Generac 5789 User Manual

Owner's Manual

GP Series Portable Generator
www.generac.com or 1-888-436-3722
DEADLY EXHAUST FUMES! ONLY use OUTSIDE
far away from windows, doors and vents! NOT INTENDED FOR USE IN CRITICAL LIFE
SUPPORT APPLICATIONS. SAVE this Manual. Provide this manual to any
operator of the generator.

Table of Contents

Introduction ............................................................. 1
Read this Manual Thoroughly .................................1
Safety Rules ........................................................... 1
Standards Index .............................................................3
General Information ................................................ 4
1.1 Unpacking ......................................................................4
1.1.1 Accessory Box....................................................4
1.2 Assembly .......................................................................4
1.2.1 Assembling the Accessory Kit .............................4
Operation ................................................................ 4
2.1 Know the Generator .......................................................4
2.2 Cord Sets and Connection Plugs ....................................6
2.2.1 120 VAC, 20 Amp, Duplex Receptacle .................6
2.3 How to Use the Generator ..............................................6
2.3.1 Grounding the Generator .....................................6
2.3.2 Conntecting the Generator to a Building's
Electrical System ................................................6
2.3.3 Connecting Electrical Loads ................................6
2.4 Don’t Overload the Generator ..........................................7
2.5 Wattage Reference Guide ...............................................7
2.6 Before Starting the Generator .........................................7
2.6.1 Adding Engine Oil ................................................7
2.6.2 Adding Gasoline ..................................................8
2.7 To Start the Engine .........................................................8
2.8 Stopping the Engine .......................................................9
2.9 Low Oil Level Shutdown System ....................................9
2.9.1 Sensing Low Oil Level .........................................9
Maintenance ........................................................... 9
3.1 Maintenance Schedule ...................................................9
3.2 Product Specifications ....................................................9
3.2.1 Generator Specifications .....................................9
3.2.2 Engine Specifications ..........................................9
3.3 General Recommendations ...........................................10
3.3.1 Generator Maintenance .....................................10
3.3.2 To Clean the Generator ......................................10
3.3.3 Engine Maintenance ..........................................10
3.3.4 Checking Oil Level.............................................10
3.3.5 Changing the Oil................................................10
3.3.6 Replacing the Spark Plug ..................................11
3.3.7 Spark Arrestor...................................................11
3.4 Service Air Filter ...........................................................11
3.5 Valve Clearance ............................................................11
3.6 General ........................................................................11
3.7 Long Term Storage .......................................................12
3.8 Other Storage Tips .......................................................12
Troubleshooting .................................................... 13
4.1 Troubleshooting Guide ..................................................13
WARNING!
California Proposition 65
Engine exhaust and some of its constituents are known to the state of California to cause cancer,
birth defects, and other reproductive harm.
WARNING!
California Proposition 65
This product contains or emits chemicals known to the state of California to cause cancer,
birth defects, and other reproductive harm.

Introduction

INTRODUCTION
Thank you for purchasing this model by Generac Power Systems, Inc. This model is a compact, high performance, air-cooled, engine driven generator designed to supply electrical power to operate electrical loads where no utility power is available or in place of utility due to a power outage.

READ THIS MANUAL THOROUGHLY

If any portion of this manual is not understood, contact the nearest Authorized Dealer for starting, operating and servicing procedures.
The operator is responsible for proper and safe use of the equipment. We strongly recommend that the operator read this manual and thoroughly understand all instructions before using the equipment. We also strongly recommend instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
The generator can operate safely, efficiently and reliably only if it is properly located, operated and maintained. Before operating or servicing the generator:
• Become familiar with and strictly adhere to all local, state and
national codes and regulations.
• Study all safety warnings in this manual and on the product
carefully.
• Become familiar with this manual and the unit before use.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all inclusive. If using a procedure, work method or operating technique that the manufacturer does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique utilized does not render the generator unsafe.
THE INFORMATION CONTAINED HEREIN WAS BASED ON MACHINES IN PRODUCTION AT THE TIME OF PUBLICATION. GENERAC RESERVES THE RIGHT TO MODIFY THIS MANUAL AT ANY TIME.
For any Frequently Asked Questions (FAQs) for your product, please go to: http://www.generac.com/service-support/faqs.

SAFETY RULES

Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
INDICATES A HAZARDOUS SITUATION OR ACTION WHICH, IF NOT AVOIDED, WILL RESULT IN DEATH OR SERIOUS INJURY.
Indicates a hazardous situation or action which, if not avoided, could result in death or serious injury.
Indicates a hazardous situation or action which, if not avoided, could result in minor or moderate injury.
NOTE:
Notes contain additional information important to a procedure and will be found within the regular text body of this manual.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compliance with the special instructions while performing the action or service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as follows:
This symbol points out important safety

information that, if not followed, could endanger personal safety and/or property of others.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical

shock hazard.
1
Safety Rules

GENERAL HAZARDS

• NEVER operate in an enclosed area, in a vehicle, or indoors EVEN
IF doors and windows are open.
• For safety reasons, the manufacturer recommends that the
maintenance of this equipment is carried out by an Authorized Dealer. Inspect the generator regularly, and contact the nearest Authorized Dealer for parts needing repair or replacement.
• Operate generator only on level surfaces and where it will not be
exposed to excessive moisture, dirt, dust or corrosive vapors.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and
other moving parts. Never remove any fan guard or shield while the unit is operating.
• Certain parts of the generator get extremely hot during operation.
Keep clear of the generator until it has cooled to avoid severe burns.
• Do NOT operate generator in the rain.
• Do not alter the construction of the generator or change controls
which might create an unsafe operating condition.
• Never start or stop the unit with electrical loads connected to
receptacles AND with connected devices turned ON. Start the engine and let it stabilize before connecting electrical loads. Disconnect all electrical loads before shutting down the generator.
• Do not insert objects through unit’s cooling slots.
• When working on this equipment, remain alert at all times. Never
work on the equipment when physically or mentally fatigued.
• Never use the generator or any of its parts as a step. Stepping on
the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
NOTE:
This generator is equipped with a spark arrestor muffler. The spark arrestor must be maintained in effective working order by the owner/ operator. In the State of California, a spark arrestor is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands.
2

EXHAUST & LOCATION HAZARDS

• Never operate in an enclosed area or indoors! NEVER use in the home, in a vehicle, or in partly enclosed areas such as garages, EVEN IF doors and windows are open! ONLY use outdoors and far from open windows, doors, vents, and in an area that will not accumulate deadly exhaust.
• The engine exhaust fumes contain carbon monoxide, which you cannot see or smell. This poisonous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death.
• Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The generator MUST be operated outdoors.
• This exhaust system must be properly maintained. Do nothing that might render the exhaust system unsafe or in noncompliance with any local codes and/or standards.
• Always use a battery operated carbon monoxide alarm indoors,installed according to the manufacturer's instructions.
• If you start to feel sick, dizzy, or weak after the generator has been running, move to fresh air IMMEDIATELY. See a doctor, as you could have carbon monoxide poisoning.

ELECTRICAL HAZARDS

• The generator produces dangerously high voltage when in operation. Avoid contact with bare wires, terminals, connections, etc., while the unit is running, even on equipment connected to the generator. Ensure all appropriate covers, guards and barriers are in place before operating the generator.
• Never handle any kind of electrical cord or device while standing in water, while barefoot or while hands or feet are wet. DANGEROUS
ELECTRICAL SHOCK MAY RESULT.
• The National Electric Code (NEC) requires the frame and external electrically conductive parts of the generator be properly connected to an approved earth ground. Local electrical codes may also require proper grounding of the generator. Consult with a local electrician for grounding requirements in the area.
• Use a ground fault circuit interrupter in any damp or highly conductive area (such as metal decking or steel work).
Safety Rules
• Do not use worn, bare, frayed or otherwise damaged electrical cord sets with the generator.
• Before performing any maintenance on the generator, disconnect the engine starting battery (if equipped) to prevent accidental start up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a non-conducting implement, such as a rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.

FIRE HAZARDS

• Gasoline is highly FLAMMABLE and its vapors are EXPLOSIVE. Do not permit smoking, open flames, sparks or heat in the vicinity while handling gasoline.
• Never add fuel while unit is running or hot. Allow engine to cool completely before adding fuel.
• Never fill fuel tank indoors. Comply with all laws regulating storage and handling of gasoline.
• Do not overfill the fuel tank. Always allow room for fuel expansion. If tank is over-filled, fuel can overflow onto a hot
engine and cause FIRE or an EXPLOSION. Never store generator with fuel in tank where gasoline vapors might reach an open flame, spark or pilot light (as on a furnace, water heater or clothes dryer). FIRE or EXPLOSION may result. Allow unit to cool entirely before storage.
• Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left on or near the generator. Keep the area surrounding the generator clean and free from debris and keep a clearance of five (5) feet on all side to allow for proper ventilation of the generator.
• Do not insert objects through unit’s cooling slots.
• Do not operate the generator if connected electrical devices overheat, if electrical output is lost, if engine or generator sparks or if flames or smoke are observed while unit is running.
• Keep a fire extinguisher near the generator at all times.

STANDARDS INDEX

1. National Fire Protection Association (NFPA) 70: The NATIONAL ELECTRIC CODE (NEC) available from www.nfpa.org
2. National Fire Protection Association (NFPA) 5000: BUILDING CONSTRUCTION AND SAFETY CODE available from www. nfpa.org
3. International Building Code available from www.iccsafe.org
4. Agricultural Wiring Handbook available from www.rerc.org, Rural Electricity Resource Council P.O. Box 309 Wilmington, OH 45177-0309
5. ASAE EP-364.2 Installation and Maintenance of Farm Standby Electric Power available from www.asabe.org, American Society of Agricultural & Biological Engineers 2950 Niles Road, St. Joseph, MI 49085
This list is not all inclusive. Check with the Authority Having Local Jurisdiction (AHJ) for any local codes or standards which may be applicable to your jurisdiction.
MODEL NO:
SERIAL NO:
Unit ID Location
3

General Information

1.1 UNPACKING

• Remove all packaging material.
• Remove separate accessory box.
• Remove the generator from carton.
1.1.1 ACCESSORY BOX
Check all contents. If any parts are missing or damaged, locate an authorized dealer at 1-888-436-3722.
• 1 - Owner’s Manual
• 1- Oil SAE 30
• 2- 7” Wheels
• 1- Handle Assembly
• 1- Handle Bracket
• 1- Wheel Axle
• 1- Hardware Bag (containing the following):
2 - Rubber bumpers 7 - M6 Flange Nuts 2 - Bumper Brackets 2 - Cotter Pins 2 - M12 Flat Washers 2 - Hubs 5 - M6-1 x 40 Flange Bolts 2 - M6-1.0 x 16 Flange
Bolts

1.2 ASSEMBLY

The generator requires some assembly prior to using it. If problems arise when assembling the generator, please call the Generator Helpline at 1-888-436-3722.
Figure 1 – Wheel Assembly
Figure 2 – Handle Kit
1.2.1 ASSEMBLING THE ACCESSORY KIT
The wheels are designed to greatly improve the portability of the generator.
NOTE:
The wheels are not intended for over-the-road-use.
1. Refer to Figure 1 to install the wheels as shown.
• Slide the axle through the frame brackets.
• Slide on the hub, wheel and flat washer, then insert the cotter pin through the wheel axle hole.
• Bend the cotter pin tabs outward to lock the pin in place.
2. Refer to Figure 1 to install the rubber bumpers as shown.
• Insert an M6 bolt through the rubber bumper and the bottom of the bumper bracket. Secure the bolt with an M6 flange nut.
• Install an M6 bolt through the generator frame and through top of the bumper bracket. Secure the bolt with an M6 flange nut.
3. Refer to Figure 2 to install the handle assembly as shown.
• Insert the handle bracket onto the generator frame and secure with two M6 bolts and two M6 flange nuts.
• Align the handle assembly holes with the handle bracket holes and secure with one M6 bolt and one M6 flange nut.
To properly install the accessory kit, the following tools are needed:
• Pliers
• 8 mm Box Wrench
• 10 mm Box Wrench

2.1 KNOW THE GENERATOR

Read the Owner’s Manual and Safety Rules before operating this generator.
Compare the generator to Figures 3 through 6 to become familiarized with the locations of various controls and adjustments. Save this manual for future reference.
1. 120 Volt AC, 20 Amp, GFCI Receptacle – Supplies electrical power for the operation of 120 Volt AC, 20 Amp, single-phase, 60 Hz electrical lighting, appliance, tool and motor loads. It also provides protection with an Integral Ground Fault Circuit Interrupter with press to "Test" and "Reset" buttons.
2. Circuit Breakers (AC) – Each receptacle is provided with a
13.5A push-to-reset circuit breaker to protect the generator against electrical overload.
4
Operation
3. Air Filter – Filters intake air as it is drawn into the engine.
4. Choke Knob – Used when starting a cold engine.
5. Fuel Tank – Tank holds 4 U.S. gallons of fuel.
6. Grounding Lug – Ground the generator to an approved earth
ground here. See "Grounding the Generator" for details.
7. ON/OFF Switch – Controls the operation of the generator.
8. Muffler – Quiets the engine.
9. Handle – Pivot and retract for storage.
10. Gas Cap – Fuel fill location.
11. Fuel Gauge – Shows fuel level in tank.
12. Oil Check/Fill – Check and fill oil here.
13. Recoil Starter – Use to start engine manually.
14. Fuel Shut Off – Valve between fuel tank and carburetor.
15. Oil Drain Plug – Used to drain engine oil.
16. Spark Arrestor – Reduces fire hazard by containing sparks.
17. Roll Over Valve – Passes fuel vapors to the carbon canister.
18. Carbon Canister – Absorbs fuel tank vapors.
19. Recovery Hose – Installed between items 17 & 18.
Figure 3 - Control Panel
7
21
15
Figure 5 - Generator Controls
7
12
Figure 6 - Generator Controls
17
19
16
8
6
6
Figure 4 - Generator Controls
18
19
5
Operation

2.2 CORD SETS AND CONNECTION PLUGS

2.2.1 120 VAC, 20 AMP, DUPLEX RECEPTACLE
This is a 120 Volt outlet protected against overload by a 13.5 Amp push-to-reset circuit breaker (Figure 6). 13.5 Amps of current may be drawn from each socket, however, total power drawn must be kept within data plate ratings. Use only high quality, well insulated, 3-wire grounded cord sets rated for 125 Volts at 20 Amps (or greater).

2.3 HOW TO USE THE GENERATOR

If there are any problems operating the generator, please call the generator helpline at 1-888-436-3722.
Never operate in an enclosed area or indoors! NEVER use in the home, in a vehicle, or in
partly enclosed areas such as garages, EVEN IF doors and windows are open! ONLY use outdoors and far from open windows, doors, vents, and in an area that will not accumulate deadly exhaust.
The engine exhaust fumes contain carbon monoxide, which you cannot see or smell.
This poisonous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death.
Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator
operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The generator MUST be operated outdoors.
This exhaust system must be properly maintained. Do nothing that might render the
exhaust system unsafe or in noncompliance with any local codes and/or standards.
Always use a battery operated carbon monoxide alarm indoors, installed according to
the manufacturers instructions.
2.3.1 GROUNDING THE GENERATOR
This generator has an equipment ground that connects the generator frame components to the ground terminals on the AC output receptacles (see NEC 250.34 (A) for explanation). This allows the generator to be used as a portable without grounding the frame of the generator as specified in NEC 250.34.
2.3.1.1 SPECIAL REQUIREMENTS
There may be Federal or State Occupational Safety and Health Administration (OSHA) regulations, local codes, or ordinances that apply to the intended use of the generator.
Please consult a qualified electrician, electrical inspector, or the local agency having jurisdiction:
In some areas, generators are required to be registered with local utility companies.
If the generator is used at a construction site, there may be additional regulations which must be observed.
2.3.2 CONNECTING THE GENERATOR TO A BUILDING’S ELECTRICAL SYSTEM
When connecting directly to a building’s electrical system, it is recommended that a manual transfer switch is used. Connections for a portable generator to a building’s electrical system must be made by a qualified electrician and in strict compliance with all national and local electrical codes and laws.
Figure 7 - Grounding the Generator
6
2.3.3 CONNECTING ELECTRICAL LOADS
DO NOT connect 240 Volt loads to 120 Volt receptacles. DO NOT connect 3-phase loads to the generator. DO NOT connect 50 Hz loads to the generator.
• Let engine stabilize and warm up for a few minutes after starting.
• Plug in and turn on the desired 120 or 240 Volt AC, single phase,
60 Hz electrical loads.
• Add up the rated watts (or amps) of all loads to be connected
at one time. This total should not be greater than (a) the rated wattage/amperage capacity of the generator or (b) circuit breaker rating of the receptacle supplying the power. See "Don't Overload the Generator".
Operation

2.4 DON’T OVERLOAD THE GENERATOR

Overloading a generator in excess of its rated wattage capacity can result in damage to the generator and to connected electrical devices. Observe the following to prevent overloading the unit:
• Add up the total wattage of all electrical devices to be connected at one time. This total should NOT be greater than the generator's wattage capacity.
• The rated wattage of lights can be taken from light bulbs. The rated wattage of tools, appliances and motors can usually be found on a data label or decal affixed to the device.
• If the appliance, tool or motor does not give wattage, multiply volts times ampere rating to determine watts (volts x amps = watts).
• Some electric motors, such as induction types, require about three times more watts of power for starting than for running. This surge of power lasts only a few seconds when starting such motors. Make sure to allow for high starting wattage when selecting electrical devices to connect to the generator:
1. Figure the watts needed to start the largest motor.
2. Add to that figure the running watts of all other connected loads.
The Wattage Reference Guide is provided to assist in determining how many items the generator can operate at one time.
NOTE: All figures are approximate. See data label on appliance for wattage requirements.

2.5 WATTAGE REFERENCE GUIDE

Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Running Watts
*Air Conditioner (12,000 Btu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1700
*Air Conditioner (24,000 Btu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3800
*Air Conditioner (40,000 Btu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6000
Battery Charger (20 Amp). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
Belt Sander (3") . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000
Chain Saw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Circular Saw (6-1/2"). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .800 to 1000
*Clothes Dryer (Electric) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5750
*Clothes Dryer (Gas). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 700
*Clothes Washer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1150
Coffee Maker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1750
*Compressor (1 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000
*Compressor (3/4 HP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1800
*Compressor (1/2 HP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1400
Curling Iron . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 700
*Dehumidifier. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 650
Disc Sander (9") . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Edge Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
Electric Blanket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 400
Electric Nail Gun . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Electric Range (per element) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1500
Electric Skillet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1250
*Freezer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700
*Furnace Fan (3/5 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 875
*Garage Door Opener. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .500 to 750
Hair Dryer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Hand Drill . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250 to 1100
Hedge Trimmer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 450
Impact Wrench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
Iron . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
*Jet Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 800
Lawn Mower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1200
Light Bulb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Microwave Oven . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .700 to 1000
*Milk Cooler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1100
Oil Burner on Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300
Oil Fired Space Heater (140,000 Btu) . . . . . . . . . . . . . . . . . . . . . . . . 400
Oil Fired Space Heater (85,000 Btu) . . . . . . . . . . . . . . . . . . . . . . . . . 225
Oil Fired Space Heater (30,000 Btu) . . . . . . . . . . . . . . . . . . . . . . . . . 150
*Paint Sprayer, Airless (1/3 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 600
Paint Sprayer, Airless (handheld) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Radio. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50 to 200
*Refrigerator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 700
Slow Cooker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
*Submersible Pump (1-1/2 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2800
*Submersible Pump (1 HP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000
*Submersible Pump (1/2 HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1500
*Sump Pump. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .800 to 1050
*Table Saw (10"). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1750 to 2000
Television . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .200 to 500
Toaster . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1000 to 1650
Weed Trimmer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500
* Allow 3 times the listed watts for starting these devices.

2.6 BEFORE STARTING THE GENERATOR

Prior to operating the generator, engine oil and gasoline will need to be added, as follows:
2.6.1 ADDING ENGINE OIL
All oil should meet minimum American Petroleum Institute (API) Service Class SJ, SL or better. Use no special additives. Select the oil's viscosity grade according to the expected operating temperature (also see chart).
• Above 32 °F (0 °C), use SAE 30
• Between 40 °F and -10 °F (4 and -32 °C), use 10W-30
• Synthetic 5W-30 for all temperature ranges
Any attempt to crank or start the engine before it has been properly serviced with the
recommended oil may result in an engine failure.
7
Operation
1. Place generator on a level surface (not to exceed 15° in any
direction).
2. Clean area around oil fill and remove oil fill cap and dipstick.
3. Wipe dipstick clean.
4. Slowly fill engine with oil through the oil fill opening until it
reaches the full mark on the dipstick. Stop filling occasionally to check oil level. Be careful not to over fill.
5. Install oil fill cap and finger tighten securely.
6. Check engine oil level before starting each time thereafter.
2.6.2 ADDING GASOLINE
Never fill fuel tank indoors. Never fill fuel tank when engine is running or hot. Allow engine
to cool entirely before filling fuel tank. Avoid spilling gasoline on HOT engine. DO NOT light a cigarette or smoke when filling the fuel tank. Gasoline is highly flammable and its vapors are explosive.
Do not overfill the fuel tank. Always leave room
for fuel expansion. If the fuel tank is overfilled, fuel can overflow onto a HOT engine and cause FIRE or EXPLOSION.
1. Use regular UNLEADED gasoline with the generator engine. Do
not use any gasoline with more than 10% added Ethanol, and never use E85 gasoline. Do not mix oil with gasoline.
2. Clean area around fuel fill cap, remove cap.
3. Slowly add unleaded regular gasoline to fuel tank. Be careful
not to overfill (Figure 8).
4. Install fuel cap and wipe up any spilled gasoline.
IMPORTANT: It is important to prevent gum deposits from forming in fuel system parts such as the carburetor, fuel hose or tank during storage. Alcohol-blended fuels (called gasohol, ethanol or methanol) can attract moisture, which leads to separation and formation of acids during storage. Acidic gas can damage the fuel system of an engine while in storage. To avoid engine problems, the fuel system should be emptied before storage of 30 days or longer. See the "Storage" section. Never use engine or carburetor cleaner products in the fuel tank as permanent damage may occur.

2.7 TO START THE ENGINE

Never start or stop engine with electrical
devices plugged into the receptacles AND devices turned on.
1. Unplug all electrical loads from the unit's receptacles before starting the engine.
2. Make sure the unit is in a level position (not to exceed 15° in any direction).
3. Turn the Fuel Shut-off Valve to the "ON" position (Figure 9).
4. Turn engine ON/OFF switch to ON position (Figure 9).
5. Move engine CHOKE lever to the START position (Figure 10).
6. To start engine, firmly grasp the recoil handle and pull slowly until increased resistance is felt. Pull rapidly up and away.
7. When engine starts, move choke lever to 1/2-CHOKE position until engine runs smoothly and then fully into RUN position. If engine falters, move choke back out to 1/2-CHOKE position until engine runs smoothly and then to RUN position.
NOTE:
If engine fires, but does not continue to run, move choke lever to the START position and repeat starting instructions.
8
Figure 8 - Fuel Tank
DO NOT FILL ABOVE THE LIP!
CHOKE
FUEL
SHUT-OFF
VALVE
Figure 9 - Fuel Shut-off Valve
RECOIL
HANDLE
ON/OFF SWITCH

Maintenance

Figure 10 - Choke Position
IMPORTANT: Do not overload the generator. Also, do not overload individual panel receptacles. These outlets are protected against overload with push-to-reset-type circuit breakers. If amperage rating of any circuit breaker is exceeded, that breaker opens and electrical output to that receptacle is lost. Read “Don’t Overload the Generator” carefully.

2.8 STOPPING THE ENGINE

1. Shut off all loads, then unplug the electrical loads from generator panel receptacles. Never start or stop the engine with electrical devices plugged in and turned on.
2. Let engine run at no-load for several minutes to stabilize the internal temperatures of engine and generator.
3. Move ON/OFF switch to OFF position.
4. Close fuel valve.

2.9 LOW OIL LEVEL SHUTDOWN SYSTEM

The engine is equipped with a low oil level sensor that shuts down the engine automatically when the oil level drops below a specified level. If the engine shuts down by itself and the fuel tank has enough gasoline, check engine oil level.

3.1 MAINTENANCE SCHEDULE

Follow the calendar intervals. More frequent service is required when operating in adverse conditions noted below.
Check Oil Level At Each Use Change Oil + *Every Season Check Valve Clearance ***Every Season Service Air Filter **Every Season Replace Spark Plug Every Season
+ Change oil after first 20 hours of operation, then every season. * Change oil every month when operating under heavy load or in high temperatures. ** Clean more often under dirty or dusty operating conditions. Replace air filter parts
if they cannot be adequately cleaned.
*** Check valve clearance and adjust if necessary after first 50 hours of operation and
every 100 hours thereafter.

3.2 PRODUCT SPECIFICATIONS

3.2.1 GENERATOR SPECIFICATIONS
Rated. Power .................................................................................. 3.25 kW**
Surge Power ...................................................................................... 3.75 kW
Rated AC Voltage ..................................................................................... 120
Rated Current ................................................................................ 27 Amps**
Rated Frequency ............................................................ 60 Hz @ 3600 RPM
Phase ........................................................................................ Single Phase
** Maximum wattage is subject to, and limited by, such factors as fuel Btu
content, ambient temperature, altitude, engine condition, etc.. Maximum power decreases about 3.5% for each 1,000 feet above sea level; and will also decrease about 1% for each 10 °F (6 °C) above 60 °F (16 °C) ambient temperature.
3.2.2 ENGINE SPECIFICATIONS
Displacement ........................................................................................208 cc
Spark Plug Type ...................... F6TC, NGK BPR4ES or Champion RN14YC
Spark Plug Gap ......................................0.028-0.031 inch or (0.70-0.80 mm)
Gasoline Capacity .................................................... 4 U.S. gallons (15.14 L)
Oil Type ......................See Chart in "Before Starting the Generator" Section
Oil Capacity ........................................................................ 0.634 Qts. (0.6 L)
Run Time ................................................................... 12.5 Hours at 1/2 Load
Operating Temperature Range ....................0 °F (-17 °C) to 110 °F (43 °C)*
* When operating above 77 °F (25 °C) there may be a decrease in power.
2.9.1 SENSING LOW OIL LEVEL
If the system senses a low oil level during operation, the engine shuts down. The engine will not run until the oil has been refilled to the proper level.
9
Maintenance

3.3 GENERAL RECOMMENDATIONS

The warranty of the generator does not cover items that have been subjected to operator abuse or negligence. To receive full value from the warranty, the operator must maintain the generator as instructed in this manual.
Some adjustments will need to be made periodically to properly maintain the generator.
All adjustments in the Maintenance section of this manual should be made at least once each season. Follow the requirements in the "Maintenance Schedule".
NOTE:
Once a year replace the spark plug and replace the air filter. A new spark plug and clean air filter assure proper fuel-air mixture and help the engine run better and last longer.
3.3.1 GENERATOR MAINTENANCE
Generator maintenance consists of keeping the unit clean and dry. Operate and store the unit in a clean dry environment where it will not be exposed to excessive dust, dirt, moisture or any corrosive vapors. Cooling air slots in the generator must not become clogged with snow, leaves, or any other foreign material.
Check the cleanliness of the generator frequently and clean when dust, dirt, oil, moisture or other foreign substances are visible on its exterior surface.
Never insert any object or tool through the air
cooling slots, even if the engine is not running.
3.3.4 CHECKING OIL LEVEL
See the “Before Starting the Generator” section for information on checking the oil level. The oil level should be checked before each use, or at least every eight hours of operation. Keep the oil level maintained (Figure 11).
Figure 11 - Oil Drain, Check & Fill
Oil Drain
Oil Check & Fill
3.3.5 CHANGING THE OIL
Change the oil after the first 20 hours of operation, then every season. If running this unit under dirty or dusty conditions, or in extremely hot weather, change the oil more often.
NOTE:
DO NOT use a garden hose to clean generator. Water can enter the engine fuel system and cause problems. In addition, if water enters the generator through cooling air slots, some water will be retained in voids and crevices of the rotor and stator winding insulation. Water and dirt buildup on the generator internal windings will eventually decrease the insulation resistance of these windings.
3.3.2 TO CLEAN THE GENERATOR
• Use a damp cloth to wipe exterior surfaces clean.
• A soft, bristle brush may be used to loosen caked on dirt, oil, etc.
• A vacuum cleaner may be used to pick up loose dirt and debris.
• Low pressure air (not to exceed 25 psi) may be used to blow away
dirt. Inspect cooling air slots and openings on the generator. These openings must be kept clean and unobstructed.
3.3.3 ENGINE MAINTENANCE
When working on the generator, always disconnect spark plug wire from spark plug and
keep wire away from spark plug.
Hot oil may cause burns. Allow engine to
cool before draining oil. Avoid prolonged or repeated skin exposure with used oil. Thoroughly wash exposed areas with soap.
Use the following instructions to change the oil after the engine cools down:
1. Clean area around oil drain plug.
2. Remove oil drain plug from engine and oil fill plug to drain oil completely into a suitable container.
3. When oil has completely drained, install oil drain plug and tighten securely.
4. Fill engine with recommended oil. (See “Before Starting the Generator” for oil recommendations).
5. Wipe up any spilled oil.
6. Dispose of used oil at a proper collection center.
10
Maintenance
3.3.6 REPLACING THE SPARK PLUG
Use spark plug F6TC, NGK BPR4ES or Champion RN14YC. Replace the plug once each year. This will help the engine start easier and run better.
1. Stop the engine and pull the spark plug wire off of the spark plug.
2. Clean the area around the spark plug and remove it from the cylinder head.
3. Set the spark plug's gap to 0.70-0.80 mm (0.028-0.031 in). Install the correctly gapped spark plug into the cylinder head and torque to 15 ft/lbs. (Figure 12).
Figure 12 - Spark Plug Gap
3.3.7 SPARK ARRESTOR
1. Shut off generator and allow the engine and muffler to cool down completely before servicing spark arrestor (located on the back of the muffler).
2. Remove the clamp and spark arrestor screen.
3. Clean the spark arrestor screen with a small wire brush.
4. Replace the spark arrestor if it is damaged.
5. Installation of the spark arrestor screen is the reverse of the removal.

3.4 SERVICE AIR FILTER

The engine will not run properly and may be damaged if using a dirty air filter. Clean the air filter once a year (Figure 13). Clean or replace more often if operating under dusty conditions.
1. Remove air filter cover.
2. Wash in soapy water. Squeeze filter dry in clean cloth (DO NOT TWIST).
3. Clean air filter cover before re-installing it.
Figure 13 - Air Filter
Air Cleaner Cover
Air Filter

3.5 VALVE CLEARANCE

• Intake — 0.10 ± 0.02 mm (cold), (0.004" ± 0.001" in)
• Exhaust — 0.15 ± 0.02 mm (cold) (0.006" ± 0.001" in)
After the first 50 hours of operation, check the valve clearance in the engine and adjust if necessary.
Important: If feeling uncomfortable about doing this procedure or the proper tools are not available, please take the generator to the nearest service center to have the valve clearance adjusted. This is a very important step to ensure longest life for the engine.

3.6 GENERAL

The generator should be started at least once every 30 days and be allowed to run at least 30 minutes. If this cannot be done and the unit must be stored for more than 30 days, use the following information as a guide to prepare it for storage.
NEVER store engine with fuel in tank indoors
or in enclosed, poorly ventilated areas where fumes may reach an open flame, spark or pilot light as on a furnace, water heater, clothes dryer or other gas appliance.
11
Maintenance

3.7 LONG TERM STORAGE

It is important to prevent gum deposits from forming in essential fuel system parts such as the carburetor, fuel hose or tank during storage. Also, experience indicates that alcohol-blended fuels (called gasohol, ethanol or methanol) can attract moisture, which leads to separation and formation of acids during storage. Acidic gas can damage the fuel system of an engine while in storage.
To avoid engine problems, the fuel system should be emptied before storage of 30 days or longer, as follows:
1. Remove all gasoline from the fuel tank. Use a commercially available, non-conductive vacuum siphon.
Drain fuel into approved container outdoors,
away from open flame. Be sure engine is cool. Do not smoke.
2. Start and run engine until engine stops from lack of fuel.
3. Drain oil from crankcase after the engine cools down. Refill with recommended grade.
4. Remove the spark plug and pour about 1/2 oz (15 ml) of engine oil into the cylinder. Cover spark plug hole with rag. Pull the recoil starter a couple times to lubricate the piston rings and cylinder bore.

3.8 OTHER STORAGE TIPS

• Do not store gasoline from one season to another.
• Replace the gasoline can if it starts to rust. Rust and/or dirt in the gasoline will cause problems with the carburetor and fuel system.
• If possible, store the unit indoors and cover it to give protection from dust and dirt. BE SURE TO EMPTY THE FUEL TANK.
• If it is not practical to empty the fuel tank and the unit is to be stored for some time, use a commercially available fuel stabilizer added to the gasoline to increase the life of the gasoline.
• Cover the unit with a suitable protective cover that does not retain moisture.
NEVER cover the generator while engine and
exhaust areas are warm.
Avoid spray from spark plug hole when
cranking engine.
5. Install and tighten spark plugs. Do not connect spark plug wire.
6. Clean the generator outer surfaces. Check that cooling air slots and openings on generator are open and unobstructed.
7. Store the unit in a clean, dry place
12

4.1 TROUBLESHOOTING GUIDE

PROBLEM CAUSE CORRECTION
Engine is running, but no AC output is available.
1. Circuit breaker is open.
2. Poor connection or defective cord set.
3. Connected device is bad.
4. Fault in generator.
5. 120V GFCI tripped (no light).
1. Reset circuit breaker.
2. Check and repair.
3. Connect another device that is in good condition.
4. Contact Authorized Service Facility.
5. Reset 120V GFCI push button (light is on).

Troubleshooting

Engine runs well but bogs down when loads are connected.
Engine will not start; or starts and runs rough.
Engine shuts down during operation.
Engine lacks power. 1. Load is too high.
1. Short circuit in a connected load.
2. Generator is overloaded.
3. Engine speed is too slow.
4. Shorted generator circuit.
1. Dirty air filter.
2. Out of gasoline.
3. Stale gasoline.
4. Spark plug wire not connected to spark plug.
5. Bad spark plug.
6. Water in gasoline.
7. Over-choking.
8. Low oil level.
9. Excessive rich fuel mixture.
10. Intake valve stuck open or closed.
11. Engine has lost compression.
1. Out of gasoline.
2. Low oil level.
3. Fault in engine.
2. Dirty air filter.
3. Engine needs to be serviced.
1. Disconnect shorted electrical load.
2. See “Don’t Overload the Generator”.
3. Contact Authorized Service Facility.
4. Contact Authorized Service Facility.
1. Clean or replace air filter.
2. Fill fuel tank.
3. Drain fuel tank and fill with fresh fuel.
4. Connect wire to spark plug.
5. Replace spark plug.
6. Drain fuel tank; fill with fresh fuel.
7. Put choke knob to No Choke position.
8. Fill crankcase to proper level.
9. Contact Authorized Service Facility.
10. Contact Authorized Service Facility.
11. Contact Authorized Service Facility.
1. Fill fuel tank.
2. Fill crankcase to proper level.
3. Contact Authorized Service Facility.
1. See “Don’t Overload the Generator”.
2. Replace air filter.
3. Contact Authorized Service Facility.
Engine “hunts” or falters. 1. Choke is opened too soon.
2. Carburetor is running too rich or too lean.
1. Move choke to halfway position until engine runs smoothly.
2. Contact Authorized Service Facility.
13
Loading...
+ 33 hidden pages