Goodman AVPTC42D14, AVPTC48D14, AVPTC30C14, AVPTC24B14, AVPTC60D14 Installation Manual

...
AVPTC**14**
®
AIR HANDLERS INSTALLATION & OPERATING INSTRUCTIONS
1 Important Safety Instructions ....................................................................2
2 Shipping Inspection ..................................................................................2
2.1 Parts ..............................................................................................3
2.2 Handling ........................................................................................3
3 Codes & Regulations................................................................................3
4 Replacement Parts ...................................................................................3
5 Pre-Installation Considerations................................................................3
5.1 Preparation....................................................................................3
5.3 Interconnecting Tubing..................................................................3
5.4 Clearances ....................................................................................3
5.5 Horizontal Applications ..................................................................4
6 Installation Location.................................................................................4
6.1 Upflow Installation .........................................................................4
6.2 Horizontal Left Installation .............................................................4
6.3 Downflow/Horizontal Right Installation ..........................................4
7 Refrigerant Lines ......................................................................................7
7.1 Tubing Size....................................................................................7
7.2 Tubing Preparation........................................................................7
7.3 Tubing Connections for TXV Models.............................................7
8 Condensate Drain Lines ...........................................................................7
9 Ductwork...................................................................................................8
9.1 Return Ductwork ...........................................................................8
10 Return Air Filters .....................................................................................8
11 Electric Heat ...........................................................................................9
12 Electrical and Control Wiring ................................................................10
12.1 Building Electrical Service Inspection .......................................10
12.2 Wire Sizing ................................................................................10
12.3 Maximum Overcurrent Protection (MOP) ..................................10
12.4 Electrical Connections – Supply Voltage...................................10
12.4.1 Air Handler Only (Non-Heat Kit Models) ................................ 11
12.4.2 Air Handler - Non-Circuit Breaker Heat Kits ...........................11
12.4.3 Air Handler With Circuit Breaker Heat Kit...............................11
12.5 Low Voltage Connections..........................................................11
13 Achieving 2% Low Leakage Rate.........................................................11
14 Start-Up Procedure...............................................................................11
15 Regular Maintenance ........................................................................... 11
Circulator Blower..........................................................................................14
Troubleshooting ...........................................................................................18
ComfortNet™ System ..................................................................................19
Start-Up Procedure ......................................................................................21
Regular Maintenance ...................................................................................21
Troubleshooting ...........................................................................................24
Diagnostic Codes .........................................................................................28
Wiring Diagrams ..........................................................................................29
© 2013-2014 Goodman Manufacturing Company, L.P. 5151 San Felipe, Suite 500, Houston, TX 77056 www .goodmanmfg.com - or - www.amana-hac.com
P/N: IO-443D Date: August 2014
RECOGNIZE
THIS SYMBOL AS A
SAFETY PRECAUTION.
ATTENTION
INSTALLING
PERSONNEL
Prior to installation, thoroughly famil­iarize yourself with this Installation Manual. Observe all safety warnings. During installation or repair, caution is to be observed. It is your responsibility to install the product safely and to edu­cate the customer on its safe use.
is a registed trademark of Maytag Corporation or its related companies and is used under license to
Goodman Company, L.P., Houston, TX, USA. All rights reserved.
1 Important Safety Instructions
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner’s and installer’s responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of personal injury, property damage, and/or product damage.
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
Install ati on an d re pa ir of t hi s u nit sho ul d b e p erform ed
by indiv id uals me et in g the re qui re men ts of an
ONLY “entry level technician” as specified by the Ai r-Co ndi ti on in g, H eati ng a nd Re fri g era ti on Inst i tu te (AHRI). Attempting to install or repair this unit without such ba ck grou nd may re sul t i n p rod uct da mag e, personal inju ry or death.
This product is factory-shipped for use with 208/240/1/60 electrical power supply. reconfigure this air handler to operate with any other power supply.
To avoid property damage, personal injury or death due to electrical shock, this unit MUST have an uninterrupted, unbroken electrical ground circuit may consist of an appropriately sized electrical wire connecting the ground lug in the unit control box to the building electrical service panel. Other meth ods of gro unding are permitted if pe rfo rmed in accordance with the National Electric Code (NEC)/A mer ican National Stan dard s Inst itut e (ANSI)/ Nati onal Fire P rotec tion Assoc iation (NFP A) 70 and local /s ta te c ode s. I n Canad a, e lect ri ca l gro unding is to be in accordance with t he Cana di an El ec tr ic C ode (CSA) C22.1.
, at a mini mum,
DO NOT
electrical ground. The
Do not connect to or use any device that is not design­certified by Goodman for use with this unit. Serious property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the use of such non-approved devices.
T o prev en t th e ri sk of pro perty damage, personal injury , or dea th, do not store co mb ustible mater ials or use gasoline or other flammable liquids or vapo rs in the vicin ity of this uni t.
When installing or servicing this equipment, safety clothing, including hand and eye protection, is strongly recommended. If installing in an area that has special safety requirements (hard hats, etc.), bserve these requirements.
o
B10259-216
2 Shipping Inspection
Always transport the unit upright; laying the unit on its side or top during transit may cause equipment damage. The installer should inspect the product upon receipt for shipping damage and subsequent investigation is the responsibility of the carrier. The installer must verify the model number, specifications, electrical characteristics, and accessories are correct prior to installation. The distributor or manufacturer will not accept claims from dealers for transportation damage or installation of incorrectly shipped units.
2
2.1 Parts
Also inspect the unit to verify all required components are present and intact. Report any missing components immedi­ately to Goodman® or to the distributor. Use only factory authorized replacement parts (see Section 5). Make sure to include the full product model number and serial number when reporting and/or obtaining service parts.
2.2 Handling
Use caution when transporting/carrying the unit. Do not move unit using shipping straps. Do not carry unit with hooks or sharp objects. The preferred method of carrying the unit after arrival at the job site is to carry via a two-wheel hand truck from the back or sides or via hand by carrying at the cabinet corners.
3 Codes & Regulations
This product is designed and manufactured to comply with applicable national codes. Installation in accordance with such codes and/or prevailing local codes/regulations is the responsibility of the installer. The manufacturer assumes no responsi­bility for equipment installed in violation of any codes or regulations.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduc­tion and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. Should you have any questions please contact the local office of the EPA and/or refer to
EPA’s website www.epa.gov.
4 Replacement Parts
When reporting shortages or damages, or ordering repair parts, give the complete product model and serial numbers as stamped on the product. Replacement parts for this product are available through your contractor or local distributor. For the location of your nearest distributor consult the white business pages, the yellow page section of the local telephone book or contact:
CONSUMER AFFAIRS
GOODMAN MANUFACTURING COMPANY, L.P.
7401 SECURITY WAY
HOUSTON, TEXAS 77040
(877) 254-4729
5 Pre-Installation Considerations
5.1 Preparation
Keep this document with the unit. Carefully read all instructions for the installation prior to installing product. Make sure each step or procedure is understood and any special considerations are taken into account before starting installation. Assemble all tools, hardware and supplies needed to complete the installation. Some items may need to be purchased locally. Make sure everything needed to install the product is on hand before starting.
5.2 System Matches
The entire system (combination of indoor and outdoor sections) must be manufacturer approved and Air-Conditioning, Heating, and Refrigeration Institute (AHRI) listed. NOTE: Installation of unmatched systems is not permitted and will void the product warranty.
5.3 Interconnecting Tubing
Give special consideration to minimize the length of refrigerant tubing when installing air handlers. Refer to Remote Cooling/Heat Pump Service Manual RS6200006, and TP-107 Long Line Set Application R-410A for tubing guidelines. If possible, allow adequate length of tubing such that the coil may be removed (for inspection or cleaning services) from the cabinet without disconnecting the tubing.
5.4 Clearances
The unit clearance from a combustible surface may be 0". However, service clearance must take precedence. A mini­mum of 24" in front of the unit for service clearance is required. Additional clearance on one side or top will be required for electrical wiring connections. Consult all appropriate regulatory codes prior to determining final clearances. When installing this unit in an area that may become wet (such as crawl spaces), elevate the unit with a sturdy, non-porous material. In installations that may lead to physical damage (i.e. a garage) it is advised to install a protective barrier to prevent such damage. Always install units such that a positive slope in condensate line (1/4" per foot) is allowed.
3
5.5 Horizontal Applications
If installed above a finished living space, a secondary drain pan (as required by many building codes), must be installed under the entire unit and its condensate drain line must be routed to a location such that the user will see the condensate discharge.
6 Installation Location
NOTE: These air handlers are designed for indoor installation only.
The AVPTC**14** product line may be installed in one of the upflow, downflow, horizontal left or horizontal right orientations as shown in Figures 2, 3, 4 and 5. The unit may be installed in upflow or horizontal left orientation as shipped (refer to specific sections for more information).
Minor field modifications are necessary to convert to downflow or horizontal right as indicated in below sections.
6.1 Upflow Installation
No field modifications are mandatory however to obtain maximum efficiency, the horizontal drip shield must be removed.
Drip Shield Removal: Refer to Figure 1, remove the two (2) screws that secure the drip shield support brackets to the condensate collectors (one screw per side). Remove the two (2) screws that secure the drip shield to the drain pan. The drip shield and drip shield brackets may now be removed.
The bottom left drain connection is the primary drain for this application and condensate drain line must be attached to this drain connection. The top connection of the three drain connections on the drain pan must remain plugged for this application. The bottom right drain connection is for the sec­ondary drain line (if used).
6.2 Horizontal Left Installation
No field modifications are permissible for this application. The bottom right drain connection is the
primary drain for this application and condensate drain line must be attached to this drain connection. The top con­nection of the three drain connections on the drain pan must remain plugged
CMK0001 CMK0002 CMK0003 CMK0007
AVPTC42D14** AVPTC48D14** AVPTC30C14** AVPTC24B14**
MODEL LISTS FOR HORIZONTAL LEFT KITS
AVPTC60D14** AVPTC36C14**
for this application. The bottom left drain connection is for the secondary drain line (if used).
Screw
Screw
DRIP SHIELD REMOVAL
Figure 1
AVPTC48C14**
Table 1
Use condensate management kit if equipment is installed in high humidity condition (for example: 70% or higher).
6.3 Downflow/Horizontal Right Installation
IMPORTANT NOTE: In the downflow application, to prevent coil pan “sweating”, a downflow kit (DFK) is available through your local Goodman distributor. The DFK is not supplied with the air handler and is required by Goodman on all downflow installations. See Table 2 for the correct DFK and follow the instructions provided for installation.
Refer to Figure 6 and 7 for the location of the components
MODEL LIST FOR DOWNFLOW KITS
DFK-B
Downflo w Kit
AVPTC24B14** AVPTC30C14** AVPTC42D14**
DFK-C
Downf l o w Ki t
AVPTC36C14** AVPTC48D14** AVPTC48C14** AVPTC60D14**
DFK-D
Downflo w Kit
DOWNFLOW KIT
Table 2
referenced in the following steps.
1. Before inverting the air handler, remove blower access panel and coil access panel. The coil access panel and tubing panel may remain screwed together during this procedure. Remove and retain the seven (7) screws securing the coil access panel to the cabinet and the six (6) screws securing the blower access panel to the cabinet.
2. Slide the coil assembly out using the drain pan to pull the assembly from the cabinet.
NOTE: DO NOT USE MANIFOLDS OR FLOWRATOR TO PULL THE COIL ASSEMBLY OUT. FAILURE TO DO SO MAY RESULT IN BRAZE JOINT DAMAGE AND LEAKS.
4
3. Removal of the center support is required on units with 21" wide cabinet. Remove and retain the two (2) screws that secure the center support to the cabinet. Remove the center support.
4. Using the drain pan to hold the coil assembly, slide the coil assembly back into the cabinet on the downflow brackets as shown in Figure 8.
5. Re-install the center support (if removed) using the two (2) screws removed in Step 4.
6. Re-install the access panels removed in Step 1 as shown in Figure 9.
7. The bottom left drain connection is the primary drain for this application and condensate drain line must be attached to this drain connection. The top connection of the three drain connections on the drain pan must remain plugged for this application. The bottom left drain connection is for the secondary drain line (if used).
UPFLOW
Figure 2
HORIZONTAL LEFT
Figure 4
DOWNFLOW
Figure 3
HORIZONTAL RIGHT
Figure 5
NOTE: If removing only the coil access panel from the unit, the filter access panel must be removed first. Failure to do so may result in panel damage.
5
Upper Tie Plate
Control Deck
Downflow Bracket
Center Support
Filter Bracket
Filter Acces s Panel
INTERNAL PART TERMINOLOGY
Figure 6
Blower Access Panel
Coil Access Panel
Secondary Drain Port for Horizontal Application
Thumb Screw
Secondary Dra in Port for Upflow/Downflow Application
EXTERNAL PART TERMINOLOGY
Figure 7
Tubing Panel
IMPORTANT NOTE:
Ensure coil slides o n the rails along the groove provided on the drain pan side walls. Failure to do so will resu lt in improper condensate drainage.
COIL INSTALLATION FOR DOWNFLOW
Figure 8
Coil Slides
on the
downflow bracket
ACCESS PANEL
CONFIGURATION FOR
DOWNFLOW OR
HORIZONTAL RIGHT
Figure 9
6
7 Refrigerant Lines
NOTE: Refrigerant tubing must be routed to allow adequate
access for servicing and maintenance of the unit. Do not install the air handler in a location that violates the
instructions provided with the condenser. If the unit is located in an unconditioned area with high ambient temperature and/ or high humidity, the air handler may be subject to nuisance sweating of the casing. On these installations, a wrap of 2" fiberglass insulation with a vapor barrier is recommended.
7.1 Tubing Size
For the correct tubing size, follow the specification for the condenser/heat pump.
7.2 Tubing Preparation
All cut ends are to be round, burr free, and clean. Failure to follow this practice increases the chances for refrigerant leaks. The suction line is spun closed and requires tub­ing cutters to remove the closed end.
NOTE: To prevent possible damage to the tubing joints, do not handle coil assembly with manifold or flowrator tubes. Always use clean gloves when handling coil as­semblies.
NOTE: The use of a heat shield is strongly recommended when brazing to avoid burning the serial plate or the finish of the unit. sensitive components such as service valves and TXV valves sensing bulb.
This product is factory-shipped with R410A and dry nitrogen mixture gas under pressure. Use appropriate service tools and follow these instructions to prevent injury .
A quenching cloth is strongly recommended to prevent scorching or marring of the equipment finish when brazin g close to the painted surfaces. Use brazing alloy of 5% minimum silver content.
CAUTION
Applying too muc h heat to any tube can melt the tube. T orc h heat required to braze tubes of various sizes must be proportiona l to th e size of th e tube. S er vice p er sonn el m u st use the appropriate he at level for the size of the tube being brazed.
Heat trap or wet rags must be used to protect heat
7.3 Tubing Connections for TXV Models
TXV models come with factory installed TXV with the bulb pre-installed on the vapor tube.
1. Remove refrigerant tubing panel or coil (lower) access panel.
2. Remove access valve fitting cap and depress the valve stem in access fitting to release pressure. No pressure indi­cates possible leak.
3. Replace the refrigerant tubing panel.
4. Remove the spin closure on both the liquid and suction tubes using a tubing cutter.
REFRIGERANT BULB MUST BE POSITIONED BETWEEN 10 & 2 O’CLOCK
REFRIGERANT BULB MUST BE POSITIONED BETWEEN 10 & 2 O’CLOCK
5. Insert liquid line set into liquid tube expansion and slide grom­met about 18" away from braze joint.
6. Insert suction line set into suction tube expansion and slide in­sulation and grommet about 18" away from braze joint.
7. Braze joints. Quench all brazed joints with water or a wet rag upon completion of brazing.
NOTE: The sensing bulb must be permanently located. A heat shield, heat trap, or wet rag must be used during brazing to prevent damage to
SUCTION LINE WITH SPIN CLOSURE
Figure 10
the TXV valve.
8. Replace access panels, suction line grommet, insulation and all screws.
RUBBER GROMMET
8 Condensate Drain Lines
The coil drain pan has a primary and a secondary drain with 3/4" NPT female connections. The connectors required are 3/4" NPT male, either
Suction Line Grommet
Figure 11
PVC or metal pipe, and should be hand tightened to a torque of no more than 37 in-lbs. to prevent damage to the drain pan connection. An insertion depth of approximately 3/8” to 1/2” (3-5 turns) should be expected at this torque.
7
1. Ensure drain pan hole is not obstructed.
2. To prevent potential sweating and dripping on to finished space, it may be necessary to insulate the condensate drain line located inside the building. Use Armaflex® or similar material.
A secondary condensate drain connection has been provided for areas where the building codes require it. Pitch all drain lines a minimum of 1/4" per foot to provide free drainage. Provide required support to the drain line to prevent bowing. If the secondary drain line is required, run the line separately from the primary drain and end it where condensate discharge can be easily seen.
NOTE: Water coming from secondary line means the coil primary drain is plugged and needs immediate attention. Insulate drain lines located inside the building or above a finished living space to prevent sweating. Install a condensate trap
to ensure proper drainage. NOTE: When units are installed above ceilings, or in other locations where damage from condensate overflow may occur,
it is MANDATORY to install a field fabricated auxiliary drain pan under the coil cabinet enclosure.
The installation must include a “P” style trap that is located as close as is practical to the evaporator coil. See Figure 12 for
If secondary drain is not installed, the secondary access must be plugged.
CAUTION
details of a typical condensate line “P” trap. NOTE: Trapped lines are required by many local codes. In the
absence of any prevailing local codes, please refer to the requirements listed in the Uniform Mechanical Building Code.
Drain
Connection
A drain trap in a draw-through application prevents air from being drawn back through the drain line during fan operation thus preventing con­densate from draining, and if connected to a sewer line to prevent sewer
Air Handler
2" MIN.
gases from being drawn into the airstream during blower operation. Field experience has shown condensate drain traps with an open verti-
cal Tee between the air handler and the condensate drain trap can im­prove condensate drainage in some applications, but may cause exces-
POSITIVE LIQUID SEAL REQUIRED
AT TRAP
3" MIN.
sive air discharge out of the open Tee. Goodman® does not prohibit this type of drain but we also do not recommend it due to the resulting air leakage. Regardless of the condensate drain design used, it is the
Figure 12
installer’s responsibility to ensure the condensate drain system is of suf­ficient design to ensure proper condensate removal from the coil drain pan.
Use of a condensate removal pump is permitted when necessary. This condensate pump should have provisions for shut­ting off the control voltage should a blocked drain occur. A trap must be installed between the unit and the condensate pump.
IMPORTANT NOTE: The evaporator coil is fabricated with oils that may dissolve styrofoam and certain types of plastics. Therefore, a removal pump or float switch must not contain any of these materials.
Tip: Priming the “P” trap may avoid improper draining at the initial installation and at the beginning of the cooling season.
9 Ductwork
This air handler is designed for a complete supply and return ductwork system. To ensure correct system performance, the ductwork is to be sized to accommodate 350-450 CFM per ton of cooling with
the static pressure not to exceed 0.5" in w.c. Refer to ACCA Manual D, Manual S and Manual RS for information on duct sizing and application. Flame retardant ductwork is to be used and sealed to the unit in a manner that will prevent leakage.
NOTE: A downflow application with electric heat must have an L-shaped sheet metal supply duct without any outlets or registers located directly below the heater.
9.1 Return Ductwork
DO NOT LOCATE THE RETURN DUCTWORK IN AN AREA THAT CAN INTRODUCE TOXIC, OR OBJEC­TIONABLE FUMES/ODORS INTO THE DUCTWORK. The return ductwork is to be connected to the air han-
Do not operate this product without all the ductwork attached.
dler bottom (upflow configuration).
10 Return Air Filters
Each installation must include a return air filter. This filtering may be performed at the air handler using the factory filter rails or externally such as a return air filter grille. When using the factory filter rails, a nominal 16x20x1”, 20x20x1” or 24x20x1” (actual dimension must be less than 23-½”x20”) filter can be installed on a B, C and D cabinet respectively (the cabinet size is the seventh letter of the model number).
8
11 Electric Heat
Refer to the installation manual provided with the electric heat kit for the correct installation procedure. All electric heat must be field installed. If installing this option, the ONLY heat kits that are permitted to be used are the HKS series. Refer to the air handler unit’s Serial and Rating plate or the HKS specification sheets to determine the heat kits compatible with a given air handler. No other accessory heat kit besides the HKS series may be installed in these air handlers.
The heating mode temperature rise is dependent upon the system airflow, the supply voltage, and the heat kit size (kW) selected. Use data provided in Tables 3, 4 and 5 to determine the temperature rise (°F).
NOTE: For installations not indicated above the following formula is to be used:
TR = (kW x 3412) x (Voltage Correction) / (1.08 x CFM)
Where: TR = Temperature Rise
kW = Heater Kit Actual kW 3412 = Btu per kW VC* = .96 (230 Supply Volts)
= .92 (220 Supply Volts) = .87 (208 Supply Volts)
1.08 = Constant CFM = Measured Airflow
VC* (Voltage Correction)
NOTE: The Temperature Rise Tables can also be used to estimate the air handler airflow delivery. When using these tables for this purpose set the room thermostat to maximum heat and allow the system to reach steady state conditions. Insert two thermometers, one in the return air and one in the supply air. The temperature rise is the supply air temperature minus the return air temperature. Using the temperature rise calculated, CFM can be estimated from the TR formula above. See Technical Manual and/or Service Manual for more information.
CFM
8001219233137 1000 9 1519253044 1200 8 12152125374962 1400 7 11131821324253 1600 6 9 12 15 19 28 37 46 1800 5 8 10 14 16 25 33 41 2000 5 7 9 12 15 22 30 37
3 5 6 8 10 15 19/20 25
HEAT KIT NOMINAL kW
230/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
Table 3
CF M
3 5 6 8 10 15 19/20 25
8001017212833 10008 1317222740 12007 11141922334556 14006 10121619293848 1600 5 8 10 14 17 25 33 42 18005 7 9 1215223037 20004 7 8 1113202733
HEAT KIT NOMINAL kW
208/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
Table 5
CFM
8001118223035 1000 9 14 18 24 28 42 1200 7 12 15 20 24 35 47 5 9 1400 6 10 13 17 20 30 40 5 1 1600 6 9 11 15 18 27 35 44 1800 5 8 10 13 16 24 31 39 2000 4 7 9 12 14 21 28 35
3 5 6 8 10 15 19/20 25
HEAT KIT NOMINAL kW
220/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
Table 4
Heater Kit (Kw)
AVPTC24B14 AVPTC30B14 AVPTC36C14 AVPTC48C14 AVPTC42D14 AVPTC48D14 AVPTC60D14
Please refer to page 16 for specific heater kit application guidelines.
3 5 6 8 1 0 15 19 20 21 or 25 550 650 700 800 850 NR NR NR NR 600 700 750 875 950 NR NR NR NR
NR 850 900 1000 1200 1440 1500 1500 NR NR 850 900 1000 1200 1440 1500 1500 NR
850** 1250 1300 1500 1550 1720 NR 1800 NR
††
NR 1250 1300 1500 1550 1720 NR 1815 1850
†††
NR 1250 1300 1500 1550 1780 NR 1850 1850
MINIMUM CFM REQUIRED FOR HEATER KITS
Table 6
9
12 Electrical and Control Wiring
IMPORTANT: All routing of electrical wiring must be made through provided electrical knockouts. Do not cut, puncture or
alter the cabinet for electrical wiring.
12.1 Building Electrical Service Inspection
This unit is designed for single-phase electrical supply only. DO NOT OPERATE ON A THREE­PHASE POWER SUPPLY. Measure the power supply to the unit. The supply voltage must be measured and be in agreement with the unit nameplate power requirements and within the range shown.
12.2 Wire Sizing
Wire size is important to the operation of your equip­ment. Use the following check list when selecting the appropriate wire size for your unit.
Wire used must carry the Minimum Circuit Ampac-
ity (MCA) listed on the unit’s Series and Rating Plate.
Nominal Input Minimum Voltage Maximum Voltage
208-240 197 253
ELECTRICAL VOLTAGE
Table 7
FIRE HAZARD! To avoid the risk of property damage, personal injury or fire, use only copper conductors.
Refer to the NEC (USA) or CSA (Canada) for wire siz­ing. The unit MCA for the air handler and the optional electric heat kit can be found on the unit Series and Rating Plate.
Wire must be sized to allow no more than a 2%
voltage drop from the building breaker/fuse panel to the unit.
Wires with different insulation temperature rating have varying ampacities - be sure to check the temperature rating used.
Refer to the latest edition of the National Electric Code or in Canada the Canadian Electric Code when deter­mining the correct wire size.
12.3 Maximum Overcurrent Protection (MOP)
Every installation must include an NEC (USA) or CEC (Canada) approved overcurrent protection device. Also, check with local or state codes for any special regional requirements.
Protection can be in the form of fusing or HACR style circuit breakers. The Series and Rating Plate provides the maximum overcurrent device permissible.
NOTE: Fuses or circuit breakers are to be sized larger than the equipment MCA but not to exceed the MOP.
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death.
HIGH VOLTAGE! T o avoid prope rty dama ge , persona l injury or death due to el ect rical shock, this unit MUST have an uninterrupted, unbroken electrical ground circuit may consist of an appro pri at ely sized electrical wire connecting the ground lug in the unit control box to the building electrica l s ervice panel. Other methods of grounding are p ermitted if pe rformed in ac co rda n ce w ith th e N a tio na l E le ctr ic C ode (NEC) /Americ an Nation al Standar ds Institu te (ANSI)/National Fire Protection Assoc iation (NFPA ) 70 and local/state codes. In Canada, electrical gro unding is to be in ac co rda nce w ith t he Cana dian E lectric C ode (CSA) C22.1.
electrical ground. The
Top of
Cabinet
12.4 Electrical Connections – Supply Voltage
IMPORTANT NOTE: USE COPPER CONDUCTORS ONLY.
Knockouts are provided on the air handler top panel and sides of the cabinet to allow for the entry of the supply voltage conductors, as shown in Figure 13. If the knockouts on the cabinet sides are used for electrical conduit, an adapter ring must be used in order to meet UL1995 safety requirements. An NEC or CEC approved strain relief is to be used at this entry point. Some codes/munici­palities require the supply wire to be enclosed in conduit. Consult your local codes.
Side of
Cabinet
KNOCK-OUT FOR ELECTRICAL
CONNECTIONS
Figure 13
10
Loading...
+ 22 hidden pages