Graco XM 24W626, XM 262869, XM 262945, XM 262943 Operation Manual

Setup - Operation
WLD
XM
PFP
3A2776H
Plural-Component Sprayer
For spraying two-component passive fire protection (PFP) intumescent epoxies. For professional use only.
Importan t Safety Instru ct io n s
Read all warnings and instructions in this manual and in all related manuals. Save all instructions.
EN
Contents
Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Related Manuals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Keep Components A and B Separate . . . . . . . . . . . . .8
Changing Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Components A and B . . . . . . . . . . . . . . . . . . . . . . . . . .8
Component Identification . . . . . . . . . . . . . . . . . . . . . . . . .9
User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Unboxing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Ratio Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Configuration Options . . . . . . . . . . . . . . . . . . . . . . . . .17
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Connect Power Cord . . . . . . . . . . . . . . . . . . . . . . . . . .19
Set Power Jumpers . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Connect Air Supply . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Connect Feed Module Lines to Sprayer Module . . . . .21
Install Level Sensor Probes . . . . . . . . . . . . . . . . . . . .23
Level Sensor Calibration . . . . . . . . . . . . . . . . . . . . . . .23
Connect the Fluid Hose Bundle to the System . . . . . . 24
Connect the Fluid Hose
Bundle to the Mix Manifold . . . . . . . . . . . . . . . . .25
Connect the Mix Manifold to the Gun . . . . . . . . . . . . .26
Connect Tank Heat Circulation Hoses . . . . . . . . . . . .26
Prime Heated Hose Bundle
Fluid Circulation System . . . . . . . . . . . . . . . . . . .26
Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Prime Flush Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Adjust Ratio and System Settings . . . . . . . . . . . . . . . . .38
Verify Desired Ratio Mode . . . . . . . . . . . . . . . . . . . . .38
Adjust Ratio Set Point . . . . . . . . . . . . . . . . . . . . . . . . .38
Temperature Settings . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Spray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Flush Mixed Material . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Park Metering Pump Rods . . . . . . . . . . . . . . . . . . . . . . .45
Pressure Relief Procedure . . . . . . . . . . . . . . . . . . . . . . .46
System Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Pump and Metering Test and Calibration for
Ratio by Weight Mode . . . . . . . . . . . . . . . . . . . . .48
Batch Dispense or Ratio Test . . . . . . . . . . . . . . . . . . .50
Down Stream Valve Leak Test . . . . . . . . . . . . . . . . . .52
Mix and Integration Tests . . . . . . . . . . . . . . . . . . . . . .53
Empty and Flush Entire System . . . . . . . . . . . . . . . . . . .54
Prepare Level Sensor for Shipping . . . . . . . . . . . . . . . .58
Download Data from USB . . . . . . . . . . . . . . . . . . . . . . . .59
USB Logs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Download Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Download Procedure . . . . . . . . . . . . . . . . . . . . . . . . .59
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Adjust Packing Nuts . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Clean the System . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Appendix A - User Interface Display . . . . . . . . . . . . . . . 68
Change a Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Test Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Information Screens . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Appendix B - Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
Alarms Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Graco Standard Warranty . . . . . . . . . . . . . . . . . . . . . . . 100
Graco Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
2 3A2776H

Models

9902471
Certified to CAN/CSA C22.2 No. 88
Conforms to
UL 499
Not for use in explosive atmospheres or hazardous locations.
9902471
Certified to CAN/CSA C22.2 No. 88
Conforms to
UL 499
II 2 G Ex db ia pxb IIA T3 Gb
System Series Location
Models
Ratio
Range Approvals
24W626 B
262869 B
262945 A
262943 A
Non-Hazardous
Hazardous
1:1 to
1.5:1
1.5:1 to 4:1
1:1 to
1.5:1
1.5:1 to 4:1
ATEX Ratings: ATEX Certificate No. ITS15ATEX18241X
Maximum Fluid Working Pressure Maximum Air Working Pressure
A and B Materials:
6000 psi (41 MPa, 414 bar)
Flushing Fluid:
4500 psi (31 MPa, 310 bar)
3A2776H 3
Heating Fluid:
100 psi (0.7 MPa, 7 bar)
IECEx Ratings Ex db ia pxb IIA T3 Gb IECEx Certificate No. IECEx ETL 15.0020X Ta = 0°C to 54°C
See Technical Data, page 96, for additional information.
Supply:
150 psi (1.0 MPa, 10.3 bar)
Max. Setpoint:
100 psi (0.7 MPa, 7 bar)

Related Manuals

Related Manuals
Manuals are available at www.graco.com. Component manuals in English:
Manual Description
3A2989 XM PFP Repair 3A2988 XM PFP Mix Manifold Instructions - Parts 3A2799
Heaters
309524
3A2954
Pumps, Motors, Supply Systems
308652 311238
311762 312375
312376 312792
312794 Merkur Pump Assembly Instructions - Parts 312796 NXT Air Motor Instructions - Parts 313526 Supply Systems Operation 313527 Supply Systems Repair - Parts 312374 Air Control Instructions - Parts
Accessories
332073 Hot Water Flush Kit Instructions 3A2987 Air Dryer Kit Instructions 406691 Hose Rack Parts 334931 Caster Kit Instructions
Other
306861 Ball Valves Instructions - Parts 307005 High Pressure Swivel Instructions - Parts
308169 407061 Simulation XM PFP Display Module 3A1244
334939 1:1 Ratio Adapter Kit Instructions 3A3072 Heater Upgrade Kit Instructions
XHF
Spray Gun
®
Viscon Instructions - Parts
Viscon HF High Flow, High Pressure Fluid Heater Instructions - Parts
Husky Pumps Instructions - Parts
NXT Xtreme Check-Mate
Instructions - Parts Check-Mate Pump Packages Instructions -
Parts Merkur
Air Filters, Lubricators, and Kit s Instructions
- Parts
Graco Control Architecture Module Pro­gramming
HP High Pressure Fluid Heater
205 Air-Operated Diaphragm
®
Air Motor Instructions - Parts
®
Lowers Instructions - Parts
®
Displacement Pumps
®
Pump Repair - Parts
4 3A2776H

Warnings

WARNINGWARNINGWARNING
WARNING
Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclama­tion point symbol alerts you to a general warning and the hazard symbols refer to procedure-specific risks. When these symbols appear in the body of this manual or on warning labels, refer back to these Warnings. Product-specific hazard symbols and warnings not covered in this section may appear throughout the body of this manual where applicable.
SPECIAL CONDITIONS FOR SAFE USE
Potential risk of electrostatic discharge. See instructions for guidance to minimize the risk of electro­static discharge.
The system must be earthed using copper conductors according to the installation instructions. All intrinsically safe circuits must be connected to ground at one point.
For information on the required dimensions of the flameproof joints contact the holder of this certifi­cate (Graco Inc.); Flame-path joints are not intended to be repaired.
Special fasteners for securing equipments covers on the flameproof heaters shall have a minimum yield strength of 1,100 MPa and be corrosion resistant and sized M8 x 1.25 x 30.
FIRE AND EXPLOSION HAZARD
Flammable fumes, such as solvent and paint fumes, in work area can ignite or explode. Paint or solvent flowing through the equipment can cause static sparking. To help prevent fire and explosion:
Use equipment only in well ventilated area.
Eliminate all ignition sources; such as pilot lights, cigarettes, portable electric lamps, and plastic drop cloths (potential static sparking).
Ground all equipment in the work area. See Grounding instructions.
Never spray or flush solvent at high pressure.
Keep work area free of debris, including solvent, rags and gasoline.
Do not plug or unplug power cords, or turn power or light switches on or off when flammable fumes are present.
Use only gr ounded hoses.
Hold gun firmly to side of grounded pail when triggering into pail. Do not use pail liners unless they are anti-static or conductive.
Stop operation immediately if static sparking occurs or you feel a shock. Do not use equipment until you identify and correct the problem.
Keep a working fire extinguisher in the work area.
ELECTRIC SHOCK HAZARD
This equipment must be grounded. Improper grounding, setup, or usage of the system can cause electric shock.
Turn off and disconnect power at main switch before disconnecting any cables and before servicing or installing equipment.
Connect only to grounded power source.
All electrical wiring must be done by a qualified electrician and comply with all local codes and regulations.
3A2776H 5
Warnings
WARNINGWARNINGWARNING
WARNING
SKIN INJECTION HAZARD
High-pressure fluid from gun, hose leaks, or ruptured components will pierce skin. This may look like just a cut, but it is a serious injury that can result in amputation. Get immediate surgical treatment.
Do not spray without tip guard and trigger guard installed.
Engage trigger lock when not spraying.
Do not point gun at anyone or at any part of the body.
Do not put your hand over the spray tip.
Do not stop or deflect leaks with your hand, body, glove, or rag.
•Follow the Pressure Relief Procedure when you stop spraying and before cleaning, checking, or servicing equipment.
Tighten all fluid connections before operating the equipment.
Check hoses and couplings daily. Replace worn or damaged parts immediately.
BURN HAZARD
Equipment surfaces and fluid that’s heated can become very hot during operation. To avoid severe burns:
Do not touch hot fluid or equipment.
MOVING PARTS HAZARD
Moving parts can pinch, cut or amputate fingers and other body parts.
Keep clear of moving parts.
Do not operate equipment with protective guards or covers removed.
Pressurized equipment can start without warning. Before checking, moving, or servicing equipment, follow the Pressure Relief Procedure and disconnect all power sources.
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
Do not operate the unit when fatigued or under the influence of drugs or alcohol.
Do not exceed the maximum working pressure or temperature rating of the lowest rated system component. See Technical Data in all equipment manuals.
Use fluids and solvents that are compatible with equipment wetted parts. See Technical Data in all equipment manuals. Read fluid and solvent manufacturer’s warnings. For complete information about your material, request Safety Data Sheet (SDS) from distributor or retailer.
Do not leave the work area while equipment is energized or under pressure.
Turn off all equipment and follow the Pressure Relief Procedure when equipment is not in use.
Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manu­facturer’s replacement parts only.
Do not alter or modify equipment. Alterations or modifications may void agency approvals and create safety hazards.
Make sure all equipment is rated and approved for the environment in which you are using it.
Use equipment only for its intended purpose. Call your distributor for information.
Route hoses and cables away from traffic areas, sharp edges, moving parts, and hot surfaces.
Do not kink or over bend hoses or use hoses to pull equipment.
Keep children and animals away from work area.
Comply with all applicable safety regulations.
TOXIC FLUID OR FUMES HAZARD
Toxic fluids or fumes can cause serious injury or death if splashed in the eyes or on skin, inhaled, or swallowed.
Read MSDSs to know the specific hazards of the fluids you are using.
Store hazardous fluid in approved containers, and dispose of it according to applicable guidelines.
6 3A2776H
Warnings
WARNINGWARNINGWARNING
WARNING
PERSONAL PROTECTIVE EQUIPMENT
Wear appropriate protective equipment when in the work area to help prevent serious injury, including eye injury, hearing loss, inhalation of toxic fumes, and burns. This protective equipment includes but is not limited to:
Protective eyewear, and hearing protection.
Respirators, protective clothing, and gloves as recommended by the fluid and solvent manufacturer SPLATTER HAZARD
Hot or toxic fluid can cause serious injury if splashed in the eyes or on skin. During blow off of platen, splatter may occur.
Use minimum air pressure when removing platen from drum.
3A2776H 7
Warnings

Keep Components A and B Separate

Cross-contamination can result in cured material in fluid lines which could cause serious injury or damage equipment. To prevent cross-contamination:
Never interchange component A and component B wetted parts.
Never use solvent on one side if it has been con­taminated from the other side.

Changing Materials

NOTICE
Changing the material types used in your equipment requires special attention to avoid equipment damage and downtime.
When changing materials, flush the equipment multiple times to ensure it is thoroughly clean.

Components A and B

IMPORTANT!
Material suppliers can vary in how they refer to plural component materials.
Be aware that in this manual:
Component A Component B
This equipment doses the B component into the A com­ponent flow. An integration hose must always be used after the mix manifold and before the static mixer.
refers to resin or major volume. refers to the hardener or minor volume.
Always clean any fluid inlet strainers after flushing.
Check with your material manufacturer for chemi­cal compatibility.
When changing between epoxies and urethanes or polyureas, disassemble and clean all fluid com­ponents and change hoses. Epoxies often have amines on the B (hardener) side. Polyureas often have amines on the B (resin) side
8 3A2776H

Component Identification

WLE
A
B C D
G
H
J
L
M
N
P
R
S
T
U
V
Y
X
K
E, F
C1
ti19927a

Typical Setup (Front View)

Component Identifica tio n
FIG. 1 Key:
AFrame B Fluid Control Assembly (see page 11) C User Interface (see page 15) D Metering Pumps Control On and Off Buttons E Main Air Supply Shutoff Valve, 1 in. npt(f) Inlet F Air Filter, 1-1/4 in. G Air Controls for Sprayer and Flush Pump (see page 13) H Viscon HP Heater for hose bundle J Main Power and Heater Controls (see page12) K Viscon HF Material Heater L Air Powe red Agita tor with Lub ric ato r M Feed Pump N Recirculation Control Valve P Pressure Tank, Double-Wall Temperature Conditioned R Remote Mix Manifold
S Static Mixer Assembly T Spray Gun U Air Motor V Feed Module Air Controls (see page 14) W High Pressure Fluid Metering Pump X Flush Pump (Merkur Pump) Y Radar Fluid Level Sensor Z Air Regulator for Feed Tanks and Pumps A1 Heated Tank Circulation Components (uses a Viscon) B1 TSL Supply Bottle and Bracket C1 Heated Fluid Circulation Pump for Hose Bundle D1 Insulation Jacket E1 Explosion Proof Box (Hazardous Location System only) F1 Junction Box Non-Hazardous Location System only) or
Purge Box (Hazardous Location System only)
3A2776H 9
Component Identification
U
Z
X (located between metering pumps, not visible in current view)
W
A1
B1
C1, A1
D1, A1
Hazardous Location Models only
E1
A1
F1

Typical Setup (Back View)

WLD
FIG. 2
10 3A2776H

Fluid Control Assembly

AA
AC
AG
AL
AE
AJ
ti19928a
Component Identifica tio n
FIG. 3
AA Dosing Valve AC Recirc ulation Valve AE Sampling Valve AG Outlet Check Valve AJ Hose Connection (Model 262869) - A side: 3/4 npt(m); B side: 1/2 npt(m)
Hose Connection (Model 24W626) - A side: 3/4 npt(m); B side 3/4 npt(m)
AL Pressure Sensor
3A2776H 11
Component Identification
ti26689a
BB
BD
Hazardous Location System
Non-Hazardous Location System
CA
r_XM1A00_312359_313289_14A
Hazardous Location System
BB
BD BA

Main Power and Heater Controls

FIG. 4
BA Main Power ON/OFF Switch (non hazardous loca tion) BB A and B Tank Water Heat ON/OFF Switch BD Optional Heated Water Flush Tank Accessory ON/OFF
Switch (only used if the water heater accessory has been added to the machine) (standard on hazardous location models
CA Main Power ON/OFF Switch (hazardous location)
12 3A2776H

Sprayer and Flush Pump Air Controls

CA
CB
CC
CD
CE
CG
CF
r_XM1A00_312359_313289_14A
FIG. 5
Component Identifica tio n
CA Metering Pump Air On/Off Control (non hazardous loca-
tion) Main Power On/Off Switch (hazardous location), see
Main Power and Heater Controls, page 12 CB Flush Pump Air On/Off Control CC Inlet Air Pressure Gauge CD Metering Pump Air Regulator CE Metering Pump Air Regulator Gauge CF Flush Pump Air Gauge CG Flush Pump Air Regulator
3A2776H 13
Component Identification
FEED PUMP
BYPASS
CR
CP
CU
CS
CT
NOTE: Both valves shown open
ti20127a
DF
DB
DA
DC
DD
DE
ti20104a

Feed Module Air Controls

F
IG
. 6: Supply Controls
CP Tank Air Pressure Regulator CR Tank Air Pressure Gauge CS Tank Air Supply Valve CT Agitator and Heated Water Circulation On/Off Valve CU Feed Pump Bypass Button
Feed Pump Air Controls
Feed Pump Bypass Button
Use the feed pump bypass button (CU) to manually run the feed pump when the automatic tank filling function is not running the feed pump. See automatic tank filling details on page 84.
DC RAM Up/Down Director Valve DD RAM Blowoff Valve DE Air Motor Regulator DF Air Motor ON/Exhaust Slider Valve
RAM Blowoff Valve (DD)
To minimize material splatter, use the minimum air pressure required to remove platen from pail.
To easily remove the RAM from the pail, press and hold the RAM Blowoff Valve button while lifting the RAM platen. A small amount of air pressure will be supplied to the pail to push the pail off of the RAM.
DA RAM Air ON/Exhaust Slider Valve DB RAM Air Regulator
14 3A2776H

User Interface

DA
DB
DD
DE
DF
DG
DH
DK
DP
DN
DM
DC
ti13365a
DR
DJ
NOTICE
To prevent damage to soft key buttons, do not press the buttons with sharp objects such as pens, plastic cards, or fingernails.
Component Identifica tio n
F
IG
. 7: User Interface
Buttons LEDs
Call
out Button Function
DA Display
Screen
DB Start Initiates Active Run Mode function cur-
DC Stop Terminates Active Run Mode function
DD Enter Press to open drop-down fields, select
DE Alarm
Reset
DF Left/Right Move between screens in run or setup
DG Function Activates mode or action represented by
DH Up/Down M ove between drop-down fields, option
DJ Setup Key
Lock
DR USB Port Connection for data download.
3A2776H 15
Use to view screens. See page 68.
rently selected in Run Screen.
currently selected.
options, and save values. Resets alarms and advisories.
modes.
the icon above ea ch o f t he fo ur butt ons in the LCD.
boxes, and selectable values within Setup screens.
Change ratio or enter Setup mode.
There are four types of LEDs on the display.
Call
out LED Function
DK Blue Dosing valve active
On - dosing valve is active
Off - dosing valve is not active
DM Green Spray mode active
Spray mode is on (active)
Spray mode is off (inactive)
DN Red Alarm
On - alarm is present
Off - no alarm
DP Yellow Warning
On - is active.
Off - no warning indicated. R atio and setup fields are not change­able.
Flashing - key is present and turned. Ratio and setup fields are changeable.
Component Identification
Current Date and Time
Go back one screen
Navigational Bar
Function Display
Remaining Potlife Time System Ratio Mode
(Volume/Weight)
User Interface Display
Main Display Screen Components NOTE: For detailed screens information, see Appendix A - User Interface Display beginning on page 68.
The following figure calls out the navigational, status, and general informational components of each display screen.
The system ratio mode shows if the mix ratio target is by volume or weight . If the weight is crossed out, the system must be calibrated before running. See Pump and Metering Test and Calibration for Ratio by Weight
Mode on page 48.
F
IG
. 8: Main Display Screen Components (shown with all display features enabled)
16 3A2776H

Setup

Front to Back Configuration
Side by Side Configuration
ti20267a
ti20268a
Setup

Location

Select a location that complies with the approval rating for your model. For approval rating, see Models, page
3. The location must have the required power and air sup-
ply to set up your sprayer. See Technical Data, page 96, for Air Consumption and Power Requirements Main­tain access from all sides.

Unboxing

The machine is shipped on two separate pallets, one with the XM PFP and one with the two feed modules.
Each pallet is wrapped in heavy cardboard with a lid secured with straps. Cut the lid straps then remove the lids and cardboard.

Ratio Configuration

Proportioners leave the factory set up for materials which are higher volume and/or viscosity on the “A” side, and lower volume and/or viscosity on the “B” side. 1:1 mix ratio machines will normally change the “B” side circulation return hose from 3/8 in. to 1/2 in. ID to bal­ance the recirculation speeds.
1:1 mis ratio machines also use outlet hose bundles which are 3/4 in. on both sides. The outlet fittings on the machine and the inlet fittings on the mix manifold must be changed on the “B” side from 1/2 in. to 3/4 in.
1:1 Ratio Adapter Kit 24X461 is provided with your machine. Install the kit, if necessary, before screwing the modules together.

Configuration Options

The system can be laid out two ways:
Side by side: where the feed modules are on either side of the system module
Front to back: where the feed modules are behind the system module
F
IG
. 9
3A2776H 17
Setup
ti20163a
5.5 in. long
2x (115211)
8x
1.5 in. long
(16J674)
ti20197a
3.5 in. long
8x (124869)
8x
1x
5.5 in. long
(115211)
(16J674)
Horizontal Braces
Connect Modules
Regardless of the chosen module configuration, the A feed module must be on the left and the B feed module must be on the right when looking at the front of the sys­tem module. The A module has a blue A sticker on the air control panel and a 1/2 in. return fitting into the tanks. The B module has a green B sticker on the air control panel and a 3/8 in. return fitting into the tanks.
Frame Connection Parts Part Description Qty
115211 SCREW, cap, hex head; 5.5 in 2 16J674 SCREW, cap, flange hd; 1.5 in 8 124869 SCREW, cap, hex head; 3.5 in 8 109570 WASHER 20 112731 NUT 10
Choose one of the configurations shown in F
IG
. 9 then bolt together the three modules on a flat surface. See F
IG
. 10 or FIG. 11 for bolt locations. The frame bolts are included in a bag. Once connected, the assembly can be moved as one piece with a fork-truck.
NOTICE
If the front-to-back module configuration is used, install the two supplied straight steel horizontal braces between each feed module and the sprayer module, see F
IG
. 11. These are not used in the side-by-side module
configuration.
FIG. 10: Bolt Locations (Side by Side)
Do not use motor lift rings to lift the entire assem­bly. This will damage the system. The system must be lifted from the bottom.
If the modules will not be connected, they must be within 12 in. of each other and in one of the two configurations in F
IG
. 9 to ensure hoses and cables can reach their
connections.
IG
. 11: Bolt Locations (Front to Back)
F
18 3A2776H
Setup
ti27665a

Grounding

The equipment must be grounded to reduce the risk of static sparking and electric shock. All internal earth grounding must use only copper wires. See electrical schematics in systems repair manual for wire size. Electric or static sparking can cause fumes to ignite or explode. Improper grounding can cause electric shock. Grounding provides an escape wire for the electric current.
All components shipped from the factory are electrically bonded through ground wires. Ground the electrical connection properly according to local codes.

Connect Power Cord

Non-Hazardous Location Models
200-240 VAC, 3 Phase Delta, Non-Hazardous Location: Use a 5/32 in. (4 mm) hex key to connect the
three power leads to top terminals L1, L2, and L3. Con­nect green to ground (GND).
350-415 VAC, 3 Phase WYE, Non-Hazardous Location: Use a 5/32 in. (4 mm) hex key to connect the
three power leads to the top terminals T4, L1, and L2. Connect neutral to L3. Connect green to ground (GND).
1 L1
8 T4
7 L4
2 T1
3 L2
5 L3
CT1
4 T2 6 T3
8 T4
7 L4
1 L1
2 T1
3 L2
5 L3
CT1
4 T2 6 T3
Power must be connected by a qualified electrician. Graco does not supply junction box power supply cords. Use the following chart to determine which power cord your system requires.
Power Cord Requirements
System Voltage Cord Specification AWG (mm
2
200-240 VAC, 3 PH 6 (13.3) 3 wire + ground 350-415 VAC, 3 PH 6 (13.3) 4 wire + ground
For Hazardous Location Models, use appropriate power cord. Follow all National, State, and Local electric codes.
1. Open junction box cover.
2. For non-hazardous location models, Insert power cord through the large empty strain relief in the bot­tom of the junction box. For hazardous location models, Insert power cord in the bottom of the explosion proof box. Use appro­priate cable gland for the 1-1/4 npt port, the cable gland must be rated to ATEX II 2 G. Follow all National, State, and Local electric codes.
3. Connect power cord as follows.
Hazardous Location Models
200-240 VAC, 3 Phase Delta, Hazardous Location:
Use a screwdriver to connect the three power leads to the left side of terminals TB3, TB4, and TB5. Connect green to ground (TB1).
)
350-415 VAC, 3 Phase WYE, Hazardous Location:
Use a screwdriver to connect the three power leads to the left side of terminals TB2, TB3, TB4, and TB5. Con­nect neutral to N. Connect green to ground (TB1).
ti27666a
3A2776H 19
Setup
E
ti20105a

Set Power Jumpers

1. Find the red power jumpers for the terminal blocks supplied in a plastic bag in the circuit box. For haz­ardous location models, are in the explosion proof box (E1).
2.
For 200-240 VAC and 350-415 VAC, 3 Phase instal­lations only,
jumpers into the terminal blocks in the correct posi­tions as shown in the following illustration. Push jumpers firmly into position.
IG
. 12: Non-Hazardous Location Models
F
use pliers to install the three red power
ti27667a

Connect Air Supply

Connect air supply line to the 1 in. npt(f) air supply ball valve inlet.
NOTE:
Use a 3/4 in. (19.1 mm) ID minimum air hose.
NOTE:
Air supply requirement:
maximum; 80 psi (552 kPa, 5.5 bar) minimum (while running).
Flow volume required:
250 scfm (7.1 m
3
sure and flow rate are directly related to available air volume. A typical single gun XM PFP application will use
125 to 175 scfm (3.5 to 5.0 m
150 psi (1.0 MPa, 10.3 bar)
100 scfm (2.8 m3/min) minimum;
/min) maximum. Available fluid pres-
3
/min).
IG
. 13: Hazardous Location Models
F
3. Close junction box cover.
NOTE:
Dosing valves are operated by air. The sprayer will not operate correctly if the inlet air pressure drops below 80 psi (552 kPa, 5.5 bar) while spraying.
ti27668a
20 3A2776H
Setup
a
b
c
e

Connect Feed Module Lines to Sprayer Module

1. Connect Modules, page 18.
2. Connect the large diameter green hose from each tank bottom outlet to the respective metering pump inlet. Hose (1403) is for side by side setup and hose (1413) is for front to back configurations.
NOTE: There is a vertical swivel union at each end of the green hose assembly.
3. Connect the two hose bundles with a red air hose on the sprayer module to the correct connection on the respective feed module, as described below.
a. Connect the red 1/2 in. air hose to the swivel
union. See the ‘a’ in F
IG
. 15.
d
IG
. 14: Feed Module Lines
F
NOTE: If desired, the green hose can be trimmed to fit
better.
a. Loosen the tank end of the hose before trying to
connect to the metering pump inlet.
b. Bend the hose as necessary to make it fit.
c. Once the vertical unions are tightened, check
that the hose clamps on the green hose are tightened to approximately 90-100 in-lb (10-11 N•m).
FIG. 15
b. Connect the 1/4 in. OD air signal tube to the
tube that has a tube connector. This is the feed pump pilot signal. See the ‘b’ in F
c. Connect the small cable with an M8 connector
to the mating M8 connector. See the ‘c’ in F
15.
d. Connect the larger cable with an M12 connector
to the mating M12 connector. This is the level sensor connection. See the ‘d’ in F
WLE
IG
. 15.
IG
. 15.
IG
.
3A2776H 21
Setup
3UHVVXUH7DQN
6\VWHP)OXVK
+HDWHU 
+HDWHU 
PS1
TB8
TB9
TB10
TB11
TB12
TB9
TB10
TB11
TB12
&LUFXLW%UHDNHU
A
B
Hose
Tank
Flush
*URXQG
%DU
WLD
e
e
3UHVVXUH7DQN
6\VWHP)OXVK
*URXQG
%DU
&LUFXLW%UHDNHU
WLE
+HDWHU 
+HDWHU 
e
e
e. For Non-Hazardous Location Models, Con-
nect heater power cables (e) for the tank heater and the flush heater to the terminal blocks. See
F
IG
. 16.
For Hazardous Location Models, Connect heater power cables (e) for the tanks heater the flush heater to the terminal blocks. See F
IG
. 17.
F
IG
. 16
FIG. 17
4. Connect the fluid ci rcul ation re turn h oses .
The 1/2 in. circulation hose from the dosing valve connects to the side of the A tank.
The 3/8 in. circulation hose from the dosing valve connects to the side of the B tank.
NOTE: Systems that will be used for 1:1 mix ratio mate­rials need to change some fittings and circulation hoses. Use parts from kit 24X461 (supplied with your machine). See manual 334939 for instructions.
22 3A2776H

Install Level Sensor Probes

WLD
Each tank uses a 37 in (94cm) stainless steel rod, which functions as the level sensor probe, that mounts into the level sensor head and extends down into the tank. The level sensor probes are tie-wrapped to the frame of each feed module at the factory prior to ship­ment. The level sensor probes must be mounted into the level sensor heads before use.
1. Verify the main power switch is OFF.
2. Disconnect 3/4 in. union that holds the level sensor on top of the tank.
3. Apply blue thread lock to the threads in the top of the rod.
4. Feed the rod into the tank and screw the threaded end up into the sensor head.
5. Use a pliers to grab the flat on the rod and tighten the rod up into the sensor head. Do not over-tighten.
Setup
IG
. 18
F

Level Sensor Calibration

Level sensors are factory set to work with these tanks. Calibration is not necessary unless replacing a sensor. See repair manual for the XM PFP (3A2989).
3A2776H 23
Setup
ti20106a
ti20272a
ti20273a

Connect the Fluid Hose Bundle to the System

The system is shipped with a 50 ft (15 m) hose bundle for connecting the system to the mix manifold.
The bundle contains one 3/4 in. ID A material hose, one 1/2 in. ID B material hose (models 262869, 262945) one 3/4 in. ID B material hose (models 24W626, 262943), one 1/4 in. ID flush hose, and 1/2 in. OD heated fluid cir­culation tubes. The hose bundle is insulated and wrapped inside a protective sheath which has a Velcro closure so it can be opened to change hoses.
For models 262869 and 262945, use 1:1 Hose and Fit­ting kit 24X461 (supplied with your machine) to replace the fittings and B side circulation hoses. See supplied manual 334939 for instructions.
1. Position the hose bundle end with the four loose red and blue tubes at the machine outlet.
Systems 262869 and 262943: Connect the 3/4 in. A and 1/2 in. B hoses to the respective material out­let check va lves on t he f ron t of t he s yste m. S ee F
19. Systems 24W626 and 262945: Connect the 3/4 in.
A and 3/4 in. B hoses to the respective material out­let check va lves on t he f ron t of t he s yste m. S ee F
19.
IG
IG
2. Connect the short purple flush hose from the flush pump to the 1/4 npsm hose in the bundle. Use the 1/4 in. nipple included with the hose bundle to con­nect the hoses. See F
IG
. 20.
FIG. 20: Flush Pump Connection
3. Connect the two red tubes in the bundle to the tube
.
tee on the red tube on the front of the machine. Do the same for the blue tubes. See F
IG
. 21.
.
F
IG
. 19
IG
. 21
F
24 3A2776H
Setup
ti20274a
Material Inlets
Flush Inlet
ti20088a
4. Locate the temperature sensor with black heat shrink sheath and a connected cable that is tie-wrapped to the B heater power cable.
a. Cut the temperature sensor loose from the tie
wrap.
b. Insert the sensor down inside the hose bundle
so it is buried in the insulation and up against the fluid hoses. Be sure the sensor cable will not get pulled tight by the hose.

Connect the Fluid Hose Bundle to the Mix Manifold

1. Unroll the hose bundle out to the spray area.
2. System 262869: Connect the 3/4 in. A and 1/2 in. B hoses to the material inlet ball valves on the mix manifold. See F
System 24W626: Change the B side inlet nipple and connect the 3/4 in. A and 3/4 in. B hoses to the material inlet ball valves on the mix manifold. Color code material hoses (green and blue) with respec­tive color id entifi cation on mix mani fold. S ee F
IG
. 23.
IG
. 23.
F
IG
. 22
c. Use electrical tape to wrap the hose bundle
from where it connects to the system to the hose sheath. This insulates and protects the hose bundle.
FIG. 23
3. Remove the U-shaped tube connectors only from the end of the longer set of red and blue tubes. Trim the excess tubing to fit the one set of the red and blue tubes fully into the two brass compression fit­tings on the aluminum heat circulation plate under the main manifold. Tighten the compression fittings.
4. Route the purple flush hoses from the manifold underneath the manifold carriage and connect to the 1/4 in. flush hose in the hose bundle. See F
IG
. 23.
5. Use electrical tape to wrap the hose bundle from where it connects to the system to the hose sheath. This insulates and protects the hose bundle.
3A2776H 25
Setup
ti20090a
R
S
T

Connect the Mix Manifold to the Gun

The following parts are supplied loose. Connect them to the mix manifold as follows. See F
1. Connect 1/2 in. ID x 2 ft hose to mix manifold (R) outlet.
F
IG
. 24
IG
. 24.

Prime Heated Hose Bundle Fluid Circulation System

The heated fluid circulation system includes heated hoses alongside the material hoses for the length of the hose bundle, heated fluid circulation through the mix manifold, and heated fluid circulation through the tank double-wall which is insulated by a jacket.
See instructions on page 29.
2. Connect static mixer (S).
3. Connect 1/2 in. ID x 10 ft. hose.
4. Connect 1/2 in. x 3/8 in. nipple.
5. Connect 3/8 in. ID x 3 ft hose.
6. Connect 1/2 x 3/8 nipple.
7. Connect swivel.
8. Connect gun (T).

Connect Tank Heat Circulation Hoses

NOTE: The tank jacket heat circulation system was pre-filled at the factory.
The tank to tank circulation hoses use quick-disconnect fittings that were connected back to their own tank for shipping.
Disconnect these fittings and connect them back to the opposite tank as shown in F
IG
. 25 or FIG. 26.
26 3A2776H
Setup
Side By Side Configuration
See Front to Back Configuration, F
IG
. 4, page 12.
FIG. 25: Heated Fluid Diagram For Tank Heat (Hazardous Location Shown)
3A2776H 27
Setup
Front to Back Configuration
FIG. 26: Heated Fluid Diagram For Tank Heat (Hazardous Location Shown)
28 3A2776H
Prime Heated Fluid Circulation System Continued
FEED PUMP
BYPASS
ti20127a
ti20126a
Adjustment Knob Location
Setup
Hose Bundle Heating System
1. Add a 50% water, 50% glycol anti-freeze mix to the small translucent tank located at the bottom right corner of the front of the sprayer module.
NOTE: Even in warm climates, a water/glycol mix should be used to keep the circulation system clean and working properly.
2. With air supply on, adjust the silver knob on top of the diaphragm pump to start the small black dia­phragm pump under the tank. Adjust pump to approximately 2-3 cycles per second.
3. Continue to add the 50/50 fluid mixture as air is purged from the fluid lines but make sure the tank is no more than 1/4 to 1/3 full when cold.
NOTE: Re-tighten all heated fluid circulation tube fittings after the first time the system has been run at full tem­perature.
Double-Walled Tank Heating System NOTE: The double-walled tanks are pre-filled with a
water/glycol mix at the factory. If your tanks are already filled, skip this section.
3. Adjust the silver knob located just above the Feed Module Air Controls. When looking at the Feed Module Air Controls, the knob will be visible just above them. See F
IG
. 28. Adjust knob until tank
heated fluid pump reaches approximately 2-3 cycles per second.
NOTE: On all models, there is only one pump and one heater, which is located on the “A” side feed module.
1. Add a 50% water, 50% glycol anti-freeze mix to the small translucent tank located between the tank and feed pump on the feed module.
2. Turn the agitator and tank heated fluid pump air ball valve ON.
F
IG
. 27
FIG. 28
4. Continue to add the 50/50 fluid mixture as air is purged from the fluid lines but make sure the tank is no more than 1/4 to 1/3 full when cold.
NOTE: Re-tighten all heated fluid circulation tube fittings after the first time the system has been run at full tem­perature.
3A2776H 29

Initial Startup

CA
purge complete
Initial Startup
Perform this procedure on new systems. Systems are tested at the factory with mineral oil and there will be residual oil in the material lines. Flush new systems if A or B material will not function properly if it contacts min­eral oil.
1. Verify all procedures in the Setup section beginning on page 17 have been properly performed.
2. Perform Adjust Packing Nuts on page 61.
Power On Machine
3.
For non-hazardous location models:
power switch (BA) ON and verify the system air inlet ball valve (E) is open. See F
IG
. 1 on page 9.
Turn main
c. While the system is in the purge sequence, wait
approximately 3 minutes until the right indicator light turns green. The system display will turn on when the purge complete indicato r turn s gree n after a 3 minute purge sequence.
NOTE: For hazardous location models, the syste m will turn off if the air is locked, turned off, or depressur­ized. Open the main power switch (CA) to turn on sys­tem and allow the purge controller to complete the 3 minute purge sequence.
For hazardous location models:
4.
a. Open the air supply valve (E). See F
page 9.
b. Open the main power switch (CA). After approx-
imately 5 seconds the left indicator light on the purge controller will turn green.
IG
. 1 on
Flush Machine (If Required)
5.
If your A or B material will not function properly if it mixes with a small amount of mineral oil,
the remainder of this Initial Startup procedure once with grounded pails of solvent instead of A and B material pails. After performing this entire procedure once with solvent, perform it a second time with the A and B materials. Be sure to choose a solvent that is compatible with your material and with the wetted parts in this system. See Technical Data on page 96.
perform
30 3A2776H
Loading...
+ 70 hidden pages