This boiler is tested and certificated for safety and performance.
It is therefore important that no alteration is made to the boiler,
without permission, in writing, from Hepworth Heating Ltd.
Any alteration not approved by Hepworth Heating Ltd., could
invalidate the certification, boiler warranty and may also infringe
the current issue of the Statutory Requirements, see Section
1.2.
CE MARK
This boiler meets the requirements of Statutory Instrument No.
3083 The boiler (Efficiency) Regulations, and therefore is
deemed to meet the requirements of Directive 92/42/EEC on
the efficiency requirements for new hot water boilers fired with
liquid or gaseous fuels.
Type test for purposes of Regulation 5 certified by: Notified body
0086.
Product/productioncertifiedby: Notified body 0086.
The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws
of the Member States relating to appliances burning gaseous
fuels.
2. Directive 73/23/EEC on the harmonization of the Laws
of the Member States relating to the electrical equipment
designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws
of the Member States relating to electromagnetic compatibility.
INFORMATION FOR THE INSTALLER AND
SERVICE ENGINEER.
Under Section 6 of The Health and Safety at Work Act 1974, we
are required to provide information on substances hazardous
to health.
CERAMIC FIBRE/INSULATION PADS,
GLASSYARN.
These can cause irritation to skin, eyes and the respiratory tract.
If you have a history of skin complaint you may be susceptible
to irritation. High dust levels are usual only if the material is
broken. Normal handling should not cause discomfort, but
follow normal good hygiene and wash your hands before
eating, drinking or going to the lavatory. If you do suffer irritation
of the eyes or severe irritation to the skin seek medical attention.
THERMOSTATS
These contain very small amounts of xylene in the sealed phial
and capillary. If broken, under normal circumstances the fluid
does not cause a problem, but in case of skin contact, wash with
cold water. If swallowed drink plenty of water and seek medical
attention.
CUT OFF DEVICES
Cut off devices with copper phial/bulb only.
Bulb contains activated charcoal and very small amounts of
chloroddifludromethane in the sealed phial and capillary. If
broken under normal circumstances the fluid does not cause a
problem. If there is irritation to the eyes or skin then seek
medical attention.
FLUE SEALANT
This contains cyclohexylaminosilane.
It may cause irritation of skin of sensitive persons. Wash contact
area with soap and water, if irritation occurs, seek medical
advice.
It will cause irritation on contact with eyes. If so, wash eye with
large amounts of fresh water for at least 15 minutes. If irritation
occurs, seek medical advice.
If swallowed drink plenty of milk and seek medical advice.
CONTENTS DESCRIPTION SECTION PAGE No.
INSTRUCTIONS
FOR USE
Introduction3
Lighting the Boiler5
General Data16
Water System28
INSTALLATION
INSTRUCTIONS
Boiler Location311
Flue412
Preparation514
Water and Condensate Connections616
Flue Installation717
Gas Connection820
Electrical Connection920
Commissioning1022
User Information1123
Please read these instructions and follow them for the safe and
economical use of your boiler.
This boiler is designed to provide central heating from a fully
pumped open vented or sealed water system with a fully indirect
cylinder.
The boiler is fully automatic in operation, having two user
controls, high/low control on the left and the control thermostat
on the right, see diagram 1.
The “high/low” control can set to “Low” during the summer
months.
Important Notice
This boiler is for use on natural gas (G20) as distributed in the
United Kingdom and Ireland, but may be converted for use on
L.P.G. Propane (G31) with the use of a conversion kit, i.e.
Energysaver 60, Kit No.444509.
If your boiler has been converted to use L.P.G. Propane the
following note applys:
Propane cylinders are under pressure and should never be
stored or used indoors residentially.
They should only be kept outside.
Under no circumstances should LPG Propane cylinders be
fitted or stored in basement areas or boiler house.
CONTROL
THERMOSTAT
0163M
KNOB
n
i
m
0
m
a
x
p
m
e
t
Diagram 1
Maintenance/Servicing
To ensure the continued efficient and safe operation of the
boiler it is recommended that it is checked and serviced as
necessary at regular intervals. The frequency of servicing will
depend upon the particular installation conditions and usage,
but in general once a year should be enough.
It is the Law that any servicing must be carried out by a
competent person.
To obtain service, please call your installer or Heatcall (Glowworm’s own service organisation) using the telephone number
given on the information plate, see diagram 2.
Please be advised that the ‘Benchmark’ logbook should be
completed by the installation engineer on completion of
commissioning and servicing.
All CORGI Registered Installers carry a CORGI ID card, and
have a registration number. Both should be recorded in your
boiler Logbook. You can check your installer is CORGI registered
by calling CORGI direct on :- 01256 372300.
7891
Gas Safety (Installation and Use) Regulations
In your interest and that of gas safety it is the Law that ALL gas
appliances are installed by a competent person in accordance
with the current issue of the above regulations.
Gas Leak or Fault
If a gas leak or fault exists or is suspected, the BOILER MUST
BE TURNED OFF, including the electrical supply and MUST
NOT BE USED UNTIL THE FAULT HAS BEEN PUT RIGHT.
Advice/help should be obtained from your installation/servicing
company or the local gas undertaking.
RESET BUTTON
INSTRUCTION LABEL
3
Diagram 2
221836B
Instructions for Use
150
Boiler Clearances
If fixtures are positioned close to the boiler, space must be left
as shown in diagram 3. Enough space must also be left in front
of the boiler to allow for servicing.
Boilers Installed in a Compartment or
Cupboard
If the boiler is installed in a cupboard or compartment do not
obstruct any ventilation openings.
Do not use the cupboard or compartment for storage.
Regularly make sure that the air vent openings are clear of
obstructions.
55
5
*
5
Cleaning
WARNING. This appliance contains metal parts (components)
and care should be taken when handling and cleaning, with
particular regard to edges.
Clean the casing occasionally by wiping it over with a damp
soapy cloth or dry polishing duster.
Do not use an abrasive cleaner.
Protection Against Freezing
If the boiler is to be out of use for any long period of time during
severe weather conditions we recommend that the whole of the
system, including the boiler, be drained off to avoid the risk of
freezing up. Make sure that, if fitted, the immersion heater in the
cylinder is switched off.
If you have a sealed water system contact your installation/
servicing company as draining, refilling and pressurising must
be carried out by a competent person.
Boiler Electrical Supply
WARNING. The boiler must be earthed.
The boiler must only be connected to a 240V~50Hz supply,
protected by a 3A fuse.
All wiring must be in accordance with the current issue of
BS7671.
The colours of three core flexible cable are:
Brown - live, Blue - neutral, green and yellow - earth.
As the markings on your plug may not correspond with these
colours, continue as follows:
The wire coloured blue must be connected to the terminal
marked “N” or “Black”.
The wire coloured brown must be connected to the terminal
marked “R” or “Red”.
The wire coloured green and yellow must be connected to the
terminal marked “E”, “Green” or the earth symbol
.
100
INCREASE THIS DIMENSION TO
*
25mm FROM COMBUSTIBLE MATERIAL
5
*
5
*
500
PERMANENT
SURFACE
CLEARANCE OPPOSITE TO FLUE EXIT
MUST BE ADEQUATE FOR THE
INTERNAL INSTALLATION
Diagram 3
Electrical Supply Failure
Failure of the electrical supply will cause the burner to go out.
Should this happen, operation of the boiler will normally resume
after the electrical supply is restored.
If the burner does not relight after an electrical supply failure the
overheat device may need resetting, press the reset button on
the underside of the boiler, see diagram 2.
221836B
4
Instructions for Use
Overheat Safety Cutoff
If the cutoff operates on any other occasion than an electrical
failure, press the reset button as stated in “Electrical Supply
Failure”.
If the boiler fails to relight contact your installation/servicing
company.
To Turn the Boiler On
Sealed Water Systems.
CAUTION A sealed water system must be filled and pressurised
by a competent person.
Only light the boiler when you are sure that the system and
boiler have been filled and pressurised.
The pressure gauge should show at least 0.7bar, anything less
than this figure could indicate a leak and you MUST contact your
installation/servicing company.
If there is any doubt about the boiler and system being full of
water consult your installation/servicing company.
All Systems
Turn the electrical supply on to the boiler and check that any
remote controls are set to your requirements (refer to
manufacturer’s instructions for these items).
On demand, the orange light will come on.
Turn the left hand switch to “high” flame.
Turn the control thermostat knob, at the right, clockwise to any
position between “MIN” and “MAX., see diagram 1. The
maximum setting is about 82
The boiler will not light between “O” and “MIN”.
The boiler lighting operation is now automatic as follows:
The fan operates, followed by an ignition spark until the burner
lights on low flame after a short period it will go to high flame and
the green light will come on.
The burner will remain alight until switched off by the control
thermostat or other remote control.
If the control thermostat is turned “Off”, by hand, wait at least 30
seconds before turning on again.
When the boiler thermostat is satisfied the burner and green
light will go out.
When the system controls are satisfied the burner, orange and
green lights will go out.
The automatic lighting sequence will operate again when heat
is required.
The “high/low” switch should be set to “high” for winter use, but
when domestic hot water only is required in the summer it can
be turned to “low”.
If no light comes on you should contact your installation/
servicing company, to check the controls, although the system
may be working.
o
C (180oF).
To Turn the Boiler Off
For short periods, turn thermostat control knob anti-clockwise
until “O” is against the setting point. To relight the main burner,
turn the thermostat knob clockwise to any setting between ”MIN”
and “MAX”.
For longer periods, turn the thermostat control knob anticlockwise until “O” is against the setting point and switch off the
electrical supply to the boiler.
To relight follow the sequence given above.
Note: If the burner goes out for any reason, wait 30 seconds
before relighting.
Condensation Pluming
Like all condensing boilers this appliance will produce a plume
of condensation from the flue terminal in cool weather. This is
due to the high efficiency and hence low flue gas temperature
of the boiler.
5
221836B
1 General
119
640
460
360
50
25
65
710
42
300
124
70
32
CAPPED OFF
FLUE
TERMINAL
DETAIL
63
Ensure flue slopes 2˚ down
towards the boiler
i.e. 35mm fall per metre
of flue length (2
CONDENSATE DRAIN
WATER CONNECTIONS
GAS CONNECTION
32
)
˚
0156M
102
DRAIN
CONNECTION
Important Notice
This boiler is for use only on G20 gas, but may be converted for
use on G31 gas (L.P.G.) with an available conversion kit.
Energysaver 60, Kit No. 444509.
The boiler is delivered in one pack.
Wherever possible, all materials and components to be used
shall comply with the requirements of applicable British
Standards.
Where no British Standard exists, materials and equipment
should be fit for their purpose and of suitable quality and
workmanship.
This boiler must have fully pumped circuits, but is suitable for
use with open vented or sealed water systems.
This boiler is not suitable for outdoor locations.
1.1 Sheet Metal Parts
WARNING. When installing or servicing the boiler care should
be taken when handling sheet metal parts to avoid any possibility
of personal injury.
1.2 Statutory Requirements
The installation of the boiler MUST be carried out by a competent
person in accordance with the relevant requirements of the
current issue of:
Manufacturer’s instructions, supplied.
The Gas Safety (Installation and Use) Regulations, The Building
Regulations, The Building Standards (Scotland) Regulations
(applicable in Scotland), local Water Company Bylaws, The
Health and Safety at Work Act, Control of Substances Hazardous
to Health, The Electricity at Work Regulations and any applicable
local regulations.
Diagram 1.1
Detailed recommendations are contained in the current issue of
the following British Standards and Codes of Practice, BS4814,
BS5440 Part 1 and 2, BS5449, BS5546, BS6700, BS6798,
BS6891 and BS7074 Part 1 and 2, BS7478, BS7593, BS7671.
We also suggest that you have to hand a copy of the British Gas
publication, “Guidance Notes for the Installation of Domestic
Condensing Boilers”.
Manufacturer’s notes must not be taken as overriding statutory
obligations.
BSI Certification
This boiler certificated to the current issue of P.A.S. 010 for
performance and safety.
It is important that no alteration is made to the boiler, without
permission, in writing, from Hepworth Heating Ltd.
Any alteration that is not approved by Hepworth Heating Ltd.,
could invalidate the warranty and could also infringe the current
issue of the Statutory Requirements.
1.3 Range Rating
The boiler is range rated and is factory preset to maximum, but
may be adjusted to suit individual system requirements, refer to
Table 2.
1.4 General Data
The data label is positioned on the inner case, visible when the
outer case is removed.
All dimensions on diagrams are given in millimetres (except as
noted).
221836B
6
1 General
The Seasonal Efficiency Domestic Boilers UK (SEDBUK)
is 86.9%.
The value is used in the UK Government’s Standard Assessment
Procedure (SAP) for energy rating of dwellings. The test data
from which it has been calculated have been certified by B.S.I.
1.5 Gas Supply
The gas installation must be in accordance with the current
issue of BS6891.
The supply from the governed meter must be of adequate size
to provide a steady inlet working pressure of 20mbar (8in wg) at
the boiler.
On completion, test the gas installation for soundness using the
pressure drop method and a suitable leak detection fluid, purge
in accordance with the above standard.
1.6 Electrical Supply
WARNING. This boiler must be earthed.
All system components shall be of the approved type and be
wired and connected in accordance with the requirements of
the current issue of BS7671 and any applicable local regulations.
Connection of the boiler and system controls to the mains
supply must be through a common isolator and must be fused
3A maximum. This method of connection should be, preferably,
by a double pole isolating switch, provided it has a minimum
contact separation of 3mm on both poles. This should be
readily accessible and preferably adjacent to the appliance. It
should supply the appliance only and be easily identifiable as so
doing.
Alternatively, an unswitched shuttered socket outlet and 3A
fused 3 pin plug both to the current issue of BS1363 may be
used, provided that they are not used in a room containing a
bath or shower.
Wiring to the boiler must be PVC insulated type to the current
issue of BS6500 Table 16.
1.7 Condensate
The boiler condensate should, if possible, be discharged into
the household internal draining system, that is, sink or washing
machine drain. If this is not practicable, discharge can be
external, into the household drainage system or a purpose
designed soakaway
The boiler is fitted with a safety device to prevent the boiler from
working if the condensate pipe gets blocked by either ice or
debris.
It is, therefore, recommended that any external condensate
drain pipe is insulated to prevent it freezing up.
Alternatively, a larger diameter pipe can be used and insulated.
The condensate drain pipe should be checked during any
servicing and any debris found removed.
Refer to the British Gas publication “Guidance Note for the
Installation of Domestic Condensing Boilers” for further
information.
DATA TABLE 1.
MODEL
TOTAL
WEIGHT
LIFT
WEIGHT
WATER
CONTENT
GAS
CONNECTION
WATER
CONNECTION
ELECTRICITY
SUPPLY
TABLE 2.
RANGE RATING
NOMINALkW
HEAT INPUT
(GROSS)Btu/h
NOMINALkW
28mm copper flow
at right return at left
240V ~ 50HZ, fused 3A.
Energysaver 60
LOWMINMIDMAX
10.16 16.94 18.6420.33
34,680 57,800 63,584 69,350
8.7914.65 16.1217.58
60
48.0 kg
(106 lb)
31.5 kg
(69.5 lb)
1.6 Litre
(0.35 gal)
Rc 1/2 in.
HEAT
OUTPUTBtu/h
NOMINALkW
HEAT
OUTPUTBtu/h
30,000 50,000 55,000 60,000
9.4015.67 17.2418.81
32,100 53,500 58,800 64.150
CONDENSING
BURNERm bar
SETTING (HOT)
PRESSURE in.w.g
APPROXm3h
GAS
RATEft3h
4.511.814.317.0
1.84.75.76.8
0.961.61.771.9
345762.568
BURNER INJECTOR MARKING: 60N
1.9 Anti-theft Kits
Anti-theft kits are available for these appliances, contact
Hepworth Heating Ltd. for further information.
1.8 Heating System Controls
The heating system should have installed: a programmer and
room thermostat controlling the boiler.
Thermostatic radiator valves may be installed in addition to the
room thermostat.
Note: For further information, see The Building Regulations
1991 - Conservation of fuel and power, 1995 edition - Appendix
G, table 4b.
7
221836B
(
)
2 Water System
Note.
The boiler has 28mm copper connections which must be used
for the Energysaver 60.
4042
2.1 Draining Tap
The boiler is provided with a draining point at the lower left hand
side of the burner manifold, to be used for draining the boiler,
see diagram 2.1.
A draining tap must be provided at the lowest points of the
system which will allow the entire system and hot water cylinder
to be drained.
Draining taps shall be to the current issue of BS2879.
2.2 Safety Valve
A safety valve need not be fitted to an open vented system.
2.3 Pump
The pump should be fitted in the flow pipe from the boiler and
have isolating valves each side, integral if possible.
A variable duty pump should be set to give a temperature
difference of 11
thermostat set at “MAX”, which is about 82
a design flow rate as shown in Table 3.
See chart for pressure drop of the boiler, diagram 2.2.
High resistance microbore systems may require a higher duty
pump.
o
C (20oF) between the flow and return, with the
o
C (180oF), to give
2.4 Bypass
A BYPASS MUST BE FITTED, see diagram 2.3 for a suitable
position.
The flow rate through the boiler must not be allowed to fall below
that given in Table 3.
Where the water system can allow the boiler and pump to
operate on bypass only, the bypass
1.5m away from the boiler.
must be placed at least
2.5 Inhibitor
Attention is drawn to the current issue of BS5449 and BS7593
on the use of inhibitors in central heating systems.
If an inhibitor is to be used, contact an inhibitor manufacturer for
their recommendations as to the best product to use.
Note: This boiler has a totally copper water system and does
not require a special inhibitor normally associated with other
types of high efficiency (“condensing”) boilers.
If an existing system is to be reused take special care to drain
the entire system, including the radiators, then thoroughly
cleaning out before fitting the boiler whether or not adding an
inhibitor.
2.6 Open (Vented) Water System
The boiler must be supplied from an unrestricted water supply
taken from a feed and expansion cistern situated at a maximum
height of 27metres (90ft) above the boiler.
The cold feed must be 15mm minimum size.
The vent must rise continuously and be unrestricted.
It is important that the relative positions of the pump, cold feed
and open vent are as shown in diagram 2.3.
BOILER
DRAIN
POINT
Diagram 2.1
Flow rate (gallons/minute)
0123
2.0
1.5
1.0
0.5
Water pressure loss
(metres head of water)
0
5
0
10 15
Flow rate
4
20 25 30
litres/minute
56
78
35 40
0164M
70
60
50
40
30
20
Water pressure loss
10
0
(inches head of water)
Diagram 2.2
TABLE 3
DesignMinimum
Flow RateFlow Rate
Energysaver 60
23L/min17L/m
2.7 Domestic Hot Water Cylinder
The domestic hot water cylinder must be of the double feed fully
indirect type. Not the single feed self priming type.
2.8 Domestic Hot Water System - Unvented
Where a storage system will not have a vent to atmosphere the
installation must comply with the Building Regulations and local
Water Company bylaws, see also the current issue of BS5546
and BS6700.
If fitting to an existing system the local authority should be
informed.
2.9 Sealed Water Systems
The installation must comply with the appropriate requirements
of the current issue of BS4814, BS5449, BS6759, BS6798 and
BS7074 Part 1 and 2.
See diagram 2.4 for a suggested layout.
221836B
8
2 Water System
2.10 Safety Valve
A safety valve must be fitted to a sealed system.
It shall be preset, nonadjustable with a lift pressure of 3bar,
incorporating seating of a resilient material, a test device and a
connection for drain.
The drain from the safety valve must be routed clear of any
electrical fittings and positioned so that any discharge can be
seen.
2.11 Expansion Vessel
A diaphragm type expansion vessel, conforming to the current
issue of BS4814 (see also BS7074 Part 1 and 2) must be
connected at a point close to the inlet side of the circulating
pump, see the diagrammatic layout, diagram 2.4 unless laid
down differently by the manufacturer.
The expansion vessel volume depends on the total water
system volume and the initial system design pressure. For any
system an accurate calculation of vessel size is given in the
current issue of BS7074 Part 1.
Example: For an initial system design pressure of 0.7bar, the
minimum total vessel volume required is 0.063xTotal System
volume.
Note: A higher initial design pressure requires a larger volume
expansion vessel.
Guidance on vessel sizing is also given in the current issue of
BS5449 and BS7074 Part 1.
The charge pressure must not be less than the static head of the
system, that is, the height of the highest point of the system
above the expansion vessel.
The water content of the boiler is given in the Data Table 1.
450mm
MIN.
HEIGHT
1150mm
MIN.
BOILER
Open (vented) system.
Recommended
relationship between
pump, cold feed and
vent.
22mm (MIN) VENT
FEED AND
EXPANSION
CISTERN
15mm (MINIMUM)
COLD FEED
15mm (MINIMUM)
BY-PASS WITH
LOCKSHIELD VALVE
PUMP
150 mm
MAX
RET.
Diagram 2.3
FLOW
RET.
CYLINDER
HEATING
FLOW
4357A
(Make-up
alternatives)
3 LITRES (0.66 gals)
MAKE-UP BOTTLE
(if required)
NON-RETURN
VALVE
HEATING
CIRCUIT
AUTO
AIR
VENT
FLOW
RETURN
DRAIN
COCK
BOILER
40/50-15mm (min)
22mm (min)
60-15mm (min)
BY-PASS WITH
LOCKSHIELD
VALVE
SAFETY
VALVE
AIR
RELEASE
POINT
FILLING POINT
CIRCULATING
PUMP
PRESSURE
GAUGE
EXPANSION
VESSEL
5609
Diagram 2.4
9
221836B
M
2 Water Sytem
2.12 Pressure Gauge
A pressure gauge with a set pointer and covering at least 0 to
4bar (0 to 60lb/in2) shall be fitted permanently to the system is
a position where it can be seen when filling the system.
2.13 Domestic Hot Water Cylinder
SINGLE FEED INDIRECT CYLINDERS ARE NOT SUITABLE.
The hot water cylinder must be of the indirect coil type. It must
be suitable for working at a gauge pressure of 0.35bar above
the safety valve setting.
2.14 Water Makeup
Provision should be made for replacing water loss from the
system using a make up bottle or filling loop mounted in a
position higher than the top point of the system, connected
through a non-return valve to the return side of either the
heating circuit or the hot water cylinder.
Alternatively, provision for make up can be made using a filling
loop.
2.15 Filling a Sealed Water System
Provision for filling the system at low level must be made. Three
methods are shown in diagram 2.5. There must be no permanent
connection to the mains water supply, even through a nonreturn valve.
METHOD 1
TEMPORARY
HOSE
SUPPLY
PIPE
METHOD 2
TEMPORARY
HOSE
SUPPLY
PIPE
METHOD 3
CISTERN
HOSE
UNIONS
SUPPLY STOP
VALVE
DOUBLE CHECK
VALVE ASSEMBLY
HOSE
UNIONS
SUPPLY STOP
VALVE
OVERFLOW
SERVICING
VALVE
COMBINED
CHECK VALVE
AND VACUUM
BREAKER
SERVICING
VALVE
SERVICING
VALVE
PRESSURE
REDUCING
VALVE
0051
HEATING
SYSTEM
HEATING
SYSTEM
HEATING
SYSTEM
SUPPLY
STOP VALVE
SUPPLY
PIPE
HOSE
UNIONS
DOUBLE CHECK
VALVE ASSEMBLY
Diagram 2.5
221836B
10
3 Boiler Location
NOTE:
The boiler may be installed in any room although particular
attention is drawn to the requirements of the current issue of
BS7671 with respect to the installation of a boiler in a room
containing a bath or shower. Any electrical switch or boiler
control using mains electricity should be so situated that it
cannot be touched by a person using the bath or shower. The
electrical provisions of the Building Standards (Scotland)
Regulations are applicable to such installations in Scotland.
The boiler must be mounted on a flat wall which is sufficiently
robust to take its total weight, see Data Table 1.
3.1 Boiler Clearances
The boiler must be positioned so that at least the minimum
operational and servicing clearances are as shown in diagram
3.1.
Additional clearances may be required around the boiler for
installation purposes, dependent upon site conditions.
3.2 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it should
be fitted in accordance with the Institute of Gas Engineers
document IGE/UP/7/1998. If in doubt seek advice from the local
gas undertaking or Hepworth Heating Ltd.
150
55
100
INCREASE THIS DIMENSION TO
*
25mm FROM COMBUSTIBLE MATERIAL
5
*
5
0157M
3.3 Room Ventilation
The boiler is room sealed, so when installed in a room or space
a permanent air vent is not required.
3.4 Cupboard or Compartment Ventilation
Where the boiler is fitted in a cupboard or compartment,
permanent high and low level ventilation must be provided. The
ventilation areas required are given in Table 4.
Where the installation of the boiler will be in an unusual location,
special procedures are necessary, refer to the current issue of
BS6798 for guidance.
Make sure that the cupboard or compartment air vents are
positioned to be clear of obstructions at all times.
A compartment used to enclose the boiler must be designed
and constructed specifically for this purpose.
The doorway opening should be of sufficient size to allow for
easy removal of the boiler.
5
*
5
*
500
PERMANENT
SURFACE
CLEARANCE OPPOSITE TO FLUE EXIT
MUST BE ADEQUATE FOR THE
INTERNAL INSTALLATION
Diagram 3.1
TABLE 4
Ventilationhighlevellowlevel
From Roomcmsin
Energysaver 60
19029.519029.5
2
cmsin
2
Ventilation
From Outside
Energysaver 60
11
9214.39214.3
221836B
4 Flue
NOTE:
The flue must be installed in accordance with the current issue
of BS5440 Part 1.
Important. The flue must be installed with a fall of 35mm per
metre (2
It is of no advantage to exceed this angle (2
the fan to flue elbow may become more difficult as the angle is
increased.
The air and flue duct connect to the top of the boiler using an
elbow which can be positioned to the side or rear.
The rear and side flue assemblies are designed for internal
installation, but if necessary, due to insufficient clearances
(boiler/flue terminal location) they can be installed from the
outside.
For a wall thickness up to 300mm the flue can be fully installed
from the inside.
For a wall thickness over 300mm the external cut hole will need
to be made good from the outside.
The standard flue is able to provide the duct lengths as shown
in diagram 4.2 for a rear flue and diagram 4.3 for a side flue.
If a longer flue duct is required, do not extend the ductings. A
1, 2 or 3metre long flue system and terminal can be supplied.
o
) towards the boiler, see diagram 4.1.
o
) indeed sealing of
'R'
REAR FLUE LENGTHS
R = Wall Thickness
STD Flue pack
1m Flue pack75mm to 953mm
2m Flue pack75mm to 1953mm
3m Flue pack75mm to 2933mm
75mm to 442mm
6860
Make sure flue slopes
2
down towards
˚
the boiler
that is 35mm fall
per metre
of flue
length (2
)
˚
300mm
2
˚
REAR FLUE
SIDE VIEW
Make sure flue slopes
2˚ down
towards the boiler
that is 35mm fall per metre
of flue length (2
)
˚
35mm
10.5mm
0158M
Diagram 4.2
'S'
SIDE FLUE LENGTHS
S = "External wall face" to "boiler casing"
STD Flue pack 80mm to 331mm
1m Flue pack80mm to 841mm
2m Flue pack80mm to 1841mm
3m Flue pack80mm to 2821mm
Diagram 4.3
6861
221836B
SIDE FLUE
FRONT VIEW
2
˚
1metre
Diagram 4.1
12
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.