Glow-worm Dovedale, Chatsworth Installation And Servicing Instrucnion

Supplied By www.heating spares.co Tel. 0161 620 6677
221030F. 01. 99
Installation & Servicing Instructions
T o be left with the user
The Glow-worm Options Collection
Remote Inset Fires
5908
DOVEDALE
Standard Frame
Wide Frame
CHATSWORTH
Standard Frame
5895
Wide Frame
References in these instructions to British Standards and Statutory
Regulations/Requirements apply only to the United Kingdom.
For Ireland the rules in force must be used.
This is a Cat I2H Appliance
Customer Services: Tel: (01773) 828100
One Contact Local Service
Fax: (01773) 828070
BS 6332 BS 5258
Hepworth Heating Ltd.,
Nottingham Road, Belper, Derbyshire. DE56 1JT
General/Sales enquiries:
Tel: (01773) 824141 Fax: (01773) 820569
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
590 WIDE FRAME 547 STANDARD FRAME
Dimensions are the same for the Dovedale except where shown
References in these instructions to British Standards and Statutory Regulations and Requirements apply only to the United Kingdom.
For Ireland the rules in force must be used. The instructions consist of two parts, Installation and Servicing Instructions for the Fire and the Instructions for Use. The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use) Regulations, be handed to the user on completion of the installation.
1 General Notes and Information
There are three cardboard cartons, which together contain all the parts necessary for the fitting of the fire.
You may also have a cardboard carton with a spacer kit in and a cardboard carton with a gas supply kit in.
Chatsworth (black) only. The brass coloured badge on this appliance can be replaced with a silver coloured badge.
Telephone:- The Sales Office on 01773-824141, quote Pt. No. 209310P.
Wherever possible, all materials, appliances and components to be used should comply with the requirements of applicable British Standards.
Where no British Standard exists, materials and equipment should be fit for their purpose and of suitable quality and workmanship.
62 Dovedale 76 Chatsworth
45
Spacer
Kit
652 WIDE FRAME
630 STANDARD FRAME
GENERAL OVERALL DIMENSIONS Chatsworth illustrated
1.1 Important Notice
This fire is for use only on G20 gas @20mbar supply pressure.
The fire is fitted with a safety device (combustion products discharge safety device) which will shut it down if there is inadequate ventilation and the chimney is not clearing the products of combustion.
If the fire shuts down for no apparent reason the flue/ chimney and air inlets into the room must be checked. Any problems found must be put right, by a competent person, before the fire is used again.
IN ALL cases the room must be ventilated before attempting to relight the fire.
The safety device must not be bypassed or put out of action.
The safety device must be serviced strictly in accordance with the instructions in this book.
Sealed components must not be interfered with. Servicing instructions and identification of parts is given
in Sections 6, 7, 8 and 9. It is essential that only genuine Glow-worm parts are
used. All WARNINGS and cautions in these instructions must
be observed.
5985
Safety -WARNING
WHEN NOT IN USE THE REMOTE CONTROL HANDSET MUST BE SECURED WITHIN ITS PRESENTATION BOX AND KEPT IN A SAFE PLACE TO PREVENT ACCIDENTAL MANIPULATION.
221030F
2
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
Sheet Metal Parts
WARNING: When fitting or servicing this fire care should be taken when handling sheet metal parts, to avoid any possibility of personal injury.
1.2 Statutory Requirements
The fitting of this fire must be done by a competent person, in accordance with the current issue and relevant requirements of:-
Manufacturer’s instructions, supplied. The Gas Safety (Installation and Use) Regulations,
The Building Regulations, The Building Standards (Scotland) Regulations, (applicable in Scotland), The Health and Safety at Work Act, The Control of Substances Hazardous to Health, The Electricity at Work Regulations and any applicable local regulations.
Detailed recommendations are contained in the current issue of the following British Standards and Codes of Practice:-
BS1251, BS5440 Part 1 and 2, BS5871, BS6891, BS7671.
Manufacturer’s instructions must not be taken as overriding statutory requirements.
1.4 Data
Gas connection 8mm compression fitting Injector Part No. 205739 Pressure setting Hot 18mbar (7.2 in wg)
Cold 18mbar (7.2 in wg) Heat input - gross - 6.74kw (23,000 Btu/h) Electrical rating 8W Fused at 3A Total appliance
unpacked weight (Approx. 20kg)
Data label is positioned, see diagram 1.1. Serial No. label is positioned, see diagram 1.1.
1.5 Fire Location
This fire is suitable for hearth mounting only. The fire must be secured to a vertical wall face.
This wall face may be a chimney breast or a surround having a minimum flat area as shown in diagram 1.2.
The fire must not be fitted directly onto a carpet , combustible floor or combustible wall.
This fire MUST NOT be fitted in a room used or intended to be used as a bathroom or shower room.
1.3 Certification
This fire is certificated for performance and safety. It is, therefore, important that no alteration is made to the fire without permission, in writing, from Hepworth Heating Ltd.
Any alteration that is not approved by Hepworth Heating Ltd., could invalidate the certification, the warranty and could also infringe the statutory requirements.
CE Mark
The CE mark on this fire shows compliance with:-
1. Directive 90/396/EEC on the approximation of the Laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 89/336/EEC on the harmonization of the Laws of the Member States relating to electromagnetic compatibility.
3. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to electrical equipment designed for use within certain voltage limits.
The fire can be fitted to a purpose made proprietary class “O” - 100oC or 150oC surround.
The fire can be fitted to a precast flue conforming to the requirements of the current issue of BS 1289 Part 1.
The fire can be fitted to a box and flue conforming to the requirements of the current issue of BS715.
A suitable Flue Box and Flue, with instructions, can be bought from:- Selkirk
Their product code No. 125BOX 0405905, see diagram
2.4 for insulation details.
5984
DATA LABEL
SERIAL NO.LABEL
3 221030F
Diagram 1.1
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
690
Chatsworth illustrated (same dimensions for Dovedale)
1.6 Clearances
Restrictions must not be placed around the assembled fire, see diagram 1.2.
A shelf or surround of a maximum depth of 150mm may be fitted, provided clearances are as shown in diagram
1.2. However, for every 25mm extra above the fire the depth of the shelf may be increased by 25mm.
Combustible furniture or materials must not be placed closer than 1 metre to the front or sides of the fire.
1.7 Gas Supply
A concealed supply, from the rear, can be fitted. It is necessary to protect the supply pipe with an
approved sheathing if the fire opening and flue have been used for a solid fuel appliance.
150
150
800 WIDE FRAME
780 NARROW FRAME
Diagram 1.2
1.8 Electrical Supply
WARNING: This fire must be earthed. There are three methods of routing the cable. Rear, right and left hand. All system components shall be of an approved type and
shall be connected in accordance with the current issue of BS7671 and any applicable local regulations.
Connection of the fire and system controls to the mains supply should be through a common isolator, a double pole isolating switch, fused 3A, should be used, having a minimum contact separation of 3mm in all poles.
Wiring to the fire MUST be PVC 85oC insulated type not less than 0.75mm2 (24/0.20mm).
NOTE: Avoid all sharp edges when routing the cable.
6033
The gas installation must be in accordance with the current issue of BS6891.
The supply from the governed meter must be of adequate size to provide 20mbar at the fire.
On completion test the gas installation for soundness using the pressure drop method and suitable leak detection fluid, purge in accordance with the above standard.
221030F
1.9 Unpacking
There are three packs:­Pack 1 - contains Body assembly, Fittings pack and
Pack 2 - contains Frame. Pack 3 - contains Fret, Ashpit cover and (Baffle
Chatsworth only). Diagram 1.3 shows the parts within the three packs. Check contents of loose items pack against packed list. You may also have a cardboard carton with a spacer kit
in and a cardboard carton with a gas supply kit in.
4
Fuel effect supports and pieces.
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
PACK 1
BODY ASSEMBLY
6030
FITTINGS PACK
FUEL EFFECT SUPPORTS AND PIECES
PACK 3 CHATSWORTH
FRET
ASHPIT COVER
PACK 3 DOVEDALE
BAFFLE
PACK 2 In the pack you will have one of these frames
FRAME (Wide)
FRET
ASHPIT COVER
5 221030F
FRAME (Standard)
Diagram 1.3
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Flue System
2 Flue and Ventilation
The minimum effective height of the chimney must be 3metres.
Suitable flues and minimum sizes are as below:­9in x 9in, 7in and 5in proprietary flue pipe. 125mm diameter conventional flue. A brick built wall chimney properly lined with a single
wall, twin wall or flexible flue liner of minimum diameter of 125mm. The materials to be used are stainless steel or aluminium as specified in the current issue of BS715.
2.1 Front Opening, Catchment Space and Minimum Opening Sizes
Note. Dimensions referring to catchment space on diagrams are for 16 inch openings.
For fireplaces where the wall is not plastered and not covered by BS1251 it is important that such installations comply with the current issue of The Building Regulations.
The catchment space and opening sizes must not be less than dimensions as given in diagram 2.1.
Catchment space
501
555
560 MIN
55 MIN
215 MIN 170 MIN If spacer kit is fitted
Remove Combustible Material From this Area
690 MIN
SPACER KIT
45
Diagram 2.1
5987
5988
Any combustible material, for example, blown vinyl wall coverings, on the fire fixing face area of the surround must be removed, see diagram 2.2.
2.2 Hearth Fixing
In ALL cases a fireproof hearth to the minimum dimensions as shown in diagram 2.3 must be fitted.
2.3 Firebox
The fire can be installed using a firebox conforming to the current issue of BS715, see Section 1.5.
The fire box must stand on non-combustible hearth of at least 50mm thickness. The top sides and rear of the box must be covered with a 50mm minimum thickness of mineral wool insulation, see diagram 2.4.
NOTE: If the firebox is already fitted it must be insulated as above.
2.4 Precast Flue
This fire is suitable for fitting to a precast flue.
405 MIN 500 MAX
FRONT
OPENING
560 MIN 590 MAX
800 MIN WIDE FRAME
Diagram 2.2
780 MIN STANDARD FRAME
6034
There must be a minimum vertical equivalent height of 3metres. The minimum dimension in the horizontal cross section of the flue shall be 90mm. The cross sectional area of the flueshall be not less than 16500 mm2.
221030F
6
13
MATERIAL
NON-COMBUSTIBLE
300
50MIN
600
Diagram 2.3
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Flue and Ventilation
2.5 Precast Flue Minimum Opening Sizes
Refer to diagram 2.5. Note: If a precast flue starter block to BS1289 Part 1 is
used. Fit a fire surround, if this does not give sufficient depth to fit the fire fit a spacer kit. You may also remove material as shown in diagram 2.5.
2.6 Check the Chimney
The chimney should be swept immediately before fitting the fire.
However, where it can be seen that the chimney is clean and unobstructed and there is no evidence that solid fuel has been used, it need not be swept.
Remove any damper or register plate. Alternatively it may be locked in the open position.
Before fitting the fire make sure that the base of the chimney is clear of debris.
If the fire is to be fitted to a fireplace in which the air enters from below floor level this supply must be sealed off.
FIRE BOX
50 MIN. BASE
6023
50 MIN. THICKNESS OF INSULATION
Diagram 2.4
2.7 Test the Flue
Apply a lighted smoke match, or taper at the opening. If there is a definite flow into the opening the fitting of
the fire can continue. If there is no definite flow into the opening preheat the
chimney for about two minutes then recheck the flow. If there is still no definite flow the problem MUST be
put right before continuing with fitting of the fire.
405 MIN 500 MAX
305 MIN
560 MIN 590 MAX
VIEW LOOKING INTO THE APPLIANCE OPENING
TYPICAL STARTER BLOCK
Note: It may be necessary to remove material from the opening to allow fire installation, care must be taken not to affect the constructional integrity of the precast starter blocks.
6120
115 MIN
205*
7 221030F
* NB if 45mm Spacer kit is used Part No. - 454024 wide frame
- 454029 standard frame
this dimension may be reduced to 160mm
Diagram 2.5
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Electrical Supply, Gas Supply and Fire Fixing
3.1 Fire Fixing - Electrical Cable Routing
It is essential at this time that you decide which way the cable is to be routed.
Remove the burner and control box, take care not to damage any components, see diagram 3.1.
1) Rear cable routing: Make a hole in the grommet, push the cable through. Refer to Section 1.8 and use enough cable to allow for
the future removal of the burner and control box, see diagram 3.2.
2) Left and Right hand cable routing: Refer to Section 1.8 and use enough cable to allow for
the future removal of the burner and control box, see diagram 3.2.
Note: Avoid all sharp edges when routing the cable.
3.2 Gas Supply - Connection
Refer to diagram 3.3. Where the fire is fitted in nurseries, old people’s homes
and the like, the isolation device may be of the type fitted with a removable key.
A flexible connection MUST NOT be used. If the gas supply is through the rear of the appliance, the
angled gas service cock is used to isolate the fire. Note: Left and right hand preformed pipe supply kits can
be bought. Part numbers 453925 (left hand) and 453926 (right hand). A means of isolating the gas inlet supply must be fitted.
BURNER ASSEMBLY SECURING SCREW
BURNER ASSEMBLY
MED
OFF
LOW
CONTROL BOX
CONTROL BOX SECURING SCREW
5904
COAL
HIGH
AUTO
MANUAL
COKE
BURNER ASSEMBLY SECURING SCREW
Diagram 3.1
221030F
8
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Electrical Supply, Gas Supply and Fire Fixing
380
330
L.H. CABLE LENGTH
480
R.H. CABLE LENGTH
GROMMET
REAR CABLE LENGTH
5961
These dimensions are the same for R/H and L/H
117
25
FIRE FIXING FACE
REAR
CENTRE LINE OF APPLIANCE
REAR OF APPLIANCE
C
L
50
C
L
6118
5970
Lengths of cable required inside the appliance for rear, right hand and left hand cable routing.
Diagram 3.2
LEFT HAND
Kit Number 453926
RIGHT HAND
Route gas supply pipe to give operating clearance around the manual override spindle on the gas control valve and the coke lever. To identify these parts, see diagram 4.1.
Kit Number 453925
Diagram 3.3
9 221030F
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Electrical Supply, Gas Supply and Fire Fixing
3.3 Fire Fixing
There are two methods of fixing the fire:­Method 1 - Standard fixing, see diagram 3.4. Standard
fixing with Spacer Kit, see diagram 3.5. Use a 10mm masonry drill bit to drill the fire fixing wall
face. Drill to a minimum depth of 40mm to accept the reusable anchor nuts and screws.
Note. If the fire fixing wall face is not of a solid construction, use the cable fixing method.
Method 2 - Cable fixing, see diagram 3.6. To fix secure the four eyelets in the fire opening. Attach the cables to the upper cable tensioning brackets at the rear of the appliance. Thread the cables down through the eyelets, forward through the holes at the bottom rear of the appliance and out through holes in the lower cable tensioning brackets. As you offer the appliance to the wall pull the slack cable tight. Thread the cables through the cable clamps pull tight and secure with the cable clamp locking screws. Apply extra tension if required using the adjuster wing nuts. Loop the excess cable, do not cut it off.
Cable fixing with Spacer Kit, see diagram 3.7. Fit the spacer kit to the appliance. Then follow the instructions as Method 2 - Cable fixing.
SECURING SCREW (4)
ANCHOR NUT (4)
5911
A. SECURING SCREW (4)
ANCHOR NUT (4)
Diagram 3.4
B. SECURING SCREW (4)
A
B
SPACER
5978
221030F
10
Diagram 3.5
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Electrical Supply, Gas Supply and Fire Fixing
5979
285
40
6MM
230
Location holes for the eyelets (4 off)
UPPER TENSIONING BRACKET on the rear of the appliance (2 off)
FIRE OPENING
5919
285
40
6MM
230
Location holes for the eyelets (4 off)
UPPER TENSIONING BRACKET on the rear of the appliance (2 off)
FIRE OPENING
SPACER
CABLE CLAMP (2 off)
LOCKING SCREW
NOTE :- Loop excess cable do not cut off.
LOWER
EYELET (4)
TENSIONING BRACKET (2 off)
ADJUSTER WING NUT (2 off)
Diagram 3.6
EYELET (4)
SECURING SCREW (4)
LOWER
CABLE CLAMP (2 off)
LOCKING SCREW
TENSIONING BRACKET (2 off)
ADJUSTER
WING NUT NOTE :- Loop excess cable do not cut off.
11 221030F
(2 off)
Diagram 3.7
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Electrical Supply, Gas Supply and Fire Fixing
3. 4 Electrical Wiring - Control Box
With the burner and control box already removed, remove the control box lid, see diagram 3.8.
Connect the mains cable to the terminals as shown in diagram 3.9.
CAUTION: Take care not to damage the PCB board or loosen any other cables.
Refit control box lid.
CONTROL BOX LID
HOOK
5973
Refit the burner, but leave the control box loose, to help with the connecting up of the gas supply, see diagram
3.10. Connect the gas supply, see diagram 3.11. IMPORTANT: Restrain the mains cable using the clip
at the rear of the control box, see diagram 3.12. Secure the control box ensuring any excess cable is to
the back of the control box. NOTE: Avoid all sharp edges when routing the cable.
OFF
SECURING SCREW
LOW
MED
HIGH
AUTO
MANUAL
CONTROL BOX
LNE
Diagram 3.8
5965
MAINS CABLE
221030F
12
TERMINAL BLOCK
HIGHMED
AUTO
MANUAL
Diagram 3.9
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Electrical Supply, Gas Supply and Fire Fixing
5912
SLIDE OVER BURNER SUPPORT TAB
BURNER
BURNER ASSEMBLY (Secure with previously removed securing screws)
SLIDE UNDER BURNER RETAINING TAB
OFF
LO
AUTO
MANUAL
SLIDE OVER BURNER SUPPORT TAB
BURNER
GAS SUPPLY PIPE TO GAS CONTROL VALVE
Rear outlet illustrated
UNION NUT
Diagram 3.11
CONTROL BOX
5971
MAINS CABLE
Diagram 3.10
CONTROL BOX
CABLE RESTRAINT CLIP
Diagram 3.12
5990
13 221030F
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Lighting, Testing and Fitting of Internal Parts
NOTE: The fire is fitted with a safety device. The information in Section 1 must be observed.
4.1 Lighting and Testing
Remove the pressure test nipple screw and fit a suitable pressure gauge, see diagram 4.1.
Turn the gas supply on at the mains supply and at the gas service cock.
To check for gas soundness, apply leak detection fluid to all joints.
Switch on electrical supply.
Lighting the Fire
Air may be present in the supply to the fire so that the initial lighting operation may need to be repeated.
Check all three methods of lighting the fire:
1. Remote Handset
2. Control Box
3. Manual Control
WARNING! Take care when doing the following checks, as the burner has a naked flame.
WARNING! The hand control must be kept in your possession whilst doing the following checks.
IMPORTANT NOTE
"Remote or Control Box" lighting method. If a flame is not detected during the ignition period the control will go to lock out. Press the OFF button to reset.
Method 1. - Remote Handset.
Fit the two batteries supplied in the fittings pack into the remote handset.
Set switch to Auto, see diagram 4.1. Point hand control towards the control box. Press either the Low, Med or High button to light the
fire, then, wait for 20 seconds before selecting the desired setting. Check all settings Low, Med and High.
IMPORTANT. IF DURING THE LIGHTING PROCEDURE THE BURNER IS EXTINGUISHED OR GOES OUT FOR ANY OTHER REASON, WAIT AT LEAST 3 MINUTES BEFORE RELIGHTING. REPEATED ATTEMPTS TO RELIGHT WITHOUT THIS DELAY MUST NOT BE CARRIED OUT.
Method 2. - Control Box.
Press either the Low, Med or High button to light the fire, then, wait for 20 seconds before selecting the desired setting. Check all settings Low, Med and High.
IMPORTANT. IF DURING THE LIGHTING PROCEDURE THE BURNER IS EXTINGUISHED OR GOES OUT FOR ANY OTHER REASON, WAIT AT LEAST 3 MINUTES BEFORE RELIGHTING. REPEATED ATTEMPTS TO RELIGHT WITHOUT THIS DELAY MUST NOT BE CARRIED OUT.
Method 3. - Manual Control
Set switch on control box to manual, see diagram 4.1. Push in and keep in manual override spindle on gas
control, see diagram 4.1. Light the burner with a match or spill, keep the control knob pushed in for about fifteen seconds.
Using this method the fire will only work on Low setting.
IMPORTANT. If the burner goes out for any reason wait at least three minutes before attempting to relight.
Coal or Coke Lever
The aeration to the burner can be adjusted to give a yellow Coal flame or a bluer Coke appearance.
To achieve these effects push the lever up for Coal effect and down for Coke, see diagram 4.1.
Testing - Gas Soundness and Rate
With the burner lit, check all joints for gas soundness, at all control positions, in accordance with the current issue of BS6891.
Check that the gas pressure is as stated in the Data Section or on the Data Label.
If there is any doubt about the gas rate, check at the meter, having first turned off all other gas appliances and pilot lights.
GAS CONTROL VALVE
MANUAL OVERRIDE SPINDLE
CONTROL BOX
INFRA RED RECEIVER FILTER
221030F
FIRE SETTING BUTTONS
14
PRESSURE TEST NIPPLE
AUTO
HIGHMEDLOWOFF
MANUAL
AUTO/MANUAL SELECTION
COAL
COKE
5964
COAL/COKE SETTING LEVER
Diagram 4.1
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Lighting, Testing and Fitting of Internal Parts
The gas rate for this fire at high setting is 22.68 ft3/h (0.8 m3/h).
Press the OFF button for "Remote" or "Control Box" method or switch "Auto/Manual switch to Auto.
Remove the pressure gauge, refit the screw and make sure that a gas tight seal is made.
FIRE FRAME
4.2 Fire Frame
Remove the frame from the packaging. Fit as shown in diagram 4.2.
4.3 Fuelbed, Fret and Ashpit Fitting
CAUTION. If the fuel effect bed supports and fuel effect pieces are damaged, do not light the fire or further
5898
test until replacement parts are fitted. USE ONLY THE FUEL EFFECT APPROVED FOR
THIS FIRE. DO NOT USE MORE FUEL EFFECT PIECES THAN
SPECIFIED. DO NOT CHANGE THE LAYOUT OF THE FUEL
EFFECT PIECES. Chatsworth only - Remove the baffle plate from the fret
pack and fit as diagram 4.3.
The importance of positioning the fuel effect pieces correctly cannot be overemphasised if sooting is to be avoided. The flame effect may also be impaired and the life of the fuel effect pieces reduced if assembly directions are not followed.
SECURING SCREW (2)
SECURING SCREW (2)
FIRE FRAME
Diagram 4.2
Before positioning the fuel effect pieces, study carefully the illustrations showing the layout procedure of the pieces, see diagram 4.4.
Follow the steps which are shown numerically in the fuelbed fitting sequence starting at Step 1, making sure that each stage is completed before carrying on to the next and that all written instructions are adhered to, see diagram 4.4.
STEP 1. When fitting the front support make sure the feet are located at the back of the retaining lip and the support fits between the brackets.
STEP 2. Fit the side supports tightly into the front corners touching the side and front of the appliance.
STEP 3. Fit the rear support, make sure it sits on the bottom of the brackets, by pushing it down firmly.
STEP 4. Fit the middle support over the burner make sure it sits behind the brackets on the burner. Keep the support clear of the cross lighting ports.
STEP 5. Place the two large fuel effect pieces with the
5980
flat bases and round indents down. Leave gaps around the pieces.
NOTE : The remaining fuel effect pieces can be turned
as required to maintain a constant gap around each fuel effect piece.
STEP 5 CONTINUED. Place four small fuel effect
OFF
LOW
MED
HIGH
AUTO
MANUAL
pieces starting from the outside. Leaving gaps around the pieces. The left hand outside piece must touch the side of the fire. The right hand outside piece must touch the left
BAFFLE PLATE (Chatsworth only)
Diagram 4.3
hand side of the burner support bracket. STEP 6. Place seven small fuel effect pieces on the
middle support starting from the outside.
15 221030F
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Lighting, Testing and Fitting of Internal Parts
STEP 1 - Front support
Make sure feet are behind retaining lip
STEP 2 - Side supports
Make sure cut-out
is on bottom
NOTE : The fuel effect pieces can be rotated to achieve a random effect.
STEP 5 - 2 Large & 4 small fuel effect pieces
IMPORTANT Leave 3mm gap between all fuel effect pieces and middle support
Touch the side
Fit 4 small fuel effect pieces
Place the 2 LARGE fuel effect pieces with flat bases and round indents down
Middle support
To touch the left hand side of support bracket
STEP 6 - 7 Small fuel effect pieces
Sit 7 fuel effect pieces on the middle support
Touch the side
Leave gaps around pieces
Touch the side
5982
Position pieces to touch the front and side
STEP 3 - Rear support
Fit this way up
Make sure the rear support sits on the bottom of the brackets by pushing it down firmly
STEP 4 - Middle support
Keep cross lighting
ports clear
IMPORTANT This row of fuel effect pieces must not overlap the front row of fuel effect pieces. Position as shown on the front edge of the middle support
STEP 7 - 6 Small fuel effect pieces
Touch the side
Leave
gaps
around
pieces
IMPORTANT This row of fuel effect pieces must not overlap the middle row of fuel effect pieces.
STEP 8 - 5 Small fuel effect pieces
Fit 5 fuel effect pieces they must touch rear of fire
Not to touch the side
This row of fuel effect pieces can overlap slightly
Not to touch the side
Leave gaps around pieces
Touch the side
Sit 6 small fuel effect pieces on rear support
221030F
16
Diagram 4.4
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Lighting, Testing and Fitting of Internal Parts
Leaving gaps around the pieces. The two outside pieces touch the sides of the fire.
STEP 7. Place six small fuel effect pieces on the six flat areas of the rear support starting from the outside. Leaving gaps around the pieces. The two outside pieces touch the sides of the fire.
STEP 8. Place five small fuel effect pieces on the top of the rear support starting from the outside overlapping slightly the previously fitted pieces and touching the rear of the fire. Leaving gaps around the front and side of the pieces. The two outside pieces do not touch the sides of the fire.
When you have fitted all the small fuel effect pieces you may have to adjust some slightly to maintain even spacing.
Fit the fret and ashpit cover as shown in diagram 4.5 and
4.6. Take care not to damage the frame.
Chatsworth (Black only).
The brass coloured badge on this appliance can be replaced with a silver coloured badge.
FRET RETAINING BRACKET
FRET (Chatsworth shown)
5972
Diagram 4.5
Telephone:- The Sales Office on 01773-824141,
quote Pt. No. 209310P.
4.5 Testing for Clearance of Products
The fire must be fitted with all its parts. Make sure that all doors and windows in the room are
closed. Using the remote handset, light the fire, set to high and
coke, run for five minutes. Insert smoke match as shown in diagram 4.7. Check that most of the smoke is drawn in. If there is any doubt, leave the fire alight for a further
ten minutes and repeat test. If there is a fan in an adjacent room, open the
interconnecting doors, light the fire and repeat the test with the fan running.
In ALL cases, if spillage occurs the cause must be found and put right before the fire is left.
IF THE FAULT CANNOT BE PUT RIGHT, THE FIRE MUST BE DISCONNECTED AND EXPERT ADVICE SOUGHT.
ASHPIT COVER (Chatsworth Shown)
50mm
5975
Diagram 4.6
70mm
5981
SMOKE MATCH
17 221030F
Diagram 4.7
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Instructions to User
5 Instructions to User
Hand the Instructions for Use to the user and make sure that they are understood.
Refer to the Instructions for Use on how to light the fire. Advise the customer that they should read their Users
instructions before operating the fire and always follow the advice in the Section headed “Cleaning your Fire”.
Advise that any smell which may be apparent on initial lighting is quite normal and it will quickly disappear.
IMPORTANT: Advise that soft wall coverings, for example, blown vinyl wallpaper, are easily affected by heat, they may, therefore, scorch or become discoloured when close to a heating appliance. This should be borne in mind when having a heating appliance installed and when redecorating.
Advise that to ensure the continued efficient and safe operation of the fire it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the particular installation and usage, but in general once a year should be enough.
Advise that the chimney must be checked at least once a year and any debris found removed.
Draw attention, if applicable, to the current issue of the Gas Safety (Installation and Use) Regulations, 35, which imposes a duty of care on all persons who let out any property containing a gas appliance.
It is the Law that any servicing must be carried out by a competent person.
Reminder, leave these instructions with the user.
221030F
18
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Servicing
6.1 Notes
To ensure the continued efficient and safe operation of the fire it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the particular installation and usage, but in general once a year should be enough.
It is the Law that any servicing is carried out by a competent person.
Refer to Section 1. Before starting make sure that the gas and electrical
supplies are turned off. Make sure that the fire is cold before doing any servicing. After servicing of parts always test for gas soundness
with a suitable leak detection fluid. WARNING. Take care as the burner has a naked flame. To test the gas control assembly apply leak detection
fluid to all joints, light the burner and check all joints for leakage at all settings.
Carry out functional check of controls. After removing or disconnecting any pipework always
make sure that it is refitted correctly and does not interfere with the fitting of the fire.
6.4 Burner Assembly / Control Box
Disconnect the gas supply, see diagram 3.11. Remove the burner, refer to diagram 3.1.
6.5 Burner
The burner can be cleaned in position, using a suitable soft brush or vacuum cleaner.
Do not use a brush with wire bristles.
6.6 Injector
Disconnect the gas supply pipe union nut from the injector. Pull the pipe down to allow easier removal, see diagram 6.1.
Do not clean the hole with a wire or sharp instrument.
BURNER SECURING SCREWS
5932
Unless stated otherwise all parts are replaced in the reverse order to removal.
6.2 Fret and Ashpit Cover
Remove Fret and Ashpit cover, see diagram 4.5 and 4.6.
6.3 Fuel Effect Bed Supports and Fuel Effect Pieces
Following steps 1 to 8 in reverse order, remove the fuel effect pieces and fuel effect supports, see diagram 4.4.
Care should be taken as they become fragile with use. Clean the fuel effect pieces and the fuel effect supports
with a soft brush. IMPORTANT: A VACUUM CLEANER MUST NOT
BE USED ON FUEL EFFECT PIECES OR FUEL EFFECT SUPPORTS.
With the fuel effect pieces and fuel effect supports removed, the base of the appliance may be cleaned
with a vacuum cleaner.
NOTE: The Importance of positioning the fuel effect pieces correctly cannot be overemphasised if sooting is to be avoided. The flame effect may also be impaired and the life of the fuel effect pieces reduced if assembly directions are not followed, see section 4.4.
GAS CONTROL VALVE
BURNER ASSEMBLY
UNION NUT
INJECTOR
Diagram 6.1
19 221030F
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Servicing
6.7 Safety Device
Refer to Section 1. Refer to diagram 6.2. Check the condition of the electrode and thermocouple,
clean with a soft brush. When cleaning also make sure that all the holes in the
safety device are clear of dust and lint. Make sure that the electrode is in line with the earth post
and that the spark gap is as shown in diagram 6.2.
7 Fault Finding
7.1 Fire Ignition
Remove the fret and ashpit cover, see diagram 4.5 and 4.6.
EARTH POST
ELECTRODE
SAFETY DEVICE
Make sure this hole is clear of dust and lint
SPARK GAP 3 +1 or - 0.5mm
THERMOCOUPLE
Diagram 6.2
5931
Refer to Fire Ignition Sequence of Operation, diagram 7.1.
7.2 Electrical
Important. The preliminary electrical system checks as contained in a Multimeter instruction book are the first checks to be carried out during a fault finding procedure. On completion of the Service fault finding task, which has required the breaking and remaking of electrical connections, and checks, earth continuity, polarity and resistance to earth must be repeated.
Isolate the fire from the electrical supply. Remove the fret and ashpit cover, see diagram 4.5 and 4.6. Refer to the electrical fault finding, diagram 7.2 and
functional flow, diagram 7.3.
7.3 Thermocouple
Remove the fret and ashpit cover, see diagram 4.5 and 4.6. Refer to fault finding, diagram 7.2.
7.4 Safety Device
If the fire shuts down for no apparent reason the flue/ chimney and the air inlets into the room must be checked. Any problems found must be put right, before the fire is used again.
Also, check for dust and lint around the holes in the safety device.
IN ALL cases the room must be ventilated before attempting to relight the fire.
The safety device must not be bypassed or put out of action.
221030F
20
Supplied By www.heating spares.co Tel. 0161 620 6677
7 Fault Finding
Sequence of operation
Select low with
either remote handset
or push button on
control box
Sparking will take place at the electrode, lighting the pilot which
in turn lights the
main burner at low
rate
Switch on mains
electricity
Select medium with
either remote handset
or push button on
control box
Sparking will take place at the electrode, lighting the pilot which
in turn lights the
main burner at low
rate
6012
Select high with
either remote handset
or push button on
control box
Sparking will take place at the electrode, lighting the pilot which
in turn lights the
main burner at low
rate
After a few seconds
the fire will
automatically go to
the medium rate
Once flame is
established the
settings of low,
medium or high can
be selected using
the handset or push
buttons on the
control box
To switch the fire off
press off on the
handset or at the
control box
After a few seconds
the fire will
automatically go to
the high rate
If a flame is not detected during the ignition period the control will go to lock out. Press the OFF button to reset
21 221030F
Diagram 7.1
Supplied By www.heating spares.co Tel. 0161 620 6677
7 Fault Finding
Check all electrical connections on the fire are correctly made. Ensure that the override switch is in the auto position. Ensure that the batteries in the remote handset are in good condition / correct polarity. Ensure there is an electrical supply to the fire. After switching on the electrical supply to the fire, the fire controls may be 'locked out', to reset press the off button
Press the high
button on the control
box. Do sparks appear
at the electrode?
YES
Does the fire
light at the
pilot / low rate?
YES
Does sparking stop once pilot
flame is
established?
YES
After approximately
20 seconds does
fire go from low
to high?
YES
NO
NO
NO
NO NO
Restart fire. Check
milli voltage at mag
unit. is it greater than
Is the electrode cracked
or the ignition lead
detached or faulty
YES
Is there 230v to
T/E solenoid on PCB
CN 2 pins 1 and 4?
Faulty PCB,
replace
Does fire
go out
5mV?
NO
YES
NO
YES
Rectify or
replace
NO
YES
Gas Control valve,
Is there 230V to
high solenoid on
PCB CN2 pin 3+6?
Control valve,
Faulty PCB,
replace
Faulty
replace
Faulty Gas
replace
Faulty PCB,
replace
NO
YES
Is there 20mV at
Faulty PCB,
replace
Faulty Gas
Control valve,
replace
NO
thermocouple
head?
6016
Press medium button
on control box. Does
the fire go from high
to medium?
YES
Press low button on
control box. Does the
fire go from medium
to low?
YES
Press off button on
control box. Does the
fire go off?
YES
Repeat the above steps
using the remote handset.
Does the fire function correctly?
NO
NO
NO
check 230V to
medium solenoid
on PCB CN2 pins
2 and 5
YES
Faulty PCB,
replace
NO
YES
NO
Faulty handset,
replace
Faulty PCB,
Faulty Gas
Control valve,
Clean filter
replace as necessary
replace
replace
Faulty PCB,
replace
Is pilot
filter
blocked
YES
Faulty
thermocouple,
replace
Safety Device
Correct sequence
of operation has
been achieved
YES
NO
Diagram 7.2
221030F
22
Supplied By www.heating spares.co Tel. 0161 620 6677
7 Fault Finding
6013
P.C.B. BOARD
FUSE TYPE F1A
L
L
br
OVERRIDE
y
y
SWITCH
N
N
b
CN2 PIN1
CN2 PIN2
CN2 PIN3
SPARK ELECTRODE
br
br
br
T/E SOLENOID
MEDIUM SOLENOID
HIGH SOLENOID
TERMINAL BLOCK CONNECTIONS
P.C.B. CONNECTIONS
KEY br BROWN b BLUE y YELLOW
23 221030F
Diagram 7.3
Supplied By www.heating spares.co Tel. 0161 620 6677
SPARK
ELECTRODE
7 Fault Finding
6029
THERMO­COUPLE
ww
r r
H.T.
GAS V ALVE
CN2
1 2 3 4 5 6
FUSE
F1A
CN1
LNE
bbr
EARTH GAS V ALVE CONTROL
EARTH CHASSIS
g/y
g/y
P.C.B.
KEY:
b - BLUE bk - BLACK br - BROWN g/y - GREEN/YELLO W w - WHITE y - YELLO W r - RED
221030F
24
bk bk
yy
AUTO/MANUAL SWITCH
Diagram 7.4
Supplied By www.heating spares.co Tel. 0161 620 6677
8 Replacement Parts
NOTES:
Refer to Section 1. Make sure that the fire is cold before replacing any parts. Replacement of parts must be done by a competent
person. Isolate the gas and electrical supplies to the fire. After replacing or disconnecting any gas carrying part,
always test for gas soundness, using a suitable leak detection fluid and carry out functional check of controls.
WARNING. Take care as the burner has a naked flame. To test the gas control assembly apply leak detection fluid
to all joints, light the burner and check all the joints for leakage at all settings.
After removing or disconnecting any pipework always make sure that it is refitted correctly and does not interfere with the fitting of the fire.
Unless stated otherwise reassemble all parts in the reverse order to removal.
8.1 Fret and Ashpit Cover
Remove the fret and ashpit cover, see diagram 4.5 and
4.6.
8.6 Safety Device
Refer to Section 1. Follow the instructions in, Section 3.1, to remove the
burner / control box. Refer to diagram 8.1, disconnect.
- the ignition lead from the electrode.
- the pilot pipe union nut at the safety device.
- the thermocouple nut at the gas control valve.
- the electrical lead, from the thermocouple, at the control box.
- the safety device.
- when refitting thermocouple lead do not make any sharp bends and only tighten the nut a quarter turn beyond finger tight.
8.7 Ignition Lead
Remove the control box, see diagram 4.1. Remove the control box lid, see diagram 3.8. Disconnect the ignition lead at the electrode and PCB,
see diagrams 8.1 and 8.2.
8.2 Fuel Effect Bed Supports and Fuel Effect Pieces
Carefully remove these items, as with use they become fragile, Refer to Section 4.3, see diagram 4.4, steps 8 to 1.
8.3 Frame
To remove refer to diagram 4.2
8.4 Burner
Follow the instructions in, Section 3.1, to remove the burner / control box.
To remove the burner follow the instructions in Section
6.6 to remove the injector, then remove the burner securing screws this will then release the burner.
8.5 Injector
Follow the instruction in Section 6.6 to remove the injector.
8.8 Control Board (PCB)
Remove the control box, see diagram 4.1. Remove the control box lid, see diagram 3.8. Disconnect all the electrical plugs the ignition lead and
the electrical leads to the thermocouple, safety device and electrical connectors to the auto / manual switch. Release and carefully pull the PCB away from its supports, see diagram 8.2.
Refer to the wiring diagram 7.4 for reassembly.
9 Spare Parts
When spare parts are required use only genuine Glow­worm parts and buy them from a recognised supplier.
Use only the fuel effect approved for this fire. Do not use more fuel effect pieces than shown. Please quote the name of the fire Dovedale or
Chatsworth (Remote).
25 221030F
Supplied By www.heating spares.co Tel. 0161 620 6677
8 Replacement Parts
GAS CONTROL VALVE
THERMOCOUPLE NUT
THERMOCOUPLE ELECTRICAL LEAD
SAFETY DEVICE ELECTRICAL LEAD
PILOT PIPE TUBE
5968
UNION NUT
SILICONE COVER
IGNITION LEAD
CAPILLARY
SAFETY DEVICE SECURING SCREW (2)
CONTROL BOX
P.C.B. BOARD
HIGH
MED
LOW
OFF
AUTO
MANUAL
Diagram 8.1
IGNITION LEAD
5966
SUPPORT POST(4)
ELECTRICAL
HIGH
LEADS
MED
LOW
OFF
AUTO
MANUAL
221030F
26
P.C.B.
ELECTRICAL PLUGS
ELECTRICAL CONNECTIONS
Diagram 8.2
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Spare Parts
Key No Part No Description 1 210269 Rear support 2 210268 Middle support 3 210272 Fuel effect pieces (small) 4 210273 Fuel effect pieces (large) 5 210270 Side support L/H 6 210271 Side support R/H 7 210267 Front support 8 202277 P.C.B. 9 230501 Gas control valve assy 10 205739 Injector 11 203443 Combustion products discharge safety device 12 202015 Fuse 13 WX5500 Ignition lead
13
1
10
2
3
12
5915
9
11
5
7
4
27 221030F
8
6
Diagram 9.1
Supplied By www.heating spares.co Tel. 0161 620 6677
Control of Substances Hazardous to Health
Information for the Installer and Service Engineer.
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health. The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
FUELBEDS, ARTIFICIAL FUEL This product uses fuel effect Pieces containing Refractory Ceramic Fibre (RCF), which are man­made vitreous silicate fibres. Excessive exposure to these materials may cause temporary irritation to eyes, skin and respiratory tract, consequently, it makes sense to take care when handling these articles to ensure that the release of dust is kept to a minimum. To ensure that the release of fibres from these RCF articles is kept to a minimum, during installation and servicing we recommend that you use a HEPA filtered vacuum to remove any dust and soot accumulated in and around the fire before and after working on the fire. When replacing these articles we recommend that the replaced items are not broken up, but are sealed within heavy duty polythene bags, clearly labelled as RCF waste. This is not classified as “hazardous waste” and may be disposed of at a tipping site licensed for the disposal of industrial waste. Protective clothing is not required when handling these articles, but we recommend you follow the normal hygiene rules of not smoking, eating or drinking in the work area and always wash your hands before eating or drinking.
INSULATION PADS/CERAMIC FIBRE, GLASSYARN, MINERAL WOOL These can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is broken. Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or going to the lavatory. If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
Because of our constant endeavour for improvement details may vary slightly from those in the instructions.
221030F
28
Loading...