Glow-worm COMPACT 80p Instructions For Use, Installation & Servicing

Page 1
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Installation and Servicing
To be left with the user
COMPACT 80p
G.C. No. 47 047 04A
Fanned Flue Combination Boiler
221679H.11.00
6936
With Honeywell gas control
This is a Cat I2H Appliance
The instructions consist of three parts, User, Installation and Servicing Instructions, which include the Guarantee Registration Card.
The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use)
Regulations, be handed to the user on completion of the installation.
Guarantee Registration
Thank you for installing a new Glow-worm appliance in your home.
Glow-worm appliances' are manufactured to the very highest standard so we are pleased
In the centre pages are to be found your Guarantee Registration Card, which we recommend you complete and
If this card is missing you can obtain a copy or record your registration by telephoning the Heatcall Customer
Our Guarantee gives you peace of mind plus valuable protection against breakdown by covering the cost of:
to offer our customers' a Comprehensive First Year Guarantee.
return as soon as possible.
Service number 01773 828100.
One Contact Local Service
All replacement parts All labour charges All call-out charges
Tel: (01773) 828100
Fax: (01773) 828070
REGISTER YOUR GLOW-WORM APPLIANCE
FOR 1ST YEAR GUARANTEE PROTECTION
CALL 0208 247 9857
Hepworth Heating Ltd.,
Nottingham Road, Belper, Derbyshire. DE56 1JT
General/Sales enquiries:
Tel: (01773) 824141 Fax: (01773) 820569
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
Important Information
Testing and Certification
This boiler is tested and certificated for safety and performance. It is therefore important that no alteration is made to the boiler, without permission, in writing, from Hepworth Heating Ltd.
Any alteration not approved by Hepworth Heating Ltd., could invalidate the certification, boiler warranty and may also infringe the current issue of the Statutory Requirements, see Section 1.4.
CE Mark
This boiler meets the requirements of Statutory Instrument No. 3083 The boiler (Efficiency) Regulations, and therefore is deemed to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with liquid or gaseous fuels.
Type test for purposes of Regulation 5 certified by: Notified body 0086.
Product/production certified by: Notified body 0086.
The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to the electrical equipment designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
Substances Hazardous to Health
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
INSULATION PADS/CERAMIC FIBRE, GLASSYARN, MINERAL WOOL These can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is broken. Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or going to the lavatory.
If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
CONTENTS DESCRIPTION SECTION PAGE No.
INSTRUCTIONS
FOR USE
Introduction 3 Clock Settings 4 Lighting the Boiler 5
General Data 1 7
INSTALLATION
INSTRUCTIONS
Boiler Location 2 9 Flue and Ventilation 3 10 Heating System 4 11 Domestic Hot Water System 5 12 Installation Preparation and Gas/Water Connections 6 13 Flue Preparation 7 14 Mounting the Boiler and Flue Fitting 8 16 Electrical Connections 9 18 Commissioning 10 20
SERVICING
INSTRUCTIONS
Servicing 12 23 Fault Finding 13 24 Replacement Parts 14 32 Spare Parts 15 43
General Data 11 23
221679H
2
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Introduction
Please read these instructions and follow them carefully for the safe and economical use of your Combination boiler.
This boiler must have been installed by a competent person in accordance with the current rules in force in the countries of destination at the time of installation.
Once the controls are set, the boiler is automatic in operation.
The Compact combination boiler is able to provide room heating as part of a central heating system and domestic hot water direct from the cold water supply, without the need for secondary storage.
The boiler can be fitted with one of two makes of clock, which look like this:-
Clock / Timers
0
P
AUTO
I
MT
P
DAY HR MIN
Digital timer
RUN
WThFSSu
R
12
11
13
14
15
16
17
18
19
20
21
10
9
8
7
6
5
4
3
22
2
1
23
24
Electro / mechanical clock / timer
I
IMPORTANT NOTICE:
This boiler is for use only on G20 gas.
Alternatively a fused 3A 3 pin plug and shuttered unswitched socket may be used.
The colours of three core flexible cable are, blue - neutral, brown
- live, green and yellow - earth.
As the markings on your plug may not correspond with these colours continue as follows:-
The wire coloured blue must be connected to the terminal marked “N” or “Black”.
The wire coloured brown must be connected to the terminal marked “L” or “Red”.
The wire coloured green and yellow must be connected to the terminal marked “E” or “Green” or the earth symbol
PVC flexible cable having a conductor size of 0.75mm
0.20mm) must be used within the boiler casing to connect to the boiler.
6937
Electrical Supply Failure
The boiler will not work without an electrical supply.
Normal operation of the boiler should resume when the electrical supply is restored.
If the power is off, except for short controlled periods, turn off the pilot.
Note. The boiler safety cut-off may have operated, please refer to the following section to reset.
Reset any external controls, to resume normal operation of the central heating.
The digital timer, has a lithium battery back up and will not need resetting. Unless it is without power for a considerable period.
.
2
(24/
Gas Leak or Fault
If a gas leak or fault exists or is suspected, turn the boiler off and consult your local gas company or your local installation/ servicing company.
Domestic Hot Water Temperature
NOTE. The mains incoming water temperature in the winter is lower than in the summer.
The water temperature is factory preset and can not be adjusted.
To achieve the same outlet water temperature in the winter, it will be necessary to reduce the water flow rate using the hot water tap.
Boilers Installed in Compartments
If the boiler has been fitted into a compartment or cupboard, do not obstruct the compartment air supply vents.
Do not use the compartment for storage.
Electrical Supply
WARNING. The boiler must be earthed.
The boiler must be connected to a 230V~50Hz permanent supply.
Connection of the whole electrical system of the boiler and any heating system controls to the electrical supply, must be through one common isolator.
Isolation should preferably be by a double pole switched fused spur box. The fused spur box should be readily accessible and preferably adjacent to the appliance. It should be identified as to its use.
Boiler Safety Cut-off Device
The boiler is fitted with a safety cut-off device to prevent damage through overheating.
Should the main burner and pilot go out, for no apparent reason, during normal use, allow the boiler and system to cool down (waiting at least a minimum of four minutes), relight the boiler as described in "To light the boiler".
If the problem persists, turn the boiler off and consult your installation/ servicing company.
The Gas Safety (Installation & Use) Regulations
In your interests and that of safety it is the law that ALL gas appliances are installed by competant persons in accordance with the current issue of the above regulations.
3
221679H
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Setting Instructions for Electro/mechanical Clock - if fitted
This clock has a twenty four hour dial, that is, 1pm is 13.
To set the time, turn the whole face clockwise until the pointer is against the time of day.
To set any “Off” time, push the tappets outwards.
To set any “On” time, push the tappets inwards.
Time can be set either “On” or “Off” in fifteen minute segments.
Note. The clock supplied could be fitted with an override device, see diagram 1, which switches the clock programme “On” or Off permanently.
The switch will need to be repositioned to resume programmed working.
OVERRIDE
CLOCK FACE
SWITCH
0
12
11
13
14
15
16
17
18
19
20
21
22
CONSTANT OFF
0
23
24
10
9
8
4
3
2
1
I
7
6
5
POINTER
TAPPETS
PROGRAMMED CONSTANT ON
I
Diagram 1
Setting Instructions for the 7 Day Digital Clock/Timer
This is a 24 hour clock/timer, that is 1pm is 13:00, and has 8 ON and 8 OFF daily switching actions.
It is fitted with a lithium battery back up which protects the programme in the event of an electrical failure. The battery should have a life of several years.
6939
P
AUTO
I
MT
WTh
RUN
FS
Su
Setting the Clock - Diagram 2
1. With both AUTO and RUN switches set to the central position, press R reset button, the display will flash.
2. Set RUN switch to .
3. Set day of week by pressing button DAY.
4. Set time of day by pressing buttons HR and MIN.
5. Set RUN switch to the central position, colon will flash, this indicates the clock is set.
With the clock set, the factory preset programme shown below will operate.
6938
MON/FRI
ON - 06:30 OFF - 08:30 ON - 16:30 OFF - 22:30
SAT/SUN
ON - 07:00 OFF - 09:00 ON - 16:00 OFF - 23:00
Setting Timed Programmes
With the clock set to the correct time, see SETTING THE CLOCK paragraphs 1-4, and then continue as follows:
1. Set RUN switch to P , the display will indicate the 1st (ON) preset programme and the symbol .
2. Set day of week to be programmed by pressing the DAY button.
Note: The days can be selected individually or as groups:
Mon-Fri., Mon-Sat., Mon-Sun., Sat/Sun.
An arrow will be displayed under the day or days selected.
3. Set time of day by pressing the buttons HR and MIN.
4. Press button P to confirm programmes, the display will indicate the 2nd (OFF) preset programme and subsequently, 3rd, 4th, 5th, 6th, 7th, 8th.
5. Repeat procedures 2, 3 and 4 until desired programmes are set.
Note. It is not a requirement to use the 8 on/off programmes.
6. Set the RUN switch the central position, your appliance will now operate at the programmed times.
General Notes.
With the AUTO switch in the I position the central heating will operated constantly ON.
With the AUTO switch in the O position the central heating will not operate.
Soft Override button indicated by the symbol central heating programme for the next available.
ON time programmes are indicated by the symbol
, this function will override the current
.
P
DAY HR MIN
R
Diagram 2
221679H
4
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
To Light the Boiler
1. Check that all four isolating valves are open, the levers in line with the valve bodies, see diagram 3.
2. Open the controls cover door an familiarize yourself with the controls, see diagram 4.
3. CAUTION. A sealed pressurised system must be filled and pressurised by a competent person.
Only operate the boiler when you are sure that the system has been filled and pressurised. Check this by looking at the pressure gauge A, it should read 0.7bar minimum.
4. Open a hot water tap, check that water flows, then close it.
5. If you are in any doubt about the boiler being filled with water contact your installation/servicing company or the local gas company.
6. Fully press and hold down the control knob “C”. Press and release the piezo button “D” until the pilot burner lights, view through window in the front case. When the pilot burner is lit, keep control knob “C” pushed in for a further 15 seconds then release. The pilot should remain alight.
7. IF THE PILOT GOES OUT NOW, OR ON ANY OTHER OCCASION, A SAFETY DEVICE PREVENTS IMMEDIATE RELIGHTING. WAIT AT LEAST FOUR MINUTES BEFORE ATTEMPTING TO RELIGHT.
8. If the pilot burner fails to remain alight, repeat instruction 11. but now hold down the control knob “C” for a little longer after the pilot has lit.
9. Check the pilot is alight and stable.
10. Switch ON the electrical supply to the boiler at the external isolator.
11. Set the switch “K” to ON 1 situated on the control fascia.
12. Check the light “E” is illuminated on the control fascia.
13. Set the summer / winter button “J”, light “H” or “F” will illuminate.
SAFETY VALVE DISCHARGE PIPE POSITION
HEATING RETURN
HEATING FLOW
HOT WATER OUT
GAS SERVICE COCK
COLD WATER SUPPLY IN
14. Set “B”, clock/timer (if fitted) and any remote controls as
required.
For central heating operation set button “J” to “On”. The main burner will ignite. Light “F” will illuminate.
Close the controls cover door.
To Turn the Boiler Off
For short periods only set switch K to 0. Turn off pilot light.
To turn the boiler off, turn the control knob “C” in the direction of the arrow clockwise.
To turn on again following the "To light the boiler" instructions.
Water Temperatures
NOTE. The mains incoming water temperature in the winter is lower than in the summer.
To achieve the same outlet water temperature in the winter, it will be necessary to reduce the water flow rate using the hot water tap.
Summer / Winter Selector Button
For central heating set button “J” to Winter light “F” will illuminate as shown in diagram 4. The main burner will light.
When the heating is controlled by a room thermostat and/or a time switch, button “J” must be set to Winter light “F” will illuminate.
If a hot water tap is opened while the boiler is on for heating, priority will be given to hot water.
Maintenance and Servicing
To ensure the continued efficient and safe operation of the appliance it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in general once a year should be enough.
If this appliance is installed in a rented property there is a duty of care imposed on the owner of the property by the current
7310
issue of the Gas Safety (Installation and Use) Regulations, Section 35.
Servicing/maintenance should be carried out by a competent person in accordance with the rules in force in the countries of destination.
To obtain service, please call your installer or Heatcall (Glow­worms own service organisation) using the telephone number behind the controls cover door.
Please be advised that the ‘Benchmark’ logbook should be completed by the installation engineer on completion of commissioning and servicing.
All CORGI Registered Installers carry a CORGI ID card, and have a registration number. Both should be recorded in your boiler Logbook. You can check your installer is CORGI registered by calling CORGI direct on :- 01256 372300.
Clearances
The boiler requires a clearance in front, below and at the sides of the casing for safety, servicing and maintenance access, see diagram 2.1.
Protection Against Freezing
If the boiler is to be out of use for any long periods during severe
LEVER (OPEN) HEATING FLOW/ RETURN
LEVER (OPEN) COLD WATER SUPPLY IN/OUT
SLOT (OPEN) GAS SERVICE COCK
Diagram 3
weather, it is recommended that the whole system, including the combination boiler, should be drained to avoid the risk of freezing.
If in doubt, contact you installation/servicing company for advice.
5
221679H
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
7004
PRESSURE
GAUGE A
CONTROLS FASCIA
CONTROL
‘C’
KNOB
PIEZO D
CONTROLS COVER
G
E
H
SUMMER/ WINTER BUTTON
‘J’
F
CLOCK TIMER IF FITTED
MAINS ELECTRIC
SWITCH
B
‘K’
7565
KEY TO NEON LIGHTS
G LOW WATER PRESSURE ‘H SUMMER SETTING (HOT WATER OPERATION ONLY)F WINTER SETTING (HOT WATER AND CENTRAL HEATING OPERATION)E POWER ‘ON’
Draining and Filling
CAUTION. This boiler works in a pressurised system which must only be drained, refilled and pressurised by a competent person.
Note: If the pressure gauge indicates a loss of system pressure, that is, less than 0.7bar, YOU MUST CONTACT YOUR INSTALLER.
Pressure Relief Safety Valve
CAUTION. A pressure relief safety valve and discharge pipe is fitted to the boiler. This valve must not be touched. Should there be any discharge from the pipe, turn the boiler off, isolate from the electrical supply and contact your installation/servicing company. The outlet should be kept clear
Cleaning
WARNING. This appliance contains metal parts (components) and care should be taken when handling and cleaning with particular regard to edges.
The boiler casing can be cleaned using a mild liquid detergent with a damp cloth, then a dry cloth to polish.
Do not use any form of abrasive or solvent cleaner as you may damage the paint work
Boiler Casing
CAUTION. Do not remove or adjust the casing in any way, as incorrect fitting may result in incorrect operation or failure to operate at all. If in doubt seek advice from the local gas company or your installation/servicing company.
Replacement Parts
If replacement parts are required apply to your local supplier or British Gas.
Please quote the name of the appliance.
Diagram 4
221679H
6
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
E
C
1 General Data
7029
A
G
D
F
M
C
L
C
L
FLUE
N
B
9mm
H
K
K
JL
ABCDEFGHJ KLMN
450 700 300 100 75 128 225 18 135 65 110 80 144
22mm COMPRESSION CENTRAL HEATING
15mm COMPRESSION DOMESTIC WATER
Rc 1/2 (1/2in. BSPT) GAS CONNECTION
Diagram 1.1
TABLE 1
Lift Weight 33.4kg (73.63b) Total Weight 42.8kg (94.36lb)
Gas connection Ø 15mm compression Heating and return Ø 22mm compression Domestic hot water Ø 15mm compression Safety valve Preset 3bar (43.5lbf/in Safety valve discharge Ø 15mm copper Water content 1.66 litres (0.37 gallon)
Expansion vessel capacity 6 litres (1.32 gallons)
Heating cold fill 0.7bar pressure minimum (10.1lbf/in
D.H.W 0.8 to 10bar
working pressure
Maximum Heating 60 litres
system water (13.2 gallons) content using with a cold fitted expansion fill pressure vessel. of 0.7bar
Electrical supply 230V~50Hz Electrical rating 154W fused 3A Internal Fuse rating F1) Type T2A
F2) Type T315mA
Boiler starts at an inlet pressure of 0.5bar but
requires 0.8bar for maximum output.
For larger systems use an additional expansion vessel, see Section 4.
2
)
1.1 Installation
Materials and equipment should be fit for their purpose and of suitable quality and workmanship.
1.2 Important Notice
This boiler is for use only on natural gas, G20.
1.3 Sheet Metal Parts
2
)
WARNING. When installing or servicing this boiler care should be taken when handling the edges of sheet metal parts to avoid any possibility of personal injury.
1.4 Requirements
The installation of this boiler must be carried out by a competent person in accordance with the current rules in force in the countries of destination at the time of installation.
Manufacturers instructions, supplied.
Manufacturers instructions must not be taken as overriding statutory requirements.
1.5 Data Label
The data label is on the inner case cover, see diagram 1.2.
1.6 Data
See table 1 and diagrams 1.1, 1.2 & 1.3.
The Seasonal Efficiency Domestic Boilers UK (SEDBUK) is
72.2%.
The value is used in the UK Governments Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from which it has been calculated have been certified by B.S.I.
7
221679H
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General Data
1.7 Gas Supply
The gas installation shall be in accordance with the rules in force in the countries of destination.
The supply from the governed meter must be of adequate size to provide a steady inlet working pressure of 20mbar (8in wg) at the boiler.
1.8 Electrical Supply
WARNING. This boiler must be earthed.
All system components shall be of an approved type.
The electrical installation shall be in accordance with the current rules in force in the countries of destination at the time of installation.
Connection of the whole electrical system of the boiler and any heating system controls to the electrical supply, must be through one common isolator.
Isolation should be by a double pole switched fused spur box, having a minimum contact separation of 3mm in each pole. The fused spur box should be readily accessible and preferably adjacent to the appliance.It should be identified as to its use.
Alternatively, a fused 3A 3pin plug and unswitched socket may be used, provided they are not used in a room containing a bath or shower.
The mains supply cable and other cables connected to the boiler must be the PVC flexible type of at least 0.75mm
0.20mm) .
2
(24/
1.9 Heating System Controls
The heating system should have installed: a timer and room thermostat controlling the boiler.
Thermostatic radiator valves may be installed, however they must not be fitted in a room where the room thermostat is located.
Note: All systems must have at least one radiator not fitted with a thermostatic valve.
Note: For further information, see The Building Regulations 1991 - Conservation of fuel and power, 1995 edition - Appendix G, table 4b.
HEPWORTH HEATING LTD., BELPER,DERBYS. DE56 1JT
3212
7.6
17.6
457501
GB IE
MIN
1.2
10.720.09
COMPACT 80P
~
230V 50Hz 150W Fused a t 3A For use on : -G20 - 20 mbar This boiler is intended exclusively to be installe d on a gas supply with a gov erned meter
SPECIFIC WATER RATE 11.22 l/min. DOMESTIC CIRCUIT PMW = 10 bar HEATING CIRCUIT PMS = 2.5 bar
G20 HOT BURNER PRESSURE HEAT HEAT
SERIAL
I
INPUT NETT OUTPUT
No.
2H
Q =
=
P
TYPE : C - C NO Class 5
x
DHW MAX.
mbar
13.0
kW
25.5
kW
23.45 8.79
INJECTOR: 4.2mm 205766
GC No. 47-047-04A
0086
86/AU/582
CH MAX.
7507
EXPANSION
VESSEL
FLOW SENSOR
OVERHEAT CUT-OFF
LOW WATER PRESSURE SWITCH
TEMP. SENSOR
D.H.W. COLD INLET
FANNED FLUE
GAS VALVE
BYPASS VALVE
C.H.
FLOW
HEAT EXCHANGER
MAIN BURNER
PUMP
SAFETY VALVE
GAS
C.H.
RETURN
AUTOMATIC AIR VENT
SAFETY
VALVE
DISCHARGE
Diagram 1.2
7643
PILOT BURNER
OVERHEAT CUT-OFF
TEMP. SENSOR
D.H.W. HOT OUTLET
Diagram 1.3
221679H
8
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Boiler Location
2.1 Location
This boiler must be installed in accordance with the rules in force in the countries of destination.
This boiler is not suitable for outdoor installation.
Any electrical switch must be positioned so that it cannot be touched by a person using the bath or shower.
The boiler must be mounted on a flat wall which is sufficiently robust to take its weight, refer to Table 1, “Data”.
If the location of the boiler or any part of the system is subject to severe cold weather conditions, it is recommended that a frost thermostat is fitted. Any part of the system that may be vulnerable to freezing must be protected.
2.2 Boilers in a Compartment
Where the installation of the boiler will be in an unusual position, the current issue of BS6798 gives detailed guidance on these requirements.
An existing cupboard or compartment modified for the purpose may be used, providing minimum clearances are maintained. Details of essential requirements for cupboard or compartment design are given in the current issue of BS6798.
The doorway opening should be of sufficient size to allow for easy removal of the boiler.
Where the boiler is fitted in a cupboard or compartment, permanent ventillation is not required.
Any existing compartment air vents must not be removed or blocked off.
2.3 Clearances
The boiler should be positioned so that at least the minimum operational and servicing clearances are provided, see diagram
2.1. Additional clearances may be required around the boiler for installation.
25 ABOVE THE TOP OF THE FLUE ELBOW
5
450
150
To achieve minimum "Installation" clearance of 5mm. The side panels will have to be fitted prior to boiler mounting.
DIMENSIONS IN MILLIMETRES
6944
5
Diagram 2.1
2.4 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it should be fitted in accorandce with the Institute of Gas Engineers document IGE/UP/7/1998. If in doubt seek advice from the local gas undertaking or Hepworth Heating Ltd.
9
221679H
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Flue and Ventilation
3.1 General
The flue must be installed in accordance with the rules in force in the countries of destination.
3.2 Terminal Position
The minimum acceptable siting dimensions for the terminal from obstructions, other terminals and ventilation openings are shown in diagram 3.1.
The terminal must be exposed to the external air, the position allowing free passage of air across it at all times.
Car port or similar extensions of a roof only, or roof and one wall, require special consideration with respect to any openings, doors, vents or windows under the roof. Care is required to protect the roof if made of plastic sheeting. If the car port comprises of a roof and two or more walls seek advice from the local gas undertaking before installing the boiler.
If the terminal is fitted within 600mm below plastic guttering, an aluminium shield 1500mm long should be fitted immediately beneath the guttering or eaves. If the terminal is fitted within 450mm below painted eaves or a painted gutter, an aluminium shield 750mm long should be fitted immediately beneath the guttering or eaves.
3.3 Flue Options
There are various flue systems to choose from, as follows:
Standard Top Outlet Flue Pack - Pt.No. 230483
Extended Top Outlet Flue Pack - Pt. No. 230487
1 Metre Extension Kit - Pt. No. 230484
Optional Wall Liner Kit No. 900862
A Flue Bend Kit or Vertical Flue Kit can be supplied, see Hepworth Heating "Flue Options Guide" for configurations available.
o
45
Flue Bend Pack - Pt. No. 230485
o
Flue Bend Pack - Pt. No. 230486
90
In Line Flue Adapter Kit - Pt. No. 230488
Vertical Flue Kit No. 458115
3.4 Internal Access Flue
All flue assemblies are designed for internal installation, given that there is sufficient clearances opposite to the flue for the installation of the flue.
If there is insufficient clearance the flue can be installed from outside.
For a wall thickness up to 300mm, provided that there is sufficient space and the optional wall liner kit is used, the flue can be installed from the inside.
For a wall thickness of over 300mm the external flue hole will need to be made good from the outside, this also applies if you use the flue kit without the optional wall liner kit, irrespective of wall thickness.
3.6 Room Ventilation
Ventilation must be provided in accordance with the rules in force in the countries of destination. The boiler is room sealed, so where the boiler is fitted in a room or space, a permanent air vent is not required.
3.6 Cupboard/Compartment Ventilation
If the boiler is to be fitted in a cupboard or compartment. Refer to Section 2.2.
K
L
D
F
C
K
L
K
G
MINIMUM SPACING
mm
A
B,C
K
F
F
G
J
A
F
G
UNDER CAR PORT etc.
B,C
G
A
E
G
H,I
MINIMUM SITING DIMENSIONS FOR FANNED FLUE TERMINALS POSITION
A DIRECTLY BELOW AN OPENABLE
WINDOW, AIR VENT, OR ANY
OTHER VENTILATION OPENING 300 B BELOW GUTTER, DRAIN/SOIL PIPE 25 C BELOW EAVES 25 D BELOW A BALCONY 25
OR CAR PORT 200 E FROM VERTICAL DRAIN PIPES AND
SOIL PIPES 25 F FROM INTERNAL OR EXTERNAL
CORNERS 25 G ABOVE ADJACENT GROUND OR
BALCONY LEVEL 300 H FROM SURFACE FACING THE
TERMINAL 600 I FACING TERMINALS 1200 J FROM OPENING (DOOR/WINDOW)
IN CAR PORT INTO DWELLING 1200 K VERTICAL FROM A TERMINAL 1500 L HORIZONTALLY FROM A TERMINAL 300
2816
3.5 Terminal Guard
A terminal guard is required if persons could come into contact with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide a minimum of 50mm clearance from any part of the terminal and be central over the terminal.
The guard should be similar to that shown in diagram 3.1 .
221679H
10
TERMINAL GUARD TYPE K3 SUPPLIED BY :
Tower Flue Components Ltd. Morley Road Tonbridge Kent TN9 1RA
Diagram 3.1
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Heating System
5.00
O)
2
4.00
3.00
2.00
1.00
Remaining conveying capacity (m H
0.00 0 5 10 15 20 25
Circuit flow rate (l/min)
Dt at 60000 btu output Dp (MH2O)
50
7487
40
30
Dt (°C)
20
10
0
Diagram 4.1
4.1 General Notes
The boiler is intended for use in a sealed system only.
4.2 Safety Valve
The safety valve is an integral part of the boiler.
It cannot be adjusted but has a manual test device.
4.3 Pressure Gauge
A pressure gauge is incorporated into the boiler to indicate the system pressure.
The gauge has a cold fill set pointer.
4.4 Pump
The circulation pump is integral with the boiler.
The remaining circulating pressure head available from the boiler is shown in diagram 4.1.
4.5 Expansion Vessel
The boiler has an integral expansion vessel with a capacity of 6Litres, (1.32gall). If the system water content exceeds the maximum quoted in Table 1, Data, an additional vessel should be connected into the system as close as possible to the central heating return connection of the boiler, see diagram 4.2.
The pressure shall not be less than the static head at the point of connection, that is, the height of the top point of the system above the expansion vessel.
4.6 Flow Rate
If required a valve can be incorporated in the main flow or return of the system, valve “A” shown in the flow diagram 4.2. This valve must be lockable and positioned so that inadvertent closure or unauthorised interference is not possible.
4.7 Bypass
The bypass is an integral part of the boiler and cannot be adjusted.
No external system bypass is required.
4.8 Filling Sealed Systems
Provision for filling the system at a low level must be made. Three methods of filling are shown in diagram 4.3.
There must be no permanent connection to the mains water supply, even through a non-return valve.
NOTE: It is important that fittings used for connection to potable water comply with the water undertakers requirements.
4.9 Corrosion Inhibitor
If an inhibitor is to be used in the system, contact the inhibitor manufacturer so that they can recommend their most suitable product.
When fitting the boiler into an existing system, special care should be taken to drain the entire system, including radiators, then thoroughly cleaning out before fitting the boiler whether or not adding an inhibitor.
4.10 Draining
A draining tap must be provided at the lowest points of the system, which will allow the entire system to be drained. An additional draining tap MUST be fitted close to the boiler.
The flow and return isolation valves are provided with drain points for boiler heat exchanger drainage.
11
221679H
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Heating System
ADDITIONAL EXPANSION VESSEL (if required)
HEATING CIRCUIT
RETURN
BOILER
A
FLOW CONTROL VALVE
DOMESTIC
WATER
FILLING POINT
DRAIN POINT
HOT
COLD SUPPLY
Diagram 4.2
7650
METHOD 1
TEMPORARY HOSE
SUPPLY PIPE
METHOD 2
TEMPORARY HOSE
SUPPLY PIPE
METHOD 3
CISTERN
HOSE UNIONS
SUPPLY STOP VALVE
DOUBLE CHECK VALVE ASSEMBLY
HOSE UNIONS
SUPPLY STOP VALVE
OVERFLOW
SERVICING VALVE
COMBINED CHECK VALVE AND VACUUM BREAKER
SERVICING VALVE
SERVICING VALVE
PRESSURE REDUCING VALVE
HEATING SYSTEM
3132
HEATING SYSTEM
HEATING SYSTEM
5 Domestic Hot Water System
5.1 General
The domestic hot water service must be in accordance with the rules in force in the countries of destination.
5.2 Water Pressure
For the minimum and maximum working pressures of the domestic hot water circuit of the boiler refer to Diagram 1.2.
If the cold water supply pressure exceeds the maximum, a governor must be fitted in the supply to the boiler to reduce the pressure to within the limits given.
SUPPLY STOP VALVE
SUPPLY PIPE
HOSE UNIONS
DOUBLE CHECK VALVE ASSEMBLY
Diagram 4.3
5.3 Hard Water Areas
In areas where the water is “hard”, more than 200mg/litre, it is recommended that a proprietary scale reducer is fitted in the cold water supply to the boiler. Consult the local water company for additional advice.
A double check valve assembly must be fitted upstream of the scale reducer. For the relative position of the scale reducer and pressure reducing valve, if required, refer to the manufacturer’s instructions.
221679H
12
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Installation Preparation and Gas / Water Connections
The installation requires the following components :-
1. Plumbing jig Carton
2. Boiler Carton
3. Flue Pack
6.1. Plumbing Jig
Remove from the carton the wall template, then follow the instructions given on the template.
Note: It is important that the wall hanging bracket and the service cock bracket are fitted to a flat and true wall area for correct alignment with the boiler. Where this cannot be achieved it is acceptable to pack out the service cock bracket to obtain the correct alignment with the wall hanging bracket.
6.2 Gas Connection
Provision is made for the gas supply to be connected from below the boiler, see diagrams 1.1 and 6.1 for position.
Refer also to Gas Supply, Section 1.7.
Make the gas supply connection to the gas service cock. While making the connection, do not subject the gas service cock to heat as you may damage the seals. Purge the gas supply.
6.3 Water Connections
Provision is made for the domestic cold water inlet to be connected from below or through an internal wall at the rear of the boiler, see diagram 1.1 and 6.1 for position.
Refer also to Section 5 Domestic Hot Water System”.
Provision is made for the water connections to be connected from below or from above, passing down either side of the boiler. Take care that any pipework connected from above will clear the expansion vessel. Refer to the wall template. If connecting from above a piping kit 457160 is available and is recommended. If necessary, temporarily fit the boiler.
Flush out the domestic water and heating system before connecting the boiler.
Make the connections to the domestic hot water outlet and the heating system by means of the isolating valves, see diagram
6.1.
While making the connections. Do not subject any of the isolating valves to heat as you may damage the seals.
Make sure that the drain screw heads on the isolating valves are accessible.
6.4 Safety Valve Discharge
WARNING. It must not discharge above an entrance or window or any type of public access area.
A short discharge pipe is supplied loose with the boiler, which when fitted to the safety valve, will end below the boiler the position is next to the heating return, see diagram 6.2. (THE DISCHARGE PIPE MUST BE FITTED BEFORE THE BOILER IS MOUNTED ON THE WALL).
This must be extended, using not less than 15mm od metal pipe, to discharge, in a visible position, outside the building, facing downwards, preferably over a drain. The pipe must have a continuous fall and be routed to a position so that any discharge of water, possibly boiling, or steam cannot create any danger to persons, damage to property or external electrical components and wiring.
Note. To ease future servicing it is advisable to use a compression type fitting to extend the discharge pipe.
HOT HEATING FLOW
SLOT (OPEN) HEATING FLOW/ RETURN
WATER
OUT
REAR VIEW OF BOILER
DISCHARGE PIPE
UNION CONNECTION
SAFETY DISCHARGE PIPE ROUTING POSITION
GAS SERVICE COCK
SLOT (OPEN) COLD WATER SUPPLY IN/OUT
COLD WATER SUPPLY IN
SAFETY VALVE DISCHARGE
6956
HEATING RETURN
SLOT (OPEN) GAS SERVICE COCK
Diagram 6.1
7028
SEALING WASHER
Diagram 6.2
13
221679H
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
7 Flue Preparation
TOP OUTLET FLUE PACK
FLUE LENGTH
MAX 840mm (extd.)
MAX 570mm (std)
C
L
15mm
117mm
SCREW
X
SIDE FLUE
& TAPE
X plus 132mm = FLUE LENGTH
STD./EXTD. TOP OUTLET FLUE PACK & 1 METRE EXTENSION KIT
3 x 1 metre extension kits may be joined together.
C
L
VIEW B
36mm
REAR FLUE
15mm
7508
FLUE LENGTH
MAX 840mm (extd.)
MAX 570mm (std)
15mm
SCREW & TAPE
Y
Y plus 50mm = FLUE LENGTH
SCREW & TAPE
SCREW & TAPE
X
Y
SCREW & TAPE
VIEW B
SIDE FLUE X plus 132mm = FLUE LENGTH REAR FLUE Y plus 50mm = FLUE LENGTH
FLUE
PACKS
TOP STD.
REAR SIDE
TOP EXTD.
REAR SIDE
MINIMUM
WALL
THICKNESS
75 75
75 75
MINIMUM
FLUE
LENGTH
126 212
126 212
MAXIMUM
FLUE
LENGTH
570 570
840 840
MAXIMUM DISTANCE FROM
BOILER MOUNTING FACE
TO EXTERNAL WALL FACE
"Y"
519
-
789
-
7.1 Flue Position and Length
Determine flue application, length and terminal position before starting, refer to diagram 7.1.
Note: The Standard Top Outlet Flue Pack and the Extended Top Outlet Flue Pack contains a flue duct extension piece complete with "O" rings, this should be discarded.
If you are using a Flue Bend or a Vertical Flue Kit, please follow the instructions supplied with the kit.
To make a neat finish to the flue outlet a flue collar kit, part No. 443286, with instructions, is available, see diagram 7.2.
Note: If required an optional wall liner kit, part no. 900862, is available complete with instructions.
"X"
BOILER CASING TO
EXTERNAL WALL FACE
-
438
-
708
7.2 Flue Assembly
Extend the telescopic flue to the required length, making sure that the minimum overlap is no less than 25mm, and that the flue terminal projects 15mm minmum beyond wall face, see diagram
7.1.
Carefully drill though air duct pilot hole and secure with self tapping screw provided in fittings pack, see diagram 7.1.
Seal the joint with the tape provided.
If the flue system requires the addition of flue extension kits, drill, seal and secure them with the self tapping screw and tape provided.
NOTE :
IF IT IS NECESSARY TO CUT THE DUCTS TO ACHIEVE THE "FLUE LENGTH" MAKE SURE THAT THE OVERLAPS ARE AS FOLLOWS :­THE OVERLAP FOR AIR DUCT = 25mm THE OVERLAP FOR FLUE DUCT = 50mm
THE MAXIMUM LENGTHS CAN BE INCREASED BY AN ADDITIONAL 3 METRES WITH THE USE OF THE 1 METRE EXTENSION KITS. NOTE :THIS APPLIES TO STANDARD KITS ONLY.
7506
Diagram 7.1
221679H
14
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
7 Flue Preparation
Note: Should any one of the flue sections require cutting to obtain desired flue system length, cut at the end opposite the expanded end.
If the boiler is not to be fitted for some time cover the hole in the wall.
7148
7.3 Internal Access Flue
If access to the outside wall is not practical, the flue system can be installed from inside. Use of the optional wall liner kit is required.
7.4 Top Outlet Rear Flue Fixing
Fit the self adhesive foam seal provided in the flue pack around the air duct at the position shown in diagram 7.1.
Make good around the flue outside after installation of the boiler.
Important: If the wall liner kit is used, the self adhesive foam seal included in the wall liner kit must be used in place of the one supplied with the flue pack, see diagram 7.3 for position of self adhesive seal.
7.5 Top Outlet Side Flue Fixing
Make good the area around the flue inside and outside after installation of the boiler.
Important: If the wall liner kit is used, the self adhesive foam seal included in the wall liner kit must be used in place of the one supplied with the flue pack, see diagram 7.3 for position of self adhesive seal.
7.6 Flue Positioning
Push the flue assembly into and through the hole such that it is within the wall, and does not stick out into the room. Do not push the flue assembly too far into the hole as it has to be pulled back into the boiler and secured.
WITH WALL LINER KIT ONLY
WALL THICKNESS­UP TO 300mm
FOAM SEAL
Q
15mm
Q-35mm
OPTIONAL FLUE COLLAR
Diagram 7.2
7331
FOAM SEAL
WALL THICKNESS­OVER 300mm
Q
Diagram 7.3
15
221679H
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677
8 Mounting the boiler and Flue Fitting
8.1 Boiler Mounting
Remove the inner case front, see diagram 8.1.
To assist with the location of the flue elbow into the fan outlet remove the fan by removing the securing screws, the electrical connections by pulling the boots not the wires and air pressure switch tubes, see diagram 8.2.
Remove the protective caps from the boiler water pipes
Fit the sealing washers (supplied in the fittings pack) to the boiler water pipes by inseting them into the tubing nuts. (the nipples on the washers will hold them in position), see diagram
8.4.
Lift the boiler into position on the top mounting brackets, see diagram 8.3.
8.2 Water and Gas Connections
Locate the boiler water pipes and gas supply pipe, making sure the washers are retained in the tubing nuts, onto the isolation valves, fully push the boiler back, see diagram 8.4.
Ensure the bottom boiler bracket is sitting on top of the service cock bracket, see diagram 8.3.
Fit the flow restrictor into the domestic water inlet, see diagram
8.4.
3
Secure all tubing nuts finger tight, plus
Connect the gas pipe to the isolation valve ensuring that the sealing washer (supplied fitted) is in position.
/4 turn maximum.
INNER CASE FRONT
SECURING SCREW (2)
FLUE COLLECTOR
SECURING SCREW (4)
ELECTRICAL CONNECTORS
7232
Diagram 8.1
7234
8.3 Boiler Securing
Secure the boiler with the two boiler securing screws supplied loose, to the service cock bracket, see diagram 8.3.
An anti theft kit is available, Kit No. 457110
8.4 Flue Fixing to the Boiler
Make sure that the ductings do not slope down towards the boiler.
Position the restrictor plate supplied in the loose items pack, between the flue elbow and boiler , (gasket facing upwards). Fit the flue elbow to the restrictor plate and top of the boiler using the four screws supplied, see diagram 8.5.
Tighten the four screws of the flue elbow evenly to ensure a good seal at the gasket.
Make the wall good internally and externally around the air duct, also making it weatherproof on the outer wall a flue collar kit is available Pt. No. 443286.
Refit fan retained by the rear bracket and two securing screws.
Refit the inner case front.
FAN
RED AIR PRESSURE SWITCH TUBES
WHITE AIR PRESSURE SWITCH TUBES
221679H
16
REAR BRACKET
Diagram 8.2
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
8 Mounting the Boiler and Flue Fitting
BOILER WATER PIPES
BOILER
TOP MOUNTING BRACKET
RETAINING LUG
7075
GAS SUPPLY PIPE
SEALING WASHER (4) (INSERT INTO TUBING NUT)
FLOW RESTRICTOR (DOMESTIC WATER INLET)
8083
SERVICE COCKS (4)
TUBING NUT
Diagram 8.4
BOILER SECURING LUG Note: The lug must be positioned on top of the service cock bracket
SECURING SCREW (2)
SERVICE COCK BRACKET
Diagram 8.3
FLUE ELBOW (REAR FLUE SHOWN)
RESTRICTOR/ GASKET
SECURING SCREW (4)
7233
PRODUCTS PROBE
Diagram 8.5
17
221679H
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Electrical Connections
9.1 Supply Cable Connection
CAUTION: To prevent an induced current from switching the central heating on, when not required, it is important that the heating system control cables are separated from the other mains supply cables.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
The boiler requires a permanent mains supply through an external isolator which must also isolate any heating system controls, see diagram 9.2.
Any heating system controls must not interrupt the permanent mains supply to the boiler.
Using PVC cable of a suitable length and rating as stated in Section 1.8 Electrical Supply, route the mains supply cable and connect to the appropriate terminals of the connector block, restrain with the cable clamp supplied, see diagram 9.2.
Standard colours are, Brown - Live, Blue - Neutral, Green and Yellow - Earth.
Make the earth cable of a greater length so that if the cable is strained the earth would be the last to become disconnected.
CAUTION: It is ESSENTIAL to make sure that the polarity is correct.
9.2 Heating System Controls
All external controls and wiring are required to provide a minimum of reinforced insulation at 250Vrms between the parts of those devices operating at mains hazardous voltage and the user accessible parts af those devices.
The heating system should have installed: a programmer and room thermostat controlling the boiler.
Thermostatic radiator valves may be installed in addition to the room thermostat.
Note: For further information, see The Building Regulations 1991 - Conservation of fuel and power, 1995 edition - Appendix G, table 4b.
If electrical controls are not to be used to regulate the heating system, do not remove the red link cable.
When any form of electrical control is being used to regulate the heating system, remove the red link cable and connect heating system controls in series.
CONTROLS FASCIA
CONTROLS COVER
CONNECTION
BLOCK
SCREW (2)
R2
R1
N
L
SECURING SCREW (2)
RED LINK
Diagram 9.1
CABLE CLAMP
BUSH
MAINS CABLE
7189
7024
9.3 Clock/timer Kit (if applicable)
Fit the clock/timer kit following the appropriate sections of the instructions supplied with it..
9.4 Frost Thermostat
If the installation requires protection by a frost thermostat”, connect a single pole type, to the appropriate terminals of the connector, see diagram 9.3.
Electrical Checks
Keep all cables away from hot surfaces.
Carry out preliminary electrical system checks as below:
1. Test insulation resistance to earth of mains cables.
2. Test earth continuity and short circuit of all cables
3. Test the polarity of the mains.
Refit the controls fascia.
221679H
18
Diagram 9.2
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Electrical Connections
EXTERNAL CLOCK INTEGRAL CLOCK
RED LINK.
REMOVE WHEN CONNECTING ANY HEATING SYSTEM CONTROLS
(L) (N)
CLOCK
TIME CONTROL
JUNCTION
BOX
TO BOILER
5 WAY TERMINAL BLOCK
(R1)
SWITCH CONTACTS
(R2)
5 WAY TERMINAL BLOCK
(L) (N) (R1) (R2)
3 AMP FUSE
DOUBLE
POLE
LN
ISOLATOR
230V~50Hz PERMANENT MAINS SUPPLY
230V~50Hz FROST STAT. NO ROOM STAT.
INTEGRAL CLOCK
3 AMP
FUSE
5 WAY TERMINAL BLOCK
TO BOILER
JUNCTION BOX
E
TO BOILER
MAINS
POTENTIAL
FROST STAT.
RED LINK
7100
DOUBLE
POLE
ISOLATOR
230V~50Hz
PERMANENT
MAINS SUPPLY
LNE
ROOM
THERMOSTAT
FROST
THERMOSTAT
ELECTRICITY SUPPLY CONNECTIONS
INTEGRAL CLOCK
(L) (N) (R1) (R2)
3 AMP FUSE
DOUBLE
LN
POLE
ISOLATOR
TO BOILER
5 WAY TERMINAL BLOCK
JUNCTION BOX
E
230V~50Hz PERMANENT MAINS SUPPLY
MAINS POTENTIAL
ROOM STAT.
RED LINK.
REMOVE WHEN CONNECTING SYSTEM CONTROLS
230V~50Hz ROOM STAT. NO FROST STAT.
INTEGRAL CLOCK
TO BOILER
5 WAY TERMINAL BLOCK
(L) (N)
FROST STAT.
3 AMP FUSE
DOUBLE
LN
POLE
ISOLATOR
230V~50Hz FROST STAT.
INTEGRAL CLOCK
(L) (N) (R1) (R2)
E
230V~50Hz PERMANENT MAINS SUPPLY
230V~50Hz ROOM STAT. USED AS LINK
TO BOILER
5 WAY TERMINAL BLOCK
FROST STAT.
(R1) (R2)
MAINS
POTENTIAL
JUNCTION BOX
RED LINK.
REMOVE WHEN CONNECTING SYSTEM CONTROLS
230V~50Hz
POTENTIAL
MAINS
POTENTIAL
ROOM STAT.
(L) (N) (R1) (R2)
3 AMP FUSE
DOUBLE
LN
POLE
ISOLATOR
POTENTIAL FREE ROOM STAT. NO FROST STAT.
E
230V~50Hz PERMANENT MAINS SUPPLY
POTENTIAL FREE
ROOM STAT.
RED LINK.
REMOVE WHEN CONNECTING SYSTEM CONTROLS
LN
230V~50Hz ROOM STAT.
19
3 AMP FUSE
DOUBLE
POLE
ISOLATOR
JUNCTION BOX
E
230V~50Hz PERMANENT MAINS SUPPLY
230V~50Hz FROST STAT.
230V~50Hz
POTENTIAL
ROOM STAT.
RED LINK.
REMOVE WHEN CONNECTING SYSTEM CONTROLS
Diagram 9.3
221679H
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Commissioning
Please ensure the “Benchmark” logbook is completed and left with the user.
10.1 Filling Domestic Water Circuit
Check that the boiler is isolated from the electrical supply, at the external isolator.
Fully open the domestic water supply stop cock or valve in the supply to the boiler.
Open the domestic water isolation valve, lever in line with the valve body, see diagram 6.1.
Open all hot water draw-off taps and close them when water flows. Check for water soundness of the whole domestic water system and boiler.
10.2 Filling the Heating System
Open the two central heating isolating valves, levers in line with the valve body, see diagram 6.1.
Flush, fill and vent the system refer to Section 4.8 “Filling Sealed Systems”.
WARNING. SEVERAL COMPONENTS OPERATE ON MAINS VOLTAGE AND WITH THE OUTER CASE REMOVED, LIVE COMPONENTS BECOME EXPOSED.
To assist in filling and venting, the pump may be operated: Connect the electrical supply, refer to diagram 4 "Instructions for Use", set button “J” to “winter”, “F” will illuminate, set any remote heating systems controls, time switch and/or room thermostat to call for heat.
Note. If the clock/timer kit is to be fitted, refer to the setting instructions in the Instructions for Use.
Make sure that the automatic air vent is operating correctly.
Take care not to splash any of the electrical components.
Open the controls cover.
Refer to diagram 4 "Instructions for Use". Operate button “J” between H summer and F winter to ensure that water flows through all parts of the boiler and air is not trapped in the boiler internal bypass.
Pressurise the system until the pressure is 1.5bar (21.5lbf/in2). Check the heating system and boiler for water soundness.
Check the operation of the safety valve by turning the safety valve knob in the direction of the arrow.
Lower the pressure to the initial cold fill design pressure, refer to Table 1. Position the set pointer on the boiler pressure gauge at this pressure also.
Refit inner case front.
10.3 Preparation for Lighting
Turn on the gas service cock, slot in line with the length of the cock.
Test for soundness and purge air from the gas supply.
Switch power 'ON' at the mains electrical supply at the external isolator and switch at the boiler.
Light the pilot refer to relevant parts of "Light the boiler" (Instructions for Use).
Loosen the burner pressure test point screw and connect a suitable pressure gauge, see diagram 10.1.
WARNING 230V 50Hz
ELECTRICAL CONNECTIONS
BURNER PRESSURE TEST POINT
GAS CONTROL VALVE
Diagram 10.1
10.4 Burner Pressure - Hot Water
Connect the electrical supply it will default to winter, select summer, the pump will operate for about 30 seconds then the pump will stop.
Fully open the largest hot water draw off tap whereby the main burner will light, the flames gradually increasing to the maximum.
Check the soundness of the boiler gas joints, with the main burner on, using a leak detection fluid. Take care not to splash any of the electrical components.
To achieve this flow rate a water pressure of at least 0.8bar is required during commissioning, although subsequently the appliance will work at a minimum pressure of 0.5bar.
This flow rate should prevent any modulation of the gas pressure.
The burner pressure is factory preset and no adjustment should be required.
Check the burner pressure is within +/-0.35mbar (+/-0.14in wg). of 13.0mbar (5.22in wg). If this is incorrect, the burner pressure may be adjusted to the correct setting by turning the hot water gas pressure adjuster (potentiometer), located on the control board to gain access remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control facia forward.
Remove the plastic plugs. Using the burner adjusting tool supplied. (Clockwise to increase), see diagram 10.2. Turn the adjuster slowly, always making adjustment by reducing below the required pressure then increasing up to the required setting.
Close the hot water draw off.
If the maximum pressure cannot be obtained, check that the gas supply is of adequate size, refer to Section 1.7.
10.5 Gas Rate Modulation
The minimum gas rate is factory preset and no adjustment should be required.
ALWAYS CHECK HOT WATER BURNER PRESSURE FIRST
- REFER TO SECTION 10.4.
To check the minimum gas rate, first make sure that the boiler is isolated from the electrical supply at the external isolator
7034
221679H
20
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Commissioning
Remove grey wire from the modureg coil (insulate from sheet metal).
Switch on the electrical supply it will default to winter, select summer.
Fully open a hot water draw off tap and the main burner will light at the minimum gas rate.
Check that the burner pressure is 1.2mbar +/-0.2mbar, (0.5in wg +/-0.1in wg). If this is incorrect, it may be adjusted by removing the cap and turning the larger adjusting nut of the modulator, (anticlockwise to decrease the pressure).
If the above adjustment was necessary, it will be essential to check that the maximum pressure can still be obtained. Push the spindle gently in to the stop and hold it in. The maximum pressure should not be less than 14.5mbar, (5.8in wg). If this pressure cannot be achieved, obtain it by turning the small adjusting nut, (clockwise to increase the pressure). Always adjust the minimum pressure first. Reconnect the grey wire and adjust pressures on potentiometers.
If the maximum pressure is unattainable, check that the gas supply is of adequate size, refer to Section 1.7 Gas Supply”. Put right as necessary.
Isolate the boiler from the electrical supply then reconnect the modulator cable and refit the cap.
10.6 Domestic Water Flow Rate
This is factory preset and can not be adjusted.
10.7 Burner Pressure - Heating
The burner pressure is factory preset and no adjustment should be required.
Check that all remote heating system controls, room thermostats, integral clock and the like are switched on/programmed and calling for heat.
Set button “J” to “winter” “F”, see diagram 4.
The pump will circulate water through the boiler and the main burner will light.
Check that the burner pressure, with the heating system cold to prevent any modulation of the gas pressure, is within +/-
0.2mbar (+/-0.08in wg) of 7.6mbar (3.05in wg), the central heating pressure.
If the burner pressure is incorrect, it may be adjusted to the correct setting by turning the central heating gas pressure adjuster (potentiometer), located on the control board to gain access remove the two screws securing the controls facia.
Hinge the control facia open.
Remove the plastic plugs. Using the burner adjusting tool supplied (clockwise to increase), see diagram 10.2. Turn the adjuster slowly, always making adjustment by reducing below the required pressure then increasing up to the required setting.
Isolate the boiler from the electrical supply.
Remove the pressure gauge and tighten the test point screw.
Test for gas soundness around the burner pressure test point with the main burner alight, using leak detection fluid. Take care not to splash any of electrical components.
Replace plastic plugs and refit the control fascia.
10.8 Temperature Settings
The domestic hot water outlet and central heating flow temperatures are factory preset and sealed, therefore cannot be adjusted.
DOMESTIC HOT WATER BURNER
PRESSURE POTENTIOMETER
CABLE ENTRY COVER
CLOCK-TIMER
COVER
PLASTIC PLUG (2)
CONTROL
CONTROL
BOARD COVER
HEATING BURNER PRESSURE POTENTIOMETER
BOARD
COVER SECURING SCREW (4)
The nominal temperature setting for the domestic hot water outlet is 65
The nominal maximum flow temperature setting for central heating is 82
o
C (149oF) at a flow rate of 3.6Litre/min (0.8gall/min).
o
C (180oF).
BURNER PRESSURE ADJUSTING TOOL
Diagram 10.2
10.9 Heating System - Commissioning
Check that all remote controls and integral clock are calling for heat.
Fully open all radiator valves.
Set the heating system in operation and balance the radiators.
Refer to Section 4.6 and diagram 4.1.
Allow the system to reach maximum temperature then switch off, isolate the boiler from the electrical supply and drain the system rapidly whilst still hot.
Remove the inner case front.
Fill and vent the system as described in Section 10.2 Filling the Central Heating Circuit. Add inhibitor, if applicable, refer to Section 4.9 Corrosion Inhibitor”.
Lower the pressure to the initial cold fill design pressure, using the external draining tap, close to the boiler, refer to Table 1 and Section 4.10.
10.10 Completion
Refit the inner case front.
Fit the side panels, hook into the threaded lugs at the top, see diagram 10.3.
Fit the case base, slide back engage the rear lugs, secure with two screws supplied, see diagram 10.4.
Secure the side panels at the bottom with the four screws, see diagram 10.3.
Fit the outer case front by locating it on one side then wrap it
7078
21
221679H
Page 22
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Commissioning
around locating it on the opposite side, slide down locating on to the threaded lugs at the top and behind the controls cover at the bottom, secure with nuts ,see diagram 10.5.
Set the boiler and any remote heating control to the desired settings, then close the control cover door.
10.11 Instruct the User
Instruct and demonstrate the lighting procedure, then advise the user of the efficient and safe operation of the boiler.
Instruct and demonstrate the operation of any heating system controls.
Advise the user that to ensure the continued efficient and safe operation of the appliance it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the particular installation and usage, but in general once a year should be enough.
Draw attention, if applicable, to the current issue of the Gas Safety (Installation and Use) Regulations, Section 35, which imposes a duty of care on all persons who let out any property containing a gas appliance.
It is the Law that any servicing is carried out by a competent person.
Advise the user of the precautions necessary to prevent damage to the system and building in the event of the heating system being out of use during frost and freezing conditions.
Reminder - Leave these instructions and the “Benchmark” logbook with the user.
CASE BASE
CUTOUT
WRAP AROUND
SECURING SCREWS
7235
CUTOUT
Diagram 10.4
7074
SIDE PANEL
7073
NUT (2)
OUTER CASE FRONT
SECURING SCREW (2)
221679H
SECURING SCREW (2)
Diagram 10.3
22
Diagram 10.5
Page 23
Supplied By www.heating spares.co Tel. 0161 620 6677
11 General Data
11.1 Servicing or Replacing Parts
To ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals.
The frequency of servicing will depend upon the particular installation conditions and usage, but in general once a year should be enough.
The servicing of this boiler must be carried out by a competent person in accordance with the rules in force in the countries of destination.
NOTE: To obtain a products of combustion reading, remove the screw from the analyser probe positioned on the top of the boiler next to the flue elbow, see diagram 8.5. After use replace the screw.
Typical values for this boiler at maximum domestic hot water demand is:- CO These are based on a 300mm length rear flue.
Make sure the appliance does not modulate whilst checking combustion and allow the appliance to warm up for five minutes before taking a reading.
Unless stated otherwise, parts removed or renewed during servicing should be fitted in the reverse order to removal.
After completing any servicing, or renewing of gas carrying components, ALWAYS test for gas soundness and carry out functional checks of controls.
Dispose of all used sealing washers, gaskets and “O” rings when renewing components.
Use the new ones supplied with the replacement.
7.5% to 8.0% and CO 0.005% to 0.015%.
2
11.2 Data Label
The data label is positioned on the front of the inner case cover.
11.3 Isolation of Boiler
Before starting any servicing or the replacement of parts, isolate the boiler from the electrical supply at the external isolator.
When servicing or replacing any cold/hot water or heating system components close all water cocks and drain appliance.
Close the gas service cock, see diagram 6.1.
BEFORE DRAINING THE BOILER, REFER TO SECTION
11.6.
11.4 Outer Case Front Removal
Remove the two nuts securing the outer case front then lift up unhook the case at the top from the threaded lugs, pull it off on one side to release then remove, see diagram 10.5.
11.5 Inner Case Front
Remove the inner case, secured by four screws, see diagram
8.1.
11.6 System Pressures and Draining
All parts containing water of the central heating circuit within the boiler, are under the system pressure. Before any parts of this circuit are disconnected, reduce the system pressure at the external draining tap, turn the central heating isolating valves off, and drain at the drain points on the appropriate valves, see diagram 6.1.
All water containing parts of the domestic hot water circuit of the boiler will be under the supply water pressure. Before any parts of this circuit are disconnected, turn the domestic cold water isolating valve off, open the hot water taps to reduce the water pressure in the boiler and drain the boiler at the valves, see diagram 6.1.
After replacing any water containing part of the central heating circuit, make up the water loss, vent all air and pressurise the system. Refer to Commissioning in the Installation Instructions.
Check for water soundness and that the safety valve seats without leaking.
12 Servicing
12.1 Pilot Check
Check if the pilot flame is burning correctly and of the correct size, see diagram 14.4. If the pilot flame is not correct, the pilot injector will require removing when accessible.
12.2 Isolation and Access
Before starting, refer to Section 11.
Remove the fan from the flue collector, refer to Section 14.1
Remove the flue collector, secured with two screws.
Remove the main burner, refer to Section 14.2.
12.3 Cleaning the Heat Exchanger
Place a sheet of paper in the combustion chamber to cover the injector and pilot assembly, to collect any debris.
Brush the heat exchanger.
Remove the paper together with any debris.
Do not use a brush with metal bristles.
12.4 Cleaning the Main Burner
Use a vacuum cleaner or suitable brush to clean the burner thoroughly, making sure that all the burner ports are not obstructed.
Do not use a brush with metal bristles.
12.5 Cleaning the Pilot Injector
If the pilot flame was not burning correctly, it is necessary to remove the pilot injector, refer to Section 14.6.
Inspect the injector and clean if necessary, by blowing clear only.
Do not use a wire or sharp instrument.
12.6 Service Checks
Inspect the pilot burner, spark electrode, adapter olive on the pilot tube and thermocouple. Clean if necessary or renew, refer to Section 14.4, 14.5 and 14.6.
Check the main injector, cleaning or renewing as necessary, refer to Section 14.3.
Before replacing any parts removed during servicing, inspect the condition of all seals and joints, renewing as necessary.
Check the condition of the combustion chamber insulation. If renewing, refer to Section 14.20.
Check the spark gap, upon assembly, see diagram 14.4.
23
221679H
Page 24
Supplied By www.heating spares.co Tel. 0161 620 6677
12 Servicing
12.7 Operational Checks
Check the safety valve manually by turning the knob in the direction of the arrow.
Light the boiler, carry out operational checks and any necessary adjustments as described in Commissioning in the Installation Instructions.
13 Fault Finding
13.1 Initial Checks
If the boiler fails to operate, first check the following:-
1) That the electrical supply is available at the boiler and the fuses are in order. The mains light should be ON. If not isolate the boiler from the electrical supply.
Test for continuity, at mains.
NOTE: THE BOILER CONTROL BOARDS CAN BE DAMAGED BY INCORRECT TESTING OF COMPONENTS AND WIRING WITH THE POWER ON.
2) Make sure that the system pressure gauge registers 0.7bar, minimum, and that the automatic air vent works. Refer to Installation Instructions, Section 10.2.
3) That the gas supply is available at the boiler and purged of air.
4) That the boiler is set for the required service.
5) With the boiler Summer/Winter Button “J” set to summer “H”, see diagram 4 User Instructions, check that the domestic water supply is available and water flows freely from the hot taps. Close the taps.
6) With the boiler Summer/Winter Button “J” set to Winter “F”, see diagram 4 User Instructions, check that all heating system controls, if fitted, are working correctly and calling for heat.
7) Check Summer/Winter Button “J” is set to Winter “F”, see diagram 4 User Instructions. Turn on a domestic hot water draw off tap to create a demand.
Allow the boiler and system to cool down waiting at least a minimum of four minutes before pressing Summer/Winter Button J to set to Winter F.
If this is satisfactory proceed with the detailed fault finding as Section 13.3.
13.2 Clock/Timer
If the clock has failed it can be bypassed by disconnecting the plug and reconnecting the link, see diagram 13.1.
Gain access by removing the two screws securing the controls facia, see diagram 10.1.
Hinge the control facia forward.
Remove the clock timer cover, see diagram 9.1.
Disconnect the clock wiring harness plug and connect the link.
This is a temporary measure and the clock should be repaired or replaced as soon as possible.
13.3 Electrical
Preliminary electrical system checks, as outlined in a Multimeter Instruction book, are the first checks to be carried out during a fault finding procedure.
Isolate the boiler from the electrical supply, refer to Section
11.3.
Gain access to the boiler controls by removing the outer case front, refer to diagram 10.5.
12.8 Completion
Hook the outer case front on the top and secure with the nuts previously removed, see diagram 10.5.
Remove the two screws securing the controls facia, see diagram
9.1.
Hinge the control facia forward.
Remove the cable entry cover, see diagram 10.2.
Remove the controls cover
Check that all cables and connectors are secure.
Check all cables at the multipin connectors on the board.
Test the fuse on the main control board and renew as necessary. Fuse F1 type (2AT and F2 315mAT). If a fuse fails repeatedly or the initial fault-finding checks described in Section 13.1 indicate a boiler fault, check the boiler electrical circuits and follow the fault finding procedures, see diagram 13.2 mains functional flow, 13.3 pilot fault finding, 13.4 boiler fault finding
13.5 thermocouple fault finding and for clock/timer fault finding, diagrams 13.6 and 13.7.
On completion of a fault finding task that has required the disconnection and making of electrical connections then checks, for earth continuity, polarity and resistance to earth must be carried out.
Before replacing any part please read points below:-
Replacement of parts must only be carried out by a competent person.
1. Refer to Section 11.1.
2. Always isolate the boiler from the electrical and as required, the gas supply, as Section 11.3.
3. On completion, make good any water loss and pressurise the system to initial design pressure, refer to “Commissioning” in the Installation Instructions.
Before starting refer to Section 11.1
Isolate the boiler from the electrical supply, refer to Section
11.3.
7025
CLOCK/TIMER PLUG
CLOCK/TIMER
LINK
Diagram 13.1
221679H
24
Page 25
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Fault Finding
TO TEST FOR COMPONENT OPERATION / FAILURE Power to the appliance :- Test for 230V~ across live
(brown) and earth (yellow and green), 230V~ across live and neutral (blue), and zero potential across neutral and earth.
Thermistors :- With the power off unplug the connector and test resistance is 10k at 25°C.
Domestic Hot Water demand sensor :- With a tap open the supply to the sensor measure between the red and black cables on X5a should be 12Vdc. The signal from the sensor measured between the white and black cables X5a should be between 1Vdc and 11Vdc dependent of the flow rate.
Overheat thermostat :- With the power off unplug the connectors and test for continuity (zero resistance).
Power to the gas control valve :- With a demand on test for voltages of 230Vac ~ across the red and purple cable connectors and 24Vdc ~ across the grey and grey cable connectors. When burner pressure at maximum.
Power to the fan :- With a demand on and the front cover removed test for 230V~ at the fan connectors at high speed and 108V at low speed
Fan failure :- with the power off and the supply leads to the fan disconnected (pull the boots only) the resistance across the fan coil should be 45 to 50Ω.
Pump :- With the power off unplug the connector from the pump. Restore the power and check that there is 230V~ between live (brown) and neutral (blue) or live and the appliance earth.
Air pressure switch :- This is a change over device. With the fan at pilot only there should be 230V at the C and NC (No air state terminals. With the appliance running and the fan at full speed there should be 230Vac at C, Nc and No (Air State).
Water pressure switch :- With no water pressure and Power On, check there is 230V~ on the black and grey cables and 0V on the grey cable X5b. With water applied to the system and power on, check there is 230V~ on the black and grey cables and on the white cable X5b. This will prove operation of the water pressure switch.
PERMANENT MAINS 230V-50HZ
brown
X3
F1 2AT
X3
X3
X4
X4
X2
X2 X2
X2
X2
CONTROL BOARD
X2 X2 X2
X5b X5b X5b
X3
TERMINAL
BLOCK
L
brown
red
red
brown
blue
red red
purple
yellow
brown
blue
red
grey
violet
grey
white
black
blue
PUMP
FAN SPEED RESISTOR
N/O
N/C
N/O4
N/C2
N
MAINS FUNCTIONAL FLOW
orange
7495
24v~
CH THERMISTOR
DHW THERMISTOR
DHW
FLOW
SENSOR
orange
orange
orange
purple
purple
black
white
red
ON/OFF
SWITCH
brown
TRANSFORMER
240/24V
OVERHEAT CUTOFF
brown
AIR
C
PRESSURE SWITCH
LOW WATER
C1
PRESSURE SWITCH
X1
X1
X6 X6
X6 X6
X5a X5a X5a
7468
24V
LOW
VOLTAGE
GAS
VALVE
FAN
3.15AT
CONTROL BOARD
MODULATING
LOW VOLTAGE FUNCTIONAL FLOW
25
VALVE
grey
grey
X5a X5a
Diagram 13.2
221679H
Page 26
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Fault Finding
PILOT WILL NOT LIGHT START HERE
Check gas line-open all cocks, rectify any blockages, purge out any air. Does pilot light?
NO YES
Apply match to pilot burner instead of pressing piezo unit button. Does pilot light?
NO
Undo tubing nut at pilot burner. Turn gas valve knob to Pilot/Ign. Press multi-functional control knob. Does gas flow freely?
NO
Rectify blockage in pilot injector, or renew pilot injector.
YES
YES
Does pilot stay alight when multi-functional control knob is released?
NO YES
PILOT SATISFACTORY
Does pilot flame envelop thermocouple?
NO
Check aeration. If necessary ­Clean pilot, rectify blockage in pilot injector, or replace.
Check thermocouple circuit using Thermocouple fault finding diagram.
YES
7460
Undo tubing nut at pilot outlet of the multi-functional control. Press gas valve knob. Does gas flow freely?
NO
Rectify or replace blocked pilot tube.
Change multi-functional control.
YES
On pressing piezo unit button is there a spark across electrode gap?
NO
Is there continuity of piezo earth?
NO
Repair or replace earth lead.
Pull ignition lead off electrode. Hold end of lead close to pilot burner and operate piezo unit. Is there a spark across gap?
NO
Pull ignition lead off piezo unit. Using blade of a screwdriver, touch unit chassis and leave approx. 4mm gap from connection tag onpiezo unit. Operate piezo. Is there a spark across gap?
YES
YES
YES
Change piezo unit.
Check electrode gap. Reposition, or replace electrode as necessary.
PILOT FAULT FINDING
221679H
26
NO
YES
Change ignition lead.
Diagram 13.3
Page 27
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Fault Finding
Check that gas,water and electricity are available at the boiler. There must be no external
voltage applied to the control board via the central heating controls to the P.C.B.
Before commencment of test, isolate the boiler electricity supply,
ensure that the remote controls are not calling for duty (no red link in terminal block)
Refer to functional flow diagrams in conjuction with the following fault finding.
START
Remove the outer case, lower the control housing and remove cable restraints. Check all connections on the control board and the boiler components, rectify or renew as necessary. Two spare fuses are provided.
YES
7491
Can pilot be lit?
YES
Switch on main supply. Do mains and winter mode LEDs illuminate?
YES
Does low water pressure LED flash?
NO
Does fan run at low speed?
NO
YES YES YES
NO NO YES
Refer to pilot fault finding.
NO
Change P.C.B.
Is there enough system pressure?
NO
Re-pressurise system.
Is there 112v at fan terminals?
Is there continuity between common and N/O?
NO
Change water pressure switch.
Is the 1kohm resistor OK?
Change P.C.B.
Change P.C.B.
YES
Winter Mode Continued.
BOILER FAULT FINDING
Summer Mode Continued.
Change fan.
YES
27
NO
Change fan resistor.
Diagram 13.4
221679H
Page 28
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Fault Finding
Winter Mode Continued.
Press button to change to summer mode. Does summer mode LED illuminate?
Turn hot water demand on. Does fan goto fast speed?
Does main burner light?
Connect a manometer to gas valve and check burner pressure. Adjust hot water burner pressure potentiometer. Does burner pressure adjust accordingly?
Summer Mode Continued.
YES
YES
YES
YES
NO
NO
NO NO
NO
Change P.C.B.
Using spare flow sensor. Connect to P.C.B. Then blow down flow sensor. Does the fan goto fast speed?
Does signal at air pressure switch change over?
YES
NO
Is there 230v at main valve?
Is there a mV signal at the modureg?
YES
NO
YES
NO
Change the gas valve.
Change flow sensor.
Change P.C.B.
Change air pressure switch.
Change P.C.B.
Change P.C.B.
7492
YES
Is there a decrease in electrical resistance across the hot water thermistor as temperature rises?
YES
Turn off hot water demand. Does main burner go out?
YES
Does central heating pump start and run for a short time?
YES
OK.
NO
NO
NO
YES
Change gas valve.
Is there 230v at main valve?
Is there 230v at pump?
YES
Change pump.
NO
Change thermistor.
NO
Change the valve.
YES
Change the P.C.B.
Change P.C.B.
BOILER FAULT FINDING
221679H
28
Diagram 13.4
Page 29
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Fault Finding
Winter Mode Continued.
YES
When demand from T/Sat is requested, does the pump operate?
YES
Does fan go to high speed?
YES
Does main burner light?
YES
Connect a manometer to gas valve and check burner pressure. Adjust central heating burner pressure potentiometer. Does the burner pressure increase and decrease accordingly?
YES
NO
NO
NO
NO
Is there 230v at pump?
Is there 230v at fan terminals?
Does signal from air pressure switch change over?
YES
Is there 24v at modureg valve?
Is there a mV signal at modureg terminals?
BOILER FAULT FINDING
NO
YES
NO
YES
NO
NO
YES
NO
YES
Change P.C.B.
Change pump.
Change P.C.B.
Change fan.
Change air pressure switch.
Change P.C.B.
Change valve.
Change P.C.B.
Change valve.
7493
Disconnect connections to central heating thermistor is there a decrease in electrical resistance accross the terminals as the temperature increases?
YES
Reconnect thermistor turn on hot water tap fully. Does the central heating pump stop?
YES
Burner pressure increases to domestic hot water setting. Adjust domestic hot water burner pressure potentiometer. Does burner pressure alter accordingly?
YES
Slowly close hot water tap. Does the Burner pressure modulate down to keep a constant temperature?
YES
Turn off hot water demand. Does pump restart?
YES
Does burner pressurere turn to Central heating setting?
YES
NO
Is there a decrease in resistance accross the domestic hot water thermistor as temperature rises?
NO
NO
NO
NO
YES
NO
NO
Change thermistor.
Change flow sensor.
Change P.C.B.
Change thermistor.
Change P.C.B.
Change P.C.B.
Change P.C.B.
Remove central heating demand. Does burner go out?
YES
O.K.
NO
Is there 230v at main valve?
Change P.C.B.
29
YES
NO
Change valve
Diagram 13.4
221679H
Page 30
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Fault Finding
With the boiler cold, check connections of the thermocouple, boiler overheat cut-off and gas valve. Disconnect overheat cut-off connectors at points A and B at the gas valve, see diagram. Test continuity of the overheat cut-off. Is there continuity?
NO
Faulty boiler overheat cut-off,
YES
Re-connect boiler overheat cut-off to points A and B. Disconnect thermocouple at point D of the gas valve. Test continuity between point C and the body of the gas valve. Is there continuity?
NO
Test continuity of thermocouple between inner point D and point E. Is there continuity?
YES
YES
NO
renew.
Faulty cut-off connectors into gas valve. Either at A or C. Renew where faulty.
Faulty thermocouple, renew.
7462
Thermocouple and boiler overheat circuit satisfactory.
GAS CONTROL VALVE
BOILER OVERHEAT CUT-OFF
CONNECTION 'A'
2313S
CONNECTION 'E'
CONNECTION 'C'
THERMOCOUPLE FAULT FINDING
221679H
30
CONNECTION 'D'
CONNECTION 'B'
Diagram 13.5
Page 31
Supplied By www.heating spares.co Tel. 0161 620 6677
13 Fault Finding
NB. The clock can be by passed by refitting the plug link which should be inside the clock timer cover.
Check continuity of clock/timer harness, ensure an electrical supply is available, ensure that remote controls are calling for heat.
Isolate the boiler from electrical supply remove outer case.
YES
Switch on electrical supply, is there a display on clock/timer?
NO
Faulty clock/timer. Replace.
YES
Disconnect and insulate the cables from heating common and heating on.
YES
Advance clock/timer until a demand is indicated Is there now continuity between heating common and heating on?
NO
Faulty clock/timer. Replace.
YES
Clock/timer in order if no central heating, refer to main fault finding.
7461
DIGITAL FAULT FINDING
NB. The clock can be by passed by refitting the plug link which should be inside the clock timer cover.
Check continuity of clock/timer harness, ensure an electrical supply is available at the clock, ensure that remote controls are calling for heat, ensure the override switch, if fitted, is in overide position.
Does clock keep time?
NO
Faulty clock/timer. Replace.
YES
Isolate electrical supply, set clock to an on period. Is there continuity across common and heating?
NO
Faulty clock/timer. Replace.
YES
Set clock to off period. Is there continuity across common and heating on?
NO
Clock/timer in order if no central heating, refer to main fault finding.
(N) (L)
YES
EXTERNAL
CONTROLS
Faulty clock/timer. Replace.
7684
Diagram 13.6
7463
ELECTRO/MECHANICAL FAULT FINDING
PLUG FROM CLOCK/TIMER
31
BLUE
BROWN
ORANGE
PURPLE
Diagram 13.7
221679H
Page 32
Supplied By www.heating spares.co Tel. 0161 620 6677
14 Replacement of Parts
14.1 Fan
Before starting refer to Section 11.
Disconnect the two electrical connectors at the fan by pulling the boots not the wires, see diagram 8.2.
Disconnect the two air pressure switch flexible tubes from the fan.
Remove the fan, secured with two screws at the front and gently ease the fan from the flue elbow and rear bracket.
To fit the fan, locate it into the rear bracket and ease the fan into the flue outlet, secure with the two screws.
The polarity of the two electrical connectors is not important.
14.2 Main Burner
Before starting refer to Section 11.
Remove the two screws securing the flue collector, see diagram
14.1.
Remove the combustion chamber front panel, secured with four screws.
Open the controls cover door, see diagram 4.
Remove the two screws securing the controls facia, see diagram
9.1.
Hinge the control facia open.
Separate the pilot assembly from the main burner secured with two screws and washers, see diagram 14.2.
Remove the sealing gland, see diagram 14.2.
Remove the burner bracket securing screw, wing nut and bracket, see diagram 14.2.
Remove the main burner from the main injector at the rear. Tilt burner up and slide in channel forwards, easing the pilot assembly forwards to clear, taking care not to damage the combustion chamber insulation or the pilot burner assembly.
When refitting make sure that the main burner is fitted correctly on assembly, located on the main injector and horizontal, the tips of the rearmost blade under the two burner guides.
Locate the combustion chamber front panel under the front edge of the flue hood on assembly, then secure all screws and wing nut.
Test pilot for gas soundness with suitable leak detection fluid with the gas control knob depressed.
FLUE COLLECTOR
SCREW (4)
COMBUSTION CHAMBER FRONT PANEL
SECURING SCREW (2)
WINGNUT
SPARK ELECTRODE
SPARK ELECTRODE RETAINING CLIP
PILOT INJECTOR
7249
Diagram 14.1
4583
THERMO­COUPLE NUT
14.3 Main Injector
Before starting refer to Section 11.
Remove the main burner, refer to Section 14.2.
Unscrew the main injector, see diagram 14.3.
Fit the new sealing washer supplied, to ensure gas soundness, when fitting the main injector.
14.4. Pilot Burner
Before starting refer to Section 11.
Remove the main burner refer to Section 14.2.
Remove the sealing angle, secured with a single screw, see diagram 14.2.
Remove the spark electrode, secured with a spring clip, see diagram 14.2.
Disconnect the thermocouple nut from the pilot burner.
221679H
32
SECURING SCREW AND WASHER (2)
WING NUT
PILOT TUBE NUT
SEALING GLAND SECURING SCREW
BURNER BRACKET
SECURING SCREW
IGNITION LEAD
Diagram 14.2
Page 33
Supplied By www.heating spares.co Tel. 0161 620 6677
14 Replacement of Parts
Disconnect the pilot supply tube, holding the pilot injector hexagon with another spanner, then remove the pilot burner.
Check the spark gap upon assembly, see diagram 14.4.
Make sure the pilot injector is fitted.
Test joints for gas soundness with suitable leak detection fluid with the gas control knob depressed.
14.5 Spark Electrode
Before starting, refer to Section 11.
Slacken the sealing angle, secured with a single screw, see diagram 14.2.
Remove the spark electrode, secured with a spring clip, see diagram 14.2.
Ease the spark electrode through the sealing angle.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Disconnect the ignition lead from the piezo unit, see diagram
14.9.
Check the spark gap upon the assembly, see diagram 14.4.
ACCESS COVER
LONG SECURING SCREW (2)
7079
SECURING SCREW (3)
SHORT SECURING SCREW (2)
COPPER WASHER
SPARK GAP 4.5mm to 5.5mm
FLAME LENGTH 25mm
MAIN INJECTOR
Diagram 14.3
Diagram 14.4
7311
4574
PILOT TUBE NUT
THERMOCOUPLE NUT
GAS CONTROL VALVE
SHORT SECURING SCREW (2)
OVER HEAT CUTOFF ELECTRICAL CONNECTION
WARNING 230V 50Hz
ELECTRICAL CONNECTION (5)
OVER HEAT CUTOFF
Diagram14.5
33
221679H
Page 34
Supplied By www.heating spares.co Tel. 0161 620 6677
14 Replacement of Parts
14.6 Pilot Injector
Before starting, refer to Section 11.
Remove the sealing angle, secured with a single screw, see diagram 14.2.
Remove the spark electrode, secured with a spring clip, see diagram 14.2.
Disconnect the thermocouple nut from the pilot burner.
Disconnect the pilot supply tube, holding the pilot injector hexagon with another spanner, then remove the pilot burner.
Remove the pilot injector from the pilot assembly by unscrewing it.
Check the pilot flame length on relighting, see diagram 14.4.
Test pilot for gas soundness with suitable leak detection fluid with the gas control knob depressed.
14.7 Thermocouple
Before starting refer to Section 11.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Remove the main burner, refer to Section 14.2.
Remove the sealing angle secured with a single screw, see diagram 14.2.
Remove the access cover in the base of the combustion chamber secured with three screws, see diagram 14.5.
Disconnect the thermocouple at the gas control valve and pilot assembly, see diagram 14.2 and 14.5.
Remove the thermocouple.
Make sure that the overheat cut-off connector is in place in the slot of the gas control valve when fitting the thermocouple. Do not tighten the thermocouple nut more than a quarter turn beyond finger tight or make any tight bends in the thermocouple capillary.
Test joints for gas soundness with suitable leak detection fluid with the gas control knob depressed.
14.8 Central Heating Boiler Overheat Cut-off
Before starting refer to Section 11.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Disconnect the overheat cut-off electrical connectors positioned at the front and rear of the gas control valve, see diagrams 14.5 and 14.7.
Unclip to remove the overheat cut-off, see diagram 14.8.
14.10 Domestic Hot Water Thermistor.
Before starting, refer to Section 11.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Disconnect the electrical connector at the domestic hot water thermistor, see diagram 14.8.
Unclip the domestic hot water thermistor from the flow pipe.
14.11 Central Heating Hot Water Thermistor.
Before starting, refer to Section 11.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control facia forward.
Disconnect the electrical connector at the domestic hot water thermistor, see diagram 14.8.
Unclip to remove the domestic hot water thermistor from the flow pipe.
14.12 Transformer
Before starting, refer to Section 11.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Disconnect the inline electrical connectors from the transformer, see diagram 14.8.
Remove the transformer, noting the correct position.
To connect the transformer cables correctly, see diagram
14.25.
14.13 Fan Resistor
Before starting, refer to Section 11.
Disconnect the electrical connectors from the resistor, see diagram 14.6.
Remove the resistor, noting the correct position.
To connect the resistor cables correctly, see diagram 14.25.
14.14 Piezo Unit
Before starting refer to Section 11.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Disconnect the ignition and earth leads at the piezo unit.
Remove the piezo unit, see diagram 14.9.
14.9 Domestic Hot Water Boiler Overheat Cut-off
Before starting refer to Section 11.
Open the controls cover door, see diagram 4 user instructions.
Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Disconnect the overheat cutoff electrical connectors, see diagram 14.8.
Remove the securing screws to release the overheat cut-off.
221679H
34
Page 35
Supplied By www.heating spares.co Tel. 0161 620 6677
RETAINING BRACKET
FAN RESISTOR
14 Replacement of Parts
7236
SECURING SCREW (2)
ELECTRICAL CONNECTION
7097
Top right hand side of boiler
BOILER OVERHEAT CUTOFF CENTRAL HEATING
RETAINING CLIP
WATER PRESSURE SWITCH
ELECTRICAL CONNECTION (2)
Diagram 14.6
DOMESTIC HOT WATER THERMISTOR
Diagram 14.7
ELECTRICAL CONNECTION
GAS CONTROL VALVE
GAS CONTROL VALVE
7034
CENTRAL HEATING HOT WATER THERMISTOR
7072
EARTH LEAD
SECURING NUT
PIEZO UNIT
TRANSFORMER
IGNITION LEAD
Diagram 14.9
MULTI PIN CONNECTORS
35
BOILER OVERHEAT CUTOFF DOMESTIC HOT WATER
CAREFULLY BEND THE RETAINING CLIPS FORWARD TO RELEASE MULTI PIN CONNECTORS
Diagram 14.8
7237
Diagram 14.10
221679H
Page 36
Supplied By www.heating spares.co Tel. 0161 620 6677
14 Replacement of Parts
14.15 Control Board
Before starting refer to Section 11.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Remove the cable entry covers, see diagram 10,2.
Disconnect the multi-pin connectors retained by clips, see diagram 14.10.
Remove the controls board cover securing screws and remove cover, see diagram 10.2.
Disconnect the remaining multi-pin connector retained by a clip.
Remove the control board securing screw, see diagram 14.11.
Remove the control board from the support posts, see diagram
14.11.
THE MAIN CONTROL BOARD MUST BE KEPT IN THE ANTI STATIC HOLDER UNTIL IMMEDIATE REQUIREMENT.
When replacing the main control board check and if necessary adjust the main burner gas pressure in both the hot water and central heating modes. Refer to Commissioning in the Installation Instructions.
4.16 Pressure Gauge
Before starting, refer to Section 11.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Release the water pressure and drain the central heating circuit of the boiler, refer to Section 11.3 and 11.6.
Disconnect the pressure gauge connection from the safety valve, discard the washer, see diagram 14.12.
Remove the pressure gauge, see diagram 14.13.
Locate the supplied washer under the pressure gauge connection when refitted to the safety valve.
IMPORTANT NOTE: Make sure the capillary follows the original route avoiding kinks and sharp bends.
14.17 Gas Control Valve
Before starting refer to Section 11.
Remove the case base, see diagram 10.4.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Remove the main burner refer to Section 14.2.
Remove the gas control knob.
Remove the access cover in the base of the combustion chamber secured with three screws, see diagram 14.5.
Disconnect the five electrical connectors, four at the front of the gas control valve and one at the rear, see diagrams 14.5 and
14.7.
Disconnect the thermocouple at the gas control valve, see diagram 14.5.
Disconnect the pilot supply tube at the gas control valve, see diagram 14.5.
Disconnect the gas supply union at the gas service cock, see diagram 8.4.
Remove the four extended hexagon screws at the gas control valve, see diagram 14.5.
Pull the gas control valve forward releasing it from the two rear support pins.
Remove the four extended screws attaching the manifold to the gas control valve
Transfer the pilot tube adapter, overheat cutoff connectors and manifold to the replacement valve. Discard the “O” rings and fit the new ones supplied, when fitting the gas valve.
To connect the gas control valve cables correctly, see diagram
14.25.
Light and adjust the boiler if necessary, refer to Commissioning in the Installation Instructions. Adjust the pilot flame if necessary, refer to Section 14.4, Pilot Burner.
Test joints for gas soundness with suitable leak detection fluid with the gas control knob depressed.
Check and adjust the main burner pressure in the hot water and central heating modes, refer to Commissioning in the Installation Instructions.
SUPPORT POST (4)
SECURING SCREW
221679H
36
7238
MULTI PIN CONNECTOR (5)
Diagram 14.11
Page 37
Supplied By www.heating spares.co Tel. 0161 620 6677
14 Replacement of Parts
14.18 Modulator
Before starting refer to Section 11.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Disconnect the two electrical connectors at the modulator, see diagram 14.14.
Remove the modulator, secured with two screws.
Discard the gasket and fit the new one supplied with the modulator.
Light, check and adjust the boiler if necessary, refer to Commissioning in the Installation Instructions.
Test joints for gas soundness with suitable leak detection fluid with the gas control knob depressed.
14.19 Automatic Bypass Valve
Before starting refer to Section 11.
Remove the case base, see diagram 10.4.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Isolate the central heating flow and return, release the water pressure and drain, refer to Section 11.3 and 11.6.
Remove the pressure automatic bypass valve by disconnecting the union nuts, see diagram 14.15.
Discard the sealing washers and use the new ones supplied.
SECURING SCREW (2)
RETAINING BRACKET (2)
GAS CONTROL VALVE
GASKET
PRESSURE GAUGE
FASCIA
Diagram 14.13
MODULATOR
7026
7247
14.20 Safety Valve
Before starting, refer to Section 11.
Remove the case base, see diagram 10.4.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Release the water pressure and drain, refer to Sections 11.3 and 11.6.
7089
SAFETY VALVE
WASHER
SCREW (2)
ELECTRICAL CONNECTOR (2)
Diagram 14.14
UNION NUTS
7035
UNION NUT
Diagram 14.12
37
AUTOMATIC BYPASS VALVE
Diagram 14.15
221679H
Page 38
Supplied By www.heating spares.co Tel. 0161 620 6677
14 Replacement of Parts
Disconnect the pressure gauge connection from the safety valve, see diagram 14.12.
Disconnect the union nuts to release the safety valve, see diagram 14.12.
Discard the sealing washers and use the new ones supplied, on assembly.
Make up water loss and pressurise the system, refer to Commissioning in the Installation Instructions.
14.21 Water Inlet Filter
Before starting refer to Section 11.
Remove the case base, see diagram 10.4.
Isolate domestic water inlet, release the domestic water pressure and drain by opening the draw off lowest tap, refer to Section
11.3 and 11.6.
Disconnect the water inlet union nut to gain access to the filter, see diagram 8.4.
Clean or renew the filter as necessary.
Discard the sealing washer and use the new one supplied, on assembly.
14.22 Pump
Before starting refer to Section 11.
Open the controls cover door. Remove the two screws securing the controls facia, see diagram 9.1.
Hinge the control fascia open.
Remove the electrical plug at the pump, see diagram 14.16.
Release the water pressure and drain, refer to Sections 11.3 and 11.6.
Disconnect the pump at the top in the combustion chamber by removing the union nut and clip, see diagram 14.16.
Rlease the union nut at the bottom of the pump, see diagram
14.16.
It may be necessary to slacken the union nut at the automatic bypass and water cock.
Remove the pump.
Discard the sealing washer from the bottom fixing.
Make sure that the flow direction arrow is pointing upward, on the pump, when fitting the pump to the lower pipework use the new sealing washer provided.
Set the flow adjuster on the pump to maximum setting. The flow rate should be controlled by means of a valve in the heating system.
Make up water loss and pressurise the system, refer to Commissioning in the Installation Instructions.
Note: Should the pump fail to work, see diagram 14.25. If all is in order but the pump still does not work, remove the screw, see diagram 14.16 then turn the pump spindle to release any temporary seizure. DO NOT HIT THE SPINDLE.
Refer to diagram 14.18.
Disconnect the domestic inlet pipe.
Remove the water flow sensor assembly.
Disconnect the electrical plug.
Unscrew the water flow sensor and remove.
Ensure sealing washers are in place when refitting.
14.24 Automatic Air Vent
Before starting refer to Section 11.
Release the water pressure and drain, refer to Sections 11.3 and 11.6.
Remove the automatic air vent, see diagram 14.17.
Discard the sealing washer and use the new one supplied, when fitting.
Slacken the small cap on the air vent. This MUST NOT be retightened.
Make up water loss and pressurise the system, refer to Commissioning in the Installation Instructions.
CLIP
SECURING SCREW (4)
PUMP ADJUSTER
PUMP
UNION NUT
7033
14.23 Flow Sensor
Before starting refer to Section 11.
Remove the case base, see diagram 10.4.
Remove the main burner, refer to Section 14.2.
221679H
PLUG
38
SPINDLE
END SCREW
Diagram 14.16
Page 39
Supplied By www.heating spares.co Tel. 0161 620 6677
14 Replacement of Parts
14.25 Air Pressure Switch
Before starting refer to Section 11.
Disconnect the electrical connectors at the microswitch, see diagram 14.19.
Disconnect the air pressure tubes.
Remove pressure switch see diagram 14.19.
14.26 Heat Exchanger
Before starting refer to Section 11.
Release the water pressure and drain the domestic hot water and central heating, refer to Sections 11.3 and 11.6.
Remove the fan from the flue collector, refer to Section 14.1.
Remove the flue collector, secured with two screws, see diagram
14.2.
Remove the combustion chamber cover, see diagram 14.1.
Remove the main burner, refer to Section 14.2.
Remove the automatic air vent, see diagram 14.17.
If renewing the heat exchanger, transfer the air vent to the new one, using the new sealing washers supplied.
Disconnect the union nuts of the heat exchanger to remove it. Take care there may be some water retained in the heat exchanger.
Discard the sealing washers and use the new ones supplied, upon assembly.
Locate the raised location tabs on the combustion chamber sides into the slots on the heat exchanger, when fitting.
Make sure that the main burner is located on the main injector and is horizontal, the tips of the rear most blade under the two burner guides.
The combustion chamber front panel should be fitted loosely, then the flue collector also fitted loosely, ensuring that it is seated correctly on the heat exchanger and over the top edge of the front panel.
Locate the fan into the flue elbow and the clip at the rear, then secure with the two screws.
7246
UNION NUT
CONNECTOR
WATER FLOW SENSOR
UNION NUT
UNION NUT
LOCATION SLOT
CAP
AUTOMATIC AIR VENT
SEALING WASHER
UNION (4)
Diagram 14.17
7248
39
AIR PRESSURE TUBES
WHITE
SECURING SCREW (2)
ELECTRICAL CONNECTION (3)
Diagram 14.18
RED
7245
AIR PRESSURE SWITCH
Diagram 14.19
221679H
Page 40
Supplied By www.heating spares.co Tel. 0161 620 6677
14 Replacement of Parts
Connect the cables, the polarity of the two connectors is not important.
Tighten the screws evenly to secure the flue collector and combustion chamber front panel.
Make up water loss and pressurise the system, refer to Commissioning in the Installation Instructions.
COMBUSTION CHAMBER FRONT PANEL
FRONT INSULATION
14.27 Combustion Chamber Insulation
Before starting refer to Section 11.
Remove the combustion chamber front panel, secured with four screws and a wing nut.
Remove the front insulation panel, secured with a clip, see diagram 14.20.
Slide out both side insulation pieces.
Pull the lower rear insulation forwards, then slide the upper rear insulation down from behind the heat exchanger.
To fit the flue collector, combustion chamber front panel and fan, refer to Section 14.1.
14.28 Expansion Vessel
Renewal of the expansion vessel requires the boiler to be removed from the wall. As an alternative, a separate expansion vessel of the same specification may be connected as close as possible to the boiler, leaving the original in position, refer to the Installation Instructions.
Remove the outer case front, side panels and inner case front, refer to Sections 11.4 and 11.5.
Release the water pressure and drain the domestic hot water and central heating, refer to Section 11.3 and 11.6.
Disconnect the boiler water connection union nuts at the front of the isolating valves, see diagram 8.4.
Disconnect the gas service cock union.
Disconnect the safety valve discharge pipe from the boiler.
Disconnect the mains supply cable at the connector block on the back of the controls fascia.
Remove the two screws at the service cock bracket. Pull the boiler from the isolating valves. Unhook the boiler at the top, easing the boiler from the flue outlet and lift off.
Carefully lay the boiler down on its side for access to the expansion vessel.
Disconnect the union nut connection, see diagram 14.21 and discard the sealing washer for the new one supplied.
Remove the expansion vessel, secured with three clamping screws.
Connect the union nut, when fitting the expansion vessel, before clamping it.
2268 S
CLIP
SIDE INSULATION PIECES
LOWER REAR INSULATION
221679H
40
UPPER REAR INSULATION
Diagram 14.20
Page 41
Supplied By www.heating spares.co Tel. 0161 620 6677
14 Replacement of Parts
14.29 Mini Expansion Vessel (If fitted)
Remove the mini-expansion vessel.
When refitting use the new sealing washer supplied.
14.30 Viewing Window (Combustion Chamber)
Remove outer case front as section 11.4.
Remove the viewing window, secured with two screws. When fitting a new window use the gasket provided, see diagram
14.22.
14.31 Viewing Window (Inner Case Front)
Remove the old self adhesive aluminium foil gasket and the old mica window. Replace with a new mica window. Peel off the backing paper and secure with new self adhesive aluminium foil gasket, see diagram 14.23. Ensure no air bubbles are trapped underneath the foil.
Important
Make sure that the mica window fully covers the opening and that the hole in the aluminium foil gasket is centred over opening.
14.32 Inner Case Front Seal
Remove outer case front as section 11.4.
Remove the old seal, clean out the old adhesive.
Glue the new seal into place, making sure that there are no breaks in it..
GASKET
GLASS
FRAME
SECURING SCREW (2)
OPENING (BOILER INNER CASE FRONT)
7002
Diagram 14.22
7886
14.33 Clock/Timer - if fitted
Before starting refer to Section 11.
Remove the two screws securing the controls cover door and controls facia, see diagram 9.1.
Hinge the assembly open.
Remove the clock-timer cover, see diagram 11.2.
ELECTRO/MECHANICAL and DIGITAL clock/timer - Release securing screws, see diagram 14.24.
Disconnect electrical cables, remove the clock/timer, see diagram 14.24.
SECURING SCREW (3)
7400
SELF ADHESIVE ALUMINIUM FOIL GASKET
7005
MICA
PEEL OFF BACKING PAPER
Diagram 14.23
ELECTRICAL CONNECTION (4)
SECURING SCREW (4)
CLOCK / TIMER
EXPANSION VESSEL
UNION NUT
Diagram 14.21
41
L
N
PLUG
Diagram 14.24
221679H
Page 42
Supplied By www.heating spares.co Tel. 0161 620 6677
14 Replacement of Parts
w- WHITE b- BLUE bk- BLACK br - BROWN g/y- GREEN/
YELLOW
BOILER OVERHEAT CUT-OFF
p
gg
ELECTRODE
PIEZO
g/y
KEY
g- GREY or- ORANGE r- RED y- YELLOW p- PURPLE v- VIOLET
GAS CONTROL VALVE
C N/C N/O
PUMP
C
v
g
WATER FLOW
PLUG
N/C
N/O
r
7683
b
rr
THERMISTOR (DOMESTIC HOT WATER)
WATER PRESSURE SWITCH
C1 N/O4 N/C2
FAN
b
br
p
p
bk
g w
bg
br
FAN RESISTOR
br
y
g/y
THERMISTOR (CENTRAL HEATING)
or
or
230V-50Hz
PERMANENT
MAINS SUPPLY
FUSED AT 3A
1
r
2
E N L
AIR PRESSURE SWITCH
NOTE 1
bk w
CHASSIS EARTH G/Y
rr
PLUG
230V TRANSFORMER
NOTE
1 Red link to be removed when external roomstat is used. 2 Plug C/W link to be removed when clock timer is used. (The removed plug to be left inside the clock timer cover.)
PLUG
r
br
br
X3 X5b X5a X6
X4
FUSED
AT 2A
X2
y
orbr
or
or
b
CONTROL BOARD
X1
FUSED
AT 3.15A
CLOCK TIMER
NOTE 2
br
br
MAINS SWITCH
g/y
CHASSIS EARTH G/Y
p
PLUG
ROOM STAT
r
221679H
42
Diagram 14.25
Page 43
Supplied By www.heating spares.co Tel. 0161 620 6677
15 Spare Parts
15.1 Part Identification
The key number in diagram 15.1 and the first column of the list will help identify the spare part.
15.2 Ordering
When ordering any spare part, please quote the part number and the description from the list together with the model name and serial number information from the data label.
The data label is positioned on the inner case front, see diagram
8.2 Installation Instructions.
Key No. Part No. Description G.C. No.
1 457412 Fan assembly E26742
2 205766 Main injector assembly E26740
3 203433 Pilot burner 379485
4 202627 Spark electrode 278131
5 203518 Pilot injector 381656
6 202435 Thermocouple 378204
7 801183 Boiler overheat cut-off assembly E27356
8 202529 Domestic hot water limit control *****
9 202712 Piezo unit E26688
10 204546 Pressure gauge assembly E26683
11 227067 Control board (inc 16,17) *****
12 202810 Transformer E26700
13 801169 Gas Control valve assembly E26726
14 227003 Thermistor Domestic Hot Water *****
15 227002 Flow Sensor E04063
16 202226 Fuse 2 type T2A x 20mm 278136
17 202240 Fuse 1 type 3.15ATx 20mm 278414
18 227097 Air Pressure switch E26707
19 227083 Fan Resistor *****
20 457068 Low Water Pressure Switch E26723
21 227004 Thermistor Central Heating E26743
22 800153 Automatic Air Vent (inc seal) 313285
43
221679H
Page 44
Supplied By www.heating spares.co Tel. 0161 620 6677
15 Spare Parts
20
18
1
13
9
7
16
19
8
21
17
14
7267
22
3
12
6
5
4
10
Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.
11
2
15
Diagram 15.1
221679H
44
Loading...