General ASH12FB, ASH12FSBCW, AOH12FSBC, ASH9FB, ASH9FSBCW Service Manual

...
SPLIT TYPE ROOM AIR CONDITIONER
WALL MOUNTED
type
Models Indoor unit Outdoor unit
ASH9FSB
ASH12FSBCW AOH12FSBC
CW
AOH9FSB
CONTENTS
. . . . . . . .
. . . . . .
. . . . . .
. . .
. . . . . .
. . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .
. . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . .
. . . . . . . .
. . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . . . . .
. . . . .
. . .
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 1
OUTLINE AND DIMENSIONS . . . . . . . . . . . . . . . 3
REFRIGERANT SYSTEM DIAGRAM . . . . . . . . 4
CIRCUIT DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . 5
INDOOR PRINTED CIRCUIT BOARD CIRCUIT DIAGRAM ERROR DISPLAY
DISASSEMBLY ILLUSTRATION . . . . . . . . . . . . .
PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
STANDARD ACCESSORIES . . . . . . . . . . . . . . . .14
6 7
8
S P E C I F I C A T I O N S
TYPE
INDOOR UNIT
OUTDOOR UNIT COOLING CAPACITY
(kW)
COOLING COOLING
ASH9FSBCW ASH12FSBCW
AOH9FSBC AOH12FSBC
2.75 3.40
ELECTRICAL DATA
POWER SOURCE
RUNNING CURRENT (A)
INPUT WATTS (kW)
E.E.R (kW/kW)
MOISTURE REMOVAL
AIR CIRCULATION-Hi
3
(m /hr) 540 540
230V 50Hz 230V 50Hz
4.7 6.2
1.05 1.33
2.62 2.56
1.3 1.8
COMPRESSOR
TYPE
CODE REFRIGERANT R410A
(g)
Hermetic type, Permanent split condenser, 2 pole, Single phase, Induction motor
80230135 220, 230, 240V / 50Hz 80235035 220-240V / 50Hz
590 720
FAN MOTOR
POWER SUPPLY (V) 230 230
INDOOR UNIT
Hi-SPEED (r.p.m) 1,310 MED-SPEED (r.p.m) 1,190 LO-SPEED (r.p.m) 1,070 S-LO (r.p.m) 960
1,310 1,230 1,150
1,080
OUTDOOR UNIT (r.p.m) 740 740
DIMENSIONS
INDOOR UNIT OUTDOOR UNIT
H x W x D
(mm)
WEIGHT INDOOR UNIT OUTDOOR UNIT
GROSS NET(kg)
NOISE LEVEL
Hi-SPEED (dB) 39 39
INDOOR UNIT
MED-SPEED (dB) 37
LO-SPEED (dB)
S-LO (dB)
OUTDOOR UNIT (dB)
257 x 808 x 187 257 x 808 x 187
535 x 695 x 250 535 x 695 x 250
10 / 8 10 / 8
33 / 30 35 / 32
37
34 35
31
33
45 46
12003.10.30
ADDITIONAL CHARGE OF REFRIGERANT (ASH9FSBCW / AOH9FSBC)
(ASH12FSBCW / AOH12FSBC)
Refrigerant suitable for a piping length of 7.5 m is charged in the outdoor unit at the factory.
When the piping is longer than 7.5 m, additional charging is necessary.
For the additional amount, see the table below.
PIPE LENGTH 7.5 m 10 m
ADDITIONAL REFRIGERANT None 50 g
Between 7.5 m and 10 m, when using a connection pipe other than that in the table,
charge additional refrigerant with 20g /1 m as the criteria.
(The maximum length of piping is 15m. If the units are further apart than this, correct
operation can not be guaranteed.)
15 m
150 g
2003.10.30 2
DIM E N S ION S
INDOOR UNIT
257
OUTDOOR UNIT
808
808
808 187
440
440
187
U nit : m m
Drain pipe hold 20
54
500
695 250
O
265
98
535
290
13
32003.10.30
REFRIGERANT SYSTEM DIAGRAM
Models : ASH9FSBCW / AOH9FSBC
[ INDOOR UNIT ]
[ Connecting pipe ]
[ OUTDOOR UNIT ]
ComĀ­pressor
(Flare connection) Gas pipe (9.52 dia.) (Flare connection)
3-Way valve (with charging port)
Condenser
Evaporator
(Flare connection) Liquid pipe (6.35 dia.) (Flare connection)
2-Way valve
Dryer
Capillary tube
Models : ASH12FSBCW / AOH12FSBC
[ INDOOR UNIT ]
[ Connecting pipe ]
(Flare connection) Gas pipe (9.52 dia.) (Flare connection)
[ OUTDOOR UNIT ]
3-Way valve (with charging port)
ComĀ­pressor
Condenser
Evaporator
(Flare connection) Liquid pipe (6.35 dia.) (Flare connection)
2-Way valve
Dryer
Capillary tube
2003.10.30 4