GE Industrial Solutions Time Delay Module User Manual

Introduction Time Delay Module:
The de-energizing operation of the undervoltage release can be delayed. This optional, externally mounted, module has an adjustable time delay of one to three seconds. The device can be implemented to prevent un-desired Breaker ‘tripping’ due to momentary voltage outages (50% of rated Voltage) and is connected in series with the under voltage release. The delay is in addition to the Under Voltage Release delay of 50 msec. The breaker must have a UVR installed for the External Time Delay Module to work.
Table 1. Catalog Numbers and Ratings
Catalog No DC Voltage AC Voltage
GTDM048D GTDM048A GTDM060D GTDM120A GTDM120D GTDM208A GTDM240A GTDM240D GTDM250D GTDM277A
48VDC
48VAC
60VDC
120-130VAC
110-130VDC
208VAC 220-240VAC
220-240VDC
250VDC
250-277VAC
DEH-41406 Installation Instructions
EntelliGuard ® G Circuit Breaker Accessories
Time Delay Module
WARNING: Before installing any accessories, turn the breaker OFF, disconnect it from all voltage sources, and discharge the closing spings.
AVERTISSEMENT: Avant d’installer tout accessoire, mettre le disjoncteur en position OFF, le déconnecter de toute tension d’alimentation , et décharger les resorts d’armement
Refer to DEH-41410 for the Under Voltage Release in the breaker
Use the following procedure to install the Time Delay Module (TDM) accessory into the circuit breaker.
1. Verify that the rating on the Time Delay Module (TDM) identification plate matches the voltage rating required for the application, as listed in Table 1.
2. The time delay module has to be mounted external to the breaker.
3. Switch off the breaker & equipment and ensure the panel is isolated
4. TDM module can be mounted in two ways either using two M4 screws on the panel or to a din rail.
5. For assembling using the screw, drill and tap two M4 holes at a distance as shown in the Fig. 1.
1
(3.13)
Fig 1: Mounting holes location dimensions are in mm (Inches)
(2.74)
6. Assemble the TDM module with two M4 screws as shown in the fig 2.
These instructions do not purport to cover all details or variations in equipment nor, to provide contingency to be met in connection with installation, operation, or maintenance. Should further information be desired, or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to GE.
GE
41 Woodford Ave, Plainville, CT 06062 www.geelectrical.com
© 2009 General Electric Company
Figure 2. TDM mounting
7. Alternatively TDM can be mounted on a din rail as shown in the fig 3.
Figure 3. Din rail mounting
-
2
Loading...