Generac 00784-2, 09290-4 User Manual

POWER SYSTEMS, INC.
®
Owner’s Manual and
Installation Instructions
Air-cooled Recreational
Vehicle Generators
• Model Nos: 00784-2 and 09290-4
Generac®Power Systems, Inc.
INTRODUCTION
READ THIS MANUAL THOROUGHLY
If you do not understand any portion of this manual, contact Generac or your nearest Generac Authorized Service Dealer for starting, operating and servicing pro­cedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert you to special instruction about a particular operation that may be hazardous if performed incorrectly or care­lessly. Observe them carefully. Their definitions are as follows:
After this heading, you can read instructions that, if not strictly complied with, will result in personal injury or property damage.
After this heading, you can read instructions that, if not strictly complied with, may result in personal injury or property damage.
After this heading, you can read instructions that, if not strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, you can read explanatory statements that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli­ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety informa­tion that, if not followed, could endanger personal safety and/or property of you and others.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock hazard.
The operator (driver) is responsible for proper and safe use of the vehicle and its equipment, and the safe­ty of all vehicle occupants. We strongly recommend that the operator read this manual and thoroughly understand all instructions before using this equip­ment. We also strongly recommend instructing other occupants in the vehicle to properly start and operate the generator. This prepares them if they need to oper­ate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information, including warranty, electrical diagrams, exploded views and lists of repair parts for generator model numbers 009290-4 and 00784-2. In addition, the lat­ter portion of this manual contains information nec­essary for the proper installation of these generators.
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safe­ty checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by a Generac Authorized Service Dealer. Normal maintenance ser­vice and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for maintenance service.
Proper maintenance and care of your generator ensure a minimum number of problems and keep operating expenses at a minimum. See your Generac Authorized Service Dealer for service aids and acces­sories.
HOW TO OBTAIN SERVICE
When your generator requires servicing or repairs, simply contact a Generac Authorized Service Dealer for assistance. Service technicians are factory-trained and are capable of handling all of your service needs.
When contacting a Generac Authorized Service Dealer or the factory about parts and service, always supply the complete model number and serial number of your unit as given on its data decal, which is located on your generator.
Model No. ____________ Serial No. ______________
AUTHORIZED SERVICE
DEALER LOCATION
To locate the GENERAC AUTHORIZED SERVICE
DEALER nearest you, please call this number:
1-800-333-1322
ONLY DEALER LOCATION INFORMATION
CAN BE OBTAINED AT THIS NUMBER.
Table of Contents
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generatorss
Generac®Power Systems, Inc. 1
Part I — Owner’s Manual
Introduction ........................................Inside Front Cover
Read This Manual Thoroughly..................................IFC
Contents ..................................................................IFC
Operation and Maintenance ......................................IFC
How to Obtain Service ..............................................IFC
Authorized Service Dealer Locator Number ................IFC
Safety Rules ........................................................................2
Section 1 – General Information....................................4
1.1 Generator Identification ........................................4
1.2 Generator Applicability ..........................................5
1.3 Installation ............................................................5
1.4 Safety ....................................................................5
1.5 Generator AC Connection System..........................5
1.6 Specifications ........................................................6
Section 2 – Operation ......................................................7
2.1 Generator Control Panel ........................................7
2.2 Optional Remote Start/Stop Panel ........................7
2.3 Automatic Choke ..................................................7
2.4 Before Starting the Engine ....................................8
2.5 Starting the Generator ..........................................8
2.6 Stopping the Generator ........................................9
2.7 Applying Loads to Generator ................................9
2.8 Protection Systems ................................................9
2.9 Additional Information ........................................10
Section 3 – Maintenance ..............................................11
3.1 Checking the Engine Oil Level ............................11
3.2 Changing the Engine Oil and/or Oil Filter ............11
3.3 Maintaining the Engine Air Cleaner ....................12
3.4 Clean Air Intake Screen ......................................12
3.5 Checking the Engine Spark Plug..........................12
3.6 Fuel Filter (Gasoline Only) ..................................13
3.7 Spark Arrestor Muffler ........................................13
3.8 Cleaning the Generator ........................................13
3.9 Battery Maintenance ............................................13
3.10 Major Service Manual ..........................................14
3.11 Drive Belt ............................................................14
3.12 Exercising the Generator ....................................14
3.13 Out of Service Procedure ....................................14
3.14 Wattage Reference Guide......................................15
Notes ..................................................................................16
P
artII — Installation Instructions
Safety Rules ......................................................................18
Section 1 – General Information ................................20
1.1 Purpose and Scope of the Manual ......................20
1.2 Safety ..................................................................20
1.3 Standards Booklets ............................................20
1.4 Equipment Description........................................20
1.5 Generator Engine Operating Speed ....................20
1.6 Generator AC Connection System........................20
Section 2 – Installation ..................................................22
2.1 Location and Support ..........................................22
2.2 Generator Compartments ....................................23
2.3 Cooling and Ventilating Air ..................................26
2.4 Gasoline Fuel System ..........................................27
2.5 Exhaust System ..................................................28
2.6 Electrical connections..........................................29
2.7 Battery Installation ..............................................32
2.8 Optional Accessories............................................32
Section 3 – Post Installation Start-up and
Adjustments ................................................33
3.1 Post Installation Tests ..........................................33
3.2 Before Initial Start-up ..........................................33
3.3 Initial Start-up ....................................................33
3.4 Testing Under Load ............................................33
3.5 Installation Checklist ..........................................34
Section4–Troubleshooting ........................................35
4.1 Troubleshooting Guide ........................................35
Section 5 – Electrical Data ............................................36
Section 6 – Exploded Views and Parts Lists ............38
Section7–Warranty......................................................48
2 Generac®Power Systems, Inc.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this manual and with the unit. The generator can operate safely, efficiently and reli­ably only if it is properly installed, operated and main­tained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
Generac cannot possibly anticipate every possible circumstance that might involve a hazard. The warn­ings in this manual, and on tags and decals affixed to the unit, are, therefore, not all-inclusive. If you use a procedure, work method or operating tech­nique Generac does not specifically recommend, you must satisfy yourself that it is safe for you and others. You also must make sure the procedure, work method or operating technique that you choose does not render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near running generators.
GENERAL HAZAR
DS
• For safety reasons, Generac recommends that the installation, initial start-up and mainte­nance of this equipment is carried out by a Generac Authorized Service Dealer.
• The engine exhaust fumes contain carbon monox­ide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust sys­tem must be installed properly, in strict compli­ance with applicable codes and standards. Following installation, you must do nothing that might render the system unsafe or in noncompli­ance with such codes and standards. The genera­tor compartment must be completely vapor sealed from the vehicle interior. There must be no possi­bility of exhaust fumes entering the vehicle interi­or. Never operate this equipment with a leaking or defective exhaust system.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and venti­lating air is critical to correct generator operation and is required to expel toxic fumes and fuel vapors from the generator compartment. Without sufficient cooling airflow, the engine/generator quickly overheats, which causes serious damage to the generator. Do not alter the installation or per­mit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator.
• When working on this equipment, remain alert at all times. Never work on the equipment when you are physically or mentally fatigued.
• Inspect the generator regularly, and contact your nearest Generac Authorized Service Dealer immedi­ately for parts needing repair or replacement.
• Before performing any maintenance on the genera­tor, disconnect its battery cables to prevent acci­dental start up. Disconnect the cable from the bat­tery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating con­ditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
Safety Rules
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas of the recreational vehicle. Safety should be stressed to all operators and potential operators of this equipment.
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
This product contains or emits chemicals known to the state of California to cause
cancer, birth defects or other reproductive harm.
WARNING:
Generac®Power Systems, Inc. 3
ELECTRICAL HAZARDS
• The generator covered by this manual produces dangerous electrical voltages and can cause fatal electrical shock. Avoid contact with bare wires, ter­minals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If you must work around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• During installation onto the vehicle, have the genera­tor properly grounded (bonded) either by solid mounting to the vehicle frame or chassis, or by means of an approved bonding conductor. DO NOT disconnect the bonding conductor, if so equipped. DO NOT reconnect the bonding conductor to any generator part that might be removed or disassem­bled during routine maintenance. If the grounding conductor must be replaced, use only a flexible con­ductor that is of No. 8 American Wire Gauge (AWG) copper wire minimum.
• In case of accident caused by electric shock, imme­diately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting imple­ment, such as a rope or board, to free the victim from the live conductor. If the victim is uncon­scious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equip­ment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving com­ponents causing injury.
FIREHAZARDS
• For fire safety, the generator must be installed and maintained properly. Installation always must comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installa­tion, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regu­lations.
• Keep a fire extinguisher in the vehicle at all times. Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the recreational vehicle generator electrical system. Keep the extinguisher properly charged and be familiar with its use. If you have any question per­taining to fire extinguishers, consult your local fire department.
EXP
LOSION HAZARDS
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no com­bustible materials are left in the generator com­partment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surround­ing the generator clean and free from debris.
• Gasoline is extremely FLAMMABLE and its vapors are EXPLOSIVE. Do not permit smoking, open flame, sparks or any source of heat in the vicinity while handling gasoline. Comply with all laws gov­erning the storage and handling of gasoline.
Safety Rules
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
4 Generac®Power Systems, Inc.
Section 1 – General Information
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Please record the following information from the generator DATA DECAL or information decal.
1. Model Number ____________________ 2. Serial Number __________________
3. kW Rating __________________________ 4. Rated Voltage __________________
5. Phase ______________________________ 6. Hertz __________________________
1.1 GENERATOR IDENTIFICATION
REFERENCE NUMBER IDENTIFICATION
1. Generator Air Intake Screen
2. Data Plate
3. Engine Start/Stop Switch
4. 15 amp Fuse
5. 25 or 30 Amp (2 Pole) Circuit Breaker
6. Optional Remote Panel Receptacle
7. Generator AC Output Leads
8. Fuel Inlet
9. Fuel Primer Switch
10. Fuel Pump
11. Oil Filter
12. Starter Contactor
13. Oil Drain Plug
14. Oil Dipstick and Filler Tube
1
3
2
4
11
10
9
8
12
7
6
5
14
13
Generac®Power Systems, Inc. 5
Section 1 – General Information
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
1.2 GENERATOR APPLICABILITY
These generators have been designed and manufac­tured for supplying electrical power for recreational vehicles. You should not modify the generator or use it for any application other than for what it was designed. If there are any questions pertaining to its application, write or call the factory. Do not use the unit until you have been advised by a competent authority.
For fire safety, the generator must have been properly installed in compliance with ANSI
119.2-1975/NFPA 501C-1974, “Standard for Recreational Vehicles, Part III – Installation of Electrical Systems.” The generator also must have been installed in strict compliance with the manufacturer’s detailed installation instruc­tions. After installation, do nothing that might render the unit in noncompliance with such codes, standards and instructions.
1.2.1 PRIMEPACT 70
Use this generator to supply electrical power for operating 230-volt, single-phase, 50 Hertz, AC elec­trical loads. These loads can require up to 7,000 watts (7.0 kW) of power, but cannot exceed 30.4 AC amperes of current at 230 volts.
1.2.2 PRIMEPACT 50
Use this generator to supply electrical power for operating 230 volt, single phase, 50 Hertz AC electri­cal loads. These loads can require up to 5,000 watts (5.0 kW) of power, but cannot exceed 20.8 amperes of current at 230 volts.
Do not overload the generator. Some installa­tions may require that electrical loads be alter­nated to avoid overloading. Applying exces­sively high electrical loads may damage the generator and may shorten its life. Add up the rated watts of all electrical lighting, appliance, tool and motor loads the generator will power at one time. This total should not be greater than the wattage capacity of the generator. If an electrical device nameplate gives only volts and amps, multiply volts times amps to obtain watts (volts x amps = watts). Some electric motors require more watts of power (or amps of current) for starting than for continuous operation.
1.3 INSTALLATION
This manual has been prepared under the assump­tion that a competent, qualified technician installed the generator into a recreational vehicle. We also assume the installer complied with all applicable codes, standards and regulations pertaining to instal­lation.
Owners/Operators should make sure nothing is done during installation that might render the unit unsafe or in noncompliance with applicable codes standards and instructions. They should be sure the unit has been installed to allow adequate ventilation for cool­ing and exhaust air.
1.4 SAFETY
Before attempting to use the generator set, carefully read the “Safety Rules” section of this manual. Comply strictly with these rules to prevent accidents and damage to equipment and/or property. We sug­gest copying and posting the “Safety Rules” in poten­tial hazard areas of the vehicle. Stress safety to all operators and potential operators of this equipment.
1.5 GENERATOR AC
CONNECTION SYSTEM
This generator set is equipped with dual stator AC power windings. These two-stator windings supply electrical power to customer electrical loads.
NOTE:
One side of the winding is grounded.
Figure 1.1 – Connections for 230 Volts Only
6 Generac®Power Systems, Inc.
Section 1 – General Information
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
1.6 SPECIFICATIONS
1.6.1 FUEL REQUIREMENTS
These generators are equipped with a gasoline fuel sys­tem. Depending on the installation, the generator may have either a separate fuel tank, or it may “share” the vehicle engine’s fuel tank.
NOTE:
Some installations using a “shared” fuel tank may have a generator fuel pickup tube that is shorter than the vehicle engine’s pickup tube. Such an arrangement causes the generator engine to “run out of gas” while adequate fuel for the vehicle remains in the tank.
To reduce lead and carbon deposits use high quality UNLEADED gasoline with the generator. Leaded REG­ULAR grade gasoline is an acceptable substitute.
NOTE:
Using unleaded gasoline contributes to longer engine valve life by reducing lead and carbon deposits.
Generac does not recommend using any gasoline containing alcohol (such as “gasohol”). If you use any gasoline containing alcohol, it must not contain more than 10 percent ethanol, and it must be removed from the generator during storage. Do NOT use any gasoline containing methanol. If you use gasoline with alcohol, inspect more frequently for fuel leaks and other abnormalities.
1.6.2 ENGINE OIL REQUIREMENTS
Use only high quality detergent oil classified “For Service SF” and with an oil viscosity rating of SAE 10W-30 oil. Do not pour in any additives to the rec­ommended oil. Engine crankcase capacity is 1.4 liters. See Section 3.2 on page 11 for oil level check and filing procedures.
1.6.3 ENGINE
Type of Engine ......................................GN-480, Twin-cylinder
Cooling Method..........................................................Air-cooled
Rated Horsepower ..........................................16 @ 3,600 rpm
Displacement ....................................................................480cc
Compression Ratio ........................................................8.6 to 1
Cylinder Block ..........................Aluminum w/Cast Iron Sleeve
Type of Governor ..............................Mechanical, Fixed Speed
Engine Governor Speed ............................................3000 rpm
Air Cleaner..........................Paper Element w/Foam Precleaner
Starter..........................................................12-volt DC Electric
Ignition System........................Solid-state w/Flywheel Magneto
Recommended Spark Plug
Champion ..................................................................RC12YC
AC....................................................................................R45S
Fram Autolite ......................................................................65
Spark Plug Gap ........................................0.030 inch (0.8 mm)
1.6.4 GENERATOR PP50G/PP70G
Rated Maximum Continuous
AC Output ....................5,000 (5.0 kW)/7,000 Watts (7.0 kW)
Rated Voltage ..............................................................230 Volts
Rated Maximum Continuous
AC Current ................................21.8 Amperes/30.4 Amperes
Phase ................................................................................Single
Rotor RPM ........................................................................3,000
Number of Rotor Poles ............................................................2
Engine RPM ............................................................2,900/3,000
Rated AC Frequency ........................................................50 Hz
Weight......................................................................222 Pounds
Length........................................................25 inches (635 mm)
Width ..................................................18.5 inches (469.9 mm)
Height..............................................16.75 inches (425.45 mm)
Generac®Power Systems, Inc. 7
Section 2 – Operation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
2.1 GENERATOR CONTROL PANEL
The following features are mounted on the generator control panel (Figure 2.1):
Figure 2.1 – Generator Control Panel
2.1.1 FUEL PRIMER
Before starting a cold engine (if it has not been start­ed in more than two weeks), you must press this switch for approximately five seconds to bring fuel from the tank to the fuel pump. This rocker type switch springs back into its original position when you release it.
2.1.2 START/STOP SWITCH
To crank and start the engine, hold this switch in the START position. Release the switch when the engine starts. To stop an operating engine, press and hold the switch in the STOP position until the engine shuts off. The switch center position is the RUN position.
2.1.3 FUSE
The fuse protects the engine’s DC control circuit against electrical overload. If the fuse element has melted open due to overloading, the engine cannot be cranked. If you must replace the fuse, use only an identical replacement.
2.1.4 MAIN BREAKER
The main breaker protects the generator’s AC output circuit against overload and provides a method of turning OFF the generator’s 230-volt AC output to the vehicle circuits. These generators have either a 25 Amp, 2-Pole circuit breaker (PP50) or a 30 Amp 2-Pole circuit breaker (PP70).
2.2 OPTIONAL REMOTE
START/STOP PANEL
A remote mounted Start/Stop Panel (Figure 2.2) is available that allows you to start and stop the gener­ator engine conveniently from inside the vehicle. The remote panel includes a Start/Stop switch, hour meter, generator run lamp and a wire harness.
Figure 2.2 — Optional Remote Panel
(Models 004057 and 004184)
2.3 AUTOMATIC CHOKE
This engine is equipped with an automatic choke that consists of two main components: a choke solenoid and prechoke.
2.3.1 CHOKE SOLENOID
During engine cranking (Start/Stop switch at START), a solid-state choke module signals the choke solenoid to activate and cycle (choke on/choke off) until the engine starts. The choke solenoid thus opens and closes the carburetor choke valve only when the engine is cranking. When the engine starts, the choke stops cycling.
2.3.2 PRECHOKE
The choke system also has a temperature-sensitive metal strip that adjusts choke valve angle according to ambient temperatures (i.e., in cold ambient tem­peratures, choke valve closes more). Once the engine starts, an element heats the temperature-sensitive strip to a normal operating condition, opening the choke valve. This may take about three minutes in cooler weather.
8 Generac®Power Systems, Inc.
Section 2 – Operation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
2.4 BEFORE STARTING THE ENGINE
NOTE:
Instructions and information in this manual assume the generator has been properly installed, connected, serviced, tested and adjusted by a qualified installation technician or installation contractor.
2.4.1 INSTALLATION
Generator installation must have been properly com­pleted so it complies with all applicable codes, stan­dards and regulations and with the manufacturer's recommendations.
2.4.2 ENGINE LUBRICATION
Have the engine crankcase properly serviced with the recommended oil before starting. Refer to Section 1.6.3 (Page 6) and Sections 3.1 and 3.2 (Page 11) for oil ser­vicing procedures and recommendations.
Any attempt to crank or start the engine before you have properly serviced it with the recom­mended oil may result in an engine failure.
2.4.3 FUEL SUPPLY
The engine must have an adequate supply of proper fuel to operate. Before starting it, check that sufficient fuel is available.
NOTE:
Depending on the installation, the generator may have either a separate fuel tank, or it may “share” the vehicle engine’s fuel tank.
2.4.4 COOLING AND VENTILATING AIR
Air inlet and outlet openings in the generator com­partment must be open and unobstructed for contin­ued proper operation. Without sufficient cooling and ventilating airflow, the engine/generator quickly over­heats, which causes it to shut down and may damage the generator.
2.4.5 ENGINE EXHAUST GAS
Before starting the generator engine, you should be sure there is no way for exhaust gases to enter the vehicle interior and endanger people or animals. Close windows, doors and other openings in the vehi­cle that, if open, might permit exhaust gases to enter the vehicle.
The generator engine gives off DEADLY carbon monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient concen­trations, can cause unconsciousness or even death. Never operate the generator set with the vehicle inside any garage or other enclosed area. DO NOT OPERATE THE GENERATOR IF THE EXHAUST SYSTEM IS LEAKING OR HAS BEEN DAMAGED. SYMPTOMS OF CARBON MONOX­IDE POISONING ARE (a) inability to think coher­ently; (b) vomiting; (c) twitching muscles; (d) throbbing temples; (e) dizziness; (f) headaches; (g) weakness; and (h) sleepiness. IF YOU FEEL ANY OF THESE SYMPTOMS, MOVE INTO FRESH AIR IMMEDIATELY. IF SYMPTOMS PERSIST, GET MEDICAL HELP.
2.5 STARTING THE GENERATOR
To start the generator from either the generator con­trol panel or from the optional remote panel, proceed as follows:
1. Turn OFF electrical loads using the means pro-
vided in your vehicle (such as a main line circuit breaker or transfer switch).
NOTE:
If starting from the generator control panel, turn OFF loads by setting the generator’s main circuit breaker to the OFF (or open) position. If starting from a remote panel, turn OFF loads using the means provided in the vehicle (such as a main cir­cuit breaker). Electrical load circuits will be turned ON after the generator has started, stabi­lized and warmed up.
2. If you have not started the engine in more than
two weeks, press the Fuel Pump Primer switch and hold it for about five seconds to prime the fuel system. However, if the engine is warm, skip Step 2.
3. Hold the engine Start/Stop switch in the START
position to crank the engine. Release the switch when the engine starts.
If the engine does not start after it has been cranking for 15 seconds, release the Start/Stop switch and try again. Holding the switch for longer than 15 seconds can damage the starter motor.
4. Let the engine run at no-load for a few minutes to
stabilize and warm up.
5. Turn ON electrical loads using the means
provided (such as a main circuit breaker or transfer switch).
Generac®Power Systems, Inc. 9
Section 2 – Operation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
2.6 STOPPING THE GENERATOR
1. Turn OFF all electrical loads using the means provided (such as a main circuit breaker or transfer switch).
2. Let generator run at no-load for a few minutes, to stabilize internal engine generator temperatures.
3. Place the Start/Stop switch in its STOP position.
2.7 APPLYING LOADS TO GENERATOR
When applying electrical loads to the generator, observe these guidelines:
• Before applying electrical loads, let the generator
stabilize and warm up for a minute or two.
• DO NOT overload the generator.
2.7.1 LETTING THE ENGINE STABILIZE
The generator supplies correct rated voltage only at the proper governed speed. Some electrical appli­ances may be extremely sensitive to voltage. Incorrect voltages can damage such appliances.
If electrical loads are applied at reduced operating speeds, such loads imposed on the engine when suffi­cient power is not available may shorten engine life. Never turn ON electrical loads until after the generator engine has started and stabilized at no-load.
2.7.2 DO NOT OVERLOAD THE GENERATOR
You can read the rated wattage/amperage capacity of your generator on the generator data decal (see Section 1.1 on Page 4).
Applying electrical loads in excess of the unit’s rated capacity will cause the engine/generator to automati­cally shut down.
To avoid overloading, add up the wattage of all con­nected electrical lighting, appliance, tool and motor loads. This total should not be greater than the gen­erator’s rated wattage capacity.
• Most lighting, appliance, tool and motor loads indi-
cate their required watts on their nameplate or data plate. For light bulbs, simply note the wattage rating of the bulb.
• If a load does not show its rated wattage, multiply
that load’s rated VOLTS times AMPS to obtain WATTS.
• Induction type motors (such as those that run the
vehicle’s furnace fan, refrigerator, air conditioner, etc.) need about 2-1/2 times more watts of power for starting than for running (for a few seconds during motor starting). Be sure to allow for this when connecting electrical loads to the generator. First, figure the watts needed to start electric motors in the system. To that figure, add the run­ning wattages of other items that will be operated by the generator.
• Do not apply heavy electrical loads for the first two
or three hours of operation.
2.8 PROTECTION SYSTEMS
2.8.1 LOW OIL PRESSURE SWITCH
This switch (Figure 2.3) has normally open (N.O.) con­tacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below a preset level, switch contacts close, and the engine automatically shuts down. The unit should not be restarted until oil is added.
2.8.2 HIGH TEMPERATURE SWITCH
This switch (Figure 2.3), which has normally open (N.O.) contacts, is mounted near the oil filter. The contacts close if the temperature should exceed approximately 284º F (140º C), initiating an engine shutdown.
Figure 2.3 – Low Oil Pressure and
High Temperature Switches
2.8.3 FIELD BOOST
The Controller Circuit Board houses a field boost diode and resistor. These two components are part of a “field boost” circuit (Figure 2.4). During engine cranking only, a positive DC (battery) voltage is deliv­ered through the diode, resistor, brushes and slip rings, and the generator rotor. Application of this voltage to the rotor “flashes the field” whenever it is started. Flashing of the field each time the generator starts makes sure that a sufficiently strong magnetic field is available to produce “pickup” voltage in the stator windings.
10 Generac®Power Systems, Inc.
Section 2 – Operation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Figure 2.4 – Field Boost Circuit
2.8.4 OVERVOLTAGE PROTECTION
A solid-state voltage regulator (Figure 2.5) controls the generator’s AC output voltage. This regulator sup­plies an excitation current to the rotor. By regulating the rotor’s excitation current, the strength of its mag­netic field is regulated and, in turn, the voltage deliv­ered to connected electrical loads is controlled. When the AC frequency is 50 Hertz, voltage is regulated at 115 volts.
NOTE:
The solid state voltage regulator is only con­nected across 1/2 of the output winding.
Figure 2.5 – Solid State Voltage Regulator
The voltage regulator also incorporates a “voltage surge protection circuit.” This circuit prevents trou­blesome surges in the generator AC output voltage. Voltage surge is a common cause of damage to elec­tronic equipment.
2.9 ADDITIONAL INFORMATION
2.9.1 25-HOUR BREAK-IN PERIOD
The first 25 hours of operation is the break-in period for the generator. Properly breaking in the generator is essential to minimize fuel consumption and pro­vide maximum engine performance. During this 25­hour break-in period, follow this procedure:
• Run the unit at varying electrical loads to help seat the engine piston rings properly.
• Check the engine oil level frequently. Add oil if needed. It is normal for the generator engine to consume more oil than is normal until the piston rings have properly seated.
• For the 75-hour operation following the break-in period, avoid light electrical loads. Load the generator at 50 percent (or more) of its rated wattage capacity. Repeated light loads during these 75 hours can cause improper seating of engine pis­ton rings, resulting in blowby and high oil con­sumption.
• After operating the unit for 25 hours, complete the tasks recommended under Section 2.10.2.
2.9.2 25-HOUR CHECK-UP
After the 25-hour break-in period, contact a Generac Authorized Service Dealer for the following mainte­nance. The vehicle owner is responsible for any charges:
• Change the engine crankcase oil and oil filter.
• Inspect the cooling and ventilation openings.
• Check the engine ignition system.
• Inspect the entire electrical system.
• Inspect the engine exhaust system.
2.9.3 OPERATION IN HIGH GRASS OR BRUSH
Never operate the generator while the vehicle is parked over high grass, weeds, brush, leaves or any other combustible substance. Such materials can ignite and burn from the heat of the exhaust system. The generator exhaust system becomes extremely hot dur­ing operation and remains hot for a long time after it has shut down.
2A
Generac®Power Systems, Inc. 11
Section 3 – Maintenance
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
3.1 CHECKING THE ENGINE OIL LEVEL
For oil capacities and requirements, see “Engine Oil Requirements,” Section 1.6.2 (Page 6). Check the engine crankcase oil level at least every eight hours of operation, or before you use it. To check the engine oil level, proceed as follows (see Figure 3.1):
1. Be sure the generator is as level as possible.
2. Remove the dipstick and wipe it dry with a clean,
lint-free cloth.
3. Install and tighten the dipstick cap; then, remove
it again. The oil level should be at the dipstick “Full” mark.
4. If necessary, remove the oil fill cap on the rocker
cover and slowly add oil until it reaches the dip­stick “Full” mark. DO NOT FILL ABOVE THE “FULL” MARK.
Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.
5. Install and tighten the oil fill cap and the dipstick
before operating the engine.
3.2 CHANGING THE ENGINE OIL AND/OR OIL FILTER
• Change the engine oil after the first 25 hours of
operation (after the 25-hour break-in period, see Section 2.9.1, Page 10). Thereafter, change the oil every 100 operating hours. Change the oil more frequently if operating consistently under heavy load or at high ambient temperatures.
• Change the engine oil filter after the first 25 hours
of operation, and every 100 operating hours there­after.
To change the oil and/or oil filter, proceed as
follows:
1. Run the engine until it is thoroughly warmed up
(at least five minutes) then shut OFF the engine.
2. With the engine still warm from running, remove
the oil drain plug (Figure 3.1). Drain the oil into a suitable container.
3. After the oil has drained, replace the oil drain plug.
(If only changing the oil, go to step 7.)
4. With the oil drained, remove the old oil filter by
turning it counterclockwise (Figure 3.2).
5. Apply a light coating of clean engine oil to the gas-
ket of the new filter.
6. Screw the new filter on by hand until its gasket
lightly contacts the oil filter adapter. Then, tight­en the filter an additional 3/4 to one turn.
7. Remove the dipstick and fill crankcase with the proper type and amount of recommended oil (see Section 1.6.2, Page 6). The engine crankcase can hold about 1.4 liters. DO NOT FILL ABOVE THE “FULL” MARK.
8. Install and tighten the dipstick before operating the engine.
9. Start the engine and check for leaks.
NOTE:
Check the oil level and fill to the “FULL” mark after checking for leaks. The filter will retain some oil.
Figure 3.1 — Oil Dipstick/Fill Tube and
Location of Oil Drain Plug
Figure 3.2 — Engine Oil Filter
OIL DIPSTICK
OIL DRAIN PLUG
12 Generac®Power Systems, Inc.
Section 3 – Maintenance
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
3.3 MAINTAINING THE ENGINE AIR CLEANER
3.3.1 CLEANING THE FOAM PRECLEANER
Clean and re-oil the foam precleaner every three months or every 25 hours of operation, whichever occurs first. Service the foam precleaner more fre­quently if operating the generator in extremely dusty or dirty conditions. Use the following procedure (Figure 3.3):
1. Turn the knob counterclockwise to loosen.
2. Remove the cover, foam precleaner and paper filter.
3. Remove the foam precleaner from the cover.
4. Wash the foam precleaner in liquid detergent and
water.
5. Wrap the foam precleaner in a clean cloth and
gently squeeze it dry.
6. Saturate the foam precleaner in clean engine oil.
Gently squeeze it in a clean cloth to remove excess oil and to distribute oil (DO NOT TWIST).
7. Install the foam precleaner into the cover, fol-
lowed by the paper filter. Tabs at edges of paper filter must lock into slots on cover.
8. Install the cover, foam precleaner and paper filter.
9. Replace knob to retain the filter in place.
Figure 3.3 – Engine Air Cleaner
3.4 CLEAN AIR INTAKE SCREEN
Clean all foreign material from the air intake screen (Figure 3.4) at least once every 100 hours of opera­tion. Clean more often if necessary.
Inspect the area around the generator exhaust muf­fler periodically and remove all grass, leaves, dirt, etc., from this area.
Figure 3.4 – Cleaning Air Intake
3.5 CHECKING THE ENGINE SPARK PLUG
Clean the spark plug and reset the spark plug gap every 100 hours of operation.
1. Clean the area around the base of the spark plug
to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and com­mercial solvent. Do not blast the spark plug to clean.
2. Remove the spark plug and check the condition.
Replace the spark plug if worn or if reuse is ques­tionable.
3. Check the spark plug gap using a wire feeler
gauge. Adjust the gap to 0.030 inch (0.76 mm) by carefully bending the ground electrode (Figure 3.5).
Figure 3.5 – Setting the Spark Plug Gap
Sparking can occur if the wire terminal does not fit firmly on the spark plug terminal end. If necessary, re-form the wire terminal to obtain a tight fit.
PAPER FILTER
FOAM PRE-CLEANER
COVER
KNOB
Section 3 – Maintenance
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
3.6 FUEL FILTER (GASOLINE ONLY)
Remove and replace the fuel filter (Figure 3.6) once each year or every 100 hours of operation, whichever comes first.
Figure 3.6 – Fuel Filter
3.7 SPARK ARRESTOR MUFFLER
If the generator is not equipped with a spark arrestor exhaust muffler and is to be used on any forest cov­ered, brush covered or grass covered unimproved land, you may have to install a spark arrestor. The spark arrestor must be maintained in effective work­ing order by the vehicle owner/operator.
For assistance in ordering, installing and maintaining spark arrestor exhaust mufflers, contact your nearest Generac Authorized Service Dealer.
Exhaust mufflers supplied by Generac are spark arrestor types. Generac exhaust mufflers for recre­ational vehicle generators do not have a spark arrestor screen, but are of the more efficient “toroid” or “swirl” type. To remove carbon and combustion deposits from such mufflers, remove the plug from the muffler and run the engine for approximately 15 minutes. Shut down the engine, let the muffler cool and install the plug.
Be sure to reinstall the muffler plug tightly. Engine vibration could cause a loose plug to fall out. Without the plug in place, hot engine exhaust is directed out the opening. This hot exhaust, depending on the installation, could be directed to areas not able to withstand the extreme heat such as wooden floor boards or other flammable material. This could result in a fire.
3.8 CLEANING THE GENERATOR
Keep the generator set as clean and dry as possible. Protect the unit against excessive dust, dirt, corrosive vapors, road splash, etc. Permitting dirt and mois­ture to accumulate on generator windings will have an adverse effect on the insulation resistance of those windings.
When moisture is allowed to remain in contact with windings, some of the moisture will be retained in voids and cracks in the insulation. This causes a reduced insulation resistance and will eventually cause problems. Dirt will make the problem worse, since dirt tends to hold moisture in contact with windings. Salt (as from sea air) also will worsen the problem since it tends to absorb moisture from the air. Salt and moisture, when combined, form a good electrical conductor.
Do NOT use a forceful spray of water to clean the generator. Water will enter the generator interior and cause problems, and may also cont­aminate the generator fuel system.
3.9 BATTERY MAINTENANCE
All lead-acid batteries will discharge when not in use. The generator battery should be inspected as follows:
3.9.1 WEEKLY
• Inspect the battery posts and cables for tightness
and corrosion. Tighten and clean as necessary.
• Check the battery fluid level of unsealed batteries
and, if necessary, fill with Distilled Water Only. Do not use tap water in batteries.
3.9.2 EVERY SIX MONTHS
• Have the state of charge and condition checked.
This should be done with an automotive-type bat­tery hydrometer.
NOTE:
Servicing of the battery is to be performed or supervised by personnel knowledgeable of batter­ies and the required precautions. Keep unautho­rized personnel away from batteries.
Damage will result if the battery connections are made in reverse.
Generac®Power Systems, Inc. 13
TO FUEL PUMP
CUSTOMER FUEL CONNECTION
FUEL FILTER
14 Generac®Power Systems, Inc.
Do not dispose of the battery in a fire. The battery is capable of exploding. Storage batter­ies give off explosive hydrogen gas. This gas can form an explosive mixture around the bat­tery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks, or any spark producing tools or equipment near the battery. Discharge static electricity from your body before touch­ing the battery by first touching a grounded metal surface.
A battery presents a risk of electrical shock and high short circuit current. The following precautions are to be observed when working on batteries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the battery;
• Disconnect any charging source prior to connecting or disconnecting battery terminals; and
• Do not use any jumper cables or booster battery to crank and start the generator engine. If any battery has discharged, remove it for recharging.
Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) or water. The bicar­bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
3.10 MAJOR SERVICE MANUAL
To obtain a service manual for your generator, con­tact Generac or your nearest Generac Authorized Service Dealer. Make sure to identify your MODEL NUMBER and SERIES.
3.11 DRIVE BELT
The engine drives the generator rotor by means of a pulley and drive belt arrangement. The drive belt and pulleys are warranted for the life of the generator. Drive belt tension was properly adjusted before the unit was shipped from the factory. If you suspect that drive belt tension is incorrect, contact a Generac Authorized Service Dealer.
3.12 EXERCISING THE GENERATOR
Generac recommends that you start and operate the generator at least once every seven days. Let the unit run for at least 30 minutes to “exercise” the engine.
3.13 OUT OF SERVICE PROCEDURE
3.13.1 REMOVAL FROM SERVICE
If you cannot exercise the generator every seven days, and it is to be out of service longer than 30 days, pre­pare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line and allow the unit to shut down.
3. While the engine is still warm from running, drain the oil completely. Refill the crankcase with SAE 10W-30 oil having API classification “For Service SF.”
4. Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase.
5. Remove the spark plug and pour two or three tablespoons of clean, fresh engine oil into the spark plug threaded openings. Reinstall and tighten the spark plug.
6. Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or earthen floor.
7. Clean and wipe the entire generator.