The information contained in this publication is intended solely for the purposes indicated.
The present publication and any other documentation supplied with the UPS system is not to be
reproduced, either in part or in its entirety, without the prior written consent of GE’s Critical Power.
The illustrations and plans describing the equipment are intended as general reference only and are not
necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
Page 3
Critical Power
Modifications reserved
Page 3/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Dear Customer,
We thank you for selecting our products and are
pleased to count you amongst our very valued
customers at GE‟s Critical Power.
We trust that the use of the TLE Series 225 - 500
Uninterruptible Power Supply system, developed and
produced to the highest standards of quality, will give
you complete satisfaction.
Please read carefully the User Manual, which contains
all the necessary information and describes all you need
to know about the use of the UPS.
Thank you for choosing GE‟s Critical Power !
START-UP AND COMMISSIONING
A GE GLOBAL SERVICES FIELD ENGINEER must perform start-up and
commissioning of the UPS.
Please Contact GE. GLOBAL SERVICES at least two weeks prior to schedule
start-up and commissioning at 1-800-637-1738, or by E-mail at
Chicago, IL 60609
24/7 T: 800-637-1738
24/7 T: 773-299-6600
F: 866-765-3595
E: pqservice@ge.com
Page 4
Critical Power
Modifications reserved
Page 4/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Congratulations on your choice of a TLE Series Uninterruptible Power Supply (UPS).
It will help eliminate load disturbances due to unexpected power problem.
This manual describes how to prepare the installation site, and it provides weight and
dimensions and procedures for moving, installing and connecting the UPS.
Please refer to the User Manual, which describes the function of the UPS module, the
purpose and location of the switches, the meaning of the system events related to the
front panel indication, and provides procedures for starting and stopping the equipment.
While every care has been taken to ensure the completeness and accuracy of this manual,
GE„s Critical Power assumes no responsibility or liability for any losses or damages resulting
from the use of the information contained in this document.
WARNING!
TLE Series 225 – 250 – 400 - 500 is a product that needs to be installed by a licensed and
knowledgeable contractor.
We recommend that this manual be kept next to the UPS for future references.
If any problems are encountered with the procedures contained in this manual, please
contact your Service Center before you proceed.
This document shall not be copied or reproduced without the permission of GE„s Critical Power.
Some of the information contained in this manual may be changed without notice to
reflect technical improvements.
Safety instructions
Read the safety instructions contained on the following pages carefully before the
installation of the UPS, options and battery system.
Pay attention to the rectangular boxes included in the text:
They contain important information and warning concerning electrical connections and
personnel safety.
Parallel System version secured with RPA
When included in the text, this symbol refers to operation needed
only for RPA Parallel System.
Preface
Page 5
Critical Power
Modifications reserved
Page 5/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Table of content Page
1 IMPORTANT SAFETY INSTRUCTIONS................................................................................................................................................... 6
2.1 LAYOUT TLE SERIES 225 & 250 .................................................................................................................................................................................. 9
2.2 LAYOUT TLE SERIES 400 & 500 ............................................................................................................................................................................... 10
4.1 BLOCK DIAGRAM AND MAIN ELEMENTS ............................................................................................................................................................ 13
4.2.1 Normal VFI Operation Mode (Voltage Frequency Independent) ............................................................................................................................ 14
4.3 RPA PARALLEL SYSTEM OPERATION .................................................................................................................................................................... 17
4.3.1 Introduction to the RPA Parallel System ............................................................................................................................................................................. 17
4.3.2 Features of RPA Parallel System ............................................................................................................................................................................................. 18
4.3.3 System control................................................................................................................................................................................................................................. 18
4.4 SERVICE AND TECHNICAL SUPPORT .................................................................................................................................................................... 19
5 CONTROL PANEL ................................................................................................................................................................................. 21
5.1 CONTROL PANEL .......................................................................................................................................................................................................... 21
6.1 HOME SCREEN ............................................................................................................................................................................................................... 22
6.1.1 Description of the selection keys ........................................................................................................................................................................................... 23
6.1.2 Description of the signalling LEDs ......................................................................................................................................................................................... 24
6.3.1 Events (alarms and messages) ................................................................................................................................................................................................ 32
6.3.2 Alarms list .......................................................................................................................................................................................................................................... 32
6.3.3 Messages list .................................................................................................................................................................................................................................... 37
7.1 PROCEDURES FOR SINGLE TLE SERIES 225 - 500 .......................................................................................................................................... 52
7.1.1 Initial start-up of the TLE Series 225 - 500 ........................................................................................................................................................................ 52
7.1.2 UPS shut-down with load transfer on Manual Bypass Q2 ........................................................................................................................................ 56
7.1.3 From Manual Bypass Q2 to normal function VFI ........................................................................................................................................................... 58
7.1.5 Restore to normal operation after “System shutdown” ............................................................................................................................................. 60
7.1.6 Restore to normal operation after EPO (Emergency Power Off) ............................................................................................................................ 61
7.2 PROCEDURES SINGLE TLE SERIES 225 - 500 FUNCTIONING AS FREQUENCY CONVERTER ......................................................... 62
7.2.1 Initial Start-up of the TLE Series 225 - 500 as frequency converter ..................................................................................................................... 62
7.2.2 Complete shut-down of the TLE Series 225 - 500 as frequency converter ...................................................................................................... 66
7.2.3 Restore to normal operation after “System shutdown” ............................................................................................................................................. 67
7.2.4 Restore to normal operation after EPO (Emergency Power Off) ............................................................................................................................ 68
7.3 PROCEDURES FOR TLE SERIES 225 - 500 PARALLEL SYSTEM ................................................................................................................... 69
7.3.1 TLE Series 225 - 500 Parallel System start-up ................................................................................................................................................................. 69
7.3.2 Parallel UPS shut-down with load transfer on Manual Bypass Q2 ....................................................................................................................... 74
7.3.3 From Manual Bypass Q2 to normal function VFI ........................................................................................................................................................... 76
7.3.4 Separate a UPS unit from the Redundant Parallel System ....................................................................................................................................... 78
7.3.5 Reconnect a UPS unit to Redundant Parallel System .................................................................................................................................................. 80
7.3.6 Complete Parallel System shut-down ................................................................................................................................................................................. 82
7.3.7 Restore to normal operation after “System shutdown” ............................................................................................................................................. 83
7.3.8 Restore to normal operation after EPO (Emergency Power Off) ............................................................................................................................ 85
9.1.1 Service check ................................................................................................................................................................................................................................... 88
9.1.2 Fans and ventilation ..................................................................................................................................................................................................................... 88
9.1.3 Other components with limited lifetime ............................................................................................................................................................................. 88
9.1.5 UPS room conditions and temperature .............................................................................................................................................................................. 89
9.1.6 Preventive maintenance program ........................................................................................................................................................................................ 89
10.1 NOTES FORM .................................................................................................................................................................................................................. 90
Page 6
Critical Power
Modifications reserved
Page 6/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
GENERAL
- Move the UPS in an upright position in its original package to the final destination room.
To lift the cabinets, use a forklift or lifting belts with spreader bars.
- Check for sufficient floor and elevator loading capacity.
- Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS.
Contact the nearest Service Center immediately.
- WARNING! RISK OF ELECTRICAL SHOCK:
Do not remove covers, there are no user serviceable parts inside.
- After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltage
remains at the terminals of the electrolytic capacitors.
- All maintenance and service work should be performed by qualified service personnel.
The UPS contains its own energy source (battery).
- The field-wiring outlets may be electrically live, even when the UPS is disconnected from the utility.
- Dangerous voltages may be present during battery operation.
- The battery must be disconnected during maintenance or service work.
- This UPS contains potentially hazardous voltages.
- Be aware that the inverter can restart automatically after the utility voltage is restored.
- End user must follow applicable regional occupational safety codes/regulations during installation,
operation and equipment maintenance. This may require additional field marking or labeling defining
appropriate level of PPE (Personal Protection Equipment) to reduce the risk of Arc-flash related injuries.
Contact our Technical Support for product specific information.
INSTALLATION
- This UPS must be installed and connected only by trained personnel.
- Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
- After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are
correctly reattached.
- This UPS is intended for use in a controlled indoor environment free of conductive contaminants and
protected against animals intrusion.
- WARNING! HIGH EARTH LEAKAGE CURRENT:
Earth connection is essential before connecting to AC input!
- Switching OFF the unit does not isolate the UPS from the utility.
- Do not install the UPS in an excessively humid environment or near water.
- Avoid spilling liquids on or dropping any foreign object into the UPS.
- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104F
(40°C).
- Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25C).
- It is important that air can move freely around and through the unit. Do not block the air vents.
- Avoid locations in direct sunlight or near heat sources.
STORAGE
- Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (+55C).
- The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the range -
4°F (-20°C) to 104°F (40°C).
- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time
depending on storage temperature).
BATTERY
- The battery-voltage is dangerous for person’s safety.
- When replacing the battery, use the same cells number, voltage (V), capacity (Ah).
All the battery used, shall be of the same manufacturer and date of production.
- Proper disposal or recycling of the battery is required.
Refer to your local codes for disposal requirements.
- Never dispose of battery in a fire: they may explode.
- Do not open or mutilate battery: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
- Avoid charging in a sealed container.
- Never short-circuit the batteries.
When working with batteries, remove watches, rings or other metal objects, and only use insulated tools.
- In case of air shipment, the cables +/- going to the battery fuses/terminals shall be disconnected and isolated.
1 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for models TLE Series 225 - 500 that should be followed
during installation and maintenance of the UPS and battery.
Page 7
Critical Power
Modifications reserved
Page 7/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE UPS BY
QUALIFIED SERVICE PERSONNEL ONLY.
INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION BEFORE HANDLING
THE UPS AND BATTERY.
DANGER!
Full voltage and current are always present at the battery terminals.
The battery used in this system can provide dangerous voltages, extremely high currents and a
risk of electric shock.
If the terminals are shorted together or to ground they may cause severe injury.
You must be extremely careful to avoid electric shock and burns caused by contacting battery
terminals or shorting terminals during battery installation.
Do not touch uninsulated battery terminals.
A qualified service person, who is familiar with battery systems and required precautions, must
install and service the battery.
The installation must conform to national and local codes.
Keep unauthorized personnel away from the battery.
The qualified service person must take these precautions:
1 Wear protective clothing, such as rubber gloves and boots and protective eye wear
Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated.
Remove rings and metal wristwatches or other metal objects and jewelry.
Do not carry metal objects in your pockets where the objects can fall into the battery
cabinet.
2 Tools must have insulated handles and must be insulated so that they will not short battery
terminals.
Do not allow a tool to short between individual or separate battery terminals or to the
cabinet or rack.
Do not lay tools or metal parts on top of the battery, and do not lay them where they could
fall onto the battery or into the cabinet.
3 Install the battery as shown on the drawing provided with the battery.
When connecting cables, never allow a cable to short across a battery’s terminals, the
string of battery, or to the cabinet or rack.
4 Align the cables on the battery terminals so that the cable lug will not contact any part of
the cabinet or rack, even if the battery is moved.
Keep the cable away from any sharp metal edges.
5 Install the battery cables in such a way that the UPS or battery cabinet doors cannot pinch them.
6 Do not connect the battery terminal to Ground.
If any battery terminal is inadvertently grounded, remove the source of the ground.
Contacting any part of a grounded battery can cause a risk of electric shock.
7 To reduce the risk of fire or electric shock, install the battery in a temperature and humidity
controlled indoor area, free of contaminants.
8 Battery system chassis ground (earth) must be connected to the UPS chassis ground (earth).
If you use conduits, this ground conductor must be routed in the same conduit as the
battery conductors.
9 Where conductors may be exposed to physical damage, protect the conductors in
accordance with all applicable codes.
10 If you are replacing the battery or repairing battery connections, shut OFF the UPS and
remove the battery fuses.
Safety instructions when working with battery
Page 8
Critical Power
Modifications reserved
Page 8/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
WARNING, if instruction is not followed injury or serious equipment damage may
occur!
CAUTION, internal parts have dangerous voltage present.
Risk of electric shock!
PE (Earth) – GND (Ground)
PROTECTIVE GROUNDING TERMINAL:
A terminal which must be connected to earth ground prior to making any other
connection to the equipment.
A terminal to which or from which an alternating (sine wave) current or voltage
may be applied or supplied.
A terminal to which or from which a direct current or voltage may be applied or
supplied.
This symbol indicated the word “phase”.
This symbol indicates the principal on/off switch in the on position.
This symbol indicates the principal on/off switch in the off position.
Safety symbols and warnings
Safety warnings
The text of this manual contains some warnings to avoid risk to the persons and to avoid damages to
the UPS system and the supplied critical loads.
The non-observance of the warnings reminding hazardous situations could result in human injury and
equipment damages.
Please pay attention to the meaning of the following warnings and symbols.
Throughout this manual the following symbols are defined:
Page 9
Critical Power
Modifications reserved
Page 9/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Fig. 2.1-1 TLE Series 225 & 250 - General view
Fig. 2.1-3 Control Panel
Fig. 2.1-4 Manual switches Q1 & Q2
Fig. 2.1-2 TLE Series 225 & 250 - General view with open doors
Q1 UPS output switch
Q2 Manual Bypass switch
TLES_UL_225-250_S1_UPS_GE_02
Q1
I ON
0 OFF
TLES_UL_225-250_S1_Switch Q1-Q2_01
Q2
I ON
0 OFF
TLES_UL_225-250_S1_UPS_GE_03
Q1
I ON
0 OFF
Q2
I ON
0 OFF
12
EPO
EPO
-
+
2 LAYOUT
2.1 LAYOUT TLE SERIES 225 & 250
Page 10
Critical Power
Modifications reserved
Page 10/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Fig. 2.2-1 TLE Series 400 & 500 - General view
Fig. 2.2-3 Control Panel
Fig. 2.2-4 Manual switches Q1 & Q2
Fig. 2.2-2 TLE Series 400 & 500 - General view with open doors
Q1 UPS output switch
Q2 Manual Bypass switch
TLES_UL_400-500_S1_UPS_GE_02
TLES_UL_400-500_S1_Switch Q1-Q2_01
Q1
I ON
0 OFF
Q2
I ON
0 OFF
TLES_UL_400-500_S1_UPS_GE_03
Q1
12
I ON
0 OFF
Q2
I ON
0 OFF
EPO
EPO
-
+
2.2 LAYOUT TLE SERIES 400 & 500
Page 11
Critical Power
Modifications reserved
Page 11/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
TLE Series 225 - 500 is a truly VFI double conversion Uninterruptible Power Supply
(UPS), equipped with automatic bypass, where the load is normally supplied by the
inverter.
TLE Series 225 - 500 can be configured, if chosen, for the eBoost™ Operation Mode
(Option - High efficiency: up to 99% / Fast power transfer: <2ms) permitting
maximum energy saving.
If the Inverter is not able to supply the required Output Voltage, or when overload or
short-circuit on the output occur, the Load is instantly transferred to the Mains via
the Automatic Bypass.
The UPS automatically returns to normal mode when the failure condition is
restored.
3 INTRODUCTION
The TLE Series 225 - 500 Uninterruptible Power Supply (UPS) provides the energy supply for critical
loads which need a reliable, continuous free from voltage disturbances and frequency fluctuations
supply.
In case the power provided by the Mains Fails, or exceeds the permitted tolerances, the power to supply
the Load is provided by the Battery for the specified time at the rated Load (or longer at a reduced Load)
or until the Mains power returns.
KEY FEATURES:
More Critical equipment supported
Rated at 1 Power Factor, TLE Series 225 - 500 delivers more real power than other UPS in the market.
With today’s trend toward power factor corrected loads, TLE Series 225 - 500 can support more total
Load than any other UPS available, allowing you to support a greater number of today’s enterprise computing Power Factor Corrected (PFC) equipment.
High Efficiency
Thanks to type Advanced Neutral Point Clamped three levelIGBT technology, TLE Series 225 - 500
guarantees a high overall performance.
Intelligent Energy Management(IEM) combined with RPA, results in the most cost efficient and reliable
UPS solution in the industry.
Fully digital
Digital Signal Processor (DSP), Flash memory and Advanced Neutral Point Clamped are the technology
corner stones of a new age of power quality and power reliability.
RPA™ - Redundant Parallel Architecture™ Parallel System
GE’s Critical Power provides a unique technology called Redundant Parallel Architecture™ (RPA™) that
can parallel Uninterruptible Power Supply (UPS) modules with true redundancy.
With RPA™, there is no need for external electronics or switches to control the UPS modules in the
parallel system.
One of the UPS modules in the system arbitrarily takes a leadership role, while the other UPS modules
have access to all control parameters.
If one UPS fails to operate, the load is automatically redistributed among the others.
If the lead UPS fails to operate then a different UPS automatically takes on the leadership role.
The RPA™ systems are designed to have no single points of failure, ensuring the highest level of power
protection for critical loads.
Extremely flexible
Tailor made power protection to meet your individual installation requirements; TLE Series 225 - 500
offers various options like EMC filter and our comprehensive software for mission control and data
protection to cover all your application needs.
Page 12
Critical Power
Modifications reserved
Page 12/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
TLE Series 225 - 500 is one of the best
performing and most reliable three-phase UPS
systems providing critical power protection for
a wide range of applications.
Every TLE Series 225 - 500 system operates in VFI mode (Voltage Frequency Independent)
yielding the maximum levels of power reliability
for all mission-critical processes.
NOTE !
Through their complete life cycle, all GE‟s Critical Power UPS systems are fully
supported by service teams which provide world-class, 24x7 preventive and
corrective services, training and application expertise.
TLES_UL_225-250_S1_UPS_GE_01
TLE Series 225 & 250
TLE Series 400 & 500
4 DESCRIPTION
With proven technology the TLE Series 225 - 500 UPS provides top class reliability and performance.
With backfeed protection and compliance to EMC standards the TLE Series 225 - 500 complies to current
standards.
Reliability can be further increased by paralleling up to six UPS units utilising GE’s unique RPA™ technology (Redundant Parallel Architecture).
With RPA every UPS is controlled in a true peer-to-peer configuration with redundancy in all critical
elements and functions, eliminating all single points of failure.
The decentralized bypass offers great flexibility to up or down grade the system in case future needs
might change.
TLE Series 225 - 500, BEST IN CLASS EFFICIENCY
High efficiency in double conversion mode up to 96.5% and eBoost™ operation mode up to 99%.
High efficiency at partial and reduced loads for cost benefits in operating conditions.
TLE Series 225 - 500 products designed in compliance with UL 1779 standard, C3 level for immunity,
i.e. can withstand possible disturbances and noise without affecting standard operating conditions.
Advanced User Interface with touch screen display guided menu.
Reduced energy consumption costs.
Reduced size and costs of the air conditioning system.
Compact design, saving installation space.
Page 13
Critical Power
Modifications reserved
Page 13/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Fig. 4.1-1 Block Diagram TLE Series 225 - 500
4.1 BLOCK DIAGRAM AND MAIN ELEMENTS
The TLE Series 225 - 500 system can be divided into the following main elements:
Control System
TLE Series 225 - 500 is designed with microprocessor-controlled signal processing circuits.
The interface between the operator and the unit is provided by the monitoring system on the front
panel.
This monitoring system consists of an active mimic diagram, a keyboard and a backlit display.
Rectifier
The Active IGBT Rectifier converts the 3-phase utility voltage into a controlled and regulated DC-voltage,
supplying the inverter and to charge the battery through the battery-charger.
Thanks to modulation strategy applied to IGBT Bridge, the rectifier provides clean input power in terms
of low THDi and unity power factor.
Inverter
The Inverter converts the DC voltage into a three-phase AC-voltage with constant amplitude and
frequency, which is completely independent and isolated from the AC-input voltage.
Automatic Bypass
The Automatic Bypass consists of a static semiconductor-switch (SSM: Static Switch Module), used to
provide an uninterrupted transfer of the Load from Inverter to Utility.
Back-feed Protection
All TLE Series 225 - 500 UPS's are equipped with an automatic system for the protection against voltage
back feeding towards Utility, through the Bypass (UL 1778 and CSA C22.2 no. 107.3).
This protection works automatically by opening contactor K6 (in series with the thyristors of the static
switch) and eventually K7, and acts in case of internal defects of the system, or due to wrong
manipulations on the Manual Bypass Q2.
Manual Bypass
The Manual Bypass consists of a pair of manual switches (Q1 and Q2), which removes the UPS from the
Load for maintenance, while still supplying the Load with power directly from the Utility.
Battery
The Battery supplies the DC power to the Inverter when the Utility is out of acceptable tolerances.
Page 14
Critical Power
Modifications reserved
Page 14/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Under normal conditions the Load is
permanently powered by the inverter with
constant amplitude and frequency.
The Rectifier, powered by the Utility, supplies
the inverter and the battery-charger keeps the
battery fully charged.
The inverter converts the DC voltage in a new
AC sine wave voltage with constant amplitude
and frequency independently from the input
Utility Power.
Fig. 4.2.1-1 Block diagram normal VFI operation mode
eBoost™
e High efficiency (up to 99%)
Boost Fast power transfer (< 2ms)
When the eBoost™ Operation Mode is
selected, and the Utility Power is available,
the Load is normally powered through the
Automatic Bypass.
When the Utility Voltage is detected out of the
prescribed tolerances, the Loadis
automatically transferred to the Inverter.
When the Utility recovers, the Load returns to
the Automatic Bypass after a variable time
defined by the control unit.
Fig. 4.2.2-1 Block diagram eBoost™ Operation Mode
The eBoost™ Operation Mode can be used for single units or the RPA Parallel System, for up to 6 UPS
modules, with all units individually able to supply power through a redundant communication bus.
The eBoost™ Operation Mode can be configured directly by the user for higher efficiency, considering
the Utility reliability and criticality of the Load.
The selection between the two operation modes “VFI mode and eBoost™ Operation Mode”, or switching
between operation modes at required time, can be done through the UPS control panel (see Section 6.4 / eBoost).
NOTE !
The eBoost™ Operation Mode is available only if enabled at the factory or by a GE GLOBAL SERVICES FIELD ENGINEER.
4.2 OPERATION MODES
4.2.1 Normal VFI Operation Mode (Voltage Frequency Independent)
4.2.2 eBoost™ Operation Mode (option)
Page 15
Critical Power
Modifications reserved
Page 15/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
When the Utility is no longer within acceptable tolerances,
the Battery will provide the DC power to the Inverter.
The Inverter will maintain continuous AC power to the
Load until the Battery Voltage reaches the lower limit of
the Inverter operation capability.
During the discharge, the LCD screen shows the estimated
time the Battery can support the critical Load.
Prior to complete Battery discharge, the "stop operation"
alarm (shut-down imminent) warns the operator that the
Battery is almost discharged and the UPS is about to shut
down.
With a Parallel System for power capacity (see Section 4.3)
With the Bypass Utility power available,a “Battery low” warning on any unit will cause the Load
to be transferred to Utility (after a selectable time delay).
With Bypass Utility power not available, a “Battery low” warning on any unit will start the “stop
operation” timer (adjustable).
The Load will shut down at the end of the “stop operation” time period.
With a Parallel System for redundancy (see Section 4.3)
When a Battery low warning occurs on a unit not necessary to support the present Load, this unit
will shut down after a timeout period (selectable).
The Load is shared between the other units.
As the warning occurs on one unit necessary to support the present Load, the system starts the
"stop operation" timeout (selectable).
The Load will shut down at the end of the “stop operation” time period.
As soon as the AC input power recovers, the Rectifier will
start automatically, supplying DC power to the Inverter
and recharging the Battery.
If the Inverter was previously shut down due to low
Battery, the Load will be initially powered by Utility
through the Automatic Bypass.
When the Battery is sufficiently recharged to ensure a
minimum time of operation with the present Load, the Inverter will start automatically and the Load will be
transferred back to the Inverter.
When the AC input power recovers, the Rectifiers will start-up sequentially, according to their
number in the Parallel System. This minimizes the initial inrush current.
The Inverters will start-up automatically, but only when the Battery has been sufficiently recharged
for a minimum runtime with the present Load.
When enough Inverters to supply the Load have been restarted, the Load will be transferred from
the Automatic Bypass back to the Inverter output.
4.2.3 Utility Failure Operation
4.2.4 Utility Recovery Operation
Page 16
Critical Power
Modifications reserved
Page 16/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
In normal operation, the Load is supplied by the
Inverter.
When the control system detects a fault in the
Inverter, an overload condition or a short-circuit
condition, the Automatic Bypass will transfer the
critical Load to the Utility without interruption.
When the Inverter recovers, or the overload or
short-circuit condition is corrected, the Load will
be automatically transferred back to the Inverter.
Fig. 4.2.5-1 Block diagram Automatic Bypass
If the UPS is unable to return to normal mode following an automatic transfer to Bypass mode, an
alarm condition will be initiated.
A Manual Bypass (operator initiated) will not be considered as an alarm condition.
In case of RPA Parallel System
Each unit has its own internal Bypass.
These units are continuously exchanging information, enabling all of the internal Bypass circuits in a
Parallel System to operate simultaneously.
If the Inverter of a unit fails, its Bypass circuit remains available to the Parallel System.
It is excluded only if the unit is separated from the common bus by opening its output switch Q1.
The Manual Bypass circuit consists of manual
switches Q1 and Q2, which permits transfer of
the Load directly to the unconditioned AC power
without interruption, leaving the UPS available
for maintenance.
Fig. 4.2.6-1 Block diagram Manual Bypass
4.2.5 Automatic Bypass
4.2.6 Manual Bypass
Page 17
Critical Power
Modifications reserved
Page 17/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Fig. 4.3.1-1 Block diagram RPA Parallel System operation
4.3 RPA PARALLEL SYSTEM OPERATION
4.3.1 Introduction to the RPA Parallel System
Two or more equal power units can be paralleled to increase the output power (paralleling for capacity)
or to improve the overall reliability of an UPS system (paralleling for redundancy).
The outputs of parallel units are connected to a common power bus, and in normal operation the units
connected on the parallel bus share the Load equally.
The modular concept of TLE Series allows parallel operation of up to 6 units, without using paralleling
switchgear, external bypass circuits or common control circuitry (see Fig. 4.3.1-1).
Parallel units for power capacity
Several units can be paralleled in order to achieve output power greater than the maximum power of a
single unit.
The maximum total power shared between the paralleled units is equal to the total installed nominal power.
In the event of a failure of one unit, the power supplied by the UPS system becomes insufficient and the
Load will be transferred to the Utility Bypass source.
Parallel units for redundancy
The nominal power rating of the n out of n+1 redundant paralleled modules must be equal to or higher
than the required Load power.
The Load will be equally shared by the n+1 units connected on the output bus.
Should one of the n+1 paralleled units trip Off-line, the remaining (n) modules will supply the Load,
maintaining conditioned power to the critical Load.
From this results higher reliability and security for the Load plus a higher MTBF (Mean Time Between
Failures).
Page 18
Critical Power
Modifications reserved
Page 18/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
It is strongly recommended that no transformers, automatic circuit breakers or
fuses should be installed between the units output and the Load common bus bars.
However, it is recommended that a disconnection or isolation switch is installed in
order to totally isolate a unit if needed.
4.3.2 Features of RPA Parallel System
The TLE Series 225 - 500 Parallel System is designed to provide a complete Redundant Parallel
Architecture, and is free from common equipment.
Not only the Inverters but also the Bypass functions are redundant.
When one UPS needs maintenance or service, the Load is powered by the other units.
The redundant communication bus to which all units are connected keeps each unit informed about the
status of all the other units.
The control panel located on each unit allows controlling and monitoring the status of this unit.
4.3.3 System control
A high-speed redundant, serial communication bus, guarantees the exchange of data and thus the
communication between the CPU's of each unit.
Each module controls is own function and operational status and communicates with all other modules,
in order to act or react if necessary, adapting to the new conditions.
4.3.4 Synchronization
All units are identical, but one unit is arbitrarily selected as the reference and all the other units
synchronize to this unit, which in turn synchronizes to the Utility Bypass voltage, as long as the latter is
within tolerances.
In case of reference failure, another unit in the Parallel System is automatically chosen to take over the
reference role.
The Bypass Input for all the units of the Parallel System must be supplied from the same AC source (no
phase shift allowed between them).
4.3.5 Load sharing
On each unit of the Parallel System, Inverter Output Voltage and Current are measured and applied to a
Load sharing bus.
An eventual difference between the units is therefore automatically equalized.
Page 19
Critical Power
Modifications reserved
Page 19/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
For any request of technical support please
contact your local Service Center.
Stamp of your local Service Center (see page 3)
Fig. 4.4-1 Identification label
The requested data permitting
to identify your UPS are marked
on the identification label fixed
on the front of the cabinet,
behind the lower front door.
For fast and efficient technical
support please mention the data
marked on the identification
label.
NOTE !
This warranty does not cover failures of the product which result from incorrect
installation, misuse, alterations by persons other than authorized agents, or
abnormal working conditions.
TLES_UL_225-500_S1_Label identification_01
Q1
12
I ON
0 OFF
Q2
I ON
0 OFF
-
+
Q1
I ON
0 OFF
Q2
I ON
0 OFF
12
-
+
kVAOutput Powerat Pow. factor
Output Freq.Hz
Output VoltageVAC: 3W + N + PE
Output CurrentA
lag.SeriesProduct. Year
Input Freq.Hz
Input VoltageVAC: 3W + N + PE
Input CurrentA
Serial Nr.
Model
g
GE Digital Energy
6595 RIAZZINO (CH)
MADE IN SWITZERLAND
4.4 SERVICE AND TECHNICAL SUPPORT
4.5 WARRANTY
GE’s Critical Power, operating through its authorised agents, warrants that the standard products will be
free of defects in materials and workmanship for a period as per contract specifications.
Page 20
Critical Power
Modifications reserved
Page 20/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
This product has been designed to respect the
environment, using materials and components respecting
eco-design rules.
It does not contain CFCs (Carbon Fluor Clorid) or HCFCs
(Halogen Carbon Fluor Clorid).
PACKING MATERIAL RECYCLING
GE„s Critical Power, in compliance with environment
protection, uses only environmentally friendly material.
UPS packing materials must be recycled in compliance with
all applicable regulations.
RECYCLING AT THE END OF SERVICE LIFE !
GE‟s Critical Power, in compliance with environment
protection recommends to the User that the UPS
equipment, at the end of its service life, must be
recovered conforming to the local applicable regulations.
WARNING !
Leads contained in the batteries is a dangerous substance
for the environment, therefore it must be correctly
recycled by specialized companies!
4.6 RECYCLING INSTRUCTIONS
Page 21
Critical Power
Modifications reserved
Page 21/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Fig. 5.1-1 Control Panel
5 CONTROL PANEL
5.1 CONTROL PANEL
The Control Panel, positioned on the UPS front door, acts as the UPS user interface.
Main features:
LCD Touch screen color graphic display. See Chapter 6.
Multilanguage communication interface:
automatically sets the “ENGLISH” language on the LCD
screen.
6 LCD SCREEN
Composed of an LCD color “Touch Screen” which provides the following information to users:
Synoptic diagram indicating UPS status.
UPS operating, AC and DC metering information.
History of events (alarms and messages).
Functionality can be programmed to meet customer needs by changing parameters.
Operation commands of the UPS.
6.1 HOME SCREEN
The LCD screen, after 5 minutes of inactivity, shuts down the backlight.
To reactivate it, it is sufficient to press any keys mentioned to Section 6.1.1.
If the keypad remains inactive for 5 minutes or longer, during the viewing of a screen such as
MEASURES, EVENTS, SETUP or COMMANDS, the LCD screen returns automatically to the main screen.
Page 23
Critical Power
Modifications reserved
Page 23/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Fig. 6.1.1-1 LCD screen
MEASURES
Shows electric parameters values and statistics of use.
See Section 6.2.
EVENTS
Shows in chronological order, all the events occurred (alarms,
messages, commands, handling, etc.).
See Section 6.3.
SETUP
Allows the user to customize some UPS functions to specific
requirements and to view UPS identification data.
See Section 6.4.
COMMANDS
Allows the user to execute UPS operation commands.
See Section 6.5.
RPA
Parallel
System
Shows the status of operation of the RPA Parallel System.
See Section 6.6.
MUTE
Key to reset general alarm and buzzer.
6.1.1 Description of the selection keys
Page 24
Critical Power
Modifications reserved
Page 24/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Fig. 6.1.2-1 LCD screen
UPS model
Date (format “DD.MM.YYYY”).
Time (format “HH.MM.SS”).
eBoost (green color)
LED ON/lit indicates that the UPS is operating in eBoost™ mode.
Service Key (yellow color)
Key for disabling the Service Key procedure.
Used only by the Service Center
LEDS UPS STATUS
LED LOAD PROTECTED (green color)
When lit, indicates that the UPS is functioning correctly and the Load is system protected (Load
supplied either from inverter or from Automatic Bypass in case of eBoost™ Operation Mode).
When blinking, indicates that a regular maintenance service is needed (SERVICE REQUIRED).
May be reset by a SERVICE TECHNICIAN only.
See Section 9 – Maintenance – Service check.
The LED is OFF when the output switch Q1 is open, indicating that the Inverter is in service mode, not
supplying the Load.
6.1.2 Description of the signalling LEDs
Page 25
Critical Power
Modifications reserved
Page 25/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
LED ALARM (yellow color)
It blinks when one or more alarm is activated. The internal Buzzer is ON.
The LED remains blinking (with the alarm condition still present) and the buzzer stops when the key
“MUTE” is pressed.
The LED ALARM is also lighted when the Load is not protected by UPS or in case Q1 is open.
LED STOP OPERATION (red color)
It warns about the imminent inverter stop (default parameter = 3 min.) and the consequent Load shutdown as result of:
The battery is fully discharged and the Load cannot be transferred on Utility.
Overtemperature or overload condition (>125%) and the Load cannot be transferred on Utility.
Bypass
Data regarding Bypass.
See Section 6.2.
Rectifier
Data regarding Rectifier.
See Section 6.2.
Load output
Data regarding Load.
See Section 6.2.
Battery
Data regarding Battery.
See Section 6.2.
Green color: indicates battery charged.
Yellow color: indicates STOP OPERATION status.
Red color: indicates low battery.
LEDs on Synoptic Diagram
LED 1 Rectifier
LED 2 Inverter
LED 3 Booster/Battery charger
LED 4 Automatic Bypass
LED 5 LOAD
Examples of typical scenarios in the Synoptic Diagram:
Load supplied by Inverter
Load supplied by Automatic Bypass
Load supplied by Manual Bypass Q2
Load supplied by Battery
Page 26
Critical Power
Modifications reserved
Page 26/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
MEASURES
The MEASURES mode is entered any time the
“MEASURES” key is pressed.
The LCD screen will indicate a series of
screenshots showing the measures of all
electric parameters like AC, DC and various
statistics.
Return to HOME screen.
Shows the main screen EVENTS.
See Section 6.3.
Shows the main screen SETUP.
See Section 6.4.
Shows the main screen COMMANDS.
See Section 6.5.
Shows the operating status of the RPA PARALLEL SYSTEM.
See Section 6.6.
Key to reset general alarm and buzzer.
Shows the screen Battery.
Shows the screen Rectifier.
Shows the screen Bypass.
Shows the screen Inverter.
Shows the screen Load.
Shows the screen Booster.
6.2 MEASURES
In this mode the keys perform the following functions:
Page 27
Critical Power
Modifications reserved
Page 27/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
BATTERY SCREEN
Voltage
The battery voltage.
Current
The battery current (negative values
correspond to the discharge of the
battery).
Temperature
The temperature of the battery (“XXX”
indicates sensor disabled).
Autonomy
The estimated backup time with the present Load.
Charge level
The battery charge level.
On battery time
Total operating time of the UPS on battery (in hours).
BATTERY DISCHARGE COUNTER / Residual Charge Level
The number of discharges combined with the percentage of the available residual battery capacity at
the time utility power is restored.
Battery charger status
Battery charge status(Off / Float / Boost).
RECTIFIER SCREEN
Frequency
The input frequency of the Rectifier.
Voltage L1 / Voltage L2 / Voltage L3
3-phase Utility voltage PHASE /NEUTRAL.
Voltage DC-link 1
DC-Link 1 voltage.
Voltage DC-link 2
DC-Link 2 voltage.
Main failure count
Total number of times a gap of utility in the Rectifier has been reordered.
Temperature
Rectifier inlet L1 Coil temperature (Normal / Alarm).
Temperature 1
Temperature of the Rectifier bridge.
Page 28
Critical Power
Modifications reserved
Page 28/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
BYPASS SCREEN
Frequency
The frequency of the input Utility.
Voltage L1 / Voltage L2 / Voltage L3
3-phase Utility voltage PHASE
/NEUTRAL.
Current L1 / Current L2 / Current L3
Input Utility current for the 3-phases.
Main failure count
The total number of minor Utility faults (Bypass Utility out of tolerance faults).
Number of fast transients
The number of fast transients occurred on the bypass utility on the last seven days.
Bypass quality index
The statistic evaluation in % (100= good; 0= bad) of the Bypass utility.
Status
Bypass status: free / blocked.
INVERTER SCREEN
Frequency
The output frequency of the Inverter.
Voltage L1 / Voltage L2 / Voltage L3
3-phase output voltage
PHASE/NEUTRAL.
Status
The synchronization status of the
Inverter with respect to Utility:
- Synchronized.
- Not synchronized.
Temperature
“XXX” indicates disabled function.
Temperature 1
The temperature of the Inverter bridge.
Page 29
Critical Power
Modifications reserved
Page 29/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
LOAD SCREEN
Voltage L1 / L2 / L3
Output voltage PHASE/NEUTRAL for
each phase.
Current L1 / L2 / L3
The output current as RMS values for
each phase.
Percent load L1 / L2 / L3
The output Load as percentage for each
phase.
Active power
Load active power (kW) for each phase.
Apparent power
Load apparent power (kVA) for each phase.
Power factor
Load power factor: + inductive load / - capacitive load
Status
Source of the power supplied to the Load.
Inverter operating time
Total operating time for the Inverter (in hours).
Apparent power
Total apparent Load power (kVA).
UPS operation time
Total operating time for the UPS (in hours).
Active Power
Total effective Load power (kW).
eBoost operation time
Total operating time for the UPS in eBoost™ Operation Mode (in hours).
This counter is displayed only when eBoost™ Operation Mode is available
(option).
Overload counter
Total number of detected output overloads.
IEMi operation time
Total operating time for the UPS in IEMi Operation Mode (in hours).
This counter is displayed only when IEMi Operation Mode is available (option).
BOOSTER SCREEN
Battery voltage
The battery voltage.
Battery current
The battery current (negative values
correspond to the discharge of the
battery).
Voltage DC-link 1
DC-link 1 voltage.
Voltage DC-link 2
DC-link 2 voltage.
Status
Booster status (Off / Booster / Charger).
Temperature
Temperature of the 4th leg’s bridge.
Temperature 1
Booster temperature.
Page 30
Critical Power
Modifications reserved
Page 30/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
EVENTS
The EVENTS mode is entered any time the
“EVENTS” key is pressed.
The LCD will display a series of screens
corresponding to the last 511 events (User
Log).
Shows the main screen MEASURES.
See Section 6.2.
Return to HOME screen.
Shows the main screen SETUP.
See Section 6.4.
Shows the main screen COMMANDS.
See Section 6.5.
Shows the operating status of the RPA PARALLEL SYSTEM.
See Section 6.6.
Key to reset general alarm and buzzer.
Shows the screen User Events.
Shows the screen Service Events. Reserved for the Service Center.
Shows the previous 50 events.
Shows the previous 5 events.
Shows the next 5 events.
Shows the next 50 events.
6.3 EVENTS
In this mode the keys perform the following functions:
Page 31
Critical Power
Modifications reserved
Page 31/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
SCREEN ACTIVE ALARMS
Shows active events with their GE
standard code and a text describing the
event in the selected language.
SCREEN USER LOG
User Log
Chronologically view 5 events per
screenshot.
Event characteristic:
- Number chronologically assigned to
an event (Nr. 511 is the more recent,
Nr. 1 is the first).
- Data (MM/DD/YYYY).
- Exact hour of the moment when the
event occurred (HH/MM/SS/
thousandth).
- Number of standard GE code of the
event.
- Explicit text describing the event in
the selected language.
SCREEN SERVICE LOG
Service Log
Chronologically view 5 events per
screenshot with service related info.
Event characteristic:
- Number chronologically assigned to
an event (Nr. 1022 is the more
recent, Nr. 1 is the first).
- Data (MM/DD /YYYY).
- Exact hour of the moment when the
event occurred (HH/MM/SS/
thousandth).
- Number of standard GE code of the
event.
Page 32
Critical Power
Modifications reserved
Page 32/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Code
Alarm
Description
4000
SETUP VALUES LOST
Parameters are lost and have been replaced with
default values.
Please call nearest Service Center for intervention.
4001
REGULATION BOARD FAILURE
A blocked DSP on the Control board causes this
alarm, and consequently the shut-down of Rectifier
and inverter and the opening of K3.
4004
UPS FAILURE ON PARALLEL SYSTEM
The master unit detected the slave unit missing on
the communication bus even though switch Q1 is
still closed.
4006
BUS JA CRC FAILURE
The parallel communication bus system is subject
to high errors rate on channel JA.
4007
BUS JB CRC FAILURE
The parallel communication bus system is subject
to high errors rate on channel JB.
4008
BUS JA FAILURE
There is an interruption in the channel JA of the
parallel communication bus system.
4009
BUS JB FAILURE
There is an interruption in the channel JB of the
parallel communication bus system.
4010
CONNECTIVITY BUS FAILURE
The connectivity communication bus is faulty or
interrupted.
4100
RECTIFIER FUSES FAILURE
The u-switch mounted on the Rectifier input fuses
indicates a blown fuse, and consequently it is shut
down.
Clearance of this condition allows you to restart
the Rectifier.
4102
K4 CLOSING FAILURE
K4 not closed despite a closing command being
issued.
Signaled by auxiliary contact. Rectifier cannot start.
4103
K4 OPENING FAILURE
K4 not open despite an opening command being
issued.
Signaled by auxiliary contact.
Utility remains connected to Rectifier bridge.
4104
BATTERY FUSES FAILURE
This function, when enabled on input
programmable relays (password required), warns
the user about the external Battery Fuses failure or
MCB opening, Signaled by NO free contact.
4105
RECTIFIER OVERTEMPERATURE
Temperature sensor indicates a situation of
overtemperature on the Rectifier bridge.
Only the alarm is given.
The Rectifier, when in an Off state, cannot start as
long as this condition persists.
6.3.1 Events (alarms and messages)
Each of the following listed events, alarm or message, can be displayed on the LCD screen, on a PC with
the software “GE Data Protection” installed or with the monitoring system “GE iUPSGuard”.
Alarms and Messages are differently specified because the alarms are indicating an abnormal
functioning of the UPS (which are additionally signaled with the LED ALARM and acoustically with the
buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list,
but not activating the LED ALARM and the acoustical alarm).
6.3.2 Alarms list
Page 33
Critical Power
Modifications reserved
Page 33/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Code
Alarm
Description
4106
RECTIFIER TRANSFORMER
OVERTEMPERATURE
The temperature sensor inside the input
transformer winding indicates
overtemperature.
Only the alarm is given.
The Rectifier, when in an Off state, cannot start
as long as this condition persists.
4110
RECTIFIER UTILITY OUT OF TOLERANCE
Rectifier Input Utility is out of tolerance
(voltage, frequency or phase).
4115
LOW BATTERY VOLTAGE
The Battery has been discharged and reached
“stop operation” time-out (default 3 minutes),
and the Inverter will be shut down.
It will restart automatically only when the
Battery has recharged enough for a minimum
runtime.
4116
HIGH BATTERY VOLTAGE
Dangerous high DC Voltage caused inverter
shut-down.
Inverter restarts automatically after Battery
returns to floating voltage.
4117
BATTERY EARTH FAULT
A leakage current to earth has been detected
on the DC circuit.
4118
BATTERY FAULT
During battery test the voltage falls under the
critical level (depending setting parameters).
Battery test is stopped.
4121
HIGH DC RIPPLE
A high ripple is present in the battery voltage.
4125
HIGH DC-LINK VOLTAGE
Detection of high voltage on the DC-link.
The rectifier, booster and inverter will switch off
for protection purposes.
The rectifier may only be switched on again if
the DC-Link’s voltage value falls below 430V.
4126
4th LEG CONTROL SATURATION (Imax)
The current in the fourth leg has reached its
highest value.
4130
TURN ON RECT. OR SHUTDOWN UPS
Rectifier and Inverter are OFF.
The DC power supply is discharging the
Battery.
Rectifier must be restarted or Battery must be
disconnected in order to avoid damage.
4140
RECTIFIER CONTROL FAILURE
Rectifier Voltage hasn’t reached the set value
(probably fault on regulation loop).
LED Rectifier on control panel is blinking.
4141
ISMAX DETECTION RECTIFIER
After 3 IS-Max condition within the time frame
specified in respective parameter, the Rectifier
remains shut-down.
4142
RECTIFIER CURRENT MAX
Will cause immediate shut-down of the
Rectifier.
Based on the value inserted in the respective
parameter.
4143
BOOSTER/BATTERY CHARGER CURRENT
MAX
Detection of maximum current in the
booster/battery charger.
The Booster/Battery charger and Inverter will
switch off for protection purposes.
Page 34
Critical Power
Modifications reserved
Page 34/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Code
Alarm
Description
4146
4TH LEG DRIVER FAILURE
The Booster’s driver indicates the presence of a
defect which switches the power off.
4147
BATTERY CHARGER DRIVER FAILURE
The Battery charger driver indicates a defect,
switching it off.
4150
BOOSTER OVERTEMPERATURE
The temperature of the booster bridge exceeds
the machine’s set limit or the coil’s sensor is on.
4151
4TH LEG OVERTEMPERATURE
The temperature of the 4
th
leg’s bridge exceeds
the machine’s set limit.
4301
INVERTER FUSES
The alarm signals an inverter outlet fuses fault,
causing it to switch off immediately.
It may only be manually switched on after the
alarm has ceased.
4304
K7 CLOSING FAILURE
K7 not closed despite a closing command.
Signaled by auxiliary contact.
Load will be supplied by Utility.
4305
K7 OPENING FAILURE
K7 not open despite an opening command.
Signaled by auxiliary contact.
Load will be supplied by Utility.
4307
INVERTER TRANSFORMER
OVERTEMPERATURE
The temperature sensor of the Inverter
Transformer indicates overtemperature.
Elapsed “stop operation” time, Inverter shutdown.
With Utility OK, Load is transferred on Utility.
4308
DC FUSES FAILURE
Blown input DC fuse(s) F1 of the Inverter.
Inverter cannot be started as long as present.
4309
DRIVER FAILURE
An abnormal condition has been detected on one
or more power modules of the Inverter
(temperature or overcurrent).
Inverter shut-down and cannot be started as
long as the alarm is present.
4310
IGBT RECTIFIER DRIVER FAILURE
Indicates a failure on the driver board or the
Rectifier IGBT bridge.
The Rectifier is shut-down.
4311
BOOSTER DRIVER FAILURE
Driver Booster error signal.
4312
INVERTER VOLTAGE OUT
OF TOLERANCE
Inverter Output Voltage is out of the tolerances (
10%).
Inverter is switched OFF.
4320
ISMAX DETECTION
Detection of Inverter Bridge (Is) current limit
causing the Inverter OFF and automatic re-start.
After 3 times the Inverter switches-Off, and it can
be restarted manually.
4321
HIGH CURRENT SHARING
A high exchange current value is detected
between the UPS of the Parallel System.
Page 35
Critical Power
Modifications reserved
Page 35/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Code
Alarm
Description
4340
INVERTER CONTROL FAILURE
The “Slave” oscillator is not in synchronized with
the Master; thus causing the shut-down of its
Inverter.
If after a restart the condition remains, the LED
inside the Inverter symbol on the panel will not
light up, indicating that this Inverter cannot
supply the Load anymore.
4404
K6 CLOSING FAILURE
K6 open despite a closing command being
issued. Signaled by auxiliary contact.
The Load cannot be supplied by Automatic
Bypass.
4405
K6 OPENING FAILURE
K6 closed despite an opening command being
issued. Signaled by auxiliary contact.
4406
SSM FAILURE
A faulty current has been detected in the staticswitch causing the opening of the contactor K6
for 10 seconds.
After 3 times K6 remains definitively open.
Only a GE Service Engineer can reset the alarm.
4410
BYPASS UTILITY OUT OF TOLERANCE
The Utility Bypass Voltage is out of the tolerances
( 10%).
K6 opens, synchronization with Utility is inhibited
and transfer to Utility is blocked.
4420
K3 CLOSING FAILURE
K3 open despite a closing command.
Inverter is switched OFF.
It can be restarted manually after recovery of the
alarm condition.
4421
K3 OPENING FAILURE
K3 not open despite an opening command.
Be aware the DC Capacitors could remain
charged.
4520
NO INVERTER POWER
The Load supplied by Utility exceeds the Inverter
power.
The Load remains supplied by Utility until the
alarm stays ON.
4522
FAN FAILURE
The Fan Control Board indicates a malfunction of
one or more ventilators.
4530
LOAD LOCKED ON UTILITY
Load is locked on Utility because 3 transfers on
Utility have been detected in a short time (default
30 sec.).
The transfer will be free after a time defined in
parameter (default 30 sec.).
4531
LOAD ON UTILITY BY ERROR DETECTOR
Load is transferred to Utility because the error
detector detected a disturbance on the output
voltage.
4563
EMERGENCY OFF ACTIVATED
Alarm after detection of an EPO (Emergency
Power Off) from an external safety device
connected on Customer Interface Board.
Consequently K4, K6, K7 open, Rectifier, Inverter
and SSM are switched Off.
4570
OVERLOAD
The UPS system is in an overload condition
105% on Inverter, or 150% on Utility.
With Utility unavailable, a sequence of “stop operation” starts.
Time out depends on degree of overload.
Page 36
Critical Power
Modifications reserved
Page 36/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Code
Alarm
Description
4571
OVERLOAD: LOAD ON UTILITY
With Utility Bypass supply available and Load
115%, the Load is transferred on Utility.
Load will be transferred again automatically on
Inverter when Load 100%.
4581
INVERTER AND UTILITY
NOT SYNCHRONIZED
The voltages of Utility and Inverter are not
synchronized, which causes the opening of K6.
4608
ECO CONFIG FAILURE
The propagation of the eBoost / IEMi
configuration to other units in a Parallel System
failed.
4697
BATTERY OVERTEMPERATURE
Detection of Battery overtemperature condition.
Only a GE Service Engineer can reset the alarm.
4698
BATTERY POWER INSUFFICIENT
In case of Utility Failure, with the actual Load, the
run time would be below stop operation time
(default 3 minutes).
4700
DC LOW
Battery voltage is at the lowest limit.
Inverter will remain Off until the battery voltage
reaches the value in parameter.
4701
POWER SUPPLY BOARD FAILURE
Detection of a failure on the Power Supply Board,
in particular from the DC supply.
Can be enabled or disabled with respective
parameter.
4702
LOSS OF REDUNDANCY
A time of lost redundancy superior than specified
in respective parameter was detected.
4900
LOAD LOCKED ON INVERTER
The Load is locked on Inverter after 3 Load
transfers within 30 seconds.
After time out (default 30 sec.) Bypass will be free.
4955
OVERTEMPERATURE
An overtemperature condition has been detected
on Inverter.
Elapsed “stop operation” time, Inverter shutdown.
With Utility OK, Load is transferred on Utility.
4998
LOAD OFF DUE TO EXTENDED
OVERLOAD
Load Off after time-out of “stop operation” for
overload on Inverter (time depending on the % of
overload).
4999
LOAD OFF DUE TO LOW BATT. OR TEMP.
Load Off after time-out of “stop operation” with
missing Utility due to Battery low voltage or
overtemperature condition.
Page 37
Critical Power
Modifications reserved
Page 37/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Code
Message
Description
4002
WATCHDOG RESET
The microprocessor has detected an incorrect
operation:
Transfers the load on utility and performs a
program reset.
The inverter will restart automatically and will
supply the load.
4003
SENSOR AUTO-CALIBRATION ERROR
The voltage/current reading were not correctly
calibrated when the UPS was switched on.
4111
RECTIFIER UTILITY OK
Rectifier Input Utility is again within the admitted
tolerance (voltage, frequency and phase).
4119
BATTERY TEST STARTED
Start of Manual or Automatic Battery Test.
4120
BATTERY TEST STOPPED
End of Manual or Automatic Battery Test.
4122
MANUAL BOOST CHARGE START
Recharging has been manually activated from
the control panel, bringing the final load up to the
value of the respective parameter.
4123
AUTOMATIC BOOST CHARGE START
After the battery has discharged, an automatic
boost charge has started to recharge the battery
based on pre-defined settings.
4124
MANUAL/AUTOMATIC BOOST CHARGE
STOP
The automatic boost charge has finished. The
battery’s voltage will return to the maintenance
value.
A manually activated boost charge will finish if: it
is manually interrupted, the initial timer setting
has expired, or the rectifier is not functioning
correctly (Alarm 4140).
The battery voltage will return to the
maintenance value.
4144
BOOSTER ON
The booster is switched ON.
It transfers energy from the battery to the DClink.
4145
BOOSTER OFF
The booster is switched Off.
4148
BATTERY CHARGER ON
The battery charger is switched on and is
charging the battery.
4149
BATTERY CHARGER OFF
The battery charger is switched off.
4161
RECTIFIER ON
Rectifier started.
4162
RECTIFIER OFF
Rectifier shut-down.
4163
GENERATOR ON
Customer Interface (X1 - 11, 22) received a Genset ON signal.
Operating mode depend on setting of
Parameters.
4164
GENERATOR OFF
Customer Interface (X1 - 11, 22) received a Genset OFF signal.
Function Bypass enabled depends on setting of
Parameter.
4302
INVERTER CANNOT BE TURNED ON
Inverter cannot be switched on because one of
the following conditions is still present:
- Overtemperature - K7 opening Failure
- Low Battery Voltage - High Battery Voltage
- Inverter Fuses - DC Low
- Overload - EPO (Emergency Power Off)
6.3.3 Messages list
Page 38
Critical Power
Modifications reserved
Page 38/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Code
Message
Description
4303
INVERTER CANNOT BE TURNED OFF
Inverter cannot be switched OFF, because the
Load cannot be switched to Utility (voltage out of
tolerance, not synchronized, BP blocked).
4361
INVERTER ON
The command to start the Inverter has been
activated on the control panel.
4362
INVERTER OFF
The command to switch OFF the Inverter has
been activated by the control panel or
automatically for alarm presence.
4411
BYPASS UTILITY OK
Bypass Input Utility is again within tolerance
(voltage, frequency and phase).
4500
COMMAND LOAD OFF
Disconnection of the Load by opening K6 and K7
for:
EPO / Load Off / Overload / Stop Operation.
4521
NO BYPASS POWER
With the Load supplied by Automatic Bypass, a
Utility Failure or K6 opening occurred.
4534
MULTIPLE LOAD TRANSFER
2 transfers Inverter- Utility have been detected in
a short time (default 30 sec.).
4535
BYPASS LOCKED
Bypass is not available.
Contactor K6 is open, SSM deactivated.
4536
BYPASS FREE
Bypass is enabled.
Contactor K6 is closed.
4561
LOAD OFF
Push-button “Load Off” on the UPS Control Panel
has been pressed, with the output circuit switch
Q1 closed.
4562
DETOUR ON
The auxiliary contact indicates that Manual
Bypass Q2 was closed.
4564
DETOUR OFF
The auxiliary contact indicates that Manual
Bypass Q2 was opened.
4567
COMMAND LOAD ON UTILITY
The control unit received a command to transfer
the Load on Utility.
4568
COMMAND LOAD ON INVERTER
The control unit received a command to transfer
the Load on Inverter.
4572
NO MORE OVERLOAD
End of the overload condition detected with
alarm 4570.
4580
INVERTER AND UTILITY SYNCHRONIZED
The voltages of Inverter and Utility Bypass are
synchronized.
4582
COMMAND NOT TO SYNCHRONIZE
Command not to synchronize with Utility.
4583
COMMAND TO SYNCHRONIZE
Command to synchronize with Utility.
4600
COMMAND UPS ON
The eBoost operation mode function has been
disabled or the programmed time is expired.
The UPS returns to VFI mode supplying the Load
normally by inverter.
4601
COMMAND UPS STAND BY
The function eBoost operation mode is enabled,
and according to the time program the UPS will
run in eBoost mode, supplying the Load normally
by utility.
4602
Q1 OPEN
The auxiliary contact indicates that the output
switch Q1 was opened.
4603
Q1 CLOSED
The auxiliary contact indicates that the output
switch Q1 was closed.
Page 39
Critical Power
Modifications reserved
Page 39/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Code
Message
Description
4605
COMMAND IEMi OFF
The IEMi Operation Mode has been disabled or the
programmed time is expired.
4606
eBoost/IEMi ACTIVATION ALLOWED
eBoost/IEMi control signal has been cleared on the
Customer Interface Board (X1 - 11, 22).
Operating mode depends on scheduled activation
of the functions.
4607
eBoost/IEMi ACTIVATION INHIBITED
Customer Interface Board (X1 - 11, 22) received an
eBoost/IEMi control signal.
eBoost™ Operation Mode and IEMi Operation
Mode will be temporarily inhibited.
4609
eBoost INHIBITED - LOW LOAD
eBoost™ Operation Mode inhibited due to minimal
load not reached.
4699
BATTERY TEST IMPOSSIBLE
Automatic Battery Test is not possible due to:
- No Utility Rectifier or Bypass.
- Battery not fully charged.
- Load is below 10% or above 80%.
Test is postponed for 1 week.
4763
REMOTE CONTROL ON
Inverter can be started or shut-down by remote
control.
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both
4764
REMOTE CONTROL OFF
Inverter cannot be started or shut-down by remote
control.
Commands source can be chosen depending on
the value of parameter (Service only):
0 = Only local panel
1 = Only Remote Control
2 = Both
4798
SERVICE KEY ACTIVATED
A valid Service Key has been entered.
It will no longer be requested in the next 6 hours.
4799
SERVICE KEY DEACTIVATED
The Service Key validity period has expired.
Page 40
Critical Power
Modifications reserved
Page 40/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
SETUP
The SETUP mode is entered any time the
“SETUP” key is pressed.
This screen allows the user to modify
some parameters permitting to adapt
some functions of the UPS to his/her
needs, described as follows.
The LCD will display a series of screens
containing the user parameters,
accessible without password protection.
Shows the main screen MEASURES.
See Section 6.2.
Shows the main screen EVENTS.
See Section 6.3.
Return to HOME screen.
Shows the main screen COMMANDS.
See Section 6.5.
Shows the operating status of the RPA PARALLEL SYSTEM.
See Section 6.6.
Key to reset general alarm and buzzer.
Shows the screen User.
Shows the screen Service Basic.
Reserved for the Service Center, at this level the parameters access is protected by a
code.
Shows the screen Service Full.
Reserved for the Service Center, at this level the parameters access is protected by a
code.
6.4 SETUP
In this mode the keys perform the following functions:
Page 41
Critical Power
Modifications reserved
Page 41/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
PRINTER SCREEN
The UPS is capable of communicating to
a serial printer, to printout disparate
information.
Please be sure to have a serial printer
with a serial RS232 interface.
This is the only printer-interface
supported by the UPS.
Baudrate
This parameter controls the baud rate
used for data transmission.
Parity
This parameter controls the parity used for data transmission.
odd / even / None can be selected.
In case “None” has been set, automatically the parameter “Data bits = 8” is used,
independently of the value of “Data Bits” set.
Data bits
This parameter controls the length of the data word on the serial line during data
transmission.
Stop bit
Parameter non programmable.
Handshake
This parameter is used to determine the communication protocol used when
printing.
Valid values are “XON” standing for the XON/XOFF protocol or “None” standing for
any protocol.
PRINTER
COMMANDS
By using the keys MEASURES / ALARMS / PARAMETERS / ALL it is possible to print
selected data
NOTE !
Please configure your printer with the following parameters:
2400/None/8/2/None (2400 bauds/sec, no parity, 8 bits, no Handshake).
DISPLAY SCREEN
Date
You can adjust the date of the real time
clock existing in the UPS by the means
of this parameter (“dd-day, mm-month, yyyy-year”).
The value you enter is thoroughly
checked to be a correct date in the
format “MM.DD.YYYY”.
Time
You can adjust the time of the real time
clock existing in the UPS by means of
this parameter.
The value you enter is thoroughly
checked to be a correct time in the
format “HH.MM.SS”.
The time is specified in AM/PM format.
Language
This parameter allows the choice of language used to display the information.
Valid choices are: English, German, Italian, Spanish, French, Finnish, Polish, Portuguese, Czech, Slovenian, Chinese, Swedish, Russian and Dutch.
UPS name
The user can choose the name of the UPS model shown on the main screen (max.
20 characters).
Page 42
Critical Power
Modifications reserved
Page 42/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
eBOOST SCREEN (option)
This screen is displayed only when
eBoost™ Operation Mode is available
(option).
Enabled
This parameter (values Yes/No) enables
or disables the eBoost™ Operation Mode.
If the value is “Yes” and the current time
is in the interval for the current day, the
eBoost™ Operation Mode is active.
In case of RPA Parallel System
If eBoost™ Operation Mode is currently disabled (No) and Q1 is closed, when
programming it to enable (Yes) the selected configuration will automatically be
propagated to all units in the RPA Parallel System.
The activation / deactivation of eBoost™ Operation Mode is indicated each time in the event list.
In order to check the inverter function, at least 1 minute of VFI mode must be programmed during the
week (the Yes/No parameter is automatically disabled if this condition is not satisfied).
In case this minimum time in VFI mode is not respected, the eBoost™ Operation Mode will be disabled.
If the value is “No”, the UPS is normally operating in VFI / double conversion mode at all times.
When the UPS is in eBoost™ Operating Mode the eBoostLED is ON (green
light).
NOTE !
The configuration of the activation schedule can only be updated when eBoost™ Operation Mode is disabled (Enabled: No).
DAY
For the weekdays from “Monday to Sunday”, the edit mode (edit day) allows to define time intervals
when the UPS is operating in eBoost™ Operation Mode. The hour is given in 24-hour format.
These intervals are defined by:
Start Time: The hour of the day after which the eBoost™ Operation Mode is enabled.
The eBoost™ Operation Mode is enabled until the following “Stop Time” time is reached
(the “Stop Time” time of the same day if this is later than the “Start Time” time, the “Stop Time” time of the following day otherwise).
Stop Time: The hour of the day before which the eBoost™ Operation Mode is enabled.
The eBoost™ Operation Mode is enabled starting from the preceding “Start Time” time (the “Start Time”
time of the same day if this is earlier than the “Stop Time” time, the “Start Time” time of the previous
day otherwise).
Identical times for “Start Time” and “Stop Time” maintain the existing mode only in case the previous
command was “Start Time” and the following command will be “Stop Time”.
Page 43
Critical Power
Modifications reserved
Page 43/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
To avoid undesired eBoost™ Operation Mode, verify:
Date and Time.
eBoost™ screen how many hours of eBoost™ Operation Mode have been
selected for each day of the week.
NOTE !
The eBoost™ Operation Mode will become active only if the Load is supplied from
the Inverter.
eBoost™ Operation Mode is only possible if the UPS load exceeds a minimum
threshold (default 10% of the rated capacity).
In case no-load conditions, or anyway below said threshold, the UPS operates in VFI mode.
TOUCH SCREEN
This screen permits the adjustment
(“CALIBRATE” key)of the LCD’s “Touch Screen” sensitivity.
IDENTIFICATION SCREEN
ID
Number of UPS in the RPA Parallel
System (0 for single unit).
Model
UPS model, power range and series
number.
S/N
The UPS serial number.
UPS SW version
The UPS software version.
Display SW version
The LCD display software version.
HOURS/DAY
The number of eBoost™ Operation Mode hours per weekday “Monday to Sunday” is displayed in the
operation mode parameter window (ceiling value).
Page 44
Critical Power
Modifications reserved
Page 44/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
COMMANDS
The COMMANDS mode is entered any time
the “COMMANDS” key is pressed.
Allows the user to execute UPS operation
commands.
Shows the main screen MEASURES.
See Section 6.2.
Shows the main screen EVENTS.
See Section 6.3.
Shows the main screen SETUP.
See Section 6.4.
Return to HOME screen.
Shows the operating status of the RPA PARALLEL SYSTEM.
See Section 6.6.
Key to reset general alarm and buzzer.
Shows the screen Commands 2.
Shows the screen Commands 1.
6.5 COMMANDS
In this mode the keys perform the following functions:
Page 45
Critical Power
Modifications reserved
Page 45/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
COMMANDS 1 SCREEN
Allows the user to execute UPS
operation commands.
Rectifier
Rectifier ON
Rectifier switching ON command.
Rectifier RESET
Rectifier restore command.
Reserved for the Service Center.
Led Rectifier status
Indicates the Rectifier’s status: ON = lit OFF = turned Off
Inverter
Inverter ON
Inverter switching ON command.
NOTE !
When eBoost™ Operation Mode is enabled, control of Inverter status and
selection of the feed path is done autonomously by the UPS control logic.
Therefore, Inverter ON / Inverter OFF commands are disabled when eBoost™ Operation Mode is enabled.
Inverter OFF
Inverter switching OFF command.
This command is also used as EPO (Emergency Power Off) reset after the contact closing.
NOTE !
Inverter OFF command is disabled when eBoost™ Operation Mode is enabled.
Led inverter status
It indicates the Inverter status:
ON / OFF / Pre-charge / Pre-charge completed / Soft-start
Page 46
Critical Power
Modifications reserved
Page 46/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Module shutdown
Module shutdown
Load Off command for a single UPS.
NOTE !
This command will immediately disconnect the Load.
“Module shutdown” cannot disconnect the UPS from the Load with Q2
closed.
For the RPA Parallel System
In an RPA Parallel System, the “Module shutdown” command disconnects the
Load to the selected unit only (switch Q1 closed).
Module shutdown RESET
Module shutdown restore command for an individual UPS.
Led Module shutdown status
Shows the Module shutdown status: ACTIVE / NOT ACTIVE
System shutdown
System shutdown
Load Off command for an RPA Parallel System.
NOTE !
This command will immediately disconnect the Load.
“System shutdown” cannot disconnect the RPA Parallel System from the
Load with Q2 closed.
For the RPA Parallel System
If “System shutdown” is pressed on one unit connected to the parallel bus (switch
Q1 closed), all the units are separated from the Load.
System shutdown RESET
System shutdown restore command for a RPA Parallel System.
For the RPA Parallel System
The “System shutdown reset” must be done only on one unit connected to the
parallel bus (switch Q1 closed).
Led System shutdown status
Shows the System shutdown status: ACTIVE / NOT ACTIVE
Booster
Only for Service Center.
Page 47
Critical Power
Modifications reserved
Page 47/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
COMMANDS 2 SCREEN
Allows the user to execute UPS
operation commands.
Buzzer TEST
Acoustical alarm test (acoustical alarm should be always
activated).
Module shutdown procedure
Function not enabled.
Module start-up procedure
Function not enabled.
System on bypass
Function not enabled.
Battery Charger
Function not enabled.
Page 48
Critical Power
Modifications reserved
Page 48/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
RPA
PARALLEL SYSTEM
(option)
The RPA PARALLEL SYSTEM is entered any
time the “RPA” key is pressed.
This screen is only displayed when the
RPA Parallel System is available (option).
The LCD screen will provide some
information on the RPA Parallel System.
Shows the main screen MEASURES.
See Section 6.2.
Shows the main screen EVENTS.
See Section 6.3.
Shows the main screen SETUP.
See Section 6.4.
Shows the main screen COMMANDS.
See Section 6.5.
Return to HOME screen.
Key to reset general alarm and buzzer.
Shows the screen for the next RPA Parallel System units
Shows the screen of the previous RPA Parallel System units.
6.6 RPA PARALLEL SYSTEM
In this mode the keys perform the following functions:
Page 49
Critical Power
Modifications reserved
Page 49/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Description of the RPA Parallel System screen’s main elements
RECT Rectifier
green color = On / grey color = Off
CHRG / BST Battery Charger / Booster
green color = On / grey color = Off
INV Inverter
green color = On / grey color = Off
BYP Automatic Bypass
green color = On / grey color = Off
UPS1÷6 Number of UPS in the RPA Parallel System
M Master unit of the RPA System Parallel
Input Utility status (for RECT – Rectifier and BYP - Bypass)
Battery status (for CHRG – Battery Charger)
green color = On / grey color = Off
Q1 Load output switch
Q2 Manual Bypass switch
Open
Open
Closed
Closed
Examples of the main RPA Parallel System unit status situations
UPS with Load
supplied by Inverter
UPS with Load
supplied by Automatic Bypass
UPS with Load
supplied by Battery
UPS in stand-by in an
Redundant RPA Parallel System
UPS in eBoost Operating Mode
UPS with Load
supplied by Manual Bypass
Page 50
Critical Power
Modifications reserved
Page 50/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
TLE Series 225 - 500 requires the introduction of a
“START-UP KEY” codeto perform the first
commissioning.
ESC
ENTER
The "START-UP KEY" code can be introduced by a GE SERVICE TECHNICIAN only.
The introduction of the "START-UP KEY" code is
mandatory to proceed to the first start-up of the UPS.
7 OPERATION
Page 51
Critical Power
Modifications reserved
Page 51/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
WARNING !
Verify that the input/output connections have been performed by qualified
personnel before connecting Utility input voltage and verify that the
equipment is correctly grounded.
Open only the front door, do not remove any panels.
Now you can initiate the start-up procedure of the UPS system.
There is no need for specific knowledge if you follow carefully the step-bystep instructions given below.
However we recommend that at least the initial procedure should be
performed by an instructed person.
Check after every step for correct reaction of the UPS (LEDs on the panel),
and correct voltage and current measurements, before you proceed to the
next step.
If you encounter any problems during the following procedures, you
should not continue, but contact GE Global Services.
NOTE !
All operations (including start-up, shut-down, removing/adding a unit
from/to a Parallel System) MUST BE PERFORMED with eBoost™ Operation
Mode DISABLED.
This symbol refers to the operations of a RPA Parallel System.
Find on the following pages the descriptions of the various procedures of start-up and
shut-down for single and parallel UPSs, divided into the following principal chapters:
8.1 PROCEDURES FOR SINGLE TLE Series 225 - 500
8.2 PROCEDURES FOR SINGLE TLE Series 225 - 500 FUNCTIONING AS FREQUENCY
CONVERTER
8.3 PROCEDURES FOR TLE Series 225 - 500 PARALLEL SYSTEM
Page 52
Critical Power
Modifications reserved
Page 52/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
WARNING !
Before proceeding to turn on the UPS system, ensure that the AC and DC external isolators are OFF, and prevent their inadverted operation.
Ensure that the Output Load distribution can be powered and all the Output Isolators are open.
LED 1 Rectifier
LED 2 Inverter
LED 3 Booster/ Battery charger
LED 4 Automatic Bypass
LED 5 LOAD on UPS
LED ALARM
LED LOAD PROTECTED
Command Inverter ON
Command Inverter OFF
Command
System shutdown
Command
System shutdown Reset
1.
Switch-ON the Utility voltage from the input distribution (both Rectifier and Bypass if
separated).
The UPS performs a “Self-test”.
A successful termination of the tests will be indicated with Overall test
results “OK”.
Commissioning cannot be continued should one or more tests result
to be negative. Please contact in this case your Service Center.
At this stage the Electronic Power Supply and Control Panel are switched
ON and the Buzzer sounds.
Press “MUTE” key to reset Acoustical Alarm.
LED ALARM remains lit.
CB3
(Option)
ON
OFF
Q1
I ON
0 OFF
TLES_UL_225-250_S1_Switch Q1-Q2_01
Q2
I ON
0 OFF
TLES_UL_400-500_S1_Switch Q1-Q2_CB3_01
Q1
I ON
0 OFF
Q2
I ON
0 OFF
CB3
(Option)
ON
OFF
7.1 PROCEDURES FOR SINGLE TLE SERIES 225 - 500
7.1.1 Initial start-up of the TLE Series 225 - 500
This procedure must be performed for the first start-up following the installation, with the UPS
completely switched Off and not powered.
Open the front door and make sure that:
All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
The safety screens are fixed in their position.
The switches Q1, Q2 and CB3 (option) are open (Pos. O) and the external Battery protectionsmust
be open (Pos. O).
Continue ►
Page 53
Critical Power
Modifications reserved
Page 53/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
WARNING !
The set-up of the UPS configuration parameters must be done only by QUALIFIED
AND TRAINED PERSONNEL.
The set-up of mistaken values could compromise the integrity and reliability of the
UPS.
UPS
Language
This parameter allows the choice of language used to display the
information.
Date (dd.mm.yyyy)
You can adjust the date of the real time clock existing in the UPS by the
means of this parameter.
The value you enter is thoroughly checked to be a correct date in the
format “DD.MM.YY”.
Time (24h)
You can adjust the time of the real time clock existing in the UPS by
means of this parameter.
The value you enter is thoroughly checked to be a correct time in the
format “HH.MM.SS”.
The time is specified in 24-hour format.
Input Frequency (Hz)
Input frequency value (50 Hz / 60Hz).
Output Frequency (Hz)
Inverter output frequency value (50 Hz / 60Hz).
Inverter Voltage (V)
Output voltage PHASE/NEUTRAL of the inverter (220V / 230V / 240V).
During the first commissioning TLE Series 225 - 500 requests a set-up of the UPS configuration
parameters presented in the following “Power-Up” screen.
Without such configuration it is not possible to continue with the commissioning procedure.
Continue ►
Page 54
Critical Power
Modifications reserved
Page 54/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
BATTERY
Capacity (Ah)
Ah capacity of the Battery.
Recharge Mode
Recharge type of the Battery
- Normal Valve Regulated Lead Acid Battery (VRLA), NiCd
without boost-charge and Flooded Lead Acid
Battery without boost-charge.
- NiCd Nickel Cadmium Battery with boost-charge.
- Wet Lead Acid Boost Flooded Lead Acid Battery with boost-charge.
Float Voltage (V)
Voltage to maintain Battery Charging.
Float voltage = Number of battery cells x battery float voltage per cell.
Typical battery float voltage per cell (ask the battery manufacturer for
confirmation):
Valve Regulated Lead Acid Battery (VRLA):
2.27Vdc for cell
240 cells x 2.27Vdc = 545Vdc
NiCd Battery without boost-charge:
1.41Vdc for cell
284÷309 cells x 1.41Vdc = 401 ÷ 436Vdc
NiCd Battery with boost-charge:
1.41 (1.55 boost-charge) Vdc for cell
281 cells x 1.41Vdc = 397 (436) Vdc
Flooded Lead Acid Battery without boost-charge:
2.23Vdc for cell
180÷195 cells x 2.23Vdc = 402 ÷ 435Vdc
Flooded Lead Acid Battery with boost-charge:
2.23 (2.35 boost-charge) Vdc for cell
180÷185 cells x 2.23Vdc = 402 (423) ÷ 413 (435) Vdc
Recharge Current (A)
Maximum Battery Recharge Current.
Max 20% of battery capacity (Ah).
Example: 100Ah – max. recharging current 20A.
Cells
Number of cells of the Battery, see “Float voltage”.
Example: 240 battery cells
- 40 blocks / 12Vdc Battery
- 80 blocks / 6Vdc Battery
- 240 blocks / 2Vdc Battery
Stop Operation Time
(min)
Residual Battery Autonomy time before UPS forced shut-down.
Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes.
NOTE !
The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the Battery
Manufacturer.
Continue ►
Page 55
Critical Power
Modifications reserved
Page 55/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
2. Close UPS output switch Q1 (Pos. I).
The Load is supplied by the Utility through the Automatic Bypass.
Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
The Synoptic Diagram must display the status“LOAD
SUPPLIED BY AUTOMATIC BYPASS”.
3. Connect the Battery to the UPS by closing the external Battery protections and close, if
present, the switch CB3 (option).
Attention: check the right DC polarities on both side of the switch/fuse holder!
NOTE !
Ensure the LED 1 (Rectifier) is lit before
carrying out this procedure.
It indicates that the DC-Link has reached
800Vdc (see screen MEASURES / Rectifier)!
Before performing the next procedure make
sure that the LED 3 (Booster/Battery charger)
is lit.
4. Insert the inverter performing the command "Inverter ON".
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
The Load is automatically transferred from Automatic Bypass to Inverter.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status“LOAD
SUPPLIED BY INVERTER”.
5. Operation mode selection.
TLE Series 225 - 500 is delivered normally selected for permanent VFI operation.
The eBoost™ Operation Mode can be enabled and the eBoost Start Time & eBoost Stop Time can be
programmed for each day of the week (see Section 6.4 SETUP / eBoost).
END OF PROCEDURE
NOTE !
The Battery must be charged for at least 10 hours, in order to ensure the full backup
runtime in case of a Utility Failure.
Page 56
Critical Power
Modifications reserved
Page 56/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
Initial status:
Load supplied from Inverter.
1. Disconnect the Inverter performing the “Inverter OFF” command.
1 - Perform the “Inverter OFF” command from the
screen: Commands 1 / Inverter / OFF.
Load is transferred to Utility by Automatic Bypass.
2 - Repeat the “Inverter OFF” command from the
screen: Commands 1 / Inverter / OFF.
Inverter shuts down. LED 2 (Inverter) must be OFF.
LED ALARM is lit.
The Synoptic Diagram must display the status“LOAD
SUPPLIED BY AUTOMATIC BYPASS”.
2. Close Manual Bypass switch Q2 (Pos. I).
Load is now supplied parallel through Automatic Bypass and Manual Bypass Q2.
The Synoptic Diagram must display the status “LOAD
SUPPLIED BY AUTOMATIC BYPASS AND MANUAL BYPASS
Q2”.
7.1.2 UPS shut-down with load transfer on Manual Bypass Q2
Continue ►
Page 57
Critical Power
Modifications reserved
Page 57/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
3. Open UPS output switch Q1 (Pos. O) and perform the
command “System shutdown”.
Perform the command “System shutdown” through the
screen: Commands 1 / System shutdown / Shutdown.
Load is now supplied from Utility by Manual Bypass Q2.
Rectifier shuts down and all contactors are opened.
The Synoptic Diagram must display the status“LOAD
SUPPLIED BY MANUAL BYPASS Q2”.
4. Disconnect the Battery from the UPS by opening, if
present, the switch CB3 (option) and then the external
Battery protections.
Press “MUTE” key to reset Acoustical Alarm.
LED ALARM remains lit.
END OF PROCEDURE
DANGER !
The UPS cabinet contains parts electrically live.
Apart from the front door, do not open any other part of the UPS.
Page 58
Critical Power
Modifications reserved
Page 58/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Initial status:
Load supplied from Manual Bypass Q2.
1. Close UPS output switch Q1 (Pos. I).
Load is now supplied parallel through Automatic Bypass and Manual Bypass Q2.
Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
The Synoptic Diagram must display the status“LOAD
SUPPLIED BY AUTOMATIC BYPASS AND MANUAL BYPASS
Q2”.
3. Connect the Battery to the UPS by closing the external Battery protections and close, if
present, the switch CB3 (option).
NOTE !
Ensure the LED 1 (Rectifier) is lit before
carrying out this procedure.
It indicates that the DC-Link has reached
800Vdc (see screen MEASURES / Rectifier)!
Before performing the next procedure make
sure that the LED 3(Booster/Battery charger)
is lit.
3. Open Manual Bypass switch Q2 (Pos. O).
The Load is supplied by the Utility through the Automatic Bypass.
The Synoptic Diagram must display the status“LOAD
SUPPLIED BY AUTOMATIC BYPASS”.
4. Insert the inverter performing the command “Inverter ON".
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
The Load is automatically transferred from Automatic Bypass to Inverter.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status“LOAD
SUPPLIED BY INVERTER”.
END OF PROCEDURE
7.1.3 From Manual Bypass Q2 to normal function VFI
Page 59
Critical Power
Modifications reserved
Page 59/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
Follow this procedure only in case the UPS system and the Load must be
completely powered-down.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
Initial status:
Load supplied from Inverter.
1. Perform the command “System shutdown”.
Perform the command “System shutdown” through the
screen: Commands 1 / System shutdown / Shutdown.
Load is disconnected from UPS.
Rectifier and Inverter are shut down and all contactors are
opened.
LED 1 (Rectifier) and LED 2 (Inverter) are OFF.
LED ALARM is lit.
2. Open UPS output switch Q1 (Pos. O).
3. Disconnect the Battery from the UPS by opening, if present, the switch CB3 (option) and then
the external Battery protections.
NOTE !
Before performing the next procedure wait 5
minutes for DC-Link Capacitors discharge.
Use the MEASURES/Rectifier screen to ensure
that the DC-link1 and DC-link 2 voltage has
reached 10Vdc.
Press “MUTE” key to reset Acoustical Alarm.
LED ALARM remains lit.
4. Disconnect the Utility from the input distribution.
All LEDs are OFF.
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
7.1.4 Complete UPS shut-down
Page 60
Critical Power
Modifications reserved
Page 60/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
Make sure the UPS to be status of the activation of “System shutdown”, i. e. Q1 and
CB3 (option) closed, Q2 open and External Battery protection connected.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
View of the Synoptic Diagram after performed the
command “System shutdown”:
All Contactors are open.
Rectifier, Inverter, Booster/Battery charger and
Static-Switch shut-down.
LED ALARM is lit.
1. Restore the command “System shutdown”.
Restore the command “System shutdown” through the
screen: Commands 1 / System shutdown / Reset.
The Load is supplied by the Utility through the Automatic Bypass.
Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
The Synoptic Diagram must display the status“LOAD
SUPPLIED BY AUTOMATIC BYPASS”.
2. Insert the inverter performing the command “Inverter ON".
Before performing this procedure make sure that the LED 1 (Rectifier) and LED 3 (Booster/Battery
charger) are lit.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
The Load is automatically transferred from Automatic Bypass to Inverter.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status“LOAD
SUPPLIED BY INVERTER”.
END OF PROCEDURE
7.1.5 Restore to normal operation after “System shutdown”
Page 61
Critical Power
Modifications reserved
Page 61/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
Make sure the UPS to be status of the activation of EPO, i. e. Q1 and CB3 (option)
closed, Q2 open and external Battery protection connected.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
View of the Synoptic Diagram after activation of
EPO (Emergency Power Off) with Utility available:
All Contactors are open.
Rectifier, Inverter, Booster/Battery charger and
Static-Switch shut-down.
LED ALARM is lit.
1. Reset the EPO (Emergency Power Off) button.
Press “MUTE” key to reset Alarm and Acoustical Alarm.
LED ALARM remains lit.
2. Perform the “Inverter OFF” command.
Perform the “Inverter OFF” command from the screen:
Commands 1 / Inverter / OFF.
Load is transferred to Utility by Automatic Bypass.
Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
The Synoptic Diagram must display the status“LOAD
SUPPLIED BY AUTOMATIC BYPASS”.
3. Insert the inverter performing the command “Inverter ON".
Before performing this procedure make sure that the LED 1 (Rectifier) and LED 3 (Booster/Battery
charger) are lit.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
The Load is automatically transferred from Automatic Bypass to Inverter.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status“LOAD
SUPPLIED BY INVERTER”.
END OF PROCEDURE
7.1.6 Restore to normal operation after EPO (Emergency Power Off)
Page 62
Critical Power
Modifications reserved
Page 62/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
WARNING !
Before proceeding to turn on the UPS system, ensure that the AC and DC external isolators are OFF, and prevent their inadverted operation.
Ensure that the Output Load distribution can be powered and all the Output Isolators are open.
LED 1 Rectifier
LED 2 Inverter
LED 3 Booster/ Battery charger
LED 4 Automatic Bypass
LED 5 LOAD on UPS
LED ALARM
LED LOAD PROTECTED
Command Inverter ON
Command Inverter OFF
Command
System shutdown
Command
System shutdown Reset
1.
Switch-ON the Utility voltage from the input distribution.
The UPS performs a “Self-test”.
A successful termination of the tests will be indicated with Overall test
results “OK”.
Commissioning cannot be continued should one or more tests result
to be negative. Please contact in this case your Service Center.
At this stage the Electronic Power Supply and Control Panel are switched
ON and the Buzzer sounds.
Press “MUTE” key to reset Acoustical Alarm.
LED ALARM remains lit.
CB3
(Option)
ON
OFF
Q1
I ON
0 OFF
TLES_UL_225-250_S1_Switch Q1-Q2-CB3_02
Q2
I ON
0 OFF
TLES_UL_400-500_S1_Switch Q1-Q2_CB3_02
Q1
I ON
0 OFF
Q2
I ON
0 OFF
CB3
(Option)
ON
OFF
7.2 PROCEDURES SINGLE TLE SERIES 225 - 500 FUNCTIONING AS FREQUENCY
CONVERTER
When the TLE Series 225 - 500 functions as a Frequency Converter, the Automatic Bypass and Manual
Bypass functions are disabled.
Therefore the Load cannot be transferred to Utility in case of overload, short circuit, or Inverter failure.
In situations where the UPS needs to be shut-down for maintenance purposes, also the Load must be
shut-down or disconnected.
7.2.1 Initial Start-up of the TLE Series 225 - 500 as frequency converter
Open the front door and make sure that:
All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
The safety screens are fixed in their position.
The switches Q1 and CB3 (option) are open (Pos. O) and the external Battery protections must be open
(Pos. O).
Continue►
Page 63
Critical Power
Modifications reserved
Page 63/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
WARNING !
The set-up of the UPS configuration parameters must be done only by QUALIFIED
AND TRAINED PERSONNEL.
The set-up of mistaken values could compromise the integrity and reliability of the
UPS.
UPS
Language
This parameter allows the choice of language used to display the
information.
Date (dd.mm.yyyy)
You can adjust the date of the real time clock existing in the UPS by the
means of this parameter.
The value you enter is thoroughly checked to be a correct date in the
format “DD.MM.YY”.
Time (24h)
You can adjust the time of the real time clock existing in the UPS by
means of this parameter.
The value you enter is thoroughly checked to be a correct time in the
format “HH.MM.SS”.
The time is specified in 24-hour format.
Input Frequency (Hz)
Input frequency value (50 Hz / 60Hz).
Output Frequency (Hz)
Inverter output frequency value (50 Hz / 60Hz).
Inverter Voltage (V)
Output voltage PHASE/NEUTRAL of the inverter (220V / 230V / 240V).
During the first commissioning TLE Series 225 - 500 requests a set-up of the UPS configuration
parameters presented in the following “Power-Up” screen.
Without such configuration it is not possible to continue with the commissioning procedure.
Continue ►
Page 64
Critical Power
Modifications reserved
Page 64/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
BATTERY
Capacity (Ah)
Ah capacity of the Battery.
Recharge Mode
Recharge type of the Battery
- Normal Valve Regulated Lead Acid Battery (VRLA), NiCd
without boost-charge and Flooded Lead Acid
Battery without boost-charge.
- NiCd Nickel Cadmium Battery with boost-charge.
- Wet Lead Acid Boost Flooded Lead Acid Battery with boost-charge.
Float Voltage (V)
Voltage to maintain Battery Charging.
Float voltage = Number of battery cells x battery float voltage per cell.
Typical battery float voltage per cell (ask the battery manufacturer for
confirmation):
Valve Regulated Lead Acid Battery (VRLA):
2.27Vdc for cell
240 cells x 2.27Vdc = 545Vdc
NiCd Battery without boost-charge:
1.41Vdc for cell
284÷309 cells x 1.41Vdc = 401 ÷ 436Vdc
NiCd Battery with boost-charge:
1.41 (1.55 boost-charge) Vdc for cell
281 cells x 1.41Vdc = 397 (436) Vdc
Flooded Lead Acid Battery without boost-charge:
2.23Vdc for cell
180÷195 cells x 2.23Vdc = 402 ÷ 435Vdc
Flooded Lead Acid Battery with boost-charge:
2.23 (2.35 boost-charge) Vdc for cell
180÷185 cells x 2.23Vdc = 402 (423) ÷ 413 (435) Vdc
Recharge Current (A)
Maximum Battery Recharge Current.
Max 20% of battery capacity (Ah).
Example: 100Ah – max. recharging current 20A.
Cells
Number of cells of the Battery, see “Float voltage”.
Example: 240 battery cells
- 40 blocks / 12Vdc Battery
- 80 blocks / 6Vdc Battery
- 240 blocks / 2Vdc Battery
Stop Operation Time
(min)
Residual Battery Autonomy time before UPS forced shut-down.
Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes.
NOTE !
The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the Battery
Manufacturer.
Continue ►
Page 65
Critical Power
Modifications reserved
Page 65/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
2. Close UPS output switch Q1 (Pos. I).
Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
3. Connect the Battery to the UPS by closing the external Battery protections and close, if
present, the switch CB3 (option).
Attention: check the right DC polarities on both side of the switch/fuse holder!
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-Link has reached 800Vdc (see screen MEASURES / Rectifier)!
4. Insert the inverter performing the command “Inverter ON".
Before performing this procedure make sure that the LED 1 (Rectifier) and LED 3 (Booster/Battery
charger) are lit.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
Load is now supplied from Inverter.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status“LOAD
SUPPLIED BY INVERTER”.
END OF PROCEDURE
NOTE !
The Battery must be charged for at least 10 hours, in order to ensure the full backup
runtime in case of a Utility Failure.
Page 66
Critical Power
Modifications reserved
Page 66/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
Follow this procedure only in case the UPS system and the Load must be completely
powered-down.
Initial status:
Load supplied from Inverter.
1. Perform the command “System shutdown”.
Perform the command “System shutdown” through the
screen: Commands 1 / System shutdown / Shutdown
Load is disconnected from UPS.
Rectifier and Inverter are shut-down and all contactors are
opened.
LED 1 (Rectifier) and LED 2 (Inverter) are OFF.
LED ALARM is lit.
2. Open UPS output switch Q1 (Pos. O).
3. Disconnect the Battery from the UPS by opening, if present, the switch CB3 (option) and then
the external Battery protections.
Press “MUTE” key to reset Acoustical Alarm. LED ALARM remains lit.
NOTE !
Before performing the next procedure wait 5 minutes for DC-Link Capacitors
discharge.
Use the MEASURES/Rectifier screen to ensure that the DC-link1 and DC-link 2 voltage
has reached 10Vdc.
4. Disconnect the Utility from the input distribution.
All LEDs are OFF.
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
7.2.2 Complete shut-down of the TLE Series 225 - 500 as frequency converter
Page 67
Critical Power
Modifications reserved
Page 67/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
Make sure the UPS to be status of the activation of “System shutdown”, i. e. Q1 and
CB3 (option) closed and external Battery protection connected.
View of the Synoptic Diagram after
performed the command “System shutdown”:
All Contactors are open.
Rectifier, Inverter, Booster/Battery
charger and Static-Switch shut-down.
LED ALARM is lit.
1. Restore the command “System shutdown”.
Restore the command “System shutdown”
through the screen:
Commands 1 / System shutdown / Reset
2. Insert the inverter performing the command “Inverter ON".
Before performing this procedure make sure that the LED 1 (Rectifier) and LED 3 (Booster/Battery
charger) are lit.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status
“LOAD SUPPLIED BY INVERTER”.
END OF PROCEDURE
7.2.3 Restore to normal operation after “System shutdown”
Page 68
Critical Power
Modifications reserved
Page 68/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
Make sure the UPS to be status of the activation of EPO, i. e. Q1 CB3 (option) closed
and external Battery protection connected.
View of the Synoptic Diagramafter
activation of EPO (Emergency Power Off) with
Utility available:
All Contactors are open.
Rectifier, Inverter, Booster/Battery charger
and Static-Switch shut-down.
LED ALARM is lit.
1. Reset the EPO (Emergency Power Off) button.
Press “MUTE” key to reset Alarm and Acoustical Alarm.
LED ALARM remains lit.
2. Perform the “Inverter OFF” command.
Perform the “Inverter OFF” command from
the screen: Commands 1 / Inverter / OFF.
Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
3. Insert the inverter performing the command “Inverter ON".
Before performing this procedure make sure that the LED 1 (Rectifier) and LED 3 (Booster/Battery
charger) are lit.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram must display the status
“LOAD SUPPLIED BY INVERTER”.
END OF PROCEDURE
7.2.4 Restore to normal operation after EPO (Emergency Power Off)
Page 69
Critical Power
Modifications reserved
Page 69/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
WARNING !
Before proceeding to turn on the UPS system, ensure that the AC and DC external isolators are OFF, and prevent their inadverted operation.
Ensure that the Output Load distribution can be powered and all the Output Isolators are open.
LED 1 Rectifier
LED 2 Inverter
LED 3 Booster/ Battery charger
LED 4 Automatic Bypass
LED 5 LOAD on UPS
LED ALARM
LED LOAD PROTECTED
Command Inverter ON
Command Inverter OFF
Command
Module shutdown
Command
Module shutdown Reset
Command
System shutdown
Command
System shutdown Reset
1.
Switch-ON the Utility voltage, on all UPS units, from the input distribution (both Rectifier and
bypass if separated).
The UPS performs a “Self-test”.
A successful termination of the tests will be indicated with Overall test
results “OK”.
Commissioning cannot be continued should one or more tests result
to be negative. Please contact in this case your Service Center.
At this stage the Electronic Power Supply and Control Panel are switched
ON and the Buzzer sounds.
Press “MUTE” key to reset Acoustical Alarm.
LED ALARM remains lit.
CB3
(Option)
ON
OFF
Q1
I ON
0 OFF
TLES_UL_225-250_S1_Switch Q1-Q2_01
Q2
I ON
0 OFF
TLES_UL_400-500_S1_Switch Q1-Q2_CB3_01
Q1
I ON
0 OFF
Q2
I ON
0 OFF
CB3
(Option)
ON
OFF
7.3 PROCEDURES FOR TLE SERIES 225 - 500 PARALLEL SYSTEM
7.3.1 TLE Series 225 - 500 Parallel System start-up
This procedure must be performed for the first start-up following the installation, with the Parallel
System completely switched Off and not powered.
Open the front door on all UPS units and make sure that:
All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
The safety screens are fixed in their position.
The switches Q1, Q2 and CB3 (option) are open (Pos. O) and the external Battery protectionsmust
be open (Pos. O).
Continue ►
Page 70
Critical Power
Modifications reserved
Page 70/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
WARNING !
The set-up of the UPS configuration parameters must be done only by QUALIFIED
AND TRAINED PERSONNEL.
The set-up of mistaken values could compromise the integrity and reliability of the
UPS.
UPS
Language
This parameter allows the choice of language used to display the
information.
Date (dd.mm.yyyy)
You can adjust the date of the real time clock existing in the UPS by the
means of this parameter.
The value you enter is thoroughly checked to be a correct date in the
format “DD.MM.YY”.
Time (24h)
You can adjust the time of the real time clock existing in the UPS by
means of this parameter.
The value you enter is thoroughly checked to be a correct time in the
format “HH.MM.SS”.
The time is specified in 24-hour format.
Input Frequency (Hz)
Input frequency value (50 Hz / 60Hz).
Output Frequency (Hz)
Inverter output frequency value (50 Hz / 60Hz).
Inverter Voltage (V)
Output voltage PHASE/NEUTRAL of the inverter (220V / 230V / 240V).
During the first commissioning TLE Series 225 - 500 requests a set-up of the UPS configuration
parameters presented in the following “Power-Up” screen.
Without such configuration it is not possible to continue with the commissioning procedure.
Continue ►
Page 71
Critical Power
Modifications reserved
Page 71/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
BATTERY
Capacity (Ah)
Ah capacity of the Battery.
Recharge Mode
Recharge type of the Battery
- Normal Valve Regulated Lead Acid Battery (VRLA), NiCd
without boost-charge and Flooded Lead Acid
Battery without boost-charge.
- NiCd Nickel Cadmium Battery with boost-charge.
- Wet Lead Acid Boost Flooded Lead Acid Battery with boost-charge.
Float Voltage (V)
Voltage to maintain Battery Charging.
Float voltage = Number of battery cells x battery float voltage per cell.
Typical battery float voltage per cell (ask the battery manufacturer for
confirmation):
Valve Regulated Lead Acid Battery (VRLA):
2.27Vdc for cell
240 cells x 2.27Vdc = 545Vdc
NiCd Battery without boost-charge:
1.41Vdc for cell
284÷309 cells x 1.41Vdc = 401 ÷ 436Vdc
NiCd Battery with boost-charge:
1.41 (1.55 boost-charge) Vdc for cell
281 cells x 1.41Vdc = 397 (436) Vdc
Flooded Lead Acid Battery without boost-charge:
2.23Vdc for cell
180÷195 cells x 2.23Vdc = 402 ÷ 435Vdc
Flooded Lead Acid Battery with boost-charge:
2.23 (2.35 boost-charge) Vdc for cell
180÷185 cells x 2.23Vdc = 402 (423) ÷ 413 (435) Vdc
Recharge Current (A)
Maximum Battery Recharge Current.
Max 20% of battery capacity (Ah).
Example: 100Ah – max. recharging current 20A.
Cells
Number of cells of the Battery, see “Float voltage”.
Example: 240 battery cells
- 40 blocks / 12Vdc Battery
- 80 blocks / 6Vdc Battery
- 240 blocks / 2Vdc Battery
Stop Operation Time
(min)
Residual Battery Autonomy time before UPS forced shut-down.
Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes.
NOTE !
The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the Battery
Manufacturer.
Continue ►
Page 72
Critical Power
Modifications reserved
Page 72/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
2. Close UPS output switch Q1 (Pos. I) on all Units.
When closing UPS output switch Q1 on the last unit of the Parallel System, the Automatic Bypass of all
Units connects to the Load.
Rectifiers start automatically, blinking LED 1 (Rectifier) indicates Soft-start.
At the end of Rectifier Soft-start, the LED 1 (Rectifier) remains lit.
The Synoptic Diagram, on all UPS units, must display the status“LOAD SUPPLIED BY AUTOMATIC BYPASS”.
Synoptic Diagram of first unit
Synoptic Diagram of other units
3. Connect the Battery on all Units by closing the external Battery protections and close, if
present, the switch CB3 (option).
Attention: check the right DC polarities on both side of the switch/fuse holder!
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-Link has reached 800Vdc (see screen MEASURES / Rectifier)!
Before performing the next procedure make sure that the LED 3 (Booster/Battery charger) is lit.
Synoptic Diagram of first unit
Synoptic Diagram of other units
4. Insert the Inverter performing the “Inverter ON” command on first unit.
Perform the “Inverter ON” command from the screen:
Commands 1 / INVERTER / ON.
Soft-start of Inverter, indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
In case of sufficient output power, the output will transfer to Inverter.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
Synoptic Diagram of first unit
Synoptic Diagram of other units
Continue ►
Page 73
Critical Power
Modifications reserved
Page 73/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
5. Insert the Inverter performing the “Inverter ON” command on all other units.
Do not start the next Inverter until the sequence of the previous ends.
Perform the “Inverter ON” command from the screen:
Commands 1 / INVERTER / ON.
Soft-start of Inverter indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with
running Inverter will transfer to Inverter.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram, on all UPS units, must display the status “LOAD SUPPLIED BY INVERTER”.
Synoptic Diagram of first unit
Synoptic Diagram of other units
5. Operation mode selection.
TLE Series 225 - 500 is delivered normally selected for permanent VFI operation.
The eBoost™ Operation Mode can be enabled and the eBoost Start Time & eBoost Stop Time can be
programmed for each day of the week (see Section 6.4 SETUP / eBoost).
END OF PROCEDURE
NOTE !
The Battery must be charged for at least 10 hours, in order to ensure the full backup
runtime in case of a Utility Failure.
Page 74
Critical Power
Modifications reserved
Page 74/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
Initial status:
Load supplied from all Inverters of the Parallel
System.
1. Disconnect the Inverter performing the “Inverter OFF” command on all Units.
1 - Perform the “Inverter OFF” command from the
screen: Commands 1 / Inverter / OFF.
2 - Repeat the “Inverter OFF” command from the
screen: Commands 1 / Inverter / OFF.
At no redundancy, the system will transfer to Utility supply. LED 2 (Inverter) is Off.
LED ALARM is lit.
The Synoptic Diagram, on all UPS units, must display the status“LOAD SUPPLIED BY AUTOMATIC BYPASS”.
Synoptic Diagram of first unit
Synoptic Diagram of other units
2. Close Manual Bypass switch Q2 (Pos. I) on all Units.
Load is now supplied from Utility in parallel from Automatic Bypass and Manual Bypass Q2 of all Units.
The Synoptic Diagram, on all UPS units, must display the status “LOAD SUPPLIED BY AUTOMATIC BYPASS AND MANUAL BYPASS Q2”.
Synoptic Diagram of first unit
Synoptic Diagram of other units
7.3.2 Parallel UPS shut-down with load transfer on Manual Bypass Q2
Continue ►
Page 75
Critical Power
Modifications reserved
Page 75/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
3. Open UPS output switch Q1 (Pos. O) and perform the command “System shutdown” on all
Units.
Perform the command “System shutdown” through the
screen: Commands 1 / System shutdown / Shutdown.
The Load is now supplied only through the Manual Bypass Q2 of all Units.
All Rectifiers are shut-down and all output and input contactors are opened.
The Synoptic Diagram, on all UPS units, must display the status “LOAD SUPPLIED BY MANUAL BYPASS Q2”.
Synoptic Diagram of first unit
Synoptic Diagram of other units
4. Disconnect the Battery on all Units by opening, if present, the switch CB3 (option) and then the
external Battery protections.
Press “MUTE” key to reset Acoustical Alarm. LED ALARM remains lit.
Synoptic Diagram of first unit
Synoptic Diagram of other units
END OF PROCEDURE
DANGER !
The UPS cabinet contains parts electrically live.
Apart from the front door, do not open any other part of the UPS.
Page 76
Critical Power
Modifications reserved
Page 76/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Initial status:
Load supplied from all Manual Bypass Q2 of
the Parallel System.
All Manual Bypass Q2 of the Parallel System
are closed.
1. Close UPS output switch Q1 (Pos. I) on all Units.
The Rectifiers will start automatically and at the closure of UPS output switch Q1 of the last Unit, the
output will be supplied parallel from Automatic Bypass and Manual Bypass Q2 of all UPS units.
Soft-start of Rectifiers, indicated with blinking LEDs 1 (Rectifier).
At the end of Rectifiers Soft-start, the LEDs 1 (Rectifier) remains lit.
The Synoptic Diagram, on all UPS units, must display the status “LOAD SUPPLIED BY AUTOMATIC BYPASS
AND MANUAL BYPASS Q2”.
Synoptic Diagram of first unit
Synoptic Diagram of other units
2. Connect the Battery on all Units by closing the external Battery protections and close, if
present, the switch CB3 (option).
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-Link has reached 800Vdc (see screen MEASURES / Rectifier)!
Before performing the next procedure make sure that the LED 3 (Booster/Battery charger) is lit.
Synoptic Diagram of first unit
Synoptic Diagram of other units
7.3.3 From Manual Bypass Q2 to normal function VFI
Continue ►
Page 77
Critical Power
Modifications reserved
Page 77/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
3. Open Manual Bypass switch Q2 (Pos. O) on all Units.
The Load is supplied by the Utility through the Automatic Bypass of all Units of the Parallel System.
The Synoptic Diagram, on all UPS units, must display the status“LOAD SUPPLIED BY AUTOMATIC BYPASS”.
Synoptic Diagram of first unit
Synoptic Diagram of other units
4. Insert the Inverter performing the “Inverter ON” command on first unit.
Before performing this procedure make sure that the LED 1 (Rectifier) and LED 3 (Booster/Battery
charger) are lit.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter, indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
In case of sufficient output power, the output will transfer to Inverter.
Synoptic Diagram of first unit
Synoptic Diagram of other units
5. Insert the Inverter performing the “Inverter ON” command on all other units.
Do not start the next Inverter until the sequence of the previous ends.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with
running Inverter will transfer to Inverter.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram, on all UPS units, must display the status “LOAD SUPPLIED BY INVERTER”.
Synoptic Diagram of first unit
Synoptic Diagram of other units
END OF PROCEDURE
Page 78
Critical Power
Modifications reserved
Page 78/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
NOTE !
The Load is powered by the UPS Redundant Parallel System.
One UPS unit of the Parallel System has to be turned Off, while the Load is shared
between the other units supplying the parallel bus.
WARNING !
The control bus cable connecting J1A - J2A and J1B - J2B cannot be connected or
disconnected after the system has been powered on.
Initial status:
Load supplied from all Inverters of the
Redundant Parallel System.
1. Disconnect the Inverter performing the “Inverter OFF” command on the Unit to separate.
1 - Perform the “Inverter OFF” command from the screen:
Commands 1 / Inverter / OFF.
2 - Repeat the “Inverter OFF” command from the screen:
Commands 1 / Inverter / OFF.
With redundant system, performing the “Inverter OFF” command the Inverter shuts down and it will stay OFF.
Performing the “Inverter OFF” command the Load is transferred to the Utility and the Inverter remains
operating, it means the system is not redundant.
In this case is not possible to switch-OFF one unit without transferring the Load on Utility.
Load supplied from Inverter(s) of the other Unit(s) of the Parallel System.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
2. Open UPS output switch Q1 (Pos. O) on the Unit to separate.
LED ALARM is lit.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
7.3.4 Separate a UPS unit from the Redundant Parallel System
Continue ►
Page 79
Critical Power
Modifications reserved
Page 79/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
3. Perform the command “Module shutdown” on the
Unit to separate only when the symbol Q1 in the
Synoptic Diagram is shown open.
Perform the command “Module shutdown” through the
screen: Commands 1 / Module shutdown / Shutdown.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
4. Disconnect the Battery on the Unit to separate by opening, if present, the switch CB3 (option)
and then the external Battery protections.
Press “MUTE” key to reset Acoustical Alarm. LED ALARM remains lit.
NOTE !
Before performing the next procedure wait 5 minutes for DC-Link Capacitors
discharge.
Use the MEASURES/Rectifier screen to ensure that the DC-link1 and DC-link 2 voltage
has reached 10Vdc.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
5. Disconnect the Utility supply on the Unit to separate.
Synoptic diagram of the unit to separate
Synoptic diagram of other units
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
NOTE !
For any further intervention contact nearest Service Center.
Page 80
Critical Power
Modifications reserved
Page 80/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE:
The Load is still powered by the other units supplying the parallel bus.
This UPS unit will be powered on and connected to the parallel bus in order to
share the Load with each other's.
The high speed bus cable connecting J1A - J2A and J1B - J2B in any case cannot be
connected or disconnected after the system has been powered on.
The bus terminals must be properly connected before powering the additional
unit.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
1.
Switch-ON the Utility voltage, on the Unit to reconnect, from the input distribution (both
Rectifier and bypass if separated).
At this stage the Electronic Power Supply and Control Panel are switched ON and the Buzzer sounds.
Press “MUTE” key to reset Acoustical Alarm.
LED ALARM remains lit.
Synoptic diagram of the unit to reconnect
Synoptic diagram of other units
2. Close UPS output switch Q1 (Pos. I) on the Unit to reconnect.
Rectifier starts automatically.
LED 1 (Rectifier) blinking, indicates Soft-start.
At the end of Rectifier Soft-start the LED 1 (Rectifier) remains lit.
Synoptic diagram of the unit to reconnect
Synoptic diagram of other units
7.3.5 Reconnect a UPS unit to Redundant Parallel System
Open the front door, of the Unit to reconnect, and make sure that:
All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
The protection panels are fastened in their correct position.
The switches Q1, Q2 and CB3 (option) are open (Pos. O) and the external Battery protectionsmust
be open (Pos. O).
Continue ►
Page 81
Critical Power
Modifications reserved
Page 81/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
3. Connect the Battery on the Unit to reconnect by closing the external Battery protections and
close, if present, the switch CB3 (option).
NOTE !
Ensure the LED 1 (Rectifier) is lit before carrying out this procedure.
It indicates that the DC-Link has reached 800Vdc (see screen MEASURES / Rectifier)!
Before performing the next procedure make sure that the LED 3 (Booster/Battery charger) is lit.
Synoptic diagram of the unit to reconnect
Synoptic diagram of other units
4. Insert the inverter performing the command "Inverter ON” on the Unit to reconnect.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
After Soft-start of the Inverter, the Inverter connects automatically to the other Units of the Parallel
System.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram, on all UPS units, must display the status “LOAD SUPPLIED BY INVERTER”.
Synoptic diagram of the unit to reconnect
Synoptic diagram of other units
END OF PROCEDURE
Page 82
Critical Power
Modifications reserved
Page 82/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
The UPS Parallel System and the Load have to be completely powered down.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
Initial status:
Load supplied from all Inverters of the Parallel System.
1. Perform the command “System shutdown” on anyone of
the units.
Perform the command “System shutdown” through the screen:
Commands 1 / System shutdown / Shutdown.
Load is disconnected from UPS Parallel System.
Rectifiers and Inverters are shut down and all Contactors are opened.
LED ALARM is lit.
Synoptic diagram of first unit
Synoptic diagram of other units
2. Open UPS output switch Q1 (Pos. O) on all Units.
Synoptic diagram of first unit
Synoptic diagram of other units
3. Disconnect on all Units the Battery from the UPS by opening, if present, the switch CB3 (option)
and then the external Battery protections.
Press “MUTE” key to reset Acoustical Alarm. LED ALARM remains lit.
Wait 5 minutes for DC-Link Capacitors discharge. Use the MEASURES/Rectifier screen to ensure that the
DC-link1 and DC-link 2 voltage has reached 10Vdc.
4. Disconnect the Utility supply on all Units.
All LEDs are OFF.
Synoptic diagram of first unit
Synoptic diagram of other units
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
7.3.6 Complete Parallel System shut-down
Page 83
Critical Power
Modifications reserved
Page 83/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
Make sure the all units of the Parallel System to be status of the activation of
“System shutdown”, i. e. Q1 and CB3 (option) closed, Q2 open and External Battery
Protection connected.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
View of the Synoptic Diagram, on all UPS
units, after performed the command
“System shutdown”:
All Contactors are open.
Rectifier, Inverter, Booster/Battery
charger and Static-Switch shut-down.
LED ALARM is lit.
1. Restore the command “System shutdown” of
the Parallel System.
Restore the command “System shutdown”, on
anyone of the parallel units, through the
screen: Commands 1 / System shutdown / Reset.
The Load is supplied by the Utility through the
Automatic Bypass of all Units.
Rectifiers start automatically, blinking LED 1
(Rectifier) indicates Soft-start.
At the end of Rectifier Soft-start, the LED 1
(Rectifier) remains lit.
LED ALARM are lit.
The Synoptic Diagram, on all UPS units, must display the status “LOAD SUPPLIED BY AUTOMATIC BYPASS”.
Synoptic diagram of first unit
Synoptic diagram of other units
7.3.7 Restore to normal operation after “System shutdown”
Continue ►
Page 84
Critical Power
Modifications reserved
Page 84/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
2. Insert the Inverter performing the “Inverter ON” command on first unit.
Before performing this procedure make sure that the LED 1 (Rectifier) and LED 3 (Booster/Battery
charger) are lit.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter, indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
In case of sufficient output power, the output will transfer to Inverter.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
Synoptic diagram of first unit
Synoptic diagram of other units
3. Insert the Inverter performing the “Inverter ON” command on all other units.
Do not start the next Inverter until the sequence of the previous ends.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with
running Inverter will transfer to Inverter.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram, on all UPS units, must display the status “LOAD SUPPLIED BY INVERTER”.
Synoptic diagram of first unit
Synoptic diagram of other units
END OF PROCEDURE
Page 85
Critical Power
Modifications reserved
Page 85/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
Make sure the all units of the Parallel System to be status of the activation of EPO, i.
e. Q1 and CB3 (option) closed, Q2 open and External Battery Protection connected.
If eBoost™ option is available, make sure that eBoost™ Operation Mode is disabled
before starting this procedure.
View of the Synoptic Diagram, on all UPS units,
after activation of EPO (Emergency Power Off)
with Utility available:
All Contactors are open.
Rectifier, Inverter, Booster/Battery charger
and Static-Switch shut-down.
LED ALARM is lit.
1. Reset the EPO (Emergency Power Off) button.
Press “MUTE” key to reset Alarm and Acoustical Alarm.
LED ALARM remain lit.
2. Perform the “Inverter OFF” command on all Units.
Perform the “Inverter OFF” command from the screen:
Commands 1 / Inverter / OFF.
After performed the “Inverter OFF” command on the last unit of the Parallel System, the output of all
Units connect to Automatic Bypass.
The Synoptic Diagram, on all UPS units, must display the status“LOAD SUPPLIED BY AUTOMATIC BYPASS”.
Synoptic diagram of first unit
Synoptic diagram of other units
7.3.8 Restore to normal operation after EPO (Emergency Power Off)
Continue ►
Page 86
Critical Power
Modifications reserved
Page 86/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
3. Insert the Inverter performing the “Inverter ON” command on first unit.
Before performing this procedure make sure that the LED 1 (Rectifier) and LED 3 (Booster/Battery
charger) are lit.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter, indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
In case of sufficient output power, the output will transfer to Inverter.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
Synoptic diagram of first unit
Synoptic diagram of other units
4. Insert the Inverter performing the “Inverter ON” command on all other units.
Do not start the next Inverter until the sequence of the previous ends.
Perform the “Inverter ON” command from the screen:
Commands 1 / Inverter / ON.
Soft-start of Inverter indicated with blinking LED 2 (Inverter).
At the end of Soft-start the LED 2 (Inverter) remains lit.
As soon as the output power of the Inverters is sufficient to supply the Load, the output of the units with
running Inverter will transfer to Inverter.
LED ALARM turns Off and the LED LOAD PROTECTED must be lit.
The Synoptic Diagram, on all UPS units, must display the status “LOAD SUPPLIED BY INVERTER”.
Synoptic diagram of first unit
Synoptic diagram of other units
END OF PROCEDURE
Page 87
Critical Power
Modifications reserved
Page 87/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
3-ph SNMP/WEB plug-in adapter
SNMP - Simple Network Management Protocol
The 3-ph SNMP/WEB plug-in adapter is an interface to the Ethernet
Network, and provides UPS information via the standard SNMP
Protocol (UPS-MIB (RFC-1628); GE Single MIB; GE Parallel MIB). The UPS can therefore be managed by a Network Management
System (NMS) or by our applications (for instance GE iUPSGuard or
GE Data Protection), which uses this information to determine the
state of the UPS in order to guarantee safe and orderly shutdown of the server, when needed.
GE iUPSGuard
GE’s iUPSGuard is a remote monitoring solution for UPS, providing
status monitoring and alarm notification that supports all GE UPS
product lines, anytime, anywhere.
iUPSGuard provides current and detailed information about UPS
operation, including its configuration, internal alarms and
operating conditions over web.
iUPSGuard notifies personnel of critical alarms and events via
email or SMS, allowing a user or GE technician to make timely
decisions on critical conditions.
In addition, comprehensive data collection and analysis improves
diagnostics capability and enhances response time.
Continuous monitoring and ongoing maintenance help ensure
maximum performance of your UPS equipment as it protects
business critical applications.
GE Data Protection
GE Data Protection software can communicate with the UPS over
RS-232, USB or SNMP to receive status information and
measurement values of the UPS. In case of a critical condition
(time on battery, remaining battery autonomy time or low battery)
for the Load, the software starts a controlled shut-down.
An enhanced alarm management system provides the possibility
to start applications, send messages, and send e-mails for every
upcoming or disappearing alarm.
eBoost™ Operation Mode
High efficiency operating mode, where the load is supplied directly by utility
and automatically transferred to inverter if the voltage is out of prescribed
tolerances.
RPA Kit
Redundant Parallel Architecture
Up to 6 units parallel possible for redundancy or capacity in RPA
configuration.
8 OPTIONS
8.1 CONNECTIVITY OPTIONS
8.2 OPTIONS IN UPS CABINET
Page 88
Critical Power
Modifications reserved
Page 88/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
WARNING !
All maintenance and service works must be performed by QUALIFIED SERVICE
PERSONNEL.
9 MAINTENANCE
9.1 MAINTENANCE
A UPS system, like other electrical equipment, needs periodic preventive maintenance.
A regular maintenance check of your installation guarantees higher reliability of your safe power supply.
GE’s Critical Power recommends to perform the first service within 12 months from the commissioning
date or within 18 months from delivery date.
Subsequent services to perform every 12 months.
Preventive maintenance work on the UPS can be done only by trained SERVICE TECHNICIANS.
We therefore recommend you sign a Maintenance and Service contract with the local Service Center
organization.
9.1.1 Service check
If this lamp lights up during normal operation, the unit has not been serviced for the last 20,000 hours by
a GE TRAINED TECHNICIAN.
Some components of the UPS which need periodic maintenance, if not replaced, could cause a reliability
reduction of the supply system
We highly recommend that you contact your Service Center for preventive maintenance work.
9.1.2 Fans and ventilation
We recommend a periodic cleaning of the ventilation channels and grids on the UPS system, in order to
guarantee proper air circulation in the unit and in the Battery.
The fans eventually wear out and must be substituted when a UPS alarm is triggered, in order to ensure
the reliability of the UPS
9.1.3 Other components with limited lifetime
Various components, such as the DC and AC filter capacitors and the lithium battery on the “P3 -Control
Panel” (memory saving), must be systematically substituted in order to maintain the UPS’S reliability.
The substitution of these components is signaled by a UPS alarm going off.
Page 89
Critical Power
Modifications reserved
Page 89/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
Ask to your local Service Center to submit the form of Preventive Maintenance Contract suitable for your specific needs.
9.1.4 Battery
We recommend a periodic Manual Battery Test, especially if the Automatic Battery Test is disabled, in
order to verify if the Battery can provide the expected backup time in case of Utility Failure.
We recommend that this test is performed at least every 3 months, especially if the Battery is not
sufficiently discharged during normal operation.
The discharge time you use should be at least half of the Battery runtime.
For Automatic Battery Test setting, a special code is required to enter user set-up parameters.
The start-up technician has access to this code and can program this feature during start-up.
Please consider that, if you did a full Battery Test to verify the full runtime of the Battery, the charger
needs at least 8 hours to recharge the Battery up to 90% of its capacity.
Long shut-down periods of the UPS system
To guarantee that the Battery is fully charged, the UPS system should be in operation for at least 12
hours every 3 months.
If not the Battery may be permanently damaged.
9.1.5 UPS room conditions and temperature
The UPS room and the Battery Room have to be maintained clean and free from dust.
A high temperature of the UPS room and of the Battery Room affect the lifetime of several components
inside the equipment.
The Battery is very sensitive to room temperatures above 77°F (25°C).
9.1.6 Preventive maintenance program
a) Cleaning, a visual inspection and a mechanical inspection of the UPS modules.
b) Replacement of defective parts or the preventive replacement of parts with a defined lifetime.
c) “Updating” of the equipment (technical improvements subsequent to the delivery).
d) Check the calibration of DC voltage and Inverter Output Voltage and Frequency.
e) Check of the settings of the electronic regulation, the control and the alarm circuits of the
Rectifier(s) and Inverter(s).
f) Functional checks on Thyristors, Diodes, Transformers, Filter Components, e.g. to ensure that they
are operating within the specified design parameters.
g) Overall performance test including a Utility Failure simulation with and without the Load.
h) Monitoring Battery operation in discharge and recharge mode including any boost charge duties.
Page 90
Critical Power
Modifications reserved
Page 90/90
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Date
Description
Done by
10 NOTES
10.1 NOTES FORM
It is recommended to note in this section Notes, with date and short description all the operations
performed on the UPS, as: maintenance, components replacement, abnormal situations, etc.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.