Goodman AVPTC183014, AVPTC313714, AVPTC426014 Installation Manual

Page 1
AVPTC
AIR HANDLER INSTALLATION INSTRUCTIONS
© 2011 - 2012 Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www.goodmanmfg.com -or- www.amana-hac.com P/N: IO-346D Date: September 2012
THIS PRODUCT CONTAINS ELECTRONIC COMPONENTS WHICH REQUIRE A DEFINITE GROUND. PROVISIONS ARE MADE FOR CONNECTION OF THE GROUND. A DEDICATED GROUND FROM THE MAIN POWER SUPPLY OR AN EARTH GROUND MUST BE PROVIDED.
NOTICE
IFA“1F
ENCOUNTEREDONSTARTUP,VERIFYTHATTHEELECTRICHEATER
SWITCHESHAVEBEENSETTOTHEAPPROPRIATEHEATERSIZE
PAGES
AIRFLOWDELIVERY
I
NTRODUCTION
This booklet contains the installation and operating instruc­tions for your air handler. All warnings and precautions within this booklet must be observed. Improper installation can re­sult in unsatisfactory operation or dangerous conditions and void the warranty. Read this booklet and any instructions packaged with accessories prior to installation. Give this book­let to the user and explain its provisions. The user should retain this booklet for future reference.
NOTE: Upon start up in communicating mode the circuit board
will display a “1 Flash” error code on the diagnostic LED and an “Ec” HTR TO LARGE error at the communicating display. This is an indication that the dip switches on the control board need to be configured in accordance with the Electric Heat­ing Airflow Table on page 13 of this manual. Configuring the dip switches and resetting power to the unit will clear the error code.
LASH”ERRORCODEORAN
12
AND
13
FORTHE
DIP
.
“EC”HTRTOOLARGE
ERRORIS
DIP
.SEE
SWITCHSETTINGSANDHEATERKIT
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
NOTE: Discharge body’s static electricity before touching unit. An electrostatic discharge can adversely affect electrical components.
Use the following precautions during modular blower instal­lation and servicing to protect the integrated control module from damage. By putting the modular blower, the control, and the person at the same electrostatic potential, these steps will help avoid exposing the integrated control module to elec­trostatic discharge. This procedure is applicable to both in­stalled and uninstalled (ungrounded) blowers.
1. Disconnect all power to the blower. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.
2. Firmly touch a clean, unpainted, metal surface of the modular blower near the control. Any tools held in a person’s hand during grounding will be discharged.
3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a blower. Return any old or new controls to their containers before touching any ungrounded object.
IMPORTANT NOTE TO THE OWNER REGARDING PRODUCT WARRANTY
Your warranty certificate is supplied as a separate document with the unit installed by your contractor. Read the limited warranty certificate carefully to determine what is and is not covered and keep the warranty certificate in a safe place. If you are unable to locate the warranty certificate please con­tact your installing contractor or contact customer service (877-254-4729) to obtain a copy.
IMPORTANT: To register your Goodman
www.goodmanmfg.com and click “Warranty Registration”. Complete registration as prompted.
To register your Amana® brand unit, go to www.amana­hac.com and click “Warranty Registration”. Complete regis­tration as prompted.
Product limited warranty certificates for models currently in production can be viewed at www.goodmanmfg.com or www.amana-hac.com. If your model is not currently in pro­duction or does not appear on the website, please contact your installing contractor or contact customer service (877­254-4729) to obtain a copy of your warranty certificate.
Each product overview page contains a Product Warranty link; by clicking on it you will be able to view the limited war­ranty coverage for that specific product. To view warranty registration information, click on the Product Warranty text on the left navigation panel on the home page of each web­site. The Online Product Registration pages are located in this same section.
®
brand unit, go to
Page 2
C
HECKING PRODUCT RECEIVED
Upon receiving the unit, inspect it for damage from ship­ment. Claims for damage, either shipping or concealed, should be filed immediately with the shipping company. Check the unit model number, specifications, electrical char­acteristics and accessories to determine if they are correct. In the event an incorrect unit is shipped, it must be returned to the supplier and must NOT be installed. The manufac­turer assumes no responsibility for installation of incorrectly shipped units.
R
EPLACEMENT PARTS
ORDERING PARTS
When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate.
Replacement parts for this appliance are available through your contractor or local distributor. For the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact:
CONSUMER AFFAIRS
GOODMAN MANUFACTURING COMPANY, L.P.
7401 SECURITY WAY
HOUSTON, TEXAS 77040
877-254-4729
I
MPORTANT SAFETY INSTRUCTIONS
To avoid property damage, personal injury or death due to electrical shock, this unit MUST have an uni nt e r r u pted, un brok e n electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel. Othe r me th o ds of groundi ng are permi t te d i f pe r fo rm ed in accordance with the National Electric Code (NEC)/Amer ican Natio nal Standards Inst itute (ANSI)/Nati onal Fire Protec tion A ssocia tion (NFPA) 70 and local/state codes. In Canada, electrical grounding is to be in ac corda n ce with t h e Canadia n El ectri c Code (CSA) C22.1.
This product is factor y-shipped for use with 208/240/1/60 elec tric al pow er supp ly. reconfigure th is ai r handler to operate with any other power supply.
When installing or servicing this equipment, safety clothing, inc lu ding hand and eye protection, is strongly reco mmended. If installing in an area that has special safety requirements (hard hats, etc.), observe these req uirements.
elec trical ground. The
DO NOT
RECOGNIZE SAFETY SYMBOLS, WORDS, AND LABELS
The following symbols and labels are used throughout this manual to indicate immediate or potential hazards. It is the owner’s responsibility to read and comply with all safety in­formation and instructions accompanying these symbols. Failure to heed safety information increases the risk of prop­erty damage, product damage, personal injury or death.
WARNING
HIGHVOLTAGE!
D
ISCONNECT
ULTIPLEPOWERSOURCESMAYBEPRESENT
M
TODOSOMAYCAUSEPROPERTYDAMAGE,PERSONAL
INJURYORDEATH
ONLY
ECHNICIAN
T
ONDITIONING
C
USETHISINFORMATION
WITHOUTSUCHBACKGROUNDMAYRESULTINPRODUCTDAMAGE
PERSONALINJURY,ORDEATH
ALL
POWERBEFORESERVICING
.
.F
AILURE
.
WARNING
INDIVIDUALSMEETINGTHEREQUIREMENTSOFAN
”,ATA
MINIMUM,ASSPECIFIEDBYTHEAIR
,H
EATINGANDREFRIGERATIONINSTITUTE
.A
TTEMPTINGTOINSTALLORREPA IRTHISUNIT
.
“E
(AHRI)
NTRYLEVEL
MAY
,
Do not connect to or use a ny dev ice that i s not design­certified by Goodman for use with this unit. Serious property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the use of such non-ap proved devices.
To prevent the risk of p roperty d amage, personal injury, or death, do not stor e co mbustible materials or use gasoline or other f lammable liquids or vapors in the vicinity of this un it.
 
2
Page 3
CARBON MONOX IDE POISON ING HAZ ARD
Special Warning for Installation of Furnace or Air Handling Units in Enclosed Areas such as Garages, Utility Rooms or Parking Areas
Carbon monoxide producing devices (such as an automobile, space heater, gas water heater, etc.) should not be operated in enclosed areas such as unventilated garages, utility rooms or parking areas because of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility room or parking area and a carbon monoxide producing device is operated therein, there must be adequate, direct outside ventilation.
This ventilation is necessary to avoid the danger of CO poisoning which can occur if a carbon monoxide producing device continues to operate in the enclosed area. Carbon monoxide emissions can be (re)circulated throughout the structure if the furnace or air handler is operating in any mode.
CO can cause serious illness including permanent brain damage or death.
C
ODES
& R
EGULATIONS
B10259-216
-
This product is designed and manufactured to comply with national codes. Installation in accordance with such codes and/or prevailing local codes/regulations is the responsibil­ity of the installer. The manufacturer assumes no responsi­bility for equipment installed in violation of any codes or regu­lations.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the in­troduction and disposal of refrigerants. Failure to fol­low these regulations may harm the environment and can lead to the imposition of substantial fines. Should
you have any questions please contact the local office of the EPA.
If replacing an air handler, the system must be manufac­turer approved and Air Conditioning, Heating and Refrigera-
tion Institute (AHRI) matched. NOTE: Installation of un-
matched systems is strongly discouraged.
F
EATURES
This air handler is a part of the ComfortNet™ family of prod­ucts. It may be installed as part of a “non-communicating” system using a standard 24 VAC thermostat. However, with the CTK0*AA ComfortNet thermostat kit, this air handler may be installed as part of a digitally communicating system. The ComfortNet system provides automatic airflow configuration, enhanced setup features, and enhanced diagnostics. It also reduces the number of thermostat wires to a maximum of four and a minimum of two.
PRE-I
NSTALLATION INSTRUCTIONS
Carefully read all instructions for the installation prior to in­stalling product. Make sure each step or procedure is un­derstood and any special considerations are taken into ac­count before starting installation. Assemble all tools, hard­ware and supplies needed to complete the installation. Some items may need to be purchased locally. Make sure every­thing needed to install the product is on hand before start­ing.
L
OCATION
NOTE: Air handlers are designed for indoor installation only.
Give special consideration to minimizing the length of refrig­erant tubing when installing air handlers. Refer to Remote Cooling/Heat Pump Service Manual TP-107 Long Line Set Application R-410A for guidelines. The unit clearance from a combustible surface may be 0". However, service clear­ance is to take precedence. In addition allow a minimum of 24" in front of the unit for service clearance.
If the unit is located in an area with high ambient tempera­ture and/or high humidity, the air handler may be subject to nuisance sweating of the casing. On these installations, a wrap of 2” fiberglass insulation with a vapor barrier is rec­ommended.
Do not install the air handler in a location that violates the instructions provided with the condenser.
Consult all appropriate regulatory codes prior to determin­ing final clearances. When installing this unit in an area that may become wet, elevate the unit with a sturdy, non-porous material. In installations that may lead to physical damage (i.e. a garage) it is advised to install a protective barrier to prevent such damage.
D
UCTWORK
This air handler is designed for a complete supply and re­turn ductwork system.
Do not operate this pro duct without all the duct work attached.
To ensure correct system performance, the ductwork is to be sized to accommodate 375-425 CFM per ton of cooling with the static pressure not to exceed .5" WC. Inadequate duct work that restricts airflow can result in improper perfor­mance and compressor or heater failure. Ductwork is to be constructed in a manner that limits restrictions and main­tains suitable air velocity. Ductwork is to be sealed to the unit in a manner that will prevent leakage.
RETURN DUCTWORK
DO NOT TERMINATE THE RETURN DUCTWORK IN AN AREA THAT CAN INTRODUCE TOXIC, OR OBJECTION­ABLE FUMES/ODORS INTO THE DUCTWORK. The re­turn ductwork is to be introduced into the air handler bottom (upflow configuration).
3
Page 4
RETURN AIR FILTERS
Each installation must include a return air filter. This filtering may be performed at the air handler or externally such as a return air filter grille. Air handlers mounted in the downflow orientation, including “B” series, require external filtering. A washable filter is available as an accessory. To ensure opti­mum performance frequent filter cleaning is advised. Refer
to Air Filter Accessory table for the appropriate filter.
AVPTC Filter Number Qty Required
1830
3137 4260
E
LECTRIC HEAT
Refer to this manual in combination with the instructions pro­vided with the heat kit for the correct installation procedure.
The air handlers listed in this manual do not have factory installed electric heat. Electric heat is available as an ac-
cessory. If installing this option, the ONLY heat kits that can
be used are the HKR series.
NOTE: The Amana are NOT approved for use with these air handlers.
FIL 36-42
(19" x 21")
FIL 48-61
(21-1/2" x 23")
Air Filter Accessories
®
brand EHK, ECB, EDB, and EDK kits
1
1
HKR INSTALLATION
Follow instructions listed in Installation and Operating Instruc­tions shipped with the heat kit.
E
LECTRICAL SUPPLY WIRE AND
FIRE HAZARD! To avoid the risk of property damage, personal injury or fire, use only copper conductors.
MOP
HIGH VOLTAGE! T o avoid prope rty dama ge , persona l injury or death due to el ect rical shock, th is u ni t MU S T have an uninterrupted, unbroken electrical ground circuit may consist of an appro pri at ely sized elec tr ical wi re co nnecting the ground lug in the unit control box to the building electrical service panel. Other methods of grounding are permit ted if perform ed in accordance with the National Electric Code (NEC) /Americ an Nation al Standar ds Institut e (ANSI)/National Fire Protection Association (NFP A) 70 and local/state codes. In Canada, electrical grounding is to be in ac co rda nce w ith th e C ana dian Elec tric Cod e (CSA) C22.1.
electrical ground. The
BUILDING ELECTRICAL SERVICE INSPECTION
This unit is designed for single-phase electrical supply. DO NOT OPERATE ON A THREE-PHASE POWER SUPPLY. Measure the power supply to the unit. The supply voltage
must be in agreement with the unit nameplate power re-
quirements and within the range specified below.
Power Supply V oltage
Nominal Input Minimum Voltage Maximum Voltage
208/240 187 253
WIRE SIZING
Wire size is important to the operation of your equipment. Use the following check list when selecting the appropriate wire size for your unit.
Wire size must carry the Minimum Circuit Ampac-
ity (MCA).
Refer to the NEC (USA) or CSA (Canada) for wire sizing. The unit MCA for the air handler and the op­tional electric heat kit can be found on the unit Series and Rating Plate.
Wire size allows for no more than a 2% voltage
drop from the building breaker/fuse panel to the unit.
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal in jury or de ath.
Refer to the latest edition of the National Electric Code or in Canada the Canadian Electric Code when deter­mining the correct wire size. The following table shows the current carrying capabilities for copper conductors rated at 75oC with a 2% voltage drop. Use the table below to determine the voltage drop per foot of vari­ous conductors.
4
Page 5
Maximum Allowable Length in Feet
to Limit Voltage Drop to 2%*
Wire Size
(AWG)
14 75 50 37 NR NR NR NR NR 12 118795947NRNRNRNR 10 188 125 95 75 63 54 NR NR
8 301 201 150 120 100 86 75 68 6 471 314 235 188 157 134 118 110
*Based on NEC 1996
Minimum Circuit Ampacity (MCA)
10 15 20 25 30 35 40 45
MAXIMUM OVERCURRENT PROTECTION (MOP)
Every installation must include an NEC (USA) or CEC (Canada) approved overcurrent protection device. Also, check with local or state codes for any special regional re­quirements.
Protection can be in the form of fusing or HACR style circuit breakers. The Series and Rating Plate can be used as a guide for selecting the MAXIMUM overcurrent device.
NOTE: Fuses or circuit breakers are to be sized larger than
the equipment MCA but not to exceed the MOP.
E
LECTRICAL CONNECTIONS
Consult the local power company and local codes before installing this unit. All wiring must be in accordance with the National Electrical Code as well as all local codes. Knock­outs have been provided on side and top of the cabinet for the installation of the electrical conduit. If the knockouts on the cabinet sides are used for electrical conduit, an adapter ring must be used in order to meet UL1995 safety require­ments. Use Minimum Circuit Ampacity and type of wire to determine proper wire size. The unit MUST be properly grounded. A ground lug is provided in the unit.
Check all factory connections before connecting electrical power to unit to ensure none were loosened or disconnected during shipping and handling.
WARNING
HIGHVOLTAGE!
TO
PREVENTPERSONALINJURYORDEATHDUETO
ELECTRICALSHOCK,DISCONNECTTHEELECTRICAL
POWERBEFOREELECTRICALLYCONNECTINGTHEUNIT
WARNING
TO
AVOIDTHERISKOFFIREOREQUIPMENTDAMAGE,USECOPPER
CONDU CTORS
.
CAUTION
TO
AVOIDTHERISKOFPERSONALINJURY,WIRINGTOTHEUNITMUST
BEPROPERLYPOLARIZEDANDGROUNDED
.
.
WARNING
ALL
WIRINGMUSTCOMPLYWITHAPPLICABLELOCALANDNATIONAL
CODES
.T
YPEANDLOCATIONOFFUSEDDISCONNECTSWITCH(ES)MUST
COMPLYWITHALLAPPLICABLECODESANDPROVIDEOVERCURRENT
PROTECTIONASSHOWNONTHENAMEPLATE
.
208/230 VOLT LINE CONNECTIONS
If heater kits will not be installed, remove the proper size knockout for the electrical conduit connection. Connect elec­trical conduit to the unit using two washers to make an ap­proved connection.
The power supply wires must be connected to the red and black power wiring. Two wire nuts are provided in the bag assembly for this connection. Wrap the wire nuts with elec­trical tape. (Insulated crimp type connectors, field supplied, may be substituted for the wire nuts and electrical tape pro­vided proper size connectors are used.) A ground wire MUST be connected to the ground lug inside the unit.
AIR HANDLER ONLY (NON-HEAT KIT MODELS)
The building supply connects to the stripped black and red wires contained in the air handler electrical compartment cav­ity. A ground screw is also contained in this area. Attach the supply wires to the air handler conductors as shown in the unit wiring diagram using appropriately sized solderless con­nectors or other NEC or CEC approved means.
AIR HANDLER WITH NON-CIRCUIT BREAKER HEAT KITS
A terminal block is provided with the HKR kit to attach the power supply and air handler connections. Follow the HKR Installation Manual and wiring diagram for complete wiring details.
AIR HANDLER WITH HEAT KITS CONTAINING A CIRCUIT BREAKER
HKR models with a “C” suffix contain a circuit breaker(s). The air handler has a plastic cover on the access panel that will require either one or both sections to be removed to al­low the heat kit circuit breaker(s) to be installed. See the HKR Installation Instructions for further details. The air han­dler wires and supply wires are installed directly onto the HKR circuit breaker(s) as shown in the HKR Installation Manual and wiring diagram.
OPERATION ON 208 VOLT SUPPLY
The unit transformer is factory connected for 240 V opera­tion. If unit is to operate on 208 V, disconnect the red wire from terminal 3 of the unit transformer and connect them to terminal 2 of the unit transformer.
LOW VOLTAGE WIRING
Low voltage wiring connections are made at the top of the
cabinet. See the 24 Volt Thermostat Wiring section of this
manual for typical low voltage wiring connections. A mini­mum 18 AWG wire must be used for installations up to 100 feet.
5
Page 6
24 VOLT THERMOSTAT WIRING - NON-COMMUNICATING
A
A
THERMOSTAT CONNECTIONS
NOTE: Wire routing must not interfere with the circulator blower operation or routine maintenance.
The air handler’s integrated control module provides termi­nals for “Y1” and “Y2” and “W1” and “W2” thermostat con­nections. This allows the air handler to support the systems shown in the table below. Refer to the following figures for typical connections to the integrated control module. Ther­mostat wiring entrance holes are located in the top of the blower. Wire routing must not interfere with circulator blower operation or routine maintenance.
RCG
12RC
RC
Remote Condensing Unit
W/E
W1 W2 Y1 Y2
G
W1 Y
(Single-Stage HP)
Y1
Typical Single-Stage Cool,
O
O
O
Single-Stage Heat
Heat Pump Thermostat
DEHUM
ir Handler
Integrated Control Module
NEU
Dehumidistat
HOT
[Optional]
Typical Single-Stage Heat Pump with Auxiliary/Emergency
Heating
COOLING HEAT PUMP HEATING ELECTRIC HEATING
1-STAGE ------ 1- or 2-STAGE 2-STAGE ------ 1- or 2-STAGE 1-STAGE 1-STAGE -----­2-STAGE 2-STAGE -----­1-STAGE 1-STAGE 1- or 2-STAGE 2-STAGE 2-STAGE 1- or 2-STAGE
NOTE: A removable plug connector is provided with the
control to make thermostat wire connections. This plug may be removed, wire connections made to the plug, and
replaced. It is strongly recommended that multiple wires
into a single terminal be twisted together prior to inserting into the plug connector. Failure to do so may result in intermittent operation.
Typical Single-Stage Cool,
Single-Stage Heat Thermostat
RCG
12RCG
RC
Remote Condensing Unit
(Single-Stage AC)
W1 Y1
W1 Y1 Y2
W2
Y
Place Jumper Between Y1
and O for Proper
Dehu mid ification Operatio n
and Proper Ramping
Prof ile Operation
Air Handler Integrated
DEHUM
O
NEU
HOT
Control Module
Dehumidistat
[Optional]
______________________________________
RCG
12RC
RC
Remote Condensing Unit
W/E
W2 Y1 Y2
W1 W2 Y1 Y2
G
W1 Y1 Y2
(Two-Stage HP)
Typical Two-Stage Cool,
O
O
O
Two-Stage Heat
Heat Pump Thermostat
DEHUM
Integrated Control Module
NEU
HOT
ir Handler
Dehumidistat
[Optional]
Typical Two Stage Heat Pump heating and Auxiliary/
Emergency Heating
24 VOLT DEHUMIDISTAT WIRING - NON-COMMUNICATING THERMOSTAT CONNECTIONS
The optional usage of a dehumidistat allows the air handler’s circulator blower to operate at a slightly lower speed during a combined thermostat call for cooling and dehumidistat call for dehumidification. This lower blower speed enhances de­humidification of the conditioned air as it passes through the AC coil. For proper function, a dehumidistat applied to this air handler must operate on 24 VAC and utilize a switch which
opens on humidity rise.
To install/connect a dehumidistat:
1. Turn OFF power to air handler.
Typical Single-Stage Cooling with Single-Stage Heating
______________________________________
2. Secure the dehumidistat neutral wire (typically the white lead) to the screw terminal marked “DEHUM” on the air handler’s integrated control module.
Typical Two-Stage Cool,
Two-Stage Heat Thermostat
RCG
W1 W2 Y1 Y2
Place Jumper Between Y1
and O for Proper
Dehumidification Operation
and Proper Ramping
Profile Operat ion
3. Secure the dehumidistat hot wire (typically the black lead) to the screw terminal marked “R” on the air handler’s integrated control module.
4. Secure the dehumidistat ground wire (typically the green
Air Handler I ntegrate d
12RCG
RC
Remote Condensing Unit
W1 W2 Y1 Y2
Y1 Y2
(Two-Stage AC)
DEHUM
O
NEU
HOT
Control Module
Dehumidistat
[Optional]
Typical Two-Stage Cooling with Two-Stage Heating
lead) to the ground screw on the air handler. NOTE:
Ground wire may not be present on all dehumidistats.
5. Turn ON power to air handler.
6
Page 7
To enable the dehumidification function, move the dehumidi­fication dipswitch from OFF to ON. See following figure.
S7
S8
ONOFF
IMPORTANT NOTE: Sensing bulbs are not permanently
installed at the factory to prevent accidental damage during brazing. Be sure to follow this checklist step-by­step to ensure the sensing bulb is not damaged during installation.
Move to the ON
position to enable
dehumidification
Dipswitches - Dehumidification Enable
R
EFRIGERANT LINES
This product is factory-shipped under pressure. Follow these instructions to prevent injury.
DEHUM
Unused
A qu en c hin g c lo th is st ro ng ly recommended to prev ent scorching or marring of the eq uipm en t finis h whe n welding clo s e t o the paint ed surfaces . Us e bra z ing alloy of 5% minimum silver content.
TUBING PREPARATION
All cut ends are to be round, burr free, and clean. Failure to follow this practice increases the chances for refrigerant leaks. The suction line is spun closed and requires pipe cutters to remove the closed end.
POST BRAZING
Quench all welded joints with water or a wet rag.
1. Loosen the 13/16 nut 1 TURN ONLY. No pressure loss
indicates possible leak.
2. Remove the nut and discard the cap.
3. Follow the instructions on the caution label, and remove the two mounting screws on the lower access panel. Then remove the lower access panel.
4. Remove the large front panel and remove the sensing bulb from suction manifold. TO PREVENT DAMAGE TO SENSING BULB, ENSURE BULB IS NOT NEAR FLAME OR IN CONTACT WITH SUCTION LINE OR MANIFOLD DURING BRAZING.
5. Use a tube cutter to remove the spin closure on the suction line.
Excessive torque can cause orifices to stick. Use the proper torque settings when tightening orifices.
6. Replace sensing bulb to horizontal portion of suction line just inside cabinet. Place bulb parallel with suction line between 10 o’clock and 2 o’clock position. Secure bulb to line with strapping provided in literature enve­lope. Insulate sensing bulb to line with self-adhesive insulation provided in the envelope. See the following figures for correct bulb placement and strapping infor­mation.
PIPING SIZE
For the correct tubing size, follow the specification for the condenser/heat pump.
SPECIAL INSTRUCTIONS
This coil comes equipped with a thermostatic expansion valve (TXV) for refrigerant management.
IMPORTANT NOTE: Torch heat required to braze tubes of
various sizes is proportional to the size of the tube. Tubes of smaller size require less heat to bring the tube to brazing temperature before adding brazing alloy. Applying too much heat to any tube can melt the tube. Service personnel must use the appropriate heat level for the size of the tube being brazed.
NOTE: The use of a heat shield when brazing is
recommended to avoid burning the serial plate or the finish on the unit. HEAT TRAP OR WET RAGS SHOULD BE USED TO PROTECT HEAT SENSITIVE COMPONENTS SUCH AS SERVICE VALVES AND TXV VALVES.
REFRIGERANT BULB MUST BE POSITIONED BETWE EN 10 & 2 O’CLOCK
REFRIGERANT BULB MUST BE POSITIONED BETWEEN 10 & 2 O’CLOCK
NOTE: The sensing bulb must be permanently located. A heat shield, heat trap, or wet rag must be used during braz­ing to prevent damage to the TXV valve.
7
Page 8
7. Replace access panels, suction line grommet, insula­tion and all screws.
SUCTION LINE WITH SPIN CLOSURE
RUBBER GROMM ET
Suction Line Grommet
A
IRFLOW CONVERSIONS
DOWNFLOW CONVERSION
Conversion to downflow MUST be performed in an area that allows access to all sides prior to placing the air handler in its final location. To prevent the evaporator coil pan from “sweating”, a drain pan insulation (DPI) accessory kit is to be used when performing this conversion. NOTE: The DPI kit is not supplied with this product and is to be purchased
separately. See the following Drain Pan Insulation Kit table
for the correct DPI kit.
AVPTC Model Insulation Kit
RETURN AIR SIDE OF UNIT
ACCESS PAN EL
NOTE: The filter provision is not applicable
in THIS downf low application.
Downflow Conversion - Conversion Preparation
REAR CHANNEL BRACKET
ZEE COIL SUPPORT BRACKET
COIL RETAINING BRACKET
TIE BRACKET
7. Install the zee coil supports and the wrapper stiffeners.
8. Install the tie bracket.
9. Install the rear channel bracket.
10. To prevent possible condensate “blow off” the insula­tion retainers are to be laid into the evaporator coil pan as shown.
1830 DPI36-42/20
3137 4260
Drain Pan Insulation Kits
DPI48-61/-20
Refer to Figures Downflow Conversion - Conversion Prepa-
ration, Downflow Conversion - Insulation Retainers, and Downflow Conversion - Conversion Completion for the lo-
cation of the components referenced in the following steps.
Figure Downflow Conversion - Conversion Preparation il-
lustrates the new installation location for the removed com­ponents.
1. Before inverting the air handler, remove all access pan­els, the coil rear channel bracket, and the filter close­off panel.
2. Remove the evaporator coil and the horizontal drain pan. Discard horizontal drain pan.
3. Install the provided plastic plug into the vacated ac­cess panel.
4. Remove the two (2) zee coil support brackets and in­sulation retaining brackets.
3” FLAT INSULATION RETAINER (BOTH SIDES)
Downflow Conversion - Insulation Retainers
To complete the conversion, slide the evaporator coil into the chassis and attach the three (3) access panels.
5. Remove the tie bracket.
6. Install the DPI Insulation Kit onto the bottom of the drain pan.
8
Page 9
WRAPPER
INSULATION JACKET
ZEE COIL SUPPORT
WRAPPER STIFFENER
DRAIN PAN INSULATION KIT
Horizontal Left-Hand Conversion
1. Remove two screws beside the liquid line on the lower access panels. Remove the (3) air handler access pan­els.
2. Remove the “J” shaped bracket that retains the evapo­rator coil.
BLOWER ASSEMBLY
Downflow Conversion - Conversion Completion
NOTE: When converted to downflow position the coil may
protrude above the cabinet on some models.
HORIZONTAL CONVERSION
Dedicated Downflow models are not suitable for horizontal application and must not be used for this type of installation. The only field modification required for conversion to “Hori­zontal Right-Hand” is the removal of the plastic knockouts in the horizontal panel drain connections. To prevent the hori­zontal drain pan from sweating in high humidity applications, it is recommended that a horizontal drain pan insulation
(DPIH) accessory kit be used. NOTE: The DPIH insulation
kit is not supplied with this product and should be purchased
separately. See Horizontal Drain Pan Insulation Kits table
for the correct DPIH kit.
AVPTC Model Insulation Kit
1830 DPIH36-42
3. Slide out the evaporator coil and horizontal drain pan.
4. Remove the gasket from the horizontal pan drain con­nections.
5. Remove the oval shaped plastic plug from the left side access panel. Remove the oval shaped rubber gasket seal from the lower right side access panel.
6. The drain connections for the horizontal pan are sealed with a thin coating of plastic. Carefully knock out this plastic seal with a screwdriver and hammer.
Note: The upper drain will become the secondary drain which is mandatory in many municipalities .
7. Install the plastic plug removed in step 5 to the right side lower access panel and the oval shaped rubber gasket to the lower left access panel.
8. Reinstall the evaporator coil with the horizontal panel on the left side. Note: Push the assembly completely to the rear to ensure the engagement of the upflow pan with the rear channel bracket.
9. Install the “J” bracket (removed in step 2) to support the upflow pan to the tie channel.
10. Attach all panels and the metering device.
3137 4260
Horizontal Drain Pan Insulation Kits
DPIH 48-61
The following describes converting to “Horizontal Left-Hand”. Conversion to downflow MUST be performed in an area that
allows access to all sides prior to placing the air handler in
its final location. See Horizontal Left-Hand Conversion fig-
ure below.
AVPTC MOTOR ORIENTATION
If the unit is in the upflow position, there is no need to rotate the motor. If the unit is in the downflow position, loosen
motor mount and rotate motor as shown in the AVPTC Mo- tor Orientation figure below. Be sure motor is oriented with
the female connections on the casing down. If the motor is not oriented with the connections down, water could collect in the motor and may cause premature failure.
9
Page 10
A
A
FRONT VIEW
FEMALE CONNECTIONS
AVPTC Motor Orientation
C
ONDENSATE REMOVAL
SIDE VIEW
W
RNING
SOFTW
RE VER.
Field experience has shown condensate drain traps with an
TOP
open vertical Tee between the air handler and the conden­sate drain trap can improve condensate drainage in some applications, but may cause excessive air discharge out of the open Tee. Goodman® does not prohibit this type of drain but we also do not recommend it due to the resulting air leakage. Regardless of the condensate drain design used, it is the installer’s responsibility to ensure the condensate drain system is of sufficient design to ensure proper con­densate removal from the coil drain pan.
Drain
Connection
The coil drain pan has a primary and an optional secondary drain with 3/4" NPT female connections. The connectors re-
Air Handler
2" MIN.
quired can be 3/4" NPT male either PVC or metal pipe and should be hand tightened to a torque of approximately 37 in­lbs. to prevent damage to the drain pan connection. An in­sertion depth between .355 to .485 inches (3-5 turns) should
POSITIVE LIQUID SEAL REQUIRED
AT TRAP
3" MIN.
be expected at this torque. Use the female (3/4 fpt) threaded fitting that protrudes outside of the enclosure for external connections.
1. Ensure drain pan hole is NOT obstructed.
2. To prevent potential sweating and dripping on to fin­ished space, it may be necessary to insulate the con­densate drain line located inside the building. Use Armaflex® or similar material.
A Secondary Condensate Drain Connection has been pro­vided for areas where the building codes require it. Pitch the drain line 1/4" per foot to provide free drainage. Insulate drain lines located inside the building to prevent sweating. Install a condensate trap to ensure proper drainage. If the second­ary drain line is required, run the line separately from the primary drain and end it where it can be easily seen.
NOTE: Water coming from this line means the coil primary
drain is plugged and needs clearing.
Use of a condensate removal pump is permitted when nec­essary. This condensate pump should have provisions for shutting off the control voltage should a blocked drain occur. A trap must be installed between the unit and the conden­sate pump.
IMPORTANT NOTE: The evaporator coil is coated with oils
that may dissolve styrofoam and certain types of plastics. Therefore, a removal pump or float switch must not contain any of these materials.
Tip: Priming the “P” trap may avoid improper draining at the
initial installation and at the beginning of the cooling season. When coils are installed above ceilings, or in other locations
where damage from condensate overflow may occur, it is
MANDATORY to install a field fabricated auxiliary drain pan
under the coil cabinet enclosure. Drain lines from the auxil­iary pan must be installed and terminated so that the home-
Condensate Drain Trap
owner can see water discharges.
CAUTION
A
If secondary drain is not installed, the secondary access must be plugged.
CHIEVING
Ensure that the Neoprene gasket with PSA remains intact on all surfaces that the access panels are secured to. These
The installation must include a “P” style trap that is located
as close as is practical to the evaporator coil. See Conden- sate Drain Trap figure for details of a typical condensate line
“P” trap.
NOTE: Trapped lines are required by many local codes. In
the absence of any prevailing local codes, please refer to
surfaces are the entire length of the wrapper and areas be­tween the upper tie plate, upper and lower access panels. Be sure that upper access panel breaker insert gasket is intact and also flowrator gasket is installed on the lower ac­cess panel. An additional drain hole cover is required.
C
IRCULATOR BLOWER
the requirements listed in the Uniform Mechanical Building Code.
A drain trap in a draw-through application prevents air from
being drawn back through the drain line during fan opera­tion thus preventing condensate from draining, and if con­nected to a sewer line to prevent sewer gases from being drawn into the airstream during blower operation.
This air handler is equipped with a multi-speed circulator blower. This blower provides ease in adjusting blower speeds. The Specification Sheet applicable to your model provides an airflow table, showing the relationship between airflow (CFM) and external static pressure (E.S.P.), for the proper selection of heating and cooling speeds. The heat­ing blower speed is shipped set at “21 kW”, and the cooling blower speed is set at “D”. These blower speeds should be
10
2% L
OW LEAKAGE RATE
Page 11
adjusted by the installer to match the installation require­ments so as to provide the correct electric heating CFM and correct cooling CFM.
Use the CFM LED (green), adjacent to the integrated con­trol module electric heat connector to obtain an approximate airflow quantity. The green CFM LED blinks once for each 100 CFM of airflow.
1. Determine the tonnage of the cooling system installed with the air handler. If the cooling capacity is in BTU/hr divide it by 12,000 to convert capacity to TONs.
Example: Cooling Capacity of 30,000 BTU/hr.
Tap A Tap B
OFF OFF OFF OFFON ON ON ON
S1
S2
Cooling Air flow Speed Tap (*indicates factory setting)
Normal* +10%
OFF OFF OFF OFFON ON ON ON
S1
S2
Tap C Tap D*
S1
S2
-10% Normal
S1
S2
30,000/12,000 = 2.5 Tons
2. Determine the proper air flow for the cooling system. Most cooling systems are designed to work with air flows between 350 and 450 CFM per ton. Most manufactur­ers recommend an air flow of about 400 CFM per ton.
Example: 2.5 tons X 400 CFM per ton = 1000 CFM
The cooling system manufacturer’s instructions must be checked for required air flow. Any electronic air cleaners or other devices may require a specific airflow; consult installa­tion instructions of those devices for requirements.
3. Knowing the air handler model, locate the high stage cooling air flow charts in the Specification Sheet appli­cable to your model. Look up the cooling air flow de­termined in step 2 and find the required cooling speed and adjustment setting.
Example: An AVPTC183014 air handler installed with
a 2.5 ton air conditioning system. The air flow needed is 1000 CFM. Looking at the cooling speed chart for AVPTC183014, find the air flow closest to 1000 CFM. A cooling airflow of 1000 CFM can be attained by set­ting the cooling speed to “C” and the adjustment to “0” (no adjustment).
S3
S4
Air flow Adjust Taps (*indicates factory setting)
S3
S4
S3
S4
S3
S4
Dipswitches - Cooling Airflow and Airflow Adjust Taps
6. The multi-speed circulator blower also offers several custom ON/OFF ramping profiles. These profiles may be used to enhance cooling performance and increase comfort level. The ramping profiles are selected using
DIP switches 5 and 6. Refer to the following Dipswitches
- Cooling Airflow Ramping Profiles figure for switch po-
sitions and their corresponding taps. Refer to the bullet points below for a description of each ramping profile. Verify profile selection by counting the green CFM LED blinks and timing each step of the ramping profile.
• Profile A provides only an OFF delay of one (1) minute at 100% of the cooling demand airflow.
OFF
100% CFM 100% CFM
1 min
OFF
4. Locate the blower speed selection DIP switches on the integrated control module. Select the desired “cooling” speed tap by positioning switches 1 and 2 appropri­ately. Select the desired “adjust” tap by positioning switches 3 and 4 appropriately. Refer to the following
Dipswitches - Cooling Airflow and Airflow Adjust Taps
figure for switch positions and their corresponding taps. Verify CFM by counting the number of times the green CFM LED blinks.
5. Continuous fan speed is 30% of the air handler’s maxi­mum airflow capability.
Example: If the air handler’s maximum airflow capabil-
ity is 2000 CFM, the continuous fan speed will be 0.30 x 2000 CFM = 600 CFM.
• Profile B ramps up to full cooling demand airflow by first stepping up to 50% of the full demand for 30 sec­onds. The motor then ramps to 100% of the required airflow. A one (1) minute OFF delay at 100% of the cooling airflow.
OFF
50% CFM
1/2 min
100% CFM
100% CFM
1 min
• Profile C ramps up to 82% of the full cooling demand airflow and operates there for approximately 7 1/2 min­utes. The motor then steps up to the full demand air­flow. Profile C also has a one (1) minute 100% OFF delay.
OFF
100% CFM
11
OFF
OFF
Page 12
• Profile D ramps up to 50% of the demand for 1/2 minute, then ramps to 82% of the full cooling demand airflow and operates there for approximately 7 1/2 minutes. The motor then steps up to the full demand airflow. Profile D has a 1/2 minute at 50% airflow OFF delay.
OFF
Tap A Tap B Tap C Tap D*
OFF OFF OFF OFFON ON ON ON
S5
S6
S5
S6
S5
S6
Dipswitches - Cooling Airflow Ramping Profiles
S5
S6
OFF
7. If an electric heater kit has been installed, determine the heater kilowatt (kW) rating. Find the heater size in the table below. Set dip switches 9, 10, and 11 for the
installed heater as shown in the Dipswitches - Electric Heat Airflow figure below. The adjust setting (already
established by the cooling speed selection) also ap­plies to the electric heater kit airflow. Thus, the electric heater airflow is adjusted by the same amount. Verify selected CFM by counting the green CFM LED blinks.
ELECTRIC HEAT TEMPERATURE RISE:
The heating mode temperature rise is dependent upon the system airflow, the supply voltage, and the heat kit size (kW) selected. Use the supply voltage/temperature rise tables
below to determine the temperature rise (
º
F).
CFM
HEAT KIT NOMINAL kW
3 5 6 8 10152021
60018283541
8001321263142 1000 11 17 21 25 34 50 1200 9 14 18 21 28 42 56 62 1400 8 12 15 18 24 36 48 53 1600 7 10 13 15 21 31 42 46 1800 6 9 12 14 19 28 37 41 2000 5 8 11 12 17 25 34 37
230/1/60 Supply Voltage - Temperature Rise Table °F
CFM
3 5 6 8 10152021
HEAT KIT NOMINAL kW
600 17 27 34 39
800 13 20 25 30 40
1000 10 16 20 24 32 48 1200 8 13 17 20 27 40 53 59 1400 7 11 14 17 23 34 46 51 1600 6 10 13 15 20 30 40 44 1800 6 9 11 13 18 27 36 39 2000 5 8 10 12 16 24 32 35
220/1/60 Supply Voltage - Temperature Rise Table °F
CFM
356810152021
HEAT KIT NOMINAL kW
600 16 25 32 37
800 12 19 24 38 38
1000 10 15 19 22 30 46 1200 8 13 16 19 25 38 51 56 1400 7 11 14 16 22 33 43 48 1600 6 9 12 14 19 28 38 42 1800 5 8 11 12 17 25 34 37 2000 5 8 10 11 15 23 30 34
208/1/60 Supply Voltage - Temperature Rise Table °F
21 kW* 20 kW
OFF OFF OFF OFFON ON ON ON
S9
S10
S11
S9
S10
S11
15 kW 10 kW
S9
S10
S11
S9
S10
S11
8 kW 6 kW 5 kW 3 kW
OFF OFF OFF OFFON ON ON ON
S9
S10
S11
S9
S10
S11
S9
S10
S11
S9
S10
S11
Electric Heating Air Flow (*indicates factory setting)
NOTE: Upon start up in communicating mode the circuit board will display a “1 Flash” error code on the diagnostic LED
and an “Ec” HTR TO LARGE error at the communicating display. This is an indication that the dip switches on the control board need to be configured in accordance with the Electric Heating Airflow Table on the following page of this manual. Configuring the dip switches and resetting power to the unit will clear the error code.
12
Page 13
NOTE: For installations not indicated in the preceding
Temperature Rise Tables, the following formula is to be used:
TR = (kW x 3412) x (Voltage Correction) x (1.08 x CFM)
Where: TR = Temperature Rise kW = Heater Kit Actual kW 3412 = Btu per kW Voltage Correction =.96 (230 Supply Volts)
=.92 (220 Supply Volts) =.87 (208 Supply Volts)
1.08 = Constant CFM = Measured Airflow
NOTE: The Temperature Rise Tables can also be used to
determine the air handler airflow delivery. When using these tables for this purpose set the room thermostat to maximum heat and allow the system to reach steady state conditions. Insert two thermometers, one in the return air and one in the supply air. The temperature rise is the supply air temperature minus the room air temperature. Use HKR specification sheets to determine the HKR avail­able for a given air handler.
Speed Selection Dip Switches
Cool Selection Switches
Tap 1 2
AOFFOFF
BONOFF COFFON
DONON
TO SET AIRFLOW:
1.Select appropriate model from Cooling/Heat P ump Airflow Table. Based on desired Ai rflow for your application select c orresponding tap (A,B,C or D). Set dip switches 1 & 2 to the appropriate ON/O FF positions.
2. Select appropr iate Airflow adjustme nt factor for appli cation (0%. +10%, -10%) . Set dip switches 3 & 4 to the appropria te ON/OFF positions.
If installed with Heater Kit:
3. Using Electric Heat Airflow Table, set di p switches 9, 10 and 11 t o the appropriate ON/OFF positions ba sed on Heater kit installed.
If installed without Heater Kit:
Ensure dip switches 9, 10 and 11 are set to a valid heater kit selecti on. Example: The only valid heat er kits for AVPTC183014* applic ations are 3, 5, 6, 8 and 10 kW.
Failure to do so will result in a Heater Kit er ror code.
TO SET COMFORT MODE:
Select desired Comfort Mode profile (see profil es above). Set switches 5 and 6 to the appropriate ON/OFF position s.
Profiles 5 6
Pre-Run Short-Ru n Off Delay
AOFFOFF
BONOFF
COFFON
DONON
------- ------- 60 sec/100%
------- 30 sec/50% 60 sec/100%
------- 7.5 mins/82% 60 sec/100%
30 sec/50% 7.5 mins/82% 30 sec/50%
TRIM
0%
+ 10%
- 10%
0%
Ad ju st Selection Switches
34
OFF OFF
ON OFF
OFF ON
ON ON
Sel ec t io n Switches
Profile
AVPTC183014*
AVPTC313714*
AVPTC426014*
NOTE: Airfl ow dat a s hown app lies t o no n- com munic at ing m ode ope rat ion onl y. For a fully commu nic at in g syste m, plea se see the ou tdoor unit 's ins tall at ion instr uctions for c oo lin g and heat pump airflow data. S ee C o m fortNe t™ System - Ai r flow Cons id er ation sec tion for detail s.
Htr k W 9 10 11
3 ONONON630610600 5 ON O N O FF 7 30 710 680 6 ON O FF O N 8 40 840 790
8 ON O FF O FF 108 0 1060 99 0 10 OFF ON ON 1270 1260 1190
15 OFF O N OFF NR 14 7 0 13 90 20 OFF OFF ON NR NR 1580
21 OFF OFF OFF NR NR 1580
NOTE: Airfl ow dat a s hown app lies t o t he e me rg ency hea t mode ( elec tric heat onl y) in eit her non­commu nicatin g mod e operat ion or full y com mun icat ing m ode oper ation.
Cooling/Heat Pump Airflow Table
Model
Tap
A 420 630 B 560 840 C 700 10 40 A 410 610 B 560 830 C 700 10 40 D 830 12 40 A 810 12 10 B 940 14 10 C10501560 D12101800
Electr ic He at Airflow Tabl e
AVPTC
183014*
Low
Stage
Coo l
AVPTC
313714*
High
Stage
Cool
AVPTC
426014*
NOTE: Airflow blink codes are approximations of actual airflow.
Heat Kit Selection
MODELS HKR-03* HKR-05*/-05C* HKR-06* HKR-08*/-08C* HKR-10*/-10C* HKR-15C# HKR-20C# HKR-21C*
AVPTC183014A* X X X
AVPTC313714A* X X X
AVPTC426014A* X X X X X X
* Revision level that may or may not be designated.
C Circuit breaker option.
# Indicates Model A or Model B. Model A is 208V only and Model B is 240V only.
NOTE: When 8kW and 10kW heat kits are used with an AVPTC1830 and AVPTC3137, matched with 2- ton outdoor unit, see Note 1 below.
1
Set Heater Kit dip switches 9, 10 and 11 to 6kW setting (9-ON, 10-OFF,11-ON) to obtain 840 CFM.
2
This heater kit can only be used for ‘1000 CFM or higher’ applications.
3
This heater kit can only be used for ‘1200 CFM or higher’ applications.
1
X
1
X
1
X
1
X
--- --- ---
2
X
--- ---
3
X
13
3
X
Page 14
T
ROUBLESHOOTING
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
NOTE: Discharge body’s static electricity before touching
unit. An electrostatic discharge can adversely affect electrical components. Use the following precautions during air handler installation and servicing to protect the integrated control module from damage. By putting the air handler, the control, and the person at the same electrostatic potential, these steps will help avoid exposing the integrated control module to elec­trostatic discharge. This procedure is applicable to both in­stalled and uninstalled (ungrounded) blowers.
1. Disconnect all power to the blower. Do not touch the integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.
FAULT RECALL
The integrated control module is equipped with a momen­tary push-button switch that can be used to display the last six faults on the red diagnostic LED. The control must be in Standby Mode (no thermostat inputs) to use the feature. De­press the push-button for approximately two seconds and less than five seconds. The LED display will then display the six most recent faults beginning with the most recent fault and decrementing to the least recent fault. The faults may be cleared by depressing the button for greater than five seconds.
NOTE: Consecutively repeated faults are displayed a
maximum of three times. Example: A clogged return air filter causes the air handler’s motor to repeatedly enter a limiting condition. The control will only store this fault the first three
consecutive times the fault occurs.
C
OMFORTNET
™ S
YSTEM
2. Firmly touch a clean, unpainted, metal surface of the modular blower near the control. Any tools held in a person’s hand during grounding will be discharged.
3. Service integrated control module or connecting wiring following the discharge process in step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an un­grounded object, repeat step 2 before touching control or wires.
4. Discharge your body to ground before removing a new control from its container. Follow steps 1 through 3 if installing the control on a blower. Return any old or new controls to their containers before touching any ungrounded object.
DIAGNOSTIC CHART
WARNING
HIGHVOLTAGE!
TO
AVOIDPERSONALINJURYORDEATHDUETO
ELECTRICALSHOCK,DISCONNECTELECTRICALPOWER
BEFOREPERFORMINGANYSERVICEORMAINTENANCE
Refer to the Troubleshooting Chart at the end of this manual
for assistance in determining the source of unit operational problems. The red diagnostic LED blinks to assist in trouble­shooting the unit. The number of blinks refers to a specific fault code.
.
OVERVIEW
The ComfortNet system is a system that includes a ComfortNet compatible air handler and air conditioner or heat pump with a CTK0*AA thermostat. Any other system con­figurations are considered invalid ComfortNet systems and must be connected as a traditional (or non-communicating)
system (see Electrical).
A ComfortNet heating/air conditioning system differs from a non-communicating/traditional system in the manner in which the indoor unit, outdoor unit and thermostat interact with one another. In a traditional system, the thermostat sends com­mands to the indoor and outdoor units via analog 24 VAC signals. It is a one-way communication path in that the in­door and outdoor units typically do not return information to the thermostat.
On the other hand, the indoor unit, outdoor unit, and ther­mostat comprising a ComfortNet system “communicate” digi­tally with one another. It is now a two-way communications path. The thermostat still sends commands to the indoor and outdoor units. However, the thermostat may also re­quest and receive information from both the indoor and out­door units. This information may be displayed on the ComfortNet thermostat. The indoor and outdoor units also interact with one another. The outdoor unit may send com­mands to or request information from the indoor unit. This two-way digital communications between the thermostat and subsystems (indoor/outdoor unit) and between subsystems is the key to unlocking the benefits and features of the ComfortNet system.
Two-way digital communications is accomplished using only two wires. The thermostat and subsystem controls are pow­ered with 24 VAC Thus, a maximum of 4 wires between the equipment and thermostat is all that is required to operate the system.
14
Page 15
AIRFLOW CONSIDERATION
Airflow demands are managed differently in a fully commu­nicating system than they are in a non-communicating wired system. The system operating mode (as determined by the thermostat) determines which unit calculates the system airflow demand. If the indoor unit is responsible for deter­mining the airflow demand, it calculates the demand and sends it to the ECM motor. If the outdoor unit or thermostat is responsible for determining the demand, it calculates the demand and transmits the demand along with a fan request to the indoor unit. The indoor unit then sends the demand to the ECM motor. The table below lists the various ComfortNet systems, the operating mode, and airflow de­mand source.
System
Air Conditioner +
Air Hand ler
He a t Pu m p + A ir
Ha ndl er
System Operating
Mode
Cooling Air Conditio ner
Heating Air Handler
Cont inu ous Fan The rmos t at
Cooling Heat Pump
He at P ump Heat ing
On ly
HP + Electric Heat
Strips
Elect ric Heat Str ips
On ly
Cont inu ous Fan The rmos t at
Air flow De ma nd S ourc e
Heat Pump
> of Heat Pump or Air
Handler Demand
Air Handler
In continuous fan mode, the CTK0*AA thermostat provides the airflow demand. The thermostat may be configured for a low, medium, or high continuous fan speed. The low, medium, and high fan speeds correspond to 25%, 50% and 75%, respectively, of the air handlers’ maximum airflow capability. During continuous fan operation, the thermostat sends a fan request along with the continuous fan demand to the air handler. The air handler, in turn, sends the demand to the ECM motor. The ECM motor delivers the requested continuous fan airflow.
CTK0*AA WIRING
NOTE: Refer to section Electrical Connections for 208/230 volt line connections to the air handler.
NOTE: A removable plug connector is provided with the
control to make thermostat wire connections. This plug may be removed, wire connections made to the plug, and replaced. It is strongly recommended that multiple wires into a single terminal be twisted together prior to inserting into the plug connector. Failure to do so may result in intermittent operation.
Typical 18 AWG thermostat wire may be used to wire the system components. One hundred (100) feet is the maxi­mum length of wire between indoor unit and outdoor unit, or between indoor unit and thermostat.
FOUR-WIRE INDOOR AND OUTDOOR WIRING
Typical wiring will consist of four wires between the indoor unit and outdoor unit and between the indoor unit and ther­mostat. The required wires are: (a) data lines, 1 and 2; (b) thermostat “R” (24 VAC hot) and “C” (24 VAC common).
12RC
CTK0*AA Thermostat
For example, assume the system is a heat pump matched with an air handler. With a call for low stage cooling, the heat pump will calculate the system’s low stage cooling airflow demand. The heat pump will then send a fan request along with the low stage cooling airflow demand to the air handler. Once received, the air handler will send the low stage cooling airflow demand to the ECM motor. The ECM motor then delivers the low stage cooling airflow. See the applicable ComfortNet air conditioner or heat pump installation manual for the airflow delivered during cooling or heat pump heating.
12RC
ComfortNet™ Compatible Air Handler Integrated Control Module
12RC
System Wiring Using Four-Wires
ComfortNet Compatible AC/HP Integrated Control Module
TWO-WIRE OUTDOOR, FOUR-WIRE INDOOR WIRING
Two wires only may be utilized between the indoor and out­door units. For this wiring scheme, only the data lines, 1 and 2, are required between the indoor and outdoor units. A 40VA, 208/230 VAC to 24 VAC transformer must be installed in the outdoor unit to provide 24 VAC power to the outdoor unit’s electronic control. The transformer is included with the CTK0*AA kit. See kit instructions for mounting and wir­ing instructions. Four wires are required between the indoor unit and thermostat.
15
Page 16
Optional
40VA Transformer
(included in
CTK0*AA kit)
208/230 VAC
24 VAC
12RC
12RC
12RC
CTK0*AA Thermostat
ComfortNet Air Handler Integrated Control Module
ComfortNet AC/HP Integrated Control Module
Compatible
Compatible
Red communications LED – Indicates the status of the network. The table below indicates the LED sta­tus and the corresponding potential problem.
Green receive LED – Indicates network traffic. The table below indicates the LED status and the corre­sponding potential problem.
Learn button – Used to reset the network. Depress the button for approximately 2 seconds to reset the network.
System Wiring using Two-Wires between Air Handler and
AC/HP and Four-Wires between Air Handler and Thermostat
COMFORTNET™ SYSTEM ADVANCED FEATURES
Refer to the communicating thermostat installation manual for information on accessing advanced features and menus.
DIAGNOSTICS
Accessing the air handler’s diagnostics menu provides ready access to the last six faults detected by the air handler. Faults are stored most recent to least recent. Any consecutively repeated fault is stored a maximum of three times. Example: A clogged return air filter causes the air handler’s motor to repeatedly enter a limiting condition. The control will only
store this fault the first three consecutive times the fault oc-
curs. Navigate to the diagnostics menu as described above
in Accessing and Navigating the Advanced Features Menus. NOTE: It is highly recommended that the fault history be
cleared when performing maintenance or servicing the air
handler.
NETWORK TROUBLESHOOTING NOTE: Indoor Unit BIAS and TERMINATION Dipswitches
are factory set and should not be changed.
SYSTEM TROUBLESHOOTING
NOTE: Refer to the instructions accompanying the
ComfortNet compatible outdoor AC/HP unit for troubleshooting information.
Refer to the Troubleshooting Chart at the end of this manual
for a listing of possible air handler error codes, possible causes and corrective actions.
S
TART-UP PROCEDURE
Prior to start-up, ensure that all electrical connections are properly sized and tightened.
All panels must be in place and secured. For Air Tight application, neoprene gasket must be positioned at prescribed locations to achieve 2% leakage.
Tubing must be leak free.
Unit should be elevated, trapped and pitched to allow for drainage.
Low voltage wiring is connected.
Auxiliary drain is installed when necessary and pitched to allow for drainage.
BIAS
BIAS
TERM
ONOFF
S2
S1
S3
Dipswitches - Indoor Unit BIAS and TERMINATION
The ComfortNet system is a fully communicating system, and thus, constitutes a network. Occasionally the need to troubleshoot the network may arise. The integrated air han­dler control has some on-board tools that may be used to troubleshoot the network. These tools are: red communica­tions LED, green receive (Rx) LED, and learn button. Refer
to the Communications Troubleshooting Chart at the end of
this manual for error codes, possible causes and corrective actions
Drain pan and drain tubing has been leak checked.
Return and supply ducts are sealed.
Unit is elevated when installed in a garage or where flammable vapors may be present.
Unit is protected from vehicular or other physical dam­age.
Return air is not obtained from any areas where there may be objectionable odors, flammable vapors or prod­ucts of combustion such as carbon monoxide (CO), which may cause serious personal injury or death.
16
Page 17
R
EGULAR MAINTENANCE
HIGH VOLTA GE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
The only item to be maintained on a regular basis by the user is the circulating air filter(s). Filter should be cleaned or replaced regularly. A certified service technician must per­form all other services.
NOTE: THESE INSTRUCTIONS ARE SPECIFICALLY FOR AVPTC MODELS. DO NOT USE THESE DIAGRAMS FOR
ANY OTHER MODELS. SEE SEPARATE INSTALLATION AND OPERATING INSTRUCTIONS FOR ATUF, ARUF, ARPT, ADPF, AND ASPF MODELS.
NOTICE: THIS PRODUCT CONTAINS ELEC-
TRONIC COMPONENTS WHICH REQUIRE A DEFI­NITE GROUND. PROVISIONS ARE MADE FOR CONNECTION OF THE GROUND. A DEDICATED GROUND FROM THE MAIN POWER SUPPLY OR AN EARTH GROUND MUST BE PROVIDED.
17
Page 18
AIR HANDLER ADVANCED FEATURES MENUS
)
CONFIGURATION
Subm e nu Item Indication (for Displa y Only; not Use r Modifiabl e)
Electric Heat Size (HTR KW ) Displays the size in kW of the selected electric heaters.
Motor HP (1/2, 3/4, or 1 MTR HP) Displays the air handler indoor blower motor horsepower.
Heat ON Delay (HT ON) Displays the electric heat indoor blower ON delay.
Heat OFF Delay (HT OFF) Display s the electric heat indoor blower OFF delay.
DIAGNOSTICS
Sub m enu It em In dicat i on/U s er Modifiabl e Optio ns Com m en ts
Fault 1 (FAULT #1) Most recent fault For display only
Fault 2 (FAULT #2) Next most recent fault For display only
Fault 3 (FAULT #3) Next most recent fault For display only
Fault 4 (FAULT #4) Next most recent fault For display only
Fault 5 (FAULT #5) Next most recent fault For display only
Fault 6 (FAULT #6) Least recent fault For display only Clear Fault History (CLEAR) NO or YES Selecting “ YES” clears the fault
history
NOTE:
Consecutively repeated faults are shown a maximum of 3 times
IDENTIFIC ATION
Submenu Item Indication (for Display Only; not Use r Modifiable)
Model Number (MOD NUM) Displays the air handler model number
Serial Number (SER NUM) Displays the air handler serial number (Optional) Software (SOFTWARE) Displays the application software revision
SET-UP
Submenu Item U ser Modifiable Option s Comments
Heat Airflow Trim (HT TRM
Subm e nu Item Indication (for Displa y Only; not Use r Modifiable )
Mode (MODE) Displays the current air handler operating mode
CFM (CFM) Displays the airflow for the current operating mode
-10% to +10% in 2% increments, default is 0%
STATUS
Trims the electric heating airflow by the selected amount.
18
Page 19
COMMUNICATIONS TROUBLESHOOTING CHART
LED LED
Red
Communications
LED
2 Flashes
1 Steady
Green Receive
LED
Flashing On Solid
Status
Off
1 Flash
Off
Flash
Rapid
Indication Possible Causes Corrective Action(s) Notes & Cautions
x Normal condition x None x None x None x Communications
Failure
x Out-of-box reset x Control power up
x No power x Communications
error
x No network found x Broken/ disconnected
x Normal network
traffic
x Data 1/ Data 2
miss-wire
x Communications
Failure
x Learn button
depressed
x No power to air
handler
x Open fuse x Communications error
data wire(s)
x Air handler is installed
as a non­communicating/ traditional system
x Control is “talking” on
network as expected
x Data 1 and data 2
wires reversed at air handler, thermostat, or ComfortNet™ compatible outdoor AC/HP
x Short between data 1
and data 2 wires
x Short between data 1
or data 2 wires and R (24VAC) or C (24VAC common)
x Depress Learn Button x Verify that bus BIAS
and TERM dipswitches are in the ON position.
x None x None
x Check fuses and
circuit breakers; replace/reset
x Replace blown fuse x Check for shorts in
low voltage wiring in air handler/system
x Reset network by
depressing learn button
x Check data 1/ data 2
voltages
x Check
communications wiring (data 1/ data 2 wires)
x Check wire
connections at terminal block
x Verify air handler
installation type (non­communicating/ traditional or communicating)
x Check data 1/ data 2
voltages
x None x None
x Check
communications wiring (data 1/ data 2 wires)
x Check wire
connections at terminal block
x Check data 1/ data 2
voltages
x Depress once
quickly for a power­up reset
x Depress and hold
for 2 seconds for an out-of-box reset
x Turn power OFF
prior to repair
x Turn power OFF
prior to repair
x Verify wires at
terminal blocks are securely twisted together prior to inserting into terminal block
x Verify data1 and
data voltages as described above
x Turn power OFF
prior to repair
x Verify wires at
terminal blocks are securely twisted together prior to inserting into terminal block
x Verify data1 and
data voltages as described above
19
Page 20
T
ROUBLESHOOTING
Notes & Cautions
C
HART
Corrective Actions
Possible Causes
ComfortNet ™
Thermostat Only
x Normal operation x None x Normal operation
None None
Message Code
model.
x Turn power OFF prior to repair.
x Use memory card for the specific
settings
x Verify electric heat dipswitch
x Verify the installed electric
dipswitches is too large for heater
kits in shared data set
x Heater kit selected via
Ec
LARGE
HTR TOO
turning power ON. Memory card
x Insert memory card BEFORE
heater is valid for the air handler.
Check nameplate or
model.
turning power ON. Memory card
may be removed after data is
loaded.
memory card.
may be removed after data is
loaded.
memory card.
data is loaded.
x Turn power OFF prior to repair.
x Use memory card for the specific
settings
x Verify electric heat dipswitch
x Verify the installed electric
dipswitches is too small for heater
kits in shared data set
x Heater kit selected via
Ec
SMALL
HTR TOO
x Insert memory card BEFORE
heater is valid for the air handler.
x Turn power OFF before removing
x Error code will be cleared once
Specification Sheet applicable to
your model* for allowable heater
kit(s).
for the specific model. Re-
populate data using correct
memory card if required.
x Verify shared data set is correct
x
Check nameplate or
Specification Sheet applicable to
your model* for allowable heater
kit(s).
x Turn power OFF before removing
x Verify shared data set is correct
for the specific model. Re-
populate data using correct
x Error code will be cleared once
memory card if required.
data is loaded.
x Turn power OFF prior to repair.
x Verify electric heat dipswitch
x Heater kit selected via
Ec
NO HTR
model.
x Use memory card for the specific
x Insert memory card BEFORE
settings
heater is valid for the air handler.
x Verify the installed electric
dipswitches is doesn’t match
heater kits in shared data set
MATCH
turning power ON. Memory card
Check nameplate or
may be removed after data is
loaded.
memory card.
data is loaded.
x Turn power OFF before removing
x Error code will be cleared once
Specification Sheet applicable to
your model* for allowable heater
kit(s).
for the specific model. Re-
populate data using correct
x Verify shared data set is correct
x Turn power OFF prior to repair.
x Replace fuse with 3-amp
voltage wiring
memory card if required.
x Short in low voltage wiring x Locate and correct short in low
Not
Displayed
Not
Displayed
automotive type
module fuse with 3A automotive
fuse.
x Turn power OFF prior to repair.
x Replace integrated control
power to air handler and
integrated control module.
x Assure 208/230 volt and 24 volt
x Check integrated control module
24 volt wire improperly
connected or loose
x Manual disconnect switch OFF or
x Blown fuse or circuit breaker
EE
FAULT
INTERNAL
x Replace integrated control
fuse (3A). Replace if necessary.
x Integrated control module has an
module with correct replacement
x Check for possible shorts in
internal fault
part
x Read precautions in “Electrostatic
208/230 volt and 24 volt circuits.
Repair as necessary.
Discharge” section of manual.
module.
x Replace bad integrated control
Fault Description
LED Codes
Diagnostic/Status
Symptoms of Abnormal Operation
(Communicating & Non-communicating
dipswitches is too large
for heater kits specified
x Normal operation
x Heater kit selected via
in shared data set
x Heater kit selected via
dipswitches is too small
for heater kits specified
in shared data set
x Heater kit selected via
dipswitches does not
heater kits specified in
shared data set
x Open Fuse
to air handler or no 24
volt power to integrated
control module
breaker
module has an internal
x No 208/230 volt power
x Blown fuse or circuit
fault.
x Integrated control
ON
1 Flash
1 Flash
1 Flash
5 Flashes
None
Thermostat)
W1 or Auxiliary/Emergency heat
provides the indicated error code.
icon illuminated
x LED display is ON continuously
x Electric heaters fail to energize on a call for
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
Handler” message
x ComfortNet thermostat scrolls “Check Air
x Electric heat airflow is higher than
expected on a call for W1 or
Auxiliary/Emergency heat
provides the indicated error code.
x Integrated control module LED display
x Electric heat airflow is higher than
expected on a call for W1 or
Auxiliary/Emergency heat
provides the indicated error code.
x Integrated control module LED display
provides the indicated error code.
Power”
provides no signal.
icon illuminated
x No air handler operation.
x Integrated control module LED display
x ComfortNet thermostat displays “Battery
x Air handler fails to operate
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
Handler” message
x ComfortNet thermostat scrolls “Check Air
20
Page 21
T
ROUBLESHOOTING
C
HART
Notes & Cautions
repair
specific model.
BEFORE turning power
ON. Memory card may be
removed after data is
loaded.
x Turn power OFF prior to
x Use memory card for the
x Insert memory card
x Turn power OFF before
removing memory card.
x Error code will be cleared
repair
specific model.
BEFORE turning power
ON. Memory card may be
removed after data is
loaded.
removing memory card.
once data is loaded.
x Turn power OFF prior to
x Use memory card for the
x Insert memory card
x Turn power OFF before
x Error code will be cleared
once data is loaded.
Corrective Actions
for the specific model. Re-
populate data using correct
x Populate shared data set using
memory card.
memory card if required.
x Verify shared data set is correct
Possible Causes
has been rejected by integrated
shared data.
x Air handler does not contain any
d0
x Shared data set on memory card
d4
control module
ComfortNet ™
Thermostat Only
Fault Description
LED Codes
Diagnostic/Status
Message Code
Thermostat)
DATA
NO NET
x Data not yet on network.
9 Flashes
INVALID
MC DATA
data.
x Invalid memory card
11 Flashes
Symptoms of Abnormal Operation
provides indicated error code.
icon illuminated.
(Communicating & Non-communicating
x Air handler fails to operate.
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
Handler” message.
x ComfortNet thermostat scrolls “Check Air
operation.
provides indicated error code.
icon illuminated.
x Operation different than expected or no
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
Handler” message.
x ComfortNet thermostat scrolls “Check Air
21
Page 22
T
ROUBLESHOOTING
C
HART
Notes & Cautions
repair
with correct replacement
x Replace circulator motor
part.
x Turn power OFF prior to
x Turn power OFF prior to
repair
with correct replacement
part.
x Replace circulator motor
x Replace integrated control
module with correct
replacement part.
x Turn power OFF prior to
repair
replacement part.
x Replace motor with correct
x Use memory card for the
specific model
x Insert memory card
BEFORE turning power
ON. Memory card may be
removed after data is
loaded.
removing memory card.
x Turn power OFF before
x Error code will be cleared
once shared data and
motor horse power match.
x Turn power OFF prior to
repair.
x Turn power OFF prior to
repair.
Corrective Actions
connection.
Replace if necessary.
connection.
x Tighten or correct wiring
Replace if necessary.
x Check circulator blower motor.
x Tighten or correct wiring
Replace if necessary.
x Check circulator blower motor.
x Check integrated control module.
x Verify circulator blower motor
horse power is the same
specified for the specific air
handler model. Replace is
necessary.
for the specific model. Re-
populate data using correct
memory card if required.
x Verify shared data set is correct
x Check filters for blockage.
Clean filters or remove
obstruction.
Remove obstruction. Verify all
registers are fully open.
sized for system. Resize/replace
ductwork if necessary.
installation requirements.
grills/registers, duct system, and
air handler/coil air inlet/outlet for
x Check ductwork for blockage.
x Verify ductwork is appropriately
x See "Installation Instructions" for
blockages.
x Check filters, filter
Possible Causes
b1
circulator motor control leads.
x Loose wiring connection at
x Failed circulator blower motor.
x Failed integrated control module.
circulator motor power leads or
circulator motor power leads
disconnected.
x Loose wiring connection at
b0
x Failed circulator blower motor.
b2
x Incorrect circulator blower motor
in air handler.
integrated control module.
x Incorrect shared data set in
x Blocked filters.
b3
change in speed or torque, sudden
blockage of air handler/coil air
inlet or outlet.
filters, very restrictive ductwork,
blockage of air handler/coil air
x Restrictive ductwork.
x Undersized ductwork.
x High ambient temperatures.
x Abnormal motor loading, sudden
b4
inlet or outlet.
x High loading conditions, blocked
ComfortNet ™
Thermostat Only
Fault Description
LED Codes
Diagnostic/Status
Message Code
Thermostat)
MOTOR
NOT RUN
is not running when it
should be running.
x Circulator blower motor
6 Flashes
COMM
MOTOR
module has lost
communications with
x Integrated control
6 Flashes
circulator blower motor.
MOTOR
MISMATCH
horse power in shared
data set does not match
x Circulator blower motor
6 Flashes
circulator blower motor
LIMITS
MOTOR
horse power.
x Circulator blower motor
6 Flashes
is operating in a power,
temperature, or speed
limiting condition.
TRIPS
MOTOR
senses a loss rotor
control.
x Circulator blower motor
6 Flashes
x Circulator blower motor
senses high current.
Symptoms of Abnormal Operation
provides indicated error code.
icon illuminated.
Handler” message.
provides indicated error code.
icon illuminated.
(Communicating & Non-communicating
x Air handler fails to operate.
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check Air
x Air handler fails to operate.
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
Handler” message.
x ComfortNet thermostat scrolls “Check Air
provides indicated error code.
icon illuminated.
x ComfortNet thermostat “Call for Service”
Handler” message.
x ComfortNet thermostat scrolls “Check Air
x Air handler fails to operate.
x Integrated control module LED display
performance.
x Air handler operates at reduced
provides b3 error code.
x Airflow delivered is less than expected.
x Integrated control module LED display
provides indicated error code.
icon illuminated.
x ComfortNet thermostat “Call for Service”
Handler” message.
x ComfortNet thermostat scrolls “Check Air
x Air handler fails to operate.
x Integrated control module LED display
22
Page 23
T
ROUBLESHOOTING
C
HART
Notes & Cautions
repair
replacement part.
x Turn power OFF prior to
x Replace motor with correct
x Replace wheel with correct
replacement part.
x Turn power OFF prior to
repair.
x Turn power OFF prior to
repair.
replacement part(s).
x Replace with correct
x Use memory card for the
repair.
specific model.
x Turn power OFF prior to
Corrective Actions
Verify line voltage to blower is
within the range specified on the
air handler rating plate.
obstructions. Remove and
repair/replace wheel/motor if
necessary.
shaft rotation and motor.
Replace motor if necessary.
x Check circulator blower for
x Check power to air handler.
x Check circulator blower motor
installation requirements.
Verify control is populated with
correct shared data set. See data
x See "Installation Instructions" for
errors above for details.
x Check integrated control module.
x Check for locked rotor condition
(see error code above for
details).
x Check filters for blockage.
Clean filters or remove
obstruction.
Remove obstruction. Verify all
registers are fully open.
sized for system. Resize/replace
x Check ductwork for blockage.
ductwork if necessary.
x Verify ductwork is appropriately
Possible Causes
handler.
b6
handler.
x High AC line voltage to air
x Low AC line voltage to air
x High ambient temperatures.
x Error with integrated control
b7
module.
condition.
x Motor has a locked rotor
b9
x Blocked filters.
x Restrictive ductwork.
x Undersized ductwork.
housing.
bearings.
x Obstruction in circulator blower
x Seized circulator blower motor
x Failed circulator blower motor.
b5
ComfortNet ™
Thermostat Only
Fault Description
LED Codes
Diagnostic/Status
Symptoms of Abnormal Operation
(Communicating & Non-communicating
ROTOR
Message Code
MTR LCKD
fails to start 10
x Circulator blower motor
6 Flashes
Thermostat)
x Air handler fails to operate.
x Integrated control module LED display
consecutive times.
provides indicated error code.
Service” icon illuminated.
x ComfortNet™ thermostat “Call for
x ComfortNet thermostat scrolls “Check Air
MOTOR
6 Flashes
Handler” message.
x Circulator blower motor
x Air handler fails to operate.
VOLTS
shuts down for over or
under voltage condition.
provides indicated error code.
x Integrated control module LED display
shuts down due to over
x Circulator blower motor
icon illuminated.
x ComfortNet thermostat “Call for Service”
MOTOR
PARAMS
temperature condition on
power module.
does not have enough
information to operate
properly.
x Circulator blower motor
6 Flashes
LOW ID
AIRFLOW
consecutive times.
x Motor fails to start 40
demanded.
x Airflow is lower than
6 Flashes
Handler” message.
provides indicated error code.
icon illuminated.
Handler” message.
performance or operates on low stage
when high stage is expected.
x ComfortNet thermostat scrolls “Check Air
x Air handler fails to operate.
x Integrated control module LED display
x ComfortNet thermostat “Call for Service”
x ComfortNet thermostat scrolls “Check Air
x Air handler operates at reduced
provides indicated error code.
x Integrated control module LED display
23
Page 24
W
A
IRING
D
IAGRAMS
WARNING
HIGH VOLTAGE!
MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO SO
DISCO NNECT ALL POWER BEFORE SERVICING.
MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
FL
TL
HTR1
FL
TL
HTR2
FL
TL
HTR3
FL
TL
HTR4
PU
BL
RD
BK
M1
M3
YL
M4
RD
M2
R1
BK
BK
RD
YL
BL
BK
RD
FOUR (4) ELEMENT ROWS
L2
L1
L1
L2
GND
INDOOR
IR
CIRCULATOR
BLWR
208/230 VAC
24 VAC
HEAT SEQUENCER R1
HEAT SEQUENCER R2
BK
RD
YL
BL
BL
RD
M5
M7
M8
M6
R2
WH
L2
GND
40 VA TRANSFORMER
INDO OR
AIR
CIRCULATOR
BLWR
1
2
3
4
5
6
7
8
9
2
CFM LED
STATUS
LED
SEE NOTE 6
FL
TL
HTR2
FL
TL
HTR1
BK
RD
M1
M3
R
M2
M4
RD
BK
BK
RD
L1
L2
TWO (2) ELEMENT ROWS
TWO (2) ELEMENT ROWS
3
RD
2
1
1
COOL
BL
ADJUST
DELAY
DEHUM
DIP S WITCHE S
BIAS
BIAS
CIRCULATOR BLOWER
CIRCULATOR BLOWER
4
3
2
1
BK
SEE NOTE 5
UNUSED
TERM
1 2 3
4
5
RD
PU
BL
WH
HEAT
ELEC
RX LED
BK
RD
AF
BK
BK
1
2
3
4
5
6
7
8
9
9
RD
RD
TH
TH
FUSE
FUSE
DEHUM
DEHUM
W2
W2
GN
GN
Y2
Y2
Y1
Y1
W1
W1
RD
RD
GND
GND
O
O
G
G
C
C
R
R
2
2
1
1
BL
BL
TR
TR
COM
COM
24 V
24 V 3 A
3 A
GND
GND
GN
GN
FL
FL
FL
YL
RD
BK
L2
L1
L1
L2
24 V THERMOSTAT CONNECT IONS
24 V THERMOSTAT CONNECT IONS
HTR1
BK
TL
TL
RD
HTR2
TL
HTR3
YL
RD
BK
BL
M1
M3
M1
M2
M2
M4
R1
R2
BK
RD
YL
BK
RD
L2
L2L1L1
THREE (3) ELEMENT ROWS
THREE (3) ELEMENT ROWS
DISCONNECT
L1
FUSE 3 A
R
R
24V THERMOSTAT CONNECTIONS
24V THERMOSTAT CONNECTIONS
W1
W1
W2
W2
Y1
Y1Y1
TO
Y2
Y2
MICRO
G
G
O
O
DEHUM
DEHUM
C
C
BK
1
2
PU
3
RD
BL
4
BR
5
WH
6
7
8
9
L1
TH
W1 (1)
W2 (2)
+VDC (1)
RX (2 )
TX (3)
GND (4)
TR
COM
INTEGRATED CONTROL MODULE
FL
HTR1
TL
BK
BK
RD
BK
M1
R
M2
BK
BK
L1
L2
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EX
NOTE: WHEN INSTALLING HEATER KIT, ENSURE SPEED TAP DOES NOT EXCEED MINIMUM BLOWER SPEED (MBS) SPECIFIED FOR THE AIRHANDLER/HEATER
KIT COMBINATION ON THIS UNIT'S S&R PLATE. AFTER INSTALLING OPTION AL HEAT KIT, MARK AN "X" IN THE PROVIDED ABOVE.
KIT COMBINATION ON THIS UNIT'S S&R PLATE. AFTER INSTALLING OPTION AL HEAT KIT, MARK AN "X" IN THE PROVIDED ABOVE.
MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS IN STALLED. NO MARK INDICATES NO HEAT KIT INSTALLED.
MARK ACCORDING TO NUMBER OF HEATER ELEMENT ROWS IN STALLED. NO MARK INDICATES NO HEAT KIT INSTALLED.
PL2
PL1
2
2
3
3
1
1
6
6 5
5
4
4
7
7
8
8 9
9
SEE
NOTE
BK
7
RD
PU
BL
WH
RD
ONE (1) ELEMENT ROWS
RD
RD
BK
BK
WH
BR
BL
4
DIAGNOSTIC
LED
3
1 2
3 4
LEARN
BL
GY
BK
RD
ECM MOTOR
HARNESS
COLOR CODES: PK PINK BR BROWN
BK
1
2
3
BL
4
5
BR
6
7
8
9
WH WHITE BL BLUE
GY GRAY
RD RED YL YELLOW
OR ORANGE
PU PURPLE GN GREEN
BK BLACK
LOW VOLTAGE (24V)
LOW VOLTAGE FIEL D
HI VOLTAGE (230V)
HI VOLTAGE FIELD
JUNCTION
TERMINAL
IN TERNAL TO
INTEGRATED CONTROL
EQUIPMENT GND
FIELD GND
FIELD SPLI CE
RESISTOR
OVERCURRENT
PROT. DEVICE
PLUG CON NEC TIO N
NOTES:
1. PLACE RED WIRES ON TRANSFORMER TERMINAL 2 FOR 208 VAC OPERATION.
2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED
L2
WHEN SERVICING.
3. IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105°C. USE COPP ER CONDUC TORS ON LY.
4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C AND LOCAL CO DES.
5. TO RECALL THE LAST 6 FAULTS, MOST RECEN T TO LE AST RECE NT, DEP RES S SWITCH FOR MORE THAN 2 SECONDS WHILE IN STANDBY (N THERMOSTAT INPUTS)
6. BIAS AND TERM DIP SWITCHES MUST BE IN "ON" POSITION. RED STATUS LED PROVIDES NETWORK STATUS. GREEN RX LED IND ICATE S NETWOR K TRAFFI C. USE LEARN BUTTON TO RESET NETWORK.
7. DISCARD CONNECTOR PL1 WHEN INSTALLING OPTIONAL HEAT KIT.
GND
0140A00039-D
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
24
Loading...