Note: CETL or CUL certification only applies to unbundled units and units packaged
with limited circuit switches. Units packaged with the Smart Switch are ETL or UL
certified in the USA only.
INNOVATIVE ENGINE DESIGN & RIGOROUS TESTING are at the heart of Gen-
erac’s success in providing the most reliable generators possible. Generac’s GForce engine lineup offers added peace of mind and reliability for when it’s needed
the most. The G-Force series engines are purpose built and designed to handle the
rigors of extended run times in high temperatures and extreme operating conditions.
TRUE POWER™ ELECTRICAL TECHNOLOGY: Superior harmonics and sine wave
form produce less than 5% Total Harmonic Distortion for utility quality power. This
allows confident operation of sensitive electronic equipment and micro-chip based
appliances, such as variable speed HVAC systems.
TEST CRITERIA:
N
PROTOTYPE TESTED
SYSTEM TORSIONAL TESTED
®
MOBILE LINK
generators, Mobile Link Wi-Fi allows users to monitor generator status from anywhere in the world using a smartphone, tablet, or PC. Easily access information such
as the current operating status and maintenance alerts. Users can connect an
account to an authorized service dealer for fast, friendly, and proactive service. With
Mobile Link, users are taken care of before the next power outage.
CONNECTIVITY: FREE with select Guardian Series Home standby
EMA MG1-22 EVALUATION
MOTOR STARTING ABILITY
SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION: This
state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge
loads to the engine. Digital voltage regulation at ±1%.
SINGLE SOURCE SERVICE RESPONSEfrom Generac’s extensive dealer network
provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.
GENERAC TRANSFER SWITCHES:Long life and reliability are synonymous with
GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC
product line is offered with its own transfer systems and controls for total system
compatibility.
PWRVIEW™ TRANSFER SWITCH: The Generac PWRview Automatic Transfer
Switch integrates the PWRview energy monitor to provide real-time energy consumption data that can help lower a home’s electricity bill. Using a convenient
mobile app, homeowners can access energy usage and alert information while under
utility power or generator power. The PWRview energy monitor is a simple to use and
low cost tool which helps save money over the life of the generator. Included with
model G007210-0.
®
20/22/24 kWFeatures and Benefits
Engine
20/22/24 kW
2 of 6
Generator
Transfer Switch (if applicable)
Generac G-Force designMaximizes engine “breathing” for increased fuel efficiency. Plateau honed cylinder walls and plasma moly
rings help the engine run cooler, reducing oil consumption and resulting in longer engine life.
“Spiny-lok” cast iron cylinder wallsRigid construction and added durability provide long engine life.
Electronic ignition/spark advance These features combine to assure smooth, quick starting every time.
Full pressure lubrication systemPressurized lubrication to all vital bearings means better performance, less maintenance, and longer engine
life. Now featuring up to a 2 year/200 hour oil change interval.
Low oil pressure shutdown systemShutdown protection prevents catastrophic engine damage due to low oil.
High temperature shutdownPrevents damage due to overheating.
Revolving fieldAllows for a smaller, light weight unit that operates 25% more efficiently than a revolving armature generator.
Skewed statorProduces a smooth output waveform for compatibility with electronic equipment.
Displaced phase excitationMaximizes motor starting capability.
Automatic voltage regulationRegulating output voltage to ±1% prevents damaging voltage spikes.
UL 2200 listedFor your safety.
Fully automaticTransfers vital electrical loads to the energized source of power.
NEMA 3RCan be installed inside or outside for maximum flexibility.
Integrated load management technologyCapability to manage additional loads for efficient power management.
Remote mountingMounts near an existing distribution panel for simple, low-cost installation.
PWRview Transfer Switch (if applicable)
PWRview energy monitorEnergy usage at-a-glance.
Ability to view real-time energy consumption dataBetter understand the home’s energy profile.
PWRview mobile appAccess daily energy intelligence and insights.
Evolution™ Controls
AUTO/MANUAL/OFF illuminated buttonsSelects the operating mode and provides easy, at-a-glance status indication in any condition.
Two-line multilingual LCDProvides homeowners easily visible logs of history, maintenance, and events up to 50 occurrences.
Sealed, raised buttonsSmooth, weather-resistant user interface for programming and operations.
Utility voltage sensingConstantly monitors utility voltage, setpoints 65% dropout, 80% pick-up, of standard voltage.
Generator voltage sensingConstantly monitors generator voltage to verify the cleanest power delivered to the home.
Utility interrupt delayPrevents nuisance start-ups of the engine, adjustable 2-1500 seconds from the factory default setting of 5
seconds by a qualified dealer.
Engine warm-upVerifies engine is ready to assume the load, setpoint approximately 5 seconds.
Engine cool-downAllows engine to cool prior to shutdown, setpoint approximately 1 minute.
Programmable exerciseOperates engine to prevent oil seal drying and damage between power outages by running the generator for
5 minutes every other week. Also offers a selectable setting for weekly or monthly operation providing
flexibility and potentially lower fuel costs to the owner.
Smart battery chargerDelivers charge to the battery only when needed at varying rates depending on outdoor air temperature.
Compatible with lead acid and AGM-style batteries.
Main line circuit breakerProtects generator from overload.
SAE weather protective enclosureSound attenuated enclosures ensure quiet operation and protection against mother nature, withstanding
winds up to 150 mph (241 km/h). Hinged key locking roof panel for security. Lift-out front for easy access
to all routine maintenance items. Electrostatically applied textured epoxy paint for added durability.
Enclosed critical grade mufflerQuiet, critical grade muffler is mounted inside the unit to prevent injuries.
Small, compact, attractiveMakes for an easy, eye appealing installation, as close as 18 in (457 mm) away from a structure.
Installation System
14 in (35.6 cm) flexible fuel line connectorListed ANSI Z21.75/CSA 6.27 outdoor appliance connector for the required connection to the gas supply
piping.
Integral sediment trapMeets IFGC and NFPA 54 installation requirements.
Connectivity (Wi-Fi equipped models only)
Ability to view generator statusMonitor generator with a smartphone, tablet, or computer at any time via the Mobile Link application for
complete peace of mind.
Ability to view generator Exercise/Run and Total HoursReview the generator's complete protection profile for exercise hours and total hours.
Ability to view generator maintenance informationProvides maintenance information for the specific model generator when scheduled maintenance is due.
Monthly report with previous month’s activityDetailed monthly reports provide historical generator information.
Ability to view generator battery informationBuilt in battery diagnostics displaying current state of the battery.
Weather informationProvides detailed local ambient weather conditions for generator location.
20/22/24 kW
3 of 6
®
20/22/24 kWSpecifications
Generator
ModelG007038-1
20/22/24 kW
Rated maximum continuous power capacity (LP)20,000 Watts*22,000 Watts* 20,000 Watts* 22,000 Watts* 24,000 Watts*
Rated maximum continuous power capacity (NG) 18,000 Watts* 19,500 Watts*18,000 Watts* 19,500 Watts*21,000 Watts*
Rated voltage240
4 of 6
Rated maximum continuous load current – 240 volts (LP/NG)83.3 / 75.091.7 / 81.383.3 / 75.091.7 / 81.3100 / 87.5
Total Harmonic DistortionLess than 5%
Main line circuit breaker90 amp100 amp90 amp100 amp100 amp
Phase1
Number of rotor poles2
Rated AC frequency60 Hz
Power factor1.0
Battery requirement (not included) 12 Volts, Group 26R 540 CCA minimum or Group 35AGM 650 CCA minimum
Unit weight (lb / kg)448 / 203466 / 211436 / 198445 / 202455 / 206
Dimensions (L x W x H) in / cm48 x 25 x 29 / 121.9 x 63.5 x 73.7
Sound output in dB(A) at 23 ft (7 m) with generator operating at normal load**6767676767
Sound output in dB(A) at 23 ft (7 m) with generator in Quiet-Test™ low-speed exercise mode**5557555757
Exercise duration5 min
Engine
Engine typeGENERAC G-Force 1000 Series
Number of cylinders2
Displacement999 cc
Cylinder blockAluminum w/ cast iron sleeve
Valve arrangementOverhead valve
Ignition systemSolid-state w/ magneto
Governor systemElectronic
Compression ratio9.5:1
Starter12 VDC
Oil capacity including filterApprox. 1.9 qt / 1.8 L
Operating rpm3,600
Fuel consumption
Natural gas ft³/hr (m³/hr)
1/2 Load
Full Load
Liquid propane ft
1/2 Load
Full Load
Note: Fuel pipe must be sized for full load. Required fuel pressure to generator fuel inlet at all load ranges - 3.5–7 in water column (0.87–1.74 kPa) for NG, 10–12 in water column (2.49–2.99 kPa) for LP
gas. For BTU content, multiply ft
Controls
Two-line plain text multilingual LCDSimple user interface for ease of operation.
Mode buttons: AUTOAutomatic start on utility failure. Weekly, Bi-weekly, or Monthly selectable exerciser.
MANUALStart with starter control, unit stays on. If utility fails, transfer to load takes place.
OFFStops unit. Power is removed. Control and charger still operate.
Ready to Run/Maintenance messagesStandard
Engine run hours indicationStandard
Programmable start delay between 2–1500 seconds Standard (programmable by dealer only)
Utility Voltage Loss/Return to Utility adjustable (brownout setting)From 140-171 V / 190-216 V
Future Set Capable Exerciser/Exercise Set Error warningStandard
Run/Alarm/Maintenance logs 50 events each
Engine start sequence Cyclic cranking: 16 sec on, 7 rest (90 sec maximum duration).
Starter lock-out Starter cannot re-engage until 5 sec after engine has stopped.
Smart Battery Charger Standard
Charger Fault/Missing AC warningStandard
Low Battery/Battery Problem Protection and Battery Condition indication Standard
Automatic Voltage Regulation with Over and Under Voltage Protection Standard
Under-Frequency/Overload/Stepper Overcurrent ProtectionStandard
Safety Fused/Fuse Problem ProtectionStandard
Automatic Low Oil Pressure/High Oil Temperature Shutdown Standard
Overcrank/Overspeed (@ 72 Hz)/rpm Sense Loss Shutdown Standard
High Engine Temperature Shutdown Standard
Internal Fault/Incorrect Wiring protection Standard
Common external fault capability Standard
Field upgradable firmwareStandard
**Sound levels are taken from the front of the generator. Sound levels taken from other sides of the generator may be higher depending on installation parameters. Rating definitions - Standby: Applicable for supplying
emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). * Maximum kilovolt amps and current are
subject to and limited by such factors as fuel BTU/megajoule content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases approximately 3.5% for each 1,000 ft (304.8 m) above sea
level; and also will decrease approximately 1% for each 10 °F (6 °C) above 60 °F (16 °C).
G007039-1
(20 kW)
204 (5.78)
3
/hr (gal/hr) [L/hr]
3
/hr x 2500 (LP) or ft3/hr x 1000 (NG). For Megajoule content, multiply m³/hr x 93.15 (LP) or m³/hr x 37.26 (NG).
301 (8.52)
87 (2.37) [8.99]
130 (3.56) [13.48]
G007042-2
G007043-2
(22 kW)
228 (6.46)
327 (9.26)
92 (2.53) [9.57]
142 (3.90) [14.77]
G007038-3
G007039-3
(20 kW)
164 (4.64)
287 (8.13)
86 (2.36) [8.95]
136 (3.74) [14.15]
G007042-3
G007043-3
(22 kW)
92 (2.53) [9.57]
142 (3.90) [14.77]
203 (5.75)
306 (8.66)
G007209-0
G007210-0
(24 kW)
®
H2
DEPTH
H1
W2
W1
20/22/24 kWSwitch Options
H2
DEPTH
H1
W2
W1
Service Rated Automatic Transfer Switch Features
Intelligently manages up to four air conditioner loads with no additional hardware.
Up to eight additional large (240 VAC) loads can be managed when used in conjunction
with Smart Management Modules (SMMs).
Electrically operated, mechanically-held contacts for fast, clean connections.
Rated for all classes of load, 100% equipment rated, both inductive and resistive.
2-pole, 250 VAC contactors.
Service equipment rated, dual coil design.
Rated for both aluminum and copper conductors.
Main contacts are silver plated or silver alloy to resist welding and sticking.
NEMA/UL 3R aluminum outdoor enclosure allows for indoor or outdoor mounting flexibility.
Dimensions
200 Amps 120/240, 1ø
Open Transition Service Rated
HeightWidth
H1H2W1W2
in26.8 30.110.513.56.9
cm67.95 76.43 26.6734.1817.5
Wire Ranges
Conductor LugNeutral LugGround Lug
250 MCM - #6350 MCM - #62/0 - #14
Depth
Model
No. of poles 2
Current rating (amps)200
Voltage rating (VAC)120/240, 1Ø
Utility voltage monitor (fixed)*
-Pick-up
-Dropout
Return to Utility*Approx. 13 sec
Exercises bi-weekly for 5 minutes*Standard
ETL or UL listedStandard
Enclosure typeNEMA/UL 3R
Circuit breaker protected22,000
Lug range250 MCM - #6
*Function of Evolution controller
Exercise can be set to weekly, bi-weekly, or monthly
Integrated PWRview monitor provides real-time energy usage data through PWRview app.
Intelligently manages up to four air conditioner loads with no additional hardware.
Up to eight additional large (240 VAC) loads can be managed when used in conjunction
with Smart Management Modules (SMMs).
Electrically operated, mechanically-held contacts for fast, clean connections.
Rated for all classes of load, 100% equipment rated, both inductive and resistive.
2-pole, 250 VAC contactors.
Service equipment rated, dual coil design.
Rated for both aluminum and copper conductors.
Main contacts are silver plated or silver alloy to resist welding and sticking.
NEMA 3R aluminum outdoor enclosure allows for indoor or outdoor mounting flexibility.
Heavy duty Generac Contactor is an ETL recognized device.
Dimensions
200 Amps 120/240, 1ø
Open Transition Service Rated
in26.8 30.110.513.56.9
cm67.95 76.43 26.6734.18 17.5
Wire Ranges
Conductor LugNeutral LugGround Lug
250 MCM - #6350 MCM - #62/0 - #14
HeightWidth
H1H2W1W2
Depth
Model
No. of poles 2
Current rating (amps)200
Voltage rating (VAC)120/240, 1Ø
Utility voltage monitor (fixed)*
-Pick-up
-Dropout
Return to Utility*Approx. 13 sec
Exercises bi-weekly for 5 minutes*Standard
ETL or UL listedStandard
Enclosure typeNEMA 3R
Circuit breaker protected22,000
Lug range250 MCM - #6
*Function of Evolution controller
Exercise can be set to weekly, bi-weekly, or monthly
G007210-0 (24 kW)
80%
65%
®
Dimensions & UPCs
648 mm
[25.5 in]
727.2 mm
[28.6 in]
637.6 mm
[25.1 in]
1232 mm
[48.5 in
]
1218 mm
[48.0 in]
LEFT SIDE VIEWFRONT VIEW
®
20/22/24 kWAvailable Accessories
Model #ProductDescription
20/22/24 kW
G005819-026R Wet Cell BatteryEvery standby generator requires a battery to start the system. Generac offers the recommended 26R wet cell battery for
G007101-0Battery Pad WarmerPad warmer rests under the battery. Recommended for use if temperature regularly falls below 0 °F (-18 °C). (Not nec-
6 of 6
G007102-0Oil WarmerOil warmer slips directly over the oil filter. Recommended for use if temperature regularly falls below 0 °F (-18 °C).
G007103-1Breather Warmer Breather warmer is for use in extreme cold weather applications. For use with Evolution controllers only in climates where
G005621-0Auxiliary Transfer Switch
G007027-0 - Bisque Fascia Base Wrap Kit
G005703-0 - Bisque Touch-Up Paint KitIf the generator enclosure is scratched or damaged, it is important to touch up the paint to protect from future corrosion.
G006485-0Scheduled Maintenance Kit Generac's scheduled maintenance kit provides all the items necessary to perform complete routine maintenance on a
G007005-0Wi-Fi LP Tank Fuel Level
G007000-0 (50 amp)
G007006-0
(100 amp)
G007169-0 - 4G LTE
G007170-0 - Wi-Fi/
Ethernet
G007220-0 - Bisque Base Plug KitBase plugs snap into the lifting holes on the base of air-cooled home standby generators. This offers a sleek, contoured
use with all air-cooled standby product (excluding PowerPact
®
).
essary for use with AGM-style batteries).
heavy icing occurs.
The auxiliary transfer switch contact kit allows the transfer switch to lock out a single large electrical load that may not be
Contact Kit
needed. Not compatible with 50 amp pre-wired switches.
The fascia base wrap snaps together around the bottom of the new air-cooled generators. This offers a sleek, contoured
(Standard on 22/24 kW)
appearance as well as offering protection from rodents and insects by covering the lifting holes located in the base.
The touch-up paint kit includes the necessary paint to correctly maintain or touch up a generator enclosure.
Generac automatic standby generator (oil not included).
The Wi-Fi enabled LP tank fuel level monitor provides constant monitoring of the connected LP fuel tank. Monitoring the
Monitor
LP tank's fuel level is an important step in verifying the generator is ready to run during an unexpected power failure. Status alerts are available through a free application to notify users when the LP tank is in need of a refill.
Smart Management Module Smart Management Modules (SMM) are used to optimize the performance of a standby generator. It manages large elec-
trical loads upon startup and sheds them to aid in recovery when overloaded. In many cases, using SMM’s can reduce
the overall size and cost of the system.
Mobile Link® Cellular
Accessories
The Mobile Link family of Cellular Accessories allow users to monitor generator status from anywhere in the world, using
a smart phone, tablet, or PC. Easily access information such as the current operating status and maintenance alerts. Users can connect an account with an authorized service dealer for fast, friendly, and proactive service. With Mobile Link,
users are taken care of before the next power outage.
appearance, as well as offers protection from rodents and insects by covering the lifting holes located in the base. Kit
contains four plugs, sufficient for use on a single air-cooled home standby generator.
ModelUPC
G007038-1696471074185
G007038-3696471074185
G007039-1696471074192
G007039-3696471074192
G007042-2696471074208
G007042-3696471074208
G007043-2696471074215
G007043-3696471074215
G007209-0696471071511
G007210-0696471078220
Dimensions shown are approximate. See installation manual for exact dimensions. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com