Installation
WARNING: Danger of electrical shock or injury.
OFF
Turn
switchboard before workin
e
ment or removing any component.
Equipment is to be installed and maintained b
properly trained and qualified personnel only.
See Figures 1 and 2 for illustrations of AEG10 and AEG21
uninsulated equipment grounds and Figures 3 and 4 for
illustrations of AEG21S and AEG31S insulated equipment
grounds.
1. Attach terminals to the straps as shown in the
appropriate figure. Find the holes for mounting the
equipment ground at the opposite end of the box
from where it is stamped
scratch through the paint in the area where the strap
is to contact the box. Mount the equipment ground
with the two 10-32 thread-forming screws provided
and tighten to 25-30 in-lb.
2. Remove the paper backing from the identification
label provided. Place the label below the equipment
ground, approximately in the position shown.
ower ahead of the panelboard or
inside the
Line. If the box is painted,
GEH5586 Installation Instructions R02
Spectra Series™ Power Panelboards
Equipment Grounds, Types AEG 10, 21, 21S, 31S
Mounting
Positions
Identification
Labels
Figure 2. Equipment ground catalog number AEG21.
Mounting
Positions
Identification
Labels
Figure 1. Equipment ground catalog number AEG10.
Mounting
Positions
Identification
Labels
Figure 3. Equipment ground catalog number AEG21S.
POSITIONS
DE
Vignettes
d’identificaatio
Figure 4. Equipment ground catalog number AEG31S.
These instructions do not cover all details or variations in equipment nor do they provide for every possible
contin
information be desired or should
purposes, the matter should be referred to the GE Company.
ency that may be met in connection with installation, operation, or maintenance. Should further
articular problems arise that are not covered sufficiently for the purchaser’s
GE Industrial Systems
General Electric Company
41 Woodford Ave., Plainville, CT 06062
GEH5586 R02 0401 © 2001 General Electric Company