Thank you for installing a new Glow-worm appliance in your home.
Glow-worm appliances are manufactured to the very highest standard so we are pleased to offer
our customers a Comprehensive First Year Guarantee. We recommend you complete and return
as soon as possible your guarantee registration card.
If your guarantee registration card is missing you can obtain a copy or record your registration by
telephoning the Glow-worm Customer Service number 01773 828100.
Customer Service:
01773 828100
Technical Helpline:
01773 828300
General and Sales enquiries:
Tel. 01773 824639
Fax: 01773 820569
To register your Glow-worm appliance
call:
0800 0732142
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided
with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s
instructions by a competent person approved at the time by the Health and Safety Executive and that it meets the requirements of
the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations
and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of
Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme.
Visit www.central heating.co.uk for more information.
2
These instructions consist of, Installation, Servicing, Fault Finding, Replacement of Parts
and Spares. The instructions are an integral part of the appliance and must, to comply
with the current issue of the Gas Safety (Installation and Use) Regulations, be handed to
the user on completion of the installation.
CONTENTSDESCRIPTIONSECTIONPAGE
INTRODUCTION
INSTALLATION
Warnings
Important Information
Statutory Requirements
Boiler Design
Safety Devices
Servicing, Maintenance and Spare Parts
Boiler Specication
Boiler Components
Boiler Dimensions and Hydraulic Schematic
Boiler Location, Clearances and Ventilation
Flue Options and Terminal Clearances
Water System - Heating
Water System - Domestic Hot Water
Installation Preparation
Boiler Fixing / Gas / Water / Safety Discharge Connection
System Pipes and Condensate Connection
Condensate Connections
Telescopic Flue - Length, Preparation and Installation
Standard Flue - Length, Preparation and Installation
Vertical Flue - Length, Preparation and Installation
Twin Flue - Length, Preparation and Installation
Plume Management Kit
Electrical Connection
Commissioning
2
3
4
5
5
6
7
8
8
9
9
9
9
9
10
11
4
4
5
6
6
7
8
9
10
11
12
14
15
16
18
19
20
21
25
29
32
35
35
38
MAINTENANCE
Servicing
Fault Finding
Replacement of Parts
Spare Parts
Manual Handling
Declaration of Conformity
12
13
14
15
16
17
46
50
56
64
66
67
3
WARNINGS
Gas Leak or Fault
Turn off the gas emergency control valve immediately. Eliminate all sources of ignition, i.e.smoking, blowlamps,
hot air guns etc. Do not operate electrical lights or switches either on or off. Open all doors and windows,
ventilate the area.
Metal Parts
This boiler contains metal parts (components) and care should be taken when handling and cleaning,
with particular regard to edges.
Sealed Components
Under no circumstances must the user interfere with or adjust sealed parts.
Important Information
Gas Category
This boiler is for use only on G20 natural gas.
Control of Substances Hazardous to Health
Under Section 6 of The Health and Safety at Work Act
1974, we are required to provide information on substances
hazardous to health.
The adhesives and sealants used in this appliance are cured
and give no known hazard in this state.
CAUTION:
While there are no substances harmful to health contained
within this boiler, some component parts of the boiler
(insulation pads, gaskets and rope seals) are manufactured
from man made bres. When damaged or broken these bres
may cause a temporary irritation. High dust levels may irritate
eyes and upper respiratory system. It is important therefore,
that sensible precautions are applied when exchanging
components.
If you have a history of skin complaint you may be susceptible
to irritation.
Normal handling should not cause discomfort, but follow good
hygiene and wash your hands before eating, drinking or going
to the lavatory.
If you suffer irritation to the eyes or severe irritation to the skin
seek medical advice.
Manual Handling
With regards to the “Manual Handling Operations, 1992
Regulations”, the appliance exceeds the recommended
weight for a one man lift, refer to section 16 for more
information.
The handling of the boiler may involve lifting, pushing and
pulling, the use of a sack truck may be required.
The following handling techniques and precautions should be
considered:
- Grip the boiler at its base
- Be physically capable
- Use safety clothing where appropriate, e.g. gloves, safety
footwear.
Ensure safe lifting techniques are used
- Keep back straight.
- Avoid twisting at the waist.
- Avoid upper body/top heavy bending.
- Always grip using the palm of the hand.
- Use designated hand holds.
- Keep load as close to body as possible.
- Always use assistance if required.
Electrical Supply
The boiler MUST be earthed.
All system components shall be of an approved type and all
wiring to current I.E.E. wiring regulations.
External wiring must be correctly earthed, polarised and in
accordance with the relevant standards.
In GB, this is BS 7671.
In IE, this is the current edition of ETCI rules.
The boiler MUST be connected to a permanent 230V ac,
50Hz supply.
Connection of the whole electrical system of the boiler,
including any heating controls, to the electrical supply MUST
be through one common isolator and must be fused 3 Amp
maximum.
Isolation should be by a double pole switched fused spur box,
with a minimum gap of 3mm for both poles. The fused spur
box should be readily accessible and preferably adjacent to
the appliance. It should be identied as to its use.
Alternatively connection can be made through an unswitched
shuttered socket and 3A fused 3-pin plug both to the current
issue of BS 1363, provided they are not used in a room
containing a bath or shower.
Wiring to the boiler must be PVC 85°C insulated cable, not
less than 0.75mm2 (24/0.20mm).
Testing and Certication
This boiler is tested and certicated for safety and performance. It is, therefore, important that no alteration is made to
the boiler, without permission, in writing, by Glow-worm.
Any alteration not approved by Glow-worm, could invalidate
the certication, boiler warranty and may also infringe the
current issue of the statutory requirements.
4
Statutory Requirements
CE Mark
This boiler meets the requirements of Statutory Instrument,
No. 3083 The Boiler (Efciency) Regulations, and therefore is
deemed to meet the requirements of Directive 92/42/EEC on
the efciency requirements for new hot water boilers red with
liquid or gaseous fuels.
Type test for purposes of Regulation 5 certied by:
Notied body IMQ 51BP2727 CE Directives 90/396/EEC.
51BP2728DR CE Directives 92/42/EEC.
Product/production certied by:
Notied body IMQ 51BP2727 CE Directives 90/396/EEC.
51BP2728DR CE Directives 92/42/EEC.
The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws
of the Member States relating to appliances burning gaseous
fuels.
2. Directive 73/23/EEC on the harmonisation of the Laws of
the Member States relating to electrical equipment designed
for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of
the Member States relating to electromagnetic compatibility.
IMPORTANT
Where no British Standards exists, materials and equipment
should be t for their purpose and of suitable quality and
workmanship.
The installation of this boiler must be carried out by a
competent personapproved at the time by the Health and
Safety Executive and in accordance with the rules in force in
the countries of destination.
Manufacturer’s instructions must not be taken as overriding
statutory requirements.
NOTE: For further information, see the current issue of the
Building Regulations, approved document L1 ( in the UK) and
the following current issues of:
1) Central heating system specication (CheSS)
and
2) Controls for domestic central heating system and hot water.
BRECSU.
Gas Supply
The gas installation must be in accordance with the relevant
standards.
In GB, this is BS6891.
In IE, this is the current edition of I.S.813 “Domestic Gas
Installations”.
The internal diameter of the gas supply from the governed
meter to the boiler’s gas inlet connection must not be less
than 22mm.
The supply from the governed meter must be of adequate size
to provide a steady inlet working pressure of 20mbar (8in wg)
(for natural gas) at the boiler. In addition to the demand of any
other gas appliances being serviced from that supply.
On completion, test the gas installation for tightness using the
pressure drop method and suitable leak detection uid, purge
in accordance with the above standard.
Domestic Hot Water
All domestic hot water circuits, connections, ttings must be
in accordance with the relevant standards and water supply
regulations.
GB: Guidance G17 to G24 and recommendation R17 to R24
of the Water Regulations Guide.
IE: The current edition of I.S.813 “Domestic Gas Installations”.
Statutory Requirements
In GB, the installation of the boiler must comply with the
requirements of the current issue of BS6798 and be carried
out by a competent personapproved at the time by the
Health and Safety Executive and as described in the following
regulations:
The manufacturer’s instructions supplied.
The Gas Safety (Installation and Use) Regulations.
The appropriate Buildings Regulations either The Building
Regulations, The Building Regulations (Scotland), The
Building Regulations (Northern Ireland).
The Water Fittings Regulations or Water byelaws in Scotland.
The Health and Safety at Work Act, Control of Substances
Hazardous to Health (COSHH).
The Current I.E.E. Wiring Regulations.
Where no specic instructions are given, reference should be
made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent
person approved at the time by the Health and Safety
Executive and installed in accordance with the current edition
of I.S.813 “Domestic Gas Installations”, the current Building
Regulations and reference should be made to the current
ETCI rules for Electrical Installation.
GB: the following Codes of Practice apply:
BS4814, BS6798, BS5440 Part 1 and 2, BS5546 Part 1,
BS5449, BS6891, BS6700, BS7074 Part 1 and 2, BS7593,
BS7671.
IE: I.S.813, BS5546, BS 5449, BS 7074, BS 7593.
Heating System
In GB, it is necessary to comply with the Water Supply (Water
Fittings) Regulations 1999 (for Scotland, the Water Byelaws
2000, Scotland).
To comply with the Water regulations your attention is drawn
to: The Water Regulations guide published by the Water
Regulations Advisory Service (WRAS) gives full details of the
requirements.
In IE, the requirements given in the current edition of I.S.813
“Domestic Gas Installations” and the current Building
Regulations must be followed.
5
Boiler Design
Boiler Design
These boilers are designed for use as part of a sealed water
central heating system with fully pumped circulation. The
pump, expansion vessel and associated safety devices are all
tted within the boiler.
The appliance has a built in frost protection device that
protects the boiler from freezing.
Once the controls are set the boiler operates automatically.
Safety Devices
Electrical Supply Failure
The boiler will not work without an electrical supply.
Normal operation of the boiler should resume when the
electrical supply is restored.
Reset any external controls, to resume normal operation of
the central heating.
If the boiler does not resume normal operation reset the
appliance. If the boiler does not resume normal operation
after this call your Installation/Servicing company or
Glow-worm service.
Overheating Safety
The boiler software is designed to recognise the potential for
an overheat (Boiler Lockout). The temperature of the water
owing from the primary heat exchanger is monitored by an
overheat thermostat located on the outlet pipe. If the water
temperature gets too hot the switch opens, cutting off the
electrical supply to the gas valve and causing the boiler to
‘Lockout’. Once activated the boiler has to be manually re-set
by switching the control knob off (for 15 seconds) and on
again.
Low Water Pressure
A hydraulically operated primary pressure sensor monitors
water pressure or water shortage in the primary hydraulic
circuit and will switch the boiler off if the pressure is below
0.3bar. The boiler will not operate until the circuit has been
re-pressurised.
Flue Blockage
For HK type; an air pressure switch situated in the boiler’s
fan compartment monitors the boiler’s ue operation. If a
partial obstruction within the ue occurs the fan will continue
operating but the boiler’s burner will shut down until the
blockage is cleared.
Condensate Drain
A plastic drain pipe must be tted to allow discharge of
condensate to a drain. Condensate should, if possible, be
discharged into the internal household draining system. If
this is not practical, discharge can be made externally into
the household drainage system or a purpose designed soak
away, see section 9 for more details.
Pluming from ue terminal
Like all condensing boilers this appliance will produce a plume
of condensation from the ue terminal in cool weather. This is
due to the high efciency and hence low ue gas temperature
of the boiler.
This is normal and not an indication of a fault.
Frost protection
The boiler’s control unit has in-built frost protection device
that res the boiler’s burner when the temperature of primary
hydraulic water falls below 6°C. The device works irrespective
of any room thermostat setting and will protect the complete
heating system. On reaching a water temperature of 15°C the
boiler reverts to normal operation.
NOTE: If the boiler will not be used for long periods of time
during cold weather, in order to avoid freezing the electric
supply must be left ON and all the central heating isolation
valves must be left open. The internal frost protection device
will then operate the boiler if the temperature falls too low.
However, if the electrical supply is to be turned off the boiler,
the heating system and domestic hot water circuit must be
drained.
Safety Discharge Valve
A safety discharge valve and discharge pipe are tted to the
boiler. This valve must not be touched. Should there be any
discharge from the pipe, isolate the boiler electrical supply and
call your installer or Glow-worm’s own service organisation
using the telephone number on the inside front cover of this
booklet.
Condensate Drain Blockage
As a safety feature the boiler will stop working if the
condensate drain becomes blocked. During freezing
conditions this may be due to the forming of ice in the
condense drain external to the house. Release an ice
blockage by the use of warm cloths on the pipe, the boiler
should then restart.
NOTE: If the boiler fails to resume normal operation and
all external controls are calling for heat, then call your
Installation/Servicing company or Glow-worm service.
6
Servicing, Maintenance and Spare Parts
Servicing and Maintenance
To ensure the continued efcient and safe operation of the
boiler it is recommended that it is checked and serviced as
necessary at regular intervals. The frequency of servicing will
depend upon the particular installation conditions and usage,
but in all cases the boiler must be serviced at least once a
year.
If this appliance is installed in a rented property there is a duty
of care imposed on the owner of the property by the current
issue of the Gas Safety (Installation and Use) Regulations,
Section 35.
Servicing/maintenance should be carried out by a competent person in accordance with the rules in force in the countries
of destination.
To obtain service, please call your installer or Glow-worm’s
own service organisation using the telephone number on the
inside front cover of this literature.
“Benchmark” scheme
Glow-worm support the Benchmark initiative. It is very
important that the Installation, Commissioning and Service
Record is completed by the installation engineer and handed
over to the user.
Spare Parts
Remember, when replacing a part on this appliance, use
only spare parts that you can be assured conform to the
safety and performance specication that we require. Do not
use reconditioned or copy parts that have not been clearly
authorised by Glow-worm.
If a part is required contact Glow-worm’s own service
organisation.
Please quote the name of the appliance, this information will
be on the name badge on the front of the appliance.
If in doubt seek advice from the local gas company or Glowworm’s own service organisation using the telephone number
on the inside front cover of this booklet.
7
Boiler Specication
Boiler Design
These boilers are designed for use as part of a sealed water
central heating system with fully pumped circulation. The
pump, expansion vessel and associated safety devices are all
tted within the boiler.
BOILER SPECIFICATION 24c 30c
Lift weight 37 kg (82 Ib) 38 kg (84 Ib)
Total weight (installed) 40 kg (88 Ib) 41 kg (90 Ib)
Gas supply (governed meter only - NG)* G20 - NG /G31 - Propane G20 - NG /G31- Propane
Gas category II
Inlet gas working pressure - NG 20 mbar 20 mbar
Heat input maximum 25.7 kW. 28.5 kW.
Heat output maximum 24.7 kW. 27.6 kW.
Heat input minimum 11 kW. 11 kW.
Heat output minimum 10.2 kW. 10.2 kW.
Usefull efficiency at 100% load 96% 96.8%
Usefull efficiency at 30% load 102.4% 103.3%
Burner injector NG / LPG (G31) 1.20 mm / 0.75mm 1.15 mm / 0.75mm
Burner pressure maximum NG** 12.5 mbar 14 mbar
Burner pressure minimum NG 2.5 mbar 2.3 mbar
SEDBUK rating Band B 86.0% Band 86.4%
NOx Class 3 Class 3
Flue Type C12-C32-C42-C52 C12-C32-C42-C52
Δ T 9.4
The appliance has a built in frost protection device that
protects the boiler from freezing.
Once the controls are set the boiler operates automatically.
L/min.
2H3P
10.5
L/min.
II
2H3P
14343
* See Commissioning section for NG (G20) to LPG (G31) conversion
** Installation to (G31) Propane is by conversion kit only
8
12
h
e
r
Condensing Unit (Turbo heat exchanger)
11
10
Boiler Components
e
t
a
t
r
A
131415
14532
e
r
h
e
t
a
t
r
A
16
9
17
8
18
7
6
r
a
e
r
e
5
h
t
t
A
4
3
2
1
A
DCB
E
19
20
21
22
23
24
25
A -Heating Flow(22mm)
B -D.H.W. Outlet (15mm)
C -Gas Inlet (22mm)
D -Cold Water Inlet (15mm)
E -Heating Return (22mm)
All dimensions are given in millimetres (except as noted).
The general arrangement of the boiler is shown in diagram
2.1 and the hydraulic and gas schematics diagrams, showing
the central heating hydraulic circuit and domestic hot water
hydraulic circuit in diagram 2.2.
The data label is positioned on the control box back cover.
14335
130 130
CONDENSATE
CONNECTION
50
C
L
BOILER
86 86
98
30
SDV
outlet
10
151 151
405 24c
430 30c
CENTRAL HEATING
DOMESTIC WATER
Diagram 2.2Diagram 2.1
3 Boiler Location, Clearances and Ventilation
20
3.1 Location
This boiler is not suitable for outdoor installation.
This boiler may be installed in any room, although particular
attention is drawn to the installation of a boiler in a room
containing a bath or shower where reference must be made to
the relevant requirements.
This boiler is suitable for installation in bathroom zones 2 and
3.
In GB this is the current I.E.E. WIRING REGULATIONS and
BUILDING REGULATIONS.
In IE reference should be made to the current edition of
I.S.813 “Domestic Gas Installations” and the current ETCI
rules.
3.2 Clearances
The boiler should be positioned so that at least the minimum
operational and servicing clearances are provided, see
diagram 3.1.
Additional clearances may be benecial around the boiler for
installation and servicing.
For ue installations where external access is not practicable,
consideration should be given for the space required to insert
the ue internally, which may necessitate clearance larger
than those specied in diagram 3.1.
3.3 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it
should be tted in accordance with the Institute of Gas
Engineers document IGE/UP/7/1998. If in doubt seek advice
from local gas undertaking or Glow-worm.
3.4 Combustible Material
The boiler and ue are suitable for installation onto and
through combustible materials provided that:-
1) The boiler must be sited at least 1m away from ammable
materials and heat sensitive walls must be protected by
appropriate insulation.
2) Minimum 5 mm clearance is maintained around the
circumference of the ue (air intake).
3) The combustible surface and xings are suitable for
supporting the load.
4) The minimum clearances from the boiler case are
maintained.
3.5 Room Ventilation
The boiler is room sealed so a permanent air vent is not
required.
3.6 Cupboard or Compartment Ventilation
If the boiler is installed in a compartment there must be
purpose made ventilation for cooling purposes.
Make sure the cupboard or compartment air vents are
positioned to be clear of obstructions at all times.
A compartment used to enclose the boiler must be designed
and constructed specically for this purpose.
An existing cupboard or compartment modied for the
purpose may be used. Refer to the current issue of BS6798
for guidance.
14344
20
600
20
200
20
2020
300
HI LO
Betacom 24c128.5cm²128.5cm²
Betacom 30c142.5cm²142.5cm²
KEY
NON COMBUSTIBLE MATERIAL
Diagram 3.1
11
4 Flue Options and Terminal Clearances
Top horizontal telescopic ue (Ø60/100)
Part No. A2043600 - Section 9, page 21
Top horizontal standard ue (Ø60/100)
Part No. A2043400 - Section 9, page 25
Plume Management Kit
basic set, white, concentric ue
(Ø60/100) - Part No. A2044100 for
use with Part No. A2043400 and Part
No. A2043600 - Section 9, page 35
A DIRECTLY BELOW AN OPENING, AIR BRICK,
OPENING WINDOWS 300
B ABOVE AN OPENING, AIR BRICK,
OPENING WINDOWS 300
C HORIZONTALLY TO AN OPENING,
AIR BRICK, OPENING WINDOWS 300
D BELOW GUTTER, DRAIN/SOIL PIPE 25
E BELOW EAVES 25
F BELOW A BALCONY OR CAR PORT 25
G FROM VERTICAL DRAIN PIPES AND SOIL PIPES 25
H FROM INTERNAL/EXTERNAL CORNERS 25
H* TO A BOUNDARY ALONGSIDE THE TERMINAL 300
I ABOVE ADJACENT GROUND OR BALCONY LEVEL 300
J* FROM SURFACE OR A BOUNDARY
FACING THE TERMINAL 600
K FACING TERMINALS 1200
L FROM OPENING (DOOR/WINDOW) IN CAR PORT INTO DWELLING 1200
M VERTICAL FROM A TERMINAL 1500
N HORIZONTALLY FROM A TERMINAL 300
4.1 Flue Options
There are various ue options to choose from as illustrated in
diagram 4.1. The ue lengths and installation are described in
section 9.
4.2 Flue Terminal Position
In GB the minimum acceptable siting dimensions for the
terminal from obstructions, other terminals and ventilation
openings are shown in diagram 4.2.
In IE the minimum distances for ue terminal positioning must
be those detailed in I.S.813 “Domestic Gas Installations”.
The terminal must be exposed to the external air, allowing free
passage of air across it at all times.
Being a condensing boiler some pluming may occur from
the ue outlet. This should be taken into consideration when
selecting the position for the terminal.
Carports or similar extensions of a roof only, or a roof and
one wall, require special consideration with respect to any
openings, doors, vents or windows under the roof. Care is
required to protect the roof if made of plastic sheeting. If
the carport comprises of a roof and two or more walls, seek
advice from the local gas supply company before installing the
boiler.
H* and J* See diagram 4.2. These dimensions comply with
the building regulations, but they may need to be increased to
avoid wall staining and nuisance from pluming depending on
site conditions.
4.3 Terminal Guard
A terminal guard is required if persons could come into contact
with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide
minimum of 50mm clearance from any part of the terminal and
be central over the terminal.
The guard should be similar to that shown in diagram 4.3.
A suitable guard is manufactured by: Tower Flue Components
Morley Rd.
Tonbridge
Kent TN9 1RA.
Size: 280mm x 280mm x 270mm.
12325
VERTICAL FLUES
P FROM ANOTHER TERMINAL 600
Q ABOVE ROOF LEVEL 300
R FROM ADJACENT OPENING WINDOW 1000
S FROM ADJACENT WALL TO FLUE 300
Diagram 4.2
Diagram 4.3
13
5 Water System - Heating
5.1 General
The boiler is designed to operate on fully pumped,
pressurised sealed systems operating at a maximum of 3bar
pressure and maximum design ow temperature of 85°C.
5.2 Safety Valve
The safety valve is an integral part of the boiler and it cannot
be adjusted.The pipe from the safety discharge valve must
not discharge above an entrance, window or any type of
public access area.
5.3 Expansion Vessel
The boiler’s integral expansion vessel with a capacity of 7
litres (1.5 gallons), is pre-charged to a pressure of 0.5bar
and will accommodate a system volume of 125 litres at an
average water temperature of 75°C and maximum system
pressure of 3 bar. NOTE: The expansion vessel volume
depends on the total water system volume and the initial
system design pressure. In GB, Guidance on vessel sizing is
also given in the current issue of BS5449 and BS7074 Part 1.
In IE, current edition of I.S.813 “Domestic Gas Installations”.
If the system volume is more than 125 litres. an additional
expansion vessel must be tted to suit the size of the system.
A typical installation of an additional pressure vessel is shown
in diagram 5.1.
5.4 Flow Rate
If it is necessary to alter the ow rate, the system can be
tted with a lockable balancing valve in the main ow or
return pipes shown as valve “A” in diagram 5.1. The ow rate
through the boiler must not be allowed to fall below that given
in Boiler Specication Table.
The heating circuit should be designed and balanced to give a
20°C temperature rise across the boiler ow and return.
5.5 Water Treatment
Existing system- It is ESSENTIAL that prior to installing the
new boiler the system is thoroughly ushed.
New system- For optimum performance after installation, the
boiler and its associated central heating system should also
be ushed.
Flushing should be carried out in accordance with BS7593:
2006 using a cleanser such as Sentinel X300 or X400, Fernox
Restorer or Salamander corrosion guard cleaner.
IMPORTANT: Ensure all cleanser is removed from the whole
system before adding an inhibitor.
Although the boiler is designed to inhibit the formation of
scale, in hard water areas above 200mg/l, a proprietary scale
reducer should be tted in the cold water supply to the boiler.
Failure to comply with this requirement may invalidate your
guarantee. Refer to the current issue of BS 5449 and BS
7593 on the use of inhibitors in central heating systems.
14561
Diagram 5.1
5.6 General
On installation it is important to ensure that the heat
exchanger is not a natural collecting point for air and where
possible, the system pipe work should have a gradient to
ensure any excess air is carried naturally to other purpose
made, air release points.
In high water volume systems or under oor heating systems
where prolonged operation of the boiler is expected at
temperatures below 600C, a by-pass must be installed on the
boiler outlet in order to prevent condensation forming inside
the boiler body. Failure to comply with this requirement will
invalidate the manufacturer’s guarantee.
5.7 Bypass
The system’s water must always be allowed to circulate
whenever the circulation pump is running. A return by-pass
must be provided.
NOTE: It is no longer permissible to use non-thermostatic
radiator valves to allow by-pass through a radiator.
Diagram 5.2 shows the pump head remaining for the heating
system depending on the bypass setting and the speed
setting of the pump, see section 12 Commissioning.
Ensure that under no circumstances does the ow rate drop
below the gure specied, refer to Boiler Specication Table.
5.8 Filling the Sealed System
With water via the lling loop, see diagram 5.3, (the lling loop
is not supplied with the boiler).
14
5.9 Draining Points
Draining taps must be provided at all low points of the system,
which will allow the entire system to be drained.
Draining taps shall be to the current issue of BS2879.
5 Water System - Domestic Hot Water
H (m)
5.10 Water Pressure
To obtain the best hot water performance from your boiler it is
suggested that the cold water supply to the boiler is the rst
draw off from the incoming mains supply.
NOTE: The boiler will not operate unless there is a minimum
pressure of 0.25 bar (3.6 Ibf/in2) with a ow rate of 2.5 l/min.
The minimum working pressure to obtain the maximum
domestic ow is:-
24c 0.7 bar (10.15 Ibf/in
30c 0.7 bar (10.15 Ibf/in
The maximum working pressure of the domestic hot water
circuit is 8 bar. If the cold water supply pressure exceeds this,
then a pressure-reducing valve must be tted in the supply to
the boiler.
Where cold water mains are tted with a water meter, check
valve(s) or loose jumper stopcock, a domestic hot water mini-
expansion vessel may need to be tted.
To obtain the best hot water performance from your boiler it is
suggested that supplies to faucets are run in 15mm copper,
as short as possible and where practical, be insulated to
reduce heat loss.
2
)
2
)
5.11 ‘Hard’ Water Areas
The temperatures within the heat exchanger are limited by
the boiler control system to minimise scale formation within
the hot water pipework. However, in areas where the water is
‘hard’ (i.e. more than 200mg/litre), it is recommended that the
hot water setting is reduced and that a scale reducer is tted,
refer to the manufacturer’s instructions or consult the local
water company for additional advice.
7
6
5
4
3
2
1
0
0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5
QH Chart
Q (m
Diagram 5.2
3
14562
/h)
14024
Diagram 5.3
15
6 Installation Preparation
CHECK IF 230V thermostat plug is
required to t to PCB board.
WALL HANGING
BRACKET
SEALING
WASHERS
(5 OFF)
WALL
TEMPLATE
CONDENSATE
OUTLET PIPE
6.1 Appliance Pack
Please check the contents of the carton:
Appliance, Isolation Valves, Wall Hanging Bracket,
Wall Template, Service Installation and User Manual,
Guarantee Card and Benchmark Log Book, see diagram 6.1.
(Literature and appliance not illustrated)
Handling
IMPORTANT: With regards to the Manual Handling
Operations, 1992 Regulations, the following lift operation
exceeds the recommended weight for a one man lift, refer to
section 17 Manual Handling.
To remove the appliance, refer to diagram 6.2.
1. Carefully slit or remove the sealing tape being
careful not to scratch the appliance door.
2. Fully open the carton lid and remove any instructions
and components.
3. Read the instructions carefully before installation of
the appliance.
4. Roll the carton onto its open face.
5. Lift the carton free of the inner packaging.
6. Remove the mounting bracket and valve package.
14339
COLD WATER
FILTER
D.H.W
OUTLET
C.H. ISOLATION
VALVE RETURN
COLD WATER
ISOLATION VALVE INLET
GAS ISOLATION VALVE
SAFETY
DISCHARGE
C.H. ISOLATION
PIPE
VALVE FLOW
Diagram 6.1
7. Stand the boiler on its base within the expanded
polystyrene block and remove the top packaging piece.
8. If you wish to remove the expanded polystyrene base lie
the appliance on its back to do so.
6.2 Site Requirements
The boiler mounting wall should be suitable for the weight of
the appliance and be true and at.
NOTE: Due to the varied site conditions we do not supply
xings and advise that the installer should supply those which
are suitable.
16
12
14594
5
3
4
Diagram 6.2
6 Installation Preparation
6.3 Wall Template
Take the wall template from the document pack and place in
the desired position on the wall, giving due consideration to
the required boiler clearances, see section 3, and the ue you
are tting.
Mark the position of the ue centre, if tting a side ue, extend
the ue centre line into the corner then 170mm along the
adjacent wall, see diagram 6.3.
For extended side ues, the ue hole centre should be
determined by extending the dashed inclined line on the
template to the side wall, then 149mm along the adjacent
wall, see diagram 6.2. This dashed line is drawn at 44mm/
metre (2.5°) rise from the boiler.
To allow for the ue passing through the wall at this angle
a 125mm hole should be drilled irrespective of internal or
external installation.
Remove the wall template whilst drilling the ue hole.
6.4 Flue Hole Cutting
External access ue installation can use a 105mm diameter
core drill.
Internal access only ue installation will need a 125mm
diameter core drill.
NOTE: The ue is designed with an internal fall of 44mm/
metre (2.5°), therefore the hole can be drilled horizontally.
If ue extension pipes are to be used then a core drill size of
125mm is required. This will allow the extension pieces to
slope at 44mm/metre (2.5°) towards the boiler.
14549
Diagram 6.3
6.5 Wall Hanging Bracket Assembly
The Wall Hanging Bracket is supplied in the main boiler
packaging.
Reposition the wall template over the ue hole and mark the
position of the xing holes for the hanging bracket.
NOTE: Due to the varied site conditions we do not supply
xings and advise that the installer should supply those which
are suitable.
Drill xing holes using a 8.5mm. drill bit and insert suitable
wall plugs. Secure the wall hanging bracket to the wall.
17
7 Boiler xing, Gas / Water / Safety Discharge Connections
14347
ISOLATION VALVES SHOWN CLOSED
7.1 System connection
Connect the isolation valves including sealing washers and
cold water inlet lter to the boiler ensuring the washers are
tted correctly, see diagram 7.1.
Make sure the isolation valves are closed.
7.2 Safety Discharge Pipe
Connect the safety discharge pipe, see diagram 7.2.
This must be extended, using not less than 15mm o.d. pipe,
to discharge, in a visible position, outside the building, facing
downwards, preferably over a drain.
To ease future servicing it is advisable to use a compression
type tting to extend the safety discharge valve tube.
The pipe must have a continuous fall and be routed to a
position so that any discharge of water, possibly boiling,
or steam cannot create any danger to persons, damage to
property or external electrical components and wiring.
7.3 Boiler Hanging
Lifting the boiler into position, lean the top of the boiler slightly
to the wall and position just above the hanging bracket. Lower
the boiler slowly onto the hanging bracket making sure the
boiler is located in the boiler mounting slots, see diagram 7.3.
IMPORTANT: With regards to the Manual Handling
Operations, 1992 Regulations, the following lift operation
exceeds the recommended weight for a one man lift, refer to
section 17 Manual Handling.
VIEWED FROM THE
REAR OF THE BOILER
Diagram 7.1
14348
Diagram 7.2
14346
18
Diagram 7.3
8 System Pipes and Condensate Connections
8.1 Condensate Trap Connection
A exible condensate outlet pipe is supplied and should be
used to couple the condensate trap to a 22mm to 25mm O.D.
non corrosive plastic pipe (overow pipe), see diagram 8.1.
NOTE: the pipe should have a fall of a least 2.5o 44mm/metre
away from the boiler.
Condensate should, if possible be discharged into the
household internal drainage system. If this is not practicable,
discharge can be allowed into the external household drains
or a purpose designed soak away, refer to diagram 8.3.
It is recommended that any external condensate drain pipe is
insulated and also preferably of 32mm diameter, to prevent
freezing in adverse weather conditions.
It is not necessary to provide air breaks or extra traps in the
discharge pipe as there is already a 75mm high trap inside
the boiler. Fitting an extra trap may cause the boiler siphon to
work incorrectly.
Refer to BS5546 or BS6798 for advice on disposal of boiler
condensate.
8.2 System Pipes Connection
Plumb gas and water system pipe work up to the isolation
valves using olives supplied, see diagram 8.2.
Do not subject isolation valves to heat.
The whole of the gas installation, including the meter, should
be inspected, tested for tightness and purged in accordance
with the current issue of BS6891 and in IE the current edition
of I.S.813 “Domestic Gas Installations”.
14527
CONDENSATE
TRAP
CONDENSATE
OUTLET PIPE
Diagram 8.1
14552
ISOLATION VALVES SHOWN CLOSED
Diagram 8.2
19
8 Condensate Connections
13000
20
Diagram 8.3
9 Telescopic Flue - Length, Preparation and Installation
Horizontal Telescopic Flue
14350
9.1 Flue Length and Restrictors
The maximum permissable horizontal ue length is 2.5 metres
plus the ue terminal assembly, this can be achieved by use
of the accessories, see diagram 9.3.
However should an additional 90º or 2 x 45º elbows be used
then the length MUST be reduced by 1 metre.
The diagram 9.1 shows the length achievable by using the kit
A2043600.
When extension pipes are used the ue system must be
designed to have a continuous fall to the boiler of at least 2.5º
44mm/metre to allow condensate to run back into the boiler
and out via the condensate drain.
The ue can be installed from inside the building, when
access to the outside wall face is not practicable.
The ue restrictor is supplied in the documentation pack, the
correct size is supplied for the boiler output:Betacom 24c - 83mmØ
Betacom 30c - 85mmØ
The flue restrictor must be fitted in the flue adaptor for,
concentric flue installations less than 1 metre and twin flue
installations less than 2 metres equivalent length.
Full instructions are provided in the documentation pack.
14470
Diagram 9.1
21
9 Telescopic Flue - Length, Preparation and Installation
14005
Diagram 9.2
15532
22
Diagram 9.3
9 Telescopic Flue - Length, Preparation and Installation
9.2 Horizontal Telescopic Flue - A2043600
Refer to diagram 9.2 for kit contents.
9.3 REAR Flue
If a wall thickness is between 210mm min. to 420mm max.
then the ue can be used without extensions.
Temporarily secure the ue elbow, measure the distance
from the outside wall to the butt joint, see diagram 9.4. If
the measurement ‘Y’ exceeds 525mm, then the appropriate
length of extension pipe is required.
If the dimension is less than 315mm DO NOT cut the ue, it
can project to a maximum of 600mm, refer to diagram 9.5. If
this is not desirable then a Standard ue MUST be used and
cut to length.
9.4 SIDE Flue
Temporarily secure the ue elbow, measure the distance
from the outside wall to the butt joint, see diagram 9.6. If
the measurement ‘Y’ exceeds 525mm, then the appropriate
length of extension pipe is required.
If the dimension is less than 315mm DO NOT cut the ue, it
can project to a maximum of 600mm, refer to diagram 9.5. If
this is not desirable then a Standard ue MUST be used and
cut to length.
14471
Diagram 9.4
12979
20
Diagram 9.5
14473
Diagram 9.6
23
9 Telescopic Flue - Length, Preparation and Installation
Diagram 9.7
12929
12977
9.5 Flue Fitting
With the air duct seams aligned and the ue set to the
required length ‘Y’, mark the securing hole position in the air
duct. Drill a 3mm diameter hole at this position, take care not
to pierce the inner ue duct. Secure with screw provided and
tape the joint, see diagram 9.7.
Fit the sealing collar onto the locating ring on the ue terminal,
see diagram 9.8.
With the ue elbow removed, push the ue assembly into
the wall, externally or internally, until the end of the assembly
protrudes a short way from the inside face of the wall. This
will enable the internal trim ring (if required) to be positioned
and allow the ue assembly to be drawn back up to the ue
elbow.
Secure the ue elbow in position on top of the boiler with the
four screws supplied.
Draw the ue assembly from wall and engage the ue duct
into the elbow and butt t between the air duct and ue elbow.
Check the correct alignment of the ue.
Fit the securing collar in position, mark through two of the pre
drilled holes in the securing collar. Remove securing collar
and drill two 3mm diameter holes one in the elbow and one in
the air duct, take care not to pierce the inner ue duct. Fit the
securing collar and secure with screws provided, see diagram
9.9.
Slide the internal trim ring back against the wall, securing in
place with a small amount of sealant if required.
The cut ducts must be de-burred and all lings and debris
removed.
Insert the ue duct into the air duct terminal assembly,
remembering to engage the catch within the terminal.
NOTE: If the seals require lubricant to ease installation, do not
use mineral oils or grease, water is recommended.
Diagram 9.8
Diagram 9.9
14474
24
9 Standard Flue - Length, Preparation and Installation
9.6 Flue Length
The maximum permissable horizontal ue length is 5.6 metres
for Betacom 24c and 4.6 metres for Betacom 30c, this can be
achieved by use of the accessories, see diagram 9.12.
However should additional 90º or 2 x 45º elbows be used then
the length MUST be reduced by 1 metre.
The diagram 9.10 shows the length achievable by using the
kit A2043400.
Standard Horizontal Flue
14475
When extension pipes are used the ue system must be
designed to have a continuous fall to the boiler of at least 2.5º
44mm/metre to allow condensate to run back into the boiler
and out via the condensate drain.
The ue can be installed from inside the building, when
access to the outside wall face is not practicable.
20mm
477.5mm
477.5mm
202.5
15533
202.5
Diagram 9.10
25
9 Standard Flue - Length, Preparation and Installation
13222
Diagram 9.11
15532
26
Diagram 9.12
9 Standard Flue - Length, Preparation and Installation
9.7 Standard Horizontal Flue - A2043400
Refer to diagram 9.11 for kit contents.
9.8 REAR Flue
Temporarily secure the ue elbow, measure the distance
from the outside wall to the butt joint, see diagram9.13. If
the measurement ‘Y’ exceeds 665mm, then the appropriate
length of extension pipe is required. The minimum dimension
is 180mm to suit a 75mm min wall thickness. The ue can
project to a maximum of 600mm, refer to diagram 9.14.
9.9 SIDE Flue
Temporarily secure the ue elbow, measure the distance
from the outside wall to the butt joint, see diagram 9.15. If
the measurement ‘Y’ exceeds 665mm, then the appropriate
length of extension pipe is required. The minimum dimension
is 262.5 to suit a minimum wall thickness of 75mm. The ue
can project to a maximum of 600mm, refer to diagram 9.14.
14471
Diagram 9.13
12979
20
Diagram 9.14
14473
Diagram 9.15
27
9 Standard Flue - Length, Preparation and Installation
Diagram 9.16
12847
14472
9.10 Flue Fitting
Remove the ue elbow.
Separate the ue duct from the terminal by twisting to release
the terminal catch, then pull out of the retaining seal, refer to
diagram 9.16.
The ue duct cutting length (L + 11mm.) is shown in diagram
9.16.
The air duct should be cut at the opposite end to the terminal
The plastic ue duct MUST be cut at the opposite end to the
terminal catch.
The plastic ue duct extensions MUST be cut at the opposite
end to seal.
The cut ducts must be de-burred and all lings and debris
removed.
Insert the ue duct into the air duct terminal assembly,
remembering to engage the catch within the terminal.
NOTE: If the seals require lubricant to ease installation, do
not use mineral oils or grease, only silicon grease or water is
recommended.
Fit the sealing collar behind the locating lugs on the ue
terminal, see diagram 9.17.
Push the ue assembly into the wall, externally or internally,
initially until the end of the assembly protrudes a short way
from the inside face of the wall. This will enable the internal
trim ring (if required) to be positioned and allow the ue
assembly to be drawn back into the ue elbow.
Secure the ue elbow in position on top of the boiler with four
torque headed screws supplied.
Draw the ue assembly from wall and engage the ue duct
into the elbow and butt t between the air duct and ue elbow.
Ensuring the correct alignment of the terminal.
Fit the securing collar into position, mark through two of the
pre drilled holes in the securing collar. Remove securing
collar and drill two 3mm diameter holes one in the elbow and
one in the air duct, take care not to pierce the inner ue duct.
Fit the securing collar and secure with screws provided, see
diagram 9.17.
Slide the internal trim ring back against the wall, securing in
place with a small amount of sealant if required.
NOTE: If the air and ue ducts have been correctly cut to the
instructions the sealing collar should t ush with the outside
wall, check this.
28
Diagram 9.17
9 Vertical Flue - Length, Preparation and Installation
9.11 Vertical ue
The vertical ue system is available as an option where the
boiler position does not permit the use of the top horizontal
ue system.
The system is made up from accessories. The accessories
include terminal assembly, bends 45º and 90º, ue
extensions, xing bracket and appropriate weather collar,see
diagram 9.19.
The maximum permitted straight ue length is 6,8 metres for
Betacom 24C, 5,8 metres for Betacom 30C.
for each 90º or 2x45º bends tted, the maximum length
must be reduced by 1 metre, see diagram 9.18.
NOTE: 2x45º bends can replace 1x90º bend if necessary.
When using 90º bends any horizontal extension pipe should
be inclined by a minimum of 44mm/metre (2.5º) towards the
boiler to facilitate condense removal, see (a) in diagram 9.18.
Alternatively use 45º bends to avoid horizontal runs, see (b)
in diagram 9.18.
The terminal siting should be as shown in diagram 4.2.
Measure the distance of ue length required for the
installation.
The ue must be designed with a continuous fall towards the
boiler.
15534
w
E
2
The maximum permitted straight flue length
is 6,8 metres for Betacom 24C, 5,8 metres
for Betacom 30C, for each
bends fitted, the maximum
90°or 45°x2
length must be
reduced by 1 metre.
Maximum flue (calculated equivalent) length
w, x, y, z, E
and E
1
2
should be les s than 6.8 m for
Betacom 24c, 5.8 m for Bet acom 30c
w
E
2
E
1
E
1
Diagram 9.18
29
9 Vertical - Flue Length, Preparation and Installation
12969
9.12 Flue Installation
Refer to diagram 9.20 and secure the ue adapter in position
on top of the boiler with four screws supplied,
NOTE: The rubber ‘O’ rings of each section should be
lubricated prior to assembly. Do not use mineral oils or
grease, silicon grease or water is recommended.
Secure the rst extension pipe to the ue adapter with the
securing collar supplied by positioning the collar centrally over
the joint, then tighten the two screws on the securing collar,
see diagram 9.21.
Fit more extension pipes as required using the collar and
screws supplied with each extension pipe. To t position the
collar centrally over the joint, tighten the two screws on the
securing collar. Using the holes provided in the securing
collar drill and insert the two self tapping screws supplied, see
diagram 9.22.
The rubber ‘O’ rings of each section should be lubricated prior
to assembly.
NOTE: Do not use mineral oils or grease, silicon grease or
water is recommended.
When installing the ue it is recommended that it is supported
every 2 metres and at every bend by a xing bracket.
Project the rise of the ue pipe to roof level and cut a 150mm
hole in the roof.
9.13 Flue Terminal Installation
(a) Pitched Roof
Fit the required pitched roof weather collar over the 150mm
hole in the roof. Make good the tiling or slating around the
collar incorporating the ashing of the weather collar. Position
the angle cap over the weather collar in the correct orientation
to attain the correct angle for your roof.
(b) Flat Roof
Fit the aluminium weather collar over the 150mm hole in the
roof ensuring a weather tight seal.
From above carefully place the ue terminal through the
weather collar.
Diagram 9.19
9.14 Flue Terminal to Boiler Connection
Should the clearances above the boiler to roof not allow for
extensions, it is permitted to cut the ue terminal ensuring the
relationship of ue and air duct lengths are retained.
30
9 Vertical Flue - Length, Preparation and Installation
9.15 Completion of Installation
With the ue terminal positioned in the roof the length of the
nal pipe can be determined. If a telescopic length cannot
be used, then a standard ue length can be cut to make the
correct length. Cut the ue to the desired length measuring
from the ‘O’ ring end and discard the plain end of the tube.
The cuts must be square and made free of burrs to allow
correct assembly.
NOTE: The ue pipe is 10mm longer than the air pipe, see
diagram 9.23.
Carefully push the terminal assembly upwards to allow room
for tting the nal ue piece. Fit a xing bracket to the terminal
assembly. Pull the terminal assembly down and join to the ue
system. Ensure that the terminal is making a weather tight
seal on the weather collar. Secure the xing bracket tted to
the terminal to the roong struts or a purpose made batton.
14528
14529
Diagram 9.21
12982
Diagram 9.22
12983
Diagram 9.20
Diagram 9.23
31
9 Twin Flue - Length, Preparation and Installation
Secure long flue lengths (horizontal &
vertical) to walls or ceiling at every joint or
on straight flue runs at every joint and
every metre flue run.
14530
32
Diagram 9.24
9 Twin Flue - Length, Preparation and Installation
12970
9.16 Twin ue
The twin ue system is available as an option when the top
horizontal or vertical ue system is not appropriate.
The system can provide an independent horizontal air inlet
and ue outlet, horizontal air inlet and vertical ue outlet or
vertical air inlet and ue outlet via a concentric terminal.
The system is made up from accessories, see diagram 9.25.
NOTE: The air and ue outlets do not have to be equal
lengths. 2x45º bends can replace 1x90º bend if necessary.
The maximum permitted combined (air inlet + ue outlet) ue
length is 14,3 metres for Betacom 24C, 11,9 metres for
maximum ue length must be reduced by 1 metre, see
diagram 9.24.
NOTE: When using 90º bends any horizontal run should be
inclined by a minimum of 44mm/metre (2.5º) towards the
boiler to facilitate condense removal.
Alternatively use 45º bends to avoid horizontal runs in the ue
pipe.
9.17 Terminal Position
The clearances for a ue outlet are given in the "Flue Location
and Ventilation" section.
In addition the horizontal air inlet must not be closer than 300
mm from a ue outlet on the same wall or 1200mm from an
opposing ue outlet.
9.18 Installation Details
The parts available for a twin ue system installation are
shown in diagram 9.25.
Diagram 9.25
33
9 Twin Flue - Length, Preparation and Installation
9.19 Boiler Connection
Place the twin ue adaptor onto the outlet of the boiler with
the air inlet to the left hand side, see diagram 9.26. Secure
the adaptor to the top panel with the screws provided. Care
should be taken when inserting the screw through the hole in
adaptor top.
To facilitate engagement, it is recommended that the rubber
‘O’ rings are lubricated with silicone grease or water prior to
assembly.
9.20 Air and Flue Pipe Installation
The air and ue pipes can now be built up from the boiler.
The ue must be designed with a continuous fall towards the
boiler. If using the horizontal ue pipe or 90° bends the pipe
must be inclined at 44mm/metre (2.5°)
9.24.
Alternatively if space allows, use 45° bends in place of 90º
bends.
The rubber ‘O’ rings of each section should be lubricated prior
to assembly with silicone grease.
When building the ue up it is recommended that it is
supported every 2 metres and at every bend by a xing
bracket.
minimum, see diagram
14531
Diagram 9.26
9.21 Horizontal Terminal Installation
With due consideration to terminal clearances mentioned in
section 4.2 drill the one or two holes as required with a 90mm
core drill.
Push the horizontal terminal through the wall allowing approx.
100mm to protrude outside.
Push a grey rubber wall seal onto either side of the wall
ensuring that both wall seals are pushed up to the wall
surface, see examples (b) and (c) diagram 9.24.
9.22 Vertical Terminal Installation
With due consideration to terminal clearances mentioned in
Section 4.2, project the rise of the ue pipe to roof level and
cut 150mm hole in the roof.
(a) Pitched Roof
Fit the required pitched roof weather collar over the 150mm
hole in the roof. Make good the tiling or slating around the
collar incorporating the ashing of the weather collar. Position
the angle cap over the weather collar in the correct orientation
to attain the correct angle for your roof. One way round gives
a pitch of 25°-38° and the other gives 37°- 50°.
(b) Flat Roof
Fit the aluminium weather collar over the 150mm hole in the
roof ensuring a weather tight seal.
9.23 Horizontal Pipes-Completion of
Installation
Having built the pipe(s) from the boiler to the terminal(s), the
length of the nal pipe piece can be determined. Cut pipes at
the opposite end to the ‘O’ ring seal making square and free
from burrs. Push the horizontal terminal through the wall to
engage the nal pipe piece and pull back ensuring the grey
wall seals are fully pulled up to the outside and inside wall
faces.
9.24 Vertical Pipes-Completion of
Installation
Refer to diagram 9.24.
For installation of (a), attach the twin pipe to concentric
ue adaptor, part number A2011600, to the base of vertical
terminal assembly. For installation of (b), attach the single
pipe to concentric adaptor, part number A2011500, to the base
of vertical terminal assembly.
With the vertical terminal assembly positioned in the roof,
the length of the nal pipe can be determined. Cut the ue
to the desired length measuring from the ‘O’ ring seal end
and discard the plain end of the tube. The cut end should
be square and free from burrs. Carefully push the terminal
assembly upwards to allow room for tting the nal ue
piece(s). Fit a 100mm xing bracket to the terminal assembly
Part No2000460486. Pull the terminal assembly down and
join to the ue system. Ensure that the terminal is making a
weather tight seal on the weather collar. Secure the xing
bracket tted to the terminal to the roong struts or a purpose
made batton.
34
9 Plume Management Kit
9.25 Plume Management Kit
12997
The Plume Management Kit: Part No. A2044100 (white) or
A2044000 (black) can be used to overcome many site issues.
The Plume Management Kit will t to the Top Horizontal
Telescopic, Rear Horizontal Telescopic and Standard
Horizontal Flue. This enables the ue products to exhaust
further away from the boiler, thereby reducing the impact of
pluming.
NOTE: The ue air inlet can be sited closer to doors, opening
windows and air bricks, than stated in section 4.2, see
diagram 9.27.
The maximum length of the Plume Management Kit must NOT
exceed 2m with a horizontal concentric ue length of 1m max.
For each 90o bend or 2 x 45o bends the maximum length of the
Plume Management Kit must be reduced by 1m.
For more information contact Glow-worm, refer to page 2.
The Plume Management Kit is supplied with installation
instructions.
Refer to BS5546 or BS6798 for advice on disposal of boiler
condensate.
150mm.
MIN.
Diagram 9.27
10 Electrical Connection
WARNING: This appliance must be earthed.
● This appliance must be wired in accordance with these
instructions. Any fault arising from incorrect wiring cannot be
put right under the terms of the Glow-worm guarantee.
● All system components must be of an approved type.
Electrical components have been tested to meet the
equivalent requirements of the BEAB.
● Do not interrupt the mains supply with a time switch or
programmer.
● Connection of the whole electrical system and any heating
system controls to the electrical supply must be through a
common isolator.
● Isolation should preferably be by a double pole switched
fused spur box having a minimum contact separation of
3mm on each pole. The fused spur box should be readily
accessible and preferably adjacent to the boiler. It should be
identied as to its use.
● A fused three pin plug and shuttered socket outlet may be
used instead of a fused spur box provided that it is not used in
a room containing a xed bath or shower.
● The boiler is suitable for installation in bathroom zones 2
and 3.
10.1 Electrical Wiring
The boiler is supplied factory wired complete with 1.5 m of
mains lead. All electrical connections to the mains supply must
be made in full accordance with the current I.E.E. regulations.
The boiler must be connected to an effective earth system.
A 3 amp fused three pin plug and shuttered socket outlet may
be used instead of a fused spur box provided that it is not
used in a room containing a xed bath or shower.
35
10 Electrical Connection
10.2 System Controls 24V
WARNING: UNDER NO CIRCUMSTANCES MUST
ANY MAINS VOLTAGE BE APPLIED TO ANY OF THE
TERMINALS ON THE 24V CONNECTION.
The 24V low voltage room thermostat terminal block is
located on the left side of the rear cover of the controls box.
To access the 24V low voltage room thermostat terminal block
remove the front panel secured with two screws, lift off the
two retaining lugs, see diagram 10.1.
Carefully pull forward and down the controls fascia, see
diagram 10.2.
On connection of a voltage free room thermostat to the boiler,
the factory tted bridge across the room thermostat terminal
block must be removed, see diagram 10.3.
24V LOW VOLTAGE
ROOM THERMOSTAT
TERMINAL BLOCK
FITTED
BRIDGE
1447814564
Diagram 10.2
RETAINING
LUGS
14457
FITTED
BRIDGE
WTHOUT ROOM
THERMOSTAT
O
C
WTH ROOM
THERMOSTAT
36
40 50
ON 30
2
3
1
4
0
bar
SECURING
SCREWS
Diagram 10.3
60 70
bar
17
3
16
1
4
15
5
0
14
6
13
7
12
8
11
9
10
22
21
23
20
24
19
1
18
2
90
80
Diagram 10.1
230V ROOM
10 Electrical Connection
10.3 System Controls 230V
If a mains voltage thermostat is to be used.
Unclip the two front retaining clips on the controls fascia, see
diagram 10.3.
Unclip and carefully pull down the control circuit board cover,
see diagram 10.4. to access the mains voltage connection
located on the printed circuit board, see diagram 10.5.
On connection of a mains voltage room thermostat to the
boiler, the bridge wire on factory tted plug must be cut to t a
connector block.
NOTE: Mains powered thermostats must be connected
directly to the mains circuit board as indicated in diagram
10.6.
NOTE: Ensure that the polarity of the mains connection is
correct as reversed polarity may cause the appliance to
malfunction.
NOTE: While the boiler’s main pcb, pump, three-way valve
and gas valve are supplied at 230V AC., all other components
and associated circuits are supplied at low voltage.
NOTE: When re-assembling, take care NOT TO TRAP the
cables and wires.
NOTE: Connection to the mains electrical supply must be
maintained at all times in order to provide domestic hot water,
frost protection and pump over-run facility.
Ensure that the boilers electrical supply is not interrupted by
any external controls.
RETAINING CLIPS
CONTROLS CIRCUIT
BOARD COVER
BRIDGE PLUG
1453814479
Diagram 10.4
10.4 Electrical Connections - Testing
Carry out preliminary electrical system checks prior to making
the nal connection as below:
1. Test insulation resistance to earth of mains cables.
2. Test the earth continuity and short circuit of cables.
3. Test the polarity of the mains.
RETAINING CLIPS
14539
PRINTED CIRCUIT
BOARD
THERMOSTAT
Diagram 10.5
14637
bar
ON 30 40 50 60 70 80 90
CONTROLS FASCIA
Diagram 10.3
4950
X20
230V ROOM
THERMOSTAT
CONNECTION
ON PRINTED
CIRCUIT BOARD
Diagram 10.6
37
11 Commissioning
145711448014481
PUMP
VENT PLUG
ISOLATION VALVES SHOWN OPEN
IMPORTANT: At the time of commissioning, complete all
relevant sections of the Benchmark Checklist located in the
centre pages of this document.
11.1 Preliminaries - All Systems
Do Not operate the boiler without water.
The commissioning should be carried out by a competent
person approved at the time by the Health and Safety
Executive and in accordance with the current issue of
BS6798.
Make sure that the system has been thoroughly ushed
out with cold water and that all cleanser if used has been
removed.
With the gas service isolation valve closed, with no demand
from any external controls and the power supply to the boiler
switched off, test for gas soundness and purge air from the
gas supply.
11.2 Filling the System
On completion of the boiler installation and ensuring that all
water connections are correctly made the boiler may be lled
with water via the lling loop (not supplied with the boiler).
1. Ensure that two manual feed valves and boiler isolation
valves are open, see diagram 11.1.
2. Release the cover cap of the boilers automatic air vent
situated on top of the pump, see diagram 11.2.
The manual feed valves must be closed and the lling
loop disconnected once the pressure sensor, sited on the
boilers control panel, indicates a system pressure
between 1.0 and 1.5 bar, see diagram 11.3.
3. Check that all the water connections throughout the
system are sound and bleed each of the heating systems
radiators in turn. As air is vented the system pressure
may need topping back up to 1.0bar.
Air must be vented from the boiler’s pump by unscrewing
the pumps integral vent plug and allowing water to bleed
for a few seconds. Take care not to allow water to splash
onto any electrical components.
4. When the system is bled of any air it must be lled until
the pressure display indicates a system pressure of 1.5
bar.
5. If the pressure exceeds 1.5 bar discharge the excess
pressure from the system via a radiator valve or pipe
connection. Do not use the safety discharge valve
as the valve seat may become contaminated with debris
and fail to re-seal.
Diagram 11.1
IMPORTANT NOTE: In order to maintain the appliances
warranty; after initial lling the heating system must be
thoroughly ushed using a propriety cleanser to remove
foreign material and contaminants.
AUTOMATIC AIR
VENT COVER CAP
Diagram 11.2
2
3
1
0
4
bar
ON 3040 5060 7080
bar
SYSTEM
PRESSURE 1.5 bar
Diagram 11.3
38
11 Commissioning
PRESSURE GAUGE
2
1
0
bar
DOMESTIC HOT WATER
TEMPERATURE
CONTROL
STANDBY
2
3
4
5
TIMER
24
1
6
7
22
21
23
8
9
20
19
18
17
1
0
11
10
16
15
14
13
12
INDICATOR
ON 30 40 50 60 70 80 90
3
4
DISPLAY
bar
14333
CENTRAL HEATING
FUNCTION
SWITCH
TEMPERATURE
CONTROL
Diagram 11.4
11.3 Control Panel Functions, diagram 11.4.
Central heating and domestic hot water temperature
controls: The boiler’s integral control unit monitors and
adjusts both the boiler’s hydraulic circuit and D.H.W. water
outlet temperatures by means of sensors located on the
CH heating and D.H.W. ow outlets. The sensors electrical
resistance, which is dependant on temperature, determines
the current passing through the control potentiometers
located on the control panel. The respective potentiometer
control dial allows manual setting of the maximum required
temperature (reference value) being between 30º and 85ºC
for CH heating and 35º and 64ºC for D.H.W. When the boiler
operates in heating or D.H.W. mode, the current received is
compared to the manually set reference value. The difference
of the two values operates the modulation of the gas valve
adjusting the useful heat output generated and stabilising the
temperature to within ±1ºC.
Re-set function: Should the boiler lock out at any time,
please check the gas supply and ionisation probe position, the
boiler may be re-started by switching to standby “O” position
waiting 15-30 seconds.
Switching back to its previous position once the fault has been
eliminated.
Function switch: The three position switch allows the boilers
operation to be set to ‘Stand-by’ (centre position), ‘Heating
+ D.H.W.’ (left hand position) or ‘D.H.W. only’ (right hand
position).
11.3 Commissioning
The Betacom 24c and 30c boilers have been tested and preset at the factory and is dispatched with its on board controls
set to provide a maximum central heating and D.H.W. output.
Consequently, once all the connections have been made and
the boiler has been lled with water to the designed system
operating pressure, the boiler may be red prior to adjusting
it’s on board parameters to match the heating systems
requirements.
11.4 Initial Lighting
Prior to ring: Check that the electrical supply to the boiler
is ‘On’ (The green boiler ‘Stand by’ indicator will light) and the
gas service isolation valve is in the open position, see diagram
11.1.
Set the boiler’s central heating and domestic hot water
temperature controls to maximum by turning them fully
clockwise.
Set the external room thermostat (if tted) to maximum and
open the thermostatic radiator valves to maximum.
Switch the boilers function switch to the central heating and
domestic hot water position. The boiler’s control unit will
now automatically carry out pre-ignition safety checks before
igniting the burner.
39
11 Commissioning
11.5 Setting Operational Pressure
Minimum setting
Remove the sensing tube from the gas valve.
Remove one lead from the modulating gas valve coil, see
diagram 11.6.
Refer to diagram 11.7.
Connect a suitable pressure gauge the pressure outlet of the
gas valve.
Turn the boiler’s function switch to the ‘Winter’ position.
(Heating and Hot Water), see diagram 11.4
Turn the central heating temperature control to maximum
setting.
Remove the protective cover from the gas valve adjuster.
Turn the inner screw using a screwdriver, clockwise: to
increase the pressure setting, anticlockwise: to decrease the
pressure setting.
After correct adjustment see, ‘Boiler specication section’
page 8, re-connect the electrical connector and protective
cover and replace the sensing tube to the boiler.
Maximum setting
Remove the sensing tube from the gas valve, see diagram
11.5.
Remove the protective cover from the gas valve adjuster.
Push the ball inside the modulating gas valve coil using a
sharp pointed tool.
Turn the nut with a 10mm spanner (keeping the ball in without
any rotation) clockwise: to increase the pressure setting,
anticlockwise: to decrease the pressure setting.
After correct adjustment see, ‘Boiler specication section’
page 8.
Finally, replace the sensing tube to the gas valve.
GAS VALVE AND
MANIFOLD INLET
CONNECTIONS
SENSING TUBE
MODULATING
COIL
ELECTRICAL
AND EARTH
CONNECTIONS
ELECTRICAL
PLUG
14585
SCREW
Diagram 11.5
GAS VALVE
ADJUSTER
15524
Diagram 11.6
40
GAS
ISOLATION
VALVE
11 Commissioning
Diagram 11.7
SECURING
SCREWS
15525
14586
SUPPLY PIPE
CONNECTION
Diagram 11.8
11.6 Checking the gas rate
The boiler is tted with a fully modulating automatic gas valve. With all other gas appliances turned off
measure the gas rate at the gas meter. Check that the gas rate is as stated in the table below:
Gas rate
Appliance Maximum net heat input in kW
Betacom 24c
Betacom 30c
Checking the combustion products
While adjusting the burner pressure at maximum and minimum, combustion products can be checked
according to the table below:
The boiler incorporates 4 potentiometers and a bank of dip
switches to allow adjustment to its pre-set parameters. These
are situated on the rear of the control panel.
The potentiometers can easily be accessed by removing
the cover on the rear of control panel. However, to reach the
dip switches, the control panel must be opened, see diagram
10.4.
Setting the maximum CH heating ow temperature: The boiler
is dispatched with a maximum ow temperature factory set to
85°C. Where a lower maximum temperature is required such
as in the case of under-oor heating, the factory setting can
be altered between a maximum of 50°C and a minimum of
30ºC, by tting dip switch ‘6’ into “ON” position, see diagram
11.11.
Setting the boiler’s integral pump: The boiler’s integral pump
is factory set to operate in both C.H. and D.H.W. mode.
Where an external pump is incorporated into the system
design the integral pump may be disconnected in C.H. mode
by tting dip switch ‘5’ into the “ON” position, see diagram
11.11.
Setting the 45 seconds delay: The boiler is factory set to
exclude the delay of 45 seconds before re-ignition between
the closing of a hot water tap and CH start-up. This delay can
be set to 45 seconds by setting dip switch ‘3’ into the “OFF”
position’, see diagram 11.10 and 11.11.
255 seconds delay setting: The boiler is capable of up to 255
seconds ignition delay (anti cycling time) before re-ignition
following burner shut down on the primary hydraulic water
reaching its set temperature. This delay can be increased up
to a maximum of 255 seconds by turning potentiometer ‘P5’
clockwise, see diagram 11.12.
Pump working mode setting: The boiler has a factory set to
operate the pump for pre-purge and post-purge times (45
secs). This delay can be excluded by tting dipswitch ‘2’ into
“ON” position, see diagram 11.10 and 11.11. However, this may
then cause the boiler over-heat thermostat to trip out.
Setting the Heating output: The Betacom 24c and 30c boilers
are factory set to give maximum CH heating output. The
maximum heat output for heating is pre-set on ‘P2’
potentiometer, see diagram 11.12.The adjustment for max CH
has no effect on max. DHW capacity of the boiler.Ignition
capacity can be increased /decreased by turning ‘P4’
potentiometer clockwise / counter-clockwise. Boiler type is
pre-set on Dip Switch ‘8’ “OFF” position denotes 24 kW,
and `ON` position denotes 28 kW.
Dipswitch 1 and 7 must always be in the “OFF” position.
Dipswitch 4 must always be in the “OFF” position.
Potentiometer 7: No adjustment required.
14553
14565
DIP SWITCH
ON POSITION
DIP SWITCH
OFF POSITION
ON
DIP
1 2 3 4 5 6 7 8
8 DIP SWITCHES IN
THE OFF POSITION
Diagram 11.10
ONDIP
1 2 3 4 5 6 7 8
ONDIP
1 2 3 4 5 6 7 8
Diagram 11.11
ON
P7
P5
POTENTIOMETERS
4 OFF
1455514554
42
POTENTIOMETER
COVER
Diagram 11.9
P2
P4
Diagram 11.12
11 Commissioning
11.8 Completion
GB: It is a requirement that the “Benchmark” Installation,
Commissioning and Service Record is completed and left with
the user.
IE: it is necessary to complete a “Declaration of Conformity” to
indicate compliance to I.S.813. An example of this is given in
the current edition of I.S.813.
11.9 Instruct the User
● Demonstrate, then instruct the User about the lighting
procedure and heating system controls operation.
● Advise that to ensure the continued efcient and safe
operation of the boiler it is recommended that it is checked
and serviced at regular intervals. The frequency of servicing
will depend upon the installation conditions and usage, but in
general, once a year should be enough.
● Draw attention, if applicable, to the current issue of the Gas
Safety (Installation and Use) Regulations, Section 35, which
imposes a duty of care on all persons who let out any property
containing a gas appliance in the UK.
● The user shall not interfere with or adjust sealed
components.
● It is the Law that any servicing is carried out by a
competent person approved at the time by the Health and
Safety Executive.
● Advise the user that, like all condensing boilers this
appliance will produce a plume of condensation from the ue
terminal in cool weather. This is due to the high efciency and
hence low ue gas temperature of the boiler.
● Advise the user of the precautions necessary to prevent
damage to the system, boiler and the building, in the event of
the heating system being out of use during frost or freezing
conditions.
● Advise the user that the permanent mains electrical supply
SHOULD NOT be switched off, as the built in frost protection
and pump saver program will not operate.
● Advise the User if the mains electricity and gas are to be
turned off for any long periods during severe weather, it is
recommended that the whole system, including the boiler,
should be drained to avoid the risk of freezing.
NOTE: Sealed System: Contact your installation/servicing
company as draining, relling and pressurising MUST be
carried out by a competent person approved at the time by
the Health and Safety Executive.
● Leave these instructions and the ‘Benchmark’ Installation,
Commissioning and Service Record with the user.
43
11 Commissioning - Nat. Gas (G20) to LPG (G31) Conversion
1 2 3 4 5 6 7 8
ONDIP
1 2 3 4 5 6 7 8
ONDIP
DIP SWITCH
OFF POSITION
DIP SWITCH
ON POSITION
11.10 LPG CONVERSION - all models
IMPORTANT: Gas conversion must be carried out by a
competent person approved at the time by the Health and
Safety Executive.
Isolate the boiler from both the Gas and Electricity supplies.
The burner must be removed from the boiler by removing,
the front panel, hermetic chamber cover and combustion
chamber cover. Remove the two securing screws, one on
each side of the burner, see diagram 11.13.
The old injector bar (manifold) must be removed.
The ignition electrode and ame (ionisation) electrode
cables must be removed by opening the control panel and
gaining access to the PCB. Disconnect the plugs of the
ignition and ame (ionisation) electrodes, see diagram
11.15.
Fit new injector bar (manifold), new sealing washer and
tighten, ensuring that the injector size is marked 0.75 mm for
LPG (both for Betacom 24c and Betacom 30c)
Fit burner and re-assemble.
The joint must be checked for Gas Tightness.
14557
FLAME AND IGNITION
ELECTRODE LEADS
Diagram 11.15
14555
SECURING SCREW
LEFT HAND SIDE
OF BURNER
SENSING TUBE
RIGHT HAND
SIDE OF BURNER
Diagram 11.13
BURNER
GROMMET
14566
8 DIP SWITCHES IN
THE OFF POSITION
ON
DIP
1 2 3 4 5 6 7 8
MAIN PCB
Remove the gasket of cables with the cables inside.
44
Diagram 11.14
Diagram 11.16
11 Commissioning - Nat. Gas (G20) to LPG (G31) Conversion
Factory settings for DIP switches
DS1DS2DS3DS4DS5DS6DS7DS8
Betacom 24c NGOFFOFFOFFOFFOFFOFFOFFOFF
Betacom 24c LPGOFFOFFOFFOFFOFFOFFONOFF
Betacom 30c NGOFFOFFOFFOFFOFFOFFOFFON
Betacom 30c LPGOFFOFFOFFOFFOFFOFFONON
Dip switch 7 must be in the ON position for LPG and OFF for NG.
Dip switch 8 must be in the OFF position for Betacom 24c and ON for Betacom 30c.
To set the Minimum Setting:
Remove one lead from the gas valve modulating coil, see
diagram 11.17.
Turn boiler’s function switch to the ‘winter’ position (both CH
and DHW).
Turn the Central Heating temperature control knob to the
maximum position.
Connect a suitable pressure gauge to the pressure outlet
on the gas valve, see diagram 11.18.
Remove the protective cover from the gas valve.
Turn inner adjuster with a at blade screwdriver.
Turn Clockwise: to increase burner pressure.
Turn Counter-Clockwise: to decrease burner pressure.
After adjustment, connect electrical lead and protective
cover.
To set the Maximum Setting:
Connect a suitable pressure gauge to the burner pressure
test point on the gas valve.
Remove the protective cover from the gas valve adjuster.
Connect a suitable pressure gauge to the pressure outlet of
the gas valve.
Turn boiler’s function switch to the ‘winter’ position.
Turn the Central Heating temperature control knob to the
maximum position.
Push the ball inside gas valve modulating coil using a sharp
pointed tool.
Turn outer nut with a 10mm spanner keeping the tool pushed
in:
Turn Clockwise: to increase burner pressure.
Turn Counter-Clockwise: to decrease burner pressure.
After adjustment, connect electrical lead and protective
cover.
GAS VALVE
ADJUSTER
MODULATING
COIL
15524
Diagram 11.17
15525
Burner operating
pressure (minimum)
Burner operating
pressure (maximum)
Betacom 24cBetacom 30c
NG
(G20)
mbar
2.58.02.36.0
12.536.51436.0
LPG
(G31)
mbar
NG
(G20)
mbar
LPG
(G31)
mbar
Diagram 11.18
45
12 Servicing
IMPORTANT NOTES:
1. To ensure the continued efcient and safe operation of the boiler it is recommended that it is checked and serviced at
regular intervals. The frequency of servicing will depend upon the particular installation and usage, but in all cases the
boiler must be serviced at least once a year.
2. It is the Law that any servicing is carried out by a competent person approved at the time by the Health and Safety
Executive.
3. Before commencing with a service or replacement of parts the boiler should be isolated from the electrical supply and the
gas supply should be turned off at the gas service isolation valve.
4. When replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and
performance specication that we require. Do not use reconditioned or copy parts that have not been clearly authorised
by Glow-worm.
5. If any electrical connections have been disconnected and after their connection, checks to the earth continuity, polarity,
short circuit and resistance to earth must be repeated using a suitable multimeter.
6. On completion the “Benchmark” Service Record should be completed.
General Inspection
Prior to, during servicing and after any maintenance or
changed parts, the following must be checked.
● The integrity of the ue system and ue seals.
● The integrity of the appliance combustion circuit and
relevant seals.
● Electrical, gas and water connections.
● System pressure.
● the combustion performance, refer to the following
procedure.
● The operational gas inlet pressure and gas rates, refer to
the commissioning section, paragraph 11.5.
Correct any fault before continuing.
COMPETENCY TO CARRY OUT THE CHECK
OF COMBUSTION PERFORMANCE
NOTE: BS 6798: 2009 Specication for installation and
maintenance of gas-red boilers of rated input not exceeding
70kW net advises that:
● The person carrying out a combustion measurement must
be assessed as competent in the use of a ue gas analyser
and the interpretation of the results.
● The ue gas analyser used should be one meeting the
requirements of BS7927 or BS-EN50379-3 and be calibrated
in accordance with the analyser manufacturers’ requirements.
● Competence can be demonstrated by satisfactory
completion of the CPA1 ACS assessment, which covers
the use of electronic portable combustion gas analysers in
accordance with BS 7967, parts 1 to 4.
● Ensure that the gas analyser is set to the correct fuel
setting.
● Select the constant central heating with DHW function by
turning the function switch, refer to commissioning section.
The boiler should re automatically.
NOTE: Safe combustion can only be veried by measuring
CO/CO2 ratio. This ratio must not exceed 0.0008.
Burner
Refer to Commissioning, section 11.5 “Setting operational
pressure”.
Check that the burner pressure at maximum and minimum
rate, is as the value in the boiler specication table on page 8.
If incorrect, adjust as necessary.
ISOLATION VALVES SHOWN CLOSED
C.H. ISOLATION
VALVE FLOW
CONDENSATE
OUTLET PIPE
D.H.W
OUTLET
46
SAFETY DISCHARGE
PIPE
GAS ISOLATION
VALVE INLET
COLD WATER
ISOLATION VALVE INLET
14540
C.H. ISOLATION
VALVE RETURN
Diagram 12.1
12 Servicing
COMBUSTION CHECK AND SETTING GAS
VALVE
● Remove the front casing panel, see diagram 10.1 and hinge
down the control box. Taking care not to touch any internal
components, proceed as follows:
● Connect the CO
point.
While adjusting the burner pressure at maximum and
minimum, combustion products can be checked if required,
according to the table below:
value exceed the value in the table, investigation of the cause such as cleaning the heat exchanger and checking
2
Propane
tolerance
GAS RATE CHECK
The boiler is tted with a fully modulating automatic gas
valve. With all other gas appliances turned off
measure the gas rate at the gas meter. Check that the gas
rate is as stated in the table below:
Appliance Maximum net heat input in kW
Betacom 24c
Betacom 30c
25,7
28,5
COMPLETION
If it is not possible to achieve the required results for either
the combustion or gas rates, it will be necessary to complete
a full service of the appliance and then repeat the combustion
check procedure. If after servicing and adjustment of the
appliance the combustion values are still unacceptable
and after further remedial work has been carried out, the
appliance must be disconnected until the CO/CO2 ratio
is acceptable. Advice can be sought from the Glow-worm
Technical Helpline.
12.1 Servicing
All routine servicing requirements can be achieved by the
removal of the front panel and inner casing panel, see
diagram 12.2.
Before commencing with a service or replacement of parts.
The boiler should be isolated from the electrical and gas
supplies.
● Remove the front casing panel by removing two screws
at the bottom of the boiler and by lifting the front casing
panel up to release from the retaining hooks, see
diagram 10.1.
● Remove the boiler inner casing panel by removing two
screws and by lifting the boiler inner casing panel up to
release from the retaining lugs, see diagram 12.2.
● Remove the side panels by removing the screws on the
upper and lower sides. Remove the panels by swinging
them out and lifting them up, see diagram 12.3.
● Remove the combustion chamber cover by removing six
screws, see diagram 12.4.
Gas rate
Natural gas in (m3 / h)
nominal
2,72
3,02
47
RETAINING
LUGS
12 Servicing
14540
INNER
CASING
PANEL
VIEWING
WINDOW
SECURING
SCREWS (6 OFF)
14495
21
22
20
23
19
24
18
1
17
2
90
80
60 70
50
40
30
ON
2
1
0
bar
bar
3
4
SECURING
SCREWS
16
3
1
15
4
0
14
5
13
6
12
7
11
8
10
9
COMBUSTION
VIEWING
WINDOW
CHAMBER
COVER
Diagram 12.2
14573
ELECTRICAL
CONNECTIONS
PRESSURE SWITCH
CONNECTION TUBE
Diagram 12.4
14563
FAN
EARTH
LEAD
SECURING
SCREW
PRESSURE SWITCH
CONNECTION TUBE
FAN HOOD
Diagram 12.5
48
SECURING
SCREWS
(4 OFF)
21
22
20
23
19
24
18
1
17
2
16
3
1
40 50 60 70 80 90
30
ON
2
1
0
bar
bar
3
4
15
4
0
14
5
13
6
12
7
11
8
10
9
SIDE PANELS
Diagram 12.3
12 Servicing
12.2 Fan removal
Disconnect the electrical connections and air pressure switch
connection tubes from the fan, remove the fan securing
screw and withdraw fan from fan hood with its 56º bend, see
diagram 12.5.
12.3 Burner removal
Remove the burner assembly from the combustion chamber
as follows:
Pull off the ignition and ame electrode leads from mains
circuit board and remove the wires with grommet from the
combustion chamber base, see diagrams 12.6 and 12.7.
Remove the burner-retaining screws at the sides and remove
the burner, see diagram 12.8.
12.4 Visually check
For debris/damage and clean/replace as necessary the
following items:
Heat exchanger, Burner, Fan/compartment
Electrodes and Insulation/gaskets
IMPORTANT: Clean the heat exchanger using a soft brush or
vacuum cleaner. Do not use any tool likely to damage painted
nish of heat exchanger.
Clean the burner by washing in soapy water. Allow to dry
thoroughly before re-tting.
Do not use wire or a sharp instrument to clean the burner
injectors.
Ensure the ignition electrode gap is set to 4 mm, see diagram
12.7.
SPARK GAP 4mm
14566
BURNER
SENSING TUBE
GROMMET
Diagram 12.7
1455714574
SECURING SCREW
12.5 Cold water inlet lter
The boiler is tted with a cold water inlet lter which must be
inspected on each service, see diagram 12.9.
To access the lter:
Close the isolating valve on the boiler’s cold water domestic
inlet by turning the valve head fully clockwise.
Open one or more hot water taps to drain the domestic hot
water circuit.
Disconnect the cold water inlet connection to the boiler.
Clean and inspect the lter, replace if necessary as described
in replacement of parts section 14.19.
Re-t the lter and reinstate the cold water inlet connection to
the boiler, t new gasket as required.
Fully open the isolating valve on boiler’s cold water inlet and
check for leaks.
14556
LEFT HAND SIDE
OF BURNER
COLD WATER INLET FILTER
RIGHT HAND
SIDE OF BURNER
Diagram 12.8
IGNITION AND FLAME
ELECTRODE LEADS
Diagram 12.6
COLD WATER INLET
ISOLATION VALVE
Diagram 12.9
49
HALL
EFFECT SENSOR
13 Fault nding
r
r
FAN
GAS CONTROL
VALVE
g g
g/y
AIR PRESSURE
SWITCH
rr
PUMP
14593
LIMIT
WATER
FLOW
SENSOR
g
THERMOSTAT
HOT WATER
w
g
r
DOMESTIC
SENSOR
CENTRAL HEATING NTC
SENSOR
r
230V ROOM
THERMOSTAT
CONNECTION
(high voltage)
br
r r
PRINTED
CIRCUIT
BOARD
WATER
PRESSURE
w
w
w
r
r
r
w
THREE WAY
VALVE
w
w
SWITCH
FLAME
(IONISATION)
ELECTRODE
OVERHEAT SAFETY
THERMOST
FUSES (2A)
w
F1
r
bk
br
r
r
w
w
b
F2
br
b
m
b
r
r
w
IGNITION
ELECTRODES
g/y
AT
br
b
g/y
g/y
CHASSIS
EARTH
g/y
g/y
g/y
50
r r
w w
24V TIME
CLOCK
(low voltage)
ww
ww
24V ROOM
THERMOSTAT
CONNECTION
(low voltage)
brBROWN
bBLUE
g/yGREEN/YELLOW
5 4 3 2 1
USER
INTERFACE
gGREY
gnGREEN
bkBLACK
mMAUVE
rRED
wWHITE
KEY
L E N
230V~50Hz PERMANENT
MAINS SUPPLY
FUSED AT 3A
FUSE RATINGS:
F1: 2 A
F2: 2 A
13 Fault nding
13.1 Preliminary fault nding
The following checks should be performed before proceeding
onto specic diagnostics:
Check the external electrical supply to the boiler is on and a
supply of 230V is present at the ‘L’ and ‘N’ terminals.
Check the electrical installation and boiler, carry out tests for
earth continuity, polarity, short circuit and resistance to earth,
using a suitable multimeter.
An aid to test
Remove the front casing panel, see diagram 10.1 and hinge
down the control box.
Unclip to gain access to the mains circuit board, see diagram
10.4.
Carry out the tests on the mains circuit board, see diagram
13.1.
Check chassis earth at a bare metal point on the boiler.
Check that there is a gas supply to the boiler and the gas
service isolation valve is turned on, see diagram 13.2.
Check pressure at the gas service isolation valve, refer to
section 11.5.
Check that the heating system pressure indicates at least
1.0 mbar, if not, ll and vent the system as described in
section 11.2.
Check that all external controls are on.
br
bk
br
w
r
b
F1
F2
br
b
m
b
b
g/y
g/y
230V
TEST
POSITION
Diagram 13.1
1457114637
13.2 Re-set function
Should the boiler lock out at any time, please check the
gas supply and ionisation probe position, the boiler may be
re-started by switching to standby “O” position waiting 15-30
seconds and switching back to its previous position once the
fault has been eliminated, see diagram 11.4.
Boiler Stand-by
Indicator
ON
30405060708090
Water
Temperature
GAS SERVICE ISOLATION
VALVE (OPEN)
Diagram 13.2
14520
Flashing
Fault on CH
sensor
Outdoor sensor
Flashing
Fault on
DHW sensor
Flashing
Fault on
bar
bar
Pressure Switch
Flashing
Low System
Pressure
Flashing
Fault on Air
Flashing
Flames or Gas
Failure
Flashing
Overheat
Themostat
Diagram 13.3
51
13 Fault nding
13.2 Fault nding chart 1. Check electrical supply central heating sensor and frost protection.
14496
52
6
Diagram 13.4
13 Fault nding
13.2 Fault nding chart 2. Check domestic hot water operation.
1449714498
13.3 Fault nding chart 3. Check central heating operation.
Ensure DHW taps
are closed
Is overheat
thermostat LED flashing?
Put CH temperature
No
Ensure external controls
are calling for heat
Is CH sensor LED
flashing ?
No
Does pump run ?
Yes
Go to chart 5
4
Diagram 13.5
Yes
No
necessary replace
Check and if
necessary reset or
replace
Is 230 V AC
present on terminals of
Yes
Check and if
No
Yes
Check and if
necessary replace
Check and if
necessary replace
Diagram 13.6
53
13 Fault nding
13.4 Fault nding chart 4. Check domestic hot water operation.
1449914500
6
13.5 Fault nding chart 5. Check domestic hot water and central heating modulation
Diagram 13.7
54
Diagram 13.8
13 Fault nding
13.6 Fault nding chart 6. Check ignition system.
15558
Diagram 13.9
55
14 Replacement of parts
14.1 General
Replacement of parts must be carried out by a competent
person.
Before replacing any parts the boiler should be isolated from
the mains electric supply and the gas should be turned off at
the gas service isolation valve on the boiler.
The boiler is cold.
Ensure that components with electrical connections are
disconnected before removal.
Unless stated otherwise parts are replaced in the reverse
order to removal.
After replacing any parts always test for gas tightness and if
necessary carry out functional test of the controls.
For replacement of parts the front casing of the boiler will
need to be removed. To remove undo the two screws on the
underside of the front casing and lift off the retaining lugs, see
diagram 10.1.
The side panels can be removed to aid replacement of parts,
see diagram 12.3.
To hinge a side panel undo and remove the two screws
securing each side panel to the boiler.
14.1 Draining of Boiler
To prevent the need to drain the entire heating system when
replacing the boiler’s integral pump, expansion vessel, safety
relief valve and pressure sensor, the boiler’s hydraulic circuit
may be isolated from the central heating circuit by closing the
boilers isolation valves. Opening the discharge safety valve
will then drain the boiler’s hydraulic circuit.
NOTE: clean the valve seat to ensure it seals before re-lling
the boiler.
After replacing parts open the heating ow and return isolating
valves and rell, vent and pressurise the heating circuit, refer
to section 11.2.
Check for leaks.
ELECTRICAL
CONNECTIONS
WATER SENSOR
Diagram 14.1
14.4 Central heating sensor
For access, refer to section 14.1.
The C.H. sensor is located on left side of the combustion
chamber on the outlet of the primary heat exchanger, see
diagram 14.2.
Unclip the C.H. sensor from the pipe.
Disconnect the electrical connections from the C.H. sensor.
Fit replacement C.H. sensor.
Re-t the electrical connections.
PRIMARY HEAT EXCHANGER
OUTLET PIPE
DOMESTIC HOT
1457514576
14.2 Draining of Boiler Hot Water Circuit
Drain the Domestic Hot Water circuit by closing the cold-water
isolation valve on the boiler.
Open one or more hot water taps to drain the hot water circuit.
After replacing parts open the cold-water isolation valve and
slowly open a hot water tap to remove air. Close the hot water
tap and check for any leaks.
14.3 Domestic hot water sensor
For access, refer to section 14.1.
The domestic hot water sensor is located on the left side of
the hydroblock’s hot water side, see diagram 14.1.
Carefully disconnect the electrical connections from the
domestic hot water sensor.
Remove the domestic hot water sensor using a 13mm
spanner.
Fit the replacement domestic hot water sensor ensuring the
washer is correctly tted.
Re-t the electrical connections to the replacement sensor.
CENTRAL HEATING
SENSOR
ELECTRICAL
CONNECTIONS
Diagram 14.2
14.5 fan unit
For access, refer to section 14.1.
Refer to section 12.2 to replace the fan.
Fit the replacement fan unit in reverse order and reconnect
the electrical connections and sensing tube.
56
14 Replacement of parts
14.6 Air pressure switch
For access, refer to section 14.1.
The air pressure switch is located above the expansion
vessel, see diagram 14.3.
Remove the sensing tubes and electrical connections from
the air pressure switch, noting which tube is connected to
which port.
Remove the air pressure switch by unclipping it from the
bracket.
Fit the replacement air pressure switch in reverse order of
removal.
BRACKET
SECURING
SCREWS (2 OFF)
ELECTRICAL
CONNECTIONS
14543
14.8 Printed circuit board
For access, refer to section 14.1.
Turn off and isolate the electrical supply.
Unclip the two front retaining clips on the controls fascia, see
diagram 10.3.
Unclip and carefully pull down the control circuit board cover,
see diagram 10.4.
Remove the electrical connections to the PCB by pulling
carefully, noting the locations of all the terminals.
Release the four screws securing the PCB to the control panel
and lift out the PCB.
Fit the replacement PCB in reverse order to removal, ensuring
that the PCB electrical connections are fully pushed home.
Check and re-set as necessary the potentiometers and dip
switches to the same value as the old PCB.
SECURING SCREWS (4 OFF)
1457814494
SENSING TUBES
(2 OFF)
AIR PRESSURE
SWITCH
Diagram 14.3
14.7 Burner
Refer to section 12.3. to replace the burner.
Retain all washers/gaskets for use on re-assembly.
Remove the burner injectors as shown in diagram 14.4.
Fit the burner injectors to the new burner injector bar and
tighten, ensuring that the injector size, marked on each
injector is the same as stated in the ‘Boiler Specication
section’ page 8, for the type of gas being used.
Replace the burner bar and re-t the burner blades (replace
any damaged seals as necessary).
Fit replacement burner in reverse order.
Check gas soundness and boiler operation.
INJECTOR
BURNER
INJECTOR BAR
14577
PRINTED CIRCUIT BOARD
Diagram 14.5
14.9 Pump head
For access, refer to section 14.1.
Drain the boiler’s circuit as detailed in section 14.2.
Remove the screws, see diagram 14.6.
Pull off the motor, remove the cover and disconnect the
electrical connections from cable box.
Fit the replacement motor in reverse order ensuring correct
polarity of the electrical connections.
Re-open the isolating valves on the ow and return
connections, rell, vent and re-pressurise the system, check
for leakage.
COVER
SECURING SCREWS (4 OFF)
PUMP
HEAD
Diagram 14.6Diagram 14.4
57
14 Replacement of parts
14.10 Pump body
For access, refer to section 14.1.
Remove the motor as described in section 14.9.
Remove the low water pressure sensor refer to section 14.11.
Remove the secondary heat exchanger as described in
section 14.12.
Refer to diagram 14.7.
Remove the expansion vessel pipe by removing the clip on
the pump body. (clip at the rear, see diagram 14.8.
Remove the pressure gauge connection and electrical
connection form the R.H.hydroblock.
Disconnect the union nuts (pressure safety relief valve and
pump outlet).
Refer to diagram 14.9.
Remove the xing screws from the pump and R.H.hydroblock
at the bottom of the boiler.
Remove the pump assembly.
Refer to diagram 14.10.
Remove the pump body, automatic air vent and brass union
connector from the R.H. hydraulic assembly by releasing the
clips. Fit these to the replacement pump body.
Fit the replacement pump body and associated parts in
reverse order ensuring that all sealing washers are sound and
tted correctly and the polarity of the electrical connections
are correct.
Open the isolating valves on the low and return connections,
rell, vent and re-pressurise the system ensuring all joints are
sound.
SECURING
SCREW
AUTOMATIC
AIR VENT
CLIP
SECURING
SCREWS
Diagram 14.9
14581
14583
UNION
NUT
ELECTRICAL
CONNECTION
EXPANSION
VESSEL
PIPE
SECURING
SCREW
CLIP
PRESSURE
GAUGE
CONNECTION
CLIP
UNION
NUT
PUMP
BODY
Diagram 14.7
14562
14579
CLIP
PUMP
BODY
CLIP
BRASS UNION
CONNECTOR
R.H. HYDRAULIC
ASSEMBLY
Diagram 14.10
58
PUMP
BODY
Diagram 14.8
14 Replacement of parts
14.11 low water pressure sensor
For access, refer to section 14.1.
Drain the boiler circuit, refer to section 14.2.
Locate the low water pressure sensor at the front right
hand side of the boiler and remove the electrical sensors
connections, see diagram 14.11.
Remove the low water pressure sensor by turning it in an
anticlockwise direction.
Fit the replacement sensor in reverse order of removal
ensuring all washers are tted.
Replace damaged washers as necessary.
Open the isolating valves on the ow and return connections,
rell, vent and re-pressurise the system ensuring all joints are
sound.
LOW WATER
PRESSURE
SENSOR
14494
14.13 Primary Heat Exchanger
For access, refer to section 14.1.
Drain the boiler circuit, refer to section 14.2.
Refer to diagram 14.13.
Remove the pipe clips on the pipes of primary heat
exchanger.
Remove the CH temperature sensor on the return pipe.
Remove the pump and three way valve connection pipes.
Release the pipe connections, retaining the washers for
re-assembly.
Remove the combustion chamber cover, see section 12.1.
Carefully remove the heat exchanger by pulling forward taking
care not to damage the insulation.
Fit the new heat exchanger and reassemble the boiler in
reverse order ensuring all the washers are tted, or replaced
as required.
Open the isolating valves on ow and return connections,
rell, vent and re-pressurise system ensuring the all joints are
sound.
PIPE CLIP
14584
ELECTRICAL
CONNECTIONS
Diagram 14.11
14.12 Secondary heat exchanger
For access, refer to section 14.1.
Drain the boiler circuit, refer to section 14.2.
Remove the two screws which connect the heat exchanger to
the L.H. / R.H. hydroblocks, see diagram 14.12.
Remove the heat exchanger from the gap on the left hand
side.
Fit the new heat exchanger checking that the plate numbers
are the same and reassemble in reverse order ensuring all
washers are tted or replaced as required.
Open the isolating valves on the ow and return connections,
rell, vent and re-pressurise the system ensuring all joints are
sound.
******
PRIMARY
HEAT
EXCHANGER
THREE WAY VALVE
CONNECTION PIPE
PIPE CLIP
OVERHEAT SAFETY
THERMOSTAT
PUMP
CONNECTION PIPE
SECURING SCREWS
Diagram 14.12
Diagram 14.13
59
14 Replacement of parts
14.14 Gas valve
For access, refer to section 14.0.
Ensure that gas supply to boiler is turned off.
Refer to diagrams 14.14 and 14.15.
Disconnect the electrical connections to the modulating coil.
Remove the screw to disconnect the gas valve electrical plug.
Release the connections from gas valve and manifold inlet,
Remove the sensing tube.
Retaining the washers for use on reassembly.
Release the main gas connection between the gas valve
supply pipe and gas inlet isolation valve, retaining the washer
for use on reassembly, see diagram 14.15.
Remove the gas valve’s two securing screws and washers
from the underside of the boiler, see diagram 14.17.
Rotate the gas pipe and withdraw gas valve assembly.
Ret in reverse order to removal, the polarity of the wires to
the modulating coil is not important.
Check gas soundness and correct boiler operation
Following replacement the maximum and minimum settings
for natural gas must be checked to ensure they are 12.5 mbar
/ 2.5 mbar for the Betacom 24 and 14 mbar / 2.3 mbar for
Betacom 30 respectively.
Check the gas valve settings and re-calibrated by the
following method if required:
GAS VALVE AND
MANIFOLD INLET
CONNECTIONS
SENSING TUBE
MODULATING
COIL
14585
SCREW
Minimum setting
Remove the sensing tube from the gas valve.
Remove one lead from the modulating gas valve coil, see
diagram 14.15.
Refer to diagram 14.16.
Connect a suitable pressure gauge to the pressure outlet of
the gas valve.
Turn the boiler’s function switch to the ‘Winter’ position.
(Heating and Hot Water), see diagram 11.4
Turn the central heating temperature control to maximum
setting.
Remove the protective cover from the gas valve adjuster.
Turn the inner screw using a screwdriver, clockwise: to
increase the pressure setting, anticlockwise: to decrease the
pressure setting.
After correct adjustment see, ‘Boiler specication section’
page 8, re-connect the electrical connector and protective
cover and replace the combustion cover to the boiler.
Maximum setting
Remove the sensing tube from the gas valve, see diagram
14.14.
Remove the protective cover from the gas valve adjuster.
Push the ball inside the modulating gas valve coil using a
sharp pointed tool.
Turn the nut with a 10mm spanner (keeping the ball in without
any rotation) clockwise: to increase the pressure setting,
anticlockwise: to decrease the pressure setting.
After correct adjustment see, “Boiler specication” section,
page 8.
Finally, replace the sensing tube to the gas valve.
ELECTRICAL
AND EARTH
CONNECTIONS
GAS VALVE
ADJUSTER
ELECTRICAL
PLUG
Diagram 14.14
Diagram 14.15
15524
60
GAS
ISOLATION
VALVE
14 Replacement of parts
15525
Diagram 14.16
SECURING
SCREWS
14586
SUPPLY PIPE
CONNECTION
Diagram 14.17
Checking the gas rate
The boiler is tted with a fully modulating automatic gas valve. With all other gas appliances turned off
measure the gas rate at the gas meter. Check that the gas rate is as stated in the table below:
Gas rate
Appliance Maximum net heat input in kW
Betacom 24c
Betacom 30c
Checking the combustion products
While adjusting the burner pressure at maximum and minimum, combustion products can be checked
according to the table below:
For access, refer to section 14.1.
Drain the boiler circuit, refer to section 14.2.
Refer to diagram 14.16.
Disconnect the exible pipe coupling on expansion vessel.
Release and remove the nut securing the expansion vessel to
the boiler.
Remove the side panels.
Remove the air pressure switch, refer to section 14.6.
Remove the ue if required.
Lift the vessel out of boiler from the gap over the chassis
and t the replacement vessel to the boiler in reverse order
to removal, ensuring that sealing washer is tted to pipe
connection before tightening, replace the washer if necessary.
Using a pressure gauge, ensure that expansion vessel charge
pressure is 0•5bar (7•5psi)
Open the isolating valves on the ow and return connections,
rell, vent and pressurise the boiler ensuring all joints are
sound.
FLEXIBLE PIPE
CONNECTION
SECURING NUT
14587
OVER HEAT SAFETY
THERMOSTAT
ELECTRICAL
CONNECTIONS
Diagram 14.17
14.17 Pressure safety relief valve
For access, refer to section 14.1.
Drain the boiler circuit, refer to section 14.2.
Refer to diagram 14.18.
Disconnect the discharge pipe on the outlet of the safety relief
valve.
Unscrew to remove the safety relief valve from the R.H.
hydroblock and retain the o-ring for use on reassembly,
replace as necessary.
Fit the replacement safety relief valve in reverse order to
removal and rell, vent and pressurise boiler ensuring all joints
are sound.
14588
Diagram 14.16
14.16 Overheat safety thermostats
For access, refer to section 14.1.
Remove the front panel, combustion chamber cover and right
side panel.
Refer to diagram 14.17.
Locate the overheat safety thermostat at the front left hand
side of the boiler and on the right hand side of the primary
heat exchanger.
Disconnect the electrical connections from the thermostat.
Unclip the thermostat from the pipe.
Fit the replacement thermostat in reverse order of removal.
PRESSURE
SAFETY RELIEF
VALVE
DISCHARGE
PIPE
UNSCREW
TO REMOVE
R.H. HYDRAULIC
BLOCK
14589
Diagram 14.18
62
14 Replacement of parts
14.18 R.H. and L.H. Hydroblock
For access, refer to section 14.1.
Drain the boiler circuit, refer to section 14.2.
Refer to diagram 14.12.
Remove the secondary heat exchanger, see section 14.12.
Remove the pump assembly, see section 14.9. and 14.10.
Remove the section of the hydroblock from the pump by
releasing the clip.
Release the heat exchanger outlet pipe nut and rotate the
pipe for easy removal of the left section of the hydroblock.
Disconnect the three way valve motor, electrical connection
and remove the motor by releasing the clip, see section
14.21.
Release the nut connecting the CH outlet connection to the
hydroblock.
Disconnect the DHW sensor, see section 14.3.
Remove the screw securing the left part of the hydroblock to
the combination boiler.
Fit the replacement hydroblock parts in reverse order to
removal ensuring all seals are correctly located and replaced
if necessary.
Open the isolating valves on the ow and return connections,
rell, vent and pressurise boiler ensuring all joints are sound.
14.19 Filter
For access, refer to section 14.1.
Drain the boiler circuit, refer to section 14.2.
Refer to section 12.5. to remove.
Remove the lter in the inlet to the hydroblock.
Clean or t a replacement lter.
Fit the components in reverse order of removal, ensuring all
seals are correctly located and replaced if damaged.
Open the isolating valves on the ow and return connections,
rell, vent and pressurise the boiler ensuring all joints are
sound.
14.21 Three way valve motor
For access, refer to section 14.1.
Refer to diagram 14.20.
Ensure that the electric supply to the boiler is switched OFF.
Remove the electrical connection to the three way valve
motor.
Remove the clips connecting the valve to L.H. hydroblock.
Fit the replacement valve in reverse order ensuring the valve
is tted properly.
ELECTRICAL
CONNECTION
CLIP
THREE WAY
VALVE MOTOR
Diagram 14.20
14590
14.20 Flow sensor
For access, refer to section 14.1.
Refer to diagram 14.19.
Remove the ow sensor using a pair of pliers.
Fit a replacement sensor in reverse order to removal.
FLOW
SENSOR
ELECTRICAL
CONNECTION
UNCLIP
TO REMOVE
Diagram 14.19
14562
63
15 Spare parts
15.1 Spare Parts
When ordering spare parts, contact Glow-worm’s own service organisation using the telephone number on the inside front cover of
this booklet. Please quote the name of the appliance and serial number, to be found on the data label. If ordering from British Gas
also quote the G.C. number of the part.
No.DescriptionModelPart No.
1Fan0020061578
2Primary heat exchanger24c0020061589
3Primary heat exchanger30c0020061590
4Air pressure switch0020064058
5Ignition electrode (right)0020051571
6Ignition electrode (left)0020061572
7Flame sense (ionisation)
electrode
8Safety valve0020061610
9CH NTC sensor0020061581
10O/h safety thermostat (reset)0020061584
11DHW sensor0020061613
12Limit thermostat0020061592
13Water ow sensor0020061608
14Low water pressure switch0020061607
15Injector24c0020061567
0020061573
No.DescriptionModelPart No.
16Injector30c0020061568
17Diverter motor0020061621
18Burner24c0020061564
19Burner30c0020061565
20Secondary heat exchanger24c0020061614
21Secondary heat exchanger30c0020061615
22Pump0020061598
23Interface board0020061647
24Timer clock0020061649
25Water pressure gauge0020061648
26Gas valve0020061602
27Printed circuit board0020061654
28Burner bar (manifold)24c0020061569
29Burner bar (manifold)30c0020061570
64
15 Spare parts
12, 3
10
11
12
13
17
18, 19
9
14
8
15,16
14595
4
5
6
7
28, 29
20, 21
27
26
25
22
23
24
Diagram 15.17
65
16 Manual Handling
IMPORTANT.With regards to the Manual Handling Opera-
tions, 1992 Regulations, the following lift operation exceeds the
recommended weight for a one man lift.
General recommendations when handling
Clear the route before attempting the lift.
Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. Do not twist – reposition feet instead. If 2 persons performing lift, ensure co-ordinated
movements during lift. Avoid upper body/top heavy bending - do not
lean forward/sideways. Recommend wear suitable cut resistant gloves
with good grip to protect against sharp edges and ensure good grip.
Always use assistance if required.
Removal of carton from delivery van
Recommend 2 person lift or 1 person with use of sack truck. If 1
person is performing lift, straddle the load, tilt and place carton into position on truck. Recommend secure appliance onto truck with suitable
straps. Ensure safe lifting techniques are used – keep back straight
– bend using legs. Keep load as close to body as possible. If 2 persons
performing lift, ensure co-ordinated movements during lift. Always use
assistance if required.
Carriage of carton from point of delivery to point
of installation – ground oor.
Recommend 2 person lift or 1 person with use of sack truck. If 1 person
is performing lift, straddle the load, tilt and place carton into position on
truck. Recommend secure appliance onto truck with suitable straps.
Ensure safe lifting techniques are used – keep back straight – bend
using legs. Keep load as close to body as possible. If 2 persons performing lift, ensure co-ordinated movements during lift. Clear the route
before attempting the lift. If removing boiler from truck straddle the load
and tilt forwards to facilitate secure grip. Ensure safe lifting techniques
are used – keep back straight – bend using legs. Do not twist – reposition feet instead. Take care to avoid trip hazards, slippery or wet
surfaces and when climbing steps and stairs. Always use assistance if
required.
Carriage of carton from point of delivery to point
of installation – rst or higher oor, cellar.
Recommend 2-person lift or 1 person with use of sack truck. If 1 person
is performing lift, straddle the load, tilt and place carton into position on
truck. Recommend secure appliance onto truck with suitable straps.
Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. If 2 persons performing lift, ensure co-ordinated movements during lift. Avoid upper body/top
heavy bending - do not lean forward/sideways. Clear the route before
attempting the lift. If removing boiler from truck straddle the load and
tilt forwards to facilitate secure grip. Ensure safe lifting techniques are
used – keep back straight – bend using legs. Do not twist – reposition
feet instead. Take care to avoid trip hazards, slippery or wet surfaces
and when climbing steps and stairs. Always use assistance if required.
Carriage of carton from point of delivery to point
of installation – roofspace.
Recommend 2-person lift. Ensure co-ordinated movements during
lift. Avoid upper body/top heavy bending - do not lean forward/sideways. Clear the route before attempting the lift. Take care to avoid trip
hazards, slippery or wet surfaces and when climbing steps and stairs.
When transferring appliance into roofspace, recommend 1 person to be
in roofspace to receive the appliance and other person to be below to
pass up and support appliance. Ensure safe lifting techniques are used
– keep back straight – bend using legs. Keep load as close to body as
possible. Always use assistance if required. It is assumed safe access,
ooring and adequate lighting are provided in the roof space. It is
recommended a risk assessment of the roof space area be carried out
before moving the appliance into the area to take into account access,
stability of ooring, lighting and other factors, and appropriate measures
taken.
Unpacking of appliance from carton.
Recommend 2 persons unpack appliance from carton. Always keep
working area clear. Recommend cut base end of carton and open
carton aps, then tilt boiler forwards from its side onto its base and
remove carton by sliding up over the boiler. Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as
close to body as possible. Always use assistance if required. Dispose
of packaging in a responsible manner. Recommend wear suitable
cut resistant gloves with good grip to protect against sharp edges and
ensure good grip when handling appliance outside packaging.
Positioning of Appliance for Final Installation
– no obstructions.
This appliance is deemed to be a one person lift when removed from
the carton. Fit bracket securely onto wall before lifting appliance into
position. Obtain rm grip on front and sides of appliance, lift upwards,
ensure stable balance achieved and lift upwards to position in place
on bracket. Ensure safe lifting techniques are used – keep back
straight – bend using legs - when lifting load from oor level. Do not
twist – reposition feet instead. Keep boiler as close as possible to
body throughout lift to minimise strain on back. Ensure co-ordinated
movements to ensure equal spread of weight of load. Always use
assistance if required. Recommend wear suitable cut resistant gloves
with good grip to protect against sharp edges and ensure good grip
when handling appliance.
Positioning of Appliance for Final Installation
– above worktop, foreseeable obstructions etc.
This appliance is deemed to be a one person lift when removed from
the carton. Fit bracket securely onto wall before lifting appliance into
position. Obtain rm grip on front and sides of appliance, lift upwards,
onto worktop if practicable. Ensure stable balance achieved and lift
upwards to position in place on bracket. If 2 persons positioning onto
bracket obtain rm grip at front and sides/base of boiler. Ensure co-
ordinated movements during 2 person lifts to ensure equal spread of
weight of load. Ensure safe lifting techniques are used – keep back
straight – bend using legs - when lifting load from oor level. Do not
twist – reposition feet instead. Keep boiler as close as possible to body
throughout lift to minimise strain on back. Avoid upper body/top heavy
bending - do not lean forward/sideways. Always use assistance if required. Recommend wear suitable cut resistant gloves with good grip
to protect against sharp edges and ensure good grip when handling
appliance.
Positioning of Appliance for Final Installation –
within compartment etc. restricting installation.
This appliance is deemed to be a one person lift when removed from
the carton. Fit bracket securely onto wall before lifting appliance into
position. Obtain rm grip on front and sides of appliance, lift upwards,
onto worktop if practicable. Ensure stable balance achieved and lift
upwards to drop into place onto bracket. If 2 persons positioning onto
bracket obtain rm grip at front and sides/base of boiler. Ensure co-
ordinated movements during 2 person lifts to ensure equal spread of
weight of load. If 1 person positioning onto bracket recommend obtain
rm grip supporting base of boiler. Ensure safe lifting techniques are
used – keep back straight – bend using legs - when lifting load from
oor level. Do not twist – reposition feet instead. Keep boiler as close
as possible to body throughout lift to minimise strain on back. Always
use assistance if required. Recommend wear suitable cut resistant
gloves with good grip to protect against sharp edges and ensure good
grip when handling appliance.
Positioning of Appliance for Final Installation
– in roof space restricting installation.
This appliance is deemed to be a one person lift when removed from
the carton. Obtain rm grip on front and sides of appliance, lift upwards, ensure stable balance achieved and lift upwards to drop into
place onto bracket. If 2 persons positioning onto bracket obtain rm
grip at front and sides/base of boiler. Ensure co-ordinated movements
during 2 person lifts to ensure equal spread of weight of load. If 1
person positioning onto bracket recommend obtain rm grip supporting base of boiler. Ensure safe lifting techniques are used - keep back
straight – bend using legs - when lifting load from oor level. Do not
twist – reposition feet instead. Keep boiler as close as possible to body
throughout lift to minimise strain on back. Always use assistance if required. Recommend wear suitable cut resistant gloves with good grip
to protect against sharp edges and ensure good grip when handling
appliance. It is recommended a risk assessment of the roof space
area be carried out before moving the appliance into the area to take
into account access, stability of ooring, lighting and other factors, and
appropriate measures taken.
66
17 Declaration of conformity
67
Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.