, MicroVersaTrip® PM or MicroVersaTrip® Plus Trip Units
For Catalog Numbers SVCA120Y, SVCA208Y. SVCA240Y, SVCA277Y, SVCA480Y,
SVCA480D, SVCA600D
Circuit Breaker Accessory
Overview
The General Electric Voltage Conditioner Plate is used
to provide voltage-sensing signals to Spectra
Molded-Case Circuit Breakers with microEntelliGuard
or MicroVersaTrip
Cable System. The Voltage Conditioner Plate includes
the Voltage Conditioner Assembly (catalog number
SVCAA) as an integral component and also includes fuse
protection for the AC source input terminals and three
1-VA @ 60 Hz high accuracy potential transformers. The
plate has the maximum capacity to provide voltagesensing signals to a Distribution Cable System consisting
of 20 Spectra
microEntelliGuard
with a maximum system cable length of 40 feet.
®
PM/Plus Trip Units via the Distribution
®
RMS Molded-Case Circuit Breakers with
TM
or MicroVersaTrip® PM/Plus Trip Units
®
RMS
TM
The Voltage Conditioner Plate requires a power supply
source of +24Vdc to operate properly. The Power
Supply Assembly (catalog number SPSAA) or Power
Supply Plate (catalog number SPSA120, SPSA208,
SPSA240, SPSA480 or SPSA600) can provide this
required input. The unit also requires direct AC voltage
inputs from the AC source (ratings of 120Vac, 208Vac,
240Vac, 277Vac, 480Vac or 600Vac are available). The
Voltage Conditioner Plate is designed to operate in
temperatures between 0°C and 70°C.
GEH-6252 Installation Instructions
Figure 1 shows how the Voltage Conditioner Plate is used in a typical MicroVersaTrip® PM system. Figure 2 shows
how the Voltage Conditioner Plate is used in a typical MicroVersaTrip
®
Plus system. The microEntelliGuard
TM
Trip
Unit can be used with either configuration, i.e. Figure 1 or Figure 2. The connection diagram shown in Figure 2
TM
applies to microEntelliGuard
Trip Units with Basic Metering.
Figure 1. Typical MicroVersaTrip® PM Trip Unit System detailing the Voltage Conditioner Plate.
GEH-6252 Installation Instructions
Figure 2. Typical MicroVersaTrip® Plus Trip Unit System detailing the Voltage Conditioner Plate.
GEH-6252 Installation Instructions
The Voltage Conditioner Plate is available in seven
ratings. Table 1 contains a listing of all GE Voltage
Conditioner Plates.
Table 1. GE Voltage Conditioner Plates
Catalog NumberSource Voltage RatingComments
SVCA120Y120Vac Wye connectionf to N potential
SVCA208Y208Vac Wye connectionf to f potential
SVCA240D240Vac Delta connectionf to f potential
SVCA277Y277Vac Wye connectionf to N potential
SVCA480Y480Vac Wye connectionf to f potential
SVCA480D480Vac Delta connectionf to f potential
SVCA600D600Vac Delta connectionf to f potential
A communications connection is provided for
applications where data is transmitted to an external
intelligent device (See Table 2).
Table 2. Associated Software and Protocol for the different
Spectra
®
Series Breakers.
Trip Unit TypeProtocolSoftware
MicroVersaTrip
microEntelliGuard
®
PMCommnetGE POWER LEADER™
TM
ModbusEnerVista Viewpoint
An additional voltage output connection is available for
applications where a voltage signal is needed on an Air
Circuit Breaker or Insulated Case Circuit Breaker with an
®
EntelliGuard™ TU or a MicroVersaTrip
not connect this voltage signal to a Spectra
PM Trip Unit (Do
®
Trip Unit.
The voltage signal structure is different between the
MCCB and ACB/ICCB Trip Unit platforms).
NOTE: THE VOLTAGE
CONDITIONER
ASSEMBLY IS SIZED
FOR A MAXIMUM OF 20 BREAKERS. Use of the Voltage
Conditioner Plate to provide voltage sensing signals
and/or +24Vdc control power to a main Air Circuit
Breaker or a main Insulated Case Breaker with a
®
MicroVersaTrip
reduces the total quantity of 20 Spectra
Case Circuit Breakers with microEntelliGuard
MicroVersaTrip
PM/Plus or EntelliGuardTM TU Trip Unit
®
RMS Molded-
TM
®
PM/Plus Trip Units by one. The overall
or
maximum cabling length of the system remains 40 feet.
The Voltage Conditioner Plate contains five connection
points. The following list contains a description and
type of connection points.
• “To Distribution Cable”
– 12-pin plug connector that mates with the 12-pin
receptacle of a Distribution Cable Harness (catalog
number SDCHA11, SDCHA30 or SDCHA60).
• “To Power Supply”
– 12-pin plug connector that mates with the 12-
pin receptacle of the Distribution Cable Harness
(catalog number SDCHA11, SDCHA30 or SDCHA60).
The other end of the harness MUST mate to either
a Power Supply Assembly (catalog number SPSAA)
or a Power Supply Plate (catalog number SPSA120,
SPSA208, SPSA240, SPSA480 OR SPSA600). Failure to
do so will result in the absence of a voltage-sensing
signal and inaccuracies in voltage dependent
®
informtaion / metering at Spectra
Case Circuit Breakers with MicroVersaTrip
Units and/or MicroVersaTrip
®
RMS Molded-
®
PM Trip
PM Programmers in Air
Circuit Breakers or Insulated Case Circuit Breakers.
• “Input Voltage”
– Three-screw terminals on the fuse block for
connection of the primaray AC source. For Power
Supply Plates (Catalog Numbers SPSA120 and
SPSA277), an additional AC neutral connection must
be made at one of the potential transformers.
• “Communications”
– Two-screw terminal block for connection to
communications network.
• “Output to ACB/ICCB”
– Three-screw terminal block for optional voltage-
®
sensing signal output to MicroVersaTrip
PM or
EntelliGuard™ TU Trip Units in Air Circuit Breakers
and/or Insulated Case Circuit Breakers.
The distribution cable system is used to interconnect
the voltage signal on the Voltage Conditioner Plate and
®
the Spectra
RMS Molded-Case Circuit Breakers.
GEH-6252 Installation Instructions
By plugging the Voltage Conditioner Plate into the
Distribution Cable System you create system wide
signals that are available to all breakers connected to
the system; a list of those functions appears in Table 3.
Table 3. Signals available on the Distribution Cable System by
connection of the Voltage Conditioner Plate.
®
Spectra® RMS ™ Breaker
with microEntelliGuard™ or
MicroVersaTrip
System communications (Comm. +)
System communications (Comm. - )
Voltage 1 (defined as potential
between A & N or between A & C)
Voltage 2 (defined as potential
between B & N or between C & B)
Voltage 3 (defined as potential
between C & N or between B & A)
®
PM Trip Unit
Spectra
MicroVersaTrip
microEntelliGuard™ with
Basic Metering Trip Unit
RMS Breaker with
®
Plus or
no signals available
Dimensions, Weights and Wiring Diagrams
A Voltage Conditioner Plate dimensioned drawing is
provided in Figure 3 to assist in mounting the accessory.
The maximum unit weight is 13 pounds.
Figure 3. Dimensioned drawing of the Voltage Conditioner Plate
(dimensions shown in inches).
GEH-6252 Installation Instructions
Figure 4 contains a point-to-point wiring diagram for a Voltage Conditioner Plate as it integrates into a typical
TM
microEntelliGuard
or MicroVersaTrip® PM system.
Figure 4. Wiring Connections to the Voltage Conditioner Plate for a typical microEntelliGuardTM or MicroVersaTrip® PM System.
GEH-6252 Installation Instructions
Connections
The screw terminals on the Voltage Conditioner Plate
are labeled by function for clarity. The terminal strip
pockets on the AC INPUT fuse block will accommodate
a spade lug or ring terminal with a tongue width up
to 0.45 inches. The terminal screw size is 10-32. The
terminal strip pockets on the Voltage Conditioner
Assembly will accommodate a spade lug or ring terminal
with a tongue width up to 0.320 inches. The terminal
screw size is 10-32. To make the connection, attach an
appropriate spade lug or ring terminal to the wire, then
slip the fastener beneath the terminal screw and tighten.
The Voltage Conditioner Plate also contains two 12pin plug connectors. The connectors are keyed so
they cannot be inserted incorrectly into a mating 12pin receptacle connector. To connect to the Voltage
Conditioner Plate plug(s), align the receptacle interlock
connector of a Distribution Cable Harness with the plug
hook connector of the Voltage Conditioner Plate. Insert
the receptacle until the interlock and hook catch (see
Figure 5). To disconnect from the Voltage Conditioner
Plate, press down at the rear of the receptacle interlock
until the interlock clears the plug hook, and withdraw
the receptacle interlock (see Figure 6).
PARTS AND OPTIONS
The only user-serviceable components or parts on the
Voltage Conditioner Plate are the fuses in the AC INPUT
fuse block. The fuses listed in Table 4 are recommended
as replacements for use with the Voltage Conditioner
Plate. Failure to use the proper type of fuses can result
in damage to the accessory. Three fuses per Voltage
Conditioner Plate are required.
If you prefer to purchase a voltage-sensing source
without the factory mounted AC line fuses and high
accuracy potential transformers, a Voltage Conditioner
Assembly is available. This assembly still requires AC
line fuse protection and the high accuracy potential
transformers to work properly. Table 5 lists the details
on the GE Voltage Conditioner Assembly.
Table 4. Recommended Replacement Fuses for use with the
Voltage Conditioner Plate.
Ampere Rating
2 ampGould-ShawmutATMR 2
Catalog
Manufacturer
NumberComments
Class CC current
limiting fuse
Figure 5. Slide view of receptacle-plug insertion into
the Voltage Conditioner Plate.
Table 5. Available GE Voltage Conditioner Assembly.
Catalog
Number
SVCAA
Description
Voltage
Conditioner
Assembly
AC Line Fuses
Requirement
2 amp class CC 120Vac @ 60 Hz
Voltage Rating of
Assembly via High
Accuracy I-VA P/T’s
Figure 6. Side view of receptacle-plug removal from
the Voltage Conditioner Plate.
GEH-6252 Installation Instructions
Additional Information
Refer to these other user’s manuals for more details·:
®
GEH-5934 MicroVersaTrip
PM Trip Units in Spectra
Plus and MicroVersaTrip®
®
RMS Molded-
Case Circuit Breakers
®
GEH-700 Spectra
G Breaker w/
microEntelliGuard™ Trip Unit
®
GEH-701 Spectra
K Breaker w/
microEntelliGuard™ Trip Unit
GEH-702 microEntelliGuard™ Trip Unit Users Manual
DEH-41318 Universal Rating Plug
GEH-6250 Voltage Module
GEH-6251 Power Supply Plate
GEH-6253 Power Supply Assembly
GEH-6254 Voltage Conditioner Assembly
GEH-703 MET Battery Pack Adapter
GEH-704 MET Advanced Distribution Cable
Junction Box
DEH-006 Distribution Cable Junction Box
GEH-705 MET Distribution Cable Extension (20-pin)
GEH-6256 Distribution Cable Extension (12-pin)
GEH-6255 Distribution Cable Harness (12-pin)
GEH-706 MET Distribution Cable Terminal Blocks
(11 point & 22 point)
GEH-6257 Distribution Cable Terminal Block (11 point)
GEH-6491 POWER LEADER™ Modbus Concentrator
GEH-6502 POWER LEADER™ PMCS 5.0 Network
Architecture Guide
GEH-707 MET Sealable Cover kits
DEH-4568 GTU digital test kit (GTUTK20)
GEH-5551 Shunt Trip and UVR instructions
GEH-5593 Aux switch and bell alarm
GEK-64467 TIM-1 Zone Selective Interlock Module
Spectra and MicroVersaTrip are registered trademarks and EntelliGuard and
microEntelliGuard are trademarks of the General Electric Company.
These instructions do not cover all details or variations in equipment nor do they
provide for every possible contingency that may be met in connection with installation,
operation, or maintenance. Should further information be desired or should particular
problems arise that are not covered sufficiently for the purchaser’s purposes, the
matter should be referred to the GE Company.