General ASH14L, ASH14LSBCW, AOH14LFBC, ASH18L, ASH18LSBCW Installation Manual

...
SPLIT TYPE ROOM AIR CONDITIONER
INSTALLATION MANUAL
(PART NO. 9313802028-01)
This air conditioner uses new refrigerant HFC (R410A).
The basic installation work procedures are the same as conventional refrigerant (R22) models.
However, pay careful attention to the following points:
(1) Since the working pressure is 1.6 times higher than that of conventional refrigerant (R22) models,
some of the piping and installation and service tools are special.(See the table below.) Especially, when replacing a conventional refrigerant (R22) model with a new refrigerant R410A
model, always replace the conventional piping and flare nuts with the R410A piping and flare nuts.
(2) Models that use refrigerant R410A have a different charging port thread diameter to prevent
erroneous charging with conventional refrigerant (R22) and for safety. Therefore, check beforehand.[The charging port thread diameter for R410A is 1/2 threads per inch.]
(3) Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant
(R22) models. Also, when storing the piping ,securely seal the opening by pinching ,taping, etc.
(4) When charging the refrigerant, take into account the slight change in the composition of the
gas and liquid phases, and always charge from the liquid phase side whose composition is stable.
For authorized service personnel only.
WARNING
(1) For the room air conditioner to operate satisfactory, install it as outlined in this installation manual. (2) Connect the indoor unit and outdoor unit with the air conditioner piping and cords available standards parts. This
installation manual describes the correct connections using the standard accessories and the parts specified in
this installation manual. (3) Have installation work done by authorized service personnel only. (4) Never cut the power cord, lengthen or shorten the cord, or change the plug. (5) Also do not use an extension cord. (6) Plug in the power cord plug firmly. If the receptacle is loose, repair it before using the room air conditioner.
(7) Do not turn on the power until all installation work is complete.
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation manual because it is used when the air conditioner is serviced or moved.
The maximum length of the piping is 20 m. The maximum height difference of the piping is 10 m,
if the units are further apart than these, correct operation can not be guaranteed.
STANDARD ACCESSORIES
The following installation accessories are supplied. Use them as required.
One set of following parts are necessary in istallation of this product.
Special tools for R410A
Tool name
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount of residual oil is less than 40 mg/10m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface). Otherwise, the ex­pansion value or capillary tube may become blocked with contaminants. As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials. Thicknesses of copper pipes used with R410A are as shown in Table1.Never us copper pipes thinner than 0.8mm even when it is available on the market.
mixing of other refrigerants, the diameter of each port has been changed. It is recommended the gauge with seals-0.1 to 5.3 MPa (-1 to 53 bar) for high pressure.
-0.1 to 3.8 MPa (-1 to 38 bar) for low pressure. To increase pressure resistance, the hose material and base size were changed. A conventional vacuum pump can be used by installing a vacuum pump adapter. Special gas leakage detector for HFC refrigerant R410A.
Contents of change
Table 1 Thicknesses of Annealed Copper Pipes
Nominal diameter
1/4
1/2
Outer diameter
(mm)
6.35
12.7
Thickness (mm)
R410A
0.80
0.80
[ref.] R22
0.80
0.80
Name and Shape Q’ty Name and Shape Q’ty
Wall hook bracket
Remote control unit
Cloth tape
1
Tapping screw (big)
1
8
1
Tapping screw (small)
2
Battery
Air cleaning filter
2
2
Remote control unit holder
Air cleaning filter frame
Name
Connection pipe assembly
Connection cord
Wall pipe
Decorative tape
Vinyl tape
Wall cap
Saddle
Drain hose
Tapping screws
Sealant
ELECTRICAL REQUIREMENT
Always make the air conditioner power supply a special branch circuit and provide a special switch and receptacle. Do not extend the power cord.
WARNING
(1) Do not use the existing (for R22) piping and flare nuts.
• If the existing materials are used, the pressure inside the refrigerant cycle will rise and cause breakage, injury, etc.(Use the special R410A materials.)
(2) When installing and relocating the air conditioner, do not mix gases other than the specified refrigerant(R410A)
to enter the refrigerant cycle.
• If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value and cause breakage, injury, etc.
SELECTING THE MOUNTING POSITION
Decide the mounting position with the customer as follows:
1. INDOOR UNIT
(1) Install the indoor unit level on a strong wall which is not subject to
vibration.
(2) The inlet and outlet ports should not be obstructed : the air should
be able to blow all over the room. (3) Install the unit near an electric outlet or special branch circuit. (4) Do not install the unit where it will be exposed to direct sunlight. (5) Install the unit where connection to the outdoor unit is easy. (6) Install the unit where the drain pipe can be easily installed. (7) Take servicing, etc. into consideration and leave the spaces shown
in (Fig. 2). Also install the unit where the filter can be removed.
INSTALLATION DIAGRAM OF INDOOR AND OUTDOOR UNITS
Fig. 2
[INDOOR UNIT]
Wall hook bracket
5 cm or over
6 cm or over
9 cm or over
2. OUTDOOR UNIT
(1) If possible, do not install the unit where it will be exposed to direct
sunlight. (If necessary, install a blind that does not interfere with
the air flow.) (2) Do not install the unit where a strong wind blows or where it is very
dusty. (3) Do not install the unit where people pass. (4) Take you neighbors into consideration so that they are not disturbed
by air blowing into their windows or by noise. (5) Provide the space shown in Fig. 2 so that the air flow is not blocked.
Also for efficient operation, leave open three of the four directions
front, rear, and both sides.
WARNING
Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not topple or fall.
[OUTDOOR UNIT]
150 cm or over
230 cm or over
Remote
control unit
Connection Cord
Conform to Type245 IEC57
60 cm or over
(Wall cap)
Remote
control unit
holder
Tapping
screw
(small)
10 cm or over
CAUTION
(1) Do not install where there is the danger of com-
bustible gas leakage. (2) Do not install near heat sources. (3) If children under 10 years old may approach the
unit, take preventive measures so that they can-
not reach the unit. (4) Install the indoor unit on the wall where the height
from the floors more than 230 cm.
10 cm or over
30 cm or over
30 cm or over
[Indoor unit piping direction]
The piping can be connected in the five directions indicated by 1, 2, 3, 4, and 5 in (Fig. 1). When the piping is connected in
direction 2 or 5, cut along the piping groove in the side of the front cover with a hacksaw. When connecting the piping in direction 3, cut a notch in the thin wall at the front bottom of the front cover.
Fig. 1
(Rear)
2 Right
outlet
3 Bottom outlet
1 Rear outlet
4 Left rear
outlet
5 Left
outlet
Fig. 3
Drain hose
54 cm
Outdoor unit bottom
32 cm
1
2
Drain pipe
Seal A
1
1
FRONT PANEL REMOVAL AND INSTALLATION
THE INTAKE GRILLE REMOVAL
(1) Open the intake grille. (2) Pull down the knob. (3) Lift the intake grille upward, until the axle at the top of the in-
take grille is removed.
THE INTAKE GRILLE INSTALLATION
(1) The fixing axle of the intake grille is installed on the Panel. (2) Lay down the intake grille.
THE FRONT PANEL REMOVAL
(1) Remove intake grille (Reference the intake grille removal.) (2) Remove four screws. (3) The thumb is hung on the lower part as shown in the figure,
and it pulls to the front, pushing [-] mark , and bottom hooks (two position) is removed from wall hook bracket.
(4) The front panel bottom is pulled to the front, and bottom hooks
is removed indoor unit.
(5) The front panel is pulled to the front, raising the upper surface,
and a front panel is removed.
THE FRONT PANEL INSTALLATION
(1) Firstly, fit the lower part of the front panel, and insert top and
bottom hooks. (Three top sides, six bottom sides) (2) Four screws is attached. (3) The intake grille is attached.
Indoor unit
Bottom hole
(six position)
CAUTION
Install the front panel and INTAKE GRILLE securely. If installation is imperfect, the front panel or INTAKE GRILLE may fall off and cause injury.
Be sure that the top hole of the front panel is hooked securely to the hook of the base.
CUSTOMER GUIDANCE
Explain the following to the customer in ac­cordance with the operating manual: (1) Starting and stopping method, opera-
tion switching, temperature adjustment, timer, air flow switching, and other re­mote control unit operations.
(2) Air filter removal and cleaning, and how
to use the air louvers.
(3) Give the operating and installation
manuals to the customer.
Bottom hooks
(six position)
Front panel
TEST RUNNING
Perform test operation and check items 1 and 2 below.
For the test operation method, refer to the operating manual.
The outdoor unit, may not operate, depending on the room temperature. In this case, press
the test run button on the remote control unit while the air conditioner is running, (Point the transmitter section of the remote control unit toward the air conditioner and press the test run button with the tip of a ball-point pen, etc.)
To end test operation, press the remote control unit START/STOP button. (When the air conditioner is run by pressing the test run button, the OPERATION indicator lamp and TIMER indicator lamp will simultaneously flash slowly.)
1. INDOOR UNIT
(1) Is operation of each button on the remote control unit normal? (2) Does each lamp light normally? (3) Do the air flow-direction louver operate normally? (4) Is the drain normal?
2. OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation? (2) Will noise, wind, or drain water from the unit disturb the
neighbors?
(3) Is there any gas leakage?
POWER
WARNING
(1) The rated voltage of this product is 230 V AC 50 Hz. (2) Before turning on the power, check if the voltage is within
the 220 V -10 % to 240 V +10 % range.
(3) Always use a special branch circuit and install a special
receptacle to supply power to the room air conditioner.
(4) Use a circuit breaker and receptacle matched to the ca-
pacity of the air conditioner. (5) Do not extend the power cord. (6) Perform wiring work in accordance with standards so that
the air conditioner can be operated safely and positively. (7) Install a leakage circuit breaker in accordance with the
related laws and regulations and electric company
standards.
(1) The power source capacity must be the sum of the air conditioner
(2) When the voltage is low and the air conditioner is difficult to start,
Fig. 4
Push
[-] mark
Top holes (two sides)
Top hole (center)
Indoor unit
Intake grille
Mounting shaft
Bearing
Front panel
Push
Wall hook bracket
Screws
(4 position)
Front panel
Top hook (center)
Top hooks
(two sides)
Transmitter section
Test run button
Intake grille
Knob
Front panel
Front panel
Fig. 5
CAUTION
current and the current of other electrical appliances. When the current contracted capacity is insufficient, change the contracted capacity.
contact the power company the voltage raised.
Installation instruction on the back.
LO
HI
INDOOR UNIT
CUTTING THE HOLE IN THE WALL FOR THE CONNECTING PIPING
(1) Cut a 65 mm diameter hole in the wall at the position shown in (Fig.
6).
(2) When cutting the wall hole at the inside of the installation frame, cut
the hole within the range of the left and right center marks 40 mm below the installation frame. When cutting the wall hole at the outside of the installation frame, cut the hole at least 10 mm below over.
(3) Cut the hole so that the outside end is lower (5 to 10 mm) than the
inside end.
(4) Always align the center of the wall hole. If misaligned, water leakage
will occur.
(5) Cut the wall pipe to match the wall thickness, stick it into the wall cap,
fasten the cap with vinyl tape, and stick the pipe through the hole. (The connection pipe is supplied in the installation set.) (Fig. 6)
(6) For left piping and right piping, cut the hole a little lower so that drain
water will flow freely. (Fig. 6)
INSTALLING THE WALL HOOK BRACKET
(1) Install the wall hook bracket so that it is correctly positioned horizon-
tally and vertically. If the wall hook bracket is tiled, water will drip to the floor.
(2) Install the wall hook bracket so that it is strong enough to withstand
the weight of an adult.
Fasten the wall hook bracket to the wall with 6 or more screws through
the holes near the outer edge of the bracket.
Check that there is no rattle at the wall hook bracket.
WARNING
If the wall pipe is not used, the cord interconnecting the indoor and outdoor units may touch metal and cause electric leakage.
CAUTION
Install the wall hook bracket horizontally and perpendicularly.
FORMING THE DRAIN HOSE AND PIPE
[Rear piping, Right piping, Bottom piping]
Install the indoor unit piping in the direction of the wall hole and bind
the drain hose and pipe together with vinyl tape. (Fig. 8)
Install the piping so that the drain hose is at the bottom.
Wrap the pipes of the indoor unit that are visible from the outside
with decorative tape.
[For Left rear piping, Left piping]
Interchange the drain cap and the drain hose.
CAUTION
After removing the drain hose, do not forget to install the drain cap.
Indoor unit drain hose
Drain cap
Insert the drain cap and drain hose until it butts against the drain port.
Fig. 6
Fasten with vinyl tape
(Wall cap)
Fig. 7
Wall hook bracket
Fig. 8
Right piping
Lower
65 mm dia. hole
(Wall pipe)
(Inside)
Tapping screw
Bottom
piping
Indoor unit drain hose
Wall (Outside)
Center mark
5 to 10 mm low
65 mm dia. hole
Center notch
Wall hook bracket
Bind with vinyl tape
Pipe (top) Rear piping
Indoor unit drain hose (bottom)
For left outlet piping, cut off the piping outlet cutting groove with a hacksaw.
Drain cap
Lower
10 mm or over
Hook
String
Remove the drain cap by pulling at the projection at the end of the cap with pliers, etc.
For left piping and left rear piping, align the marks on the wall hook
bracket and shape the connection pipe.
Bend the connection piping at the bend radius of 70 mm or more and
install no more than 35 mm from the wall.
After passing the indoor piping and drain hose through the wall hole,
hang the indoor unit on the hooks at the top and bottom of the wall hook bracket.
[Installing the indoor unit]
Hang the indoor unit from the hooks at the top of the wall hook bracket.
Insert the spacer, etc. between the indoor unit and the wall hook
bracket and separate the bottom of the indoor unit from the wall.
Indoor unit
(Spacer)
Wall hook bracket
CONNECTING THE PIPING
CONNECTION
(1) Install the outdoor unit wall cap (supplied with the optional installation set
or procured at the site) to the wall pipe. (2) Connect the outdoor unit and indoor unit piping. (3) After matching the center of the flare surface and tightening the nut hand
tight, tighten the nut to the specified tightening torque with a torque wrench.
(Table 2)
FLARING
(1) Cut the connection pipe to the necessary
length with a pipe cutter. (2) Hold the pipe downward so that cuttings
will not enter the pipe and remove the
burrs. (3) Insert the flare nut onto the pipe and flare
the pipe with a flaring tool.
Insert the flare nut (always use the flare nut attached to the indoor and outdoor units respectively) onto the pipe and perform the flare processing with a flare tool. Use the special R410A flare tool, or the conv­entional (for R22) flare tool. When using the conventional flare tool, always use an allowance adjustment gauge and secure the A dimension shown in table 3 .
Check if [L] is flared uniformly and is not cracked or scratched.
Die
A
Pipe
INDOOR UNIT WIRING
(1) Remove the cord clamp. (2) Bend the end of the connection cord as shown in the figure.
Fig. 11
Right bottom of indoor unit
Cord clamp
(There is a
terminal block
inside.)
Screw
(1) Match the terminal block numbers and connection
cord colors with those of the outdoor unit. Erroneous wiring may cause burning of the elec­tric parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
Connection cord
Connection cord
CAUTION
Fig. 9
Connection pipe (6.35 mm dia.)
Bend (R70) with a pipe bender
Connection pipe (12.7 mm dia.)
Indoor unit
After hooking the indoor unit to the top hook, hook the fittings of the indoor unit to the two bottom hooks while lowering the unit and pushing it against the wall.
Fig. 10
Indoor unit pipe
(Fitting)
Tighten with two wrenches.
Wrench (fixed)
Torque wrench
Flare nut
Connection pipe
Align the marks.
Top hooks
Wall hook
Bottom hooks
To prevent gas leakage, coat the flare surface with refrigerator oil.
bracket
Table 2 Flare nut tightening torque
Flare nut
6.35 mm dia.
12.7 mm dia.
Tightening torque
15.7 to 17.6 N•m
(160 to 180 kgf•cm)
49.0 to 53.9 N•m
(500 to 550 kgf•cm)
Tightening torque standard
(using a 20 cm wrench)
Wrist strength
Arm strength
Table 3 Pipe outside diameter
Pipe outside
diameter
ø 6.35 mm (1/4”) ø 12.7 mm (3/8”)
Flash tool for
R410A, clutch type
0 to 0.5 0 to 0.5
A (mm)
Conventional (R22) flare tool
Clutch type
1.0 to 1.5
1.0 to 1.5
Wing nut type
1.5 to 2.0
1.5 to 2.0
(3) Connect the end of the connection cord fully into the terminal block. (4) Fasten the connection cord with a cord clamp.
Cord clamp
5 mm
12 mm
50 mm
5 mm
12 mm
40 mm
Ta b
Square hole
Screw
Insert the tab into the square hole of the indoor unit and fasten with a screw.
(3) Always fasten the outside covering of the connec-
tion cord with the cord clamp. (If the insulator is
chafed, electric leakage may occur.) (4) Securely earth the power cord plug. (5) Do not use the earth screw for an external connector.
Only use for interconnection between two units.
OUTDOOR UNIT
OUTDOOR UNIT INSTALLATION
Set the unit on a strong stand, such as one made of concrete blocks
to minimize shock and vibration.
Do not set the unit directly on the ground because it will cause trou-
ble.
Connector cover removal
Remove the tapping screws.
Installing the connector cover
(1) After inserting the two front hooks, then insert the rear hook. (2) Tighten the tapping screws.
AIR PURGE
Always use a vacuum pump to purge the air. Refrigerant for purging the air is not charged in the outdoor unit at the factory.
Close the high pressure side valve of the gauge manifold fully and do not operate it during the following work.
WARNING
(1) Install the unit where it will not be tilted by more
than 5°.
(2) When installing the outdoor unit where it may ex-
posed to strong wind, fasten it securely.
Fig. 12
Tapping screw
Front hooks
Rear hooks
Connector cover
CAUTION
(1) Refrigerant must not be discharged into
atmosphere.
(2) After connecting the piping , check the joints for
gas leakage with gas leak detector.
Additional charge
Refrigerant suitable for a piping length of 15 m is charged in the outdoor unit at the factory. When the piping is longer than 15 m, additional charging is necessary. For the additional amount, see the table below.
Table 5
Pipe length
Additional refrigerant
15 m
None
20 m
100 g
OUTDOOR UNIT WIRING
(1) Remove the outdoor unit connector cover. (2) Bend the end of the cord as shown in the figure. (3) Connect the end of the connection cord fully into the terminal block. (4) Fasten the sheath with a cord clamp. (5) Install the connector cover.
Fig. 14
Control box
Cord clamp
Connector cord
CAUTION
(1)
When adding refrigerant, add the refrigerant from the charging port at the completion of work.
(2) The maximum length of the piping is 20 m. If
the units are further apart than this, correct operation can not be guaranteed.
Between 15 m and 20 m, when using a connection pipe other than that in the table, charge additional refrigerant with 20g/1 m as the criteria.
5mm
30mm
12mm
Earth screw
Earth screw
Cord clamp
Earth screw
Fig. 15
Sheath
Connection cord
12mm
25mm
Outdoor unit terminal blockIndoor unit terminal block
5mm
1. Check if the piping connections are secure.
2. Check that the stems of 2-way valve and 3-way valve are closed fully.
3. Connect the gauge manifold charge hose to the charging port of the 3-way valve (side with the projection for pushing in the valve core).
4. Open the low pressure side valve of the gauge manifold fully.
5. Operate the vacuum pump and start pump down.
6. Slowly loosen the flare nut of the 3-way valve and check if air enters, then retighten the flare nut. (When the flare nut is loosened the operating sound of the vacuum pump changes and the reading of the compound pressure gauge goes from minus to zero.)
7. Pump down the system for at least 15 minutes, then check if the compound pressure gauge reads -0.1 MPa (-76 cmHg, -1 bar).
8. At the end of pump down, close the low pressure side gauge of the gauge manifold fully and stop the vacuum pump.
9. Slowly loosen the valve stem of the 3-way valve. When the compound pressure gauge reading reaches 0.1-0.2 MPa, retighten the valve stem and disconnect the charge hose from the 3-way valve charging port. (If the stem of the 3-way valve is opened fully before the charge hose is disconnected, it may be difficult to disconnect the charge hose.)
10. Fully open the valve stems of the 2-way valve and 3-way valve using a hexagon wrench. (After the valve stem begins to turn, turn it with a torque of less than 2.9 N•m (30 kgf•cm) until it stops turning.)
11. Firmly tighten the 2-way valve and 3-way valve blank cap and the charging port cap.
Fig. 13
Gauge manifold
-0.1 MPa (-76 cmHg
-1 bar)
Low pressure side valve
Charge hose
Pressure gauge
High pressure side valve (closed)
Charge hose
Vacuum pump
3-way valve
Charging port cap
Compound pressure gauge
2-way valve
Flare nut
Valve stem
Blank cap
Charging port
Table 4
Tightening torque
Blank cap (2-way valve) 19.6 to 24.5 N•m (200 to 250 kgf•cm)
Blank cap (3-way valve) 27.4 to 31.4 N•m (280 to 320 kgf•cm)
Charging port cap 12.3 to 15.7 N•m (125 to 160 kgf•cm)
Connection cord wiring
Run the connection cord to the rear of the outdoor unit within the A range of the arrows shown in the figure. (The connector cover becomes difficult to install.)
CAUTION
(1) Match the terminal block numbers and connection
cord colors with those of the indoor unit. Erroneous wiring may cause burning of the electric parts.
(2) Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
(3) Always fasten the outside covering of the connec-
(4) Securely earth the power cord plug. (5) Do not use the earth screw for an external connector.
FINISHING
(1) Insulate between pipes.
For rear, right, and bottom piping, overlap the connection pipe heat insulation and indoor unit pipe heat insulation and bind them with vinyl tape so that there is no gap.
For left and left rear piping, butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with and vinyl tape so that there is no gap.
For left and left rear piping, wrap the area which accommodates the rear piping housing section with cloth tape.
For left and left rear piping, bind the connection cord to the top of the pipe with vinyl tape.
For left and left rear piping, bundle the piping and drain hose together by wrapping them with cloth tape over the range within which they fit into the rear piping housing section.
(2) Temporarily fasten the connection cord along the connection pipe with vinyl tape. (Wrap
to about 1/3 the width of the tape from the bottom of the pipe so that water does not enter.)
(3) Fasten the connection pipe to the outside wall with saddles, etc. (4) Fill the gap between the outside wall pipe hole and the pipe with sealer so that rain
water and wind cannot blow in.
(5) Fasten the drain hose to the outside wall, etc.
Wall
(Outside wall cap)
(Sealer putty)
(Outdoors)
Fig. 16
(Saddle)
Pipe
Connector cord
tion cord with the cord clamp. (If the insulator is chafed, electric leakage may occur.)
Only use for interconnection between two units.
Fig. 17
Connection pipe (heat insulation)
Bind the pipes together so that there is no gap.
Left piping
Connection cord
Pipe
Check the following:
GOOD
Drain hose
Overlap the insulation
Pipe
Drain hose
Drain hose
Saddle
Indoor unit pipe (heat insullation)
Vinyl tape
Wrap with cloth tape
Cloth tape
For connection from the left rear
Wall pipe
Drain hose
BAD
Lifted up
Connection cord
Connection pipe
BAD BAD
Wave End in water
P/N 9313802028-01
Loading...