Glow-worm Clearly Solar Cylinders User Manual

Instructions for use Installation and Servicing
Solar Hot Water Cylinders/ Flurocyl 200 250 300
2
TABLE OF CONTENTS
INTRODUCTION
1 Instructions guidance ................................................................................................................... 3
1.1 Product documentation .......................................................................................3
1.2 Associated documents ........................................................................................3
1.3 Storage of documents .........................................................................................3
1.4 Explanation of symbols .......................................................................................3
1.5 Benchmark .........................................................................................................3
2 Safety instructions and regulations ............................................................................................... 3
2.1 Intended use ......................................................................................................3
2.2 General safety information ..................................................................................4
2.3 Cylinder safety information ..................................................................................4
2.4 Cylinder identication plate .................................................................................4
2.5 Regulation and statutory requirements .................................................................4
3 Introducing your appliance ........................................................................................................... 5
3.1 Appliance description .........................................................................................5
READ CAREFULLY BEFORE U S I N G
4 Operation .................................................................................................................................... 6
4.1 Adjusting the hot water temperature ....................................................................6
4.2 Switching o hot water ........................................................................................6
4.3 Frost protection ..................................................................................................6
4.4 Cleaning the cylinder ..........................................................................................6
4.5 Fault nding .......................................................................................................7
5 Inspection and Maintenance ......................................................................................................... 7
TECHNICAL DATA
6 Technical data .............................................................................................................................. 8
INSTALLAT I O N
7 Hydraulic and electrical schematics ............................................................................................. 10
8 Description of the components ................................................................................................... 12
8.1 Flurocyl2 solar cylinder ......................................................................................12
8.2 Solar pump safety thermostat ............................................................................12
9 Cylinder installation ................................................................................................................... 13
9.1 Cylinder device description ................................................................................13
9.2 Installation site .................................................................................................15
9.3 Installing of discharge pipe ...............................................................................15
9.4 Pipes for the reheating circuit ............................................................................17
9.5 Installing hot water pipes ..................................................................................18
9.6 Installation of cold water pipe ............................................................................18
9.7 Electrical installation .........................................................................................20
10 Commissioning ......................................................................................................................... 21
10.1 Filling the cylinder ............................................................................................21
- 1 -
TABLE OF CONTENTS
MAINTENANCE
11 Inspection and maintenance ....................................................................................................... 23
11.1 Maintenance checklist .......................................................................................23
11.2 Draining the cylinder .........................................................................................23
11.3 Fault diagnosis .................................................................................................24
12 Recycling and disposal ............................................................................................................... 25
12.1 Cylinder disposal ..............................................................................................25
12.2 Disposal of packaging .......................................................................................25
13 Customer service and manufacturer's warranty ............................................................................ 26
13.1 Glow-worm service ............................................................................................26
13.2 Glow-worm warranty .........................................................................................26
14 Spare parts ................................................................................................................................ 27
- 2 -
INTRODUCTION
INTRODUCTION
1 Instructions guidance
1.1 Product documentation
The instructions are an integral part of the appliance and must be handed to the user on completion of the installation in order to comply with the current regulation.
• Carefully read the manual, to understand all the information to enable safe installation, use and servicing. No liability can be accepted in the event of damage for not complying with the guidance in this instruction manual.
1.2 Associated documents
When installing and maintaining the solar system, you must observe all of the installation and maintenance instructions for system parts and components as well as those for other accessories which are used in the system.
These installation and maintenance manuals are provided with the relevant system parts, components, and accessories.
1.3 Storage of documents
Pass this installation manual and all other applicable documents and, if necessary, any required aids to the system operator.
The system operator will be responsible for storing them so that the instructions and aids are available when required.
1.4 Explanation of symbols
a
DANGER: Risk of injuries.
installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist must be used to demonstrate compliance with Building Regulations and must be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme.
• Visit www.central heating.co.uk for more information.
2 Safety instructions and regulations
2.1 Intended use
Glow-worm cylinders are constructed using state-of-the-art technology in accordance with recognised safety regulations. Nevertheless, there is still a risk of injury or death to the user or others or of damage to the unit and other property in the event of improper use or use for which the unit is not intended.
Glow-worm cylinders are not intended for use by persons who have inadequate experience and/or knowledge, unless they are supervised by a person responsible for their safety or have been given instructions by this person regarding the operation of the unit. Children must be supervised to ensure that they do not play with the unit.
Glow-worm Flurocyl indirectly heated domestic hot water cylinders designed for use
with gas-red boilers as per GB standards for hot water supply
systems. The cylinders work with the pressure of the water supply line and do not need a cold water tank for their supply.
They are used only to supply potable water heated up to 80°C in solar systems with a collector array. They may only be used for this purpose. The cylinders can be used in combination
with a downstream gas-red boiler for hot water generation in
accordance with GB standards.
domestic hot water cylinders are unvented,
2
e
DANGER: Risk of electric shock.
ATTENTION: Risk of damage to the appliance or to its vicinity.
IMPORTANT: Useful information.
1.5 Benchmark
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is
0020115479_03 - 10/12 - Glow-worm
Any other use or extended use is considered to be improper. Improper use of any kind is prohibited.
The manufacturer/supplier is not liable for any damage resulting from improper use. The user alone bears the risk. Intended use also includes observing the operating and installation manuals and all other applicable documents, as well as complying with the inspection and maintenance conditions.
At the end of this manual there is a commissioning report which
you must ll in and hand over to the operator. All installers
should have a current ID card and registration number. The cylinder must be installed by a competent person approved at the time by the Health and safety Executive to the prevailing standards, installation book and building regulations at the time of installation.
- 3 -
INTRODUCTION
2.2 General safety information
Installation and adjustment as well as service, maintenance and repair must be carried out by a competent person approved at the time by the Health and Safety Executive and be in accordance with the relevant requirements of the Local Authority, Building Regulations, Building Regulations (Scotland), Building Regulations (Northern Ireland), and the bye-laws of the local Water Undertaking.
2.3 Cylinder safety information
This product has been assessed and found to comply with the requirements of the Building Regulations for unvented hot water
storage systems and must not be altered or modied in any way.
In the event of parts replacement, use only genuine spare parts supplied by Glow-worm.
The installation is subject to Building Regulation approval.
Notify the Local Authority of intention to install.
As stipulated in the manual "Handling Operations Regulations 1992", the weight of the unit exceeds that which should be lifted by one person.
Without potential equalisation, life-threatening voltage from the electric immersion heater can reach the piping and water taps.Earth the electric immersion heater. If the solar cylinder is connected with pipes made of non-metallic materials and is not earthed, corrosion damage can occur.
Earth the solar cylinder for potential equalisation and to protect against overvoltage.
If using non-metallic pipes on the water route, make sure that they are designed by the manufacturer for continuous operation at 70°C and operation by the hour at temperatures of up to 95°C
Always use a suitable open-end spanner to tighten or undo threaded connections. Do not use pipe wrenches, extensions, etc. If the water does not meet the requirements of the UK water quality standards with a maximum chloride level of 250 mg/l, corrosion damage may occur to the cylinder.
Only use the cylinder to heat potable water.
2.3.1 Electric potential equalisation
If you use an electric immersion heater in the cylinder, the external voltage may build up electrical potential in the water which can result in the electrochemical corrosion of the electric immersion heater. Make sure that both the hot water and cold water pipes are connected to the earth line by means of earth cable directly on the cylinder. You must also make sure that the electric immersion heater is connected to the earth line via the earthing terminal.
2.3.2 Preventing frost damage
You should not turn the gas-red boiler o completely so that
you can still use all of the safety functions for your heating installation. If you want to take the unit out of operation for a relatively long period of time in an unheated room at risk from frost, you must completely drain the Flurocyl2.
2.3.3 Avoiding damage caused by leaks
If there are leaks in the pipe network, close o the cold water stop valve on the safety assembly and notify an engineer qualied to
work on unvented systems to rectify the leaks.
2.3.4 Avoiding burns and scalds
For scald protection, install a hot water thermostat mixer in the system.
If the system is in stagnation then hot steam can discharge from the expansion relief valve of the solar pump unit. This may be visible in the receptor canister. Should this occur contact your installer for advice.
The temperature of the stored water could reach high temperatures after solar charging and your Glow-worm solar
installer will have tted a tempering valve so as to prevent this
reaching the hot water taps. Should excessively hot water reach your hot taps contact your installer immediately.
2.3.5 Preventing damage due to unauthorised changes to the unit
Changes to the supply lines, relief valve termination, and expansion relief valve may only be carried out by an engineer
qualied to work on unvented systems.
Never shut o the expansion relief valve or relief valve
termination.
Never bypass any of the security devices.
2.4 Cylinder identication plate
The identication plate is attached to the middle of the cylinder
at the factory.
2.5 Regulation and statutory requirements
2.5.1 Cylinder and cylinder assembly
Pressure equipment directive 97/23/EC
Directive of the European Parliament and Council from 29th May, 1997 for the approximation of the laws on pressure equipment of the Member States
EN 12977-3
Thermal solar systems and components; Custom built systems, Part 3: Performance characterisation of domestic hot water cylinders
EN 12897:2006
Water supply - specication for indirectly heated unvented
(closed) domestic hot water cylinders
- 4 -
0020115479_03 - 10/12 - Glow-worm
INTRODUCTION
EN 806-1
Specications for installations inside buildings conveying water
for human consumption - Part 1: General
EN 1717
Protection against pollution of potable water installations and
general requirements of devices to prevent pollution by backow
EN 60335-2-21
Safety of household and similar electrical appliances; Part 2: Particular requirements for storage water heaters (domestic hot water cylinders and hot water boilers) (IEC 335-2-21: 1989 and
supplements 1; 1990 and 2; 1990, modied)
2.5.2 CE Mark
CE labelling shows that the appliance according to the model overview comply with the basic requirements of the applicable directives.
The CE declarations of conformity can be viewed at the manufacturer's premises and can be supplied if necessary.
3 Introducing your appliance
3.1 Appliance description
3.1.2 Hot water temperature regulation
You can set the hot water temperature and reheating times in the upper half of the cylinder on the controller.
One of the following controllers may be used depending on the design of your system:
- Glow-worm Fluropro
- Climapro
Refer to the operating manual for the installed controller or timer.
in conjunction with a timer
2
3.1.3 Electric immersion heater
The cylinder is equipped with an additional electric immersion heater (3) with a heating output of 3 kW. The electric immersion heater is designed for use in unvented cylinders and has a thermostat with a temperature controller (2) and a safety thermostat (TCO) with a reset button (1).
3.1.4 Functional elements of cylinder
1
2
3
The Flurocyl2 solar cylinder is available in three sizes: 200, 250 and 300 litres. The containers are made from stainless steel with EPS with additional infared absorbing insulation. The cylinder works with the pressure of the water supply line and does not need a cold water tank for its supply. To enable the cylinder to work as well as possible, a cold water supply with an appropriate
pressure and ow rate is required.
3.1.1 Safety devices
The solar cylinder has been provided with all safety and control devices for operation of the unvented domestic hot water supply:
- Temperature/pressure relief valve (90 °C, 7 bar)
- Pressure limiting valve (3.5 bar) with line strainer
- Expansion relief valve (one-way valve, 6.0 bar)
- Solar pump safety thermostat, set to 80 °C, connected with the solar pump in order to isolate this heat source if there is a malfunction in the solar control.
- Safety thermostat for electric immersion heater (85 °C).
- Solar cylinder safety thermostat, set to 80 °C, to be connected to the 2-port motorised valve in order to isolate the primary heat source if a domestic water supply thermostat malfunction occurs.
4
Key 1 Reset button for reheating circuit 2 Cylinder thermostat 3 Electric immersion heater
4 Reset button for solar circuit
0020115479_03 - 10/12 - Glow-worm
- 5 -
READ CAREFULLY BEFORE USING
4 Operation
Risk of scalding and bursts due to inappropriate
a
a
4.1 Adjusting the hot water temperature
The hot water temperature is set to the required value by the
engineer qualied to work on unvented systems during the
cylinder commissioning. If an external controller is installed for hot water temperature control, you can adjust the hot water temperature and reheating times using this controller.
For information on making settings, see the operating manual for the controller.
If no controller for hot water temperature control is installed, you can set the required hot water temperature on the cylinder thermostat (2). You can set the reheating times on the installed hot water timer. Refer to the operating manual for the hot water timer.
alterations!
There is a risk of escaping steam, bursting, and damage to the system if you make any changes to the cylinder, control system, supply lines for water and power (if present), relief valve termination, or
expansion relief valve for the cylinder water.
Do not make any improper changes.
Risk of scalding!
The output temperature of the draw-o points can reach 85 °C if the mixing valve is set incorrectly.
- Do not adjust the mixing valve.
- If the output temperature at a draw-o point is too high or low, Contact an engineer qualied to work on
unvented systems to adjust the temperature.
Always make sure that there is clear access to the cylinder to enable the use of the hot water thermostat controller and the thermostat mixer.
4.2 Switching o hot water
• Switch o the immersion heater and the gas-red boiler (see the operating manual for the gas-red boiler) to temporarily switch o the heating and hot water system.
4.3 Frost protection
Risk of damage due to frost!
If the cylinder is placed out of operation for a relatively long period of time in an unheated room (e.g. during a winter holiday), the cylinder must be completely drained.
- Contact an engineer qualied to work on unvented
systems to drain the cylinder.
If you are absent during a relatively long period when there is a risk of frost, make sure that you leave the central heating on and that the temperature in the cylinder room and in all other rooms are kept above freezing.
4.4 Cleaning the cylinder
• Clean the outside of the cylinder only with a damp cloth, using soapy water if it is especially dirty.
Do not use abrasive cleaning agents or solvents (any type of scouring agent, petroleum etc.) since they can damage the
cladding and the cylinder xtures.
• Set the desired cylinder hot water temperature on the cylinder thermostat (2).
• For optimum eciency, choose a setting of 45 °C.
• Use the operating manual for the gas-red boiler to make sure
that the unit is ready for operation.
We recommend the cylinder is set to 60 °C periodically, to provide protection against the proliferation of harmful bacteria.
If you are heating up water for the rst time or after a long switch-o period, the full cylinder performance is
only available following a waiting period.
If the Flurocyl2 is installed in a cupboard, make sure that clothing and other objects are not placed on the cylinder, control devices, pipes, or other system components.
- 6 -
0020115479_03 - 10/12 - Glow-worm
READ CAREFULLY BEFORE USING
4.5 Fault nding
Fault Remedy
Fluid is dripping from the system? If possible, collect the uid in a bucket and contact an engineer qualied to
The controller issues a message telling me the sensor is faulty or there is a cable break?
The cylinder is not providing sucient hot water? Check that the hot water temperature is set correctly on the controller
A safety thermostat trips? Contact an engineer qualied to work on unvented systems.
Water escapes from the expansion relief valve? Contact an engineer qualied to work on unvented systems.
5 Inspection and maintenance
An annual inspection/maintenance run by an engineer qualied
to work on unvented systems is a prerequisite for ensuring that the cylinder is permanently ready for operation, reliable, and has a long service life.
work on unvented systems.
Contact an engineer qualied to work on unvented systems.
(recommended value of approx. 45 °C, however, set periodically to 60 °C to provide protection against the proliferation of harmful bacteria) and
that the gas-red boiler is working. If the settings are correct, the cylinder may be calcied. Then: contact an engineer qualied to
work on unvented systems.
It is important that your hot water cylinder is serviced annually.
We recommend entering into a maintenance agreement.
After servicing, the servicing engineer must complete the relevant Service Interval Record section of the Benchmark Checklist located on the inside back pages of this document.
Risk of death from electric shock.
e
a
Improperly executed work on the cylinder can result in
a risk to life and limb.
- Never try to rectify cylinder malfunctions yourself.
- Contact an engineer qualied to work on unvented
systems to rectify all malfunctions.
Risk of injury resulting from improper maintenance or repair.
Failure to arrange for the system to be maintained and repaired and improper maintenance and repair can impair the operational safety of the unit, leading to injuries and damage to property
- Never attempt to perform maintenance work or repairs on the cylinder yourself.
- Always employ an engineer qualied to work on
unvented systems.
0020115479_03 - 10/12 - Glow-worm
- 7 -
TECHNICAL DATA
TECHNICAL DATA
6 Technical data
Unit Flurocyl2 200 Flurocyl2 250 Flurocyl2 300
Total capacity l 200 250 300
Actual capacity l 209.4 254.4 297.2
Hot water capacity (upper coil) l 104.8 142 144.2
Hot water capacity (solar coil) l 203.3 246.1 271.1
Dedicated solar volume l 104.6 112.4 153.0
Maximum supply pressure to pressure reducing valve bar 12
Maximum operating pressure of cylinder bar 7
Maximum operating pressure of heating coil bar 3.5
Maximum operating pressure of solar coil bar 6
Operating pressure bar 3.5
Pressure limiting valve bar 3.5
Expansion relief valve bar 6.0
Temperature and pressure relief valve bar 7.0
Charge pressure of hot water expansion vessel bar 4.0
Maximum temperature of heating circuit oC 85
Maximum temperature of potable hot water oC 85
Maximum temperature of solar uid oC 85
Standing heat loss kW/24h 2.05 2.20 2.40
Heat up time according to EN 12897 mins 22 29 30
Recovery time (70% capacity) mins 16 21 22
Primary heat exchanger performance kW 14.9 15.3 15.0
Flow rate for primary heat exchanger performance l/min 23.3 23.3 23.3
Primary heat exchanger pressure drop mbar 79 78 79
Primary heat exchanger volume l 2.37 2.37 2.37
Primary heat exchanger surface area m2 0.5 0.5 0.5
Solar heat exchanger performance kW 18.7 18.5 16.5
Flow rate for solar heat exchanger performance l/min 23.3 23.3 23.3
Solar heat exchanger pressure drop mbar 97 95 98
Solar heat exchanger volume l 2.94 2.94 2.94
Solar heat exchanger surface area m2 0.62 0.62 0.62
Heat up time according to EN12897 (solar) mins 34 42 51
Temperature and pressure relief valve oC/bar 90 / 7.0
Dimensions
Height mm 1593 1843 2153
Height with hot water draw o mm 1625 1875 2185
Topple measure mm 1680 1918 2217
Diameter mm 554.5
Depth mm 624
Net weight kg 40 43 50
Weight (lled) kg 249 298 347
Connections
Cold water inlet 22mm compression joint
Hot water draw-o 22mm compression joint
Balanced pressure cold water outlet 22mm compression joint
Secondary return 15 mm compression joint
- 8 -
0020115479_03 - 10/12 - Glow-worm
TECHNICAL DATA
Unit Flurocyl2 200 Flurocyl2 250 Flurocyl2 300
Primary heater ow 22mm compression joint
Primar heater return 22mm compression joint
Solar ow 22mm compression joint
Solar return 22mm compression joint
Primary heating circuit immersion sleeve size mm 8
Solar circuit immersion sleeve size mm 8
Electrical data
Immersion heater (according to ENBS 60335) 2.7 kW / 230 V / 50 Hz
Length of immersion heater inch 14
Two port motorised valve 230/240 V, 50 Hz
Thermal cut out solar 230/240 V, 50 Hz
Cylinder thermostat 230/240 V, 50 Hz
Material data
Cylinder body material Stainless Steel (1.4521)
Cylinder jacket material Polypropylene
Insulation material EPS with infrared absorber
Insulation thickness 50
Corrosion protection Stainless Steel
Blowing agent for insulation material Pentane (GWP < 5)
ODP 0
The heat up time is based on a ow rate of 1400 l/h at
80 °C. Temperature rise from 15 °C to 60 °C.
0020115479_03 - 10/12 - Glow-worm
- 9 -
INSTALLATION
INSTALLATION
7 Hydraulic and electrical schematics
4
3
8
230V~ PCSA PCSB/PC LEG/BYP V3VR
3A
8
7.1
C 2 C 2 1
6
N L L link
C 2
C 2
14
18
19
19
Gr
R
Bl
Bl Gr Or R R
14
N L 334 5 6 7 8 9
3A
10
11
15
17
N L
11
CH
Or
N
Load
15
R
R1
1 C
3A
18
Gr
Or
Bl
10
230V
9
5
6
2
1
A
B
7
7.3
4
13
2
16
230V
N L
3A
D
7
7.1
13
16
7.3
G
H
10
7.2
R
1
16A
12
7.2
E
F
C
20
230V
9
16A
12
L
10 7
L link
Key: 1 Boiler 2 Solar gain NTC 3 Solar collector 4 Collector NTC 5 Solar expansion vessel and protection vessels 6 Solar pump station 7 Domestic hot water cylinder
7.1 Cylinder dual thermostat
7.2 Immersion heater with thermal safety
7.3 Solar pump thermal cut-out
8 Additional terminal block 9 Electrical supply + protection (This must have it's own single
isolation) 10 Fluropro solar controller 11 CH time controller
- 10 -
12 Electrical switch 13 NTC sensor pocket (TAC 2) 14 Terminal block 15 Room thermostat 16 NTC sensor (TAC 2) 17 Heating circuit 18 DHW 2 port valve 19 CH 2 port valve A Boiler circuit return
B Boiler circuit ow
C Cold water supply D Domestic hot water outlet
E Cylinder circuit ow
F Cylinder circuit return G Solar circuit return
H Solar circuit ow
0020115479_03 - 10/12 - Glow-worm
INSTALLATION
4
3
8
230V
9
5
16A
10
230V~ PCSA PCSB/PC LEG/BYP V3VR
3A
8
6
N L L link
C 2
C 2
L L link
6
2
D
7
12
11
EBUS
7.1
13
14
7.1
1
15
7.2
F
F
E
C
16
17
19
G
H
A
B
230V
9
16A
18
10
12
14
4
13
15
2
12
CYL.
230V~ CH
DHW
DHW
On
On
Off
On
NTC
BUS
+
+
7.1
1
N L N L
2
7.2
3A
1
BUS
N L
16A
BUS
20
18
17
Key:
1 Ebus boiler 2 Solar gain NTC 3 Solar collector 4 Collector NTC 5 Solar expansion vessel and protection vessel 6 Solar pump station 7 Domestic hot water cylinder
7.1 Immersion heater with thermal safety
7.2 Cylinder overheat thermostat
7.3 Solar pump thermal cut-out 8 Additional terminal block 9 Electrical supply + protection (This must have it's own single
isolation) 10 Fluropro solar controller 11 Climapro RF
0020115479_03 - 10/12 - Glow-worm
12 Electrical switch 13 NTC sensor (TAC 1) 14 Smart Wiring Center 15 NTC sensor (TAC 2) 16 Heating circuit 17 DHW 2 port valve 18 CH 2 port valve 19 Automatic air separator 20 RF receiver A Boiler circuit return
B Boiler circuit ow
C Cold water supply D Domestic hot water outlet
E Cylinder circuit ow
F Cylinder circuit return G Solar circuit return
H Solar circuit ow
- 11 -
INSTALLATION
8 Description of the components
8.1 Flurocyl2 solar cylinder
Section 4.1 of this manual describes the Flurocyl2 solar cylinder in detail.
8.2 Solar pump safety thermostat
1
3
3
3
4
2
3
Fig. 4.1 Connection diagram for solar pump
Key 1 Solar controller or solar module 2 Terminal strip 3 Solar pump 4 Solar circuit safety thermostat
In order to meet the requirements for unvented hot water cylinder systems (G3), you must connect the power supply for the solar pump (3) via a manually resettable safety thermostat (TCO) in the solar cylinder.
The Flurocyl thermostat (4) at the factory. If the cylinder temperature is higher
solar cylinder is tted with an appropriate safety
2
than 80 °C, the safety thermostat interrupts the power supply to the solar pump.
8.2.1 Cylinder frost protection
If you want to put a cylinder out of operation where it may be at risk from frost, you must drain it completely. It is drained at the cold water inlet with a T-piece with tap to be provided by the installer.
Any heat exchangers not lled with solar uid in rooms which are
at risk of frost must also be completely drained.
- 12 -
0020115479_03 - 10/12 - Glow-worm
9 Cylinder installation
9.1 Cylinder device description
INSTALLATION
1
21
18
14
20
15
22
26
25
24
23
19
17
16
13
2 3
4
67
5
9
3
8
12
11
Key 1 Hot water connection 2 Expansion relief valve (one-way valve, 6.0 bar) 3 Pressure limiting valve (3.5 bar) with line strainer 4 Cold water connection 5 Pressure-controlled cold water connection 6 Connection for hot water expansion vessel 7 Cylinder connection 8 Hot water expansion vessel 9 Tundish 10 Cylinder drain valve (not supplied) 11 Return line (solar circuit) 12 Solar collector temperature sensor 13 Cold water pipe 14 Solar circuit safety thermostat (TCO), set to 80 °C, to be connected with the solar pump in order to isolate this heat source if there is a malfunction in the solar control. 15 Solar circuit immersion sleeve (length 70mm dia. 8mm) (TAC 2) 16 Supply line (solar circuit)
10
17 2- pole circuit breaker for electric immersion heater 18 Electric immersion heater with thermostat and safety thermostat
(20°C to 65 °C) (length 70mm dia. 8mm)
19 Return line (gas-red boiler)
20 Reheating circuit immersion sleeve (TAC 1) 21 Reheating circuit safety thermostat, set to 80 °C, to be connected to the 2-way motorised valve in order to isolate the primary heat source if a malfunction occurs. 22 Cylinder thermostat (25 °C to 65 °C) 23 2 -way motorised valve
24 Supply line (gas-red boiler)
25 Circulation line connection 26 Temperature and pressure relief valve (90 °C, 7 bar)
0020115479_03 - 10/12 - Glow-worm
- 13 -
INSTALLATION
The Flurocyl2 solar cylinder is available in three sizes: 200, 250, and 300 litres. The containers are made from stainless steel with EPS insulation. The cylinder is supplied along with all required cold and hot water control devices and a 2-way motorised valve. The cylinder works with the pressure of the water supply line and does not need a cold water tank for its supply. The cylinder has hot and cold water connections with a diameter of 22 mm. To enable the cylinder to work as well as possible, a cold water
supply with an appropriate pressure and ow rate is required.
9.1.1 Cylinder operating elements
8
6
7
1
2
3
9.1.2 Electric immersion heater operating elements
1
2
3
4
5
Key 1 Electric immersion heater temperature controller 2 Electric immersion heater TCO reset button 3 Electric immersion heater
The cylinder is equipped with an additional electric immersion heater (3) with a heating output of 3 kW. The electric immersion heater is located behind the top front cladding. The electric immersion heater is designed for use in unvented cylinders and has a thermostat with a temperature controller (2) and a safety thermostat (TCO) with a reset button (1).
2
3
1
5
4
Key 1 Cover cap for reset button for reheating circuit TCO 2 Reheating circuit temperature controller 3 Electric immersion heater cover 4 Cover cap for reset button for solar circuit TCO 5 Solar circuit safety thermostat (TCO) 6 Electric immersion heater 7 Cylinder thermostat 8 Reheating circuit safety thermostat
The following are pre-mounted at the factory for the Flurocyl solar cylinder:
2
Cylinder thermostat (7) and reheating circuit safety thermostat (8)
Electric immersion heater (6) with safety thermostat and cylinder thermostat
Solar circuit safety thermostat (5)
The cylinder must be properly wired in order to comply with G3 building regulations.
If you need to make a replacement, you must use the correct electric immersion heater with a safety thermostat for overheating protection. Only use original replacement parts from Glow-worm. Always replace the immersion heater gasket when parts are replaced.
- 14 -
You must connect the solar pump to the solar controller via the solar circuit safety thermostat.
The thermostat switches the solar pump o if the
temperature of the hot water in the cylinder exceeds 80 °C.
0020115479_03 - 10/12 - Glow-worm
INSTALLATION
9.1.3 Safety devices
The cylinder is delivered with all safety and control devices for the operation of the unvented domestic hot water supply:
- Temperature/pressure relief valve (90 °C, 7 bar)
- Pressure limiting valve (3.5 bar) with line strainer
- Expansion relief valve (one-way valve, 6.0 bar)
- Solar circuit safety thermostat, set to 80 °C, to be connected with the solar pump in order to isolate this heat source if there is a malfunction in the solar control.
- Safety thermostat for electric immersion heater (set to 85 °C).
- Reheating circuit safety thermostat, set to 80 °C, to be connected to the 2-way motorised valve in order to isolate the primary heat source if a cylinder thermostat malfunction occurs.
- Do not bypass the thermal cut-outs or other saftey devices in any circumstances
9.1.4 Pack contents
Check the contents of the enclosed box.
Make sure the cylinder is stored in an upright position in a dry environment prior to its installation.
9.2 Installation site
Place the cylinder in a suitable location in the building, paying attention to the following:
- The tundish discharge pipe must be installed with a minimum slope of 1:200 and must end in a safe and visible place.
- The installation surface must be at and capable of bearing the weight of the entire cylinder and associated controls when full of water.
- The installation site must not be at risk of frost. If necessary, install a frost protection thermostat.
- The control system for the installed cylinder thermostat must be easily accessible to the operator.
- There must be sucient space for the assembly, check and pressure build-up of the expansion vessel.
- There must be sucient space for the assembly, check and maintenance of the immersion heater.
- The oor must be even.
8
7
6
1
5
4
3
2
Item Quantity Component
1 1 Flurocyl2 solar cylinder in separate packaging
2 1 Safety assembly (pressure limiting valve,
3 1 2-way motorised valve
4 1 15mm compression cap for secondary return
5 1 Tundish
6 1 Assembly set for hot water expansion vessel
7 1 Hot water expansion vessel:
8 1 Instructions for use, Installation and Servicing
expansion relief valve, connections for pressure-controlled cold water connection and hot water expansion vessel)
18 l for Flurocyl 25 l for Flurocyl2 250, 300
manual
200
2
Where cylinders are tted high up in the building
a
there are some situations where a vacuum could be created in the cylinder. The installer must consider
in these circumstances the necessity of tting an
anti vacuum valve to prevent cylinder damage. This valve allows air to enter the cylinder if the pressure becomes too low due to draining or thermal contraction.
9.3 Installation of discharge pipe
9.3.1 Design of discharge pipe
Risk of burns and scalds resulting from escaping hot
a
water.
If there is a malfunction, hot water will discharge from the TPRV via the tundish.
- Lay the discharge pipe so that it ends at an easily visible point inside or outside the building where escaping hot water does not pose a risk to persons.
0020115479_03 - 10/12 - Glow-worm
- 15 -
INSTALLATION
S
AFETY DEVICE
9.3.2 Discharge requirements (G3 building regulations)
(E.G. TEMPERATURE RELIEF VALVE VENTIL)
600 MM
300 MM
MINIMUM
METAL DISCHARGE PIPE FROM TUNDISH WITH CONTINUOUS FALL
The discharge connections of the temperature/pressure relief valve and the expansion relief valve must be connected with the supplied tundish via 15 mm copper piping. The tundish should be attached so that it is vertical, as near to the cylinder as possible, and not more than 600 mm from the connection of the temperature/ pressure relief valve. It must be mounted
in the same room as the cylinder at a sucient distance from
the electrical components. The discharge pipes from the temperature/pressure relief valve and expansion relief valve can be joined above the tundish using a T-piece.
The discharge pipe from the 22 mm connection of the drain funnel must be laid using copper piping with a diameter of at least 22 mm to a safe and visible discharge point.
METAL DISCHARGE PIPE FROM TEMPERATURE RELIEF VALVE TO TUNDISH
DISCHARGE
TUNDISH
BELOW FIXED GRATING
TRAPPED GULLY
FIXED GRATING
From Sizing Table:
Maximum resistance allowed for a straight length of 22 mm copper discharge pipe from a G1/2 temperature relief valve is:
9.0 m.
Subtract the resistance for 4 No. 22 mm elbows at 0.8 m each =
3.2 m.
Therefore the maximum permitted length equates to: 5.8 m, which is less than the actual length of 7 m therefore calculate the next largest size.
Maximum resistance allowed for a straight length of 28 mm pipe from a G1/2 temperature relief valve is: 18 m.
Subtract the resistance of 4 No. 28 mm elbows at 1.0 m each =
4.0 m.
Therefore the maximum permitted length equates to: 14 m.
As the actual length is 7 m, a 28 mm copper pipe will be satisfactory.
A suitable place for the end of the discharge pipe is, for
example, beneath a xed grille above the odour seal in a gully
with a siphon. Low discharge pipes, for example up to 100 mm above external surfaces such as car and other parking spaces, grasslands etc. can be used provided that they are secured by a wire fence or something similar to prevent children from coming into contact with the waste water and as long as the system is not visible. You must not install any valves or stop cocks in the discharge pipe.
• Make sure that the discharge pipe from the tundish to the drain has a constant downward incline of at least 1:200. The discharge pipe from the pressure relief valve of the Glow-worm
gas-red boiler can be connected to the horizontal discharge
pipe of the cylinder behind the tundish using a T-piece.
There must be a vertical section of pipe at least 300 mm long beneath the tundish before any bends or elbows in the pipework. If the total resistance of the discharge pipe exceeds the values
specied in table below, you must increase the diameter of the
piping. When installing the discharge piping, you must observe Directive G3 (section 2.5).
9.3.3 Sizing of copper discharge pipe for G1/2 temperature and pressure relief valve outlet size
Minimum diameter of discharge pipe from tundish
22 mm Up to 9 m 0.8 m
28 mm Up to 18 m 1.0 m
35 mm Up to 27 m 1.4 m
Worked example
The example below is for a G1/2 temperature relief valve with a discharge pipe having 4 No. 22 mm elbows and length of 7 m from the tundish to the point of discharge.
Maximum permissable total resistance, expressed as straight pipe length (without elbows or bends)
Resistance due to each elbow or bend
- 16 -
0020115479_03 - 10/12 - Glow-worm
9.3.4 Dimensions
c
b
a
d
e
f
g
i
j
h
k
l
1
2
5
3
4
6
7
8
9
10
11
Ø 554,5
624
25°
45°
INSTALLATION
Key
1 Hot water draw o
2 Temperature and pressure relief valve 3 Secondary return
4 Primary heater ow
5 Immersion sleeve 6 Primary heater return 7 Electric immersion heater
8 Solar ow
9 Solar circuit immersion sleeve (TAC 2) 10 Cold mains inlet 11 Solar return
Flurocyl2a b c d e f g h i j k l
200 1625 1593 1341 1158 1052 912 822 802 534 506 259 51
250 1875 1843 1591 1346 1102 962 872 852 534 506 259 51
300 2185 2153 1901 1578 1377 1237 1147 1127 534 506 259 51
9.4 Pipes for the reheating circuit
Make sure that the pipes between the gas-red boiler and
cylinder are as short as possible in the reheating circuit. Use copper piping with a minimum diameter of 22 mm.
0020115479_03 - 10/12 - Glow-worm
- 17 -
INSTALLATION
If you are using the cylinder with a gasred boiler as per GB
standards, you may have to install a suitable heating pump in the reheating circuit.
9.4.1 Installing the 2-way motorised valve
1
The 2-way motorised valve prevents the cylinder from overheating.
Install the 2-way motorised valve (1) supplied with the cylinder in
the supply line of the gas-red boiler. Do not install the valve with
the head upside down.
9.5 Installing hot water pipes
Connect the hot water piping to the 22 mm hot water connection of the cylinder.
Lay the 22 mm piping up to the rst T-piece.
The required diameter of subsequent pipes depends on the system design.
9.5.1 Connecting up the secondary circulation line
The cylinder has a connection with a 15 mm diameter for a circulation line.
• Connect a WRAS-approved circulation pump which has a non-
return valve with the circulation connection.
In a thermal solar system, a hot water thermostat mixer must be installed as scald protection. The hot water thermostat mixer mixes the hot water from the cylinder with cold water to produce water with a maximum temperature of between 30 and 60 ºC as required.
The hot water thermostat mixer must be provided by the installer.
9.5.2 Installing the hot water thermostat mixer (with secondary circulation line)
3
2
230
1
1 6 5
7
8
Key: 1 Non-return valve 2 Hot water thermostat mixer 3 Solar controller 4 Hot water pipe 5 Circulation line 6 Circulation pump 7 Contact thermostat 8 Expansion relief valve 9 Cold water pipe 10 Solar cylinder
10
Where possible, avoid installing a circulation line, since a circulation line results in higher energy consumption.
If the installation of a circulation line is required, keep circulation operations to a minimum by only using circulation mode when required for demand and temperature reasons.
Connect the circulation line (6) to the hot water pipe (4) via a hot water thermostat mixer (2).
4
9
• Establish the connection to the circulation line.
If you are not using the secondary circulation connection, you must ensure that it is properly closed
o. Where secondary return circuits are used, an
additional expansion vessel may be required.
1
A
B
Key: 1 Thermostat mixer A Hot water B Cold water AB Mixed water
- 18 -
AB
9.6 Installation of cold water pipe
The eciency of an unvented cylinder depends on the available pressure in the cold water pipe and the ow rate. To obtain maximum cylinder eciency, there must be a suitable cold water
pipe, i.e. the measured static line pressure must be at least 2.0
bar. A corresponding ow rate of at least 20 - 25 l/min must be
available.
The pressure in the cold water pipe will be reduced at times of high consumption. Thus, measurements should be taken at such times.
The cylinder still works satisfactorily with a pressure below 2 bar
but the ow rate is reduced. If the pressure is below 1 bar, you
should not install an unvented cylinder.
Glow-worm can provide information on alternative hot water supply systems.
0020115479_03 - 10/12 - Glow-worm
INSTALLATION
9.6.1 Flurocyl2 hot water ow rates at 60 °C
80
60
40
Flowrate (l/min)
20
0
4 5
1
2
Inlet pressure (bar)
3
The displayed ow rates apply to installations in which the cold
water supply is of appropriate dynamic pressure. If the static water pressure is less than 1 bar, contact Glow-worm.
9.6.2 Mounting the safety assembly
Risk of damage to the cylinder as a resultof excess
pressure! Excess pressure can cause the cylinder to burst. Make sure that there is no stop valve installed between the safety assembly and the cylinder.
Risk of damage to the cylinder as a result of excess
pressure! Excess pressure can cause the cylinder to burst. Make sure that the expansion relief valve outlet is not covered or closed.
- Mount the discharge pipe of the expansion relief valve with a constant slope to the outside. The discharge pipe must
nish at a safe and visible point where there is no danger of it
freezing up and where it poses no risk of injury to persons.
- Actuate the expansion relief valve regularly to prevent
calcication.
- Connect the cylinder to the cylinder connection (4).
- For the pipe from the main stop valve of the building to the cylinder, use copper piping with a diameter of at least 22 mm
to ensure that the cylinder is as ecient as possible. This
is particularly important for installations with a pressure­controlled cold water connection (3).
- Mount a drain valve in the cold water pipe at the lowest point between the cylinder and the safety assembly.
- Mount the safety assembly in the cold water pipe on the cylinder.
If you mount the safety assembly above the cylinder, you do not need to drain the cylinder in order to maintain the safety assembly. Make sure there is
sucient space for maintenance and the connection of
the discharge pipe from the expansion relief valve.
When the discharge pipes are connected, the expansion relief valve may not be more than 600 mm away from the temperature/ pressure relief valve.
9.6.3 Safety assembly
7
6
5
4
Key 1 Pressure limiting valve with line strainer 2 Cold water connection 3 Pressure-controlled cold water connection 4 Cylinder connection 5 Hot water expansion vessel connection 6 15 mm expansion relief valve connection 7 Expansion relief valve
During the installation process, position the valves so that you are able to connect the 15 mm connection (6) of the expansion
relief valve (7) with the tundish. Note the direction of ow, which
is marked on the safety assembly with arrows. Do not install the valve with the relieve valve opening upside down.
1
2
3
9.6.4 Mounting the expansion vessel
The Glow-worm solar cylinder is delivered with an external expansion vessel. Connect this expansion vessel to the installed safety assembly as follows:
- Connect the expansion vessel with the safety assembly via a copper pipe or suitable hose line. Make sure the expansion
vessel is supported suciently.
- Use the supplied wall bracket if you want to mount the expansion vessel to a wall.
- If necessary, establish the connection to the cold water connection (3) with pressure compensation of the safety assembly.
Depending on the ttings used and the type of the draw-o points, it may be necessary to install a backow preventer in the
pressure-controlled cold water connection.
In regions with high water pressure (4 bar or more),
you can also connect the mixer tap for a bath or shower to the cold water connection with pressure
compensation (3) of the safety assembly. This ensures
that the hot and cold water supply to the mixer tap have the same pressure. You should install the cold water supply for all other connections using a T-piece before the safety assembly in the cold water pipe to the cylinder.
0020115479_03 - 10/12 - Glow-worm
- 19 -
INSTALLATION
9.7 Electrical installation
Improperly executed electrical connections can impair
a
e
Wiring should be installed by a qualied heating engineer in
accordance with the building regulations, Part P of the current IEE regulations, and all other applicable regulations and directives.
You can use standard commercial cables (H05RR-F 3G1.5 or H05VV-F 3G1.5) for the wiring:
- Cross-section of conductors: 1.5 mm
- Torque for strain relief: 1,5 Nm.
- Maximum length of bus cables: 300m.
230 V supply lines and bus cables must be laid separately above lengths of 10 m.
the operational safety of the unit.
- Only a competent person approved at the time by
the Health and Safety Executive may carry out the
electrical installation.
Without earthing, life-threatening voltage can reach
the piping and water draw-o points.
- Earth the cylinder.
2
9.7.4 Electrical connection of control components
9
3
8
5
7
10
1
2
4
5
6
The discharge pipes of the tundish, drain valves, and motorised valves etc. must be laid at a distance from electrical components.
9.7.1 Wiring
Wiring can be accommodated via the Glow-worm Smart Wiring Centre or Systempro as a system solution. This enables Glow­worm dual-channel eBUS controllers (low-voltage) to be used along with 230 V valves to give control of Hot Water and Heating systems. Alternatively, using a standard 230 V cabling box and controls.
All wiring must be carried out in accordance with BS 7671: "Requirements for electrical installations" (IEE
wiring regulations, current edition).
Smart Wiring Centre will accomodate 1 CH plus 1 DHW zone. Systempro will accomodate up to 3 CH zones plus 1 DHW zone.
9.7.3 Mounting the drain valve
- Mount a drain valve in the cold water pipe at the lowest point between the cylinder and the safety assembly.
The drain valve must be provided by the customer. We recommend applying a hose which reaches about 1 m under the base of the cylinder to the outlet of the drain valve.
Key 1 Cover cap for reset button for reheating circuit TCO 2 Reheating circuit temperature controller 3 Reheating circuit immersion sleeve (TAC 1) 4 Electric immersion heater cover 5 Solar circuit immersion sleeve (TAC 2) 6 Cover cap for reset button for solar circuit TCO 7 Solar circuit safety thermostat (TCO) 8 Electric immersion heater 9 Reheating circuit safety thermostat 10 Cylinder thermostat
- 20 -
0020115479_03 - 10/12 - Glow-worm
INSTALLATION
1
2
3
4
5
4
2
3
1
5
9.7.5 Cylinder thermostat and thermal cut out (TCO) for the reheating circuit
14
13
12
11
10
9
Key: 1 Cylinder thermostat 2 Cylinder thermostat temperature sensor 3 Lower immersion sleeve 4 Terminal for cylinder thermostat protective earth 5 Cylinder thermostat terminal 1 6 Cylinder thermostat terminal 2 7 Cylinder thermostat terminal C 8 Bridge 9 Reheating circuit TCO terminal 2 10 Reheating circuit TCO protective earth terminal 11 Reheating circuit TCO C terminal 12 Reheating circuit TCO reset button 13 Reheating circuit TCO temperature sensor 14 Reheating circuit safety thermostat (TCO)
Disconnect from the mains supply before you remove any of the underlying component covers.
1
2
3
4
5 6 7
8
9.7.6 Solar circuit thermal cut out (TCO)
9.7.7 Connecting up the electric immersion heater
The Glow-worm Flurocyl2 solar cylinders are tted with an electric immersion at the factory.
9.7.8 Electrical connection of electric immersion heater
Key 1 Protective earth terminal (PE) 2 Cable grip 3 Neutral conductor terminal (N) 4 Outer conductor terminal (L) 5 Electric immersion heater
Without earthing, life-threatening voltage can reach
e
the piping and water draw-o points.
- Earth the cylinder.
1
2
3
4
5
Key: 1 Solar circuit thermal cut-out (TCO) 2 Solar circuit TCO reset button 3 Solar circuit TCO terminal C 4 Solar circuit TCO protective earth terminal 5 Solar circuit TCO terminal 2
The live supply to the solar pump MUST be run in series through terminals 3 and 5 from the solar control to the pump for this to be operative as the solar TCO.
• The electric immersion heater must be earthed.
• Dismantle the electric immersion heater cover.
• Install a separate electrical power supply for the electric
immersion heater in accordance with current IEE regulations (BS 7671).
- Use heat-resistant cables (H05BN4-F 1.5 mm² 3 core HOFR
sheathed exible cable) for the cabling of the electric
immersion heater.
- Use the cable grip (2) to rmly secure the supply cable of the immersion heater.
- Connect the electric immersion heater to the power mains via double pole isolating switch with a contact separation of at least 3 mm in both poles.
- Protect the circuit using a 13 A fuse. Mount the cover for the electric immersion heater.
Only switch the immersion heater on once the cylinder is completely full.
With the circuit breaker, the electric immersion heater can be switched on if the reheating device has malfunctioned.
0020115479_03 - 10/12 - Glow-worm
- 21 -
INSTALLATION
10 Commissioning
10.1 Filling the cylinder
Use the draw-o points to bleed the cylinder and water pipes. Do not use the combined temperature/pressure
relief valve of the cylinder or the pressure relief valve of the cold water safety assembly for bleeding, since foreign bodies can contaminate or damage the valves.
• Make sure that the drain valve is closed.
• Open all of the draw-o points in the cold and hot water pipes.
• Open the water supply inlet to the cylinder and allow the water
to run until bubble-free water runs from all of the draw-o
points and the air is removed from the system.
• Close all of the draw-o points.
• Check the system for leaks. In particular, check the installed
electric immersion heater for leaks.
• Open two hot water draw-o points, one at the lowest point
and one at the highest point of the pipe system, and allow water to run for at least 5 minutes.
• Close both of the hot water draw-o points.
10.1.1 Setting thermostats
You can set the hot water temperature by turning the knob with the arrow pointing at the numbers 1 to 5. The following table gives in indication of approximate hot water temperature for each setting:
Setting hot water temperature
- 1 20 °C
- 2 35 °C
- 3 45 °C
- 4 60 °C
- 5 68 °C
• Place the cylinder thermostat (1) and the electric immersion heater thermostat (2) for start-up into the central position
(around 45°C) to achieve maximum energy eciency.
We recommend the cylinder is set to 60 °C periodically, to provide protection against the proliferation of harmful bacteria.
• Place the gas-red boiler into operation until the cylinder
reaches the operating temperature and all radiators in the system are hot.
• Then drain the entire central heating system again to remove any residue from the pipes.
• Fill and bleed the central heating system again as described in
the installation manual of the gas-red boiler.
1
2
• Dismantle the electric immersion heater cover.
- 22 -
0020115479_03 - 10/12 - Glow-worm
MAINTENANCE
MAINTENANCE
11 Inspection and maintenance
Glow-worm solar systems are designed to give a long trouble free life.
In order to ensure this, an annual inspection of the solar circuit should be carried out by a competent person approved at the time by the Health and Safety executive . This would be carried out at the same time as the boiler and cylinder inspection and comprise mostly of visual checks.
Inspection access to the cylinder is available through the immersion heater boss.
Where secondary return circuits are used then an additional expansion vessel may be required.
The essential maintenance work on the solar system and
corresponding maintenance intervals are specied in the
following table.
After servicing, the servicing engineer must complete the relevant Service Interval Record section of the Benchmark Checklist located on the inside back pages of this document.
11.2 Draining the cylinder
• Close the cold water feed line.
• Secure a hose to the drain valve.
• Place the free end of the hose in a suitable discharge position.
The opening should be around 1 m beneath the cylinder.
• Open the highest hot water draw-o point to reduce the
pressure and bleed the water pipes, thus draining them completely.
• Open the cylinder drain valve and leave open until no more water escapes and the cylinder is completely empty.
• Once the water has drained out, close the hot water draw-o
point and the drain valve.
• Remove the hose from the drain valve.
When replacing parts, only use original replacement parts from Glow-worm.
11.1 Maintenance checklist
Nature of maintenance work Maintenance interval
Cylinder
Check all connections to ensure no leaks Annually
Check the temperature and pressure relief valve Annually
Checking the expansion relief valve Annually
Check the charge pressure of the hot water expansion vessel, re-pressurise as necessary Annually
Check water ow rates are correct (Check and clean lters as necessary) Annually
Ensure set temperatures are correct Annually
Check the hot water thermostat mixer function Annually
Fill in the service section of the benchmark cylinder commissioning checklist Annually
0020115479_03 - 10/12 - Glow-worm
- 23 -
MAINTENANCE
11.3 Fault diagnosis
The following checks should be performed before proceeding
onto specic diagnostics:
11.3.1
The faults described in this chapter should be carried
out by an engineer qualied to work on unvented
systems.
Malfunction Cause Solution
Cylinder
The cylinder cools down at night.
After the solar pump is switched o, the supply and return lines have dierent
temperatures. The collector temperature is higher than the air temperature at night.
Reheating is not working. The Gas-red
boiler runs for a short time,
goes o and then back on again. This is
repeated until the cylinder is at its target temperature.
1. The anti-siphon valve is blocked. 1. Check the position of the blue handle.
2. One-pipe circulation in the case of short tube networks with low pressure loss.
1. Air in the reheating heat exchanger Bleed the reheating heat exchanger.
1. The cold and hot water connections on the cylinder have been mixed up.
2. Hot water thermostat mixer set too low. Increase the setting.
3. Solar heating insucient; gas-red boiler does
not reheat. External control device is faulty.
Air in the reheating heat exchanger.
2. Check the anti-siphon valve for tightness (jammed cuttings, particles of dirt in the sealing face).
3. Do not connect the solar heat exchanger
directly; instead, rst pull the supply lines
downwards and then upwards to the collector (the siphon supports the antisiphon valve) or mount a 2-way valve which is switched at the same time as the solar pump.
Install an anti-siphon valve (as close as possible to the cylinder).
Turn o the cold water supply, then let water ow out via the hot water connection. Only a few litres of water ow out if the connection is laid
correctly. The hot water withdrawal pipe intake is then in the air space and further draining is not possible. If it is possible to empty the entire cylinder via the hot water connection, the connections have been laid incorrectly. Change the connections!
Check whether the gas-red boiler is working.
Check whether the external control device is working. Check that the 2-way valve is in the DHW position. Replace the 2-way valve. Bleed the reheating heat exchanger.
Water ows out of the expansion relief
valve (only when heating up).
- 24 -
Cylinder sensor is faulty.
Dirt on the valve seat of the expansion relief valve.
Pressure limiting valve is faulty. If water only escapes during heating, switch
Expansion vessel is faulty. Check the pressure in the expansion vessel.
Expansion relief valve is faulty. If the pressure is normal, replace the expansion
Check the safety thermostat and suppress the fault. Replace the cylinder thermostat.
Check the seat of the expansion relief valve and suppress the fault.
o the gas-red boiler and electric immersion
heater and check whether the pressure behind the pressure limiting valve is lower than 3.0 bar. If so, replace the pressure limiting valve.
If the pressure is insucient, reestablish the
pressure and check whether the expansion vessel maintains it.
relief valve.
0020115479_03 - 10/12 - Glow-worm
MAINTENANCE
Water ows out of the temperature/pressure
relief valve (only during heating up).
Only connection wiring diagram 6: The safety thermostat for the reheating circuit actuated at 80 ºC, thus causing the 2-way motorised valve to close the supply line to the cylinder.
There is dirt on the valve seat of the temperature/pressure relief valve.
The temperature control system for
the gas-red boiler is faulty.
Cylinder sensor is faulty. Check the cylinder sensor and corresponding
The 2-way valve is faulty. Check the function of the 2-way valve and
Temperature and pressure relief valve is faulty.
Electric immersion heater is faulty. Check the temperature sensor of the electric
The cylinder has been overheated by the solar circuit.
Check the seat of the temperature/pressure relief valve and suppress the fault.
If water is only escaping when being heated up
by the gas-red boiler, check the temperature control system of the gas-red boiler.
Check whether the 2-way valve switches to the heating position when the cylinder temperature is reached.
safety thermostat, replace the cylinder sensor if necessary, and suppress the safety thermostat fault.
replace if necessary.
If water is only escaping when being heated up by the electric immersion heater, replace the temperature/pressure relief valve.
immersion heater and the corresponding safety thermostat and replace the electric immersion heater if necessary.
Set the maximum cylinder temperature (MAXT
1) on the solar controller to a maximum temperature of 70 Use the fuses to deenergise the cylinder thermostat. Unscrew the cover cap of the reset button for the safety thermostat (TCO) for the reheating circuit. Press the reheating circuit TCO button to suppress the TCO fault. Mount the cover cap. Switch on the cylinder thermostat using the fuses.
o
C.
12 Recycling and disposal
Both the cylinder and its transport packaging are made primarily of recyclable raw materials.
12.1 Cylinder disposal
You must not dispose of the cylinder or any of its accessories in normal domestic rubbish.
• Dispose of the old unit and any accessories properly and in accordance with national regulations.
12.2 Disposal of packaging
Arrange for the recognised heating engineer who installed the unit to dispose of the transport packaging.
0020115479_03 - 10/12 - Glow-worm
- 25 -
MAINTENANCE
13 Customer service and manufacturer's
warranty
13.1 Glow-worm service
To ensure regular servicing, it is strongly recommended that arrangements are made for a Maintenance Agreement. Please contact Glow-worm Service (Tel. No. 01773 828100) for further details.
13.2 Glow-worm warranty
Glow-worm provides a full parts and labour warranty for this appliance.
The appliance and all associated pipe work and controls must be installed by suitably competent persons in accordance with all current and relevant safety, building control and planning regulations and in full compliance with the manufacturer’s instructions.
All unvented domestic hot water cylinders must be installed by a competent person to the prevailing building regulations at the time of installation (G3).
Terms and conditions apply to the warranty, details of which can be found on the warranty registration card included with this appliance.
Failure to install and commission this appliance in compliance with the manufacturer’s instructions may invalidate the warranty
(this does not aect the customer’s statutory rights).
- 26 -
0020115479_03 - 10/12 - Glow-worm
14 Spare parts
Key No. Part No. Description
1 0020010155 Tundish
2 0020010154 Temperature and pressure relief valve
3 0020012036 Hot water expansion vessel assembly 18ltr
3 0020012037 Hot water expansion vessel assembly 25ltr
4 0020127614 Cylinder thermostat
5 0020127615 Solar thermostat
6 0020127613 Immersion heater seal
7 0020127611 Immersion heater
8 0020127609 Safety assembly
9 0020127610 Pressure relief valve
10 0020127608 2-way motorised valve
MAINTENANCE
3
10
1
9
8
2
4
5
0020115479_03 - 10/12 - Glow-worm
6
7
- 27 -
MAINTENANCE
SERVICE RECORD
It is recommended that your hot water system is serviced regularly and that the appropriate Service Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
SERVICE 1 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 2 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 3 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 4 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 5 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 6 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 7 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 8 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 9 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 10 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
MAINS PRESSURE HOT WATER STORAGE SYSTEM COMMISSIONING CHECKLIST
This Commissioning Checklist is to be completed in full by the competent person who commissioned the storage system as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission this equipment to the manufacturer’s instructions will invalidate the warranty but does not affect statutory rights.
Customer Name Telephone Number
Address
Cylinder Make and Model
Cylinder Serial Number
Commissioned by (print name) Registered Operative ID Number
Company Name Telephone Number
Company Address
Commissioning Date
To be completed by the customer on receipt of a Building Regulations Compliance Certificate
Building Regulations Notification Number (if applicable)
:
*
ALL SYSTEMS PRIMARY SETTINGS (indirect heating only)
Is the primary circuit a sealed or open vented system? Sealed
What is the maximum primary flow temperature?
ALL SYSTEMS
What is the incoming static cold water pressure at the inlet to the system?
Has a strainer been cleaned of installation debris (if fitted)? Yes
Is the installation in a hard water area (above 200ppm)? Yes
If yes, has a water scale reducer been fitted? Yes
What type of scale reducer has been fitted?
What is the hot water thermostat set temperature?
What is the maximum hot water flow rate at set thermostat temperature (measured at high flow outlet)?
Time and temperature controls have been fitted in compliance with Part L of the Building Regulations? Yes
Type of control system (if applicable) Y Plan
Is the cylinder solar (or other renewable) compatible? Yes
What is the hot water temperature at the nearest outlet?
All appropriate pipes have been insulated up to 1 metre or the point where they become concealed Yes
UNVENTED SYSTEMS ONLY
Where is the pressure reducing valve situated (if fitted)?
What is the pressure reducing valve setting?
Has a combined temperature and pressure relief valve and expansion valve been fitted and discharge tested? Yes
The tundish and discharge pipework have been connected and terminated to Part G of the Building Regulations Yes
Are all energy sources fitted with a cut out device? Yes
Has the expansion vessel or internal air space been checked? Yes
THERMAL STORES ONLY
What store temperature is achievable?
What is the maximum hot water temperature?
Open
No
No
No
S Plan
Other
No
No
No
No
bar
l/min
bar
°C
°C
°C
°C
°C
ALL INSTALLATIONS
The hot water system complies with the appropriate Building Regulations Yes
The system has been installed and commissioned in accordance with the manufacturer’s instructions Yes
The system controls have been demonstrated to and understood by the customer Yes
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
Commissioning Engineer’s Signature
Customer’s Signature
(To confirm satisfactory demonstration and receipt of manufacturer’s literature)
llA installations in England and Wales must be notified to Local Authority Building Control (LABC) either directly or through a Competent Persons Scheme.
*
A Building Regulations Compliance Certificate will then be issued to the customer.
©Heating and Hotwater Industry Council (HHIC) www.centralheating.co.uk
- 28 -
0020115479_03 - 10/12 - Glow-worm
SERVICE RECORD
INSTALLATION
It is recommended that your hot water system is serviced regularly and that the appropriate Service Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
SERVICE 1 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 3 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 5 Date
Engineer Name
Company Name
Telephone Number
Comments
SERVICE 2 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 4 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 6 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 7 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 9 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
0020115479_03 - 10/12 - Glow-worm
Signature
SERVICE 8 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
SERVICE 10 Date
Engineer Name
Company Name
Telephone Number
Comments
Signature
- 29 -
GLOW-WORM
Subject to engineering changes
0020115479_03 - 10/12
Nottingham Road, Belper, Derbyshire. DE56 1JT
www.glow-worm.co.uk
Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.
Loading...