GE Industrial Solutions Spectra Series Power Panelboards Ground Fault Neutral, 1200 A Maximum User Manual

GEH5683 Installation Instructions R02
g
Spectra Series™ Power Panelboards
Ground Fault Neutral, 1200 A Maximum
WARNING: Danger of electrical shock or injur y.
OFF power ahead of the panelboard or
Turn switchboard before working inside the equipment or removing any component not remove circuit protective devices or any other component until the power is turned OFF.
. Do
Installation
1. Remove the c onnection bar. Loosen the four nuts on the studs (two in each strap) located at the current transformer and at the load end of the neutral, as shown in Figure 1. Slide out the connection bar assembly.
Connection
Bar
Load End
of Neutral
2. Mount the neutral. Place the neutral in the desired position in the en d of the b ox st amp ed on the studs in the back of the box. as shown in Figure
2. Place a flat washer, lock washer, and nut on the studs, as shown in Figure 3. Leave the nuts hand tight.
Align the elongated holes in the neutral with the
holes in the b ox and secure with eight #1 0-32 x thread-forming screws, as shown in Figure 4. Tighten the screws and nuts to 27–32 in.-lb.
LINE. Mount it
7
/8"
Stud (one
each side)
Nuts
Figure 1. Removing the connection bar assembly.
Current
Transformer
Figure 2. Neutral mounting position.
#10 Flat Washer,
Lock Washer,
Figure 3. Mounting the neutral in the box.
Hex Nut
3. Mount the bond stra p. If a bonding s trap is required for service entrance use, loosen the bolt at the line end of the neutral transformer and slide the bond strap under the head of the bolt, as shown in Figure 5. (For NEMA 3R/12 enclosures go to step 4.) If the box is painted, scratch through the paint in the area where the bond str ap is to con tact the box. Secure the bond
3
strap to the box w ith on e #10-32 x
/8" thread-forming screw. Tighten the screws to 27–32 in.-lb. Retighten the nut at the other end of the bond strap at the neutral transformer to 200–250 in.-lb.
#10-32 x
3
/8" Screw
Bond Strap
Figure 4. Securing the neutral in position.
Neutral
Base
Elongated
Hole
#10-32 x
7
/8" Screw
Nut Washer (bolt
head on underside)
Slide Bond Strap
(with slot) under
Head of Bolt
Figure 5. Attaching a bond strap.
Loading...
+ 2 hidden pages