Graco GLC 2200, GLC 2200 24N468 Instructions Manual

Page 1
Instructions
GLC 2200 Lubrication Controller
3A2960F
For controlling and monitoring an automated lubrication system. Not approved for outdoor use or use in explosive atmospheres or hazardous locations.
Model: 24N468
Important Safety Instructions Read all warnings and instructions in this manual. Save these instructions.
EN
Page 2

Warnings

WARNINGWARNINGWARNING
WARNING
Warnings
The following warnings are for the setup, use, grounding, maintenance, and repair of this equipment. The exclama­tion point symbol alerts you to a general warning and the hazard symbols refer to Procedure-specific risks. When these symbols appear in the body of this manual or on warning labels, ref er bac k to these W arnings. Prod uct-specific hazard symbols and warnings not covered in this section may appear throughout the body of this manual where applicable.
EQUIPMENT MISUSE HAZARD
Misuse can cause death or serious injury.
Do not operate the unit when fatigued or under the influence of drugs or alcohol.
Do not exceed the maxim um working Pres sure or tem per ature r ating of t he lo west r ated syst em com­ponent. See Technical Data in all equipment manuals.
Use fluids and solvents that are compatible with equipment wetted parts. See Technical Data in all equipment manuals. Read flu id and solv ent manuf acturer ’ s wa rnings. F or complete inf ormation about your material, request MSDS from distributor or retailer.
Do not leave the work area while equipment is energized or under pressure.
Turn off all equipment and follow the Pressure Relief Procedure when equipment is not in use.
Check equipment daily. Repair or replace worn or damaged parts immediately with genuine manu­facturer’s replacement parts only.
Do not alter or modify equipment. Alter atio ns or modificati ons may void agency appro vals and create safety hazards.
Make sure all equipment is rated and approved for the environment in which you are using it.
Use equipment only for its intended purpose. Call your distributor for information.
Route hoses and cables away from traf fic areas, sharp edges, moving parts, and hot surfaces.
Do not kink or over bend hoses or use hoses to pull equipment.
Keep children and animals away from work area.
Comply with all applicable safety regulations.
2 3A2960F
Page 3

Component Identification

ON
OFF
HH MM
SS
##
!
J
D
F
A
B
C
E
H
G

Keypad, Display, and Icons

Component Identification
NOTICE
To prevent damage to soft ke y button s, do not pr ess the buttons with sharp objects such as pens, plastic cards, or fingernails.
Display (E)
•A blinking field on the display indicates the controller is in SETUP MODE.
•In RUN MODE numbers on the display will not blink.
Alarm LED (F)
Illuminates when any alarm is detected. When an alarm is active an error code displays and an audible alarm also sounds.
RIGHT Direction Arrow / MANUAL RUN / ENTER (G)
•In SETUP MODE, saves entry, moves cursor in dis-
play one field to the right or to the next setup step.
•In RUN MODE activates the pump for one com-
plete ON cycle if actuated during the OFF por­tion of the RUN cycle.
UP and DOWN Direction Arrows (H)
•Press and hold both the UP and DOWN Arrow k eys
together for 3 seconds to enter SETUP MODE.
•In SETUP MODE increase or decrease number
values associated with the various RUN
FIG. 1
Pump ON LEDs (A, B, C)
APressure Control LED: In RUN MODE illuminates
indicating function mode that is currently running.
BCycle Control LED: In RUN MODE illuminates
CTime Control LED: In RUN MODE illuminates
indicating function mode that is currently running.
indicating function mode that is currently running.
Pump OFF LED (D)
•In RUN MODE this LED illuminates when in the OFF or RESET portion of the RUN CYCLE.
LEFT Direction Arrow / RESET (J)
MODES.
•In SETUP MODE moves cursor in display one field to the left.
•In RUN MODE, Pressing RESET starts a PUMP OFF cycle.
•In ALARM MODE, Press once to clear buzzer; Press and hold for 3 seconds to clear warning and switch controller to OFF MODE.
3A2960F 3
Page 4

Installation

Controller
Capabilities
B1
B2
B3
C
E
H
G
F
D
Low Reservoir Level
switch (user provided)
Pressure or Cycle Switch
for system control
(user provided)
Remote Alarm Device
i.e., light or horn
(user provided)
A
K
J
Installation

Typical Installation

The installation shown in FIG. 2 is only a guide for selecting and installing system components. Contact your Graco distributor for assistance in planning a system to suit your needs.
FIG. 2
AMain Air Supply BFilter/Regulator/Lubricator Assembly
B1 - Filter B2 - Regulator B3 - Lubricator
CAir Solenoid Valve DPump Module
4 3A2960F
EIgnition Switch FHigh-Pressure Lubricant Supply Lines GInjector Banks HLubrication Controller JIn-line Fuse KPower Source
Page 5
Installation
a
a

Installing the Lubrication Controller

AUTOMATIC SYSTEM ACTIVATION HAZARD
Unexpected activation of the system could result in seri­ous injury, including skin injection and amputation.
This device has an automatic timer that activates the pump lubrication system when power is connected or when exiting the programming function. Before you install or remove the Lubrication Controller from the system, disconnect and isolate all power supplies and relieve all pressure.
1.Select a flat surface to install th e Lubrication Control­ler. Drill mounting holes. Refer to Mounting Hole Layout Provided in the Technical Data section of this manual, page 24.
2.Align junction box with predrilled holes (F Use two screws (not provided) to secure junction box to mounting surface.
IG. 3, (a).

System Configuration and Wiring

The System Configuration Diagrams (FIG. 4 - FIG. 6), Sensor Wiring Diagrams (F grams (F Injector, Series Progressive and Dual Line lubrication system configurations.
Refer to Table 1, 2 and 3 to determine the Required Sys­tem Configuration, Sensor Configuration an d Wiring Diagram to use to setup your system.
IG. 7) on the following page s, show typical
Table 1: System Configurations
System Figure Page
Injector 4 6 Series Progressive 5 7 Dual Line 6 8
Table 2: Sensor Wiring Configurations
Sensor Figure Page
Dry Contact 7 10 Source Switch 8 10
IG. 8 - FIG. 9) and Wiring Dia-
FIG. 3
Table 3: Modes of Operation
Mode Power Figure Page
Time ON/Time OFF DC 9 9 Cycle ON or Pressure ON/Time OFF Low Level Switch
DC 9 9
99
3A2960F 5
Page 6
Installation
GLC 2200
Low Level Switch
Pump & Reservoir
Injector System
Pressure Switch
Injectors
Lubrication Points
Vent Line
Pump On/Off
External Alarm
Vent Valve

System Configuration

FIG. 4
6 3A2960F
Page 7
GLC 2200
Low Level Switch
Pump & Reservoir
Master Divider Valve
Secondary Divider Valves
Cycle Switch
Divider Valve System
Pump On/Off
External Alarm
Installation
FIG. 5
3A2960F 7
Page 8
Installation
GLC 2200
External Alarm
Low Level Switch
Pump & Reservoir
Dual Line System
Cycle Switch
Bi-flo Valves
Lubrication Points
Vent Line
Pump On/Off
Reverser
FIG. 6
8 3A2960F
Page 9

Wiring Diagram

1 2 3 4 5
6 7 8 9 10
M
9A Fuse
+
-
V
*
9A 2A
P/C
+9V +30V
Modes of Operation: Optional I/O Wiring Diagram
Used with all modes of GLC2200 Operation
Installation
FIG. 7
*Normally open vent valve for use with Injector-based systems
Wiring Key Connector Identification Label
PIN12345
PIN678910
Pin Description
1Pump 2Alarm 3Low Level 4 Pressure/Cycle Switch 5 Voltage Input 6Pump 7Alarm 8Low Level 9 Pressure/Cycle Switch
10 Voltage Input
+/-
-
-
-
-
­+ + + + +
3A2960F 9
Page 10
Installation
4
9
GLC 2200
4
+VDC
-VDC
GLC 2200

Sensor Wiring Configurations

DRY CONTACT SWITCH
FIG. 8
SOURCE SWITCH - 2 or 3 Wire Type
FIG. 9
10 3A2960F
Page 11

Setup

Setup

Entering SETUP MODE

1.Press both the UP and DOWN ARROW buttons together for three seconds.
NOTE:
•If a button is not pushed for 1 minute, the controller returns to the start of an OFF cycle.
•Setting changes are not stored unless programming is completed and setup mode is exited normally by pressing the ENTER button.
•A blinking dot below the HH, MM, SS, or ## indicates the field currently being programmed.
PIN Code (Series E or later models only)
NOTE: If, after entering Setup Mode, four 0000’s are
displayed, the unit has a PIN Code lock out enabled. See Entering a PIN Code to Access Setup Mode for instructions on entering a value.
Entering a PIN Code to Access Setup Mode
The controller does not require a user to provide a PIN code to access the programming features of the unit. However, some users may want to protect the program settings and therefore, an option for adding PIN Code authorization is available. The instructions for setting a PIN Code are provided in the Advanced Programming section of this manual. See page 19.
To en te r th e PIN Cod e :
1.Press both the UP and DOWN ARROW buttons for 3 seconds.
2.Four zeros appear on the display indicating the system requires a PIN Code entry to access the SETUP MODE.
3.The cursor is automatically positioned to enter the first character of the PIN Code . Use the UP and DOWN ARROW buttons to move up and down through the num­bers 0-9 until the first number in the PIN code is displayed in the field.
4.Press the ENTER (right arrow) button to set the number. The cursor automati­cally moves to the next number field.
5.Repeat steps 3 and 4 for each PIN Code prompt field.
If the PIN Code you entered is correct, the unit will enter setup mode.
6.Press the ENTER (right arrow) button to set the number. The cursor automati­cally moves to the next number field.
NOTE: A blinking field on the displa y indicates t he is in SETUP MODE. In RUN MODE numbers on the display will not blink.
3A2960F 11
Page 12
Setup
Programming ON Duration
on:Pr, on:CY or on:ti appears on the display identi fy- ing the function you are programming (see below).
•The illuminated LED below the related symbol on the controller label also indicates the function.
NOTE: Selection on:Pr, on:CY or on:ti designates the way the pump run time is controlled:
on:Pr = Pressure Control, reach-
ing a specific pressure thresh­old measured by an external pressure switch
on:CY = Cycle Control, complet-
ing a specific number of cycles of an external prox/cycle switch
Cycle Control (on:CY) ON Setup
1.Use the UP or DOWN ARROW until on:CY displays.
2.Press the ENTER button.
The first number displayed after the on:CY is entered, blinks, indicating the device is ready to program the number of cycles.
NOTE: The cycle entry is a 2-digit number. A leading zero (0) must be enter ed in the f irst field i f the n umber o f cycles is fewer than 10.
3.Program the cycles by pressing the UP or DOWN ARROW to move up or down through the numbers 0-9.
on:ti = Time Control, a specific duration of time elapses
Pressure Control (on:Pr) ON Setup
1.Use the UP or DOWN ARROW until on:Pr displays.
2.Press the ENTER button.
3.Pressure control is an ON / OFF selection only. After you press the ENTER button, the controller saves the Pressure Control information and moves to setting Backup Time, page 13.
4.When the correct first digit is displayed, press the ENTER button.
The cursor automatically moves to the second number field and flashes.
Use the UP or DOWN ARROW to scroll through the numerals 0-9 until the desired number appears in the second cycle number field.
5.Press the ENTER button. After you press the ENTER button, the controller saves the Cycle Control infor­mation and moves to setting Backup Time, page 13.
Time Control (on:ti) ON Setup
1.Use the UP or DOWN ARROW to cycle through until on:ti displays.
12 3A2960F
Page 13
Setup
2.Press ENTER.
3.To set the ON time use the UP or DOWN ARROW to scroll through the numerals 0-5 until the desired number appears in the first Minutes (MM) field.
NOTE:
•The MM field is a 2-digit number.
•A leading zero (0) must be e ntered in the first fie ld if
the number of minutes is fewer than 10.
•The highest number that can be set f or the MM field
value is 59.
4.Press the ENTER button.
The next MM number fie ld to the right flashes , indicating it is ready for programming.
5.Use the UP or DOWN ARROW to scroll through the numerals 0-9 until the desired number appears in the second MM number field.
Backup Time
In both Cycle and Pressure Modes, a maximum run Time (Backup Time) for the lubrication period must be set up. If this Time expires before the lubrication is com­pleted an alarm/warning is triggered and the pump stops.
To determine the Backup Time, Graco recommends the user verify the length of time it takes to complete a typi­cal cycle and double that value.
Backup Time is setup after Cycle or Pressure Sensor Setup is complete.
NOTE:
•The LED below the clock in the ON field lights, indicating the Backup Time is being programmed.
•BACKUP (ON) Time is set as minutes and seconds (MM:SS) only.
6.Press the ENTER button. The next number field to the right flashes indicating it is
ready to program the Seconds (SS) fields. NOTE:
•The Seconds (SS) field is a 2-digit number.
•A leading zero (0) must be e ntered in the first fie ld if the number of seconds is fewer than 10.
•The highest number that can be set for the SS field value is 59.
7.Repeat steps 3 - 6 to set the SS fields.
8.Press the ENTER button. After you press the ENTER button the controller automatically switches to the OFF TIME SETUP MODE.
•The small flashing LED under the MM indicates you are setting minutes.
•The first field (left side of displa y) blinks indicating the device is ready for you to begin programming.
Programming Backup Time NOTE: When programming a time of less than 10 min-
utes you must program the leading zero in the first num- ber field and press the ENTER button.
1.To set the ON Time use the UP or DOWN ARROW button to scroll through numer­als 0 to 5 until the desired number appears in the first MM (minutes) field.
2.Press the ENTER button. The ne xt MM number field to the right flashes indi­cating it is ready for programming.
3.Use the UP or DOWN ARROW button to scroll through numerals 0 to 9 until the desired number appears in the second MM number field.
3A2960F 13
Page 14
Setup
OFF
4.Press the ENTER button. The next number field to the right
flashes and the LED lights under SS; indicating it is ready to program the seconds fields.
5.Repeat steps 1 - 4 to set the SS (seconds) fields.
6.After pressing the ENTER button to set the last SS field, all the programmed ON Time information is saved.
The controller automatically switch es to t he OFF Time SETUP MODE.
Programming OFF TIME Duration
After setting the parameters for either Pressure (Pr), Cycle (CY) or Time (Ti) ON Modes, the OFF TIME or PUMP REST CYCLE must be set up.
The LED below the OFF TIME Symbol Illu­minates.
NOTE:
•The HH field is a 2-digit number.
•A leading zero (0) must be entered in
the first field if the number of ho ur s is fewer than 10.
•The highest number that can be set f or the HH field
value is 99.
The next number field to the right flashes indicating it is ready to program the Minutes (MM) fields.
NOTE:
•The MM field is a 2-digit number.
•A leading zero (0) must be ente red in the first field if the number of minutes is fewer than 10.
•The highest number that can be set f or the MM field value is 59.
5.Repeat steps 1 - 4 to set the MM fields.
6.Press the ENTER button to lock in the last MM field. The controller automatically switches to the LOW
LEVEL SETUP MODE.
Programming the Low Level Setting
NOTE: If Low Le vel is not used (i.e., low le vel inputs are
not connected), configuring the low level setting is still required. The unit’ s de f a ult settings (LL: 01) can b e used.
1.Use the UP or DOWN ARROW to select the low level setting.
2.Press ENTER.
To set the OFF Time:
1.Use the UP or DOWN ARROW to scroll through the numerals 0-9 until the desired number appears in the first Hours (HH) field.
LL:01 - Default
This is the default low level setup when working with a standard, normally open, low level switch. The pump stops when the low level occurs.
The unit will enter a low level fault condition after the
2.Press ENTER.
switch input is closed for more than 1 second when the unit is in the ON portion of the RUN MODE.
The next HH number field to the right flashes, indicating it is ready for programming.
When low level occurs:
• The pump stops
• The unit displays ER:LL
3.Use the UP or DOWN ARROW to scroll through the numerals 0-9 until the desired number appears in the second HH field.
4.Press the ENTER button.
14 3A2960F
• A buzzer sounds
• The alarm LED illuminates
• The alarm output contact is closed
Page 15
Setup
To Clear Alarm Buzzer
Press RESET button to silence the buzzer.
To Clear Low Level Alarm
Resolve low level condition at low level sensor (i.e., fill the reservoir).
Press and hold RESET button for 3 seconds.
LL:02 - Paddle Sty le
This setting is intended for use with “paddle-style” low level sensors (such as the Graco G3 grease units).The pump stops when low level occurs . To ensure a low level condition has been met in this mode , 10 consecutiv e low level triggers must be detected. If a low level trigger is not detected in 30 seconds of run mode, the count is reset to zero.
When low level occurs:
• The pump stops
• The unit displays ER:LL
• A buzzer sounds
• The alarm LED illuminates
• The alarm output contact is closed
Press and hold RESET button for 3 seconds to clear the error.
LL:03 - Low Level Warning (Series F or later models only)
This setting configures the controller into low lev el warning mode. This mode is intended to operate with a standard, normally open, low level switch. This mode is also intended to operate with a low lev el switch that provides a persistent output.
The enters a low level condition after the switch input is closed for more than 1 second when the uni t is in the ON portion of the RUN MODE. The pump continues to operate.
When low level occurs:
• The unit periodically displays ER:LL (approximately 5 out of 10 seconds)
• A buzzer sounds
• The alarm LED illuminates
• The alarm output contact is closed
• The pump controller continues to operate normally
To Clear Alarm Buzzer
To Clear Alarm Buzzer
Press RESET button to silence the
buzzer. Press RESET button to silence the buzzer.
NOTE: The buzzer will sound again
after 4 hours if the low level condition
is not resolved. Buzzer will also sound again when
To Clear Low Level Alarm
power is cycled. Resolve low level condition at low level sensor (i.e., fill
the reservoir).
To Clear Low Level Alarm
Resolve low level condition at low level sensor (i.e., fill
the reservoir). To remove the low level condition from the
controller (Er:LL) the low level must be cleared for more
than 5 seconds.
3A2960F 15
Page 16

Operation

Operation

Run Mode

The controller is in Run Mode providing the following cir­cumstances are present:
•The controller is not in SETUP MODE.
•An Alarm is not active.
Pressure Mode: Pump ON
The display indicates the amount of backup time remaining (see Pressure Mode (on:Pr) ON setup, page
12).
•The Pressure ON LED illuminates and the pump output is enabled as long as the system is in the Pump ON state.
•If the pressure switch input is activated before the Backup Pump On Time expires, the system switches to a Pump OFF state.
•If the pressure switch is NOT activated before the Backup Pump On Time expires the system faults, goes to the Pump OFF state and pauses until the alarm is cleared.
•Pump ON time is shown in MM:SS (minutes:seconds)
Cycle Mode: Pump ON
The display alternates between the number of cycles remaining and indicates the amount of time remaining in the pump cycle, counting down the Backup Pump ON time value (see Cycle Mode (on:CY) ON Setup, page
12).
•The Cycle ON LED illuminates and the pump output is enabled as long as the system is in the Pump ON state.
•If the Input Cycle Switch is activated the amount of times equal to the Cycle Definition variable before the Backup Pump On Time expires, the system switches to a Pump OFF state.
•If the cycle switch is NOT activa ted the number of times equal to the cycle definition variable before the Backup Pump On Time expires the system faults, goes to the Pump OFF state and pauses until the Alarm is cleared.
•Pump ON time is shown in MM:SS (minutes:seconds)
Cycle Mode: Pump OFF
The display indicates the amount of time remaining in the pump OFF cycle, counting down the Pump OFF time value (see Programming OFF Time Duration, page 13).
Pressure Mode: Pump OFF
The display indicates the amount of time remaining in the pump OFF cycle, counting do wn the Pump OFF time value (see Programming OFF Time Duration, page 13).
•The pump output is disabled during the Pump OFF time.
•The Time OFF LED is illuminated as long as the sys­tem is in the Pump OFF state.
•Pump OFF time is shown in HH:MM (hours:minutes) or MM:SS if the time remaining is less than an hour.
16 3A2960F
•The pump output is disabled during the Pump OFF time.
•The Time OFF LED illuminates as long as the system is in the Pump OFF state.
•Pump OFF time is shown in HH:MM (hours:minutes) or MM:SS if the time remaining is less than an hour.
Timer Mode: Pump ON
The display indicates the amount of time remaining in the pump cycle, counting down th e Pump ON time valu e (see Time Control (on:ti) ON Setup, page 12).
•The Pump output is enabled.
•Pump ON time is shown in MM:SS (minutes:seconds).
Page 17
Timer Mode: Pump OFF
The display indicates the amount of time remaining in the pump OFF cycle, counting do wn the Pump OFF time value (see Programming OFF Time Duration, page 13).
•The Time OFF LED illuminates and the pump output is disabled during the Pump OFF time.
•Pump OFF time is shown in HH:MM (hours:minutes) or MM:SS if the time remaining is less than an hour.

Alarm Operation

When an alarm situation occurs:
•pump operation is immediately dis­abled,
•the front panel Alarm LED illuminates,
•an error code displays
Operation
•an audible alarm sounds
•the alarm output contact activates
Press the Reset button once to clear buzzer; press and hold f or 3 seconds to clear alarm and switch controller to OFF MODE.
See Alarm Types and Messages Table, page 18 for additional information related to alarms and alarm mes­sages.
3A2960F 17
Page 18
Operation
Alarm Types and Messages
Alarm Type Error Code Description Things to Check/Do
Refill lubrication reservoir.
Low Level Low lubricant level
Backup time e xpired prior to
Cycle
Pressure
receiving programmed number of cycle counts
Backup time e xpired prior to receiving pressure switch input.
If low lev el fault occurs une xpectedly v erify wiring and programming setup.
Inspect lubrication system for broken or plugged lines.
Confirm pump is operating correctly. Inspect wiring and switch. Confirm that sufficient backup time was
programmed f or environment conditions (e.g., slower system response in cold temperatures)
Verify programming. Inspect lubrication system for broken or plugged
lines. Confirm pump is operating correctly. Confirm vent valve is operating correctly. Inspect wiring and switch.
System Fault
Internal system error occurred.
Confirm that sufficient backup time was programmed f or environment conditions (e.g., slower system response in cold temperatures).
Verify programming. Cycle power.
If the system error persists the controller may need to be replaced.
18 3A2960F
Page 19

Advanced Programming (Series E or later models only)

9A 2A
P/C
+9V +30V
Advanced Programming (Series E or later models only)
The following Table Identifies each option and when it is used.
Advanced
Option Setting Format/ Description Why Use This?
A1 Lockout
Code (Optional)
A2 Pulsed Mode MM:SS (minutes:seconds) First,
A3 Auxiliary Out-
put Mode
Secures setup modes with PIN Prevents unauthorized users from adjusting set-
tings.
Pulsed Mode allows the user to program the set Pulse ON Time; then set Pulse OFF time
Enables alarm output as second­ary output dur i n g run mode.
pump cycle on and off during the normal run
mode.
Auxiliary Output Mode allows the user to operate
a second device, such as a solenoid, during the
normal run mode. When enabled, the output is
on for the entire duration of the ON cycle.
NOTE: When pulsed mode is enabled, the auxil-
iary output will remain enabled and will not pulse
during the Pump ON cycle. When not enabled,
alarm output will operate as an alarm output.
Entering Advanced Setup
1.Press the UP ARROW button for three sec­onds.
If a PIN Code is required, the unit will show four zeros.
2.The cursor is positioned to enter the first character of the PIN Code. Use the UP and DOWN ARROW buttons to move through the numbers 0-9 until the first number in the PIN code is displayed.
3.Press the ENTER button to set the num­ber. The cursor automatically moves to the next number field.
4.Repeat steps 2 and 3 for each PIN Code prompt field.
If the PIN Code you entered is correct, the unit will enter advanced setup mode.
Selecting Advanced Setup Options
1.Press the UP or DOWN ARROW button to move up or down through Advanced Options A1 - A3.
2.Press the ENTER button to set the selection.
A1 - Setting Up PIN Code
A PIN Code can be programmed into the GLC 2200 to protect the settings from inadv ertently being changed by unauthorized users.
Four zeros on the display lights, indicating you have entered the PIN Mode.
3A2960F 19
Page 20
Advanced Programming (Series E or later models only)
1.The word A1:OF appears in the display. Press the UP or DOWN ARR OW butt on to change this to A1:ON.
2.The cursor is automatically positioned to entered the first character of the PIN Code. Use the UP and DOWN ARR O W buttons to move up and down through the numbers 0-9 until the first number in the PIN code is dis­played in the field.
3.Press the ENTER button to set the num­ber. The cursor automatically moves to the next number field.
4.Repeat steps 2 and 3 for each PIN Code prompt field.
5.Press the ENTER button to set the PIN Code and exit Advanced Setup.
A2 - Pulsed Setup
Programs ON and OFF time in MM: SS (minutes and seconds) for pump operation during a normal pump on cycle.
1.The word A3:ON appears in the display. Press the UP or DOWN ARRO W b utton to cycle between A3:ON and A3:OF.
2.Press the ENTER button to save and exit setup.
•When the Auxiliary Output is
enabled, the output will remain powered during the Pump ON cycle whether or not the main pump output is pulsing.
•When the Auxiliary Output is not enabled (OFF) the
alarm output will operate as an alarm output.
1.To set the ON time use the UP or DOWN ARROW button to scroll through numerals 0 to 9 until the desired num­ber appears in the first MM (minutes) field.
2.Press the ENTER button to set the n u m­ber. The cursor automatically moves to the next number field.
3.Repeat Steps 1 and 2 until all MM:SS fields are pro­grammed.
4.Repeat Steps 1 - 3 to program the OFF time.
NOTE: If the pulse mode is enabled, the pump ON led will blink for the duration of the pulse ON time while the pump is on in Run Mode. The pump ON led will remain solid during the Run Mode for the dur ation of the pulse OFF time.
A3 - Auxiliary Output Setup
Allows the use of the alarm output dur i n g normal pump ON cycle.
20 3A2960F
Page 21

Troubleshooting

Description Problem Solution
Unit does not power on or display is dim/unresponsive
Pump is not running during Pump ON
Troubleshooting
Incorrect or loose wiring Input voltage is out of range Confirm power source is between 9
Tripped external fuse Confirm that none of the devices or
Incorrect or loose wiring Confirm current is being delivered to
Controller output is incorrect Confirm output voltage (PUMP+)
Refer to installation instructions beginning on page 4.
and 30 VDC.
wiring connected to the controller are causing a short circuit connection. Replace fuse.
the pump during pump ON. Refer to installation instructions, page 4. Ver­ify that your machine has been wired correctly.
from controller during pump ON is correct (should be similar to input voltage).
Air solenoid failure Replace air solenoid.
Reservoir quickly and unexpectedly runs out of grease
Test mode is engaged Turn off test mode.

Program Settings

Modes of Operation
Description
PROGRAMMING ON, page 12 Pressure, Cycle, Time PRESSURE CONTROL, page 12 MM:SS (00:01 - 59:59) CYCLE CONTROL Setup, page 12 Cycles = 01 - 99 BACKUP TIME Setup, 13 MM:SS (00:01 - 59:59) TIME CONTROL, page 12 MM:SS (00:01 - 59:59)
PUMP OFF Setup, page 14
LOW LEVEL, page 14 LL:01 = Default single activation
Maximum / Minimum and Additional Comments
Time Pump OFF Time: HH:MM (00:01 - 99:59)
NOTE: Measure at controller to ensure there is not wiring issue caus­ing the problem.
If controller output voltage is never present, the device may need replacement.
LL:02 = “Paddle Style” - 10 count activation
3A2960F 21
Page 22

Parts

1
3
4
2
Parts
Ref. Description Qty
1 BOX, enclosure 1 2 LABEL, control, overlay 1 3 LABEL, serial, name 1 4 LABEL, connector 1

Accessories

Related Kits

Kit No. Description
24P314 GLC2200 Wiring Harness Kit 24P686 Single Connector Kit 24P687 Multiple Connector Kit
22 3A2960F
Page 23

Technical Data

Technical Data
Input Contact
Power Source DC 9 - 30 VDC
Power Consumption 1 Watt
Cycle/Pressure Control Input (optional) 9 - 30 VDC, Normally open Pressure or cycle switch Lubrication level (optional) Normally open level switch, closes upon low level
Outputs
Pump control Pump Control Voltage = Power Source
Voltage Pump Control Voltage = Power Source Max Switching Voltage 30 VDC Max Switching Current 7A(DC), 9A (Peak) Min Switching Current 100 mA (DC)
Alarm, normally open
Voltage Alarm = Power Source Max Switching Voltage 30 VDC Max Switching Current 2A (DC)
Protection grade Alarm Sound Pressure Level Enclosure Material Membrane Material Maximum Humidity
Operating temperature range - 40°F to 176°F (- 40°C to 80°C) Storage Temperature - 40°F to 176°F (- 40°C to 80°C)
IP54 for indoors and vehicle cab use
75 dB
ABS
Polyester
90% RH (non-condensing)
3A2960F 23
Page 24

Dimensions

2.75 in. (70.0 mm)
5.53 in.
(140.0 mm)
1.38 in.
(35.0 mm)
1.57 in.
(40.0 mm)
4.92 in.
(125.0 mm)
2 x Ø
0.2 in. (5.0 mm)-

Dimensions Mounting Hole Layout

24 3A2960F
Page 25

Notes

Notes
3A2960F 25
Page 26

Graco Standard Warranty

Graco warrants all equipment referenced in this document which is manufactured by Graco and bearing its name to be free from defects in material and workmanship on the date of sale to the original purchaser for use. With the exception of any special, extended, or limited warranty published by Graco, Graco will, for a period of twelve months from the date of sale, repair or replace any part of the equipment determined by Graco to be defective. This warranty applies only when the equipment is installed, operated and maintained in accordance with Graco’s written recommendations.
This warranty does not cover, and Graco shall not be liable for general wear and tear, or any malfunction, damage or wear caused by faulty installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of non-Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility of Graco equipment with structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture, installation, operation or maintenance of structures, accessories, equipment or materials not supplied by Graco.
This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributor for verification of the claimed defect. If the claimed defect is verified, Graco will repair or replace free of charge any defective parts. The equipment will be returned to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material or workmanship, repairs will be made at a reasonable charge, which charges may include the costs of parts, labor, and transportation.
THIS WARRANTY IS EXCLUSIVE, AND IS IN LIEU OF ANY OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NO T LIMITED TO WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE.
Graco’s sole obligation and buyer’s sole remedy for any breach of warranty shall be as set forth above. The buyer agrees that no other remedy (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property, or any other incidental or consequential loss) shall be available. Any action for breach of warranty must be brought within two (2) years of the date of sale.
GRACO MAKES NO WARRANTY, AND DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, IN CONNECTION WITH ACCESSORIES, EQUIPMENT, MATERIALS OR COMPONENTS SOLD BUT NOT MANUFACTURED BY GRACO. These items sold, but not manufactured by Graco (such as electric motors, switches, hose, etc.), are subject to
the warranty, if any, of their manufacturer. Graco will provide purchaser with reasonable assistance in making any claim for breach of these warranties.
In no event will Graco be liable for indirect, incidental, special or consequential damages resulting from Graco supplying equipment hereunder, or the furnishing, performance, or use of any products or other goods sold hereto, whether due to a breach of contract, breach of warranty, the negligence of Graco, or otherwise.
FOR GRACO CANADA CUSTOMERS
The Parties acknowledge that they have required that the present document, as well as all documents, notices and legal proceedings entered into, given or instituted pursuant hereto or relating directly or indirectly hereto, be drawn up in English. Les parties reconnaissent avoir convenu que la rédaction du présente document sera en Anglais, ainsi que tous documents, avis et procédures judiciaires ex écutés, donnés ou intentés, à la suite de ou en rapport, directement ou indirectement, avec les procédures concernées.

Graco Information

TO PLACE AN ORDER, contact your Graco distributor or call to identify the nearest distributor.
Phone: 612-623-6928 or Toll Free: 1-800-533-9655, Fax: 612-378-3590
All written and visual data contained in this document reflects the latest product information available at the time of publication.
GRACO INC. AND SUBSIDIARIES • P.O. BOX 1441 • MINNEAPOLIS MN 55440-1441 • USA Copyright 2012, Graco Inc. All Graco manufacturing locations are registered to ISO 9001.
Graco reserves the right to make changes at any time without notice.
For patent information, see www.graco.com/patents.
Original instructions. This manual contains English. MM3A2960
Graco Headquarters: Minneapolis
International Offices: Belgium, China, Japan, Korea
www.graco.com
January 2016
Loading...