Installer: Affix all manuals adjacent to the unit.
(Type FSP CATEGORY IV Direct or Non Direct Vent Air Furnace)
These furnaces comply with requirements
embodied in the American National Standard / National Standard of Canada ANSI
Z21.47·CSA-2.3 Gas Fired Central Furnaces.
C
®
US
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to know the product better than the customer. This includes all safety
precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special attention to all safety
warnings. Often during installation or repair it is possible to place yourself in a position which is more hazardous than
when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to instruct a customer
in its safe use.
Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of specific good safety
practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices. However, if there is
a direct conflict between existing practices and the content of this manual, the precautions listed here take precedence.
NOTE: Please contact your distributor or our website
for the applicable Specification Sheet referred to in this manual.
IMPORTAN T NOTETOTHE OWNERREGARDING PRODUCT WARRANTY .................................................................................. 4
I. Component Identification ..................................................................................................................................... 5
II. Safety ....................................................................................................................................................................... 6
III. Product Application .............................................................................................................................................. 6
IV. Location Requirements & Considerations .................................................................................................... 7
V. Combustion & Ventilation Air Requirements .................................................................................................... 9
VI. Installation Positions ......................................................................................................................................... 11
VII. Horizontal Applications & Considerations .................................................................................................... 11
LTERNATE VENT/FLUEAND COMBUSTION AIR CONNECTIONS ......................................................................................... 11
A
LTERNATE ELECTRICALAND GAS LINE CONNECTIONS .................................................................................................. 12
A
RAIN PAN ............................................................................................................................................................. 12
VIII. Propane Gas /High Altitude Installations .................................................................................................... 12
IX. Vent/Flue Pipe & Combustion Air Pipe ........................................................................................................... 12
TANDARD RIGHTOR LEFT SIDE DRAIN HOSE CONNECTIONS ......................................................................................... 21
S
PRIGHT INSTALLATIONS-TRAPON LEFT SIDE ............................................................................................................... 23
XI. Electrical Connections ...................................................................................................................................... 26
OLT LINE CONNECTIONS ................................................................................................................................... 26
XII. Gas Supply and Piping ..................................................................................................................................... 28
AS PIPING CONNECTIONS ....................................................................................................................................... 28
G
ROPANE GAS TANKSAND PIPING ............................................................................................................................. 31
P
XIII. Circulating Air & Filters ................................................................................................................................... 31
UCTWORK - AIR FLOW ............................................................................................................................................ 31
AS SUPPL Y PRESSURE MEASUREMENT .................................................................................................................... 34
G
AS MANIFOLD PRESSURE MEASUREMENTAND ADJUSTMENT ....................................................................................... 35
G
AS INPUT RATE MEASUREMENT (NATURAL GAS ONLY) ............................................................................................... 35
XV. Normal Sequence of Operation ...................................................................................................................... 37
OWER UP ............................................................................................................................................................. 37
AN ONLY MODE .................................................................................................................................................... 38
F
XVI. Operational Checks ......................................................................................................................................... 38
NTEGRATED CONTROL MODULE ................................................................................................................................. 38
XVIII. Troubleshooting............................................................................................................................................. 39
ESETTING FROM LOCKOUT ...................................................................................................................................... 39
R
XIX. Maintenance ..................................................................................................................................................... 39
XX. Before Leaving an Installation ....................................................................................................................... 41
XXI. Repair & Replacement Parts .......................................................................................................................... 41
G
OODMAN WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY
DAMAGE ARISING FROM IMPROPER SERVI CE OR SERVICE PROCEDURES.
I
F YOU INSTALL OR PERFORM SERVICE ON THIS UNIT, YOU ASSUME
RESPONSIBILITY FOR ANY PERSONAL INJURY OR PROPERY DAM AGE WHICH
MAY RESULT.
SERVICE HEATING AND AIR CONDITIONING EQUIPMENT.
WARNING
M
ANY JURISDICTIONS REQUIRE A LICENSE TO INSTALL OR
3
WARN ING
IF
THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED
EXACTLY, A FIRE OR EXPLOSION MAY RESULT CAUSING PROPERTY
DAMAGE, PERSONAL INJURY OR LOSS OF LIFE
- D
O NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS
AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE
.
.
- WHAT T O D O IF YO U SMELL GA S:
* D
O NOT TRY TO LIGHT ANY APPLIANCE
* D
- I
NSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED
INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER
O NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE
ANY PHONE IN YOUR BUILDING
MMEDIATELY CALL YOUR GAS SUPPLIER FROM A
* I
NEIGHBORS PHONE
INSTRUCTIONS
F YOU CANNOT READCH YOUR GAS SUPPLIER, CALL THE
* I
FIRE DEPARTMENT
. F
OLLOW THE GAS SUPPLIERS
.
.
.
.
WARN ING
S
HOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT
OFF, TURN OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE
FURNACE BEFORE TURNING OFF THE ELECTRICAL SUPPLY
.
CARBON MONOXIDE POI SONING HAZARD
Special Warning for Installation of Furnace or Air Handling Units in
Enclosed Areas such as Garages, Utility Rooms or Parking Areas
Carbon monoxid e producing devices (such as an automobile, space
heater, gas water heater, etc.) should not be operated in enclosed areas
such as unventilated garages, utility roo ms or parking areas because of
the danger of carbon monoxide (CO) poisoning resulting from the exhaust
emissions. If a furnace or air handler is installed in an enclosed area such
as a garage, utility room or parking area and a carbon monoxide producing
device is operated therein, there must be adequate, direct outside
ventilation.
This ventilation is necessary to avoid the danger of CO poisoning which
can occur if a carbon monoxide producing device continues to operate in
the enclosed area. Carbon monoxide emissions can be (re)circulated
throughout the structure if the furnace or air handler is operating in any
mode.
CO can cause serious illness including permanent brain damage o r death.
B10259-216
-
TO THE INSTALLER
Before installing this unit, please read this manual thoroughly to
familiarize yourself with specific items which must be adhered to,
including but not limited to: unit maximum external static pressure,
gas pressures, BTU input rating, proper electrical connections, circulating air temperature rise, minimum or maximum CFM, and motor speed connections.
SHIPPING INSPECTION
All units are securely packed in shipping containers tested according to International Safe Transit Association specifications. The carton must be checked upon arrival for external damage. If damage is
found, a request for inspection by carrier’s agent must be made in
writing immediately .
The furnace must be carefully inspected on arrival for damage and
bolts or screws which may have come loose in transit. In the event
of damage the consignee should:
1. Make a notation on delivery receipt of any visible damage to
shipment or container.
2. Notify carrier promptly and request an inspection.
3. With concealed damage, carrier must be notified as soon as
possible - preferably within five days.
4. File the claim with the following support documents within a
nine month statute of limitations.
•Original or certified copy of the Bill of Lading, or indemnity
bond.
•Original paid freight bill or indemnity in lieu thereof.
•Original or certified copy of the invoice, showing trade and
other discounts or reductions.
•Copy of the inspection report issued by carrier’s
representative at the time damage is reported to carrier.
The carrier is responsible for making prompt inspection of damage
and for a thorough investigation of each claim. The distributor or
manufacturer will not accept claims from dealers for transportation
damage.
Keep this literature in a safe place for future reference.
IMPORTANT NOTETOTHE OWNERREGARDING PRODUCT WAR-
RANTY
Your warranty certificate is supplied as a separate document with
the unit installed by your contractor. Read the limited warranty certificate carefully to determine what is and is not covered and keep
the warranty certificate in a safe place. If you are unable to locate
the warranty certificate please contact your installing contractor or
contact customer service (877-254-4729) to obtain a copy.
To receive the Lifetime Heat Exchanger Limited Warranty (good for
as long as you own your home) and the 10-year Parts Limited
Warranty, online registration must be completed within 60 days of
installation. Online registration is not required in California or Quebec. Complete warranty details available from your local dealer or
at www.goodmanmfg.com.
T o register your Goodman® brand unit, go to www.goodmanmfg.com.
and click “Warranty Registration”. Complete registration as
prompted.
Product limited warranty certificates for models currently in production can be viewed at
currently in production or does not appear on the website, please
contact your installing contractor or contact customer service (877254-4729) to obtain a copy of your warranty certificate.
Each product overview page contains a Product Warranty link; by
clicking on it you will be able to view the limited warranty coverage
for that specific product. To view warranty registration information,
click on the Product Warranty text on the left navigation panel on the
home page of each website. The Online Product Registration pages
are located in this same section.
www.goodmanmfg.com. If your model is not
4
I. COMPONENT IDENTIFICATION
5
26
27
10
11
25
23
24
28
3
3
15
*
*
*
*
*
*
*
*
*
14
17
31
18
19
29
16
30
18
19
20
13
12
BLOWER COMPARTMENTBURNER COMPARTMENT
9
8
7
6
7
4
2
21
1
Upflow/HorizontalCounterflow/Horizontal
1Gas Valve
2Gas Line Entrance (Alternate)
3Pressure Switch
4Gas Manifold
5Combustion Air Intake Connection / “Coupling”
6Hot Surface Igniter
7Rollout Limit
8Burners
9Flame Sensor
10 Flue Pipe Connection / “Coupling”
11 Flue Pipe (Internal)
12 Primary Limit
13 Gas Line Entrance
14 Flue Pipe Connection (Alternate)
15 Rubber Elbow
16 Induced Draft Blower
17 Electrical Connection Inlets (Alternate)
18 Coil Front Cover Pressure Tap
19 Coil Front Cover Drain Port
20 Drain Line Penetrations
21 Drain Trap
22 Blower Door Interlock Switch
23 Capacitor
24 Integrated Control Module
Please adhere to the following warnings and cautions when installing, adjusting, altering, servicing, or operating the furnace.
WARN ING
TO
PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER
INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR
MAINTENANCE, REFER TO THIS MANUAL
ASSISTANCE OR INFORMATION, CONSULT A QUALIFIED INSTALLER
SERVICE AGENCY OR THE GAS SUPPLIER
. FOR
.
ADDITIONAL
,
WARN ING
T
HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS
WHICH MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE
KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH
DEFECTS OR OTHER REPRODUCTIVE HARM
.
WARN ING
HIGH VOLTAGE!
O AVOID PROPERTY DAMAGE, PERSONAL INJURY OR
T
DEATH DUE TO ELECTRICAL SHOCK, THE FURNACE MUST
BE LOCATED TO PROTECT THE ELECTRICAL
COMPONENTS FROM WATER
.
WARN ING
DO
NOT UTILIZE THE HEATING UNIT WITHOUT REASONABLE ROUTINE
INSPECTION, MAINTENANCE AND SUPERVISION
BUILDING THAT IS OR WILL BE VACANT, CARE SHOULD BE TAKEN TO
ROUTINELY INSPECT, MAINTAIN AND MONITOR THE UNIT
EVENT THAT THE BUILDING MAY BE EXPOSED TO FREEZING
TEMPERATURES AND WILL BE VACANT, DRAIN ALL WATER-BEARING
PIPES, PROPERLY WINTERIZE THE BUILDING, AND TURN OFF ALL
WATER SOURCES
FREEZING TEMPERATURES AND IS VACANT, ANY HYDRONIC COIL
UNITS SHOULD ALSO BE DRAINED AND AN ALTERNATIVE HEAT
SOURCES UTILIZED
. IN
THE EVENT THAT THE BUILDING IS EXPOSED TO
.
. IF
THE UNIT IS IN A
. IN
THE
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
NOTE: Discharge static electricity accumulated in the body before
touching the unit. An electrostatic discharge can adversely affect
electrical components.
Use the following precautions during furnace installation and servicing to protect the integrated control module from damage. By
putting the furnace, the control, and the person at the same electrostatic potential, these steps will help avoid exposing the integrated
control module to electrostatic discharge. This procedure is applicable to both installed and non-installed (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the
integrated control module or any wire connected to the control
prior to discharging your body’s electrostatic charge to
ground.
2. Firmly touch a clean, unpainted, metal surface of the
furnaces near the control. Any tools held in a person’s hand
during grounding will be discharged.
3. Service integrated control module or connecting wiring
following the discharge process in step 2. Use caution not
to recharge your body with static electricity; (i.e., do not move
or shuffle your feet, do not touch ungrounded objects, etc.).
If you come in contact with an ungrounded object, repeat
step 2 before touching control or wires.
4. Discharge your body to ground before removing a new
control from its container. Follow steps 1 through 3 if
installing the control on a furnace. Return any old or new
controls to their containers before touching any ungrounded
object.
III. PRODUCT APPLICA TION
This furnace is primarily designed for residential home-heating
applications. It is NOT designed or certified for use in mobile
homes, trailers or recreational vehicles. This unit is NOT designed
or certified for outdoor applications. The furnace must be installed
indoors (i.e., attic space, crawl space, or garage area provided the
garage area is enclosed with an operating door).
This furnace can be used in the following non-industrial commercial applications:
Schools, Office buildings, Churches, Retail stores
Nursing homes, Hotels/motels, Common or office areas
In such applications , the furnace must be installed with the following stipulations:
•It must be installed per the installation instructions
provided and per local and national codes.
•It must be installed indoors in a building constructed on
site.
•It must be part of a ducted system and not used in a free
air delivery application.
•It must not be used as a “make-up” air unit.
•It must be installed with two-pipe systems for combustion
air, especially if VOC’s or other contaminants are present
in the conditioned space.
•All other warranty exclusions and restrictions apply This
furnace is an ETL dual-certified appliance and is
appropriate for use with natural or propane gas (NOTE: If
using propane, a propane conversion kit is required).
Dual certification means that the combustion air inlet pipe is optional and the furnace can be vented as a:
Non-direct vent (single pipe) central forced air furnace in
which combustion air is taken from the installation area
or from air ducted from the outside or,
Direct vent (dual pipe) central forced air furnace in which
all combustion air supplied directly to the furnace burners
through a special air intake system outlined in these
instructions.
This furnace may be used as a construction site heater ONLY if the
following conditions are met:
•The vent system is permanently installed per these
installation instructions.
•A room thermostat is used to control the furnace. Fixed
jumpers that provide continuous heating CANNOT be
used.
•Return air ducts are provided and sealed to the furnace.
•A return air temperature range between 60ºF (16ºC) and
80ºF (27ºC) is maintained.
•Air filters are installed in the system and maintained
during construction, replaced as appropriate during
construction, and upon completion of construction are
replaced.
•The input rate and temperature rise are set per the furnace
rating plate.
6
•100% outside air is provided for combustion air
requirements during construction. Temporary ducting can
be used.
NOTE: Do not connect the temporary duct directly to the
furnace. The duct must be sized according to the
instructions under Section V, Combustion and Ventilation
air filters and evaporator coils are thoroughly cleaned
following final construction clean up.
•All furnace operating conditions (including ignition, input
rate, temperature rise and venting) are verified according
to these installation instructions.
NOTE: The Commonwealth of Massachusetts requires that the
following additional requirements must also be met:
•Gas furnaces must be installed by a licensed plumber or
gas fitter.
•A T-handle gas cock must be used.
•If the unit is to be installed in an attic, the passageway to
and the service area around the unit must have flooring.
To ensure proper installation and operation, thoroughly read this
manual for specifics pertaining to the installation and application
of this product.
WARN ING
P
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO
FIRE, EXPLOSION, SMOKE, SOOT, CONDENSATION, ELECTRICAL
SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER
INSTALLATION, REPAIR, OPERATION, OR MAINTENANCE OF THIS
PRODUCT
.
WARN ING
TO
PREVENT PERSONAL INJURY, PROPERTY DAMAGE OR DEATH DUE
TO FIRE, DO NOT INSTALL THIS FURNACE IN A MOBILE HOME
TRAILER OR RECREATIONAL VEHICLE
.
,
To ensure proper furnace operation, install, operate and maintain
the furnace in accordance with these installation and operation
instructions, all local building codes and ordinances. In their absence, follow the latest edition of the National Fuel Gas Code
(NFPA 54/ANSI Z223.1), and/or CAN/CSA B149.1-05.1-05 Installation Codes, local plumbing or waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI Z223.1) can
be obtained from any of the following:
American National Standards Institute
1430 Broadway
New York, NY 10018
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02269
CSA International
8501 East Pleasant Valley
Cleveland, OH 44131
A copy of the CAN/CSA B149.1-05.1-05 Installation Codes can also
be obtained from:
CSA International
178 Rexdale Boulevard
Etobicoke, Ontario, Canada M9W 1R3
The rated heating capacity of the furnace should be greater than or
equal to the total heat loss of the area to be heated. The total heat
loss should be calculated by an approved method or in accordance with “ASHRAE Guide” or “Manual J-Load Calculations” published by the Air Conditioning Contractors of America.
IV . LOCATION REQUIREMENTS & CONSIDERA TIONS
GENERAL
WARNING
TO
PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE
PERSONAL INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST
BE OBSERVED WHEN INSTALLING THE UNIT
Follow the instructions listed below when selecting a furnace location. Refer also to the guidelines provided in Section V, Combus-
tion and Ventilation Air Requirements.
•Centrally locate the furnace with respect to the proposed
or existing air distribution system.
•Ensure the temperature of the return air entering the
furnace is between 55°F and 100°F when the furnace is
heating.
•Provide provisions for venting combustion products
outdoors through a proper venting system. Special
consideration should be given to vent/flue pipe routing
and combustion air intake pipe when applicable. Refer
to Section IX, Vent/Flue Pipe and Combustion Air Pipe -Termination Locations for appropriate termination
locations and to determine if the piping system from
furnace to termination can be accomplished within the
guidelines given. NOTE: The length of flue and/or
combustion air piping can be a limiting factor in the
location of the furnace.
•Locate the furnace so condensate flows downwards to
the drain. Do not locate the furnace or its condensate
drainage system in any area subject to below freezing
temperatures without proper freeze protection. Refer to
Section X, Condensate Drain Lines and Trap for further
details.
•Ensure adequate combustion air is available for the
furnace. Improper or insufficient combustion air can
expose building occupants to gas combustion products
that could include carbon monoxide. Refer to Section V,
Combustion and Ventilation Air Requirements.
•Set the furnace on a level floor to enable proper
condensate drainage. If the floor becomes wet or damp
at times, place the furnace above the floor on a concrete
base sized approximately 1-1/2" larger than the base of
the furnace. Refer to the Section VII, HorizontalApplications and Considerations for leveling of horizontal
furnaces.
•Ensure upflow or horizontal furnaces are not installed
directly on carpeting, or any other combustible material.
The only combustible material allowed is wood.
•A special accessory subbase must be used for upright
counterflow unit installations over any combustible
material (including wood). Refer to subbase instructions
for installation details. (NOTE: A subbase will not be
required if an air conditioning coil is located beneath the
furnace between the supply air opening and the
combustible floor.
.
,
7
•Exposure to contaminated combustion air will result in
safety and performance-related problems. Do not install
the furnace where the combustion air is exposed to the
following substances:
chlorinated waxes or cleaners
chlorine-based swimming pool chemicals
water softening chemicals
deicing salts or chemicals
carbon tetrachloride
halogen type refrigerants
cleaning solutions (such as perchloroethylene)
printing inks
paint removers
varnishes
hydrochloric acid
cements and glues
antistatic fabric softeners for clothes dryers
and masonry acid washing materials
•Seal off a non-direct vent furnace if it is installed near an
area frequently contaminated by any of the above
substances. This protects the non-direct vent furnace
from airborne contaminants. To ensure that the
enclosed non-directvent furnace has an adequate supply
of combustion air, vent from a nearby uncontaminated
room or from outdoors. Refer to the Section V,Combustion and Ventilation Air Requirements for details.
•If the furnace is used in connection with a cooling unit,
install the furnace upstream or in parallel with the cooling
unit. Premature heat exchanger failure will result if the
cooling unit is placed ahead of the furnace.
•If the furnace is installed in a residential garage, position
the furnace so that the burners and ignition source are
located not less than 18 inches (457 mm) above the floor.
Protect the furnace from physical damage by vehicles.
•If the furnace is installed horizontally, the furnace access
doors must be vertical so that the burners fire horizontally
into the heat exchanger. Do not install the unit with the
access doors on the “up/top” or “down/bottom” side of
the furnace.
CLEARANCESAND ACCESSIBILITY
Installations must adhere to the clearances to combustible materials to which this furnace has been design certified. The minimum clearance information for this furnace is provided on the unit’s
clearance label. These clearances must be permanently maintained. Clearances must also accommodate an installation’s gas,
electrical, and drain trap and drain line connections. If the alternate
vent/flue connection is used, additional clearance must be provided to accommodate these connections. Refer to Section IX,Vent Flue Pipe and Combustion Air Pipe for details. NOTE: In
addition to the required clearances to combustible materials, a
minimum of 24 inches service clearance must be available in front
of the unit.
TOP
TOP
SIDESIDESIDE
BOTTOM
BOTTOM
UpflowCounterflowHorizontal
A furnace installed in a confined space (i.e., a closet or utility room)
must have two ventilation openings with a total minimum free area
of 0.25 square inches per 1,000 BTU/hr of furnace input rating.
Refer to the Specification Sheet applicable to your model for minimum clearances to combustible surfaces. One of the ventilation
openings must be within 12 inches of the top; the other opening
must be within 12 inches of the bottom of the confined space. In a
typical construction, the clearance between the door and door frame
is usually adequate to satisfy this ventilation requirement.
FURNACE SUSPENSION
If suspending the furnace from rafters or joists, use 3/8" threaded
rod and 2”x2”x1/8” angle iron as shown below. The length of rod
will depend on the application and the clearances necessary.
PROVIDE 8" MINMUM CLEARANCE BETWEEN
CENTER ROD AND FURNACE CABINET
TO ALLOW FOR CIRCULATOR BLOWER REMOVAL
3/8" DIAMETER
THREADED ROD
(6 PLACES)
HOLD DOWN
NUTS
SUPPORT
NUTS
2"X2"X1/8" ANGLE IRON
(3 PLACES)
POSITION AS CLOSE AS POSSIBLE
TO BLOWER DECK TO ALLOW FOR
CIRCULATOR BLOWER REMVOAL
ASSURE FURNACE IS LEVEL FROM
END TO END AND HAS A SLIGHT
FORWARD TILT WITH THE FRONT
OF THE FURNACE 0"-3/4"
BELOW THE BACK OF THE FURNACE
TILT OUTWARD TO ALLOW FOR
DOOR AND CIRCULATOR BLOWER
REMOVAL
Suspended Furnace
EXISTING FURNACE REMOVAL
NOTE: When an existing furnace is removed from a venting system
serving other appliances, the venting system may be too large to
properly vent the remaining attached appliances.
The following vent testing procedure is reproduced from the American
National Standard/National Standard of Canada for Gas-Fired Central Furnaces ANSI Z21.47-Latest Edition, CSA-2.3b--Latest Edition
Section 1.23.1.
The following steps shall be followed with each appliance connected to the
venting system placed in operation, while any other appliances connected
to the venting system are not in operation:
a. Seal any unused openings in the venting system;
b. Inspect the venting system for proper size and horizontal pitch, as
required by the National Fuel Gas Code, ANSI Z223.1 or the CSA
B149.1-05.1-05 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe condition;
c. In so far as practical, close all building doors and windows and all
doors between the space in which the appliance(s) connected to the
venting system are located and other spaces of the building. Turn on
clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom
exhausts, so they shall operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers;
d. Follow the lighting instructions. Place the appliance being inspected
in operation. Adjust thermostat so appliance shall operate continuously;
*NOTE: Please contact your distributor or our website for the applicable Specification Sheet referred to in this manual.
8
e. Test for draft hood equipped spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use the flame of a match
or candle;
f. After it has been determined that each appliance connected to the
venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other
gas burning appliance to their previous conditions of use;
g. If improper venting is observed during any of the above tests, the
common venting system must be corrected.
Corrections must be in accordance with the latest edition of the
National Fuel Gas Code NFP A 54/ANSI Z223.1 and/or CSA B149.1-
05.1-05 Installation Codes.
If resizing is required on any portion of the venting system, use the
appropriate table in Appendix G in the latest edition of the National
Fuel Gas Code ANSI Z223.1 and/or CSA B149.1-05.1-05 Installation Codes.
THERMOSTAT LOCATION
The thermostat should be placed approximately five feet from the
floor on a vibration-free, inside wall in an area having good air
circulation. Do not install the thermostat where it may be influenced by any of the following:
•Drafts, or dead spots behind doors, in corners, or under
cabinets.
•Hot or cold air from registers.
•Radiant heat from the sun.
•Light fixtures or other appliances.
•Radiant heat from a fireplace.
•Concealed hot or cold water pipes, or chimneys.
•Unconditioned areas behind the thermostat, such as an
outside wall.
DRAFTS OR DEAD SPOTS
-BEHIND DOORS
-IN CORNERS
-UNDER CABINETS
Thermostat Influences
Consult the instructions packaged with the thermostat for mounting instructions and further precautions.
V . COMBUSTION & VENTILA TION AIR REQUIREMENTS
WARNING
OSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH MAY OCCUR IF
P
THE FURNACE IS NOT PROVIDED WITH ENOUGH FRESH AIR FOR PROPER
COMBUSTION AND VENTILATION OF FLUE GASES. MOST HOMES REQUIRE
OUTSIDE AIR BE SUPPLIED TO THE FURNACE AREA.
Improved construction and additional insulation in buildings have
reduced heat loss by reducing air infiltration and escape around
doors and windows. These changes have helped in reducing
heating/cooling costs but have created a problem supplying com-
HOT
COLD
bustion and ventilation air for gas fired and other fuel burning appliances. Appliances that pull air out of the house (clothes dryers,
exhaust fans, fireplaces, etc.) increase the problem by starving
appliances for air.
House depressurization can cause back drafting or improper combustion of gas-fired appliances, thereby exposing building occupants to gas combustion products that could include carbon monoxide.
If this furnace is to be installed in the same space with other gas
appliances, such as a water heater, ensure there is an adequate
supply of combustion and ventilation air for the other appliances.
Refer to the latest edition of the National Fuel Gas Code NFPA 54/
ANSI Z223.1 (Section 5.3), or CSA B149.1-05 Installation Codes
(Sections 7.2, 7.3, or 7.4), or applicable provisions of the local
building codes for determining the combustion air requirements
for the appliances.
Most homes will require outside air be supplied to the furnace area
by means of ventilation grilles or ducts connecting directly to the
outdoors or spaces open to the outdoors such as attics or crawl
spaces.
The following information on air for combustion and ventilation is reproduced from the National Fuel Gas Code NFP A 54/ANSI Z223.1 Section
5.3.
5.3.1 General:
(a) The provisions of 5.3 apply to gas utilization equipment installed in
buildings and which require air for combustion, ventilation and dilution of flue gases from within the building. They do not apply to (1)
direct vent equipment which is constructed and installed so that all
air for combustion is obtained from the outside atmosphere and all
flue gases are discharged to the outside atmosphere, or (2) enclosed
furnaces which incorporate an integral total enclosure and use only
outside air for combustion and dilution of flue gases.
(b) Equipment shall be installed in a location in which the facilities for
ventilation permit satisfactory combustion of gas, proper venting
and the maintenance of ambient temperature at safe limits under
normal conditions of use. Equipment shall be located so as not to
interfere with proper circulation of air. When normal infiltration
does not provide the necessary air, outside air shall be introduced.
(c) In addition to air needed for combustion, process air shall be pro-
vided as required for: cooling of equipment or material, controlling
dew point, heating, drying, oxidation or dilution, safety exhaust,
odor control, and air for compressors.
(d) In addition to air needed for combustion, air shall be supplied for
ventilation, including all air required for comfort and proper working
conditions for personnel.
(e) While all forms of building construction cannot be covered in detail,
air for combustion, ventilation and dilution of flue gases for gas
utilization equipment vented by natural draft normally may be obtained by application of one of the methods covered in 5.3.3 and
5.3.4.
(f) Air requirements for the operation of exhaust fans, kitchen ventila-
tion systems, clothes dryers, and fireplaces shall be considered in
determining the adequacy of a space to provide combustion air
requirements.
5.3.2 Equipment Located in Unconfined Spaces:
In unconfined spaces (see definition below) in buildings, infiltration may
be adequate to provide air for combustion ventilation and dilution of
flue gases. However, in buildings of tight construction (for example,
weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in 5.3.3b or 5.3.4.
9
Space, Unconfined.
A
For purposes of this Code, a space whose volume is not less than 50
cubic feet per 1,000 BTU per hour of the aggregate input rating of all
appliances installed in that space. Rooms communicating directly with
the space in which the appliances are installed through openings not
furnished with doors, are considered a part of the unconfined space.
5.3.3 Equipment Located in Confined Spaces:
(a) All Air from Inside the Building: The confined space shall be pro-
vided with two permanent openings communicating directly with
an additional room(s) of sufficient volume so that the combined
volume of all spaces meets the criteria for an unconfined space. The
total input of all gas utilization equipment installed in the combined
space shall be considered in making this determination. Each opening shall have a minimum free area of 1 square inch per 1,000 BTU
per hour of the total input rating of all gas utilization equipment in
the confined space, but not less than 100 square inches. One opening shall be within 12 inches of the top and one within 12 inches of
the bottom of the enclosure.
NOTE: Each opening must have
a free area of not less than one
square inch per 1000 BTU of
the total input rating of all equipment in the en closure, but not
less than 100 square inches.
Chimney or Gas Vent
Opening
2. When communicating with the outdoors through vertical ducts,
each opening shall have a minimum free area of 1 square inch per
4,000 BTU per hour of total input rating of all equipment in the
enclosure.
Chimney o r Gas Vent
Ventilation louvers
(each end of attic)
NOTE: Th e inlet and ou tlet air
openings must each have a free
area of not less than one square
inch per 4000 BTU of the
total input rating of all equipment
in the enclosure.
Outlet A i r
Furnace
Water
Heater
Inlet air duct
[ends 1 ft (300 mm)
above floor]
Equipment Located in Confined Spaces; All Air from Outdoors
Through Ventilated Attic. See 5.3.3-b.
3. When communicating with the outdoors through horizontal ducts,
each opening shall have a minimum free area of 1 square inch per
2,000 BTU per hour of total input rating of all equipment in the
enclosure.
Chimney or Gas Vent
Water
Heater
Furnace
Opening
Equipment Located in Confined Spaces; All Air from Inside
Building. See 5.3.3-a.
(b) All Air from Outdoors: The confined space shall be provided with
two permanent openings, one commencing within 12 inches of the
top and one commencing within 12 inches of the bottom of the
enclosure. The openings shall communicate directly, or by ducts,
with the outdoors or spaces (crawl or attic) that freely communicate
with the outdoors.
1. When directly communicating with the outdoors, each opening
shall have a minimum free area of 1 square inch per 4,000 BTU
per hour of total input rating of all equipment in the enclosure.
Chimney or Gas Vent
Ventil ation louv ers
(each end of attic)
NOTE: Th e inlet and outlet ai r
openings must each have a free
area of not less than one square
inch per 4000 BTU of the
total inpu t rating of all equi pm e n t
in the enclosure.
Outlet Air
NOTE: The air duct openings
must have a free area of not
less than one square inch per
2000 BTU of the total input
rating of all equipment in the
Outlet air duct
Water
Heater
Furnace
Inlet air duct
*If the appliance room is located against an outside wall and the air openings communicate directly with the
outdoors, each opening shall have a free area of not less than one square inch per 4,000 BTU per hour of
the total input rating of all appliances in the enclosure.
enclosure*.
Equipment Located in Confined Spaces; All Air from Outdoors.
See 5.3.3-b.
4. When ducts are used, they shall be of the same cross-sectional
area as the free area of the openings to which they connect. The
minimum dimension of rectangular air ducts shall not be less
than 3 inches.
Water
Heater
lternate
air inlet
Furnace
Ventilation louvers for
unheated crawl space
Inlet Air
Equipment Located in Confined Spaces; All Air from Outdoors—
Inlet Air from Ventilated Crawl Space and Outlet Air to Ventilated
Attic. See 5.3.3-b
10
NOTE: The single opening must have
a free area of not less than o ne
square inch per 3000 BTU of
the total input rati ng of all equipment in the enclosure, but not less than
the sum of the areas of all vent
connectors in the confined space.
Chimney or Gas Vent
Water
Heater
Furnace
Opening
Alternate
Opening
Location
VII. HORIZONTAL APPLICA TIONS & CONSIDERATIONS
GENERAL
Horizontal applications, in particular, may dictate many of the
installation’s specifics such as airflow direction, ductwork connections, flue and combustion air pipe connections, etc. The basic
application of this furnace as a horizontal furnace differs only slightly
from an upright installation. When installing a furnace horizontally,
additional consideration must be given to the following:
LOCATION
Equipment Located in Confined Spaces; All Air from Outdoors -
Single Air Opening. See 5.3.3-b.
5. When directly communicating with the outdoors, the single opening shall have a minimum free area of 1 square inch per 3,000
BTU per hour of total input rating of all equipment in the enclosure.
5.3.4 Specially Engineered Installations:
The requirements of 5.3.3 shall not necessarily govern when special
engineering, approved by the authority having jurisdiction, provides an
adequate supply of air for combustion, ventilation, and dilution of flue
gases.
5.3.5 Louvers and Grilles:
In calculating free area in 5.3.3, consideration shall be given to the blocking effect of louvers, grilles or screens protecting openings. Screens used
shall not be smaller than 1/4 inch mesh. If the area through a design of
louver or grille is known, it should be used in calculating the size of
opening required to provide the free area specified. If the design and free
area is not known, it may be assumed that wood louvers will have 20-25
percent free area and metal louvers and grilles will have 60-75 percent
free area. Louvers and grilles shall be fixed in the open position or
interlocked with the equipment so that they are opened automatically
during equipment operation.
5.3.6 Special Conditions Created by Mechanical Exhausting or Fireplaces:
Operation of exhaust fans, ventilation systems, clothes dryers, or fireplaces may create conditions requiring special attention to avoid unsatisfactory operation of installed gas utilization equipment. Air from
Inside Building. See 5.3.3-a.
VI. INSTALLA TION POSITIONS
This furnace may be installed in an upright position or horizontal
on either the left or right side panel. Do not install this furnace on
its back. For upright upflow furnaces, return air ductwork may be
attached to the side panel(s) and/or basepan. For horizontal up-flow furnaces, return air ductwork must be attached to the basepan.
For both upright or horizontal counterflow furnaces, return ductwork must be attached to the basepan (top end of the blower compartment). NOTE:
Ductwork must never be attached to the back of
the furnace. For upflow installations requiring 1,800 CFM or more,
use either two side returns or a bottom return or a combination of
side and bottom. Contact your distributor for proper airflow requirements and number of required ductwork connections. Refer to
“Recommended Installation Positions” figure for appropriate installation positions, ductwork connections, and resulting airflow
arrangements.
Horizontal Furnace
DRAIN TRAPAND LINES
In horizontal applications the condensate drain trap is secured to
the furnace side panel, suspending it below the furnace. A minimum clearance of 4 3/4 inches below the furnace must be provided for the drain trap. Additionally, the appropriate downward
piping slope must be maintained from the drain trap to the drain
location. Refer to Section X, Condensate Drain Trap and Lines for
further details. If the drain trap and drain line will be exposed to
temperatures near or below freezing, adequate measures must
be taken to prevent condensate from freezing.
LEVELING
Leveling ensures proper condensate drainage from the heat exchanger and induced draft blower. For proper flue pipe drainage,
the furnace must be level lengthwise from end to end. The furnace
should also be level from back to front or have a slight tilt with the
access doors downhill (approximately 3/4 inches) from the back
panel. The slight tilt allows the heat exchanger condensate, generated in the recuperator coil, to flow forward to the recuperator coil
front cover.
ALTERNATE VENT/FLUEAND COMBUSTION AIR CONNECTIONS
In horizontal installations, provisions for alternate vent/flue piping
is available for upflow furnaces with left air discharge. Counterflow
furnaces include provisions for both alternate vent/flue and combustion air piping with right air discharge. These configurations
allow the flue and combustion air piping to be run vertically through
the furnace. Refer to the “Recommended Installation Positions”
figure for further detail. The standard piping connections may also
be used in these positions. Refer to Section IX, Vent/Flue Pipe
and Combustion Air Pipe for details concerning the conversion to
the alternate vent/flue air connections.
When using the horizontal alternate vent configuration, you must
use the RF000142 vent drain kit. See following illustration.
11
AIR
DISCHARGE
Side
Return
Duct
Connection
Connection
UPFLOW
UPRIGHT
AIR
DISCHARGE
UPFLOW HORIZONTAL
LEFT AIR DISCHARGE
Bottom
Return
Duct
Connection
UPFLOW HORIZO NTA L
RIGHT AIR DISCHARGE
Bottom
Return
Duct
ALTERNATE FLUE
PIPE LOCATION
ALTERNATE FLUE PIPE
LOCATION
Side
Return
Duct
Connection
Bottom
Return
Duct
Connection
AIR
DISCHARGE
Connection
COUNTERFLOW
UPRIGHT
Bottom
Return
Duct
Connection
COUNTERFLOW HORIZONTAL
RIGHT AIR DISCHARGE
AIR
DISCHARGE
COUNTERFLOW HORIZONTAL
LEFT AIR DISCHARGE
Bottom
Return
Duct
DISCHARGE
ALTERNATE FLUE AND
COMBUSTION AIR PIPE
LOCATIONS
AIR
ALTERNATE FLUE AND
COMBUSTION AIR PIPE
LOCATIONS
AIR
DISCHARGE
Bottom
Return
Duct
Connection
Recommended Installation Positions
NOTE: Alternate “vertical” piping connections can not be used when
an upflow furnace is installed with supply air discharging to the
right, or when a counterflow furnace is installed with supply air
discharging to the left. In either case, use the standard flue and
combustion air piping connections.
FURNACE SUSPENSION
If the furnace is installed in a crawl space it must be suspended
from the floor joist or supported by a concrete pad. Never install the
furnace on the ground or allow it to be exposed to water. Refer to
Section IV, Location Requirements and Considerations - Furnace
Suspension for further details.
VIII. PROPANE GAS /HIGH AL TITUDE INSTALLA TIONS
WARN ING
P
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MAY
OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED
APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER
FURNACE OPERATION
A QUALIFIED INSTALLER OR SERVICE AGENCY
. ALL
CONVERSIONS MUST BE PERFORMED BY
.
This furnace is shipped from the factory configured for natural gas
at standard altitude. Propane gas installations require an orifice
change to compensate for the energy content difference between
natural and propane gas.
High altitude installations may require both a pressure switch and
an orifice change. These changes are necessary to compensate
for the natural reduction in the density of both the gas fuel and the
combustion air at higher altitude.
For installations above 7000 feet, please refer to your distributor
for required kit(s).
GMH95, GCH95, GCH9 GAS ORIFICE CHART
AltitudeGasKitOrifice
Natural
None
0-7000
Propane
AltitudeGasKitOrifice
Natural
0-7000
Propane
1
LPM-0 5* supports White-Rodg ers 2-stage va lve only
2
LPM- 06* sup po r ts both Honey well and White-Rodgers 2-s tage val v es
In Canada, gas furnaces a r e certifi ed to 4500 feet.
NOTE:
LPM-05*
LPM-06*
GME95 GAS OR IFICE CHART
None
LPM-06*
#43
1
#55
2
#45
2
#55
Manifold
Pressure
3. 5" w.c .
10.0" w. c .
Manifold
Pressure
3.5" w .c.
10.0" w.c.
. THE
Pressure
Switch
None
Pressure
Switch
None
ALTERNATE ELECTRICALAND GAS LINE CONNECTIONS
This furnace has provisions allowing for electrical and gas line
connections through either side panel. In horizontal applications
the connections can be made either through the “top” or “bottom” of
the furnace.
DRAIN PAN
A drain pan must be provided if the furnace is installed above a
conditioned area. The drain pan must cover the entire area under
the furnace (and air conditioning coil if applicable).
FREEZE PROTECTION
Refer to Section VII, Horizontal Applications and Conditions - Drain
Trap and Lines.
Contact the distributor for a tabular listing of appropriate
manufacturer’s kits for propane gas and/or high altitude installations. The indicated kits must be used to insure safe and proper
furnace operation. All conversions must be performed by a qualified installer, or service agency.
IX. VENT/FLUE PIPE & COMBUSTION AIR PIPE
GENERAL
WARN ING
F
AILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN BODILY
INJURY OR DEATH
INSTRUCTIONS GIVEN IN THIS SECTION
12
. C
AREFULLY READ AND FOLLOW ALL
.
WARN ING
U
PON COMPLETION OF THE FURNACE INSTALLATION, CAREFULLY
INSPECT THE ENTIRE FLUE SYSTEM BOTH INSIDE AND OUTSIDE OF
THE FURNACE TO ASSURE IT IS PROPERLY SEALED
FLUE SYSTEM CAN RESULT IN SERIOUS PERSONAL INJURY OR DEATH
DUE TO EXPOSURE TO FLUE PRODUCTS, INCLUDING CARBON
MONOXIDE
.
. L
EAKS IN THE
A condensing gas furnace achieves its high level of efficiency by
extracting almost all of the heat from the products of combustion
and cooling them to the point where condensation takes place.
Because of the relatively low flue gas temperature and water condensation requirements, PVC pipe is used as venting material.
This furnace must not be connected to T ype B, BW, or L vent or vent
connector, and must not be vented into any portion of a factory built
or masonry chimney except when used as a pathway for PVC as
described later in this section. Never common vent this appliance
with another appliance or use a vent which is used by a solid fuel
appliance. Do not use commercially available “no hub connectors” other than those shipped with this product.
It is the responsibility of the installer to follow the manufacturers’
recommendations and to verify that all vent/flue piping and connectors are compatible with furnace flue products. Additionally, it
is the responsibility of the installer to ensure that all piping and
connections possess adequate structural integrity and support to
prevent flue pipe separation, shifting, or sagging during furnace
operation.
DUAL CERTIFICATION: NON-DIRECT/DIRECT VENT
This furnace is dual certified and may be installed as a non-direct
vent (single pipe) or direct vent (dual pipe) appliance. A non-directvent installation requires only a vent/flue pipe, while a direct vent
installation requires both a vent/flue pipe and a combustion air
intake pipe. Refer to the appropriate section for details concerning
piping size, length, number of elbows, furnace connections, and
terminations.
MATERIALSAND JOINING METHODS
WARN ING
TO
AVOID BODILY INJURY, FIRE OR EXPLOSION, SOLVENT CEMENTS
MUST BE KEPT AWAY FROM ALL IGNITION SOURCES (I.E
OPEN FLAMES, AND EXCESSIVE HEAT) AS THEY ARE COMBUSTIBLE
LIQUIDS
. A
SKIN AND/OR EYES
VOID BREATHING CEMENT VAPORS OR CONTACT WITH
.
., S
Two- or three-inch nominal diameter PVC Schedule 40 pipe meeting ASTM D1785, PVC primer meeting ASTM F656, and PVC solvent cement meeting ASTM D2564 specifications must be used.
Fittings must be DWV type fittings meeting ASTM D2665 and ASTM
D3311. Carefully follow the manufacturer’s instructions for cutting,
cleaning, and solvent cementing of PVC.
The use of Schedule 40 PVC Cellular Core (Foam Core) plastic
pipe is also acceptable as a flue/vent and intake pipe material. PVC
primer meeting ASTM F656 and PVC solvent cement meeting
ASTM D2564 specifications must be used. Fittings must be DWV
type fittings meeting ASTM D2665 and ASTM D3311. Carefully
follow the manufactures instructions for cutting, cleaning and
solvent cementing of PVC.
PARKS
,
As an alternative to PVC pipe, primer, solvent cement, and fittings,
ABS materials which are in compliance with the following specifications may be used. Two-or-three-inch ABS Schedule 40 pipe
must meet ASTM D1527 and, if used in Canada, must be CSA
listed. Solvent cement for ABS to ABS joints must meet ASTM
D2235 and, if used in Canada, must be CSA listed. The solvent
cement for the PVC to ABS transition joint must meet ASTM D3138.
Fittings must be DWV type fittings meeting ASTM D2661 and ASTM
D3311 and, if used in Canada, must be CSA listed. Carefully
follow the pipe manufacturers’ instructions for cutting, cleaning,
and solvent cementing PVC and/or ABS.
All 90° elbows must be medium radius (1/4 bend DWV) or long
radius (Long sweep 1/4 bend DWV) types conforming to ASTM
D3311. A medium radius (1/4 bend DWV) elbow measures 3 1/
16” minimum from the plane of one opening to the centerline of the
other opening for 2” diameter pipe, and 4 9/16” minimum for 3”
pipe.
PROPER VENT/FLUEAND COMBUSTION AIR PIPING PRACTICES
Adhere to these instructions to ensure safe and proper furnace
performance. The length, diameter, and number of elbows of the
vent/flue pipe and combustion air pipe (when applicable) affects
the performance of the furnace and must be carefully sized. All
piping must be installed in accordance with local codes and these
instructions.
Piping must be adequately secured and supported to prohibit sagging, joint separation, and/or detachment from the furnace. Horizontal runs of vent/flue piping must be supported every three to five
feet and must maintain a 1/4 inch per foot downward slope, back
towards the furnace, to properly return condensate to the furnace’s
drain system. Allowances should be made for minor expansion
and contraction due to temperature variations. For this reason,
particular care must be taken to secure piping when a long run is
followed by a short offset of less than 40 inches.
Precautions should be taken to prevent condensate from freezing inside the vent/flue pipe and/or at the vent/flue pipe termination. It is our recommendation that all vent/flue piping exposed to
temperatures below 35°F for extended periods of time should be
insulated with 1/2” thick closed cell foam. Also all vent/flue piping
exposed outdoors in excess of the terminations shown in this
manual (or in unheated areas) should be insulated with 1/2” thick
closed cell foam. Inspect piping for leaks prior to installing insulation.
13
V
X
v
DIRECT VENT TERMINAL CLEARANCES
A= Clearance above grade,
veranda, porch, deck or
balcony. (See 1.24.6-i(9)b.)
B= Clearance to window or
door that may be opened.
C= Clearance to permanently
closed window.
D= Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm)
from the center line of the terminal.
E= Clearance to unventilated s o ffit.**
F= Clearance to outside corner.**
G= Clearance to inside corner.**
H= Cleara nc e to each side of cen t er
line extended above meter/regulator
assembly.
Canadian Installations
12 in. (30 cm)12 in. (30 cm)
6 in. (15 cm) for appliances
10,000 Btuh (3 kW), 12 in. (30 cm) for
appliances > 10,000 Btuh (3 kW) and
100,000 Btuh (30 kW), 36 in. (91 cm)
for appliances > 100,000 Btuh (30
kW).
**
**
3 ft. (91 cm) within a height 15 ft.
(4.5 m) above the meter/r e g ul ator
assembly.
1
OTHER THAN DIRECT VENT TERMINAL CLEARANCES
A= Clearance above grade,
veranda , porch, deck or
balcony. (See 1.24.6-i(9)b.)
B= Clearance to window or
door that may be opened.
C= Clearance to permanently
closed window.
D= Vertical clearance to ventilated soffit
located above the terminal within a
horizontal distance of 2 feet (61 cm)
from the cente r line of the terminal.
E= Clearance to unventilated soffit.**
F= Clearance to outside corner.**
G= Clearance to inside corner.**
H= Clearance to each side of center
line extended above meter/regulator
assembly.
Canadian Installations
12 in. (30 cm)12 in. (30 cm)
6 in. (15 cm) for appliances
10,000 Btuh (3 kW), 12 in. (30 cm) for
appliances > 10,000 Btuh (3 kW) and
100,000 Btuh (30 kW), 36 in. (91 cm)
for appliances > 100,000 Btuh (30
kW).
**
**
3 ft. (91 cm) within a height 15 ft.
(4.5 m) above the meter/regulator
assembly.
1
U.S. Installa tions
6 in. (15 cm) for appliances
10,000 Btuh (3 kW), 9 in. (23 cm) for
appliances > 10,000 Btuh (3 kW) and
50,000 Btuh (15 kW), 12 in. (30 cm) for
appliances > 500,000 Btuh (15 kW).
*
U.S. Inst allations
4 ft. (1.2 m) belo w or to side of
opening; 1 ft. (300 m) above opening.
*
2
2
I= Clearance to servic e
regulator vent outlet.
J= Cle aran c e to non m ech anical air
supply inlet to building or the
combustion air inlet to any other
appliance.
K= Clearance to a mechanical
air supply inlet.
L= Clearanc e ab ove p aved sid ew alk or
paved driveway loca te d on pub lic
property.
M= Clearance under veranda, porch,
deck or balcony.
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
† A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single fanily dwellings and serves
both dwellings.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, the following statement shall be included:
“Clearance in accordance wtih local installation codes and the requirements of the gas supplier and the manufacturer’s installation
instruction.”
I= Cleara nc e t o sev ice
regulator vent outlet.
J= Clearance to nonmechanical air
supply inlet to building or the
combustion air inlet to any other
appliance.
K= Clearance to a mechanical
air supply inlet.
L= Clearance above paved sidewalk or
paved driveway located on public
property.
M= Clearance under veranda, porch,
deck or balcony.
1 In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
2 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
† A vent shall not terminate directly above a sidewalk or paveable driveway that is located between two single family dwellings and
serves both dwelling.
‡ Permitted only if veranda, porch, deck or balcony is fully open on a minimum of two sides beneath the floor.
* For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, the following statement shall be included:
“Clearance in accordance wtih local installation codes and the requirements of the gas supplier and the manufacturer’s installation
instruction.”
Canadian Installations
3 ft. (91 cm).*
6 in. (15 cm) for appliance s 10,000
Btuh (3 kW), 12 in. (30 cm) for
appliances > 10,0 00 Btu h (3k W) an d
100,000 Btuh (30 kW), 36 in. (91 cm)
for appliances > 100,000 Btuh (30 kW).
6 ft. (1.83 m)3 ft. (91 cm) above if within
7 ft. (2.13m) †*
12 in. (30 cm) ‡*
Canadian Installations
3 ft. (91 cm).*
6 in. (15 cm) for appliances 10,00 0
Btuh (3 kW), 12 in. (30 cm) for
appliances > 10,000 Btuh (3kW) and
100,000 Btuh (30 kW), 36 in. (91 cm)
for appliances > 100,000 Btuh (30 kW).
6 ft. (1.83 m)3 ft. (91 cm) above if within
7 ft. (2.13m) †7 ft. (2.13m)
12 in. (30 cm) ‡*
1
1
U.S. Installations
6 in. (15 cm) for applianc es 10,000
Btuh (3 kW), 9 in. (23 cm) fo r
appliances > 10,000 Btuh (3kW) and
50,000 Btuh (15 kW), 12 in. (30 cm) for
appliances > 50,000 Btuh (15 kW).
10 ft. (3 m) horizontally.
U.S. Installations
4 ft. (1.2 m) below or to side of
opening; 1 ft. (300 m) above opening.
10 ft. (3 m) horizontally.
2
2
14
TERMINATION LOCATIONS
NOTES: Refer to Section IV, Location Requirements and
Considerations for combustion air contaminant restrictions.
The following bullets and diagram describe the restrictions con-
cerning the appropriate location of vent/flue pipe and combustion
air intake pipe (when applicable) terminations. Refer to Non-Di-rect Vent (Single Pipe) Piping and Direct Vent (Dual Pipe) Piping
located in this section for specific details on termination construction.
•All terminations (flue and/or intake) must be located at
least 12 inches above ground level or the anticipated
snow level.
•Vent terminations (non-direct and direct vent) must
terminate at least 3 feet above any forced air inlet located
within 10 feet.
NOTE: This provision does not apply to the combustion
air intake termination of a direct vent application.
•The vent termination of a non-direct vent application must
terminate at least 4 feet below, 4 feet horizont ally from, or
1 foot above any door, window, or gravity air inlet into any
building.
•The vent termination of a direct vent application must
terminate at least 12 inches from any opening through
which flue gases may enter a building (door, window, or
gravity air inlet).
•The vent termination of vent pipe run vertically through a
roof must terminate at least 12 inches above the roof line
(or the anticipated snow level) and be at least 12 inches
from any vertical wall (including any anticipated snow
build up).
•A vent termination shall not terminate over public walkways
or over an area where condensate or vapor could create
a nuisance or hazard or could be detrimental to the
operation of regulators, relief valves, or other equipment.
•The combustion air intake termination of a direct vent
application should not terminate in an area which is
frequently dusty or dirty.
VENT/FLUE PIPE
Vent/flue pipe can be secured to the vent/flue coupling using the
rubber coupling and worm gear hose clamps provided with this
furnace (see “Standard Connections” figure). The rubber coupling
allows separation of the vent/flue pipe from the furnace during
servicing. Combustion Air and Vent piping should be routed in a
manner to avoid contact with refrigerant lines, metering devices,
condensate drain lines, etc. If necessary, clearances may be
increased by utilizing two 45 deg. Long-Sweep Elbows and creating an “S” joint to provide additional space at connection locations. This joint can be rotated on the fitting to establish maximum clearance between refrigerant lines, metering devices, and
condensate drain lines, etc. This joint is the equivalent of one 90
deg. elbow when considering elbow count.
V
E
N
T
45 DEGREE
LONG-SWEEP
ELBOWS
Increased Clearance Configuration
NOTE: Do not use other commercially available “no hub connec-
tors” due to possible material conflicts. The vent/flue pipe can
also be secured using a PVC or ABS elbow or coupling using the
appropriate glue (see Section IX, Materials and Joining Methods).
NOTE: In Canada, the Canadian Fuel Gas Code takes precedence
over the preceding termination restrictions.
CANADIAN VENTING REQUIREMENTS
In Canada, venting must conform to the requirements of the current CAN/CSA-B149.1-05 Installation Code. Use only CSA-listed,
ULC-S636 compliant two- or three-inch diameter PVC or ABS pipe,
solvent cement, and fittings throughout. The certified piping should
be clearly marked with the ULC St d “S636” on the pipe and fittings.
Carefully follow the pipe manufacturers’ instructions for cutting,
cleaning, and solvent cementing PVC and/or ABS.
The vent can be run through an existing unused chimney provided
the space between the vent pipe and the chimney is insulated and
closed with a weather-tight, corrosion-resistant flashing.
STANDARD FURNACE CONNECTIONS
It is the responsibility of the installer to ensure that the piping
connections to the furnace are secure, airtight, and adequately
supported.
As shipped, attachment “couplings” for vent/flue and combustion
air intake pipe connections are provided on the furnace’s top cover
(upflow) or basepan (counterflow). To use the standard connections, field supplied vent/flue pipe and combustion air intake pipe
(when applicable) should be secured directly to the furnace at
these locations.
NOTE: For non-direct vent installations, a minimum of one 90°
elbow should be installed on the combustion air intake coupling
to guard against inadvertent blockage.
COMBUSTION AIR PIPE
DIRECT VENT I NSTALLATIONS
On upflow units secure the combustion air intake pipe directly to
the air intake coupling. On counterflow units secure the combustion air intake pipe to the air intake coupling using the rubber coupling and worm gear hose clamps provided with the unit. The
counterflow rubber coupling allows service removal of air intake
piping internal to the furnace blower compartment. NOTE: Because of probable material conflicts, do not use other commercially available “no hub connectors”. The combustion air intake
pipe can also be secured directly to the counterflow unit air intake
pipe coupling.
NON-DIRECT VENT INSTALLATIONS
A minimum of one 90° elbow should be installed on the combustion air intake “coupling” to guard against inadvertent blockage.
15
(DIRECT VEN T ONLY)
90º PVC
ELBOW
(NON-DIREC T VENT)
90º PVC
ELBOW
COMBUSTION
AIR PIPE
(DIRECT VEN T ONLY)
OR
COMBUSTION
AIR PIPE
OR
VENT/FLUE
PIPE
RUBBER
COUPLING
WITH WORM
GEAR CLAMPS
UPFLOW COUNTERFLOW
(NON-DIR ECT VENT)
RUBBER
COUPLIN GS
WITH WORM
GEAR CLAMPS
VENT/FLUE
PIPE
STANDARD CONNECTIONS
Counterflow units.
Cut the vent/flue pipe 3.75 inches from the blower deck
coupling. See Vent/Flue Pipe Cuts figure. Save vent/flue pipe
attached to blower deck coupling for use in the alternate
location. Discard remaining pipe and elbows.
FLANGE
3.75"
CUTHERE
ALTERNATE FURNACE CONNECTIONS
If the standard locations are undesirable for a specific installation,
alternate side panel locations are available on the upflow models
for the vent/flue. Counterflow furnaces include provisions for both
alternate vent/flue and combustion air piping. These locations may
be of particular benefit to upright upflow installations requiring additional access to an A coil, or to upright counterflow installations
requiring additional access to a filter or electronic air cleaner, or to
horizontal installations desiring vent/flue (upflow and counterflow)
and combustion air intake (counterflow only) piping run vertically
from the side of the cabinet.
NOTE: Standard and alternate locations can be combined (i.e., an
installation may use the standard combustion air intake location
but use the alternate vent/flue location), if needed.
WARN ING
E
DGES OF SHEET METAL HOLES MAY BE SHARP
PRECAUTION WHEN REMOVING HOLE PLUGS
ALTERNATE VENT/FLUE LOCATION
The alternate vent/flue location is the large hole directly in line with
the induced draft blower outlet. To use the alternate vent/flue location refer to the following steps, the “Vent/Flue Pipe Cuts” figure,
and the “Alternate Vent/Flue Location” figure.
NOTE: Counterflow instructions follow the upflow instructions.
1. Remove and save the four screws securing the vent/flue
coupling to the furnace top panel.
Counterflow units.
1. Remove and save the four screws securing the vent/flue
coupling to the furnace basepan. Also remove the three
screws securing the furnace’s internal vent/flue piping to
the blower deck.
2. Upflow and Counterflow units.
Loosen the worm gear hose clamps on the rubber elbow
and detach it from both the induced draft blower and the
vent/flue pipe.
3. Upflow and Counterflow units.
Remove the vent/flue pipe from the furnace.
4. Cut the vent/flue pipe 3.75 inches from the flanged end of
the pipe. See Vent/Flue Pipe Cuts figure. The section of
pipe attached to the coupling will reach through the side
panel to the induced draft blower. Discard remaining pipe
and elbows.
.
. USE
GLOVES AS A
5. Remove plastic plug from alternate vent/flue location.
Vent/Flue Pipe Cuts
Relocate and install plug in standard vent/flue location (top
cover).
Counterflow units.
Remove plastic plug from alternate vent/flue location.
Relocate and install plug in standard vent/flue location
(basepan). Plug remaining hole in blower deck with plastic
plug included in the drain kit bag.
6. Upflow and Counterflow units.
Insert cut section of vent/flue pipe and coupling into alternate
vent/flue location. Using a rubber coupling and worm gear
hose clamps from the drain kit bag, attach the vent/flue pipe
and coupling to the induced draft blower. Secure the
coupling to the cabinet using the screws removed in step 1
or with field-supplied 3/8” #8 self drilling screws.
WARN ING
THE
RUBBER ELBOW IS NOT DESIGNED TO SUPPORT A LOAD
THE RUBBER ELBOW IS MOUNTED EXTERNALLY TO THE FURNACE
CABINET, EXTREME CARE MUST BE TAKEN TO ADEQUATELY SUPPORT
FIELD-SUPPLIED VENT/FLUE PIPING, AS DAMAGE CAN RESULT IN
LEAKS CAUSING BODILY INJURY OR DEATH DUE TO EXPOSURE TO
FLUE GASES, INCLUDING CARBON MONOXIDE
.
7. Upflow and Counterflow units.
For upright installations, externally mount the rubber elbow
to the vent/flue coupling using a worm gear hose clamp.
Secure field supplied vent/flue piping to the rubber elbow
using a worm gear hose clamp. NOTE: Use of the alternate
vent/flue location for upright installations, requires the drain
trap be installed on the same side of the unit as the flue
pipe.
8. Upflow and Counterflow units.
For horizontal installations, externally secure the field-
supplied vent/flue pipe directly to the vent/flue coupling using
a PVC or ABS coupling or elbow.
. W
HEN
16
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.