GE Industrial Solutions SVCAA User Manual

GE Energy
Industrial Solutions
GEH-6254 Installation Instructions
Voltage Conditioner Assembly
For Spectra® RMS Molded-Case Circuit Breakers
TM
with microEntelliGuard
, MicroVersaTrip® PM or MicroVersaTrip® Plus Trip Units
For Catalog Number SVCAA
Circuit Breaker Accessory
Overview
The General Electric Voltage Conditioner Assembly is used to provide voltage-sensing signals to Spectra microEntelliGuard Units via the Distribution Cable System.
The assembly has the maximum capacity to provide voltage signals to a Distribution Cable System consisting of 20 Spectra Breakers with microEntelliGuard PM/Plus Trip Units with a maximum system cable length of 40 feet.
®
RMS Molded-Case Circuit Breakers with
TM
or MicroVersaTrip® PM/Plus Trip
®
RMS Molded-Case Circuit
TM
or MicroVersaTrip®
The Voltage Conditioner Assembly requires a power supply source voltage of +24Vdc to operate properly. The Power Supply Assembly (catalog number SPSAA) or Power Supply Plate (catalog number SPSAI20, SPSA208, SPSA240, SPSA480 or SPSA600) can provide this required input. The unit also requires 120Vac @60 Hz voltage inputs from the secondary of three 1-VA high accuracy potential transformers (not included). The primary side of each potential transformer must be fused with 2-amp class CC fuses (not included). The Voltage Conditioner Assembly is designed to operate in temperatures between 0°C and 70°C.
GEH-6254 Installation Instructions
Figure 1 shows how the Voltage Conditioner Assembly is used in a typical MicroVersaTrip® PM system.
®
Figure 2 shows how the Voltage Conditioner Assembly is used in a typical MicroVersaTrip
TM
microEntelliGuard diagram shown in Figure 2 applies to microEntelliGuard
Trip Unit can be used with either configuration, i.e. Figure 1 or Figure 2. The connection
TM
Trip Units with Basic Metering.
Plus system. The
Figure 1. Typical MicroVersaTrip® PM Trip Unit System detailing the Voltage Conditioner Assembly.
GEH-6254 Installation Instructions
Figure 2. Typical MicroVersaTrip® Plus Trip Unit System detailing the Voltage Conditioner Assembly.
GEH-6254 Installation Instructions
A communications connection is provided for applications where data is transmitted to an external intelligent device (See Table 1). The distribution cable system is used to interconnect the voltage signal on the
®
Voltage Conditioner Assembly and the Spectra
RMS
Molded-Case Circuit Breakers.
Table 1. Associated Software and Protocol for the different Spectra
®
Series Breakers.
Trip Unit Type Protocol Software
MicroVersaTrip microEntelliGuard
®
PM Commnet GE POWER LEADER
TM
Modbus EnerVista Viewpoint
TM
An additional voltage output connection is available for applications where a voltage signal is needed on an Air Circuit Breaker or Insulated Case Circuit Breaker with an
®
EntelliGuard™ TU or a MicroVersaTrip not connect this voltage signal to a Spectra
PM Trip Unit (Do
®
Trip Unit. The voltage signal structure is different between the MCCB and ACB/ICCB Trip Unit platforms).
NOTE: THE VOLTAGE CONDITIONER ASSEMBLY IS SIZED FOR A MAXIMUM OF 20 BREAKERS. Use of the Voltage Conditioner Assembly to provide voltage sensing signals and/or +24Vdc control power to a main Air Circuit Breaker or a main Insulated Case Breaker with a
®
MicroVersaTrip reduces the total quantity of 20 Spectra Case Circuit Breakers with microEntelliGuard MicroVersaTrip
PM/Plus or EntelliGuardTM TU Trip Unit
®
RMS Molded-
TM
®
PM/Plus Trip Units by one. The overall
or
maximum cabling length of the system remains 40 feet.
The Voltage Conditioner Assembly contains five connection points. The following list contains a description and type of connection points.
• “To Distribution Cable” – 12-pin plug connector that mates with the 12-pin
receptacle of a Distribution Cable Harness (catalog number SDCHA11, SDCHA30 or SDCHA60).
• “To Power Supply” – 12-pin plug connector that mates with the 12-
pin receptacle of the Distribution Cable Harness (catalog number SDCHA11, SDCHA30 or SDCHA60). The other end of the harness MUST mate to either
a Power Supply Assembly (catalog number SPSAA) or a Power Supply Plate (catalog number SPSA120, SPSA208, SPSA240, SPSA480 OR SPSA600). Failure to do so will result in the absence of a voltage-sensing signal and inaccuracies in voltage dependent
®
informtaion / metering at Spectra Case Circuit Breakers with MicroVersaTrip Units and/or MicroVersaTrip
®
RMS Molded-
®
PM Trip
PM Programmers in Air
Circuit Breakers or Insulated Case Circuit Breakers.
• “120Vac Input From P/T’s” – Six-screw terminal block for connection of the
potential transformers.
• “Communications” – Two-screw terminal block for connection to
communications network.
• “Output to ACB/ICCB” – Three-screw terminal block for optional voltage-
®
sensing signal output to MicroVersaTrip
PM or EntelliGuard™ TU Trip Units in Air Circuit Breakers and/or Insulated Case Circuit Breakers.
By plugging the Voltage Conditioner Plate into the Distribution Cable System you create system wide signals that are available to all breakers connected to the system; a list of those functions appears in Table 2.
Table 2. Signals available on the Distribution Cable System by connection of the Voltage Conditioner Assembly.
Spectra® RMS Breaker with microEntelliGuard Trip Unit
control power (+24vdc)
control power (common)
system communication (comm. +)
system communication (comm. -)
voltage 1 (defined as potential between Af & N or between Af & Cf)
voltage 2 (defined as potential between Bf & N or between Cf & Bf)
voltage 3 (defined as potential between Cf & N or between Bf & Af)
Spectra Breaker with
TM
MicroVersaTrip Trip Unit
control power (+24vdc)
control power (common)
system communication (comm. +)
system communication (comm. -)
voltage 1 (defined as potential between Af & N or between Af & Cf)
voltage 2 (defined as potential between Bf & N or between Cf & Bf)
voltage 3 (defined as potential between Cf & N or between Bf & Af)
®
RMS
®
PM
®
Spectra Breaker with MicroVersaTrip Plus Trip Unit
control power (+24vdc)
control power (common)
RMS
®
GEH-6254 Installation Instructions
Dimensions and Wiring Diagrams A Voltage Conditioner Assembly dimensioned drawing is provided in Figure 3 to assist in mounting the accessory. The maximum unit weight is one and a half pounds.
Figure 3. Dimensioned drawing of the Voltage Conditioner Assembly (dimensions shown in inches).
GEH-6254 Installation Instructions
Figure 4 contains a point-to-point wiring diagram for a Voltage Conditioner Assembly as it integrates into a typical microEntelliGuardTM or MicroVersaTrip® PM system.
Figure 4. Wiring connections to the Voltage Conditioner Assembly for a typical MicroVersaTrip® PM System.
GEH-6254 Installation Instructions
Connections
The screw terminals on the Voltage Conditioner Assembly are labeled by function for clarity. The terminal strip pocket will accommodate a spade lug or ring terminal with a tongue width up to 0.320 inches. The terminal screw size is 10-32. To make the Connection, attach an appropriate spade lug or ring terminal to the wire, then slip the fastener beneath the terminal screw and tighten.
The Voltage Conditioner Assembly also contains two 12-pin plug connectors. The connectors are keyed so they cannot be inserted incorrectly into a mating 12­pin receptacle connector. To connect to the Voltage Conditioner Assembly plug(s), align the receptacle interlock connector of a Distribution Cable Harness with the plug hook connector of the Voltage Conditioner Assembly. Insert the receptacle until the interlock and hook catch (see Figure 5).
To disconnect from the Voltage Conditioner Assembly, press down at the rear of the receptacle interlock until the interlock clears the plug hook and withdraw the receptacle interlock (see Figure 6).
PARTS AND OPTIONS
There are no user-serviceable components or parts within the Voltage Conditioner Assembly; however, in order for the unit to be properly protected, the fuses and fuse holders listed in Table 3 are recommended for use with the Voltage Conditioner Assembly (connect to the primary side of the three potential transformers). Table 4 contains a list of potential transformers that are recommended for use with the Voltage Conditioner Assembly (all units rated 120Vac on the secondary and are rated 1-VA @ 60Hz with 0.2% on magnitude accuracy). These potential transformers must always be protected. It is recommended that the primary side of the potential transformer be fused with the fuses previously described.
If it is preferred to purchase a voltage-sensing accessory that has factory-mounted AC line fuses and three 1-VA @ 60Hz accuracy potential transformers, Table 5 contains a listing of GE Voltage Conditioner Plates. These Voltage Conditioner Plates contain the Voltage Conditioner Assembly as an integral part of the plate and are factory-wired from the Voltage Conditioner Assembly to the three 1-VA potential transformers and to the fuses holders (one set of fuses is included).
Table 3. Recommended replacement fuses for use with the Power Supply Assembly.
Class CC Current limiting Fuse Fuse Holder
Gould-Shawmut ATMR 2 Gould-Shawmut 3012R & DFC3M
Figure 5. Slide view of receptacle-plug insertion into the Voltage Conditioner Assembly.
Figure 6. Side view of receptacle-plug removal from the Voltage Conditioner Assembly.
Table 4. Recommended potential transformers for use with the Voltage Conditioner Assembly.
Primary Rating Transfab Inc. Catalog Number
120Vac DL7027EE 208Vac DL7026FE 240Vac DL7029GE 277Vac DL7030LE 480Vac DL7025OE 600Vac DL7028QE
Table 5. Available Voltage Conditioner Plates.
Catalog Number Source Voltage Rating Comments
SVCA120Y 120Vac Wye connection f to N potential SVCA208Y 208Vac Wye connection f to f potential SVCA240D 240Vac Delta connection f to f potential SVCA277Y 277Vac Wye connection f to N potential SVCA480Y 480Vac Wye connection f to f potential SVCA480D 480Vac Delta connection f to f potential SVCA600D 600Vac Delta connection f to f potential
GEH-6254 Installation Instructions
Additional Information
Refer to these other user’s manuals for more details·:
®
GEH-5934 MicroVersaTrip
PM Trip Units in Spectra
Plus and MicroVersaTrip®
®
RMS Molded-
Case Circuit Breakers
®
GEH-700 Spectra
G Breaker w/
microEntelliGuard™ Trip Unit
®
GEH-701 Spectra
K Breaker w/
microEntelliGuard™ Trip Unit GEH-702 microEntelliGuard™ Trip Unit Users Manual DEH-41318 Universal Rating Plug GEH-6250 Voltage Module GEH-6251 Power Supply Plate GEH-6252 Voltage Conditioner Plate GEH-6253 Power Supply Assembly GEH-703 MET Battery Pack Adapter GEH-704 MET Advanced Distribution Cable
Junction Box
DEH-006 Distribution Cable Junction Box GEH-705 MET Distribution Cable Extension (20-pin) GEH-6256 Distribution Cable Extension (12-pin) GEH-6255 Distribution Cable Harness (12-pin) GEH-706 MET Distribution Cable Terminal Blocks
(11 point & 22 point) GEH-6257 Distribution Cable Terminal Block (11 point) GEH-6491 POWER LEADER™ Modbus Concentrator GEH-6502 POWER LEADER™ PMCS 5.0 Network
Architecture Guide GEH-707 MET Sealable Cover kits DEH-4568 GTU digital test kit (GTUTK20) GEH-5551 Shunt Trip and UVR instructions GEH-5593 Aux switch and bell alarm GEK-64467 TIM-1 Zone Selective Interlock Module
Spectra and MicroVersaTrip are registered trademarks and EntelliGuard and microEntelliGuard are trademarks of the General Electric Company.
These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that may be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE Company.
GE Energy
41 Woodford Avenue, Plainville, CT 06062 www.geelectrical.com © 2011 General Electric Company
imagination at work
GEH-6254 Rev. 4 (11/11 M45)
Loading...