Glow-worm Economy Plus 41 319 04, Economy Plus 41 319 62, economy plus 60B, economy plus 75B Installation & Servicing Instructions Manual

Page 1
Supplied By www.heating spares.co Tel. 0161 620 6677
220459C.03.96
2
Installation & Servicing Instructions
To be left with the user
60B
75B
G.C. No. 41 319 04
G.C. No. 41 319 62
Balanced Flue Boilers
With Honeywell Control
2404
This is a Cat I2H Appliance
Customer Services:
One Contact Total Service
Tel: (01773) 828100 Fax: (01773) 828070
Hepworth Heating Ltd.,
Nottingham Road, Belper, Derbyshire. DE56 1JT
General/Sales enquiries :
Tel: (01773) 824141 Fax: (01773) 820569
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
RETURN
338
WATER
CONNECTIONS
GAS CONNECTION
446
OVERALL DIMENSIONS Given in millimetres
FLOW
98
56
11
490
600
110
GAS CONNECTION
300
225
WATER CONNECTIONS
98
43
C
L
FLUE
2401
154
340
414
Diagram 1.1
The instructions consist of two parts Installation and Servicing Instructions and Instructons for Use which includes the Guarantee Registration Card. The instructions are an integral part of the appliance and must, comply with the current issue of the Gas Safety (Installation and Use) Regulations, be handed to the user on completeion of the installation.
1 General Notes and Information.
This boiler is suitable for fully pumped systems only.
Important Notice
The boiler is for use on natural gas as distributed in the United Kingdom (G20) and cannot be used on any other gas.
Sheet Metal Parts
WARNING. When installing or servicing the boiler care should be taken when handling sheet metal parts to avoid any possibility of personal injury.
Wherever possible, all materials, appliances and components to be used shall comply with the requirements of applicable British Standards.
Where no British Standards exists, materials and equipment should be fit for their purpose and of suitable quality and workmanship.
2220459C
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
1.1 Statutory Requirements
This boiler must be installed by a competent person in accordance with the requirements of the current issue of:
The Gas Safety (Installation and Use) Regulations, The Building Regulations, The Building Standards (Scotland) Regulations, (applicable in Scotland), Local Water Company Bye-laws, Control of Substances Hazardous to Health, The Electricity at Work Regulations and any applicable local regulations.
Detailed recommendations are contained in the current issue of the following British Standards and Codes of Practice:
BS6798, BS5440 Parts 1 and 2, BS6891, BS5546 Part 1, BS5449, BS7074 Part 1 and 2, BS7478, BS7593, BS7671.
1.2 Data
Weight 60B - 32kg (71lb)
75B - 33.2kg (73.1lb) Electrical supply - 240V~50Hz fused 3A Water content 60B - 0.71Litre (0.16gal)
75B - 0.75Litre (0.17gal) Gas connection - Rc 1/ Water connection- 28mm copper flow at right Data label- Bottom right, inner case. Injector 60B - Bray 30-1700
2
1.3 Range Rating
This boiler is range rated and may be adjusted to suit individual system requirements.
Table 1 gives the ratings and settings.
1.4 B.S.I. Certification
This boiler is certificated to the current issue of BS6332 Part 1, invoking the current issue of BS5258 Part 1 for performance and safety. It is, therefore, important that no alteration is made to the boiler without permission, in writing, from Hepworth Heating Ltd.
Any alteration that is not approved by Hepworth Heating Ltd., could invalidate the B.S.I. Certification of the boiler, the warranty and could also infringe the current issue of the Statutory Requirements.
CE Mark
The CE Mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the Laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to electrical equipment designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
75B - Bray 30-2200
3
220459C
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
1.5 Gas Supply
The gas installation shall be in accordance with the current issue of BS6891.
The supply from the governed meter must be of adequate size to provide a steady inlet working pressure of 20mbar (8in wg) at the boiler.
On completion test the gas installation for soundness using the pressure drop method and suitable leak detection fluid, purge in accordance with the above standard.
1.6 Electrical Supply
WARNING. This boiler must be earthed. All system components shall be of the approved type
and wiring shall comply with and be connected in accordance with the requirements of the current issue of BS7671 and any applicable local regulations.
Connection of the boiler and system controls to the mains supply must be through a common isolator and must be fused 3A maximum. This method of connection should be, preferably, by a fused double pole isolating switch, provided it has a minimum contact separation of 3mm on both poles. This should be readily accessible and preferably adjacent to the appliance. It should supply the appliance only and be easily identifiable as so doing.
ECONOMY PLUS 60B
RANGE RATING NOMINAL
kW
HEAT INPUT
NOMINAL
Btu/h
kW
HEAT OUTPUT
BURNER
Btu/h
m bar
SETTING PRESSURE
in. w.g.
ECONOMY PLUS 75B
RANGE RATING NOMINAL
HEAT INPUT
NOMINAL HEAT OUTPUT
BURNER SETTING PRESSURE
kW
Btu/h
kW
Btu/h
m bar
in. w.g.
Table 1
Max.Min. Med.
-18.47 22.00
-63,000 75,000
16.1214.66 17.59
55,00050,000 60,000
11.69.3 13.4
4.63.7 5.4
Table 1
Max.Min. Med.
-22.13 27.50
-75,500 93,800
19.817.60 22.00
67,50060,000 75,000
11.89.4 14.5
4.73.8 5.8 2399
B
Alternatively an unswitched shuttered socket outlet and 3A fused 3 pin plug both to the current issue of BS1363 may be used provided that they are not used in a room containing a bath or shower.
Wiring to the boiler must be PVC insulated type to the current issue of BS6500 Table 16, not less than
0.75mm2(24/0.20mm).
1.7 Contents of Packaging
The boiler is delivered in one pack. The other pack contains the balanced flue terminal
assembly and accessories. Refer to Section 2.3 to check that the flue terminal
assembly supplied is suitable.
1.8 Water System
The boiler may be fitted to an open vented or sealed system, refer to Section 3 for details.
AA
C
Minimum Clearances from Walls, Ceiling, Floor, Cupboard, Worktops, Inflammable Material etc.
A L.H and R.H. side of casing 5 B Top of casing 75 C Bottom of casing 150 D Front of boiler
(from a permanent surface) 305
Balanced
Flue
Model
MINIUMUM CLEARANCES
4220459C
Diagram 1.2
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
1.9 Draining Tap
A draining tap must be provided at the lowest points of the system which will allow the entire system, boiler and hot water cylinder to be drained.
The boiler is fitted with a drain tap for draining down the heat exchanger.
Draining taps shall be to the current issue of BS2879.
1.10 Safety Valve
A safety valve need not be fitted to an open vented system.
1.11 Location
This boiler is not suitable for outdoor location. The boiler may be installed in any room, although
particular attention is drawn to the requirements of the current issue of BS7671 with respect to the installation of a boiler in a room containing a bath or shower.
2 Flue and Ventilation
Any electrical switch or boiler control using mains electricity should be so fitted that it cannot be touched by a person using the bath or shower. The electrical provisions of the Building Standards (Scotland) Regulations are applicable to such installations in Scotland.
The boiler must be mounted on a flat wall which is sufficiently robust to take its weight.
1.12 Boiler Location
Refer to diagram 1.2. The boiler must be positioned so that at least the
minimum operational and servicing clearances are provided.
Additional clearances may be required for installation. If fixtures are positioned next to the boiler they should
be made removable for access to pipework. Sufficient clearance must be left in front of the boiler for
servicing.
2.1 Terminal Position
The minimum acceptable spacings from the terminal to obstructions and ventilation openings are shown in diagram 2.1.
Where the terminal is fitted within 850mm (34in) below plastic guttering or within 450mm (18in) of painted eaves or painted gutters an aluminium shield 750mm (2ft6in) long should be fitted to the underside and immediately beneath the guttering/eaves.
2.2 Protecting the Terminal
A terminal guard is required if persons could come into contact with the terminal or the terminal could be subject to damage.
POSITION MINIMUM
SPACING
A Directly below an openable window,
air or any other ventilation opening 300mm
B Below gutter, drain/soil pipe 300mm C Below eaves 300mm D Below a balcony or car port 600mm E From vertical drain pipes and soil pipes 75mm F From internal or external corners 600mm G Above adjacent ground or balcony level 300mm H From a surface facing the terminal 600mm I Facing terminals 600mm J From opening (door/window) in car
port into dwelling 600mm
K Vertical from a terminal 1500mm
If a terminal guard is required, it must be positioned to provide a minimum of 50mm clearance from any part of the terminal and be central over the terminal.
Guards are available from,
Tower Flue Components Ltd.,
Morley Road, Tonbridge, Kent, TN9 1RA.
quoting their reference “F”black,
1112
A
A
F
G
Under Car Port etc.
B,C
B,C
G
A
E
G
K
F
F
G
H,I
C
K
L
L
K
G
D
J
F
K
1112
MINIUMUM SITING DIMENSIONS FOR BALANCED FLUE TERMINALS
5
Diagram 2.1
220459C
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Flue and Ventilation
2.3 Wall Thickness
Check the thickness of the wall. The standard flue set supplied is suitable for wall
thickness 238mm to 330mm. For other wall thickness, a short flue kit No.443239 for 76mm to 238mm and a long flue kit No. 443240 for 324 to 580mm are available.
2.4 Boilers in a Compartment
Where the installation of the boiler will be in an unusual location, special procedures are necessary, the current issue of BS6798 gives detailed guidance on this aspect.
A compartment used to enclose the boiler must be designed and constructed specifically for this purpose.
An existing cupboard or compartment modified for the purpose may be used.
Details of essential features of cupboard design are given in the current issue of BS6798.
The doorway opening should be of sufficient size to allow for easy removal of the boiler.
Where the boiler is fitted in a cupboard or compartment, permanent high and low level ventilation must be provided. The minimum ventilation areas required are given in Table 2.
AIR VENT AREA TABLE FOR
COMPARTMENT INSTALLATIONS
TABLE 2 AIR VENT AREAS
POSITION AIR FROM AIR DIRECT
OF ROOM OR FROM
AIR VENTS INTERNAL OUTSIDE
SPACE
HIGH VENT 200cm
LOW VENT 200cm
2
2
100cm 100cm
2
2
2.5 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it should be fitted in accordance with the British Gas publication “Guide for Gas Installation in Timber Framed Housing” reference “DM2”. If in doubt, seek advice from the local gas undertaking or Hepworth Heating Ltd.
3 Water Systems
Notes
Pump
The pump should be fitted in the flow pipework from the boiler with valves each side, integral if possible, it should produce at least 2.5m (8ft) head, a temperature difference across the boiler of 11oC (20oF). Flow rate through the boiler of 23Litres/min (5.1gal/min).
See diagram 3.1 for pressure loss across the boiler. High resistance microbore systems may require a higher
duty pump.
Bypass
A bypass must be fitted, see diagram 3.2. The flow rate through the boiler must not be allowed to
fall below 18Litres/min (3.9gal/min) whilst the burner is alight.
3.1 Water System - Open Vented Systems
For an open, vented, system the boiler must be supplied from an unrestricted water supply taken from a feed and expansion tank, situated at a maximum height of
27.5metres (90ft) above the boiler.
Flow rate (gallons/minute)
01
1500 1250 1000
750 500 250
Water pressure loss
(mm head of water)
60B
0123456
Flow rate (litres/minute)
23456
75B
2428
60 50 40 30 20 10
00
PRESSURE LOSS OF BOILER Diagram 3.1
The cold feed supply must be 15mm minimum size. It is important that the relative positions of the pump,
cold feed and open vent are as shown in diagram 3.2.
Water pressure loss
(inches head of water)
6220459C
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Water Systems
3.2 Cylinder
SINGLE FEED (SELF PRIMING) CYLINDERS ARE NOT RECOMMENDED.
The hot water cylinder must be a double feed, fully indirect, type.
3.3 Inhibitor
Attention is drawn to the current issue of BS5449 and BS7593 on the use of inhibitors in central heating systems.
If an inhibitor is to be used, contact a manufacturer for their recommendations for the best product to use.
When fitting the boiler in an existing system take special care to drain the entire system including the radiators, then thoroughly cleaning out before fitting the boiler whether or not adding an inhibitor.
Sealed Water Systems
The installation should comply with the requirements of the current issue of BS4814, BS5449, BS6759, BS6798 and BS7074 Part 1 and 2.
See diagram 3.3. for a suggested layout.
Open (vented) system. Recommended relationship between
450mm MIN. HEIGHT
1150mm MIN.
BOILER
OPEN (VENTED) WATER SYSTEM
150mm MAX
pump, cold feed and vent.
22 mm (MIN) VENT
FEED AND EXPANSION CISTERN
15mm (MINIMUM) COLD FEED
22mm (MINIMUM) BY-PASS WITH LOCKSHIELD VALVE
PUMP
Recommended relationship between pump, cold feed and vent
RET.
CYLINDER
Diagram 3.2
0750
0011M
FLOW
RET.
HEATING
FLOW
( Make-up alternatives)
3 LITRES (0.66 gals) MAKE-UP BOTTLE (if required)
NON-RETURN VALVE
AUTO AIR VENT
22mm (min) BYPASS WITH LOCKSHIELD VALVE
HEATING
CIRCUIT
FLOW
RETURN
DRAIN COCK
SAFETY VALVE
BOILER
0854
AIR RELEASE POINT
FILLING POINT
CIRCULATING PUMP
PRESSURE GAUGE
EXPANSION VESSEL
SEALED WATER SYSTEM DIAGRAMMATIC LAYOUT
7
Diagram 3.3
220459C
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Water Systems
3.4 Safety Valve
A safety valve must be fitted in a sealed water system. It shall be preset, nonadjustable with a lift pressure of
3bar, incorporating seating of a resilient material, a test device and a connection for drain.
The drain from the safety valve must be routed clear of any electrical fittings and positioned so that any discharge can be seen.
3.5 Expansion Vessel
A diaphragm type expansion vessel, conforming to the current issue of BS4814, see also BS7074 Part 1 and 2, must be connected at a point close to the inlet side of the circulating pump, see diagram 3.3 or as laid down by the manufacturer.
The expansion vessel volume depends on the total water system volume and the initial system design pressure. For any system an accurate calculation of the vessel size is given in the current issue of BS7074 Part 1.
Example. For an initial system design pressure of
0.7bar, the minimum total vessel volume required id
0.063xTotal System volume. Note. A higher initial design pressure requires a larger
volume expansion vessel. Guidance on vessel sizing is also given in the current
issue of BS5449 and BS7074 Part 1. The charge pressure must not be less than the static head
of the system, that is, the height of the highest point of the system above the expansion vessel.
The water content of the boiler is given in Data Table 1.
3.6 Pressure Gauge
A pressure gauge with a set pointer and covering at least the range 0 to 4bar (0 to 60lb/in2) shall be permanently fitted to the system in a position where it can be seen when carrying out the filling operation.
METHOD 1
TEMPORARY HOSE
HOSE UNIONS
SUPPLY PIPE
SUPPLY STOP VALVE
METHOD 2
TEMPORARY HOSE
HOSE UNIONS
SUPPLY STOP
SUPPLY PIPE
VALVE
METHOD 3
CISTERN
SUPPLY STOP VALVE
SUPPLY PIPE
OVERFLOW
SERVICING VALVE
FILLING SEALED WATER SYSTEMS
COMBINED CHECK VALVE AND VACUUM BREAKER
SERVICING VALVE
DOUBLE CHECK VALVE ASSEMBLY
SERVICING VALVE
PRESSURE REDUCING VALVE
HOSE UNIONS
DOUBLE CHECK VALVE ASSEMBLY
3132
HEATING SYSTEM
HEATING SYSTEM
HEATING SYSTEM
Diagram 3.4
3.7 Cylinder
SINGLE FEED INDIRECT CYLINDERS ARE NOT SUITABLE.
The hot water cylinder must be of the indirect coil type. It must be suitable for working at a gauge pressure of
0.35bar above the safety valve setting.
3.8 Water Make Up
Provision must be made for replacing water lost from the system. A make up vessel mounted above the highest point of the system and connected through a non-return valve to the system on the return side of either the hot water cylinder or heating system.
Alternatively, provision for make up can be made by using a filling loop.
3.9 Filling Sealed Water Systems
Provision for filling the system at low level must be made. Three methods of filling are shown in diagram 3.4. There must be no permanent connection to the mains supply, even through a non-return valve.
8220459C
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Flue and Appliance Preparation
4.1 Positioning
Place the template, provided, square on the wall in the required position and mark location of the balanced flue hole, see diagram 4.1.
Cut the hole in the wall to accept the wall liner, see diagram 4.1.
Make good any plasterwork at this stage. When dry, select the liner with the turned flange at one end “C”, see diagram 4.2. Push it into the cavity until the flange is flush to the internal wall. Fit the second half of the liner “B” from inside so that it is flush with the outside brickwork. Mark the two liner positions and remove from hole. Align the marks on the liners and tape together with the tape provided.
The extension “B” is not required when the wall thickness is equal to the length of duct.
Reposition the template on the wall in line with the wall opening, or see diagram 4.1.
Mark the positions for the three fixing screws. Drill and plug the fixing holes, suitable for No.10x50mm
woodscrews and plugs.
0855
BOILER FIXING DIMENSIONS Diagram 4.1
A - TERMINAL ASSEMBLY B - AIR DUCT EXTENSION
C - AIR DUCT D - SELF ADHESIVE SEAL E - HOLE FOR CORD / STRING
A
D
0858
E
15 mm
B
APPROX
C
TERMINAL and AIR DUCT
9
Diagram 4.2
220459C
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Installation
5.1 External Access Procedure
From inside the room fit the already prepared air duct assembly.
Attach the self adhesive seal “D” to the terminal wall plate, see diagram 4.2.
Place the terminal against the outside wall with the inner flange of the wall plate located inside the air duct assembly. Support the terminal in any suitable way.
Working from the inside, bend the two perforated straps around the hexagon nuts provided at about 15mm from the brackets on the air duct assembly, see diagram 4.2.
Secure the two straps with the screws and nuts, the screw head passing first through the large part of the keyhole in the bracket, then sliding into the smaller recessed portion.
Tighten the screws to tension the straps securing the terminal in position, do not overtighten. Cut off any excess strap length.
5.2 Internal Access Procedure
If required the terminal can be installed from inside the premises.
Fit the already prepared air duct assembly into the hole in the wall.
Attach the self adhesive seal “D” to the terminal wall plate “A”, see diagram 4.2.
Attach a length of strong cord or similar, to the terminal through the small hole “E” provided in the top centre baffle, see diagram 4.2. Attach a suitable weight to the free end of the cord.
Pass the terminal through the duct assembly, using the straps to manoeuvre the terminal into position. NOTE, the terminal “Top” is indicated and the inside flange of the wall plate is located inside the air duct assembly. The weight will support the terminal in position.
LUG
INNER CASE
OUTER CASE SECURING SCREW
INNER and OUTER CASING
WING NUT AND SPRING WASHER (2)
OUTER CASE
SECURING ANGLE
LUG
2407
INNER CASE SECURING SCREWS (TOP)
OUTER CASE
INNER CASE
INNER CASE SECURING SCREWS (BOTTOM)
Diagram 5.1
2389
FLUE HOOD
HOOK BOLT (2)
Bend the two perforated straps around the hexagon nuts provided, see diagram 4.2.
Secure the two straps with the screws and nuts, the screws head passing first through the large part of the keyhole in the bracket, then sliding into the smaller recessed portion.
Tighten the screws to tension the straps securing the terminal in position, but do not overtighten. Cut off excess strap length and remove cord.
APPLIANCE PREPARATION Diagram 5.2
10220459C
CASING SIDE STRIP
SECURING SCREW
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Installation
5.3 Appliance Preparation
Remove the controls cover by pulling if forward and off. Remove the outer case by undoing the screw at the
bottom and unhooking at the top. Remove the inner case by undoing the screws at the top
and bottom, see diagram 5.1. Remove the flue hood by releasing the wing nuts and
remove angle, see diagram 5.2. Lift off flue hood. Remove the two flue duct screws.
Fit the sponge seal “J” around the spigot at the back of the boiler, adhesive face to the back of the case, see diagram 5.3.
Take the side strips from the packaging and hook them over the top edge of the side panel and secure with a screw at the bottom.
5.4 Appliance Fixing
Fit the top two screws, allowing them to protrude from the wall face to accept the keyhole slots on the boiler.
Hook the boiler onto the screws, fit the bottom screw and tighten all three.
5.5 Standard and Short Flue Only
Push the flue duct “G” into the terminal with the unflanged end entering the terminal. Make sure that the lower flange of the duct fits behind the combustion chamber rear panel. For wall less than 150mm thick cut the surplus length from the unflanged end of the flue duct “G”, see diagram 5.3.
Fit the two screws through the flue duct flange and sealing plates but do not fully tighten.
Replace the flue hood “H”, inserting the rear into the flue duct. Push on the rear of the hood and tighten the duct screws. Refit the securing angle, hook bolts, wing nuts and spring washers firmly but do not overtighten.
Refit the inner case and secure with the screws previously removed.
G - FLUE H - FLUE HOOD J - CASE SEAL
2775
FLUE
G
J
DUCT SECURING SCREW (2)
H (60)
STANDARD or SHORT FLUE DUCT
11
H (60)
Diagram 5.3
220459C
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Installation
5.6 Long Flue Set Only
For long flues the flue duct “G”, extension “L” and sleeve “K” need to be assembled together to suit the wall thickness. This assembly is 75mm longer than the air duct assembly already prepared. A minimum overlap of 40mm is required at each joint. Use the tape provided to make permanent the assembly of the three flue parts, see diagram 5.4.
Push the flue duct assembly into the terminal, with the unflanged end entering the terminal. Make sure that the lower flange of the duct fits behind the combustion chamber rear panel.
Fit the two screws through the flue duct flange and sealing plates, do not overtighten.
Replace the flue hood “H”, inserting the rear into the flue duct. Push down on the rear of the hood and tighten the sealing plate screws. Refit the securing angle, tie rods and wing nuts firmly, do not overtighten.
Refit the inner case and secure it with the screws previously removed.
G - FLUE DUCT H - FLUE HOOD L - FLUE DUCT EXTENSION K - FLUE DUCT SLEEVE J - CASE SEAL
2776
K
L
G
J
FLUE DUCT SECURING SCREW(S)
H (60)
LONG FLUE DUCT
12220459C
H (75)
Diagram 5.4
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Gas and Water Connection
Connect the gas supply to the Rc1/2 gas cock. The whole of the gas installation, including the meter
should be inspected, tested for soundness and purged in accordance with the current issue of BS6891.
Connect water to the boiler using the nuts and olives supplied to BS2871 copper tube.
7 Electrical Wiring
WARNING. THE BOILER MUST BE EARTHED AND HAVE A PERMANENT MAINS SUPPLY.
7.1 Electrical Connection
To remove the control box release the two screws at the front, see diagram, lower the box until it is clear then push backward to disengage the hinge at the rear, see diagram 7.1 Take care not to damage the thermostat and capillaries.
Thread the mains lead through the clamp at the rear of the control box cover, and connect to the terminal strip.
The mains cable outer insulation must not be cut back external to the cable clamp.
When making connections, make sure that the earth conductor is made of greater length than the current carrying conductors, so that if the cable is strained the earth conductor would be the last to become disconnected.
7.2 Pump and External Controls Connections
The pump must be wired into the boiler control box as shown in diagram 7.2.
STRAIN
SECURING SCREWS
TERMINAL STRIP
CONTROL BOX
RELIEF GROMMET
FASTENER
7.3 Testing - Electrical
2420
RETAINING STRAP
EARTH POST
Diagram 7.1
Any external controls must only be wired to interrupt the red link between terminals 9 and SL.
Take the strain relief grommets from the loose items pack. Place around the external controls and pump connection cables respectively. Squeeze the sides of the grommets when pushing them into the obround holes in the rear of the control box, see diagram 7.1.
Make sure that the supply cables and all external cables are secured.
Checks to ensure electrical safety should be carried out by a competent person.
After installation of the system, preliminary electrical system checks as below should be carried out.
1. Test insulation resistance to earth of mains cables.
2. Test the earth continuity and short circuit of all cables.
3. Test the polarity of the mains.
13
220459C
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
7 Electrical Wiring
BROWN
CIRCULATION PUMP
240~50Hz PERMANENT MAINS SUPPLY FUSED AT 3A
SWITCHED CONTROL TIME SWITCH PROGRAMMER ETC. (if fitted)
Remove Red Link between 9 and SL when fitting a time control etc. (If link is not removed the circulation pump will run constantly.)
WIRING for CONTROL BOX
L
BLUE
N
GRN / YELLOW BROWN
L
BLUE
N
SL
NL
N
L987
BROWN BLUE GRN / YELLOW
987
SL
GRN/YEL
CHASSIS EARTH POST
BLUE PURPLE RED
RED BROWN
COMBINED THERMOSTAT AND PUMP OVERUN
GAS VALVE
BROWN
2419
7
3
98 6
Diagram 7.2
14220459C
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
8 Commissioning
8.1 All Systems
Make sure that the system has been thoroughly flushed out with cold water without the pump in place. Refit the pump, fill the system with water, ensuring that all air is properly vented from the system and pump.
Before operating the boiler check that all external controls are calling for heat.
8.2 Sealed Water Systems Only
Flush the whole of the system with cold water without the pump in place. Refit the pump and fill until the pressure gauge registers 1.5bar (21.5lbf/in2). Clear any air locks and check for water soundness.
Check the operation of the safety valve, by allowing the water pressure to rise until the valve opens. The valve should open within +/- 0.3 bar (+/-4.3lbf/in2) of the 3bar preset pressure. Where this is not possible conduct a manual check and test.
Release cold water to initial system design pressure. The set pointer on the pressure gauge should be set to
coincide with the indicating pointer.
8.3 Initial Lighting and Testing
Refit the outer case, see diagram 5.1. Identify the controls by reference to diagram 8.1. Turn boiler thermostat to “O” the Off position. Remove the gas pressure test point screws “K” and fit a
suitable pressure gauge. Turn the electrical supply on and check that the pump is
working. OPEN ALL WINDOWS AND EXTINGUISH ANY
NAKED LIGHTS, PIPES, CIGARETTES etc. Turn on the main gas supply and purge in accordance
with the current issue of BS6891. Turn boiler gas service cock “J” to On. Depress control button “B”, keep pressed in and at the
same time operate the piezo unit button “C” until the pilot burner lights. After the pilot burner lights keep the button “B” depressed for about 15 seconds. If the pilot fails to stay alight a safety device prevents immediate relighting. Do not attempt to relight until the safety device has reset. Check the length of the pilot flame, it should envelop the thermocouple tip as shown in diagram 10.3. The pilot rate can be adjusted by turning screw “H” having first removed the gas valve cover by releasing the screw. Test pilot supply connection for gas soundness with a suitable leak detection fluid.
2416
G
A
A. BOILER THERMOSTAT H. GAS RATE ADJUSTMENT SCREW B. GAS CONTROL KNOB H. (UNDER COVER SCREW) C. IGNITION BUTTON J. GAS SERVICE COCK G. VIEWING WINDOW K. PRESSURE TEST POINT
BOILER CONTROLS Diagram 8.1
C
K
L
L. PILOT BURNER
L. ADJUSTMENT SCREW
BH
J. (SHOWN OFF)
MODEL AND SERIAL NUMBER
15
220459C
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677
8 Commissioning
Fit the outer case, secure with the screws previously removed.
Make sure that the pilot is alight and stable, view through window “G”.
Set the boiler thermostat control knob “A” between “1” and “5” and check that the burner lights smoothly. Check the gas connections for gas soundness with a suitable leak detection fluid.
To set the burner pressure operate the boiler for 10 minutes, remove the gas valve cover, if not already removed, adjust the the gas pressure by screw “H” until the required pressure is obtained, see Table 1 for setting pressures.
Align and attach the self adhesive arrow, from the loose items pack, in the appropriate space beneath the “MIN” and “MAX” column on the Data label.
Should any doubt exist about the gas rate this should be checked at the meter, using a stop watch to time at least one cubic foot of gas consumption.
Remove the pressure gauge, refit the test point screw and ensure a gas tight seal is made.
Replace gas valve cover.
8.4 Testing
8.6 Adjustment - All Systems
When commissioning the system the boiler should first be fired with the bypass fully closed on full service, that is, central heating and domestic hot water. The system should then be balanced, adjusting the pump and lockshield valve as necessary. Having achieved a satisfactory condition operate the boiler with the bypass valve fully closed on minimum load, normally this will be central heating only with one radiator operating in the main living area. The valve should be gradually opened to achieve a flow rate of 18.0Litre/min (3.9gal/min).
UNDER NO CIRCUMSTANCES SHOULD THIS VALVE BE LEFT IN THE FULLY CLOSED POSITION.
Operate the boiler again on full service and check the balancing, making further adjustments as necessary.
If thermostatic radiator valves are fitted care must be taken to ensure an adequate flow rate when the valves close, refer to the current issue of BS7478 for guidance.
Refit the controls cover.
8.7 Sealed Water Systems
Sealed water systems should be adjusted to the initial design pressure and the set pointer repositioned.
Check the operation of the flame failure device on the boiler, by turning the gas service cock off, to make sure that the gas valve shuts down within 60 seconds, indicated by a “click” from the valve.
8.5 Flushing
Allow the system to reach maximum working temperature and examine for water leaks.
The system should then be turned off and drained rapidly whilst hot.
Refill the system, vent all air and check for water soundness.
9 Instruct User in Correct Operation of the Boiler
Hand the Instructions for Use to the user for their retention.
Instruct and demonstrate the safe and efficient operation of the boiler.
Advise that to ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the particular installation and usage, but in general once a year should be enough.
Advise the user of the precautions necessary to prevent damage to the system and building in the event of the heating system being out of use during frost and freezing conditions.
Draw attention if applicable, to the current issue of the Gas Safety (Installation and Use) Regulations, Section 35 which imposes a duty of care on all persons who let out any property containing a gas appliance.
Reminder, leave these instructions with the user for use during future service calls.
It is the law that any servicing must be carried out by a competent person.
16220459C
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Servicing and Replacement of Parts
Servicing and replacement of parts must be carried out by a competent person.
Before commencing a service or replacing parts isolate the gas and electrical supplies.
Unless stated otherwise replacement of parts is in the reverse order to removal.
10.1 Heating Body - Service
Remove controls cover by pulling it forward and off. Remove outer casing by releasing screw at the bottom
and unhooking at the top. Remove the inner case by releasing screws at top and
bottom, see diagram 10.1. To remove the flue hood release the wing nuts and lift
off securing angle and flue hood. Remove the combustion chamber front panel by undoing
the wing nut at the bottom front and the four screws securing it to the combustion chamber sides.
Remove the two screws and washers securing the pilot burner and shield to the main burner, see diagram 10.2.
Pull the pilot assembly forward enough to allow the main burner to be freed from the injector. Raise the burner up at the front, withdraw forward. Take care not to damage the insulation and the pilot burner and electrode assemblies.
Place a sheet of paper in the combustion chamber and brush away any deposits.
Remove the paper and debris.
10.2 Main Burner
Follow the instructions generally as Section 10.1. With the main burner removed brush or vacuum any
deposits away, ensure that the flame ports are clean.
WING NUT (2)
SECURING ANGLE
WING NUT
Casing not illustrated for clarity
MICA WINDOW PILOT
SHIELD
SECURING SCREWS
PILOT INJECTOR
ADAPTOR OLIVE
PILOT TUBING NUT
PILOT ASSEMBLY
0947
FLUE HOOD
HOOK BOLT (2)
COMBUSTION CHAMBER FRONT PANEL SECURING SCREW (4)
FRONT PANEL
Diagram 10.1ACCESS for SERVICING
1049
M3 SCREW
ELECTRODE
IGNITION LEAD (clear end)
THERMOCOUPLE THERMOCOUPLE
NUT
Diagram 10.2
Do not use a brush with metallic bristles.
10.3 Main Injector
Follow the instructions generally as Section 10.1. With the main burner removed the injector can be
unscrewed and replaced as necessary using a new sealing washer.
If cleaning do not use a wire or sharp instrument on the hole.
When replacing the main burner ensure that it is pushed fully home onto the injector and that the guides are engaged on the injector manifold.
10.4 Pilot Burner and Injector
Follow the instructions generally as Section 10.1. With the main case and controls cover etc., removed as
above pull off ignition lead from electrode. Unscrew the tubing nut at the base of the pilot burner
releasing the pilot pipe. Remove the pilot injector by unscrewing if from the pilot burner.
Release the wing nuts securing the flue hood, see diagram 10.1.
Remove combustion chamber front panel as above. Remove the two screws and washers securing the pilot
burner and pilot shield to the main burner, see diagram 10.1.
Remove the pilot shield complete with the electrode.
17
220459C
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Servicing and Replacement of Parts
Unscrew the thermocouple nut. The pilot burner can now be lifted away. Take care not to damage the electrode. When replacing ensure that the spark gap is as shown in
diagram 10.3.
10.5 Thermocouple
Generally follow the instructions given in Section 10.1. Release, but do not remove, the two screws securing the
front plate and rear gland plates. Pull the front gland plate forward, see diagram 10.4. Disconnect the thermocouple at the gas valve and remove.
Use the old thermocouple as a pattern when fitting the new one. Do not tighten more than a quarter turn beyond finger tight at the gas valve.
Check the electrode spark gap, see diagram 10.3.
10.6 Electrode
Generally follow the instructions given in Section 10.1. Unscrew the electrode from the pilot shield. When refitting check that the spark gap is as in
diagram 10.3.
14 to 17 mm
SPARK GAP 3 to 4 mm
ELECTRODE
PILOT FLAME & SPARK GAP
RELEASE SCREWS DO NOT REMOVE AND PULL FRONT GLAND PLATE FORWARD
THERMOCOUPLE
FRONT GLAND
14 to 17 mm
Diagram 10.3
PLATE
1053
0394
10.7 Over Heat Cutoff
Generally follow the instructions in Section 10.1. Remove the two screws securing the over heat cutoff
clamp, see diagram 10.5. Release connections at the gas valve, see diagram 10.6. Release but do not remove the two screws securing the
front and rear gland plates, see diagram 10.4 and withdraw the cutoff leads.
When refitting smear a little of the heat sink compound, supplied, between the face of the cutoff and the water pipe, make sure that it is correctly located on the pipe.
THERMO-
COUPLE PILOT TUBE
GLAND PLATE Diagram 10.4
CUT-OFF SECURING SCREW(S)
OVERHEAT CUT-OFF LEADS
IGNITION LEAD
THERMOSTAT CAPILLARY
OVERHEAT CUT-OFF
HEAT EXCHANGER
RETAINING CLIP
REAR GLAND PLATE
0951
THERMOSTAT PHIAL/OVERHEAT CUT-OFF
18220459C
THERMOSTAT PHIAL
Diagram 10.5
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Servicing and Replacement of Parts
10.8 Gas Valve
Gain access generally as Section 10.4. Remove the screw to release the gas valve cover. Disconnect all leads and pipes at the gas valve. Undo the four screws each side of the gas valve to
release the gas service cock and burner supply tube, take care not to damage the “O” rings.
Fit the new valve and remake all connections. Do not tighten the thermocouple nut more than a quarter
turn beyond finger tight at the gas valve. It will be necessary to purge the pipework and valve
before relighting, refer to Commissioning.
10.9 Electrical Control Box
Remove the controls cover and outer casing as Section 10.1.
Remove the retaining clip from the boiler thermostat phial pocket and withdraw the phial, see diagram 10.5.
Release but do not remove the two screws securing the front and rear gland plates. Pull the gland plates forward.
10.12 Thermostat
Gain access as under Section 10.4. Remove and support control. See Section 10.9. Remove the control knob and electrical connections
from the thermostat. Release, but do not remove, the two screws securing the
front and rear gland plates. Pull the gland plates forward, see diagram 10.4.
Remove the two screws screws securing the thermostat to the control box. The thermostat may now be removed withdrawing the capillary through the bottom of the air duct.
When replacing smear the thermostat phial with the heat sink compound supplied, before fitting and securing in the pocket.
EXT. SCREW (4)
'O' RING
2414
Remove the control box by undoing the two fixing screws at the front and lower the front of the box until it is clear of the cover. Push box toward the rear of the boiler to disengage the hinge and lower, see diagram 7.1.
Withdraw the thermostat capillary through the bottom of the air duct.
Disconnect cables (a) mains, L.N. and E. (b) pump at terminal 8, 7 and earth stud, (c) cables at gas valve, (d) disconnect any remote controls at terminal 9 and SL.
When replacing refer to diagram 7.2 for electrical connections. Smear the thermostat phial with heat sink compound and ensure that it is secured, with the retainer, into the phial pocket.
10.10 Piezo Unit
Gain access as Section 10.4. Disconnect the ignition lead and remove backing nut
from the piezo unit.
10.11 Ignition Lead
Remove the controls cover and outer casing as Section 10.1.
PILOT TUBE NUT
GAS VALVE CONNECTORS
'O' RING
GAS SERVICE COCK (SHOWN OFF)
EXT. SCREW (4)
Release, but do not remove, the two screws securing the front and rear gland plates. Pull the gland plates forward, see diagram 10.4.
Remove the ignition lead, when replacing ensure that the clear end is fitted to the electrode.
INTERRUPTER GAS VALVE ASSEMBLY Diagram 10.6
19
THERMOCOUPLE NUT
ELECTRICAL CONNECTOR (2)
220459C
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Fault Finding
Fault and Cause Remedy
11.1 Pilot goes out after a period of remaining alight
Front cover not fitted correctly Fit parts correctly. Flue parts not fitted or sealed properly. Seal cavity or fit parts flue parts correctly as described
in installation instructions. Electrical supply failure causing overheat cutoff to operate. Relight pilot. Overheat cutoff operating. Refer to 11.3 below
Pump wired incorrectly. Refer to diagram 7.2 and wire accordingly.
11.2 Main burner will not ignite
External controls not on. Check that any external controls are calling for heat. Boiler thermostat not on. Check that boiler thermostat is on. See also
Section 11.9.
11.3 Thermostat will not cut out
Thermostat phial not fitted in pocket. Fit phial in pocket. Faulty thermostat Replace thermostat.
11.4 Overheat cutoff cuts out prematurely
Air in heating body. Vent system. Alter system layout if necessary. Water circulation low or stopped.
Pump not working correctly. Check pump is wired
directly to the boiler. Alter system if necessary. Overheat cutoff operates Change faulty overheat cutoff.
before boiler cycles on maximum boiler thermostat setting.
The correctly set overheat Change faulty heating body. cutoff operates prematurely. There is no air in the heating body and the water circulation is satisfactory.
11.5 Insufficient heat
Thermostat set too low. Increase setting. Inlet gas pressure inadequate. Increase gas pressure. Burner setting incorrect. Check burner pressure against
(ensure thermostat is on data badge.) Reset only if more maximum setting than 10% away
from required figure.
11.6 Appliance noisy in operation*
Overgassed. Check burner pressure against data badge and adjust
Complete lack of water flow. Check system controls for correct installation or
Air in system. Remove air from system. When system is first
Water flow rate. Check that flow rate is correct. Check that pump is
only if more than 10% away from the stated required
figure.
correct type of controls.
commissioned the air dissolved may take some time
to boiler out, therefore attempts should be made to
vent air during the first weeks of the installation.
Check venting of system, as air bubbles can remain
suspended in the water if system is not well vented.
correct size and is correctly adjusted.
Bypass not fitted or correctly set.
20220459C
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Fault Finding
11.7 Thermocouple and Over Heat Cutoff
To test the thermocouple, a meter with a range of0 to 30mV is required.
Symptoms: The pilot burner fails to stay alight. Test the thermocouple, overheat cutoff and thermocouple
connectors, as described in fault finding diagram 11.2 and diagram 11.1.
Check the millivoltage of the thermocouple closed circuit at points “A” and “E” see diagram 11.1.
This should be within the range 6 to 13mV. Take the millivoltage drop reading and refer to thermocouple/ overheat cutoff fault finding diagram 11.2.
2487
CONNECTION 'A'
GAS VALVE
CONNECTION 'E'
CONNECTION 'D'
BOILER OVERHEAT CUT-OFF
With the boiler cold, check connections of the thermocouple, boiler overheat cut-off and gas valve.  Disconnect overheat cut-off connectors at points A and B at the gas valve, see diagram 3.4. Test continuity of the overheat cut-off. Is there continuity?
YES
Re-connect boiler overheat cut-off to points A and B. Disconnect thermocouple at point  D of the gas valve. Test continuity between  point C and the body of the gas valve.  Is there continuity?
NO
Test continuity of thermocouple between inner connection point D and point E. Is there continuity?
YES
NO
CONNECTION 'C'
THERMOCOUPLE
Faulty boiler overheat cut-off,  renew.
Faulty cut-off connectors into gas valve, either at A or C. Renew where faulty.
Faulty thermocouple, renew.
CONNECTION 'B'
Diagram 11.1
2327
NO
YES
Thermocouple and boiler overheat circuit  satisfactory.
THERMOCOUPLE and BOILER OVERHEAT CUT-OFF Diagram 11.2
21
220459C
Page 22
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Fault Finding
ELECTRICAL
Ensure that all services are available at the appliance, i.e. Gas, Electricity, Water. With Pilot Lit.
Isolate the supply. Gain access to the control box, check all connections etc. Restore supply. Using multimeter set at 240V.
YES
Is ther 240 V between L and N ?
YES
Is ther 240 V between 9 and N ?
YES
NO
NO
Check incoming supply and fuses. Repair where required.
Faulty Brown bridge wire between L and 9 Repair where required.
4403
With Red Link removed between 9 and SL and Remote Controls Calling for Duty. Is there 240V between SL and N ?
YES
Is ther 240 V between 9 and N ?
YES
Is ther 240 V between 8 and N ?
YES
Is ther 240 V between 3 and N ?
YES
Turn ON thermostat. With appliance cold. Is there 240V between 6 and N ?
YES
Turn OFF thermostat.  Is there 240V between 6 and N ?
NO
YES
NO
NO
NO
NO
Faulty Remote Controls, inform customer.
Faulty cable (BROWN), from terminal block to thermostat, repair or renew.
Faulty cable (RED), from terminal block to thermostat, repair or renew.
Faulty cable (RED), from terminal block to thermostat, repair or renew.
NO
Faulty thermostat, renew.
Turn ON thermostat. Does main burner light ?
NO
YES
NO
Isolate the supply. Remove gas valve cover. Restoresupply. Is there 240V between 'L' and 'N' on gas valve ?
NO
Turn ON thermostat. With appliance cold. Is there 240V between 7 and N ?
Faulty gas valve harness, renew.
YES
Turn ON thermostat.  Is there 240V between 7 and N ?
YES
YES
NO
Continued
Continued
22220459C
NO
Faulty gas valve, renew.
MAIN TERMINAL STRIP THERMOSTAT TERMINALS
YES
Continued
Diagram 11.3
Page 23
Supplied By www.heating spares.co Tel. 0161 620 6677
ELECTRICAL continued
Continued
NO
Turn ON thermostat; Is there 240V between 7 and N ?
11 Fault Finding
Continued
NO
Faulty Cable (PURPLE) between thermostat and terminal block, repair or renew.
4403A
YES
NO
Does pump run ?
YES
With thermostat set to MAX. allow appliance temperature to reach max. When appliance cuts out on temp. is there 240V between 7 and N ?
NO
YES
With Remote Controls NOT Calling for Duty does pump stop when the appliance has  cooled down ?
NO
YES
CONTROLS IN ORDER
11.8 Electrical
IMPORTANT. On completion of the service/fault finding task which has required the breaking and remaking of electrical connections then the checks, earth continuity, polarity and resistance to earth must be repeated, using suitable multimeter.
To check the boiler thermostat and multifunctional control (gas valve) see diagram 11.3 and functional flow wiring diagram 11.4.
Faulty pump, inform customer
Faulty thermostat, renew.
MAIN TERMINAL STRIP THERMOSTAT TERMINALS
YES
Diagram 11.3 continued
To check thermostat pump over run circuit see diagram 11.3 and functional flow wiring diagram 11.4.
11.9 Pilot
Refer to fault finding for pilot, see diagram 11.5.
PERMANENT LIVE 240V 50 Hz FUSED AT 3A
RED LINK (If no switch control is used)
MAIN TERMINAL STRIP
THERMOSTAT TERMINALS
BRN
9L
SL
SWITCH CONTROL (If used)
COMBINED THERMOSTAT AND PUMP OVERRUN
BROWN
69 8
3
FUNCTIONAL FLOW
23
RED
7
BRN
PURPLE
8
Solenoid
VALVE
BLUE
GAS
7
BLUE
L
N
TO
PUMP
2415
BLUE
BLUE
N
Diagram 11.4
220459C
N
Page 24
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Fault Finding
PILOT WILL NOT LIGHT START HERE
Check gas line-open all cocks, rectify any blockages, purge out  any air. Does pilot light?
NO
Apply match to pilot burner instead of pressing piezo unit button. Does pilot light?
NO YES
Undo tubing nut at pilot burner. Turn gas valve knob to Pilot/Ign. Press gas valve knob. Does gas flow freely?
NO
Rectify blockage in pilot injector, or renew pilot injector.
YES
YES
Does pilot stay alight when gas valve knob is released?
NO YES
PILOT SATISFACTORY
Does pilot flame envelop  thermocouple?
NO
Check aeration. If necessary - Clean pilot, rectify blockage in pilot injector, or replace.
YES
2839
Undo tubing nut at pilot outlet of gas valve. Press gas valve knob. Does gas flow freely?
NO
Change blocked pilot tube.
Change gas valve.
YES
Check thermocouple circuit using Thermocouple and Boiler Overheat Cut-Off fault finding.
On pressing piezo unit button is there a spark across electrode gap?
NO
Pull ignition lead off electrode. Hold end of lead close to pilot burner and operate piezo unit. Is there a spark across gap?
NO
Pull ignition lead off piezo unit. Using blade of a screwdriver, touch  unit chassis and leave approx.  4mm gap from connection tag on piezo unit. Operate piezo. Is there a spark across gap?
NO
YES
YES
YES
PILOT / IGNITION
24220459C
Change piezo unit.
Check electrode gap. Reposition, or replace electrode as necessary.
Change ignition lead.
Diagram 11.5
Page 25
Supplied By www.heating spares.co Tel. 0161 620 6677
12 Spare Parts
12.1 Ordering
When ordering spare parts, quote the part number, description, serial number and model from the label on the boiler, see diagram 8.1.
14
2421
8
7
6
3
1
6A
10
9
2
14
11
12
4
13
5
Diagram 12.1
Key No. Part No. Description G.C. No.
1 433504 Electrical control box 313 053 2 900501 Piezo unit 384 146 3 416189 Boiler thermostat assembly 355 501 4 800014 Over heat cutoff assembly 313 064 5 800015 Gas valve assembly - incs 14 313 067 6 900000 Thermocouple 394 162 6 381 651 7 203415 Pilot burner 394 161 8 202600 Electrode 384 149 9 416144 Thermostat control knob 355 401 10 WW4608 Ignition lead 355 381 11 203028 Injector - Cat 30-1700 - 60B 398 238 11 203089 Injector - Cat 30-2200 - 75B 12 203509 Pilot injector 394 163 13 411194 Sight glass 355 153
Alternatives
}
14 208040 “O” ring for gas valve (2 off) 334 674
25
220459C
Page 26
Supplied By www.heating spares.co Tel. 0161 620 6677
Control of Substances Hazardous to Health
Information for the Installer and Service Engineer.
Under Section 6 of The Health and Safety at Work Act, 1974, we are required to provide information on substances hazardous to health.
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
Insulation and Seals
Ceramic fibre and glass fibre are used in insulation panels, rope and gaskets. The can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaint you may be susceptible to irritation.
High dust levels are usual only if the material is broken. Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating,
drinking or going to the lavatory. If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
Thermostat
This contains a very small amount of xylene in the sealed phial and capillary. If broken, under normal circumstances the fluid does not cause a problem, but in cases of skin contact, wash with cold water.
If swallowed drink plenty of water and seek medical attention.
26220459C
Page 27
Supplied By www.heating spares.co Tel. 0161 620 6677
27
220459C
Page 28
Supplied By www.heating spares.co Tel. 0161 620 6677
Because of our constant endeavour for improvement details may vary slightly from those given in these instructions.
28220459C
Loading...