
GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Table of content Page
1 IMPORTANT SAFETY INSTRUCTIONS................................................................................................................................................... 6
2 LAYOUT .................................................................................................................................................................................................... 9
2.1 LAYOUT TLE SERIES 225 & 250 .................................................................................................................................................................................. 9
2.2 LAYOUT TLE SERIES 400 & 500 ............................................................................................................................................................................... 10
3 INTRODUCTION ................................................................................................................................................................................... 11
4 DESCRIPTION ....................................................................................................................................................................................... 12
4.1 BLOCK DIAGRAM AND MAIN ELEMENTS ............................................................................................................................................................ 13
4.2 OPERATION MODES..................................................................................................................................................................................................... 14
4.2.1 Normal VFI Operation Mode (Voltage Frequency Independent) ............................................................................................................................ 14
4.2.2 eBoost™ Operation Mode (option) ........................................................................................................................................................................................ 14
4.2.3 Utility Failure Operation .............................................................................................................................................................................................................. 15
4.2.4 Utility Recovery Operation ......................................................................................................................................................................................................... 15
4.2.5 Automatic Bypass .......................................................................................................................................................................................................................... 16
4.2.6 Manual Bypass ................................................................................................................................................................................................................................ 16
4.3 RPA PARALLEL SYSTEM OPERATION .................................................................................................................................................................... 17
4.3.1 Introduction to the RPA Parallel System ............................................................................................................................................................................. 17
4.3.2 Features of RPA Parallel System ............................................................................................................................................................................................. 18
4.3.3 System control................................................................................................................................................................................................................................. 18
4.3.4 Synchronization .............................................................................................................................................................................................................................. 18
4.3.5 Load sharing ..................................................................................................................................................................................................................................... 18
4.4 SERVICE AND TECHNICAL SUPPORT .................................................................................................................................................................... 19
4.5 WARRANTY ..................................................................................................................................................................................................................... 19
4.6 RECYCLING INSTRUCTIONS ..................................................................................................................................................................................... 20
5 CONTROL PANEL ................................................................................................................................................................................. 21
5.1 CONTROL PANEL .......................................................................................................................................................................................................... 21
6 LCD SCREEN ......................................................................................................................................................................................... 22
6.1 HOME SCREEN ............................................................................................................................................................................................................... 22
6.1.1 Description of the selection keys ........................................................................................................................................................................................... 23
6.1.2 Description of the signalling LEDs ......................................................................................................................................................................................... 24
6.2 MEASURES ....................................................................................................................................................................................................................... 26
6.3 EVENTS ............................................................................................................................................................................................................................. 30
6.3.1 Events (alarms and messages) ................................................................................................................................................................................................ 32
6.3.2 Alarms list .......................................................................................................................................................................................................................................... 32
6.3.3 Messages list .................................................................................................................................................................................................................................... 37
6.4 SETUP ................................................................................................................................................................................................................................ 40
6.5 COMMANDS .................................................................................................................................................................................................................... 44
6.6 RPA PARALLEL SYSTEM .............................................................................................................................................................................................. 48
7 OPERATION .......................................................................................................................................................................................... 50
7.1 PROCEDURES FOR SINGLE TLE SERIES 225 - 500 .......................................................................................................................................... 52
7.1.1 Initial start-up of the TLE Series 225 - 500 ........................................................................................................................................................................ 52
7.1.2 UPS shut-down with load transfer on Manual Bypass Q2 ........................................................................................................................................ 56
7.1.3 From Manual Bypass Q2 to normal function VFI ........................................................................................................................................................... 58
7.1.4 Complete UPS shut-down .......................................................................................................................................................................................................... 59
7.1.5 Restore to normal operation after “System shutdown” ............................................................................................................................................. 60
7.1.6 Restore to normal operation after EPO (Emergency Power Off) ............................................................................................................................ 61
7.2 PROCEDURES SINGLE TLE SERIES 225 - 500 FUNCTIONING AS FREQUENCY CONVERTER ......................................................... 62
7.2.1 Initial Start-up of the TLE Series 225 - 500 as frequency converter ..................................................................................................................... 62
7.2.2 Complete shut-down of the TLE Series 225 - 500 as frequency converter ...................................................................................................... 66
7.2.3 Restore to normal operation after “System shutdown” ............................................................................................................................................. 67
7.2.4 Restore to normal operation after EPO (Emergency Power Off) ............................................................................................................................ 68
7.3 PROCEDURES FOR TLE SERIES 225 - 500 PARALLEL SYSTEM ................................................................................................................... 69
7.3.1 TLE Series 225 - 500 Parallel System start-up ................................................................................................................................................................. 69
7.3.2 Parallel UPS shut-down with load transfer on Manual Bypass Q2 ....................................................................................................................... 74
7.3.3 From Manual Bypass Q2 to normal function VFI ........................................................................................................................................................... 76
7.3.4 Separate a UPS unit from the Redundant Parallel System ....................................................................................................................................... 78
7.3.5 Reconnect a UPS unit to Redundant Parallel System .................................................................................................................................................. 80
7.3.6 Complete Parallel System shut-down ................................................................................................................................................................................. 82
7.3.7 Restore to normal operation after “System shutdown” ............................................................................................................................................. 83
7.3.8 Restore to normal operation after EPO (Emergency Power Off) ............................................................................................................................ 85
8 OPTIONS ............................................................................................................................................................................................... 87
8.1 CONNECTIVITY OPTIONS ........................................................................................................................................................................................... 87
8.2 OPTIONS IN UPS CABINET ........................................................................................................................................................................................ 87
9 MAINTENANCE .................................................................................................................................................................................... 88
9.1 MAINTENANCE .............................................................................................................................................................................................................. 88
9.1.1 Service check ................................................................................................................................................................................................................................... 88
9.1.2 Fans and ventilation ..................................................................................................................................................................................................................... 88
9.1.3 Other components with limited lifetime ............................................................................................................................................................................. 88
9.1.4 Battery ................................................................................................................................................................................................................................................. 89
9.1.5 UPS room conditions and temperature .............................................................................................................................................................................. 89
9.1.6 Preventive maintenance program ........................................................................................................................................................................................ 89
10 NOTES ................................................................................................................................................................................................... 90
10.1 NOTES FORM .................................................................................................................................................................................................................. 90

GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
GENERAL
- Move the UPS in an upright position in its original package to the final destination room.
To lift the cabinets, use a forklift or lifting belts with spreader bars.
- Check for sufficient floor and elevator loading capacity.
- Check the integrity of the UPS equipment carefully.
If you notice visible damage, do not install or start the UPS.
Contact the nearest Service Center immediately.
- WARNING! RISK OF ELECTRICAL SHOCK:
Do not remove covers, there are no user serviceable parts inside.
- After switching off takes 5 minutes for the DC capacitors to discharge because a lethally high voltage
remains at the terminals of the electrolytic capacitors.
- All maintenance and service work should be performed by qualified service personnel.
The UPS contains its own energy source (battery).
- The field-wiring outlets may be electrically live, even when the UPS is disconnected from the utility.
- Dangerous voltages may be present during battery operation.
- The battery must be disconnected during maintenance or service work.
- This UPS contains potentially hazardous voltages.
- Be aware that the inverter can restart automatically after the utility voltage is restored.
- End user must follow applicable regional occupational safety codes/regulations during installation,
operation and equipment maintenance. This may require additional field marking or labeling defining
appropriate level of PPE (Personal Protection Equipment) to reduce the risk of Arc-flash related injuries.
Contact our Technical Support for product specific information.
INSTALLATION
- This UPS must be installed and connected only by trained personnel.
- Verify accurately during Commissioning and Maintenance of the UPS, for the following:
Damaged components, squeezed wires and cables, or not correctly inserted plugs.
- After removing the sidewalls of the UPS, make sure that all earth connections when reassembling, are
correctly reattached.
- This UPS is intended for use in a controlled indoor environment free of conductive contaminants and
protected against animals intrusion.
- WARNING! HIGH EARTH LEAKAGE CURRENT:
Earth connection is essential before connecting to AC input!
- Switching OFF the unit does not isolate the UPS from the utility.
- Do not install the UPS in an excessively humid environment or near water.
- Avoid spilling liquids on or dropping any foreign object into the UPS.
- The unit must be placed in a sufficiently ventilated area; the ambient temperature should not exceed 104F
(40°C).
- Optimal battery life is obtained if the ambient temperature does not exceed 77°F (25C).
- It is important that air can move freely around and through the unit. Do not block the air vents.
- Avoid locations in direct sunlight or near heat sources.
STORAGE
- Store the UPS in a dry location; storage temperature must be within -13°F (-25°C) to 131°F (+55C).
- The optimal temperature for Battery storage is 68°F (20°C) to 77°F (25°C) and shall never exceed the range -
4°F (-20°C) to 104°F (40°C).
- If the unit is stored for a period exceeding 3 months, the battery must be recharged periodically (time
depending on storage temperature).
BATTERY
- The battery-voltage is dangerous for person’s safety.
- When replacing the battery, use the same cells number, voltage (V), capacity (Ah).
All the battery used, shall be of the same manufacturer and date of production.
- Proper disposal or recycling of the battery is required.
Refer to your local codes for disposal requirements.
- Never dispose of battery in a fire: they may explode.
- Do not open or mutilate battery: their contents (electrolyte) may be extremely toxic.
If exposed to electrolyte, wash immediately with plenty of water.
- Avoid charging in a sealed container.
- Never short-circuit the batteries.
When working with batteries, remove watches, rings or other metal objects, and only use insulated tools.
- In case of air shipment, the cables +/- going to the battery fuses/terminals shall be disconnected and isolated.
1 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions for models TLE Series 225 - 500 that should be followed
during installation and maintenance of the UPS and battery.

GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
EXTERNAL BATTERY MUST BE INSTALLED AND CONNECTED TO THE UPS BY
QUALIFIED SERVICE PERSONNEL ONLY.
INSTALLATION PERSONNEL MUST READ THIS ENTIRE SECTION BEFORE HANDLING
THE UPS AND BATTERY.
DANGER!
Full voltage and current are always present at the battery terminals.
The battery used in this system can provide dangerous voltages, extremely high currents and a
risk of electric shock.
If the terminals are shorted together or to ground they may cause severe injury.
You must be extremely careful to avoid electric shock and burns caused by contacting battery
terminals or shorting terminals during battery installation.
Do not touch uninsulated battery terminals.
A qualified service person, who is familiar with battery systems and required precautions, must
install and service the battery.
The installation must conform to national and local codes.
Keep unauthorized personnel away from the battery.
The qualified service person must take these precautions:
1 Wear protective clothing, such as rubber gloves and boots and protective eye wear
Batteries contain caustic acids and toxic materials and can rupture or leak if mistreated.
Remove rings and metal wristwatches or other metal objects and jewelry.
Do not carry metal objects in your pockets where the objects can fall into the battery
cabinet.
2 Tools must have insulated handles and must be insulated so that they will not short battery
terminals.
Do not allow a tool to short between individual or separate battery terminals or to the
cabinet or rack.
Do not lay tools or metal parts on top of the battery, and do not lay them where they could
fall onto the battery or into the cabinet.
3 Install the battery as shown on the drawing provided with the battery.
When connecting cables, never allow a cable to short across a battery’s terminals, the
string of battery, or to the cabinet or rack.
4 Align the cables on the battery terminals so that the cable lug will not contact any part of
the cabinet or rack, even if the battery is moved.
Keep the cable away from any sharp metal edges.
5 Install the battery cables in such a way that the UPS or battery cabinet doors cannot pinch them.
6 Do not connect the battery terminal to Ground.
If any battery terminal is inadvertently grounded, remove the source of the ground.
Contacting any part of a grounded battery can cause a risk of electric shock.
7 To reduce the risk of fire or electric shock, install the battery in a temperature and humidity
controlled indoor area, free of contaminants.
8 Battery system chassis ground (earth) must be connected to the UPS chassis ground (earth).
If you use conduits, this ground conductor must be routed in the same conduit as the
battery conductors.
9 Where conductors may be exposed to physical damage, protect the conductors in
accordance with all applicable codes.
10 If you are replacing the battery or repairing battery connections, shut OFF the UPS and
remove the battery fuses.
Safety instructions when working with battery

GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
TLE Series 225 - 500 is a truly VFI double conversion Uninterruptible Power Supply
(UPS), equipped with automatic bypass, where the load is normally supplied by the
inverter.
TLE Series 225 - 500 can be configured, if chosen, for the eBoost™ Operation Mode
(Option - High efficiency: up to 99% / Fast power transfer: <2ms) permitting
maximum energy saving.
If the Inverter is not able to supply the required Output Voltage, or when overload or
short-circuit on the output occur, the Load is instantly transferred to the Mains via
the Automatic Bypass.
The UPS automatically returns to normal mode when the failure condition is
restored.
3 INTRODUCTION
The TLE Series 225 - 500 Uninterruptible Power Supply (UPS) provides the energy supply for critical
loads which need a reliable, continuous free from voltage disturbances and frequency fluctuations
supply.
In case the power provided by the Mains Fails, or exceeds the permitted tolerances, the power to supply
the Load is provided by the Battery for the specified time at the rated Load (or longer at a reduced Load)
or until the Mains power returns.
KEY FEATURES:
More Critical equipment supported
Rated at 1 Power Factor, TLE Series 225 - 500 delivers more real power than other UPS in the market.
With today’s trend toward power factor corrected loads, TLE Series 225 - 500 can support more total
Load than any other UPS available, allowing you to support a greater number of today’s enterprise
computing Power Factor Corrected (PFC) equipment.
High Efficiency
Thanks to type Advanced Neutral Point Clamped three level IGBT technology, TLE Series 225 - 500
guarantees a high overall performance.
Intelligent Energy Management (IEM) combined with RPA, results in the most cost efficient and reliable
UPS solution in the industry.
Fully digital
Digital Signal Processor (DSP), Flash memory and Advanced Neutral Point Clamped are the technology
corner stones of a new age of power quality and power reliability.
RPA™ - Redundant Parallel Architecture™ Parallel System
GE’s Critical Power provides a unique technology called Redundant Parallel Architecture™ (RPA™) that
can parallel Uninterruptible Power Supply (UPS) modules with true redundancy.
With RPA™, there is no need for external electronics or switches to control the UPS modules in the
parallel system.
One of the UPS modules in the system arbitrarily takes a leadership role, while the other UPS modules
have access to all control parameters.
If one UPS fails to operate, the load is automatically redistributed among the others.
If the lead UPS fails to operate then a different UPS automatically takes on the leadership role.
The RPA™ systems are designed to have no single points of failure, ensuring the highest level of power
protection for critical loads.
Extremely flexible
Tailor made power protection to meet your individual installation requirements; TLE Series 225 - 500
offers various options like EMC filter and our comprehensive software for mission control and data
protection to cover all your application needs.

GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
TLE Series 225 - 500 is one of the best
performing and most reliable three-phase UPS
systems providing critical power protection for
a wide range of applications.
Every TLE Series 225 - 500 system operates in
VFI mode (Voltage Frequency Independent)
yielding the maximum levels of power reliability
for all mission-critical processes.
NOTE !
Through their complete life cycle, all GE‟s Critical Power UPS systems are fully
supported by service teams which provide world-class, 24x7 preventive and
corrective services, training and application expertise.
TLES_UL_225-250_S1_UPS_GE_01
TLE Series 225 & 250
TLE Series 400 & 500
4 DESCRIPTION
With proven technology the TLE Series 225 - 500 UPS provides top class reliability and performance.
With backfeed protection and compliance to EMC standards the TLE Series 225 - 500 complies to current
standards.
Reliability can be further increased by paralleling up to six UPS units utilising GE’s unique RPA™
technology (Redundant Parallel Architecture).
With RPA every UPS is controlled in a true peer-to-peer configuration with redundancy in all critical
elements and functions, eliminating all single points of failure.
The decentralized bypass offers great flexibility to up or down grade the system in case future needs
might change.
TLE Series 225 - 500, BEST IN CLASS EFFICIENCY
High efficiency in double conversion mode up to 96.5% and eBoost™ operation mode up to 99%.
High efficiency at partial and reduced loads for cost benefits in operating conditions.
TLE Series 225 - 500 products designed in compliance with UL 1779 standard, C3 level for immunity,
i.e. can withstand possible disturbances and noise without affecting standard operating conditions.
Advanced User Interface with touch screen display guided menu.
Reduced energy consumption costs.
Reduced size and costs of the air conditioning system.
Compact design, saving installation space.

GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
Fig. 4.1-1 Block Diagram TLE Series 225 - 500
4.1 BLOCK DIAGRAM AND MAIN ELEMENTS
The TLE Series 225 - 500 system can be divided into the following main elements:
Control System
TLE Series 225 - 500 is designed with microprocessor-controlled signal processing circuits.
The interface between the operator and the unit is provided by the monitoring system on the front
panel.
This monitoring system consists of an active mimic diagram, a keyboard and a backlit display.
Rectifier
The Active IGBT Rectifier converts the 3-phase utility voltage into a controlled and regulated DC-voltage,
supplying the inverter and to charge the battery through the battery-charger.
Thanks to modulation strategy applied to IGBT Bridge, the rectifier provides clean input power in terms
of low THDi and unity power factor.
Inverter
The Inverter converts the DC voltage into a three-phase AC-voltage with constant amplitude and
frequency, which is completely independent and isolated from the AC-input voltage.
Automatic Bypass
The Automatic Bypass consists of a static semiconductor-switch (SSM: Static Switch Module), used to
provide an uninterrupted transfer of the Load from Inverter to Utility.
Back-feed Protection
All TLE Series 225 - 500 UPS's are equipped with an automatic system for the protection against voltage
back feeding towards Utility, through the Bypass (UL 1778 and CSA C22.2 no. 107.3).
This protection works automatically by opening contactor K6 (in series with the thyristors of the static
switch) and eventually K7, and acts in case of internal defects of the system, or due to wrong
manipulations on the Manual Bypass Q2.
Manual Bypass
The Manual Bypass consists of a pair of manual switches (Q1 and Q2), which removes the UPS from the
Load for maintenance, while still supplying the Load with power directly from the Utility.
Battery
The Battery supplies the DC power to the Inverter when the Utility is out of acceptable tolerances.

GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
When the Utility is no longer within acceptable tolerances,
the Battery will provide the DC power to the Inverter.
The Inverter will maintain continuous AC power to the
Load until the Battery Voltage reaches the lower limit of
the Inverter operation capability.
During the discharge, the LCD screen shows the estimated
time the Battery can support the critical Load.
Prior to complete Battery discharge, the "stop operation"
alarm (shut-down imminent) warns the operator that the
Battery is almost discharged and the UPS is about to shut
down.
Fig. 4.2.3-1 Block diagram Utility Failure operation
In case of RPA Parallel System
With a Parallel System for power capacity (see Section 4.3)
With the Bypass Utility power available, a “Battery low” warning on any unit will cause the Load
to be transferred to Utility (after a selectable time delay).
With Bypass Utility power not available, a “Battery low” warning on any unit will start the “stop
operation” timer (adjustable).
The Load will shut down at the end of the “stop operation” time period.
With a Parallel System for redundancy (see Section 4.3)
When a Battery low warning occurs on a unit not necessary to support the present Load, this unit
will shut down after a timeout period (selectable).
The Load is shared between the other units.
As the warning occurs on one unit necessary to support the present Load, the system starts the
"stop operation" timeout (selectable).
The Load will shut down at the end of the “stop operation” time period.
As soon as the AC input power recovers, the Rectifier will
start automatically, supplying DC power to the Inverter
and recharging the Battery.
If the Inverter was previously shut down due to low
Battery, the Load will be initially powered by Utility
through the Automatic Bypass.
When the Battery is sufficiently recharged to ensure a
minimum time of operation with the present Load, the
Inverter will start automatically and the Load will be
transferred back to the Inverter.
Fig. 4.2.4-1 Block diagram Utility recovery operation
In case of RPA Parallel System
When the AC input power recovers, the Rectifiers will start-up sequentially, according to their
number in the Parallel System. This minimizes the initial inrush current.
The Inverters will start-up automatically, but only when the Battery has been sufficiently recharged
for a minimum runtime with the present Load.
When enough Inverters to supply the Load have been restarted, the Load will be transferred from
the Automatic Bypass back to the Inverter output.
4.2.3 Utility Failure Operation
4.2.4 Utility Recovery Operation

GE_UPS_USM_TLE_SUL_M22_M50_1US_V010.docx
User Manual TLE Series 225 - 500 UL S1
NOTE !
It is strongly recommended that no transformers, automatic circuit breakers or
fuses should be installed between the units output and the Load common bus bars.
However, it is recommended that a disconnection or isolation switch is installed in
order to totally isolate a unit if needed.
4.3.2 Features of RPA Parallel System
The TLE Series 225 - 500 Parallel System is designed to provide a complete Redundant Parallel
Architecture, and is free from common equipment.
Not only the Inverters but also the Bypass functions are redundant.
When one UPS needs maintenance or service, the Load is powered by the other units.
The redundant communication bus to which all units are connected keeps each unit informed about the
status of all the other units.
The control panel located on each unit allows controlling and monitoring the status of this unit.
4.3.3 System control
A high-speed redundant, serial communication bus, guarantees the exchange of data and thus the
communication between the CPU's of each unit.
Each module controls is own function and operational status and communicates with all other modules,
in order to act or react if necessary, adapting to the new conditions.
4.3.4 Synchronization
All units are identical, but one unit is arbitrarily selected as the reference and all the other units
synchronize to this unit, which in turn synchronizes to the Utility Bypass voltage, as long as the latter is
within tolerances.
In case of reference failure, another unit in the Parallel System is automatically chosen to take over the
reference role.
The Bypass Input for all the units of the Parallel System must be supplied from the same AC source (no
phase shift allowed between them).
4.3.5 Load sharing
On each unit of the Parallel System, Inverter Output Voltage and Current are measured and applied to a
Load sharing bus.
An eventual difference between the units is therefore automatically equalized.