GEH-6251 Installation Instructions
Power Supply Plate
For Spectra® RMS Molded-Case Circuit Breakers with microEntelliGuardTM,
®
MicroVersaTrip
PM or MicroVersaTrip® Plus Trip Units
For Catalog Numbers SPSA120, SPSA208, SPSA240, SPSA480, SPSA600
Circuit Breaker Accessory
Overview
The General Electric Power Supply Plate is used to provide +24Vdc Control Power to Spectra Case Circuit Breakers with microEntelliGuard MicroVersaTrip Cable System. The Power Supply Plate also provides power to the Voltage Conditioner Assembly or Voltage Conditioner Plate (Spectra Breakers with microEntelliGuard PM Trip Units require connection to a Voltage Conditioner Assembly or Voltage Conditioner Plate to function properly). The Power Supply Plate includes the Power Supply Assembly (catalog number SPSAA) as an
®
PM/Plus Trip Units via the Distribution
®
RMS Molded-Case Circuit
TM
or MicroVersaTrip®
®
RMS Molded-
TM
or
integral component and also includes fuse protection for the AC source input terminals.
The Power Supply Plate is rated 24 watts (+24Vdc @
1.0 Amp) and has the maximum capacity to power a Distribution Cable System consisting of either a Voltage Conditioner Assembly or a Voltage Conditioner Plate AND 20 Spectra with microEntelliGuard Trip Units with a maximum system cable length of 40 feet. The Power Supply Plate is designed to operate in temperatures between O°C and 70°C.
®
RMS Molded-Case Circuit Breakers
TM
or MicroVersaTrip® PM / Plus
GEH-6251 Installation Instructions
Figure 1 shows how the Power Supply Plate is used in a typical MicroVersaTrip® PM system. Figure 2 shows how the Power Supply Plate is used in a typical MicroVersaTrip
®
Plus system. The microEntelliGuard
TM
Trip Unit can
be used with either configuration, i.e. Figure 1 or Figure 2. The connection diagram shown in Figure 2 applies to
TM
microEntelliGuard
Trip Units with Basic Metering.
Figure 1. Typical microEntelliGuard™ or MicroVersaTrip® PM Trip Unit System detailing the Power Supply Plate.
GEH-6251 Installation Instructions
Figure 2. Typical microEntelliGuardTM or MicroVersaTrip® Plus Trip Unit System detailing the Power Supply Plate.
GEH-6251 Installation Instructions
The Power Supply Plate is available in five ratings. Table 1 contains a listing of all GE Power Supply Plates. All units are rated 60 Hz. Supplemental 24Vdc input terminals are provided for systems that have access to an external +24Vdc power supply. If this supplemental input is connected, the assembly will continue to pass the control power to breakers and accessories connected to the Distribution Cable System if the primary AC power is lost or drops below the minimum requirement. This backup input must meet ANSI C37.90.1 for oscillatory and fast transient surges (the Power Supply Plate provides this protection for the primary AC input). Additional 24Vdc output connections are supplied for applications where +24Vdc control power is required independent of the Distribution Cable System (i.e., feeding an Air Circuit Breaker or
®
Insulated Case Breaker with microVersaTrip
TM
EntelliGuard
TU Trip Unit).
PM/Plus or
NOTE: THE POWER SUPPLY PLATE IS SIZED FOR A MAXIMUM OF 20 BREAKERS. Use of the Power Supply Plate to provide voltage sensing signals and/or +24Vdc control power to a main Air Circuit Breaker or a main
®
Insulated Case Breaker with a MicroVersaTrip
TM
or EntelliGuard of 20 Spectra microEntelliGuard
TU Trip Unit reduces the total quantity
®
RMS Molded-Case Circuit Breakers with
TM
or MicroVersaTrip® PM/Plus Trip
PM/Plus
Units by one. The overall maximum cabling length of the system remains 40 feet.
Table 1. Ge Power Supply Plates
Voltage Rating
I20VAC SPSA12O
208VAC SPSA208 2amp 2
240VAC SPSA240 2amp 2
480VAC SPSA480 2amp 2
600VAC SPSA600 2amp 2
1
Fuse protection only in one leg – this is a line-to-neutral connection. All other connections are line to line.
Catalog Number
Class CC Line Fuses
1
2amp 1
# Comments
SPSAA on mounting plate with fuse holder
SPSAA on mounting plate with fuse holder
SPSAA on mounting plate with fuse holder
SPSAA on mounting plate with fuse holder and 480 Vac transformer
SPSAA on mounting plate with fuse holder and 480 Vac transformer
The Power Supply Plate contains six connection points. Refer to Figures 4 and 5 for connection details and location information. The following is a detailed list of the Power Supply Plate connection points:
• “To Distribution Cable” – 12-pin plug connector that mates with the 12-pin
receptacle of a Distribution Cable Harness (catalog number SDCHA11 , SDCHA30 or SDCHA60).
• “To Voltage Conditioner” – 12-pin plug connector that mates with the 12-
pin receptacle of a Distribution Cable Harness (catalog number SDCHA11, SDCHA30 or SDCHA60).
®
For Spectra with microEntelliGuard
RMS Molded-Case Circuit Breakers
TM
, MicroVersaTrip® PM Trip Units, the other end of the harness MUST connect to either a Voltage Conditioner Assembly (catalog number SVCAA) or a Voltage Conditioner Plate (catalog number SVCA120Y, SVCA208Y, SVCA240D, SVCA277Y, SVCA480Y, SVCA480D or SVCA600D) for the breaker to function properly.
• “Input Voltage” – Two-screw terminals on the fuse block for
connection of the primary AC source.
• “Input” – Three-screw terminal block on the Power Supply
Assembly. Use one-terminal screw for connection of the ground (the other two-terminal screws are factory wired to the load side of the fuse block).
• “Output to 24Vdc” – Two-screw terminal block for optional control power
output (in lieu of using the Distribution Cable System).
• “Supplemental Input 24Vdc” – Two-screw terminal block for connection of an
external +24Vdc power supply.
By plugging the Power Supply Plate into the Distribution Cable System, you create system wide signals that are available to all breakers connected to the system; a list of those functions appears in Table 3.
Table 3. Signals available on the Distribution Cable System by connection of the Power Supply Plate
Spectra® RMS Breaker with MicroVersaTrip Trip Unit
control power (+24vdc) control power (common)
®
PM
®
Spectra Breaker with MicroVersaTrip Plus Trip Unit
control power (+24vdc) control power (common)
RMS
Spectra Breaker with
®
microEntelliGuard Trip Unit
control power (+24vdc) control power (common)
®
RMS
TM