use fluids and solvents that are compatible with equipment wetted parts. See Technical Data in all
equipment manuals. Read fluid and solvent manufacturer’s warnings. For complete information
about your material, request MSDS forms from distributor or retailer.
•Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manufacturer’s replacement parts only.
•Do not alter or modify equipment.
•Use equipment only for its intended purpose. Call your distributor for information.
•Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
•Do not kink or over bend hoses or use hoses to pull equipment.
•Keep children and animals away from work area.
•Comply with all applicable safety regulations.
TOXIC FLUID OR FUMES HAZARD
Toxic fluids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled, or
swallowed.
•Read MSDS’s to know the specific hazards of the fluids you are using.
•Store hazardous fluid in approved containers, and dispose of it according to applicable guidelines.
•Always wear impervious gloves when spraying or cleaning equipment.
BURN HAZARD
Equipment surfaces and fluid that’s heated can become very hot during operation. To avoid severe
burns, do not touch hot fluid or equipment. Wait until equipment/fluid has cooled completely.
PERSONAL PROTECTIVE EQUIPMENT
You must wear appropriate protective equipment when operating, servicing, or when in the operating
area of the equipment to help protect you from serious injury, including eye injury, inhalation of toxic
fumes, burns, and hearing loss. This equipment includes but is not limited to:
•Protective eyewear
•Clothing and respirator as recommended by the fluid and solvent manufacturer
•Gloves
•Hearing protection
6312359J
Page 7
Models
Models
XM sprayers are not approved for use in hazardous
locations unless the base model, all accessories, all
kits, and all wiring meet local, state, and national
codes.
Check the identification plate (ID) for the 6-digit part number of the sprayer. Use the following matrix to define the
construction of the sprayer, based on the six digits. For example, Part XM1A00 represents an XM Plural-Component
sprayer (XM); 5200 psi pump set with pump filters (1); wall power supply, no heaters, no junction box, and is not
approved for hazardous areas (A); with no additional kits (00).
NOTE:
Some configurations in the following matrix cannot be built. Consult with distributor or Graco representative.
To order replacement parts, see Parts section the XM Plural-Component Sprayer Repair-Parts manual 313289. The
digits in the matrix do not correspond to the Ref. Nos. in the Parts drawings and lists.
XM1A
First and
Second
Digits
XM
(plural com-
ponent
sprayer
mounted
on a frame)
(See Table 1 for lower models)Kit Choice
Pump Set
(hose/gun)
15200 psi
25200 psiB
36300 psi
46300 psiD
55200 psi
65200 psi
76300 psi
86300 psi
Third DigitFourth Digit
System Choice
Pump
Filters
✔
✔
✔✔
✔✔
Remote
Manifold
✔
✔
Control
Box
Wall Power
A
SupplyNE
Wall Power
Supply
Wall Power
C
Supply
IS/
AlternatorEH
IS/
E
Alternator
Fluid
Heaters
Location Category Key:
Junction
Box
✔✔
✔
✔
Location
Category
Approvals
(see page 8
for approvals
CE, FM,
FMc
NECE, FM,
c
FM
NECE, FM,
FMc
CE, FM,
FMc, Ex
EH
CE, FM,
FMc, Ex
00
Fifth and
Sixth
Digits
Additional
Kit
See Table
2 for
)
selections
NE Not for use in explosive atmospheres.
EH For use in explosive atmospheres and hazardous
locations
312359J7
.
Page 8
Models
Approvals:
See appropriate column on page 7.
XM _ A_ _
XM _ B_ _
XM _ C_ _
XM _ D_ _
XM _ E_ _
Intrinsically safe for Class I, Div 1, Group D, T2
Class I, Division 1, Group D, T2
Ta = 0°C to 54°C
See Special Conditions for Safe Use in Warnings, page 4.
FM09ATEX0015X
II 2 G
Ex d ia px IIA T2 Tamb = 0ºC to 54ºC
Table 1: Lower Models and Corresponding Identification Codes
System Pressure
Code
(MPa, bar)
1 or 55200 psi (35, 350)
Pump
Filters
✔
A Lower
(see manual 311762)
L250C4L220C4
B Lower
(see manual 311762)
2 or 65200 psi (35, 350)L250C3L220C3
3 or 76300 psi (49, 490)
✔
L180C4L145C4
4 or 86300 psi (49, 490)L180C3L145C3
Table 2: Additional Kits - Identification Code/Part No. Index
See Accessories and Kits, page 59, for more information.
See Related Manuals, page 3, for kit manual numbers.
8312359J
Page 9
Overview
Overview
Usage
XM plural-component sprayers can mix and spray most
two-component epoxy and urethane protective coatings.
When using quick-setting materials (less than 10 minute
pot life) a remote mix manifold must be used.
XM plural-component sprayers are operated via the user
interface, air controls, and fluid controls.
XM sprayers are not approved for use in hazardous
locations unless the base model, all accessories, all
kits, and all wiring meet local, state, and national
codes. See Models, page 7, to determine the appropriate location for your particular sprayer model.
Some materials may become self-igniting if applied
too thick. Read material manufacturer’s warnings and
material MSDS.
Moisture Sensitivity of
Isocyanates
Isocyanates (ISO) are catalysts used in two component
urethane coatings. ISO will react with moisture (such as
humidity) to form small, hard, abrasive crystals, which
become suspended in the fluid. Eventually a film will
form on the surface and the ISO will begin to gel,
increasing in viscosity. If used, this partially cured ISO
will reduce performance and the life of all wetted parts.
NOTE:
The amount of film formation and rate of crystallization
varies depending on the blend of ISO, the humidity, and
the temperature.
To prevent exposing ISO to moisture:
Read material manufacturer’s warnings and material
MSDS to know specific hazards and precautions
related to isocyanates.
Prevent inhalation of isocyanate mists, vapors, and
atomized particulates by providing sufficient ventilation in the work area. If sufficient ventilation is not
available, a supplied-air respirator is required for
everyone in the work area.
To prevent contact with isocyanates, appropriate personal protective equipment, including chemically
impermeable gloves, boots, aprons, and goggles, is
also required for everyone in the work area.
•Always use a sealed container with a desiccant
dryer in the vent, or a nitrogen atmosphere. Never
store ISO in an open container.
•Use moisture-proof hoses specifically designed for
ISO, such as those supplied with your system.
•Never use reclaimed solvents, which may contain
moisture. Always keep solvent containers closed
when not in use.
•Never use solvent on one side if it has been contaminated from the other side.
•Always park pumps when you shutdown.
•Always lubricate threaded parts with Part 217374
ISO pump oil or grease when reassembling.
312359J9
Page 10
Overview
Components A and B
IMPORTANT!
Material suppliers can vary in how they refer to plural
component materials.
Be aware that in this manual:
Component A refers to resin or major volume.
Component B refers to the hardener or minor volume.
NOTE:
This equipment doses the B component into the A component flow. An integration hose must always be used
after the mix manifold and before the static mixer.
NOTE:
Follow these recommendations for setup:
•use at least a 3/8 in. (10 mm) x 25 ft. (7 m) hose as
the integration hose.
•install a 24-element static mix tube after the integration hose.
Changing Materials
•When changing materials, flush the equipment multiple times to ensure it is thoroughly clean.
•Always clean the fluid inlet strainers and outlet filter
after flushing, Flush Mixed Material, page 36.
•Check with your material manufacturer for chemical
compatibility.
•Epoxies often have amines on the B (hardener)
side. Polyureas often have amines on the A (resin)
side.
NOTE:
If the amine will switch between the two sides, see
Flush Mixed Material, page 36.
Keep Components A and B Separate
NOTICE
To prevent cross-contamination of the equipment’s wetted parts, never interchange component A (resin) and
component B (hardener) parts.
10312359J
Page 11
Location
Location
XM sprayers are not approved for use in hazardous
locations unless the base model, all accessories, all
kits, and all wiring meet local, state, and national
codes. See ModelsModels, page 7, to determine the
appropriate location for your particular sprayer model.
Grounding
Connect the XM sprayer ground wire clamp (FG) to a
true earth ground. If wall power is used to power controls or heaters, ground electrical connection properly
according to local codes.
Proper Lifting of Sprayer
Follow instructions to avoid serious injury or damage
to equipment. Never lift with the hopper(s) filled.
NOTICE
Drain all fluid prior to lifting sprayer.
Lift Using a Forklift
Power must be off. Sprayer can be raised and moved
using a forklift. Carefully lift the sprayer; make sure it
balances evenly.
Lift Using a Hoist
Sprayer can also be lifted and moved using a hoist. Connect a bridle swing, hooking an end to each of the air
motor lift rings. Hook the center ring to a hoist. See the
following figure. Carefully lift the sprayer; make sure it
balances evenly.
ti21273a
FG
2.0 ft. (0.61 m)
minimum
ti21274a
312359J11
Page 12
Initial System Setup
Initial System Setup
Complete the following steps in the order they are listed,
as they apply to your specific system, for initial system
setup.
1. Check your shipment for accuracy. Ensure you have
received everything you ordered. See Component Identification, page 13, to familiarize yourself with
typical system components.
2. Mount caster kit, if ordered. See manual 406690 for
instructions.
3. Mount hopper brackets, if ordered. See manual
312747 for instructions.
4. Loosely mount hoppers, if ordered, on brackets. See
manual 312747 for instructions.
5. Connect bottom hopper outlet if using a gravity feed
pump. See manual 312747 for instructions.
6. Tighten hopper mounting bolts. See manual 312747
for instructions.
7. Mount and connect agitator(s) and feed pump(s), if
ordered. See manual 312769 for instructions.
15. For hazardous location sprayers, connect explosion-proof heaters. See Wire Sprayers with Explo-sion-Proof Heaters, page 21, and manual 309524
for instructions and recommendations.
16. Connect air supply line. See Connect Air Supply,
page 21, for instructions and recommendations.
17. Connect fluid hose assembly, including whip hose
and gun. See Connect Fluid Hose Assembly,
page 22, for instructions. Also connect remote mix
manifold, if ordered. See manual 312749 for instructions.
8. Mount and connect hopper immersion heater kit, if
ordered. See manual 312747 for instructions.
9. Connect recirculation hose, restrictor valve (including knob and nipple), and recirculation tube. Place
in hopper or drum. See manual 312747 for instructions.
10. Replace USB label (front of control panel) with correct language version, if needed.
11. Replace Alarms Codes label (under fluid control
valves) with correct language version, if needed.
12. Install hopper/hose heated circulation kit, if ordered.
See manual 313259 for instructions.
13. For non-hazardous location sprayers, connect
power cord (not supplied). See Connect Power Cord, page 19, for instructions.
14. For non-hazardous location sprayers, connect junction box wiring for immersion or recirculation heaters. See manual 312747 for immersion heater
instructions. See manual 309524 for recirculation
heater instructions.
12312359J
Page 13
Component Identification
Component Identification
Typical Setup: 20 Gallon Hoppers with Recirculation (Front View)
AFrame
BFluid Control Assembly (see Fluid Control Assembly,
page 15)
C20 Gallon Hopper Assembly (see manual 312747)
D20 Gallon Hopper Bracket (see manual 312747)
EMain Air Valve
FGCA Control Display (see User Interface Display, page
18)
312359J13
GPump Control On and Off Buttons
HAir Filter
JAir Controls
KViscon HP Fluid Heater
LJunction Box/Heater Controls (see Junction Box/Heater
Controls, page 16)
MInline Fluid Heater Control
NAir Powered Agitator
PPressure Feed Pump
RRecirculation Control Valve
Page 14
Component Identification
Typical Setup: 20 Gallon Hoppers with Recirculation (Back View)
AA Dosing Valve A
AB Dosing Valve B
AC Recirculation Valve A
AD Recirculation Valve B
AE Sampling Valve A
312359J15
AF Sampling Valve B
AG Restriction Valve
AH Mix Manifold Shutoff / Check Valve A
AJ Mix Manifold Shutoff / Check Valve B
AK Solvent Shutoff Valve
AL Pressure Sensor
AM Solvent Check Valve
Page 16
Component Identification
Junction Box/Heater Controls
BA
FIG. 4: Junction Box/Heater Controls
BB
BC
BE
BD
BA Main Power Disconnect Switch
BB Fluid Heater A Control
BC Fluid Heater B Control
Air Controls
CA
CB
FIG. 5: Air Controls
BD Hopper Heater A Control
BE Hopper Heater B Control
CC
CD
CE
CF
CG
r_XM1A00_312359_313289_14A
CA Main Pump and Air On/Off Control
CB Solvent Pump Air On/Off Control
CC Inlet Air Pressure Gauge
CD Main Pump Air Regulator
16312359J
CE Main Pump Air Regulator Gauge
CF Solvent Pump Air Gauge
CG Solvent Pump Air Regulator
Page 17
User Interface
Component Identification
DJ
IG. 6: User Interface
F
DR
DA
DG
DF
DD
DM
DB
ButtonsLEDs
DK
DC
ti13365a
DN
DH
DE
DP
Call
out ButtonFunction
DADisplay
Screen
DBStartInitiates Active Run Mode function cur-
DCStopTerminates Active Run Mode function
DDEnterPress to open drop-down fields, selection
DEAlarm
Reset
DFLeft/RightMove between screens in run or setup
DGFunctionActivates mode or action represented by
DHUp/DownMove between selection boxes,
DJSetup Key
Lock
DRUSB PortConnection for data download. Use only
Use to view Ratio, Mode Selection, Error
Conditions, Totalizers, System Information.
rently selected in Run Screen.
currently selected.
options, and save values.
Resets alarms and advisories.
modes.
the icon above each of the four buttons in
the LCD.
drop-down fields, and selectable values
within Setup screens.
Change ratio or enter Setup mode.
in non-hazardous locations.
There are four types of LEDs on the display.
Call
out LEDFunction
DKBlueDosing valve active
•on - dosing valve is active
•off - dosing valve is not active
DMGreenSpray mode active
•spray mode is on (active)
•spray mode is off (inactive)
DNRedAlarm
•on - alarm is present
•off - no alarm
DPYellowWarning
•on - is active.
•off - no warning indicated. Ratio
and setup fields are not changeable.
•flashing - key is present and
turned. Ratio and setup fields
are changeable.
312359J17
Page 18
Component Identification
User Interface Display
NOTE:
For details regarding the user interface display see User
Interface Display, page 61.
Main Display Screen Components
The following figure calls out the navigational, status, and general informational components of each display screen.
Current Date and Time
Current Status Bar
Navigate to screens
within same group
Navigational Bar
F
IG. 7: Main Display Screen Components (shown with all display features enabled)
Remaining Potlife Time
Function Display
Go back one screen
NOTICE
To prevent damage to soft key buttons, do not press
the buttons with sharp objects such as pens, plastic
cards, or fingernails.
18312359J
Page 19
Setup
Setup
Connect Power Cord
(For sprayers with heater junction boxes.
Non-hazardous location sprayers only.)
Graco does not supply heater junction box power cords.
Use the following chart to determine which power cord
your specific model requires.
Power Cord Requirements
2
VoltageCord Specification AWG (mm
240V, 1 PH4 (21.2) 2 wire + ground
240V, 3 PH6 (13.3) 3 wire + ground
380V, 3 PH6 (13.3) 4 wire + ground
NOTE:
Sprayers without heaters for non-hazardous locations
include a U.S. style NEMA 5-15 power cord and an
IEC-320 power cord. (European and Australian adapters
are also included.) These power cords are rated for
90-240 Vac, 47-63 Hz. See the XM Plural-Component
Sprayers Repair-Parts manual or the XM Plural-Component OEM Sprayers Instructions-Parts manual for part
numbers.
)
230V, 1 Phase: Use a screwdriver to connect two power
leads to the top terminals N and L2 positions. Connect
green to ground (GND).
L2
L1
7L4
L1 L2 L3N
1L1
ti8611a
123N
L1
N
PE
GRND
G
L3
L2
230V, 3 Phase Delta: Use a screwdriver to connect
three power leads to top terminals L1, L2, and L3. Connect green to ground (GND).
PE
L3
L2
L1
L1 L2 L3N
1L1
ti8612a
123N
GRND
G
L3
L1
N
L2
380V, 3 Phase WYE: Use a screwdriver to connect three
power leads to the top terminals L1, L2, and L3. Connect
neutral to N. Connect green to ground (GND).
NOTE:
Disregard terminal numbers on disconnect switch
blocks. Wire to positions shown.
1. Open junction box cover.
N
7L4
L1 L2 L3
1L1
ti8613a
L1N
123N
GRND
G
L3
L1
N
L2
PE
L3
L2
2. Connect electrical cord as follows.
312359J19
Page 20
Setup
Configure to Supply Power
(Non-hazardous location sprayers only.)
NOTE:
Disregard terminal numbers on disconnect switch
blocks. Wire to positions shown.
1. Locate power jumpers.
2. Use a flat-blade screwdriver to move red jumpers
from storage positions to positions for your power as
shown below. Push jumpers firmly into new position.
NOTE:
For 230V, 1 Phase and 230V, 3 Phase Installations,
change jumper positions as shown below. Machine is
shipped with jumpers in the fail-safe 380 3Ø position.
3. Close junction box cover.
TB2
Terminal Blocks
Position red jumpers
as shown
ti18664a
L3
L2
L1
N
380V 3ø WYE
(as shipped)
Power
Jumpers
N
L1
L2
L3
230V 3ø Delta
N
L1
L2
230V 1ø
L3
20312359J
Page 21
Setup
Wire Sprayers with
Explosion-Proof Heaters
(Hazardous location sprayers only)
If your sprayer is rated for hazardous areas, and you
have explosion-proof heaters, you must have a qualified electrician connect heater wiring. Ensure wiring
and installation comply with local electrical codes for
hazardous areas.
Improperly installed or connected equipment will create
a hazardous condition and cause fire, explosion, or electric shock. Follow local regulations.
When explosion-proof heaters are used, ensure wiring,
wiring connections, switches, and electrical distribution
panel all meet flame-proof (explosion-proof) requirements.
Refer to Viscon HP heater manual 309524 for electrical
connection instructions and guidelines in hazardous
locations.
Connect Air Supply
Connect air supply line to 3/4 npt(f) air filter inlet.
250 scfm (7.0 m
sure and flow rate are directly related to available air volume. See Pump Performance Charts, page 83.
3
/min) maximum. Available fluid pres-
3
/min) minimum;
General flow volume guidelines:
•70 scfm (1.96 m
spraying
•10 scfm (0.28 m
•10 scfm (0.28 m
pump
NOTE:
If your sprayer is for use in hazardous areas, the control
box is powered by an air-driven alternator.
NOTE:
Dosing valves are operated by air. The sprayer will not
operate correctly if the inlet air gauge drops below 50
psi (0.35 MPa, 3.5 bar) while spraying.
3
/min) per gpm (lpm) while
3
/min) added per agitator
3
/min) added per drum feed
312359J21
Page 22
Setup
Connect Fluid Hose Assembly
1. Connect fluid hose to fluid manifold outlet. Do not
install gun spray tip yet.
Fluid
Integrator
Hose
NOTICE
Do not assemble static mixer directly to the fluid manifold. Install static mixer after first 25 ft. (7.5 m) of integrator hose to ensure material doses are completely
integrated. Spraying poorly integrated material could
require rework of parts sprayed.
2. Tighten all fittings.
Adjust Packing Nuts
1. Fill A and B pump packing nuts with throat seal liq-
™
uid (TSL
low instructions in Xtreme Lowers manual 311762.
NOTE:
After the first day of use re-torque packing nuts.
2. Fill metering valves A and B packing nuts with throat
seal liquid (TSL) and tighten 1/4 turn after nut contacts packings; about 145-155 in-lbs (16-18 N•m).
r_XM1A00_312359_313289_20A
TSL
NOTE:
For pump and meter valves, check packing nut tightness
after first hour of operation and again after 24 hours.
Then check as needed, or when TSL discolors or seeps
over packing nut. Also check tightness whenever
sprayer is transported. Tighten packing nuts only when
all fluid pressure is relieved.
) and torque to 50 ft-lbs (67.5 N•m). Fol-
TSL
22312359J
Page 23
Basic Operation
Basic Operation
Power On (Alternator Power
Supplied Systems)
1. Set main pump air regulator (CD) to minimum setting.
2. Open main air valve (E) and main pump and air
valve (CA) to start air-powered alternator.
Main air pressure is displayed on gauge (CC). Fluid
Control screen will display after five seconds.
CC
CA
CD
CE
Final Setup
Perform the following steps if shutting down during
setup.
1. Relieve system pressure. See Pressure Relief Pro-cedure, page 34.
2. Flush and prime system. See Prime (page 27),
Flush Mixed Material (page 36) and Park Fluid
Pump Rods (page 38).
3. Check ratio accuracy. Run Pump and Metering
Test (page 40) and Batch Ratio Dispense Test
(page 43) to check ratio accuracy.
View Alarms
When an alarm occurs the alarm information screen
automatically displays. It shows the current alarm code
along with a bell icon. It also shows the alarm location
with top and side views of the sprayer
Power On (Wall Power Supplied
Systems)
Turn on main power disconnect. Fluid Control screen
will display after five seconds.
Adjust Ratio and Setup
1. Turn key to right (setup position). Yellow LED will
flash and the Home Setup screen will display.
2. Press and to change ratio.
3. When desired ratio is displayed, turn key to left. Yellow LED will turn off.
4. Change optional setup selections to desired parameters, as described in Set System Settings (Optional), page 24.
There are two levels of error codes: alarms and advisories. A bell icon indicates an alarm. A solid bell icon with
an exclamation point and three audible alerts indicate a
alarm. And an outlined hollow bell icon and a single
audible alert indicate an advisory.
Diagnose Alarms
See Alarm Codes and Troubleshooting, page 52, for
causes and solutions to each alarm code.
Clear Alarms
Press to clear alarms and advisories. Press
to return the run (fluid control) screen.
For more information on alarms and alarm codes, see
Alarms, page 51.
312359J23
Page 24
Basic Operation
Set System Settings (Optional)
NOTE:
For details regarding the user interface display screens
see User Interface Display, page 61.
To set user interface parameters and USB parameters,
press from the Home Setup screen.
Set User Interface Parameters
Press from the potlife/hose length screen to
move to the user interface parameters screen.
The following user interface parameters are configurable:
•date format
•date (factory set)
•time (factory set)
•units of measurement for:
•fluid flow rate
•pressure
•temperature
•hose length
To change the date format, press to select the field.
To change the date and time, press to select the
field. Press to make the field selectable. Press
and to scroll through each digit. Press
and to move to the next digit in the field.
Press to save the change.
Set USB Parameters
Press from the user interface parameters
screen to move to the USB parameters screen.
To set the sprayer number, configure the number of
hours downloaded to external USB flash drive, and how
Press to open the drop down field. Press
and to select the preferred format. Press
again to save that date format. Follow this procedure to
change the units of measurement formats as well.
often the data will record: press and to move
through each field. Press to make a field select-
able. Press and to scroll through each digit.
Press and to move to the next digit in
each field. Press to save the change.
24312359J
Page 25
Basic Operation
Set Maintenance Parameters
(Optional)
NOTE:
Prior to configuring system settings, see Enable Setup
Screens, page 66, to ensure screens shown in this sec-
tion are viewable and configurable. If they are not, follow
instructions in Enable Setup Screens to enable them.
NOTE:
For details regarding the user interface display screens
see User Interface Display, page 61.
To set maintenance parameters for pumps and valves,
including maintenance schedules, press from
the Home Setup screen.
Use the first screen to set maintenance setpoint
amounts for pumps and dosing valves. Use the second
screen to set the maintenance schedule for changing
the incoming air filter.
Set Maintenance Schedule
To set the number of days between changing the incoming air filter that will result in a reminder advisory, press
to move to the Maintenance Setup 2 screen.
Press to make the field selectable. Press
to scroll through each digit, and press and to
scroll through the optional values. Press to save
the number of days value.
Set Maintenance Setpoints
To set maintenance setpoint values, press and
to move through each field, and press to
make a field selectable. Press to scroll through
each setpoint digit. Press and to scroll
through the optional values. Continue this process until
the desired setpoint is reached. Press to save
that setpoint.
312359J25
Page 26
Basic Operation
Set Sprayer Limits (Optional)
NOTE:
For details regarding the limits setup screens, see User
Limits Setup Screens, page 68.
To set and adjust pump pressure limits and temperature
limits:
1. Select in the Enable Setup 2 screen. See
Enable Setup Screens, page 66, for instructions.
2. From the Home Setup screen press to jump
to the limits screens.
3. Follow the instructions in Set Pressure Limits and
Set Temperature Limits.
Set Pressure Limits
Set Temperature Limits
Use the following instructions to set temperature limits
that if met will issue an advisory and/or warning.
Press to move to the temperature limits screen.
To set temperature limits, press and to move
through each field, and press to make a field
selectable. Press to scroll through each tempera-
ture digit, and press and to scroll through the
optional values. Continue this process until you reach
your desired temperature limit. Press to save the
value.
NOTE:
The allowable range for the temperature setpoint is 34° 160°F (1° - 71°C).
Use the following instructions to set pressure limits for
each pump that if met will issue an advisory and/or
warning.
To set pressure limits, press and to move
through each field, and press to make a field
selectable. Press to scroll through each pres-
sure digit, and press and to scroll through the
optional values. Continue this process until you reach
the desired pressure limit. Press to save.
NOTE:
The B pump pressure always runs 10-20% higher than
the A pump pressure.
26312359J
Page 27
Prime
Prime
Prime A and B Fluids
Wear gloves when using flush solvents and/or if fluid
temperature exceeds 110° F (43° C).
NOTE:
Do not install gun spray tip yet. To avoid splashing, use
the lowest pressure possible to prime.
1. Condition materials prior to adding to hoppers.
Ensure resin materials are thoroughly agitated,
homogenous, and pourable prior to adding to hopper. Stir hardeners back into suspension prior to
adding material to hopper.
2. Fill A and B reservoirs with proper materials. Fill A
side with major volume of material; fill B side with
minor volume of material.
4. Open ball valves into pumps.
5. Turn mix manifold valves (AH, AJ) clockwise to
close them.
AJ
AH
20 Gallon Hopper Shown
3. Move recirculation lines to empty containers.
7. Use manual pump run mode.
6. Turn on air supply. Set main pump air regulator (CD)
to 20 psi (138 kPa 1.38 bar).
CD
312359J27
Page 28
Prime
NOTE:
When run independently set to or
. Press
and as needed to prime. Monitor containers
to avoid overflow.
8. Select Pump A . Press . Slowly turn
main pump air regulator (CD) clockwise to increase
air pressure until pump A starts. Dispense into pail
until clean fluid comes out of A. Close recirculation
valve.
NOTE:
When priming or flushing pumps, it is normal to get cav-
itation or pump runaway alarms. Clear alarms , and
press again as necessary. These alarms prevent
excessive pump speeds, which will damage pump packings.
11. Dispense a small amount of each material through
both sampling valves (AE, AF).
NOTE:
Open sampling valves slowly to avoid splashing.
AFAE
12. Close both sampling valves (AE, AF).
NOTE:
If a remote mix manifold is used, disconnect hoses at
mix manifold and prime with material. Reconnect hoses.
9. Move recirculation line back to reservoir.
10. Repeat for B side.
28312359J
Page 29
Prime
Prime Solvent Flush Pump
1. Connect flush pail ground wire to a metal pail of solvent.
2. Place siphon tube in the pail of solvent.
3. Open solvent flush valve (AK) on mix manifold.
AK
5. Disengage trigger lock and trigger gun into a
grounded pail. Use a pail lid with a hole to dispense
through. Seal around hole and gun with a rag to prevent splash back. Be careful to keep fingers away
from front of gun.
TI1950a
TI1953a
6. Open solvent pump air valve (CB). Pull out and
slowly turn solvent pump air regulator (CG) clockwise to prime solvent pump and push air out of mix
hose and gun. Trigger gun until all air is purged.
CG
CB
4. Ensure trigger lock is engaged. Remove spray tip.
TI1949a
4)!
TI1948a
7. Close solvent pump air valve (CB) and trigger gun to
relieve pressure. Engage gun trigger lock.
TI1949a
312359J29
Page 30
Recirculate
Recirculate
Without Heat
If using a system that does not require heat, recirculation is still required prior to spraying. Recirculation
ensures that any settled fillers are mixed in, the pump
lines are fully primed, and the pump check valves are
operating smoothly.
1. Follow Prime, page 27.
2. Close mix manifold valves (AH, AJ).
AJ
AH
4. Open recirculation valves (AC, AD).
.
AC
5. Select pumps to recirculate by pressing to
scroll through: , , or .
6. Turn on the main air shutoff valve (CA). Use system
air regulator (CD) to slowly increase the air pressure
to the pumps until they start running slowly.
AD
3. Ensure recirculation hoses are in the correct hoppers.
CA
7. If the pumps are running too quickly, close the
restrictor on each fluid line.
CD
30312359J
Page 31
Recirculate
8. Run the pumps until the material has reached the
desired temperature. See Heat Fluid, page 31.
9. Once desired temperature is reached, press .
10. Turn off the main air shutoff valve (CA).
CA
11. Close recirculation valves (AC, AD).
With Heat
Using recirculation mode when heating the material is
required. Note the temperature at the top of the heater
(outgoing or back to hopper). When the thermometer
and display reach operating temperature, the material is
ready to spray.
Heat Fluid
To heat fluid evenly throughout the system:
1. Circulate fluid at approximately 1 gpm (10-20
cycles/min.) to raise temperature of hoppers to
80-90° F (27-32° C).
2. Decrease circulation rate to approximately 0.25 gpm
(5 cycles/min.) to increase the heater outlet temperature to match the spray temperature.
NOTE:
Circulating fluid too quickly without decreasing the circulation rate will increase only the hopper temperature.
Similarly, circulating fluid too slowly will increase only
the heater outlet temperature.
AC
12. See Spray, page 32.
NOTE:
If you circulate the A side pump at pressures greater
than 3000 psi (21 MPa, 210 bar), an advisory is issued
and the yellow LED on the display illuminates. This is a
reminder to select Spray mode prior to spraying and to
circulate at a lower pressure to avoid excessive pump
wear.
If you circulate the A side pump above 5200 psi (35.4
MPa, 354 bar), an alarm shuts the pump down to prevent accidentally spraying material while still in circulation mode.
AD
NOTE:
Agitate, recirculate, and heat material only as necessary
to avoid mixing air into the fluid.
312359J31
Page 32
Spray
Spray
Wear gloves when using flush solvents and/or if fluid
temperature exceeds 110° F (43° C).
NOTE:
After the first day of spraying follow Pressure Relief
Procedure, page 34, and then tighten throat seals on
both pumps and dosing valves.
1. If heaters are used, use heater junction box to turn
them on. To adjust heater temperature, refer to the
Viscon HP manual for instructions, and the Heat Fluid section, page 31.
.
3. Adjust pump air regulator to 30 psi (0.21 MPa, 2.1
bar).
4. Select. Press .
5. Disengage trigger lock and trigger gun into a
grounded metal pail. Use a metal pail lid with a hole
to dispense through to avoid splashing. Dispense
flush solvent out of mix hose until a well mixed coating flows from the gun.
TI1950a
TI1953a
6. Engage trigger lock. Install tip on gun.
Fluid Heater B
Fluid Heater A
ti21275a
2. Close recirculation valves and mix manifold flush
valve. Open mix manifold valves A (blue) and B
(green).
.
Resin
Circulate
Resin
Valve
(Blue)
Hardener
Circulate
Hardener
Val ve
(Green)
TI1949a
7. Adjust air regulator (CD) to the necessary spraying
pressure and apply coating to a test panel. Look at
ratio screen to ensure it is reading the correct ratio.
Also, look at bar graph to ensure mix manifold
restriction adjustment is within optimal range. Refer
to Batch Ratio Dispense Test, page 43 and Adjust B Machine Outlet Restriction, page 33.
8. Follow Flush Mix Manifold, page 36, or Park Fluid Pump Rods, page 38, when you are finished spraying or before potlife expires.
NOTE:
Mixed material potlife or working time decreases with
increased temperature. Pot life in hose is much shorter
than dry time of coating.
32312359J
Page 33
Adjust B Machine Outlet Restriction
Adjust B Machine Outlet
Restriction
Adjust the restriction stem on mix manifold, or on restrictor valve if mix manifold is remote, to optimize the B side
dosing control window. The goal is to create a near constant flow on the A side and frequent dosing or a near
constant flow on the B side.
Mix Manifold
Restriction
Stem
1. With material at normal spray temperature and tip
installed on spray gun, trigger gun for at least 10
seconds.
NOTE:
•For remote mix manifolds, set the machine restrictor
first. Then close the remote mix manifold restrictor
to approximately the same setting, or until the
restrictor screen starts to move to the left.
•It is normal for the bar to move on the graph while
spraying. If the adjustment is too far off, you will
receive an alarm. If the ratio will not hold, you will
receive alarm R4B or R1B. See Alarm Codes and Troubleshooting, page 52.
•If the bar swings back and fourth and you are using
feed pumps, the feed pressure may be too high.
Keep feed pressure under 250 psi (1.75 MPa, 17.5
bar). High pressure pumps receive a pressure boost
that is twice the pressure feed on the upstroke only.
High feed pressures can cause pressure swings
between A and B. The system will compensate, but
the bar graph will the show the swing.
Resin
dosing
size
Combined
flow rate
2. Navigate to Ratio Mode screen. See Ratio Mode,
page 71. Check bar graph.
The ratio bar graph is shown when is pressed.
This screen is used to show the accuracy of the spray
ratio. The bar should be in the center three segments
when the restrictor is adjusted.
3. Press to go to the restrictor adjustment screen.
The restrictor adjust bar graph is shown when is
pressed. This screen is used to adjust the restrictor.
•At maximum fluid flow, the bar should be in the center.
•At flows less than maximum, the bar should be on
the right side.
•The bar should never be on the left.
•Configure the system at maximum fluid flow. Then
turn the restrictor clockwise if the bar graph is on the
right and counter-clockwise if the bar graph is on the
left.
NOTE: A pump dosing size, shown on the upper left corner, will be minimum when the restrictor is adjusted correctly. Once the restrictor is set for a given ratio and
material, it should be locked in place and left alone.
312359J33
Page 34
Pressure Relief Procedure
Pressure Relief Procedure
Follow Flush Mixed Material when you stop spraying
or dispensing; and before cleaning, checking, servicing, or transporting equipment.
Relieve A and B Fluid Pressure
7. Hold a metal part of the gun firmly to a grounded
metal pail with a splash guard in place. Trigger gun
to relieve pressure in material hoses.
1. Engage trigger lock.
TI1949a
2. Press .
3. If fluid heaters are used, shut them off using the
controls on the heater control box or the heater
power junction box.
.
Fluid Heater B
Fluid Heater A
TI1953a
8. Engage trigger lock.
TI1949a
Relieve Pump Fluid Pressure and Flush Mix
Hose
9. Close mix manifold valves (AH, AJ), then open solvent flush valve (AK) on mix manifold.
AK
AH
AJ
ti21275a
4. Shut off feed pumps, if used.
5. Remove spray tip and clean.
6. Disengage trigger lock.
TI1950a
34312359J
Page 35
Pressure Relief Procedure
10. Open solvent pump air control valve (CB). Use lowest pressure needed to flush material out of hose.
CB
11. Disengage trigger lock.
TI1950a
13. Shut off solvent pump air control valve (CB).
14. Disengage trigger lock.
15. Close solvent flush valve (AK) on mix manifold.
AK
16. Release any residual gun pressure and engage trigger lock.
12. Hold a metal part of the gun firmly to a grounded
metal pail with a splash guard in place. Trigger gun
to flush mixed material out of line with clean solvent.
TI1949a
312359J35
Page 36
Flush Mixed Material
Flush Mixed Material
Flush Mix Manifold
Use Solvent Pump
1. Press to turn off system. Engage trigger lock.
Remove spray tip.
4)!
TI1949a
2. Ensure sampling valves (AE, AF) and mix manifold
valves (AH, AJ) are closed.
TI1948a
4. Open solvent pump air valve (CB). Pull out and
slowly turn solvent pump air regulator (CG) clockwise to increase air pressure. Use lowest possible
pressure.
.
CG
CB
5. Disengage trigger lock and trigger gun into a
grounded pail. Use a pail lid with a hole to dispense
through. Seal around hole and gun with a rag to prevent splash back. Be careful to keep fingers away
from front of gun. Flush out mixed material until
clean solvent dispenses.
AE
AH
3. Open solvent shutoff valve (AK) at mix manifold.
AF
AK
AJ
TI1950a
6. Engage trigger lock.
TI1953a
TI1949a
36312359J
Page 37
Flush Mixed Material
7. Close solvent pump air valve (CB) and solvent shutoff valve (AK) at mix manifold. Trigger spray gun to
relieve pressure.
AK
8. Follow Pressure Relief Procedure, page 34.
9. Engage trigger lock.
TI1949a
10. Disassemble and clean spray tip with solvent by
hand. Reinstall on gun.
312359J37
Page 38
Park Fluid Pump Rods
Park Fluid Pump Rods
1. Relieve pressure. See Pressure Relief Procedure,
page 34.
2. Press.
3. Turn recirculation valves (AC, AD) counter clockwise
to open them. Each pump will run through recirculation until they reach the bottom stroke, and then
stop.
ADAC
5. Shut off main pump air valve (CA) and air supply to
entire system.
CA
CB
4. When each blue pump LED turns off, close the corresponding circulation valve.
ADAC
38312359J
Page 39
Shutdown Entire System
Shutdown Entire System
Follow this procedure prior to servicing equipment or
shutdown.
1. Follow Flush Mixed Material, page 36. Use a metal
pail lid with a splash guard to avoid splashing.
TI1953a
2. Engage trigger lock, turn off air regulator, and close
main air shutoff valve. Remove spray tip.
4)!
TI1949a
TI1948a
3. For overnight shutdown:
•Follow Park Fluid Pump Rods on page 38.
•Cap fluid outlets to keep solvent in the lines.
•Fill pump A and B packing nuts with throat seal
liquid (TSL).
312359J39
Page 40
System Verification
System Verification
Graco recommends running the following tests daily.
Mix and Integration Tests
Use the following tests to check for proper mix and integration.
Butterfly Test
At low pressure, normal flow rate, and without a spray tip
installed, dispense a 1/2 in. (12.7 mm) bead of material
onto foil until multiple changeovers of each pump have
occurred. Fold the sheet of foil over the fluid then peel it
back and look for unmixed material (appears marble-like).
Curing Test
Spray a single continuous pattern on foil at typical pressure setting, flow rate, and tip size until multiple changeovers of each pump have occurred. Trigger and
de-trigger at typical intervals for the application. Do not
overlap or cross over your spray pattern.
Check curing at various time intervals, listed on the
material data sheet. For example, check for dry to touch
by running your finger along the test pattern’s entire
length at the time listed on the data sheet.
NOTE:
Spots that take longer to cure indicate insufficient integration.
Appearance Test
Pump and Metering Test
This test checks the following four items and should be
run every time a new job is started, or if there is a suspected problem.
•Verifies that the pumps installed match the pumps
selected on the Setup screen by dispensing exactly
750 ml of each material.
•Verifies that each pump holds fluid against the pump
inlet valve by stalling on the down stroke.
•Verifies that each pump holds fluid against the pump
piston valve and packings by stalling on the
upstroke.
•Verifies that each metering valve holds fluid, and
that there are no external leaks between the pump
and metering valve.
•Verifies that the recirculation valves (AC, AD) are
closed and do not leak.
This test will dispense 750 ml of component A, and then
750 ml of component B. Dispense into separate cups so
the fluid can be returned to the supply tanks.
NOTE:
During each dispense the flow will stop once to stall the
upstroke, once to stall the downstroke, and then it will
finish the dispense. Do not close the sampling valve until
the third flow stops and the blue pump light (DK) goes
out.
1. Enter Test mode in the run (fluid control) screen.
See Test Screens on page 71. Select
run pump test.
to
Spray material onto metal substrate. Look for variations
in color, gloss, or texture that may indicate improperly
catalyzed material.
40312359J
Page 41
System Verification
2. Set main pump air regulator (CD) pressure to zero.
Open main pump and air valve (CA). Adjust main
pump air regulator (CD) pressure to 50 psi (0.35
MPa, 3.5 bar).
CA
CD
3. Dispense fluid A:
a. Close recirculation valves (AC, AD), mix mani-
fold valves (AH, AJ), and both sampling valves
(AE, AF).
.
AC
AD
b. Place a clean 1 quart (1000 cc) container under
sampling valve A (AE).
c. Press . Pump A light (DK) comes on.
d. Slowly open and adjust sampling valve A (AE)
to achieve desired flow. Pump stops automatically; twice during test and again when dispense completes. Pump A light (DK) turns off,
Pump B light (DK) turns on.
AE
AH
AF
AJ
4. Close sampling valve A (AE).
5. Dispense fluid B as follows:
a. Place a clean 1 quart (1000 cc) container under
sampling valve B (AF).
312359J41
Page 42
System Verification
b. Slowly open and adjust sampling valve B to
achieve desired flow. Pump stops automatically;
twice during test and again when dispense
completes. Pump B light (DK) turns off.
c. Close sampling valve B (AF).
6. Compare fluid amounts in containers; they should
be equal at 750 ml (25.3 fl. oz.) each. Repeat test if
fluids are not equal. If problem persists, see Alarm Codes and Troubleshooting, page 52
.
7. Return fluid used in test to corresponding fluid supply container.
Confirm Pump Test
The Confirm Pump Test screen displays when the pump
test completes without error. This screen displays the
target volume of material dispensed into each beaker
from each pump.
42312359J
Page 43
System Verification
Batch Ratio Dispense Test
NOTE:
This test dispenses a calculated volume of each fluid
based on ratio. The two fluids combined equal the batch
size selected.
Follow this procedure to dispense a batch (into one container) for touch-up work or to verify a ratio setting (use
separate containers for fluids A and B).
Dispense into a container with graduations no greater
than 5% of each component. If the ratio is known by
weight, use a scale for greatest accuracy.
1. Enter Test mode in the run (fluid control) screen.
See Test Screens on page 71. Select
batch dispense test.
to run
CA
CD
4. Close recirculation valves (AC, AD), mix manifold
valves (AH, AJ), and sampling valves (AE, AF).
.
AC
AE
AD
AF
2. Adjust dispense amounts from 500 ml to 2000 ml (in
250 ml increments) by pressing to open the
drop-down box. Then press and to select
the desired value. Press to select that value.
3. Set main pump air regulator (CD) pressure to zero.
Open main pump and air valve (CA). Adjust main
pump air regulator (CD) pressure to 50 psi (0.35
MPa, 3.5 bar).
AH
5. Place a clean container under sampling valve A
(AE).
AJ
6. Press . Pump A light comes on.
312359J43
Page 44
System Verification
7. Dispense fluid A. Slowly open and adjust sampling
valve A (AE) to achieve desired flow. The pump
stops automatically when dispense completes.
Pump A light (DK) turns off, Pump B light (DK) turns
on.
8. Close sampling valve A (AE).
9. Dispense fluid B as follows:
a. Batch dispense: move container under sam-
pling valve B (AF).
Ratio check: place clean container under sampling valve B (AF).
The gray at the bottom of the beaker represents the volume of material dispensed by pump A and the black at
the top of the beaker represents the volume of material
dispensed by pump B.
Down Stream Valve Leak Test
This test confirms or troubleshoots leaks in components
located down stream of the dosing valves. Use this test
to detect closed or worn valves, and to detect leaks in
circulation valves installed at a remote mix manifold.
b. Slowly open and adjust sampling valve B (AF)
to achieve desired flow. The pump stops automatically when dispense completes. Pump B
light (DK) turns off.
c. Close sampling valve B (AF).
10. Batch dispense: stir material until mixed.
Ratio check: compare A and B fluid dispensed.
Confirm Batch Dispense Test
The Confirm Batch Dispense Test screen displays when
the batch dispense test completes without error. This
screen displays the selected ratio between the pumps
and the volume of material dispensed from each pump.
1. Close both mix manifold valves downstream of the
dosing valves.
2. Close recirculation valves (AC, AD).
3. Enter Test mode in the run (fluid control) screen.
See Test S creen s on page 71. Select
down stream valve leak test.
4. Select
(AA, AB) are open by verifying blue LEDs are illuminated for both dosing valves.
5. If test is successful, both pumps will stall against the
down stream valves when the dosing valves (AA,
AB) are open. If any movement is detected in the
pumps after stalling, an alarm is issued indicating
which side has a leak.
. Press. Ensure dosing valves
to run
44312359J
Page 45
System Verification
XM Setup and Troubleshooting Guide
The following setup information will help ensure the system is setup properly. See the XM repair-parts manual for troubleshooting and repair instructions.
Grounding
•Ground system to a true earth ground.
•Ensure incoming power is grounded.
Air Supply
•Use at least a 3/4 in. (19mm) ID air hose, no longer
than 50 feet (15m).
•Ensure the first gauge (supply) stays above 80 psi
(0.55 MPa, 5.5bar) while spraying.
•Ensure that the pump spray pressure regulator is set to
at least 35 psi (2.4 bar) for spraying.
•Ensure that the solenoid air filter/regulator behind the
air panel is set to at least 80-85 psi.
•Check that the air filter element in the solenoid air filter/regulator behind the air panel is clean.
Calibration
•Adjust the B side fluid restrictor so that the calibration
bar graph averages center to right middle. This means
that the “B” dosing valve is open 25% to 75% of the
time.
•Ensure dosing valve needle packing nuts are not
adjusted too tight. They should be snug when there is
no fluid pressure on the valve.
•If feed pumps are used, don’t use more than 250psi
(17 bar). Excess pressure adds double the amount of
pressure on only the upstroke of the XM metering
pump.
Motor Icing
•Ensure that the NXT motor De-Ice bleed valves are
open to bleed warm air across the ice.
•Ensure that the motor is left active when not spraying
to keep the internal bleed air working. Leave the motor
active in Spray mode or Manual mode to keep the
bleed air on.
Restrictions or Lost Pressure
•Always use filter screens in the XM pump lowers. Filter
style pumps come with 60 mesh screens. Optional 30
mesh elements are also supplied.
•Always use a gun filter. 60 mesh is provided in the gun.
Check that the static mixer is clean.
•Early mix manifolds (2009) had a 40 mesh screen on
the B side. The screen could plug with materials that
have filled ‘B’ side fluids.
Remote Mix Manifold Applications
Ensure remote mix manifold outlet kit is installed. See XM
Repair parts manual. The kit includes outlet check valves
which isolate the pump pressure sensors from the outlet
hoses, and includes a ‘B’ side restrictor valve for the
machine outlet.
NOTE: Early remote manifold machines didn’t include
the ‘B’ restrictor valve from the factory.
•Ensure that the ‘A’ and ‘B’ outlet hose sizes volume
balanced close to the mix ratio. Unbalanced hose sizes
can cause off ratio slugs at the mix manifold during
pressure and/or flow transitions. See XM Mix Manifold
Kits manual.
•If a minimum of integration and mix hose is used,
ensure that “Fast Dosing” is selected in the setup
screens
Air motors accumulate ice in the exhaust valving and muffler under hot and humid conditions or under cold ambient
conditions. It can cause pressure loss or motor stalling.
•The ‘B’ fluid pressure should always be 15% to 30%
higher than ‘A’ pressure.
•A larger pressure difference indicates ‘A’ motor icing.
•A smaller or negative pressure difference indicates ‘B’
motor icing.
312359J45
Software Version
•Ensure all modules in the system use software from
same token. Different software versions may not be
compatible.
•The latest software version for each system can be
found at Tech Support at www.graco.com.
Page 46
Empty and Flush Entire System (new sprayer or end of job)
Empty and Flush Entire System
(new sprayer or end of job)
Procedure
1. Follow Prime, page 27 and Flush Mixed Material,
page 36, as required. Engage trigger lock. Turn
main pump air regulator (CD) fully counter-clock-
NOTE:
•If the system includes heaters and heated hose,
turn them off and allow to cool before flushing. Do
not turn on heaters until fluid lines are clear of solvent.
•Cover fluid container and use the lowest possible
pressure when flushing to avoid splashing.
•Before color change or shutdown for storage, flush
at a higher flow rate and for a longer time.
wise to shut off.
CD
•To flush only the fluid manifold, see Flush Mixed
Material, page 36.
Guidelines
Flush new systems if coating materials will be contaminated by 10W oil.
Flush system when any of the following situations occur.
Flushing will help prevent materials from clogging the
line between hoppers and pump inlets.
•anytime sprayer will not be used for more than
one week
•if materials used will settle
•if using thixotropic resins that require agitation
2. Move circulation return lines to separate fluid containers to pump remaining fluid out of system.
3. Increase main pump air regulator (CD) pressure to
20 psi (138 kPa, 1.38 bar).
4. Select . Press.
NOTE:
When running pumps independently set to or
. Press and as needed to clean.
NOTE:
If sprayer does not start with static pressure, increase
air pressure by 10 psi (69 kPa, 0.7 bar) increments. To
avoid splashing, do not exceed 35 psi (241 kPa, 2.4
bar).
46312359J
Page 47
Empty and Flush Entire System (new sprayer or end of job)
5. Open recirculation valves (AC, AD) for respective
pump dispense side. Run pumps until the A and B
reservoirs are empty. Salvage the material in separate, clean containers.
AC
AD
NOTE:
When priming or flushing the pumps, it is normal to get
cavitation or pump runaway alarms. Clear the alarms
, and press again as necessary. These
alarms prevent excessive pump speeds that can damage pump packings.
9. Close recirculation valves (AC, AD) and open mix
manifold valves (AH, AJ). Dispense fresh solvent
through mix manifold valves and out gun.
AC
AE
AF
AH
10. Close mix manifold valves (AH, AJ).
11. Slowly open sampling valves (AE, AF) to flush solvent through until clean. Close sampling valves.
Press .
AD
AJ
6. Wipe reservoirs clean, then add solvent to each.
Move circulation lines to waste containers.
7. Repeat Step 4 to flush through each side until clean
solvent exits recirculation hose.
8. Press . Move recirculation hoses back to reservoirs. Continue recirculating until system is thoroughly flushed.
12. Follow Park Fluid Pump Rods, page 38.
13. Remove pump fluid filters, if installed, and soak in
solvent. Clean and replace filter cap. Clean filter
o-rings and leave out to dry. Do not leave o-rings in
solvent.
14. Close main air valve (E).
NOTE:
Fill A and B pump packing nuts with TSL. Also, always
leave some type of fluid, such as solvent or oil, in the
system to prevent scale build up. This build up can flake
off later. Do not use water.
312359J47
Page 48
Download Data from USB
Download Data from USB
Do not connect USB device in explosive atmospheres.
Download Setup
Navigate to the System Setup screen. Change the number of hours of recorded data to download (default is
768 hours), by pressing and to move
USB Logs
Spray Log 1
(Default log for download.) The spray log records key
data while the system is in spray mode. It records A and
B temperature, A and B pressure, A and B flow, A and B
batch totals, ratios, restrictor adjustments, alarm codes,
and commands.
By default, the spray log records data every 60 seconds.
This 60 second interval will record about 32 days of data
if spraying 8 hours per day, 7 days per week. To change
the default, see Download Setup, page 48. This log
can hold up to 18000 lines of data.
NOTE:
Once the spray log is full, new data automatically overwrites old data.
NOTE:
After data in the spray log is downloaded it remains in
the USB module until it is overwritten.
Alarm Log 2
The alarm log records all alarm codes generated over a
two year period. This log should be used for troubleshooting purposes and cannot be deleted. This log can
hold up to 73000 lines of data.
Data Log 3
The data log records (every 120 seconds) all data that
occurs during spray mode over a two year period. This
log should be used for troubleshooting purposes and
cannot be deleted. This log can hold up to 84000 lines
of data.
to. Press to make the field selectable.
Press to scroll through each digit. Press
to save the new digit. Follow the same procedure
to change the time interval at which data will record
(default is 60 seconds). Exit the System Setup screen.
Download Procedure
Remove sprayer from hazardous location or remove
the hazard before inserting, downloading, or removing
USB flash drive.
1. Insert USB flash drive into USB port (DR). Use only
Graco-recommended USB flash drives; see Rec-
ommended USB Flash Drives, page 75.
NOTE:
Inserting the USB flash drive while the sprayer is running will stop sprayer operation.
NOTE:
The 120 second recording period cannot be adjusted.
48312359J
Page 49
Download Data from USB
2. The USB download screen automatically displays,
and the selected log(s) automatically downloads.
The USB symbol flashes to indicate download is in
process.
NOTE:
To cancel download, press while in process. Wait
for USB icon to stop flashing, and then remove USB
flash drive.
3. The USB icon stops flashing when download com-
pletes. The box below displays , which indicates the download was successful
4. Remove USB flash drive from USB port (DR).
Never leave USB flash drive in USB port (DR).
7. Open Graco folder.
8. Open sprayer folder. If downloading data from more
than one sprayer, there will be more than one
sprayer folder. Each sprayer folder is labeled with
the corresponding USB serial number.
9. Open DOWNLOAD folder.
10. Open folder labeled with the highest number. The
highest number indicates the most recent data
download.
11. Open log file. Log files open in Microsoft
®
Excel® by
default. However, they can also be opened in any
text editor or Microsoft
®
Word.
NOTE:
All USB logs are saved in Unicode (UTF-16) format. If
opening the log file in Microsoft Word, select Unicode
encoding.
5. Insert USB flash drive into USB port of computer.
6. The USB flash drive window automatically opens. If
it does not, open USB flash drive from within Win-
®
Explorer.
dows
312359J49
Page 50
Maintenance
Maintenance
Filters
Once a week check, clean, and replace (if needed) the
following filters. Be sure to follow the Flush Mixed Mate-rial, page 36, prior to performing filter maintenance.
•Both pump filters; see manual 311762 for instructions.
•Main air inlet manifold filter; see manual 313289,
Replace Air Filter Element section, for instructions.
•Air regulator filter (5 micron) on air control assembly; see manual 313289, Replace Air Filter Element
section, for instructions.
•B side mix manifold strainer (as required); see manual 312749.
Seals
Once a week, check and tighten throat seals on both
pumps and dosing valves. Be sure to follow the Flush
Mixed Material, page 36, prior to tightening seals.
Cleaning Procedure
1. Ensure all equipment is grounded. See Grounding,
page 11.
2. Ensure the area where the sprayer will be cleaned is
well ventilated; and remove all ignition sources.
3. Turn off all heaters and allow equipment to cool.
4. Flush mixed material. See Flush Mixed Material,
page 36.
5. Relieve pressure. See Pressure Relief Procedure,
page 34.
6. Shutdown sprayer and turn off all power. See Shut-down Entire System, page 39.
7. Clean external surfaces only using a rag soaked in
solvent that is compatible with the spray material
and the surfaces being cleaned.
8. Allow enough time for solvent to dry before using
sprayer.
50312359J
Page 51
Alarms
Alarms
View Alarms
When an alarm occurs the alarm information screen
automatically displays. It shows the current alarm code
along with a bell icon. It also shows the alarm location
with top and side views of the sprayer.
There are two levels of alarms: warnings and advisories.
A bell icon indicates an alarm. A solid bell icon with an
exclamation point and three audible alerts indicate a
warning. And an outlined hollow bell icon and a single
audible alert indicate an advisory.
Advisories are notifications that require attention but not
immediately. Alarms require immediate correction;
therefore, sprayer operation automatically stops.
This screen also shows diagnostic information. There
are three lines of data on the left side. The top line
shows the power supply or alternator power supply. This
should be between 23-25 Volts for power supply systems and 10-14 Volts for alternator systems. The middle
line shows the sensor voltage. This should be between
4.9-5.1 Volts.
IconFunction
Moving up
Moving down
Top changeover
Bottom changeover
One reed switch signal is missing
Blank: No reed switch signal
Diagnose Alarms
See Alarm Codes and Troubleshooting for causes
and solutions to each alarm code.
Clear Alarms
Press to clear alarms and advisories. From the
alarm information screen, press to return to the
run (fluid control) screen.
The center of the screen shows linear sensor vertical
bar graphs and reed switch information. The A side
information is on the left and the B side information is on
the right. Linear sensor position is displayed on the bar
graph that goes up and down when the pump moves.
This bar graph should move from top to bottom to match
each pump stroke.
The state of the two reed switches in each air motor are
shown with the arrow above each vertical bar graph.
312359J51
Page 52
Alarms
Alarm Codes and Troubleshooting
NOTE: See XM Plural-Component Sprayers Repair-Parts manuals for non-alarm based troubleshooting.
Alarm
CodeAlarm ProblemWhen ActiveCauseSolution
General Performance Alarms
R4BRatio High B (Overdose B),
system delivering too much B
component.
SprayB Dosing valve not closing.Perform Pump Test to test for
leakage. See Pump and Meter-ing Test, page 40.
Loosen valve packing nut. See
manual 313289.
Check air signal at valve top
Repair valve or air solenoid.
See manual 313289.
No B restriction at mix manifold. Increase B Restriction by turn-
ing B restrictor stem clockwise.
See Adjust B Machine Outlet Restriction, page 33.
Pump filter plugged on A side.Clean filter. See manual
311762.
Use alternate 30 mesh screen.
See manual 311762 for part
number.
Inlet air dropping below 80 psi
(0.55 MPa, 5.5 bar) while spraying. B dosing valve not closing
correctly.
Check air filters. See manual
313289.
Use larger air hose.
Use larger compressor.
Use smaller gun tips or less
guns to reduce flow rate.
Solenoid air regulator set below
80 psi (0.55 MPa, 5.5 bar)
R1BRatio Low B (under dose B);
system delivering not enough
B component.
RECSystem detected five R4B
(ratio high B) or five R1B
(ratio low B) alarms within five
minutes. Sprayer shuts down
for five minutes to resolve
problem.
FHA
FHB
52312359J
System detects pump movement (fluid flow) when there
should not be.
SprayB dosing valve will not open.Check for air signal to valve.
B mix manifold valve closed.Open green mix manifold valve.
Pump filter plugged on B side.Use alternate 30 mesh screen.
SpraySee R4B or R1B alarm causes. See R4B or R1B alarm solu-
SprayRecirculation valve or dosing
valve open or leaking for more
than five seconds.
Adjust air regulator.
See manual 311762 for part
number.
Clean B pump outlet filter. See
manual 311762.
tions. Flush mixed material if
necessary, and purge off-ratio
mixed material in hose.
Close or repair recirculation
valve, and run Pump Test. See
Pump and Metering Test,
page 40. See manual 313289 if
needed.
Page 53
Alarm
CodeAlarm ProblemWhen ActiveCauseSolution
R2DDosing sizes are not opti-
mized.
P4A
P4B
DAA
DAB
DDA
DDB
P1A
P1B
P4RPressure high.RecirculationPressure is above maximum
P5RPressure high.RecirculationPressure is above maximum
P9AA pump pressure is abnor-
P9BB pump pressure is abnor-
Pressure high.AlwaysFluid pressure is above maxi-
Pump runaway, above 80
cpm for 10 sec.
Pump cavitation; dives more
than 1/2 of stroke.
Pressure low.Spray, Pump
mally low compared to B
pump pressure.
mally low compared to A
pump pressure.
SprayDosing valve is operating near
high or low timing limits.
mum.
AlwaysNo material in pump or lines; no
fluid restriction.
SprayNo fluid or valve closed.Refill supply and open inlet
Material is too cold or thick.Increase material temperature
Pump inlet check valve not
closing.
Feed pump not providing material.
Inlet strainer plugged (if used).Check and clean strainer. See
Fluid pressure is below 1000
Test, Leak Test
SprayA air motor is icing up causing
SprayB air motor is icing up causing
psi (7 MPa, 70 bar).
advisory limit of 3000 psi (21
MPa, 210 bar) on A side.
warning limit of 5200 psi (35.9
MPa, 359 bar) on A side.
restriction and lower fluid pressure.
A pump is binding.Repair lower. See manual
A motor is hanging up.Repair air motor. See manual
restriction and lower fluid pressure.
B pump is binding.Repair lower. See manual
Adjust mix manifold B restrictor
stem clockwise or counter
clockwise as indicated by bar
graph on restrictor screen. See
Adjust B Machine Outlet
Restriction, page 33.
Decrease main air regulator.
Refill material in tank or hoses;
install fluid tip.
valve.
to reduce viscosity. See Heat Fluid, page 31. Shear material
with agitation to reduce viscosity.
Clear debris from check valve.
Or replace ball, seat, and seal.
Check feed pump (if used).
manual 313289.
Increase main air regulator.
Decrease pump air regulator
pressure.
Decrease pump air regulator
pressure.
Open the air motor de-ice bleed
air controls. Allow ice to melt.
Dry compressed air. Heat compressed air.
Use a smaller tip.
313289.
313289.
Open the air motor de-ice bleed
air controls. Allow ice to melt.
Dry compressed air. Heat compressed air.
Use a smaller tip.
313289.
Alarms
312359J53
Page 54
Alarms
Alarm
CodeAlarm ProblemWhen ActiveCauseSolution
B3ADosing size A advisorySprayThe fluid dosing size is greater
than 35 cc when fast dosing is
turned off.
The fluid dosing size is greater
than 20 cc when fast dosing is
turned on.
B4ADosing size A alarmSprayThe fluid dosing size is greater
than 45 cc when fast dosing is
turned off.
The fluid dosing size is greater
than 30 cc when fast dosing is
turned on.
Adjust the B side fluid restriction. See Adjust B Machine Outlet Restriction, page 33.
Decrease the air motor velocity
with a smaller tip.
Adjust the B side fluid restriction. See Adjust B Machine Outlet Restriction, page 33.
Decrease the air motor velocity
with a smaller tip.
Pump Test (Daily Check Recommended)
DFA
DFB
DGA
DGB
DEA
DEB
Pump did not stall against
fluid pressure on up stroke
only.
Pump did not stall against
fluid pressure on down stroke
only.
Pump does not move in 10
minutes.
Pump TestPump piston check valve, pis-
ton packings, or dosing valve
are not holding fluid pressure.
Pump TestPump inlet check or dose valve
is fouled, or damaged.
Park or Pump
Te st
Recirculation valves were not
opened to allow flow.
Flush pump. See XM Setup and Troubleshooting Guide,
page 45. Recheck. Remove,
clean, and repair lower. See
manual 313289.
Remove inlet housing & clean
and inspect. See manual
313289.
Open recirculation valves.
General System Component Alarms
DJA
DJB
DKA
DKB
P6A
P6B
Pump motor linear sensor
has no signal.
Pump motor linear sensor is
out of range.
Pump motor reed switch failure; missing signals from one
or both switches.
Pressure sensor failure; no
signal.
AlwaysNo linear sensor signal from
motor.
Linear sensor plugged in while
power is on.
Bad connection inside fluid control module.
AlwaysLinear sensor is beyond range. Replace sensor or sensor mag-
Sprayer is not properly
grounded.
AlwaysBad motor cable connections,
or bad reed switch.
Reed switch cable is plugged in
while power is on.
Bad connection inside fluid control module.
AlwaysPressure sensor or cable is bad
on the side indicated.
Swap A and B sensors.
Replace sensor if problem follows sensor. See manual
313289.
Power sprayer off and back on.
Do not plug in linear sensor
while power is on.
Replace fluid control module.
See manual 313289.
net. See manual 313289.
See Grounding, page 11.
Swap A and B motor cables.
Replace cable if problem persists. Otherwise replace reed
sensor assembly. See manual
313289.
Power sprayer off and back on.
Do not plug in reed switch cable
while power is on.
Replace fluid control module.
See manual 313289.
Replace sensor and cable
assembly. See manual 313289.
Turbine not spinning with air on. Replace air turbine cartridge.
N6CDisplay has no signal.AlwaysNo display communication sig-
nal.
Machine powered down in
spray mode.
DLAA air motor reed switch signal
missing advisory.
DLBB air motor reed switch signal
missing advisory.
DMAA air motor linear sensor
jump advisory.
DMBB air motor linear sensor
jump advisory.
AlwaysReed switch does not see the
air motor magnet.
Reed switches are bad.Replace air motor reed switch.
Air motor is icing up.
AlwaysReed switch does not see the
air motor magnet.
Reed switches are bad.Replace air motor reed switch.
Air motor is icing up.
AlwaysSystem ran out of fluid.Add fluid to the system.
Linear sensor is bad.Replace linear sensor.
AlwaysSystem ran out of fluid.Add fluid to the system.
Linear sensor is bad.Replace linear sensor.
Change air filter in control filter
regulator. See manual 313289.
Check the pressure setting is
18 psi (0.13 MPa, 1.3 bar) on
turbine air regulator.
Check voltage on information
screen.
See manual 313289.
Check cable connections.
Replace display.
See manual 313289.
Press stop button before turning
off power.
Replace air motor reed switch
magnet.
Prevent air motor icing. See
advisory P9A and P9B.
Replace air motor reed switch
magnet.
Prevent air motor icing. See
advisory P9A and P9B.
Optional User-Settable Maintenance Warnings
*MAA
*MAB
*MEA
*MEB
*MG0Maintain air filter.Always, if enabled Air filter exceeds user-set limit.
*P5A
*P5B
Maintain pump.Always, if enabled Pump usage exceeds user-set
limit. Maintenance due.
Maintain dosing valve.Always, if enabled Dosing valve usage exceeds
user-set limit. Maintenance
due.
Maintenance due.
Pressure exceeded alarm
limits.
SprayPressure exceeded high or low
alarm limits for more than 15
seconds.
Service pump. See manual
313289.
Service dosing valve. See manual 313289.
Service main air filter and control filter regulator.See manual
313289.
Adjust pump pressure regulator,
change tips, or adjust target set
point.
Alarms
312359J55
Page 56
Alarms
Alarm
CodeAlarm ProblemWhen ActiveCauseSolution
Optional User-Settable Spray Limits
*T5A
T5B
*P2A
P2B
*T2A
T2B
*N4DPot life timer expired. Mixed
Temperature exceeded alarm
limits.
Pressure exceeded advisory
limits.
Temperature exceeded advisory limits.
fluid will cure in hoses, mixer,
and gun.
SprayFluid temperature exceeded
high or low alarm limits for more
than four minutes.
SprayPressure exceeded high or low
advisory limits for more than 15
seconds.
SprayFluid temperature exceeded
high or low limits for more than
four minutes.
SprayHave not sprayed enough vol-
ume to keep fresh mixed fluid in
the integration hose, mixer,
whip hose, and spray gun.
If fluid temperature is too low,
return to circulation mode to
increase fluid temperature.
Adjust heater set point if
needed. See Heat Fluid, page
31.
If fluid temperature is too high,
lower heater set point, and
return circulation mode to cool.
See Heat Fluid, page 31.
Adjust temperature target setpoint. See Heat Fluid, page 31.
Same as P5A or P5B above.
Same as T5A or T5B above.
Spray fluid, or flush. Resets
when you leave spray mode.
See Spray, page 32, or Flush Mixed Material, page 36.
56312359J
Page 57
Alarms
Possible Alarms by Mode
The following table outlines the alarms that you may receive while operating the system. The alarms are categorized
according to each mode.
ModeControl LogicAlarms
SprayDosing valves close for startup test; green light blinks.--
If fluid pressure is under 1000 psi (7 MPa, 70 bar), STOP.P1A
If pumps move (indicating internal leakage), STOP.FHA, FHB
If fluid pressure is more than 103% of allowed maximum, air motor shuts
off until fluid pressure drops.
If is pressure more than 110% of allowed maximum, STOP.P4B
Dosing valve A opens, and dosing valve B cycles to maintain ratio.--
A and B blue lights illuminate when dosing valves are operating.--
If there is not enough B component to hold ratio, dosing valve A closes
momentarily.
If A or B component is more than 5% off ratio setpoint, STOP.R1B, R4B
If A dose size is too large, STOP.B4A
A and B dosing valves close momentarily at each pump changeover.--
ParkBoth dosing valves open; A and B blue lights turn on.--
User opens circulation valves or sprays gun. When pump reaches bottom stroke the blue light turns off.
If park does not complete in 10 minutes, turn off air to both motors.DEA, DEB
CirculationA and/or B dosing valves close and motor air turns on.--
If fluid pressure exceeds 3000 psi (21.0 MPa, 210 bar) on the A pump,
receive yellow light advisory.
If fluid pressure exceeds 5600 psi (39.2 MPa, 392 bar) on the A pump,
STOP.
If no movement in 10 minutes, turn off air to both motors.DEA, DEB
Pump TestBoth dosing valves close; green light blinks.--
If fluid pressure is under 1000 psi (7.0 MPa, 70 bar), STOP.P1A, P1B
If pumps move (indicating leakage) STOP.FHA, FHB
Turn on A blue light, open A dosing valve, user opens sampling valve.--
Close A dosing valve on upstroke; check for no movement.DFA
Close A dose valve on down stroke; check for no movement.DGA
Open A dose valve and dispense total of 750 ml material, close valve,
turn off blue light.
Repeat for B side.DFB, DGB, DHB
If both pumps pass pump test, display shows two beakers of 750ml each.--
Batch Dispense TestUser selects total volume desired.--
Open A dosing valve, turn on blue light, user opens sampling valve, turn
off blue light when complete.
Open B dosing valve, turn on blue light, user opens sampling valve, turn
off blue light when complete.
Display shows volume of A and B components at end of batch dispense
test.
Valve TestIf fluid pressure is not 1000 psi (7 MPa, 70 bar), STOP.P1A
Check for no movement of pumps (stall within 10 seconds).FHA, FHB
None
R2D
--
P4A
P4A
--
--
--
--
312359J57
Page 58
Alarms
Alarm Code Key
Use the following table as a quick guide to determine alarm codes.
WhatAlertWhere
BDose1LowAMaterial A
FFlow2DeviationBMaterial B
NTime3Deviation HighCController
PPressure4HighDDosing/Pot life
RRatio5Limit warningMPower or Air supply
TTemperature6Sensor or connection failureRRecirculation
VVoltage9Unbalanced
DPumpAPump runaway
DPump diving/cavitation
EPump time-out
FPump failed to stall up
GPump failed to stall down
HPump failed to stall
JLinear sensor failure
KDirectional switch failure
MLinear sensor jump
MMaintenance dueAPump
EDosing valve
GFilter
LED Diagnostic Information
The following LED signals, diagnosis, and solutions are the same for the display module, fluid control module, and
USB module. LEDs are located next to the module power cable.
Module Status LED SignalDiagnosisSolution
Green onSystem is powered up and power
supply voltage is greater than 11
Vdc.
YellowInternal communication in progress-
Red solidHardware failureReplace display module, fluid control
Red flashing fastUploading software-
Red flashing slowToken errorRemove token and upload software
-
module, or USB module.
token again.
58312359J
Page 59
Accessories and Kits
Not all accessories and kits are approved for use in
hazardous locations. Refer to the specific accessory
and kit manuals for approval details.
Accessories and Kits
20-Gallon Hopper Kit, 255963
One complete double-wall 20-gallon hopper. See manual 312747 for more information.
Hopper Heater Kit (240V), 256257
For heating fluid in a 20-gallon hopper. See manual
312747 for more information.
Universal Hopper Fluid Inlet Kit, 256170
For connecting any of the four lower models included
with XM sprayer to a 20-gallon hopper. See manual
312747 for more information.
Universal Hopper Mounting Kit, 256259
For mounting a 20-gallon hopper to the side or back of
an XM sprayer. See manual 312747 for more information.
5:1 Feed Pump Kit, 256276
For supplying viscous materials from a 20-gallon hopper
to an XM sprayer. See manual 312769 for more information.
7-Gallon Hopper and Bracket Kit,
256260 (Green)
24N011 (Blue)
One 7-gallon hopper and mounting brackets. Mounts to
the side or back of an XM sprayer. See manual 406699
for more information.
2:1 Drum Feed Kit, 256232
One T2 pump feed kit and one Twistork agitator kit for
mixing and supplying viscous materials from a with
55-gallon drum to an XM sprayer. See manual 312769
for more information.
5:1 Drum Feed Kit, 256255
One 5:1 pump feed kit and one Twistork agitator kit for
Twistork® Agitator Kit, 256274
For mixing viscous materials held within a 20-gallon
hopper. See manual 312769 for more information.
mixing and supplying viscous materials from a with
55-gallon drum to an XM sprayer. See manual 312769
for more information.
Hopper/Hose Heat Circulation Kit, 256273
T2 Feed Pump Kit, 256275
For supplying viscous material from a 20-gallon hopper
to an XM sprayer. See manual 312769 for more information.
312359J59
For circulating heated water through 20-gallon hoppers,
heated hose, and Viscon HP heater. See manual
313259 for more information.
Page 60
Accessories and Kits
Desiccant Dryer Kit, 256512
For use with 20-gallon hoppers. See manual 406739 for
more information.
Caster Kit, 256262
For mounting casters on XM sprayer frame. See manual
406690 for more information.
Hose Rack Kit, 256263
For mounting to side, front, or back of XM sprayer frame.
See manual 406691 for more information.
Lower Strainer and Valve Kit, 256653
For straining material from a feed pump to an XM
sprayer fluid inlet. See manual 312770 for more information.
10:1 Drum Feed Kit, 256433
For supplying highly viscous material from a 55-gallon
drum to an XM sprayer. See manual 312769 for more
information.
Shutoff/Check Valve Kit, 255278
For replacing shutoff valve or check valve. See manual
313343 for more information.
Alternator Conversion Kit, 256991
For converting an XM sprayer from wall power supply to
intrinsically safe alternator power supply. See manual
313293 for more information.
Mix Manifold Kit, 255684
See manual 312749 for more information.
Electric Heated Hose Power Supply Kit,
256876
For monitoring and controlling fluid temperature in
low-voltage heated hoses. See manual 313258 for more
information.
5000 psi Two-Component Main Heated
Hose Set Kit
Electric heated hose set for adding additional sections.
PartDescription
248907Heated hose set; 1/4 in. ID x 3/8 in. ID;
50 ft.
248908Heated hose set; 3/8 in. ID x 3/8 in. ID;
50 ft.
Xtreme Pump Wetcup Wrench, 15T258
Xtreme Pump Filter Wrench, 16G819
Remote Mix Manifold and Carriage Kit,
256980
For converting to a remote mix manifold kit with a protective guard. See manual 312749 for more information.
Restrictor Valve Kit, 24F284
For B dosing outlet on remote mix manifold machines.
Use to convert early XM machines without the valve on
the B outlet.
Restrictor Valve Wrench, 126786
For adjusting restrictor valve. See page 33.
60312359J
Page 61
Appendix A
Appendix A
User Interface Display
The user interface display is divided into three main
functions: Setup, Command, and Automatic.
Setup Functions (key “ON”)
The setup functions enable users to:
•set desired mix ratio;
•configure system settings;
•set potlife parameters;
•enable/disable functions, displays, and display
components;
•set which USB logs to download;
•schedule maintenance parameters for alarms
and advisories;
•and set pressure and temperature limits.
NOTE:
All setup functions, except for mix ratio, must be enabled
from the Enable Setup screens before users can change
or set configurations. See Enable Setup Screens, page
66, for instructions.
Command Functions (key “OFF” or removed)
The command functions enable users to:
•run pumps, including flush, circulate, and prime
procedures;
•park pumps so pump rods are down when not in
use;
•mix and spray;
•view mix ratio;
•run pump tests;
•run batch dispense ratio tests;
•run valve leak checks;
•view dispense totals;
•view alarms;
•diagnose alarms;
•and clear alarms.
Automatic Display Functions
The automatic display functions enable users to:
•issue potlife timer alarms
•and download USB logs.
312359J61
Page 62
Appendix A
Setup Mode Screens
Setup mode screens are divided into five major sections: home, limits, maintenance, enable, and system. The following figure demonstrates the flow of the Setup mode screens beginning with the Home screen.
Home
Maintenance Setup
Version Control
Pressure Limits
Limits Setup
Maintenance Setup 1
Temperature Limits
Maintenance Setup 2
(shown with factory default settings)
Enable Setup 1
Enable Setup
Potlife/Hose Length
System Setup
62312359J
Enable Setup 2
Date/Time/Units
System/USB/Pump Config.
Page 63
Appendix A
Home Setup Screens
Home
Home is the first screen that displays in Setup mode. It
shows the current pump ratio, and enables users to
change the mix ratio and access the following screens:
system setup, enable/disable functions, maintenance
setup, and limits. Refer to the following table for more
details.
IconFunction
Increase or decrease mix ratio. Press
and to change the mix ratio.
Press to jump to system setup screens.
Press to jump to functional enable/disable
setup screens.
Press to jump to maintenance setup
screens.
Press to jump to pressure and temperature
limits setup screens.
Version Control
This screen displays the versions and/or status of the
system components. Refer to the following table for
details. To access this screen, press from the
Home Setup screen.
IconFunction
Display module version (Vs)
Fluid control module version (Vs)
USB version (Vs)
USB Configuration (Vc)
A
B
A+B
Total amount dispensed by pump A
Total amount dispensed by pump B
Total amount dispensed by pumps A and B
Number of hours system has been running
.
312359J63
Page 64
Appendix A
System Setup Screens
System Setup enables users to configure system settings for fluid control and operator interaction. Refer to
the following table for details.
NOTE:
System settings must be enabled from the Enable Setup
screens before users can change or set configurations.
See Enable Setup Screens, page 66, for instructions.
IconFunction
Set number of minutes before mixed material will set in hose. Resets after material
volume set by user is passed through hose.
Indicates total hose volume. Always displayed in cc units.
Set length of hose after mix manifold. Used
to indicated total hose volume.
Set calendar date and format.
Set time.
Set Potlife/Hose Length
To set the potlife timer and enter the mixed material
hose dimensions, press and to move through
each field, and press to make a field selectable.
Press and to select preferred units of measurement for the potlife timer and length of each mixed
material hose. Press and to move to the
next digit in each field. Once the measurement unit in
the field is correct, press to save that measurement.
When the fluid flow stops the displayed time counts
down in one minute intervals. The timer automatically
resets when the calculated mixed fluid volume is dispensed.
Set units of measurement desired for display, such as fluid and temperature.
Set sprayer number if using more than one
sprayer.
Set number of hours of recorded data to
record to USB data logs.
Set how often data will record to USB spray
logs.
Select resin pump size for A side.
Select hardener pump size for B side.
Potlife/Hose Length
This screen enables users to set the potlife timer and
enter the hose inside diameter and length of each mixed
material hose specific to the system. The potlife time
displays in the upper right corner.
Date/Time/Units
This screen enables users to set day, time, and units
that will be displayed on each screen.
64312359J
Page 65
Appendix A
System Number and USB Settings
This screen enables users to set the sprayer number if
using more than one sprayer. It also enables users to
configure the number of hours downloaded to external
USB flash drive and how often the data will record. See
Set System Settings (Optional), page 24, for instructions.
Pump Configuration
Users can change the pump size that is specific to the
system if the pump box is selected on Enable Setup 1,
page 66.
NOTICE
Changing the pump size settings may cause the system
to spray off ratio.
Set Pump Sizes
To change the pump size, press and to select
the field. Press to open the drop down field.
Press and to select the preferred pump size.
Press again to save the change.
312359J65
Page 66
Appendix A
Enable Setup Screens
Enable Setup allows users to enable and disable functionalities, screens, and USB download log files.
Checked boxes indicate the function, screen, or log file
is active. Refer to the following table for details.
To enable and disable functionalities, screen, and USB
log files, press from the Home Setup screen.
Once in the Enable Setup screen, press and
to scroll through each subscreen. Press
and to scroll through each field within the sub-
screens, and press to enable or disable each.
Press to return to the Home Setup screen
IconFunction
USB data download function. Disable this
function to prevent operators from changing USB settings.
NOTE: Even if this function is disabled,
selected USB logs will still be downloaded.
Enable or disable totalizer screens.
IconFunction
Enable or disable dosing valve maintenance setup screen.
Enable or disable incoming air filter maintenance setup screen.
Enable or disable limits (pressure and temperature) screens.
Fast dosing function. Enable function to
minimize B side dose size and increase
dosing rate. See table below.
Use this function with short integration
hose. The system will attempt to hold the
dosing sizes below the advisory level.
Display time on all screens.
Enable or disable USB log files (1-3) to
download.
Fast Dosing Function
Fast DosingAdvisory B3AAlarm B4A
on20 cc30 cc
off35 cc45 cc
Enable or disable batch totalizer clear function.
Display potlife timer on all screens.
Enable or disable potlife timer setup
screen.
Display flow rates on run screens
Display A and B pressures on run screens.
Display A and B temperatures on run
screens.
Enable or disable ability to change pump
size in system setup screens.
Enable or disable ratio screen. If enabled,
ratio screen will automatically display after
sprayer runs for 10 seconds.
Enable or disable pump maintenance setup
screens.
Enable Setup 1
(Shown with factory default settings.)
66312359J
Page 67
Appendix A
Enable Setup 2
(Shown with factory default settings.)
Maintenance Setup Screens
The maintenance setup 1 screen enables users to set
maintenance setpoint amounts for pumps and dosing
valves. The maintenance setup 2 screen enables users
to schedule the number of days between changing the
main incoming air filter before a reminder advisory will
sound.
The number displayed below each selectable field indicates the amount of material dispensed, counting up to
the setpoint requiring maintenance.
IconFunction
Set amount of material moved through
pump that will result in a maintenance
warning.
Set amount of material moved through dosing valve that will result in a maintenance
warning.
Set number of days between changing the
main incoming air filter before a reminder
advisory is issued.
Maintenance Setup 1
Maintenance Setup 2
312359J67
Page 68
Appendix A
User Limits Setup Screens
User Limits Setup enables users to set and adjust pressure and temperature limits for both pumps, including
limits that will issue advisories and alarms. Refer to the
following table for details.
NOTE:
The allowable range for the temperature setpoint is 34° 160°F (1° - 71°C). If the temperature or pressure setpoint is zero, pressure limits and alarms are disabled.
IconFunction
Set and adjust pressure limits for both
pumps.
Set and adjust high and low temperature
limits for both pumps.
Set target pressure or temperature.
Set and adjust limits that if exceeded will
issue an advisory. Used with pressure and
temperature limits.
Set and adjust limits that if exceeded will
issue a alarm. Used with pressure and
temperature limits.
Process Pressure Limits (for spray mode)
Process Temperature Limits (for spray mode)
68312359J
Page 69
Appendix A
Operator Command Functions Screens
Command mode screens are divided into three major sections: run (fluid control), test, and alarm control. The following figure demonstrates the flow of the Command mode screens beginning with the run (fluid control) screens.
Maintenance 2
Alarm Information
Alarm Control Screens
Pump Test
Test Screens
Alarm Log
Batch Test
Totali zer
Maintenance 1
Valve Test
Restrictor Screen
Pump Mode
Spray Mode
Park Mode
Ratio Screen
Run (Fluid Control) Screens
312359J69
Page 70
Appendix A
Run (Fluid Control) Screens
Run (fluid control) is the first screen displayed at power
on. It enables users to spray material, and operate and
park pumps. Run consists of two screens: power
on/enter and ratio mode.
The power on/enter screen cycles through power on
mode, spray mode, and pump mode. It always displays
the current ratio setpoint, and may also display: pressure, temperature and flow rate if these functions are
selected.
The ratio screen displays the current ratio and monitors
the B side restriction adjustment.
IconFunction
Spray: proportion and spray material.
Run pumps: operate both pumps or oper-
ate each pump independent from the other
(priming, flushing).
Park Pumps: runs pump to bottom of the
stroke.
Ratio: jump to ratio screen.
Spray Mode
Users must be in this mode to spray or proportion material. Press the button below the spray icon to enter this
mode.
Pump Mode
Users must be in this mode to operate pumps for priming or flushing. Press the button below the pump icon to
enter this mode. Continue pressing the pump icon button to cycle through pump A, pump B, and both pumps.
Power On/Enter Mode
Power On/Enter Mode is the default screen when users
enter Fluid Control.
NOTE:
This screen remains blank until a mode is selected.
70312359J
Page 71
Appendix A
Park Mode
Users must be in this mode to park fluid rod pumps at
the bottom of the stroke. Press the button below the
park icon to enter this mode.
Ratio Mode
Displays the current ratio or the restrictor screen. To
access this screen, press The bar graph indi-
cates whether the B restriction adjustment should be
turned clockwise or counter clockwise. See Adjust B
Machine Outlet Restriction, page 33.
Test Screens
Test screens enable users to run batch dispense tests,
pump tests, and down stream valve leak tests.
IconFunction
Pump Test: dispenses 750cc of each A and
B; verifies pump selection, operation, and
metering.
Batch Dispense: dispenses proportioned
amounts of A and B with a selectable total.
Down Stream Valve Leak Test: test if valves
after the dosing valves hold pressure.
Pump Test
This screen enables users to dispense a fixed 750 ml
volume of material from each pump. When the pump is
active it flashes in black on the screen. When the pump
completes dispensing it displays gray on the screen.
NOTE: If the field is enabled on the Enable
Setup screen, the Spray Mode screen will be replaced
by the bar graph screen after 10 seconds of spray time.
Press to return to the Spray Mode screen.
Restrictor Screen
IconFunction
Display Ratio: show the accuracy of the
fluid mix ratio.
Display Restrictor Adjust: Adjust the restrictor to optimize the mix ratio.
•At the maximum fluid flow, the bar
should be in the center.
•At less than maximum flow, the bar
should be on the right side.
Confirm Pump Test
This screen displays when the pump test completes
without error. This screen displays the target volume of
material dispensed into each beaker from each pump.
312359J71
Page 72
Appendix A
Batch Dispense Test
This screen enables users to dispense a selected total
volume of material on ratio. For example, 1000 ml at 4:1
= 800 ml of A + 200 ml of B. The total batch volume can
be selected from the drop down menu.
When the pump is active it flashes in black on the
screen. When the pump completes dispensing it displays in gray on the screen
Confirm Batch Dispense Test
This screen displays when the batch dispense test completes without error. This screen displays the selected
ratio between the pumps and the volume of material dispensed from each pump. The gray at the bottom of the
beaker represents the volume of material dispensed by
pump A. The black at the top of the beaker represents
the volume of material dispensed by pump B.
Down Stream Valve Leak Test
This screen enables users to test for closed or worn
valves down stream of the A and B dosing control
valves. It can be used to test the mix manifold shutoff/check valves or any remote circulation valves.
While running the test, if there is continuous pump
movement on the A or B side, an error will be issued.
The error indicates a leak in the valve.
There is no confirmation screen for this test. However, if
the down stream valve leak test fails, an warning is
issued to indicate the cause of the failure.
72312359J
Page 73
Appendix A
Alarm Control Screens
The Alarm control screens enable users to view alarm
diagnostic information, alarm logs, and pump batch and
grand totals. These screens also enable users to view
maintenance information for pump and check valves,
including the maintenance schedule.
NOTE:
If the potlife timer is enabled, displays.
Alarm
The Alarm screen displays the specific alarm code.
There are two levels of error codes: alarms and advisories. A solid bell icon with an exclamation point and
three audible alerts indicate a alarm. And an outlined
hollow bell icon and a single audible alert indicate an
advisory.
Additionally, this screen displays the location of the error
with the top view and side view of the system. Refer to
the following table and subsections for more details.
IconFunction
Go to maintenance screen. Allows user to
view maintenance information but not make
changes.See Maintenance Setup 2, page
67.
Flush confirm. Use when the potlife timer is
enabled. Press button to confirm flush
before a potlife advisory is issued.
Amount of material moved through pump
that will result in a maintenance warning.
Amount of material moved through dosing
valve that will result in a maintenance warning.
Number of days between maintenance
cycles that will result in a reminder advisory.
Clear batch totalizers or maintenance
counters.
Alarm Log
View details regarding alarms received, including the
date, time, and alarm code for the last 16 alarms. Up to
four pages of alarms are available.
IconFunction
Go to Alarm log. Use up and down arrows
to scroll through list of the past 16 errors.
Go to totalizer screen. Allows users to view
the grand and batch totals for each pump
and both pumps combined.
Press to access the alarm log. The press
and to scroll through each page of alarms.
312359J73
Page 74
Appendix A
Totalizers and Job Number
View the grand and batch totals for each pump and both
pumps combined. The units of measurement are displayed on the bottom of the screen and displayed in the
units of measurement selected during setup.
Grand total is the amount of material the system has
dispensed during its lifetime. Batch total is the amount of
material dispensed since the last user reset.
A job number can be entered to identify the batch total.
Clear Batch Totalizer
To clear the batch totalizer values for A, B, and A+B,
press to set all values to zero.
Maintenance 1 Screen
View setpoints for the amount of material that needs to
move through both pumps and dosing valves that will
result in a maintenance warning.
Maintenance 2 Screen
View number of days between changing the main
incoming air filter before a reminder advisory is issued.
IconFunction
Displays batch total and grand total for
pump A. The grand total is displayed at
the top, and the batch total is displayed at
the bottom.
Displays batch total and grand total for
pump B. The grand total is displayed at
the top, and the batch total is displayed at
the bottom.
Displays batch total and grand total for
both pumps combined. The grand total is
displayed at the top, and the batch total is
displayed at the bottom.
Displays job number for each spray
period.
Change Job Number
1. Press to highlight the first digit. Press
and to change the number and and
to move to the next digit. Press to
Reset Maintenance Counter
1. Press and to scroll through and select the
maintenance field to reset.
2. Press to reset the maintenance counter to
zero.
save the number or to cancel.
74312359J
Page 75
Appendix A
Auto Display Screens
Potlife Screen
The potlife screen automatically displays when a potlife
advisory occurs. The screen automatically closes when
the advisory end or the user presses the flush confirm
button. Refer to the following table for more details.
IconFunction
Advisory has been issued.
Potlife timer is enabled.
Time after potlife expires. Starts at 0.00
and counts down in negative one minute
intervals.
Press to mute advisory buzzer.
Press to confirm that mixed hose has been
flushed. Resets potlife timer.
IconFunction
Flashes while data download is in process.
Check mark appears after download completes. Indicates download was successful.
If download was not successful,
appears.
Displays total memory to download and
remaining memory left to download.
Displays time remaining for log download to
complete.
Press to cancel download. If download is
cancelled, remove USB flash drive.
Indicates which log(s) is being downloaded.
Recommended USB Flash Drives
It is recommended that users use the USB flash drive
(16A004) included with the XM sprayer for data download. However, the following USB flash drives can also
be used, but are not available through Graco.
USB Screen
The USB screen automatically displays and the selected
log(s) automatically starts downloading when the USB
flash drive is inserted into the control box.
NOTE:
Inserting the USB flash drive while the sprayer is running automatically stops sprayer operation. Removing
the USB flash drive automatically closes the USB
screen.
The log selected for current download is displayed in the
single box next to the USB icon. The other available logs
are displayed in the boxes on the right side of the
screen. Refer to the following table for more details.
312359J75
•Crucial Gizmo!
JDO4GB-730) or 8GB USB flash drive (model
7DOD8GB-730)
•Transcend JetFlash
(model TS4GJFV30)
•Transcend JetFlash
(model TS4GJF300)
•Corsair Flash Voyager
(model CMFUSB2.0-8GB)
™
4GB USB flash drive (model
®
V30 4GB USB flash drive
®
300 4GB USB flash drive
®
8GB USB flash drive
Page 76
Appendix A
FIG. 8: Example Spray Log
76312359J
Page 77
Appendix B
N
A
N
g
S
H
A
R
H
A
R
U
H
N
pray
Metering Diagrams
Metering Diagram without Remote Mix Manifold
XM Metering Diagram
Appendix B
Recirculation
Back P ssure re
Control
Linea r
H
O
P
P
E
R
Gravity Feed
Or
Pump Feed
XT
6500
Air
Motor
Circulation
Shut/Check
250 HF or
180 HP
Reed
witches
E
T
E
Control
Valves
Re
Double
Motor Pilots
Controls
F
L
S
psi
Air
psi
6500
Air
Motor
E
T
E
XT
220 HF or
145 HP
B
H
O
P
P
E
R
rtd
Integration
Hose
3/8 x 25 ft
minimum
Mix Manifold
Shut-off &
Check Valves
Settable ‘B’
Balancing
Restriction
after the integration hose and mixer
ote: Additional guns may only be added
Mixers
Whip Hose
Spray Gun 3
S
Gun
Spray Gun 2
Fluid Line
Control cable
Air Signal
Sample
& Test
Valves
rtd
Mix
Manifold
312359J77
Page 78
Appendix B
N
A
N
B
S
H
A
R
H
A
R
j
N
g
Metering Diagram with Remote Mix Manifold
XM Metering Diagram with
Remote Mix Manifold
Linea r
Motor Pilot
XT
6500
Air
Motor
Reed
witches
Air
Re
Double
XT
6500
Air
Motor
Recirculation
Back Pr ssure e
Control
H
O
P
P
E
R
Gravit y Feed
Circulation On / Off
250 HF or
180 HP
E
T
E
Sample
& Test
Valves
Control
Valves
Remote
Shut-off &
Check Valves
Controls
psi
Shut-off &
Hose Isolation
Check Valves
F
L
U
S
H
psi
220 HF or
145 HP
H
O
P
E
P
E
T
R
E
These hose isolation check valves must
be added when mix manifold is remote.
This insures that pressure transducers
read pump output and cavitation, and
ust dampened hose pressure.
not
ote: Additional guns may only be added
Mix Manifiold
Settable ‘B’
Balancing
Restriction
after the integration hose and mixer
Spray Gun 3
Fluid Line
Control cable
Air Signal
78312359J
Integration Hose
3/8 x 25 ft minimum
Mixers
Spray Gun 2
Spray Gun
Page 79
Appendix C
Power Cord Guidelines
Use the guidelines listed in the following table to determine the power cord needed for your specific system.
1 A, 120 Vac1 A, 120/240 Vac1 A, 240 Vac1 A, 240 VacN/AN/AN/A
N/AN/A32 A at
N/A13 A at 240 V,
N/A
N/AN/AN/AN/A
N/A
XM_A (14-19,
24-29)XM_B (all)XM_C (all)
240 Vac,
1 PH
1 PH
16 A at 240 V,
1 PH◆
or
15 A at 240 V,
1 PH◆
1 A30 A62 A62 A0 A
2
) at:
◆
13 A at 240 V,
1 PH
16 A at 240 V,
1 PH
or
15 A at 240 V,
1 PH
4 (21.2)
2 wire + ground
6 (13.3)
3 wire + ground
6 (13.3)
4 wire + ground
32 A at
240 Vac,
1 PH
13 A at 240 V,
1 PH
16 A at 240 V,
1 PH ◆
or
15 A at 240 V,
1 PH ◆
◆
XM_D (00, 11, 13,
21, 23, 30-32)
N/AN/A32 A at 240 V,
N/AN/AN/A
N/A16 A at 240 V,
(air only)
N/AN/AN/A
XM_D (17, 19, 27,
29)XM_E (all)
1 PH (wired by
user with
explosion proof
methods)
16 A48 A
1 PH (wired by
user with
explosion proof
methods)
16 A at 240 V,
1 PH (wired by
user with
explosion proof
methods)
◆ Wired by user if ordered. Cord size determined by user.
❄ Full load amperes with all components operating at maximum capabilities. Fuse requirements for various flow
rates and heater temperature settings may be less.
312359J79
Page 80
Dimensions
Dimensions
System Dimensions without Hoppers
39.5 in.
(1003.3 mm)
70.0 in.
(1788.0 mm)
36.0 in.
(914.4 mm)
80312359J
38.0 in.
(965.2 mm)
ti21282a
Page 81
System Dimensions with Hoppers
Two 20-Gallon Hoppers
Side Mounted
Dimensions
72.5 in.
(1841.5 mm)
43.1 in.
(1094.7 mm)
98.6 in.
(2504.4 mm)
Two 20-Gallon Hoppers
Rear Mounted
(Top View)
54.0 in.
(1371.6 mm)
49.7 in.
(1262.4 mm)
62.8 in.
(1595.1 mm)
38.4 in.
(975.4 mm)
312359J81
56.2 in.
(1427.5 mm)
ti21283a
Page 82
Dimensions
System Dimensions with Hoppers
One 20-Gallon Hopper and One 7-Gallon Hopper
72.5 in.
(1841.5 mm)
43.1 in.
(1094.7 mm)
70.0 in.
(1788.0 mm)
33.4 in.
(848.4 mm)
Two 7-Gallon Hoppers
79.1 in.
(2009.1 mm)
70.0 in.
(1788.0 mm)
33.4 in.
(848.4 mm)
59.7 in.
(1516.4 mm)
82312359J
ti21284a
Page 83
Pump Performance Charts
Pump Performance Charts
Calculate Fluid Outlet Pressure
To calculate fluid outlet pressure (MPa/bar/psi) at a specific
fluid flow (lpm/gpm) and operating air pressure (MPa/bar/psi),
use the following instructions and pump data charts.
1.Locate desired flow along bottom of chart.
2.Follow vertical line up to intersection with selected fluid
outlet pressure curve. Follow left to scale to read fluid outlet pressure.
Calculate Pump Air Consumption
To calculate pump air consumption (m3/min or scfm) at a specific fluid flow (lpm/gpm) and air pressure (MPa/bar/psi), use
the following instructions and pump data charts.
1.Locate desired flow along bottom of chart.
2.Follow vertical line up to intersection with selected air consumption curve. Follow right to scale to read air consumption.
NOTE: Ratio setpoint has no significant effect on curves in either performance chart.
Air consumption includes turbine alternator; it does not include feed pumps or agitators.
XM50 Fluid Performance and Air Consumption
7000
(49.0, 490)
5000
(35.0, 350)
3000
(21.0, 210)
1000
(7.0, 70)
Fluid Pressure in psi (MPa, bar)
0.0
KEY:
A = 100 psi (0.7 MPa, 7 bar)
B = 70 psi (0.48 MPa, 4.8 bar)
A
B
1.0
2.0
(3.8)(7.6)
Fluid Flow in gpm (lpm)
A
B
3.0
(11.4)
180
(5.0)
140
(3.9)
100
(2.8)
60
(1.7)
20
(0.6)
Air Consumption in SCFM (m
3
/min)
XM70 Fluid Performance and Air Consumption
7000
(49.0, 490)
5000
(35.0, 350)
3000
(21.0, 210)
A
A
B
B
180
(5.0)
140
(3.9)
100
(2.8)
60
(1.7)
1000
(7.0, 70)
Fluid Pressure in psi (MPa, bar)
KEY:
0.0
A = 90 psi (0.62 MPa, 6.2 bar)
B = 70 psi (0.48 MPa, 4.8 bar)
742 lbs (336.87 kg)
(Add component weights to base sprayer weight for your
specific model weight.)
* Minimum flow rate is dependent on material being sprayed and mixing capability. Test your material specific to flow rate.
84312359J
Page 85
Technical Data
312359J85
Page 86
Graco Standard Warranty
Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its name to be free from defects in
material and workmanship on the date of sale to the original purchaser for use. With the exception of any special, extended, or limited warranty
published by Graco, Graco will, for a period of twelve months from the date of sale, repair or replace any part of the equipment determined by
Graco to be defective. This warranty applies only when the equipment is installed, operated and maintained in accordance with Graco’s written
recommendations.
This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction, damage or wear caused by faulty
installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of
non-Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment with
structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture, installation, operation or
maintenance of structures, accessories, equipment or materials not supplied by Graco.
This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributor for verification of
the claimed defect. If the claimed defect is verified, Graco will repair or replace free of charge any defective parts. The equipment will be returned
to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material or workmanship, repairs will
be made at a reasonable charge, which charges may include the costs of parts, labor, and transportation.
THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED
TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
Graco’s sole obligation and buyer’s sole remedy for any breach of warranty shall be as set forth above. The buyer agrees that no other remedy
(including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or
consequential loss) shall be available. Any action for breach of warranty must be brought within two (2) years of the date of sale.
GRACO MAKES NO WARRANTY, AND DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, IN CONNECTION WITH ACCESSORIES, EQUIPMENT, MATERIALS OR COMPONENTS SOLD BUT NOT
MANUFACTURED BY GRACO. These items sold, but not manufactured by Graco (such as electric motors, switches, hose, etc.), are subject to
the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable assistance in making any claim for breach of these
warranties.
In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from Graco supplying equipment hereunder, or
the furnishing, performance, or use of any products or other goods sold hereto, whether due to a breach of contract, breach of warranty, the
negligence of Graco, or otherwise.
FOR GRACO CANADA CUSTOMERS
The Parties acknowledge that they have required that the present document, as well as all documents, notices and legal proceedings entered into,
given or instituted pursuant hereto or relating directly or indirectly hereto, be drawn up in English. Les parties reconnaissent avoir convenu que la
rédaction du présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciaires exécutés, donnés ou intentés, à la suite
de ou en rapport, directement ou indirectement, avec les procédures concernées.
Graco Information
For the latest information about Graco products, visit www.graco.com.
TO PLACE AN ORDER, contact your Graco distributor or call to identify the nearest distributor.
Phone: 612-623-6921 or Toll Free: 1-800-328-0211 Fax: 612-378-3505
All written and visual data contained in this document reflects the latest product information available at the time of publication.
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA
Copyright 2009, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
Graco reserves the right to make changes at any time without notice.
For patent information, see www.graco.com/patents.
Original instructions. This manual contains English. MM 312359
Graco Headquarters: Minneapolis
International Offices: Belgium, China, Japan, Korea
www.graco.com
Revised March 2013
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.