Glow-worm Clearly Solar System Hydraulics User Manual

Clearly Solar
Installation and Servicing
System Hydraulics
including
Solar Pump Station
and Accessories
www.glow-worm.co.uk
1
Guarantee Registration
Glow-worm products are manufactured to the very highest standard so we are pleased to offer our
customers a Comprehensive Guarantee.
This product is guaranteed for 24 months from the date of installation or 30 months from the date
of manufacture, whichever is the shorter, for parts and labour.
The second year of the guarantee, from the beginning of the 13th month onwards after installation
or manufacture, is conditional upon the product having been serviced by a competent person
(i.e. clear skies registered engineer), in accordance with the manufacturer’s recommendations.
We strongly recommend regular servicing of your product, but where the condition is not met, any
chargeable spare parts or components issued within the applicable guarantee period still benet
from a 12 month warranty from the date of issue by the manufacturer.
The “Benchmark” Installation, Commissioning and Service Record must be completed on
installation and kept up to date.
We recommend you complete and return as soon as possible your guarantee registration card.
If your guarantee registration card is missing you can obtain a copy or record your registration by
telephoning the Glow-worm Customer Service number 01773 596510.
Customer Service:
01773 596510
Technical Helpline:
01773 828300
General and Sales enquiries:
Tel. 01773 824639
Fax: 01773 820569
To register your Glow-worm product call:
0800 0732142
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference. Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme. Visit www.centralheating.co.uk for more information.
2
These instructions consist of, Installation, Servicing, Fault Finding. The instructions
are an integral part of the product and must be handed to the user on completion of the
installation.
CONTENTS DESCRIPTION SECTION PAGE
Warnings 4 Important Information 4
INTRODUCTION
Statutory Requirements 5 Notes on the Documentation 6 Safety Instructions 6
System Specications 1 7 Product Specications 2 8 Component Specications 3 9
INSTALLATION
Installation 4 11 Commissioning 5 16 Commissioning Checklist 6 18 Commissioning Data 6 19
MAINTENANCE
Inspection and Maintenance 7 21 Fault Finding 8 22 Solar Fluid Safety Data 9 25
3
WARNINGS
SAFETY
The system must be installed by a competent person, who is responsible for adhering to
the existing standards and regulations.
ALTERATIONS
Under no circumstances should you ever attempt to make alterations to these
components or any other part of the system
SEALED COMPONENTS
Under no circumstances must the user interfere with or adjust sealed parts.
Important Information
Installation and Use Regulations
In your own interests and that of safety, it is the LAW that this product is installed by a competent person in accordance with the current issue of these regulations.
Local authority planning permission may be required for the
installation. The local authority should be notied.
Control of Substances Hazardous to Health
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health.
The adhesives and sealants used in this product are cured and give no known hazard in this state.
Solar uid safety data, see section 9.
Manual Handling
With regards to the “Manual Handling Operations, 1992 Regulations”, the appliance exceeds the recommended weight for a one man lift, refer to section 9 for more information.
Electrical Supply
The product MUST be earthed.
All system components shall be of an approved type and all wiring to current I.E.E. wiring regulations.
External wiring must be correctly earthed, polarised and in accordance with the relevant standards.
In GB, this is BS 7671.
In IE, this is the current edition of ETCI rules.
The product MUST be connected to a permanent 230V ac, 50Hz supply.
CE Mark
The CE mark on this product indicates that it complies with the basic requirements of the applicable directives as stated on the data badge.
“Benchmark scheme”
Glow-worm support the Benchmark initiative. It is very important that the service record is completed by the installation engineer and handed over to the user.
Testing and Certification
This product is tested and certicated for safety and
performance. It is, therefore, important that no alteration is made to the product, without permission, in writing, by Glow­worm.
Any alteration not approved by Glow-worm, could invalidate
the certication, warranty and may also infringe the current
issue of the statutory requirements.
4
Statutory Requirements
IMPORTANT
Where no British Standards exists, materials and equipment
should be t for their purpose and of suitable quality and
workmanship.
The installation of this product must be carried out by a competent person in accordance the rules in force in the countries of destination.
Manufacturer’s instructions must not be taken as overriding statutory requirements.
Statutory Requirements
In GB, the installation of the product must be carried out by a competent person as described in the following regulations:
The manufacturer’s instructions supplied.
The appropriate Buildings Regulations either The Building Regulations, The Building Regulations (Scotland),The Building Regulations (Northern Ireland).
The Water Fittings Regulations or Water byelaws in Scotland.
The Health and Safety at Work Act, Control of Substances Hazardous to Health (COSHH).
The Current I.E.E. Wiring Regulations.
Where no specic instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent person and installed in accordance with the current edition
of I.S.813 “Domestic Gas Installations”, the current Building Regulations and reference should be made to the current ETCI rules for Electrical Installation.
GB: the following Codes of Practice apply:
BS4814, BS6798, BS5440 Part 1 and 2, BS5546 Part 1, BS5449, BS6891, BS6700, BS7074 Part 1 and 2, BS7593, BS7671.
IE: I.S.813, BS5546, BS 5449, BS 7074, BS 7593.
Solar system in general
EN ISO 9488 Thermal solar system and components,
terminology (ISO/DIS 9488; 1995)
EN 12975-1 Thermal solar systems and components; Collectors, Part 1: General requirements
EN 12975-2 Thermal solar systems and components; Collectors; Part 2: Test methods
ENV 1991-2-3 Eurocode 1 – Basis of design and actions on structures, Part 2–3: Actions on structures - Snow loads
EN 12976-1 Thermal solar systems and components; Factory made systems - Part 1: General requirements
EN 12976-2 Thermal solar systems and components; Factory made systems - Part 2: Testing methods
ENV 12977-1 Thermal solar systems and components; Custom built systems, Part 1: General requirements
ENV 12977-2 Thermal solar systems and components; Factory made systems, Part 2: Testing methods
ISO 9459-1: 1993 Solar heating – Domestic water heating systems – Part 1: Performance rating procedure using indoor test methods
ISO/TR 10217 Solar energy – Water heating systems – Guide to material selection with regard to internal corrosion
Collectors and collector assembly
ENV 1991-2-4 Eurocode 1 – Basis of design and actions on
structures - Part 2–4: Actions on structures - Wind actions
Solar cylinder and cylinder installation
Pressure equipment directive 97/23/EC Directive of the
European Parliament and Council from 29th May, 1997 for the approximation of the laws on pressure equipment of the Member States
EN 12977-3 Thermal solar systems and components; Custom built systems, Part 3: Performance characterisation of stores for solar heating systems
EN 12897 Water supply - specication for indirectly heated
unvented (closed) storage water heaters
EN 806-1 Specications for installations inside buildings
conveying water for human consumption - Part 1: General
EN 1717 Protection against pollution of potable water installations and general requirements of devices to prevent
pollution by backow
EN 60335-2-21 Safety of household and similar electrical appliances; Part 2: Particular requirements for storage water heaters (hot water cylinders and hot water boilers) (IEC 335-
2-21: 1989 and supplements 1; 1990 and 2; 1990, modied).
Lightning protection
ENV 61024-1 Protection of structures against lightning – Part
1: General principles (IEC 1024-1: 1990; modied) BS 6651
Code of practice for protection of structures against lightning.
Regulations in Great Britain
Building Regulation, dating from 1991 (England and Wales)
Requirement G3, L1 and Regulation 7
BS 7671 Requirements for electrical installations (IEE Wiring Regulations, 16th edition)
BS 6759-1 Directive for the usage of the safety assembly for hot water cylinders.
5
Notes on the Documentation
Notes on the documentation
Your solar system is a quality product from Glow-worm.
This manual covers the solar system, excluding the cylinder and provides you with information on installation,
commissioning, maintenance and fault nding. It is
supplemented by the installation instructions of the individual components.
Observe the manuals for each individual system component in conjunction with this manual.
Look after this manual and pass it on to the user for safe keeping.
Glow-worm accepts no liability for any damage caused by failure to observe this manual.
Safety Instructions
Safety instructions
The entire solar system must always be installed and operated in accordance with recognised technical standards.
IMPORTANT: Risk of falling! Make sure you adhere to the valid work protection regulations, in particular when working on the roof. Make absolutely sure you wear anti-fall devices whenever there is a risk of falling. (We recommend Glow­worm fall protection systems, item no. 0020054985.) Observe the accident prevention regulations of the trade associations.
IMPORTANT: Risk of being burned or scalded by hot components! Install and replace collectors or collector parts on very cloudy days. Perform installation work on sunny days only in the morning or evening or with the collector covered.
IMPORTANT: Risk of being burned or scalded by hot solar uid or components! Fill and ush the solar system when the collectors are cold. Cover the collectors while doing so.
IMPORTANT: Risk of being burned or scalded by escaping hot steam! Steam can escape from the expansion relief valve of the solar pump unit if the system is shut down. To avoid injuries, you must connect the expansion relief valve to a collecting container with a hose line.
Other applicable documents
Collector installation instructions.
System hydraulic installation instructions.
System electrical installation instructions including Fluropro.
System user instructions including Fluropro.
Installation and user instructions for the boiler.
Installation instructions for all sub components and accessories used. Warranty card.
Please observe the safety instructions in this manual when installing this solar system.
IMPORTANT: A thermostatic mixing valve must be tted to
the outlet of the cylinder and can be adjusted to the desired domestic hot water temperature by an installation or service engineer. Otherwise there is a risk of scalding as the cylinder outlet temperature at the taps could be up to 85°C.
IMPORTANT: Risk of being burned or scalded by escaping hot steam! Steam can escape from unblocked automatic bleeders if the system is shut down. Therefore block all automatic bleeders after bleeding.
We recommend using the automatic air separator system supplied as part of Glow-worm optional pipework kit. It works fully automatically and does not need to be subsequently blocked. It must be installed in an area however, in which no steam can enter, preferably in the return pipe nearby the solar cylinder.
6
1 System Specications
1.1 Intended use
The solar system is used for the solar-supported supply of DHW.
Any other use is considered to be improper. The manufacturer / supplier is not liable for any resulting damage. The user alone bears the risk.
Intended use includes the observance of the system description and all other applicable documents, as well as adherence to the maintenance and inspection conditions.
IMPORTANT: We accept no liability for any damage or injuries caused by failure to observe this manual.
At the end of this manual is a commissioning protocol, which
should be lled in by the installer and/or commissioning
engineer and handed over to the user.
1.2 Design and function of the solar system
The solar system consists of four main components:
The collectors, which absorb the solar radiation and utilise it.
The solar control, which monitors, displays and controls all functions of the system.
The solar pump unit, which transports the solar heat.
The solar cylinder.
The solar collector transforms solar energy into heat and
transfers the heat energy to a frost-protected solar uid.
The solar pump of the solar pump unit ensures the heat is transported from the collector to the twin coil solar cylinder via a pipe system. The solar pump unit is controlled by the solar control.
The solar control switches the solar pump on or off as soon as the difference in temperature between the collector and solar cylinder falls below or exceeds the preset value. If the
solar energy is insufcient, the control system switches on the
boiler so that the upper third of the cylinder is reheated to the set value for the domestic hot water temperature. In addition the solar cylinder can be reheated by the immersion heater installed by the manufacturer.
The solar expansion vessel compensates pressure
uctuations in the solar circuit.
On days on which the solar radiation is insufcient to heat the
DHW in the cylinder, the stored water must be reheated by a heating system. This can be done with boilers or electrically with an immersion heater.
The optional protection vessel protects the expansion vessel from increased temperatures in the solar circuit. We recommend installing a protection vessel.
Local authority planning permission may be required for
the installation. The local authority should be notied
about the intended installation.
The solar system is a closed system and must be bled carefully. We recommend the automatic air separator system for this purpose (item no. 0020054969). It works fully automatically and does not need to be subsequently blocked.
The automatic air separator system must be installed in an area in which no steam can enter, preferably in the return pipe between the solar pump unit and the solar cylinder.
7
2 Product Specications
Solar Pump Unit
Flow
Return
14162
Clearly Solar Collector
Protection Vessel
Solar Expansion Vessel
Automatic Air
Separator System
Boiler
Flow Return
DHW
2 Port Valve
M
Flurocyl
Immersion Heater
Drinking Water Expansion Vessel
M
2 Port Valve
2.1 Diagramatic view of the system installation
Refer to diagram 2.1
Diagram 2.1
8
3 Component Specications
358
120
Ø 22
Ø 22
Ø 22
Ø 22
Ø 22
Ø 22
250
1
5
6
2
3
4
CONTAINER
SOLAR EXPANSION VESSEL
7
Solar Pump Station part no. 0020054961
14829
Item Qty. Description
1 1 Flow tube with isolating valve with integrated
gravity brake and temperature display
2 1 Return tube with isolating valve with
integrated gravity brake and temperature
display, ow rate meter with ll/vent valve,
circulating pump
3 1 Safety valve with pressure gauge, ll valve
and corrugated tube DN16 including wall bracket for solar expansion vessel
4 1 Wall bracket for expansion vessel with tting
5 1 Wall bracket for solar pump station
6 4
7 2 C-clips
22mm Compression nuts
22mm Brass olives
4
22-18mm Reducers (discard)
4
Solar Expansion Vessel
Diagram 3.1
18 litre Supplied with 1 collector pack
25 litre Supplied with 2 collector packs
35 litre Supplied with 3 collector packs
3.1 Solar pump station
Refer to diagram 3.1 for contents and description.
The solar pump unit is equipped with a three-speed solar pump for the optimum adaptation of the required circulating volume and the pump capacity in the solar circuit.
Select the pump capacity, depending on the solar system (e.g. collector surface, pipe diameter, length of the solar circuit), so
that the actual ow rate is slightly higher than the nominal ow rate. The ow rate meter is used for ne adjustment of the ow rate.
The solar pump unit is delivered with a water control pack, consisting of an expansion relief valve and a pressure gauge.
The ow rate meter installed in the return pipe is an essential
component of the solar system. To achieve optimum heat
transfer, you must achieve a certain ow rate, refer to section
5.2.
Upper deviations are not as serious as lower deviations.
Make the rough adjustments with the solar pump rst. You can make the ne adjustments with the adjustment valve of the ow rate meter. You can view the set value on the display of the ow rate meter.
The ow rate meter has a ll/vent valve for lling and draining
the solar circuit.
NOTE: Do not under any circumstances set the ow rate below the calculated ow rate. The collector efciency will be
considerably reduced.
If you would like to use the solar exible pipework (DN16
0020054964) from the pump station to the cylinder, please
order an additional two ttings packs, part No. 0020054965, these contain the relevant ttings for this application.
9
3 Component Specications
3.2 Solar expansion vessel
The solar expansion vessel, is used to equalise the pressure
while the pressure relief valve blows off the solar uid into
the collecting container via the pressure release pipe if the operating pressure of 6 bar is exceeded.
The size of the solar expansion vessel is based on the expansion volume of the solar system.
The expansion vessel not only accommodates the expansion
volume of the solar uid, but also the entire volume of the
collectors in the event of a shutdown. The total volume of the solar system is the total of the individual values of the collector, heat exchanger volume and the volume of the pipeline.
The admission pressure of the solar expansion vessel can be set between 0.5 and 4.0 bar.
Component Volume (l)
Flurocyl 200 l heat exchanger solar circuit 3.04
Flurocyl 250 l heat exchanger solar circuit 3.04
Flurocyl 300 l heat exchanger solar circuit 4.14
Flurocyl 200 l heat exchanger reheating circuit 3.7
Flurocyl 250 l heat exchanger reheating circuit 3.7
Flurocyl 300 l heat exchanger reheating circuit 3.7
Solar pump unit 0.9
Vertical solar thermal at plate collector 1.85
Horizontal solar thermal at plate collector 2.16
Protection vessel 5.0
Table 3.2 Volume of individual circuits
3.3 Thermal cut out of the solar pump
The solar pump must be protected by its own thermal cut out (TCO) which must be mounted on the solar cylinder (pre­assembled at the factory on the Glow-worm Flurocyl cylinder). The power supply to the pump MUST be interrupted at cylinder temperatures higher than 90°C.
3.4 Solar fluid
This information applies to Glow-worm solar uid (20 l
canister: item no. 0020054968).
Glow-worm solar uid is a ready-mixed antifreeze and
anticorrosive, consisting of approximately 45% propylene glycol with anti-corrosion inhibitors and 55% water. It is resistant to high temperatures.
Furthermore the solar uid has a high thermal capacity.
The inhibitors provide reliable corrosion prevention when using different types of metal (mixed installations).
NOTE: Do not use any other anti-freeze or inhibitors with the
collector. Only Glow-worm solar uid is approved.
IMPORTANT: Risk of damage! Glow-worm solar uid is ready
mixed. You may not under any circumstances mix it with water
or other uids. Otherwise it will become ineffective as an
antifreeze or anticorrosive, resulting in damage to collectors or other parts of the system.
Glow-worm solar uid is innitely durable in hermetically
sealed containers.
Skin contact is normally not dangerous. Eye contact only causes minor irritations, you should nevertheless immediately wash your eyes.
Observe the safety data sheet, see section 9.
3.5 Protection of the solar circuit against frost and corrosion
To protect the solar system reliably against frost in winter, the
entire solar circuit must be lled 100% with solar uid.
NOTE: You can achieve frost resistance of about -28°C by
lling the solar system with Glow-worm solar uid. No damage
is caused by frost even at outside temperatures below -28°C, since the expansive effect of the water is reduced. Check the
antifreeze effect after lling the system and then once a year.
To check the solar uid; refer to the operating manual of the solar uid tester (item no. 0020054984).
10
4 Installation
Make sure that you have all the components required, see diagram 4.1, 4.2 and tables 4.1 and 4.2, below.
4.1 Recommended installation sequence
Assuming that the cylinder and collectors are tted with
the exception of the solar system hydraulics and wiring, it
is recommended that the solar pump station is now tted
followed by the solar circuit pipework.
The cylinder and collectors must be installed in accordance with the separate installation instructions.
Proceed with the installation as described in the following sections and shown in the diagrams 4.3 and 4.4 .
Item Description
1 Solar collector panel
2 On-roof, In-roof or Flat roof kit
3 Solar pump unit
4 Fluropro solar control
5 Roof bracket set, concrete tiles
6 Solar uid (20 litre)
7 Automatic air separator
8 Expansion vessel
9 Protection vessel
Table 4.1 Typical solar items
14172
1
2
4
3
5
9
6
Item Description
1 Single insulated tube DN16 15m x 2
2 Fittings pack for DN16 tube
Table 4.2 Optional pipework kit
8
Solar set items
1
Optional pipework kit items
7
Diagram 4.1
14351
2
Diagram 4.2
11
4 Installation
14213
SOLAR COLLECTOR
THERMOSTAT MIXER
BOILER
MOTORISED 2 PORT VALVE
SOLAR COLLECTOR CIRCUIT PUMP
MOTORISED 2 PORT VALVE
AUTO AIR
SEPARATOR
HOT WATER CONNECTION
FLOW
RETURN
FLOW
RETURN
LEGIONNELLA LOOP (optional)
PUMP
TEMPERATURE AND PRESSURE RELIEF VALVE (95 °C, 7 BAR)
EXPANSION VESSEL
TUNDISH
EXPANSION RELIEF VALVE (6.0 BAR)
PRESSURE LIMITING VALVE (3.5 BAR) WITH LINE STRAINER
COLD WATER SUPPLY
12
FLUROCYL DRAIN VALVE
Diagram 4.3
4 Installation
Collector arrays setup for East / West orientation
14212
N
SOLAR COLLECTOR
SOLAR COLLECTOR CIRCUIT PUMP
HOT WATER CONNECTION
SOLAR COLLECTOR
LEGIONNELLA LOOP (optional)
W
S
THERMOSTAT MIXER
PUMP
TEMPERATURE AND PRESSURE RELIEF VALVE (95 °C, 7 BAR)
E
BOILER
MOTORISED 2 PORT VALVE
MOTORISED 2 PORT VALVE
AUTO AIR
SEPARATOR
FLOW
RETURN
FLOW
RETURN
13
EXPANSION VESSEL
EXPANSION RELIEF VALVE (6.0 BAR)
TUNDISH
FLUROCYL DRAIN VALVE
COLD WATER SUPPLY
PRESSURE LIMITING VALVE (3.5 BAR) WITH LINE STRAINER
Diagram 4.4
4 Installation
4.2 Fitting the solar pump station (wall-mounted installation)
Fit the wall bracket and the pump station ow and return
assemblies.
Secure the assemblies in the wall bracket using the two C-
clips. Put them onto the ow and return assemblies below the
wall bracket.
4.3 Pressure relief valve and expansion vessel
Fit the pressure relief valve assembly to the connection nozzle in the pump station return tube assembly.
IMPORTANT: Loss of solar uid! Install a discharge pipe from
the pressure relief valve outlet to a container to ensure that
any hot solar uid escaping from the system is contained.
The solar uid container is intended as a collecting container when the system is lled and the container is empty. Connect
a discharge pipe from the relief valve outlet to the intended location for the container.
Mount the expansion vessel wall bracket using screws and
plugs. Screw the ange and the expansion vessel to the wall
bracket.
The expansion vessel must be mounted vertically and the ow
from the system must enter the vessel from the top. To avoid
accidental spillage or access by children to the uid, best
practice is to take the discharge pipe right to the bottom of (but not touching) the container.
The empty solar uid container is recommended, as re­using it helps to reduce landll, the contents of the container
are visible (you must be able to see if the safety valve has discharged) and offers a practical solution. However, if preferred, an alternative vessel may be used, provided it is of adequate size, the contents are visible and it is not fully sealed.
4.4 Notes on the solar circuit pipework
When installing solar circuit pipework between the collector array and the cylinder, carefully consider the location of the pump station and the requirement for an automatic air separator. The Glow-worm solar system is a closed hydraulic system in which heat can only be transferred to the cylinder
by means of special heat transfer uid in the solar system.
Observe the following points to ensure perfect operation with maximum energy utilisation:
Bleed the system completely during commissioning and servicing since air in the system has a considerable effect on
the efciency.
The pipe diameters should not be too large, otherwise the
the ow in the solar system will slow down, reducing the efciency.
Lay all system components in such a way to ensure an even
ow at the required nominal ow rate.
Provide sufcient thermal insulation of the pipes to prevent
excessive heat loss. The insulation must withstand temperatures up to 150°C. Select weather and UV resistant insulation which is “bird peck proof“ especially for pipes laid outside.
When using compression ttings, you must consult the manufacturer of these ttings to check their suitability for solar
systems.
Use compression ttings only if temperatures of up to 200°C
are allowed by the manufacturer.
IMPORTANT: Use hard solder only, soft solder is NOT suitable.
Do not use any plastic pipes.
Flexible stainless steel pipes supplied by Glow-worm or copper pipes should be used for the solar circuit.
Optional Glow-worm exible pipes for the connection of the
collectors to the solar pump unit.
0020054994: 2 in 1 exible pipe DN 16 x 15 m
0020054964: single exible pipe DN 16 x 15 m
Two single exible pipes DN 16 x 15 m are available as part
of the Glow-worm optional pipework kit. Instructions for the
connection of these exible pipes can be found in separate
installation instructions.
Due to the occasionally high temperatures of the solar uid,
plastic pipes must not be used for the solar circuit. Copper pipes must be joined using hard soldering or compression
ttings. Soft soldering is NOT suitable.
Teon tape can be used on pipework below the Solar Pump
Station.
IMPORTANT: Earth the solar circuit! The solar pipework must be earthed in accordance with the requirements of BS 7671 IEE Wiring Regulations. Wiring protection should be provided if there is high risk of lightning strikes. The electronics in the solar system, heating system or in the house could otherwise be destroyed if they were to be hit by lightning. Connect the collectors to an existing lightning protection on the house.
IMPORTANT: Risk of damage to the collectors due to excessive pressure. The installation of a motorised 2 port valve in the pipes of the solar system is not allowed, since the
safety devices in the solar circuit could be overridden by it.
The right selection of the pipe diameters plays a signicant role in terms of maximum efciency of the solar system.
To keep the pressure loss in the solar circuit to a minimum,
the ow velocity in the copper pipe should not be higher than
1.5 m/s.
A nominal ow rate of 0.66 l/min per net m
required by the collectors to achieve optimum heat transfer.
Another decisive criteria for the optimum operation of your solar system is the speed of the solar pump. The pump must
be able to deliver more than the nominal ow rate at the specied operating pressure. The selection of the required
pump speed depends on the installed system. Reference value for the pump selection can be found in section 5.2.
Connections to solar pump station
IMPORTANT: An air separator is required - refer to diagram
4.5.
Using the compression ttings supplied with the pump station, connect the pump station ‘ow’ assembly to the collector ow
pipe and the pump station ‘return’ assembly to the collector return pipe. IMPORTANT: ensure the collector pipes are connected correctly - the pump station ‘return’ assembly includes the pump.
Use the ttings included to connect to 22mm copper pipes.
Again using the compression ttings supplied with the pump station, connect the pump station ‘ow’ assembly to the cylinder ‘solar circuit ow’ connection then the pump station
‘return’ assembly to the cylinder ‘solar circuit return’.
2
collector surface is
14
4 Installation
IMPORTANT: Ensure the cylinder pipes are connected
correctly - the pump station return assembly includes the pump.
4.5 Automatic air separator
Air in the system impairs the efciency of the solar system
considerably. Install an automatic air separator in the return of the solar circuit, between the cylinder and solar pump station. High temperature vapour is unlikely in this area. However, check with the manufacturer that the device is suitable for domestic solar system applications.
A suitable and effective air separator is supplied in all solar packs or separately (item no. 0020054969). This is recommended.
The air separator system works fully automatically and does not need to be isolated.
The system must be bled whenever it is lled or subjected to
maintenance. Bleeding is performed constantly by means of the automatic air separator system as long as the solar pump is in operation.
Fit the protection vessel as shown in diagram 4.6.
The protection vessel must be mounted vertically. The ow
from the safety group must enter the vessel at the upper connection.
14183
14236
Diagram 4.5
Flexpipe
Protection Vessel
3/4” Adapter Fitting
Wall Bracket
Solar Expansion
Vessel
Diagram 4.6
15
5 Commissioning
0,5
1
2
3
0,5
1
2
3
4
5
6
4
5
6
L/min
L/min
You must adhere to the following procedure for the commissioning of the total system:
Use only Glow-worm solar uid (item no. 0020054968) for pressure tests and for ushing and lling the solar circuit.
5.1 Flushing and filling the solar circuit
Glow-worm recommends using the Glow-worm lling pump, part no. 0020054986, to ush and ll the solar circuit. Observe the separate user manual when using the Glow-worm lling
pump.
Expansion vessel admission pressure
During the commissioning, the gas side admission pressure p
of the expansion vessel must be adjusted to the equipment
v
height whilst disconnected. The static pressure p corresponds, to a certain extent, to the static height h between the collector array and the expansion vessel.
10m static height correspond to approx. 1 bar.
p
= p
= h x 0.1 but not less than 1.5 bar.
v
stat
NOTE: A deviation from the optimum admission or lling
pressure always results in a reduction of the expansion vessel's effective volume. This can cause operational malfunctions.
Flushing is performed from the solar pump station to the cylinder via the collector.
A self-priming pump with a pressure of 2 to 3 bar is required
to ll the solar circuit.
Collector circuit lling pressure
The lling pressure Pa should be approx. 0.5 bar over the
static pressure Pstat.
Pa = h x 0.1 + 0.5 bar but not less than 2 bar.
stat
EXAMPLE: The installed (net) collector surface area for Clearly Solar collectors is 2.35 m2. Multiplied with the value
for the specic ow rate of 0.66 l/m2 • min, it results in a calculated ow rate, which should be indicated by the ow
rate meter, see diagram 5.1.
Select the next pump speed if the calculated ow rate is not achieved on the ow rate meter. Switch to a lower speed if it is exceeded. If the ow rate cannot be achieved even at the
highest pump speed, check whether it is possible to use fewer collectors in series reverting to a combination of series and parallel connections (eg 2 collectors in series in parallel with an additional 2 collectors in series).
Use an Allen key to nely adjust the ow rate at the
adjustment valve, see diagram 5.1.
The adjusted ow rate can be viewed on the display, see
diagram 5.1.
Table 5.1 provides reference values for possible pump speeds depending on the collector connection and pipe length and cross-section.
The ow rate can be used to calculate and display the gain. To make an accurate calculation, the ow rate must be entered into the Fluropro solar control. You can nd
further information in the separate system wiring instructions including the Fluropro solar control.
The pump speed is used to achieve a particular ow rate in the collector array. The nal ow rate should not be signicantly above or below the calculated value. Up to 10%
lower solar gain or unnecessarily high power consumption of the pump could occur.
5.2 Setting the flow rate / pump speed
The 3-speed circulating pump can be ne-tuned to adjust the ow rate to the collector's performance.
NOTE: We recommend a value of 0.66 l/min per m2 collector surface area.
This is how to do it:
Use Table 5.1 to calculate the ow rate to be set by
multiplying the installed collector surface area with the value
of 0.66 l/m2 • min.
Set the pump speed to roughly set the ow rate as follows:-
1,1 l/min
Let the pump run rst at the lowest speed (minimum power
consumption).
Check whether the calculated value is achieved on the ow
rate meter.
Clearly Solar, solar collector panel Flow rate
Flow Rate Display
Minimum cross-section of the copper pipe in the
solar circuit at a total pipe length of:
Number in series l/min 20m 50m
1 1 1.55 15 15
2 2 3.1 15 15
3 3 4.65 15 15
Pump speed: Minimum (speed 1) Maximum (speed 3)
Table 5.1 Layout of pipe cross-section and pump speed depending on the collector connection
Adjustment Valve
Diagram 5.1
14168
16
5 Commissioning
5.3 Commissioning checklist
Fill in the commissioning checklist, refer to section 6.
5.4 Benchmark
GB: It is a requirement that the “Benchmark” Installation,
Commissioning and Service Record is completed and left with the user. This is supplied with the Glow-worm ‘Flurocyl’ range of cylinders.
IE: it is necessary to complete a “Declaration of Conformity” to indicate compliance to I.S.813. An example of this is given in the current edition of I.S.813.
5.5 Hand over to the householder
l Hand over all manuals to the householder. l Advise the householder to keep the manuals near to the
system. l Draw special attention to the safety instructions which the householder must follow. l Review the user instructions with the householder and answer any questions. l Show the householder how to operate the solar control, CH control and any separate DHW control. l Inform the householder that the cylinder temperature is factory set at 65°C and that the DHW temperature can be adjusted using the TMV by the installer. l Inform the householder that the immersion heater is intended as a standby device and should not be used simultaneously with the boiler to heat the cylinder. l Inform the householder that they are not permitted to change the settings made on the solar system. l Inform the householder that to ensure the continued efficient and safe operation of the solar system it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the installation conditions and usage, but in general, once a year should be enough. lInform the householder that the boiler and solar cylinder
should be serviced by a qualied engineer annually.
Leave these instructions and the “Benchmark” Installation, Commissioning and Service record document with the user.
17
6 Commissioning Checklist
1. Assembly O.K. Remarks
Roof bracket xed according to instructions?
Solar pipework connected to potential equalisation?
Roof covering rexed according to instructions after laying the roof bracket?
Roof membrane not damaged?
Pressure release pipe installed at the expansion relief valve of the solar
circuit?
Catch vessel (empty canister) placed under pressure release pipe?
Pressure release pipe installed at expansion relief valve on hot water side
and connected to waste water?
Thermostat mixer installed, temperature set and checked?
2. Commissioning O.K. Remarks
System lled with prescribed solar uid?
Solar circuit ushed with solar uid?
Line strainer cleaned after ushing the system?
System bled several times?
Solar circuit subjected to hydraulic pressure test, including leak inspection
of screw connections and soldering points?
Stufng boxes at stop valve and ll/vent valve checked for leaks (retighten union nuts if necessary)?
Temperature and pressure relief valve checked?
Stop valve for reheating source installed (normally motorised 2 port valve)?
Flow rate set according to system manual?
Pump, cylinder heat exchanger and collector bled (gravity brake blocked for
bleeding)?
Gravity brake released?
Fill/vent valve caps screwed tight?
Cylinder bled?
Heating circuit bled?
Does the system installation meet the requirements of the building
regulations?
Has the system been installed and started up in accordance with the
installation manuals of the manufacturer?
3. Control systems O.K. Remarks
Do the temperature sensors display plausible values?
Solar pump running and circulating (ow rate measuring meter)?
Solar circuit and cylinder become warm?
The temperature difference between the ow and return is a max. of 10 to 14 °C at full sunshine?
Correct hydraulic plan set
4. Instruction O.K. Remarks
The system user has been instructed as follows:
– Basic functions and operation of the solar control?
– Functions and operation of the reheating system?
– Frost protection of the system?
– Maintenance intervals?
– Manuals/documents (possibly with special circuit plan) handed over to the
user?
Table 6.1 Commissioning checklist
18
6 Commissioning Data
Information Unit Value/Detail
Benchmark no.
Registration no.
Basic acceptances
Number of persons
Additional hot water equipment Washing machine,
dishwasher etc.
Circulation Available/Not available
Circulation runtime h/d
(please tick as appropriate)
Daily hot water consumption in l/d
At a cylinder temperature of °C
Estimated solar coverage of the total hot water consumption %
Collector array performance data
Installed effective collector surface area m
Maximum power at full solar radiation kW (500–600 W/m2
2
collector)
Solar cylinder
Appliance type Vented/Unvented
Appliance designation
Capacity l
Serial number
Boiler
Appliance type
Appliance designation
Serial number
Boiler system type Open/Closed
Installation location of pressure limiting valve
System values
Hot water temperature at the nearest tap °C
Achievable maximum cylinder temperature °C
Maximum hot water temperature °C
Maximum hot water volume at maximum temperature l/min.
Boiler ow temperature °C
Operating pressure setting at pressure limiting valve bar
Charge pressure in DHW expansion vessel (check before
lling)
Charge pressure in solar expansion vessel (check before
lling)
Cold water system pressure at pressure limiting valve (cold) bar
Set ow rate l/min
Temperature difference between ow and return at full solar
radiation
Volume of solar expansion vessel l
Operating pressure at solar pump unit pressure gauge in cold condition
bar
bar
Kelvin
bar
Table 6.2 Commissioning data
19
6 Commissioning Data
Information Unit Value/Detail
Frost protection set to Density of solar uid >
1.05 g/cm3
Controller settings
Installed controller(s)/timer(s)
Manufacturer
Reheating with boiler starts at (TSP1 min. see installation
manual of solar control)?
Switch-on temperature difference: Kelvin
Switch-off temperature difference: Kelvin
Other settings
°C
Important activated functions
Name of the installer (in block letters)
Corgi ID No.
Date
Signature
Signature of the user to conrm the receipt of all manuals of
the system
Table 6.2 Commissioning data (continued)
20
7 Inspection and Maintenance
The operational reliability of the solar system may be impaired, resulting in damge to property or personal injury, if the inspections and maintenance work are not carried out.
The main maintenance work on the solar system and the
corresponding maintenance intervals are specied in table
7.1.
Maintenance Maintenance interval
Solar circuit
Check the frost protection of the solar uid (use the Glow-worm 0020054984 solar uid tester) Annually
Check the system pressure Annually
Check the pH value of the solar uid (with litmus paper, pH > 7.5) Annually
Check the solar pump function Annually
Bleed the system Annually
Check the circulating volume in the solar circuit Annually
Check the hot water thermostat mixer function Annually
Rell with solar uid if necessary Annually
Check the quantity of blow-off liquid Annually
Release the return ow preventer Annually
Check the charge pressure of the expansion vessel Annually
Collector
Visual inspection of the collector, collector fastenings and connections Annually
Check whether the brackets and collector components are clean and tted properly Annually
Check the pipe insulation for damage Annually
Solar control
Check the pump function (on/off, automatic) Annually
Check the sensor temperature display Annually
Reheating
Check the circulation pump Annually
Check the timer/time programme settings Annually
Reheating: does it deliver the desired deactivation temperature? Annually
Solar cylinder
Bleed the heat exchanger if necessary Annually
Check the connections for leaks Annually
Check the temperature and pressure relief valve Annually
Checking the expansion relief valve Annually
Table 7.1 Maintenance checklist
21
8 Fault Finding
The following tables provide information on possible malfunctions during the operation of the solar system as well as their cause and remedy.
All work on the Glow-worm solar system (installation, maintenance, repairs etc.) may be performed only by approved specialists.
IMPORTANT: Risk of serious injury or death! Never try to correct faults in the solar system yourself. Bear in mind that you risk death or serious injury if the work is performed
incorrectly. Consult an approved qualied servicing company
in the event of malfunctions.
NOTE: Only use original spare parts from Glow-worm. for the replacement of parts. We recommend making a maintenance agreement.
Malfunction Cause Remedy
Solar pump
Pump is not running although the collector is warmer than the cylinder (neither motor noises can be heard nor vibrations felt).
Pump is running, but no solar uid
is coming from the collector (pump
gets hot). Forward and return ow
temperatures are the same or the storage tank temperature not increasing at all or only slowly.
Pump goes on too late and stops running early.
Pump starts up and goes off shortly afterwards. This is repeated several times until the system runs its course. The same occurs in the evening.
The pump is making noises. 1. Air in the pump Bleed the pump.
Solar system
Clocking of the system. Incorrect position of the collector sensor. Position the collector sensor in the ow.
1. No current available. Check the power cables and fuses.
2.Temperature difference set too high or controller is not switching.
3. Maximum temperature reached.
4. Pump shaft jammed by deposits in the bearings.
5. Pump dirty. Dismantle the pump and clean it. Close
6. Pump defective. Replace the pump.
7. Flow rate set incorrectly Check the setting and adjust it if
Air is in the pipework. Check the system pressure. Operate the
1. The temperature difference between the collector and cylinder has been set too high.
2. Collector connection pieces not insulated (tube collector).
The temperature difference of the controller is too low or the pump speed is set too high. The solar radiation is not yet
sufcient to heat up the entire pipework.
2. Insufcient system pressure. Increase the system pressure.
Check the controller.
Check the temperature sensor.
Reduce the temperature difference.
Switch temporarily to max. speed or unblock the rotor, insert a screwdriver in the notch and turn it by hand.
the ow rate meter and pump ball valve.
necessary.
pump intermittently at maximum power. Open the bleeder at the pump and at the
cylinder and bleed. Bleed the back ow
prohibition. If there is no improvement, check whether there is a “u pocket” anywhere in the piping (e. g. at beam projections or at the bend of water pipes). Change the pipework or install additional air vents. If the system has already been
started up and is relled again, check
the automatic air vent: Unscrew the
protective cap and check the oater for mobility with a blunt needle. If the oater
is jammed, replace the air vent.
Reduce the temperature difference.
Insulate the collector connection pieces.
Check whether the entire pipework is fully insulated. Increase the temperature difference of the controller.
Insulate the collector sensor.
Table 8.1 Fault Finding
22
8 Fault Finding
Malfunction Cause Remedy
The pressure gauge indicates a drop in pressure.
The water pressure and amount of discharged water decreases at hot water taps.
The system is making noises. Normal in
the rst few days after lling the system.
If it occurs later, there are two possible causes:
The solar gain is unusually low. The pipe insulation is too thin or incorrect.
Solar control
Display example “NTCA Err“ or similar
(reference system wiring instructions including Fluropro solar controller)
Solar cylinder
The cylinder cools down at night. The
ow and return temperatures vary after
switching off the pump. The collector temperature is higher than the air temperature at night.
Reheating is not working. The boiler runs for a short time, goes off and then back on again. This is repeated until the cylinder is at its target temperature.
A drop in pressure is normal shortly
after lling the system, since air still
escapes from the system. If a pressure drop occurs again later on, the cause may be an air bubble, which has been subsequently released.Furthermore there
are uctuations to the pressure in normal
operation mode between 0.2 to 0.3 bar, depending on the system temperature. If the pressure drops continuously, there is a leak in the solar circuit, in particular in the collector array.
Pressure in the main cold water supply too low.
Line strainer in the pressure limiting valve dirty.
Pressure limiting valve defective. Replace the pressure limiting valve.
Blockage in the system. Unblock the blockage and replace any
1. The system pressure is too low. The pump is drawing air via the bleeder.
2. Pump power set too high. Switch to a lower speed.
The system may have been designed incorrectly.
Defective sensor (short circuit or interruption).
1. The gravity brake is blocked. 1. Check the position of the blue handle.
2. One-pipe circulation in the event of short pipe networks with low pressure loss.
1. Air in the reheating heat exchanger. Bleed the reheating heat exchanger.
2. Heat exchanger surface area too small. Compare the specications of the boiler
First check all screw connections, stufng
boxes at gate valves and threaded connections, then the soldering points. Check the collector array and replace a tube or the collector if necessary.
Inform the user and notify the water supply company.
Clean the line strainer in the pressure limiting valve and replace it if necessary.
blocked parts.
Check the system for water leaks at the expansion relief valve and temperature / pressure limiting valve.
Increase the system pressure.
Check the insulation. Check the layout of the system (collector size, shading, pipe lengths) and modify the system if necessary.
1. Check the cable connection.
2. Measure the resistance values of the disconnected sensor at known temperatures, and compare these with the manufacturer's specications.
3. Inspect the piping for damage.
2. Check the gravity brake for tightness (jammed cuttings, particles of dirt in the sealing face).
3. Do not connect the solar heat exchanger directly, rather pull the supply pipes downwards and then upwards to the collector (syphon supports the gravity brake) or install a 2-port valve, which is switched on at the same time as the pump.
Install a gravity brake (as close as possible to the cylinder).
manufacturer with those of the cylinder manufacturer. The problem may be able to be solved by a higher setting of the
ow temperature at the boiler.
Table 8.1 Fault Finding (continued)
23
8 Fault Finding
Malfunction Cause Remedy
Only cold or lukewarm water comes out of the taps.
Water ows out of the expansion relief
valve (only when heating up).
Water comes out of the temperature and pressure relief valve (only when heating up).
1. Cold and hot water connections on the cylinder have been mixed up.
2. Hot water thermostat mixer set too low. Increase the setting.
3. Solar heating insufcient; boiler does
not reheat. External control device faulty.
Air in the reheating heat exchanger
Cylinder temperature sensor defective.
Dirt on the valve seat of the expansion relief valve.
Pressure limiting valve defective. Switch off the boiler and immersion
Expansion vessel defective. Check the pressure in the expansion
Expansion relief valve defective. If the pressure is normal, replace the
Dirt on the valve seat of the temperature and pressure relief valve.
Temperature control of the boiler defective.
Cylinder temperature sensor defective. Check the cylinder temperature sensor
Two port valve defective. Check whether the two port valve is
Temperature and pressure relief valve defective.
Immersion heater defective. Check the temperature sensor of the
Turn off the cold water supply, then
let water ow out via the hot water
connection. Only a few litres of water
ow out if the connection is laid correctly.
The inlet of the hot water draw-off pipe then rests in the air space; no further emptying is possible. If the entire solar cylinder runs empty via the hot water connection, the connections have been laid incorrectly. Change the connections!
Check whether the boiler is working.
Check whether the external control device is working. Check whether the two port valve is in the hot water position. Replace the two port valve.
Bleed the reheating heat exchanger.
Check the thermal cut out and reset it. Replace the cylinder thermostat.
Check the expansion relief valve and reset it manually.
heater and check whether the pressure behind the pressure limiting valve is lower
than 3.0 bar if water ows out only when
heating up. If so, replace the pressure limiting valve.
vessel. If the pressure is insufcient,
re-establish the pressure and check whether the equalisation tank maintains the pressure.
expansion relief valve.
Check the seat of the temperature and pressure relief valve and reset it manually.
Check the temperature control of the boiler if water only comes out when reheating with the boiler. Check whether the two port valve switches to the heating position after reaching the cylinder temperature.
and the corresponding thermal cut outs and replace the temperature sensor and reset the thermal cut outs if necessary.
working and replace it if necessary.
Replace the temperature and pressure relief valve if water only comes out when heating up with the immersion heater.
immersion heater and the corresponding thermal cut out and replace the immersion heater if necessary.
Table 8.1 Fault Finding (continued)
24
9 Solar Fluid Safety Data
10.1 Safety data sheet
1 Substance/Formulation and company name
Information on the product: Trade name of the Glow-worm solar uid (item no.
0020054968)
2 Composition/Information on components
Chemical properties Watery solution of 1.2 propylene glycol with corrosion inhibitors
3 Possible risks
No particular risks known
4 First-aid measures
General notes: Remove dirty clothes.
After inhaling: Discomfort after inhaling fumes/aerosol: fresh air, help from a doctor.
After skin contact: Wash off with water and soap.
After eye contact: Wash thoroughly under running water with wide open eyes for at least 15 minutes.
After swallowing: Rinse your mouth and then drink plenty of water.
Notes for the doctor: Treatment of symptoms (decontamination, vital function), no
specic antidote known.
5 Fireghting measures
Appropriate extinguishing agents: Spray, solid extinguishing agent, alcohol-fast foam, carbon dioxide (CO
Particular hazards: Fumes which are detrimental to health. Formation of smoke/
mist. The specied substances/substance groups may be released in the event of a re.
Special protective equipment for re ghting:
Wear a breathing apparatus which is independent of the
circulating air in the event of a re.
Further details: The hazard depends on the combustible substances and
the re conditions. Polluted re water must be disposed of according to local ofcial regulations.
)
2
6 Measures to be taken if substances are released accidentally
Individual-related measures: No particular measures required.
Environmental measures: The product may not be discharged into waters without pre­treatment (biological sewage plant).
Cleaning/Collection methods: Pump out the product in the event of large quantities. Absorb
small quantities with appropriate uid bonding material.
Then dispose of them according to regulations. Rinse away splashes with plenty of water. Inform the local water authority
in the event of large quantities which could ow into the
drainage or waters.
7 Handling and storage
Handling: Good ventilation of the workplace, no other particular measures required.
Fire and explosion protection: No exceptional measures required. Cool any endangered containers with water.
Storage: Close containers tightly and store them at dry places. Do not use any galvanised containers for storage.
8 Limitation of exposure and personal protective equipment
Personal protective gear: Hand protection: chemical-resistant protective gloves (EN
374). Suitable materials even in the event of prolonged, direct contact (recommended: protection index 6, corresponding
to > 480 minutes permeation time according to EN 374): our elastomer (FKM) – 0.7 mm layer thickness. Suitable
materials for brief contact or splashes (recommended: at least
protection index 2, corresponding to > 30 minutes permeation
time according to EN 374): nitrile rubber (NBR) – 0.4 mm layer thickness. Due to the large variety of types, observe the instruction manuals of the manufacturer.
Eye protection: Safety glasses with lateral protection (framed glasses) (EN
166)
General safety and hygiene measures: Observe the usual protective measures for dealing with chemicals.
9 Physical and chemical properties
Form: uid Colour: violet
Odour: product-specic Solidication temperature: approx. -28 °C (DIN 51583) Boiling temperature: > 100 °C (ASTM D 1120)
Flash point: none Lower explosion limit: 2.6 % by vol. (details for Upper explosion limit: 12.6 % by vol. 1.2 propylene glycol) Ignition temperature: omitted vapour pressure (20 °C): 20 mbar Density (20 °C): approx. 1.030 g/cm3 (DIN 51757) Water solubility: entirely soluble Solubility (qualitative) solvent: polar solvents: soluble pH value (20 °C): 9.0 – 10.5 (ASTM D 1287) Viscosity, kinematic (20 °C): approx. 5.0 mm2/s (DIN 51562)
25
9 Solar Fluid Safety Data
10 Stability and reactivity
Substances to be avoided: Strong oxidants
Dangerous reactions: No dangerous reactions if the storage and handling regulations/notes are observed
Dangerous decomposition products: No dangerous decomposition products if the storage and handling regulations/notes are observed.
11 Toxicological information
Acute toxicity: LD50/oral/rat: > 2000 mg/kg Primary skin irritation/rabbit: not irritating. (OECD guideline 404) Primary irritation to the mucous membrane/rabbit: not irritating. (OECD guideline 405)
Additional notes: The product has not been checked. The statements have been taken from the individual components.
12 Ecological information
Ecological toxicity:
Fish toxicity: LC50 leuciscus idus (96 h): > 100 mg/l Aquatic invertebrates: EC50 (48 h): > 100 mg/l Water plants: EC50 (72 h): > 100 mg/l
Micro-organisms/effect on activated sludge:
DEV-L2 > 1000 mg/l. No disturbances to the biodegrading
activity of the activated sludge are expected in adapted biological sewage plants if discharged appropriately in low concentrations.
Assessment of aquamatic toxicity: The product has not been checked. The statements have been taken from the properties of the individual components.
Persistence and biodegradability/information on elimination: OECD 301 A test method (new version) Analysis method: DOC acceptance Degree of elimination > 70 % (28 d) Assessment: easily biodegradable.
13 Note on disposal
Disposal:
Glow-worm solar uid (item no. 0020054968) must be
disposed of at an appropriate waste site or waste incineration plant, for example, while observing local regulations.
Contact the local municipal sanitation ofce or the mobile
environmental service for quantities under 100 l.
Uncleaned packings: Uncontaminated packings can be reused. Dispose of packings which are unable to be cleaned together with the substance.
14 Transport information:
VbF: not subject to the ordinance on combustible uids. Mailing permitted. GGVE/RID: -, UN no.: -, GGVS/ADR: -, IATA DGR: -, IMDG code: -, TA air: -. No dangerous goods according to transport regulations.
15 Regulations
Labelling in accordance with EC directives/national regulations: No labelling obligation
Other regulations: water hazard class (Germany, Appendix 4 of the VwVwS (administrative regulation on water-pollutant substances) from 17.05.1999): (1), slightly water-pollutant
16 Other information
The safety data sheet is intended to provide essential physical, safety-related, toxicological and ecological data and give recommendations for safe handling or safe storage, handling and safe transport of chemical substances and formulations.
No liability is assumed for damage in connection with the usage of this information or the usage, application, adaptation or processing of the products described here.
This does not apply as long as we, our statutory agents or assistants are liable in the event of intention or gross negligence.
No liability is assumed for indirect damage.
This information has been compiled to the best of our knowledge and conscience according to our current state of knowledge.
No guarantee can be made for product properties.
26
27
0020055003
Glow-worm, Nottingham Road, Belper, Derbyshire. DE56 1JT
Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.
28
0020055003-04 02.09
Loading...