General ABH18L, ABH18LBAJ, AOH18LMAKL Technical Manual

R410A
2 . FLOOR / CEILING TYPE :  AB 18LBAJ
D2D_AB007E/01
2006.01.10
2-1. FEATURE
FLOOR / CEILING TYPE
AB18
FEATURES
Compact design
Symmetrical thin and compact design Flat and round form
Flexible installation
FLOOR / CEILING TYPE
AB18
FLOOR
Double auto swing
Combination of up/down and right/left air direction swing allows three-dimensional air direction control. Since up/down air direction flaps operate automatically, according to the operating mode of the unit, it is possible to set the air direction based on the operating mode.
Super vane
The double-flap "Super Vane" with newly developed special configuration boosts the air flow, sending cool air quickly to every corner of the room.
CEILING
RIGHT and LEFT
swing
5 steps selectable
UP and DOWN
swing
Swing
Steps
7 steps selectable
Others
Auto Restart
Detachable and Washable Open Panel
Auto Shut Flaps
New model Old model
Non-operation mode Operation mode
- (02 - 01) -
2-2. REMOTE CONTROLLER
2-2-1.
FLOOR / CEILING TYPE
AB18
WIRELESS REMOTE CONTROLLER
FEATURES
Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible.
Four kinds of timers. Easy operation.
Easy to change transmission code (4 patterns) by button operation.
Built-in timers
Select from four different timer programs (On/Off/Program/Sleep).
Program timer
The program timer operates the ON and OFF timer once within a 24 hour period.
FLOOR / CEILING TYPE
AB18
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the time setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature automatically rises 1 °C every hour. The set temperature can rise up to a maximum of 2 °C.
Timer setting
60min.
1 °C
2 °C
Heating operation
When the sleep timer is set, the set temperature automatically drops 1 °C every 30 minutes. The set temperature can drop to a maximum of 4 °C.
1 °C
2 °C
3 °C
4 °C
30min.
60min.
90min.
Timer setting
Easy operation
After code change
Mixed-up
• Code selector switch eliminates unit being wrongly switched. (Up to 4 codes can be set.)
A B C D
A B
C
D
•Wide and precise transmitting range.
1. Press the MASTER CONTROL button for more than five seconds to start the code change.
2. Press the (+) or (-) button to select the desired code.
A B C D
3. Press the MASTER CONTROL button again to end the code change.
- (02 - 02) -
FUNCTIONS
5
1
START/STOP button
Pressed to start and stop operation
64
Display
2
Set temp./Set time buttons/Set remote controller custom code buttons
Sets the indoor temp./Sets the current time and on-off time /Set R.C. custom code
FLOOR / CEILING TYPE
AB18
3
2
9
10
13
1
7
11
12
14
8
3
Master control button/
Code change
Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY). Start/end R.C. custom code change. (Max. 4 types)
4
Sleep timer button
Pressed to select sleep timer.
5
Signal transmitter
6
Timer button
FLOOR / CEILING TYPE
AB18
Pressed to select the timer mode. (OFF TIMER, ON TIMER, PROGRAM TIMER, TIMER RESET)
7
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
8
Battery compartment lid
9
Air flow direction vertical set button
TEST
RUN
15
10
Air flow direction vertical swing button
Display panel
16
17
18
SPECIFICATION
19
20
21
22
23
11
Air flow direction horizontal swing button
12
Air flow direction horizontal set button
13
Time adjust button
Sets the current time.
14
ACL button
Used when replacing batteries or change the code.
15
Test run button
Used when testing the air conditioner after installation.
16
Transmit indicator
17
Clock display
18
Master control display
19
Timer mode display
20
Fan speed display
21
Set temperature display
22
Timer set indicator
23
Temperature set indicator
SIZE (H x W x D mm) 160 x 56 x 20
WEIGHT ( g ) 120
ACCESSORY Holder
- (02 - 03) -
2-3. SPECIFICATIONS
AB 18LBAJ
AO 18LMAKL
230V 50Hz
198-264V 50Hz
Fin Pitch 1.30
Fin Pitch 1.45
6.35
12.7
mm
INDOOR
COMPRESSOR
AVAILABLE VOLTAGE RANGE
mm
Rows x Stages
OUTPUT
r.p.m
INDOOR OUTDOOR
dB(A)
W
EUROPEAN ENERGY LABEL
FAN SPEED COOL/HEAT INDOOR
m3/h
CURRENT STARTING CURRENT
MOISTURE REMOVAL
INDOOR
TYPE
STARTING METHOD
INDOOR
Coil
MODEL NAME
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
INDOOR FAN TYPE x Q'ty
FAN MOTOR OUTPUT OUTDOOR
CAPACITY
AIR CIRCULATION COOL/HEAT
OUTDOOR
kW/kW
A
TYPE
CONNECTION METHOD
NET OUTDOOR
MAX HEIGHT
MAX LENGTH
mm
Fin
TYPE
kW
INPUT POWER
COOLING
HEATING
RATED / MAX
RATED / MAX
INDOOR
OUTDOOR
POWER SOURCE
DIMENSIONS H × W × D
Rows x Stages
GROSS
NET / GROSS
OUTDOOR
OUTDOOR
Coil
CASING COLOR
HEAT EXCHANGER TYPE
Fin
REFRIGERANT TYPE
PIPE
SIZE
OPERATION(OUTDOOR)
°C
kg(lbs)
SIZE
REMOTE CONTROLLER
DRAIN PIPE MATERIAL
WEIGHT REFRIGERANT OIL
mm
FLOOR / CEILING TYPE
AB18
COOLING RATED / MAX 1.70/1.99
HEATING RATED / MAX 1.90/2.40
COOLING RATED / MAX 7.4/8.8
HEATING RATED / MAX 8.3/10.5
EER COOLING 3.06
COP HEATING 3.26
High 780/780
Med 650/650
Low 550/550
High 2800/2800
Low 1400/1400
High 1030/1030
Med 890/890
Low 770/770
High 780/780
Low 400/400
INDOOR 30
OUTDOOR 65
High 44/44(Floor console) , 43/43(Under ceiling)
Med 40/40(Floor console) , 39/39(Under ceiling)
Low 36/36(Floor console) , 35/35(Under ceiling)
FLOOR CEILING MODELS
HEAT PUMP TYPE
B
kW 5.20/5.90
BTU/h 17800/20100
kW 6.20/7.50
BTU/h 21200/25600
A 10
l/h(Pints/h) 1.7(3.6)
Sirocco × 2
Propeller × 1
50/52
DC TWIN ROTARY
W 1300
Inverter Method
Copper tube
Aluminiume
3 × 12
FLOOR / CEILING TYPE
AB18
Note: Specifications are based on the following conditions. Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB. Heating: Indoor tem perature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB. Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Coil Dimensions 252 × 800 × 39.9
Copper tube
Aluminiume
2 × 30
Coil Dimensions 630 × 901 × 36.38
White(5Y9/0.5NN)
Beige(10YR7.5/1.0NN)
INDOOR 199 × 990 × 655
OUTDOOR 650 × 830 × 320
INDOOR 320 × 1150 × 790
OUTDOOR 743 × 984 × 413
INDOOR 28/37(62/82)
OUTDOOR 54/58(119/128)
FLARE
LIQUID
GAS
m 25(Chargeless 10)
m 15
R410A
CHARGE g 1500
COOLING 0 to 43 °C
HEATING -10 to 24 °C
WIRELESS
mm Outer diameter 26.0 / Inner diameter 21.5
- (02 - 04) -
POE
ABS
2-4. DIMENSIONS
2-4-1. OUTDOOR UNIT
MODEL : AO 18L
FLOOR / CEILING TYPE
AB18
Top view
830
650
12
Front view
Bottom
Air flow
Side view
(Unit : mm)
350
320
FLOOR / CEILING TYPE
AB18
154
101
58
90
MOUNTING POSITION
When there are obstacles at the back or front sides.
603
Bottom view
When there are obstacles at the back, side(s), and top.
600 mm or more
343
When there are obstacles at the back, side with the installation of more than one unit.
600 mm or more
100 mm or more
100 mm or more
25
(
S
0 mm o
er
v
i
c
r
more
e s
p
ac
e)
- (02 - 05) -
300 mm or more
250 mm or more
250 mm or more
300 mm or more
2-4-2. INDOOR UNIT
MODEL : AB 18L
FLOOR / CEILING TYPE
AB18
6
1 2
Side view
1
2
Rear view
(Unit : mm)
45
FLOOR / CEILING TYPE
AB18
3
1
Refrigerant piping flare connection (Gas)
2
Refrigerant piping flare connection (Liquid)
3
Drain piping connection (Drain pipe : I.D. 25 O.D. 29 L 700)
4
Knock out hole for drain piping
5
Knock out hole for refrigerant piping
6
Hole for lifting bolt (Use M10 screw bolt)
990
500 245
65
655
530
45
125
100 hole
50 hole
100 hole
Wall bracket
Side of set
65
Bottom view
3
- (02 - 06) -
MOUNTING POSITION
Floor
(Unit : mm)
FLOOR / CEILING TYPE
AB18
Left Right
300 or more300 or more
Ceiling
FLOOR / CEILING TYPE
AB18
Left
150 or more 300 or more
Indoor unit
Ceiling
2300 or more
20 or more
1000 or more
Obstruction
Right
- (02 - 07) -