Glow-worm Dovedale, Chatsworth Installation And Servicing Instrucnion

Supplied By www.heating spares.co Tel. 0161 620 6677
221030F. 01. 99
Installation & Servicing Instructions
T o be left with the user
The Glow-worm Options Collection
Remote Inset Fires
5908
DOVEDALE
Standard Frame
Wide Frame
CHATSWORTH
Standard Frame
5895
Wide Frame
References in these instructions to British Standards and Statutory
Regulations/Requirements apply only to the United Kingdom.
For Ireland the rules in force must be used.
This is a Cat I2H Appliance
Customer Services: Tel: (01773) 828100
One Contact Local Service
Fax: (01773) 828070
BS 6332 BS 5258
Hepworth Heating Ltd.,
Nottingham Road, Belper, Derbyshire. DE56 1JT
General/Sales enquiries:
Tel: (01773) 824141 Fax: (01773) 820569
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
590 WIDE FRAME 547 STANDARD FRAME
Dimensions are the same for the Dovedale except where shown
References in these instructions to British Standards and Statutory Regulations and Requirements apply only to the United Kingdom.
For Ireland the rules in force must be used. The instructions consist of two parts, Installation and Servicing Instructions for the Fire and the Instructions for Use. The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use) Regulations, be handed to the user on completion of the installation.
1 General Notes and Information
There are three cardboard cartons, which together contain all the parts necessary for the fitting of the fire.
You may also have a cardboard carton with a spacer kit in and a cardboard carton with a gas supply kit in.
Chatsworth (black) only. The brass coloured badge on this appliance can be replaced with a silver coloured badge.
Telephone:- The Sales Office on 01773-824141, quote Pt. No. 209310P.
Wherever possible, all materials, appliances and components to be used should comply with the requirements of applicable British Standards.
Where no British Standard exists, materials and equipment should be fit for their purpose and of suitable quality and workmanship.
62 Dovedale 76 Chatsworth
45
Spacer
Kit
652 WIDE FRAME
630 STANDARD FRAME
GENERAL OVERALL DIMENSIONS Chatsworth illustrated
1.1 Important Notice
This fire is for use only on G20 gas @20mbar supply pressure.
The fire is fitted with a safety device (combustion products discharge safety device) which will shut it down if there is inadequate ventilation and the chimney is not clearing the products of combustion.
If the fire shuts down for no apparent reason the flue/ chimney and air inlets into the room must be checked. Any problems found must be put right, by a competent person, before the fire is used again.
IN ALL cases the room must be ventilated before attempting to relight the fire.
The safety device must not be bypassed or put out of action.
The safety device must be serviced strictly in accordance with the instructions in this book.
Sealed components must not be interfered with. Servicing instructions and identification of parts is given
in Sections 6, 7, 8 and 9. It is essential that only genuine Glow-worm parts are
used. All WARNINGS and cautions in these instructions must
be observed.
5985
Safety -WARNING
WHEN NOT IN USE THE REMOTE CONTROL HANDSET MUST BE SECURED WITHIN ITS PRESENTATION BOX AND KEPT IN A SAFE PLACE TO PREVENT ACCIDENTAL MANIPULATION.
221030F
2
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
Sheet Metal Parts
WARNING: When fitting or servicing this fire care should be taken when handling sheet metal parts, to avoid any possibility of personal injury.
1.2 Statutory Requirements
The fitting of this fire must be done by a competent person, in accordance with the current issue and relevant requirements of:-
Manufacturer’s instructions, supplied. The Gas Safety (Installation and Use) Regulations,
The Building Regulations, The Building Standards (Scotland) Regulations, (applicable in Scotland), The Health and Safety at Work Act, The Control of Substances Hazardous to Health, The Electricity at Work Regulations and any applicable local regulations.
Detailed recommendations are contained in the current issue of the following British Standards and Codes of Practice:-
BS1251, BS5440 Part 1 and 2, BS5871, BS6891, BS7671.
Manufacturer’s instructions must not be taken as overriding statutory requirements.
1.4 Data
Gas connection 8mm compression fitting Injector Part No. 205739 Pressure setting Hot 18mbar (7.2 in wg)
Cold 18mbar (7.2 in wg) Heat input - gross - 6.74kw (23,000 Btu/h) Electrical rating 8W Fused at 3A Total appliance
unpacked weight (Approx. 20kg)
Data label is positioned, see diagram 1.1. Serial No. label is positioned, see diagram 1.1.
1.5 Fire Location
This fire is suitable for hearth mounting only. The fire must be secured to a vertical wall face.
This wall face may be a chimney breast or a surround having a minimum flat area as shown in diagram 1.2.
The fire must not be fitted directly onto a carpet , combustible floor or combustible wall.
This fire MUST NOT be fitted in a room used or intended to be used as a bathroom or shower room.
1.3 Certification
This fire is certificated for performance and safety. It is, therefore, important that no alteration is made to the fire without permission, in writing, from Hepworth Heating Ltd.
Any alteration that is not approved by Hepworth Heating Ltd., could invalidate the certification, the warranty and could also infringe the statutory requirements.
CE Mark
The CE mark on this fire shows compliance with:-
1. Directive 90/396/EEC on the approximation of the Laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 89/336/EEC on the harmonization of the Laws of the Member States relating to electromagnetic compatibility.
3. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to electrical equipment designed for use within certain voltage limits.
The fire can be fitted to a purpose made proprietary class “O” - 100oC or 150oC surround.
The fire can be fitted to a precast flue conforming to the requirements of the current issue of BS 1289 Part 1.
The fire can be fitted to a box and flue conforming to the requirements of the current issue of BS715.
A suitable Flue Box and Flue, with instructions, can be bought from:- Selkirk
Their product code No. 125BOX 0405905, see diagram
2.4 for insulation details.
5984
DATA LABEL
SERIAL NO.LABEL
3 221030F
Diagram 1.1
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
690
Chatsworth illustrated (same dimensions for Dovedale)
1.6 Clearances
Restrictions must not be placed around the assembled fire, see diagram 1.2.
A shelf or surround of a maximum depth of 150mm may be fitted, provided clearances are as shown in diagram
1.2. However, for every 25mm extra above the fire the depth of the shelf may be increased by 25mm.
Combustible furniture or materials must not be placed closer than 1 metre to the front or sides of the fire.
1.7 Gas Supply
A concealed supply, from the rear, can be fitted. It is necessary to protect the supply pipe with an
approved sheathing if the fire opening and flue have been used for a solid fuel appliance.
150
150
800 WIDE FRAME
780 NARROW FRAME
Diagram 1.2
1.8 Electrical Supply
WARNING: This fire must be earthed. There are three methods of routing the cable. Rear, right and left hand. All system components shall be of an approved type and
shall be connected in accordance with the current issue of BS7671 and any applicable local regulations.
Connection of the fire and system controls to the mains supply should be through a common isolator, a double pole isolating switch, fused 3A, should be used, having a minimum contact separation of 3mm in all poles.
Wiring to the fire MUST be PVC 85oC insulated type not less than 0.75mm2 (24/0.20mm).
NOTE: Avoid all sharp edges when routing the cable.
6033
The gas installation must be in accordance with the current issue of BS6891.
The supply from the governed meter must be of adequate size to provide 20mbar at the fire.
On completion test the gas installation for soundness using the pressure drop method and suitable leak detection fluid, purge in accordance with the above standard.
221030F
1.9 Unpacking
There are three packs:­Pack 1 - contains Body assembly, Fittings pack and
Pack 2 - contains Frame. Pack 3 - contains Fret, Ashpit cover and (Baffle
Chatsworth only). Diagram 1.3 shows the parts within the three packs. Check contents of loose items pack against packed list. You may also have a cardboard carton with a spacer kit
in and a cardboard carton with a gas supply kit in.
4
Fuel effect supports and pieces.
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
PACK 1
BODY ASSEMBLY
6030
FITTINGS PACK
FUEL EFFECT SUPPORTS AND PIECES
PACK 3 CHATSWORTH
FRET
ASHPIT COVER
PACK 3 DOVEDALE
BAFFLE
PACK 2 In the pack you will have one of these frames
FRAME (Wide)
FRET
ASHPIT COVER
5 221030F
FRAME (Standard)
Diagram 1.3
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Flue System
2 Flue and Ventilation
The minimum effective height of the chimney must be 3metres.
Suitable flues and minimum sizes are as below:­9in x 9in, 7in and 5in proprietary flue pipe. 125mm diameter conventional flue. A brick built wall chimney properly lined with a single
wall, twin wall or flexible flue liner of minimum diameter of 125mm. The materials to be used are stainless steel or aluminium as specified in the current issue of BS715.
2.1 Front Opening, Catchment Space and Minimum Opening Sizes
Note. Dimensions referring to catchment space on diagrams are for 16 inch openings.
For fireplaces where the wall is not plastered and not covered by BS1251 it is important that such installations comply with the current issue of The Building Regulations.
The catchment space and opening sizes must not be less than dimensions as given in diagram 2.1.
Catchment space
501
555
560 MIN
55 MIN
215 MIN 170 MIN If spacer kit is fitted
Remove Combustible Material From this Area
690 MIN
SPACER KIT
45
Diagram 2.1
5987
5988
Any combustible material, for example, blown vinyl wall coverings, on the fire fixing face area of the surround must be removed, see diagram 2.2.
2.2 Hearth Fixing
In ALL cases a fireproof hearth to the minimum dimensions as shown in diagram 2.3 must be fitted.
2.3 Firebox
The fire can be installed using a firebox conforming to the current issue of BS715, see Section 1.5.
The fire box must stand on non-combustible hearth of at least 50mm thickness. The top sides and rear of the box must be covered with a 50mm minimum thickness of mineral wool insulation, see diagram 2.4.
NOTE: If the firebox is already fitted it must be insulated as above.
2.4 Precast Flue
This fire is suitable for fitting to a precast flue.
405 MIN 500 MAX
FRONT
OPENING
560 MIN 590 MAX
800 MIN WIDE FRAME
Diagram 2.2
780 MIN STANDARD FRAME
6034
There must be a minimum vertical equivalent height of 3metres. The minimum dimension in the horizontal cross section of the flue shall be 90mm. The cross sectional area of the flueshall be not less than 16500 mm2.
221030F
6
13
MATERIAL
NON-COMBUSTIBLE
300
50MIN
600
Diagram 2.3
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Flue and Ventilation
2.5 Precast Flue Minimum Opening Sizes
Refer to diagram 2.5. Note: If a precast flue starter block to BS1289 Part 1 is
used. Fit a fire surround, if this does not give sufficient depth to fit the fire fit a spacer kit. You may also remove material as shown in diagram 2.5.
2.6 Check the Chimney
The chimney should be swept immediately before fitting the fire.
However, where it can be seen that the chimney is clean and unobstructed and there is no evidence that solid fuel has been used, it need not be swept.
Remove any damper or register plate. Alternatively it may be locked in the open position.
Before fitting the fire make sure that the base of the chimney is clear of debris.
If the fire is to be fitted to a fireplace in which the air enters from below floor level this supply must be sealed off.
FIRE BOX
50 MIN. BASE
6023
50 MIN. THICKNESS OF INSULATION
Diagram 2.4
2.7 Test the Flue
Apply a lighted smoke match, or taper at the opening. If there is a definite flow into the opening the fitting of
the fire can continue. If there is no definite flow into the opening preheat the
chimney for about two minutes then recheck the flow. If there is still no definite flow the problem MUST be
put right before continuing with fitting of the fire.
405 MIN 500 MAX
305 MIN
560 MIN 590 MAX
VIEW LOOKING INTO THE APPLIANCE OPENING
TYPICAL STARTER BLOCK
Note: It may be necessary to remove material from the opening to allow fire installation, care must be taken not to affect the constructional integrity of the precast starter blocks.
6120
115 MIN
205*
7 221030F
* NB if 45mm Spacer kit is used Part No. - 454024 wide frame
- 454029 standard frame
this dimension may be reduced to 160mm
Diagram 2.5
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Electrical Supply, Gas Supply and Fire Fixing
3.1 Fire Fixing - Electrical Cable Routing
It is essential at this time that you decide which way the cable is to be routed.
Remove the burner and control box, take care not to damage any components, see diagram 3.1.
1) Rear cable routing: Make a hole in the grommet, push the cable through. Refer to Section 1.8 and use enough cable to allow for
the future removal of the burner and control box, see diagram 3.2.
2) Left and Right hand cable routing: Refer to Section 1.8 and use enough cable to allow for
the future removal of the burner and control box, see diagram 3.2.
Note: Avoid all sharp edges when routing the cable.
3.2 Gas Supply - Connection
Refer to diagram 3.3. Where the fire is fitted in nurseries, old people’s homes
and the like, the isolation device may be of the type fitted with a removable key.
A flexible connection MUST NOT be used. If the gas supply is through the rear of the appliance, the
angled gas service cock is used to isolate the fire. Note: Left and right hand preformed pipe supply kits can
be bought. Part numbers 453925 (left hand) and 453926 (right hand). A means of isolating the gas inlet supply must be fitted.
BURNER ASSEMBLY SECURING SCREW
BURNER ASSEMBLY
MED
OFF
LOW
CONTROL BOX
CONTROL BOX SECURING SCREW
5904
COAL
HIGH
AUTO
MANUAL
COKE
BURNER ASSEMBLY SECURING SCREW
Diagram 3.1
221030F
8
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Electrical Supply, Gas Supply and Fire Fixing
380
330
L.H. CABLE LENGTH
480
R.H. CABLE LENGTH
GROMMET
REAR CABLE LENGTH
5961
These dimensions are the same for R/H and L/H
117
25
FIRE FIXING FACE
REAR
CENTRE LINE OF APPLIANCE
REAR OF APPLIANCE
C
L
50
C
L
6118
5970
Lengths of cable required inside the appliance for rear, right hand and left hand cable routing.
Diagram 3.2
LEFT HAND
Kit Number 453926
RIGHT HAND
Route gas supply pipe to give operating clearance around the manual override spindle on the gas control valve and the coke lever. To identify these parts, see diagram 4.1.
Kit Number 453925
Diagram 3.3
9 221030F
Loading...
+ 19 hidden pages